8/7/2019 Battery Maintenance Technologies
1/23
8/7/2019 Battery Maintenance Technologies
2/23
LOGOwww.aitelong.com
Outlines
Type of batteries- Chng loi accu1
How to judges the condition of batteries Lm th no chn on tnh trng accu
2
Two ways to test batteries condition Hai cch kim tra tnh trng accu
3
Operations - Hot ng4
8/7/2019 Battery Maintenance Technologies
3/23
LOGO
Diagram
Lead-Acid
Battery
Two common types LA batteryHai loi accu ph bin
Flooded VRLA
www.aitelong.com
8/7/2019 Battery Maintenance Technologies
4/23
LOGOwww.aitelong.com
Battery Cell
Type of battery cell Loi bn cc ca accu
Voltage: 2V 4V 6V 8V 10V 12V 14V 16V
Capacity- Dung lng: 50AH to 3000AH or more
Applications: Motive Power, Auto Motive
Stationary/Backup Powerng c in, t ng lcVn phng phm / Sao lu in
8/7/2019 Battery Maintenance Technologies
5/23
LOGOwww.aitelong.com
Battery Cell
Type of battery cell
Single Cell
Battery Unit: JAR / Monoblock
8/7/2019 Battery Maintenance Technologies
6/23
LOGOwww.aitelong.com
Battery String
Type of battery String
Telecommunication: 48V
UPS system: 110V 220V 380V 600V
Forklift: 24
V/48
V
8/7/2019 Battery Maintenance Technologies
7/23
LOGOwww.aitelong.com
Hot Tip How to know the condition of batteries?
To compare current capacity to the nominal orinitial capacity- so snh dung lng hin ti vidung lng danh nh .
It should be noted that if capacity has fallen to 80%, the one-year replacement period mightnot ensure that the battery can fulfill its duty cycle. In this instance, the battery should bereplaced at the earliest opportunity -Cn lu rng nu nng lc gim n 80%, thigian thay th mt nm c th khng m bo rng pin c th hon thnh nhim v chu kca n. Trong trng hp ny, pin s c thay th ti cc c hi sm nht .
A capacity of 80% shows that the battery rate of deterioration is increasing even if there isample capacity to meet the load requirements.
Page 15, Section 8 Battery replacement criteriaIEEE Standard 450-2002
Mt cng sut 80% cho thy t l pin ca suy thoi ang gia tng, ngay c nu c nng lc dido p ng nhu cu ph ti. "
15 Page, Mc 8 "Pin tiu chun thay th"Tiu chun IEEE 450-2002
8/7/2019 Battery Maintenance Technologies
8/23
LOGO
Test Methods
DischargeTest Kim
tra x
BatteryTest
InternalResistance
orConductanceTest kim tra Ni tr
hoc dn
www.aitelong.com
8/7/2019 Battery Maintenance Technologies
9/23
LOGOwww.aitelong.com
Discharge Test
Benefits u im
The only way to exactly know the condition of
battery cell by Ah (ampere-hour) result Cch duy nht bit chnh xc tnh trng ca pin bng Ah (ampe-gi) kt qu
Extend lifecycle of battery cell M rng vng i ca t bo pin
To test whole battery string in same time kim tra ton b pin chui thi
8/7/2019 Battery Maintenance Technologies
10/23
LOGOwww.aitelong.com
Discharge Test
Disadvantage
Long test period10 hours discharging time plus 4 to 10 hours charging time
Long giai on th nghim
10 gi thi gian x cng 4 n 10 gi thi gian sc pin
High extra cost
Electricity fee and employee salaryThm chi ph cao
in ph v lng nhn vin
No record and analyzing function for oldmodels
Khng c chc nng ghi li v phn tch cho cc m hnh c
8/7/2019 Battery Maintenance Technologies
11/23
LOGOwww.aitelong.com
Discharge Test
Aitelongs SAT-AL intelligent Load Bank
Monitoring Function
to monitoring whole battery string voltage, each battery cell voltage, whole batterystring current, discharged capacity
Full Automatic Operation
Four terminated conditions: time,
capacity, string volt, cell volt
Data record and powerful PC analyzing function
Chc nng gim st theo di ton b chui in p pin, mi pin in p, ton b chui pin hin ti, cngsut thi
Ton t ng hot ngBn chm dt iu kin: thi gian,nng lc, dy volt, t bo volt
Bn ghi d liu v my tnh mnh m phn tch chc nng
8/7/2019 Battery Maintenance Technologies
12/23
LOGOwww.aitelong.com
Ohmic Test
Ohmic and Discharge Test- Ohmic v th nghim phng
e.g. A bottle has 500 ml of water how do you know if the bottle has less than 400 ml of water80%
a) by cup measureb) by weight
c) by water level
Ohmic measurement is like weight or water level measurement to monitor the loss ofwater and calculate the remaining volume of water (capacity).
v d: Mt chai 500 ml c nc lm th no bn bit nu chai c t hn 400 ml nc 80%a) bng bin php lyb) tnh theo trng lng
c) theo cp nc
Ohmic o c nh o mc trng lng hoc nc theo di s mt nc vtnh ton khi lng cn li ca nc (cng sut).
8/7/2019 Battery Maintenance Technologies
13/23
LOGOwww.aitelong.com
Ohmic Test
It is a measure of the plate surface whichdetermines how much chemical reaction or powerthe battery can generate.
The battery state of health can be diagnosed bythe change of the plate surface.
8/7/2019 Battery Maintenance Technologies
14/23
LOGOwww.aitelong.com
Ohmic Test
Conductance
Internal resistance/ impedance
SOHSOHStateState--ofof--healthhealth
Conductance
Internal resistance/ impedance
8/7/2019 Battery Maintenance Technologies
15/23
LOGOwww.aitelong.com
Ohmic Test
Internal Ohmic Measurements
Impedance measurements can be performed by passing acurrent of known frequency and amplitude through thebattery and measuring the resultant ac voltage dropacross each cell/unit.
Impedance and resistance are inversely related toconductance.
Conductance = 1 / Impedance
8/7/2019 Battery Maintenance Technologies
16/23
LOGOwww.aitelong.com
Ohmic Test
8/7/2019 Battery Maintenance Technologies
17/23
LOGOwww.aitelong.com
Ohmic Test
Reference Value
Reference Value / Threshold Value is a sample orstandard which tester get from when battery is initialinstalled or from manufactory recommended.
Use latest test value compare to the reference value
to get rate which can refer to batterys SOH.
8/7/2019 Battery Maintenance Technologies
18/23
LOGOwww.aitelong.com
Ohmic Test
British Telecom Paper at Intelec 1998
eImpedance/Conductance Measurements as an Aid toDetermining Replacement Strategy
Conclusions:This paper has shown that two particular parameters,
namely conductance/impedance monitoring andtemperature/time/life factors can be effective inforecasting battery replacement timescales.
8/7/2019 Battery Maintenance Technologies
19/23
LOGOwww.aitelong.com
Ohmic Test
8/7/2019 Battery Maintenance Technologies
20/23
LOGOwww.aitelong.com
Ohmic Test
France Telecom Paper at Intelec 2001
eMeasurement of Impedance and Conductance: Myth and RealityTested in the Field
Analysis and ConclusionIn a power system architecture serving telecommunications equipment,
batteries are used in an emergency through lack of normalelectrical supply, generally the mains. It is therefore absolutely
impossible to disconnect them to test their residual capacity bymeasurement of conductance or impedance. These must becarried out online. Consequently, as soon as a battery is made upof more than one string, it is necessary to take into account thecorrection factor.
(p. 419, Analysis and Conclusion)
8/7/2019 Battery Maintenance Technologies
21/23
LOGOwww.aitelong.com
Ohmic Test
France Telecom Paper at Intelec 2001
Regarding the conductance measured with apparatus A, the fault
thresholds determined from measurements on more than 1200Monoblock (AGM 12 V 75 Ah) are as follows:
Loss of conductance less than 30%= loss of capacity less than 20%
Loss of conductance more than 40%= loss of capacity more than 20%
(p. 420, Measurement Results)
8/7/2019 Battery Maintenance Technologies
22/23
LOGOwww.aitelong.com
Ohmic Test
Guidelines on Measurement
a) - The battery tested should be under stable conditions (Not
in the process of charging and discharging)
b) - The battery should be tested under the same condition.(We compare apple with apple, not apple with orange);
c) - The test probes or clamp should be placed as close aspossible to the battery posters (to avoid the impact fromother metal accessories)
d) - The test can identify good or bad cells
8/7/2019 Battery Maintenance Technologies
23/23
LOGOwww.themegallery.com