Automatic Snow/Ice Melting System ControllerMODEL EUR™–5A
Installation and Operation Manual
21776 Rev C 03/14(800) 234-4239http://www.networketi.com2 of 12 Environmental Technology, Inc.
Model EUR–5A Snow & Ice Melting Control
SafetyThe electric panel location creates exposure to lethal voltages. Make all electrical connections in
compliance with the National Electric Code (NEC)/NFPA 70 in the United States of America, the Canadian Electrical Code in Canada and local electrical codes and laws.
The EUR–5A, its sensors and remote control accessory devices are NEC Class 2 devices.
If you have questions concerning the installation or application, please contact Customer Service.
Additional InformationMore information is regularly made available through the Environmental Technology, Inc. (ETI) website,
www.networketi.com. Please visit us online for data sheets, manuals, white papers, technical articles and more. The most current version of this and every other manual for our products can be found in Portable Document Format (PDF) files to view online or to print. This is to assist you in installing and using our products to the best effect possible. If you have any comments about this or any other product from Envi-ronmental Technology, Inc., please contact us.
Contacting Environmental Technology, Inc.For assistance, contact Customer Service. Office hours are from 8:00 AM until 5:00 PM ET.Voice (800) 234-4239 (USA and Canada) or (574) 233-1202 (elsewhere)Fax (888) 234-4238 (USA and Canada) or (574) 233-2152 (elsewhere)E-mail [email protected] Mail Environmental Technology, Inc. 1850 North Sheridan Street South Bend, IN 46628
ReturnsContact Customer Service to obtain a Return Authorization before shipment to Environmental Technology,
Inc. Otherwise, the shipment may be refused.
21776 Rev C 03/14 (800) 234-4239 http://www.networketi.com 3 of 12Environmental Technology, Inc.
Model EUR–5A Snow & Ice Melting Control
General
IntroductionThe EUR–5A Snow and Ice Melting Control is the interface between environmental sensors, building
energy management computer (if present), operating personnel and heater control contactors. Figure 1 shows a typical snow melting system using the EUR–5A. Currently, compatible environmental sensors are available for pavement, aerial and gutter snow and ice melting applications. A special sensor measures ambient temperature.
The EUR–5A accommodates up to six environmental sensors. Using at least two environmental sensors, as shown in Figure 1, improves performance through superior coverage. A single environmental sensor can miss tracked or blowing and drifting snow. The first environmental sensor detecting snow or ice starts the heaters.
Figure 1. Typical EUR–5A installation
When these environmental sensors become clear of snow and ice, the heater hold-on interval begins. During hold-on, heater operation continues for a user-adjustable time interval. Since re-freezing can create hazardous conditions, hold-on serves the dual purposes of melting any accumulated snow and ice and drying the pavement.
The EUR–5A includes an adjustable high temperature limit thermostat. This feature is useful in systems using MI cable and other constant wattage heaters to prevent excessive energy use. When using self-limiting heaters, this feature can be defeated.
Typically, the EUR–5A is located in an electrical enclosure with heater contactors: this may not be convenient for operating personnel or accessible to laymen. Supervisory control is sometimes necessary due to the need for testing and/or unusual environmental conditions which can include blowing, drifting and tracked snow. The EUR–5A itself provides control and indicators for this purpose; accessing them, however, may require opening the electrical enclosure, perhaps exposing personnel to lethal voltages. This problem is avoided when employing the included RCU–3 Remote Control Unit. Another simple alternative is to mount a customer supplied pushbutton switch in the electric panel door for cycling the hold-on timer.
21776 Rev C 03/14(800) 234-4239http://www.networketi.com4 of 12 Environmental Technology, Inc.
Model EUR–5A Snow & Ice Melting Control
Environmental InterfacesThe EUR–5A determines when to start heater operation. It monitors the signals produced by up to six
environmental, customer-supplied sensors paralleled together using a three-wire bus. Available Environmental Technology, Inc. sensors include:
• SIT–6E Pavement Mounted Snow and Ice Sensor
• CIT–1 Aerial Snow and Ice Sensor
• GIT–1GutterSnowandIceSensor
The EUR–5A includes a temperature sensor for measuring pavement slab temperature. This sensor is required for proper operation of the unit. Its signal is used to provide an adjustable high limit thermostat function. This feature is essential when using a potentially high temperature heater such as mineral insulated (MI) cable.
Energy Management Computer (EMC) InterfaceThe EUR–5A provides an Energy Management Coputer interface (EMC) to communicate with the EMC
of building automation systems. The EMC interface provides 10 mA dry switch contacts for communicating status to the EMC or starting or stopping the system from the EMC.
Operator Interfaces
EUR–5A Front PanelThe EUR–5A has indicators, adjustments, and a switch for local control of the snow melting system.
These include:
• SUPPLYindicator
• HEATindicator
• SNOWindicator
• HEATERCYCLEpushbuttonswitch
• HOLD-ONtimeadjustmentwitharangeof0to10hoursandoff
• HIGHTEMPERATURELIMITtemperatureadjustmentwitharangeof40°to90°F(4°to32°C)
Figure 2 shows the EUR–5A front panel layout and pin number assignments.Figure 2. EUR–5A front panel layout and pin assignment
* hold-on: continued heater operation after sensors indicate the cessation of the weather event that initiated the heating; the interval is customer-determined
21776 Rev C 03/14 (800) 234-4239 http://www.networketi.com 5 of 12Environmental Technology, Inc.
Model EUR–5A Snow & Ice Melting Control
Pushbutton SwitchAt pins 28 and 29, the EUR–5A has an interface for a customer-supplied pushbutton switch which
initiates the hold-on timer for the interval set by the EUR–5A. This switch also resets the hold-on timer if it is running. Typically, this switch is located on the door of the electrical enclosure. This feature is optional.
RCU–3 Remote Control UnitEach EUR–5A includes an RCU–3 for monitoring the snow melting and controlling system operation
from a convenient observation point. This accommodates unusual conditions in the environment that could result in heater operation being terminated before the snow was completely cleared and the pavement dry. The RCU–3 provides both a heater hold-on switch and an independent cycle time interval adjustment.
The RCU–3 provides the following indicators, switches and adjustments (Figure 3):
• HEATERindicator(yellow“HEAT”)
• POWERindicator(green“SUPPLY”)
• HEATERCYCLEswitch
• HOLD-ONtimeadjustment(twotoeighthoursintwohoursteps)
Figure 4 illustrates the RCU–3 connection to the EUR–5A The RCU–3 mounts in a single gang switch box up to 500 feet (152.4 m) from the EUR–5A at a location convenient for observing snow melting system operation.
Figure 4.RCU–3 remote control connection to EUR–5A
Figure 3.RCU–3 remote control
Power SourceThe EUR–5A operates from a 24 volt AC NEC Class 2 power source. The optional 120 to 24 volt 50 VA
control transformer is included for use in installations using 120 VAC power.
Contactor InterfaceSince the EUR–5A is a NEC Class 2 device, it usually requires a customer supplied auxiliary relay for
operating the heater control contactor solenoids.
500' (152.4m) max20' (6m) supplied
21776 Rev C 03/14(800) 234-4239http://www.networketi.com6 of 12 Environmental Technology, Inc.
Model EUR–5A Snow & Ice Melting Control
Specifications
Environmental InterfacesEnvironmental Sensors Up to 6 sensors from the CIT–1/GIT–1/SIT–6E family
Temperature Limit Sensor ETI p/n 19272ThermistorTemperatureSensor. Locate up to 500' (152.4m) from the EUR–5A. Can be eliminated by
substituting a fixed resistor (470kΩ 1/3-watt) for the p/n 19272 (contact Customer Service for additional information)
Energy Management Computer (EMC) InterfaceInputs are relay coils operating from 5 VDC at 50 mA (nominal):
connect OVERRIDE ON/OVERRIDE OFF to input common to energize OVERRIDE ON OVERRIDE OFF
Outputs are relay contacts rated at up to 24 VAC or VDC at 50 mA, MAX 400 mA ± 100 mA: provides dry contact SUPPLY
SNOW
HEAT
Operator InterfacesEUR–5A Snow and Ice Melting Control Indicators SUPPLY
HEAT SNOW
Adjustments HOLD-ON TIME: 0 to 10 hours
HIGH TEMPERATURE LIMIT: 40° to 90°F (4° to 32°C) with a ± 0.5° F (± 0.3°C) dead-band
Control HEATER CYCLE: operates heaters for the hold-on timePanel-mounted Switch Electrical interface for a SPST dry-circuit panel-mounted switchRCU–3 Remote Control Unit Locate up to 500' (152.4m) from the EUR–5A Indicators SUPPLY
HEAT Adjustment HOLD-ON TIME: 2 to 8 hours Control HEATER CYCLEContactor Interface SPDT Class 2 pilot duty relay contact rated at 1 amp
Power Requirements NEC Class 2 source of 24 VAC
2 volt-amps (nominal)
Temperature Ranges Operating:−40°F(−40°C)to+140°F(+60°C)
Storage:−67°F(−55°C)to+167°F(+75°C)
Mechanical NEMA 1 housing
35mm DIN rail or bulkhead mounting
Dimensions: 3.95" wide x 4.31" deep x by 2.96" high (100.3mm x 109.5mm x 75.2mm)
21776 Rev C 03/14 (800) 234-4239 http://www.networketi.com 7 of 12Environmental Technology, Inc.
Model EUR–5A Snow & Ice Melting Control
OperationThe snow melting system can be monitored and controlled either locally from the EUR–5A or from
remote locations including:
• RCU–3 Remote Control Unit
• EMC
An alternative uses a customer-supplied switch at the front panel of the electrical enclosure to toggle the heaters into activation for the hold-on time.
Local Control from the EUR–5AThe EUR–5A face has indicator lights to its left and adjustment knobs to its right.
Indicators
• SUPPLY(green)showsthatpowerispresent
• HEAT(yellow)showsthatthereisacallforheat.Thishappensduringsnowandforthehold-ontimethereafter or when the heater cycle switch is operated. Please note, if thermistor temperature exceeds the setting on the temperature limit dial, the heaters will shut off; the hold-on timer remains active.
• SNOW(yellow)showsthatitissnowing
Adjustments
• HOLD-ONTIMEadjustmentcontrolsetsthetimethatheatersoperateaftersnowstops.Doingthisis necessary to make certain the pavement dries before heating ceases to prevent re-freezing. Try an initial setting of 5 hours. Increase, if necessary. Reduce with care since energy savings are being traded for an increased likelihood of re-freezing.
• HIGHTEMPERATURELIMITadjustmentcontrolsetsthemaximumdeicingtemperature.
Remote Control from the RCU–3The RCU–3 location is chosen for convenient observation of snow melting system operation. It monitors
snow melting and permits overriding automatic control in the event that heating terminates before the pavementisdry.TheyellowHEATindicatoroperateswiththesnowmeltingheaterswhilethegreenSUPPLYindicator shows that power is available for the snow melting system.
OperatingtheHEATERCYCLEswitchcausessnowmeltingheateroperationfortheHOLD-ONTIMEadjustment setting. Using this switch during hold-on turns the heaters off.
TheCYCLETIMEadjustmentcontrolsetstheheateroperatingtimefrom2to8hours.Therangeofthisadjustmentisindependentofitsequivalent(HOLD-ONTIME)ontheEUR–5A for flexibility.
Iftheheatersturnoffbeforethepavementisdry,engagetheHEATERCYCLEswitch.ThiscontinuesheateroperationfortheCYCLETIME.AtrialCYCLETIMEof4hoursissuggested.Ifthepavementdriesduringthehold-oninterval,operatetheHEATERCYCLEswitchtoturntheheatersoff.AdjusttheCYCLETIMEinstepsof plus or minus two hours to optimize heater operation.
Remote Control from the EMCOperation of this interface is defined in the Specifications section of this manual.
When jumpered to pin 10, inputs from the EMC include OVERRIDE ON (pin 11), which causes heater operation, and OVERRIDE OFF (pin 12), which inhibits heater operation. These functions are independent of weather conditions and the status of the hold-on timer. If both are engaged, OVERRIDE OFF prevails.
• OVERRIDEONcanbeusedtooverrideanconnectedEUR–5A in order to turn heaters on. A normal contact closure will turn on heaters until operation is cancelled.
• OVERRIDEOFFcanbeusedtooverrideaconnectedEUR–5A in order to turn heaters off. A normal contact closure will turn off heaters.
21776 Rev C 03/14(800) 234-4239http://www.networketi.com8 of 12 Environmental Technology, Inc.
Model EUR–5A Snow & Ice Melting Control
EMC interface outputsThe EUR–5AprovidesthreesystemstatuscontactclosuresfortheEMCincludingSUPPLY,HEATand
SNOW.TheSUPPLYrelaycontactclosesontheabsenceofpowersinceitisreverseacting.
• SUPPLYindicatesthatpowerispresent.
• HEATindicatesthatthereisacallforheat.ThishappensduringsnowandfortheHold-OnTimethereafter or when the heater cycle switch is operated.
• SNOWindicatesthatthereisasnow/icesignaloriginatingfromatleastoneoftheconnectedCIT–1, GIT–1 and/or SIT–6E sensors attached to the system.
Absent signals from the EMC, the EUR–5A controls the heaters based upon environmental conditions. Automatic snow melting control is the default condition of the system.
Panel-Mounted SwitchOperating this switch initiates heater operation for the hold-on time set by the EUR–5A. If operated
during the hold-on time, heater operation is terminated.
Upacking the EUR–5AImmediately upon receipt, inspect the container and packing material for any noticeable damage. Unpack
theunit,takingcarenottodamagethepackingmaterials.Confirmallcomponentsnotedin“PackingList”below are included. Save the shipping container and related materials until normal operation has been es-tablished. If the unit must be returned, take care to ensure that it is repackaged as it was received.
As soon as the unit arrives at your facility, inspect it for mechanical damage. If any of the following problems is found, contact Environmental Technology, Inc., Customer Service immediately:
•contentsincompleteorincorrect;•internalorexternalmechanicaldamage;or•defectiveoperation.Environmental Technology, Inc. Customer Service is available between 8:00 a.m. and 5:00 p.m. Eastern
Time at (574) 233-1202 or (800) 234-4239. In the event of shipping damage, keep the packing materials for inspection by the carrier.
Packing List
Order Number Quantity Description21496 1 EUR–5A Snow and Ice Melting Control
19272 1 TemperatureLimitSensor
14257 1 Power Transformer, 50 VA
21357 1 RCU–3 Remote Control
21776 1 EUR–5A Installation and Operation Manual (this document)
RETURNS AND REPLACEMENT PART PURCHASESEquipment cannot be returned for credit once it has been installed. Environmental Technology, Inc. will
repair or replace faulty equipment under warranty. Prior to removal of equipment for warranty return, please contact Environmental Technology, Inc. Technical Support at (800) 234-4239 for troubleshooting assistance.
Before returning a unit to Environmental Technology, Inc., obtain a Return Merchandise Authorization from our Customer Service Department, available between 8:00 a.m. and 5:00 p.m. Eastern Time at (574) 233-1202 or (800) 234-4239. If possible, use the original container and packing materials when packing the unit for shipment. It is important to mark the Return Merchandise Authorization clearly on the outside of the shipping container so that it may be correctly processed upon receipt at Environmental Technology.
For more information about replacement parts or for a replacement Data Sheet or Manual, please visit http://www.networketi.com/.
21776 Rev C 03/14 (800) 234-4239 http://www.networketi.com 9 of 12Environmental Technology, Inc.
Model EUR–5A Snow & Ice Melting Control
Figure 5. EUR-5A dimensions
(bottomview)
Connections
Safety InformationThe electric panel location creates
exposure to lethal voltages. Make all electrical connections in compliance with the National Electric Code (NEC)/NFPA 70 in the United States of America, the Canadian Electrical Code in Canada and local electrical codes and laws.
The EUR–5A, its sensors and remote control accessory devices are NEC Class 2 devices.
Customer SuppliedAuxiliary
Relay
HeaterControl
Contactor120 VAC50 VA
Figure 6. Power and contactor connections
Power Source and Contactor Connections
The EUR–5A operates from a 24 volt AC NEC Class 2 power source. The optional 120 to 24 volt 50 VA control transformer is included for use in installations using 120 VAC power.
Figure 6 shows power and contactor connections for a typical installation. Since the EUR-5A is a NEC Class 2 device, it usually requires a customer supplied auxiliary relay for operating the heater control contactor solenoids. If your installation is atypical, Customer Service is available for assistance.
Installation
LocationThe EUR–5A requires a protected location for a NEMA Type 1 enclosure
suitable for the environmental range given under Specifications (page 6). The electric panel that has the heater control contactors is an ideal location.
MechanicalFigure 5 shows a mechanical outline drawing of the EUR–5A. It mounts in
35 MM DIN rail (customer supplied). Optionally, the DIN rail locking mechanism can be removed from the bottom of the enclosure for direct panel mounting. For convenience, leave a generous space for wiring connections.
21776 Rev C 03/14(800) 234-4239http://www.networketi.com10 of 12 Environmental Technology, Inc.
Model EUR–5A Snow & Ice Melting Control
Red
White
Black
Red
White
Black
Red
Whi
te
Bla
ck
24 VAC Return
24 VAC
No Connection
No Connection
No Connection
No Connection
No Connection
No Connection
Remote Heater Toggle Return
Remote Heater Toggle
No Connection
Sensor 24 VAC (Red)
Sensor Signal (White)
Sensor Ground (Black)
No Connection
Control Relay Common
Control Relay NO
No Connection
Control Relay NC
3837
3635
3433
3231
3029
2827
2625
2423
2221
20
CIT–1Aerial
Snow Sensor
SIT–6EPavement-Mounted
Sensor
Power
Figure 7. Sensor connections for a typical pavement snow melting application
Figure 8. Temperature limit sensor connection
Ambient/Slab Temperature Sensor Connections
NOTE: The Ambient/Slab Temperature Sensor or a 470K ohm resistor is required across terminal 1 and 2 for the unit to properly operate. See Figure 8.
Environmental Sensors ConnectionsFigure 7 shows connections for a typical pavement snow melting application using both a CIT–1 Aerial
Snow Sensor and a SIT–6E Embedded Sensor. Up to six sensors can be used with a single EUR–5A. Use #18 AWGextensionwirefordistancesupto1000'(304.8m)and#12forupto2000'(609.6m).Runningsensorand line voltage wiring in the same conduit is not recommended.
Temperature LimitSensor
ETI p/n 19272
Equipment Ground
No Connection
EMC Heater On
EMC Snow Present
EMC Supply Present
EMC Output Common
EMC Override Off
EMC Override On
EMC Input Common
No Connection
No Connection
No Connection
No Connection
Remote Control Return
Remote Control
No Connection
Temperature Sensor Return
Equipment Ground
Temperature Sensor 12
34
56
78
910
1112
1314
1516
1718
19
500' (152.4m) max, 20' (6m) supplied
No Connection
No Connection
Remote Control Return
Remote Control
No Connection
Temperature Sensor Return
Temperature Sensor 12
34
56
100 kΩ resistor to earth ground
21776 Rev C 03/14 (800) 234-4239 http://www.networketi.com 11 of 12Environmental Technology, Inc.
Model EUR–5A Snow & Ice Melting Control
EMC Interface ConnectionsConnections are made to pins 10 through 16.
See page 9 for details.
Heater Cycle Switch Connections
Figure 10. Heater cycle switch connection
Figure 9. EMC interface connection
Remote HeaterCycle
Switch
24 VAC Return
24 VAC
No Connection
No Connection
No Connection
No Connection
No Connection
No Connection
Remote Heater Toggle Return
Remote Heater Toggle
No Connection
Sensor 24VAC (Red)
Sensor Signal (White)
Sensor Ground (Black)
No Connection
Control Relay Common
Control Relay NO
No Connection
Control Relay NC
3837
3635
3433
3231
3029
2827
2625
2423
2221
20
Power
Maintenance
GeneralThe EUR–5A contains no field replaceable components. Defective units must be returned to ETI for
repair or replacement.
TroubleshootingAlthough the EUR–5A is a relatively simple device electronically, troubleshooting is complicated by the
multiplicityoffeaturesprovidedbythisproduct.Hencecomponent-leveltroubleshootinginthefieldisnotpractical. Checking only basic functions is the correct approach. Contact Customer Service if this does not identify the problem.
First, check the installation for security. Make certain that all EUR–5A terminal block screws are snugly tightened. Do not over-tighten! If this is a new installation, check for wiring errors and similar problems.
IfnoneoftheLED’sontheEUR–5A front panel operate, check for 24 to 28 VAC between terminal block terminals 36 and 37. If the voltage is present, the EUR–5A is defective.
If the “HEAT” LED is flashing it indicates that the Ambient/Slab Temperature Sensor is not properly connected. Check the sensor connection and replace the sensor if necessary.
The next tests determine whether a sensor or the EUR–5A is defective. Remove EUR–5A power. Turn temperature limit dial to 90°F:ifambienttemperatureisabove85°F(29.4°C),install470kresistorinplaceof temperature limit thermistor. Remove the wire connected to terminal block terminal 25 which is the sensor signal connection. Re-apply EUR–5A power. If the Control Relay operates, the EUR–5A is defective. Connect a short jumper wire between terminal block terminals 25 (sensor signal) and 24 (sensor ground). The Control Relay should close within 10 seconds or the EUR–5A is defective.
21776 Rev C 03/14(800) 234-4239http://www.networketi.com12 of 12 Environmental Technology, Inc.
Model EUR–5A Snow & Ice Melting Control
LIMITED WARRANTYETI’stwoyearlimitedwarrantycoveringdefectsinworkmanshipandmaterialsapplies. Contact Customer Service for complete warranty information.
DISCLAIMEREnvironmental Technology, Inc. makes no representations or warranties, either expressed or implied, with respect to the contents of this publication or the products that it describes, and specifically disclaims any implied warranties of merchantability or fitness for any particular purpose. Environmental Technology, Inc. reserves the right to revise this publication, and to make changes and improvements to the products described in this publication, without the obligation of Environmental Technology, Inc. to notify any person or organization of such revisions, changes or improvements.
TheETIlogo,WeManageHeat,CIT,GIT,andSITareregisteredtrademarksofEnvironmentalTechnology,Inc.EURandRCUaretrademarksofEnvironmentalTechnology,Inc. Copyright © 2014 Environmental Technology, Inc. All rights reserved. Printed in USA.
Appendix: Pin Assignment TablePin # Label Description
1 Temperature Sensor HighTemperatureLimitSensor(included)2 Temperature Sensor Return HighTemperatureLimitSensor(included)3 No Connection4 Remote Control RCU-3 (included)5 Remote Control Return RCU-3 (included)6 No Connection7 No Connection8 No Connection9 No Connection10 EMC Input Common Remote Control (page 7)11 EMC Override ON Remote Control (page 7)12 EMC Override OFF Remote Control (page 7)13 EMC Output Common Reports this condition to EMC14 EMC Supply Present Reports this condition to EMC15 EMC Snow Present Reports this condition to EMC16 EMCHeaterON Reports this condition to EMC17 No Connection18 EquipmentGround19 EquipmentGround20 Control Relay NC Normally Closed21 Control Relay NO Normally Open. With pin 21 to pin 22,22 Control Relay Common output to heater controller contactor
23 No Connection24 SensorGround(Black) Parallel: only one (1) connection required25 Sensor Signal (White) Parallel: only one (1) connection required26 Sensor Power (Red) Parallel: only one (1) connection required27 No Connection28 RemoteHeaterToggle ExternalHEATCYCLEswitch29 RemoteHeaterToggleReturn ExternalHEATCYCLEswitch30 No Connection31 No Connection32 No Connection33 No Connection34 No Connection35 No Connection36 24 VAC input power from 24 VAC37 24 VAC Return input power from 24 VAC38 No Connection
Either pin works: tied together internally