Beginning Next SlideBack 1 of 15 End Program
AVADAL AVADALSK-3 Rolls
Rolls Will Not Extend/Extend Slowly
Beginning Next SlideBack 2 of 15 End Program
AVADAL AVADALSK-3 Rolls
1. Are the isolation valves on SK-3 open?
Beginning Next SlideBack 3 of 15 End Program
AVADAL AVADALSK-3 Rolls
2. Are the isolation valves on SK-5, SK-5A & SK-6
modules open?
Beginning Next SlideBack 4 of 15 End Program
AVADAL AVADALSK-3 Rolls
3. Is there 650 psi at test point on SK-5, SK-5A &
SK-6 modules?
Beginning Next SlideBack 5 of 15 End Program
AVADAL AVADALSK-3 Rolls
4. Are 2 position 4 way Directional Valves M1 & M3 energized on SK-5,
SK-5A & SK-6 modules?
Beginning Next SlideBack 6 of 15 End Program
AVADAL AVADALSK-3 Rolls
5. Are Rotary Flow Dividers operating properly on SK-3
Modules?
Beginning Next SlideBack 7 of 15 End Program
AVADAL AVADALSK-3 Rolls
6. Are Cross Line Pressure Relief
Valves on module SK-3 set correctly?
Beginning Next SlideBack 8 of 15 End Program
AVADAL AVADALSK-3 Rolls
7. Is there any mechanical binding?
Beginning Next SlideBack 9 of 15 End Program
AVADAL AVADALSK-3 Rolls
Roller Segments Will Not Retract/Retract Slowly
Beginning Next SlideBack 10 of 15 End Program
AVADAL AVADALSK-3 Rolls
1. Are the isolation valves on SK-3 open?
Beginning Next SlideBack 11 of 15 End Program
AVADAL AVADALSK-3 Rolls
2. Are the isolation valves on SK-5, SK-5A & SK-6
modules open?
Beginning Next SlideBack 12 of 15 End Program
AVADAL AVADALSK-3 Rolls
3. Is there 650 psi at test point on SK-5, SK-5A &
SK-6 modules?
Beginning Next SlideBack 13 of 15 End Program
AVADAL AVADALSK-3 Rolls
4. Are 2 position 4 way Directional Valves M1 & M2 energized on SK-5,
SK-5A & SK-6 modules?
Beginning Next SlideBack 14 of 15 End Program
AVADAL AVADALSK-3 Rolls
5. Are Rotary Flow Dividers operating properly on SK-3
Modules?
Beginning Next SlideBack 15 of 15 End Program
AVADAL AVADALSK-3 Rolls
6. Is there any mechanical binding?