CUSTOMER: PLN
SITE: Palembang, South Sumatra, Indonesia
LM6000 MICRONET CONTROL
GE PACKAGED POWER, L.P.
© Copyright2011
GEPackagedPower,L.P.
Allrights reserved.
This drawingis the proprietaryand/or confidentialpropertyof GEPackagedPower,L.P.and is loanedinstrict
confidence withthe understandingthatit willnotbe reproducednor usedfor anypurpose exceptthatfor whichit is
loaned.Itshallbe immediatelyreturnedondemandandis subject to allother terms andconditions of anywritten
agreementor purchase order thatincorporates or relates to this drawing.
LINE REV TAG NO. PROCESS DESCRIPTIONRANGE LOW
(English)
RANGE HIGH
(English)
LIMIT DECR
(English)
LIMIT INCR
(English)ENGLISH UNIT
RANGE LOW
(Metric)
RANGE HIGH
(Metric)
LIMIT DECR
(Metric)
LIMIT INCR
(Metric)METRIC UNIT ACTION NOTE ALARM ALM DLY (S) SHUT DOWN ABORT START START PERM. CRANK PERM. MOTORS HEATERS VALVES COMMENTS
CAUSE AND EFFECT MATRIX
TURBINE LUBE OIL SYSTEM
10. WINTERIZED FIN FAN LUBE OIL COOLER LOUVERS (SOV-68349) OPEN IF TE-61069 > 50 DEG F (10.0 DEG C) OR TE-60019 > 50 DEG F (10.0 DEG C)
11. WINTERIZED FIN FAN LUBE OIL COOLER LOUVERS (SOV-68349) CLOSE IF TE-61069 < 30 DEG F (-1.1 DEG C) AND TE-60019 < 34 DEG F (1.1 DEG C)
12. THE SELECTED WINTERIZED FIN FAN LUBE OIL COOLER FAN (MOT-6090 OR MOT-6091) IS ON IF TE-61069 > 70 DEG F (21.1 DEG C) OR TE-60019 > 70 DEG F (21.1 DEG C) AND ENGINE CRANKING OR RUNNING
13. THE SELECTED WINTERIZED FIN FAN LUBE OIL COOLER FAN (MOT-6090 OR MOT-6091) IS OFF IF TE-61069 < 35 DEG F (1.7 DEG C) AND TE-60019 < 35 DEG F (1.7 DEG C) OR ENGINE IS NOT CRANKING OR RUNNING
14. WINTERIZED FIN FAN LUBE OIL COOLER HEATER HE-68345 WILL TURN ON IF TE-68347 < 175 DEG F (79.4 DEG C) AND LOUVERS ARE CLOSED.
15. WINTERIZED FIN FAN LUBE OIL COOLER HEATER HE-68345 WILL TURN OFF IF TE-68347 > 250 DEG F (121.1 DEG C) OR LOUVERS ARE OPEN.
16. XN25 > 6050 RPM
LEGEND
1. SEE LEGEND TAB
REVISION LIST DATE:
A ORIGINAL ISSUE 07/18/1
B NO CHANGES THIS SHEET 05/16/1
====== END ======
CAUSE AND EFFECT MATRIXTURBINE LUBE OIL SYSTEM
ORIGINATED: 07/18/11PRINTED: 7/5/2012 1:56 PM
REV DATE: 05/16/05/16/05/16/12
DRA
SHE
8/18/2019 Cause Effect & Matrix 07-05-2012 REV_B
8/16
8/18/2019 Cause Effect & Matrix 07-05-2012 REV_B
9/16
CUSTOMER: PLN
SITE: Palembang, South Sumatra, Indonesia
LM6000 MICRONET CONTROL
GE PACKAGED POWER, L.P.
© Copyright2011
GEPackagedPower,L.P.
Allrights reserved.
This drawingis the proprietaryand/or confidentialpropertyof GEPackagedPower,L.P.and is loanedinstrict
confidence withthe understandingthatit willnotbe reproducednor usedfor anypurpose exceptthatfor whichit is
loaned.Itshallbe immediatelyreturnedondemandandis subject to allother terms andconditions of anywritten
agreementor purchase order thatincorporates or relates to this drawing.
LINE REV TAG NO. PROCESS DESCRIPTIONRANGE LOW
(English)
RANGE HIGH
(English)
LIMIT DECR
(English)
LIMIT INCR
(English)ENGLISH UNIT
RANGE LOW
(Metric)
RANGE HIGH
(Metric)
LIMIT DECR
(Metric)
LIMIT INCR
(Metric)METRIC UNIT ACTION NOTE ALARM ALM DLY (S) SHUT DOWN ABORT START START PERM. CRANK PERM. MOTORS HEATERS VALVES COMMENTS
1 LS-6543 WATER WASH TANK LEVEL CONTROL 23.0 % 23.0 % LAL 2 X MOT-6535 PERM HE-6536 PERM
2
3 HS-6505 WATER WASH CONTROL STATION
4
5 S OV-6540 WATER WASH PURGE AIR VALVE 1 = OPEN VALVE
67 MOT-6535 WATER WASH SUPPLY PUMP 2
8
9 HE-6536 WATER WASH TANK HEATER 2 OPT: WATER WASH TANK HEATER
10
11 SOV-6504 WATER WASH OFF-LINE SUPPLY VALVE 1 = OPEN VALVE
12
13 SOV-6516 WATER WASH ON-LINE SUPPLY VALVE 1 = OPEN VALVE
14
15
NOTES
1. INTENTIONALLY LEFT BLANK.
2. HEATER AND PUMP OFF IF LEVEL LOW (HEATER AND PUMP PERMISSIVE).
LEGEND
1. SEE LEGEND TAB
REVISION LIST DATE:
A ORIGINAL ISSUE 07/18/1
B NO CHANGES THIS SHEET 05/16/1
====== END ======
CAUSE AND EFFECT MATRIX
WATER WASH
CAUSE AND EFFECT MATRIXWATER WASH
ORIGINATED: 07/18/11PRINTED: 7/5/2012 1:56 PM
REV DATE: 05/16/05/16/05/16/12
DRA
SHE
8/18/2019 Cause Effect & Matrix 07-05-2012 REV_B
10/16
8/18/2019 Cause Effect & Matrix 07-05-2012 REV_B
11/16
8/18/2019 Cause Effect & Matrix 07-05-2012 REV_B
12/16
8/18/2019 Cause Effect & Matrix 07-05-2012 REV_B
13/16
8/18/2019 Cause Effect & Matrix 07-05-2012 REV_B
14/16
8/18/2019 Cause Effect & Matrix 07-05-2012 REV_B
15/16
CUSTOMER: PLN
SITE: Palembang, South Sumatra, Indonesia
LM6000 MICRONET CONTROL
GE PACKAGED POWER, L.P.
© Copyright2011
GEPackagedPower,L.P.
Allrights reserved.
This drawingis the proprietaryand/or confidentialpropertyof GEPackagedPower,L.P.and is loanedinstrict
confidence withthe understandingthatit willnotbe reproducednor usedfor anypurpose exceptthatfor whichit is
loaned.Itshallbe immediatelyreturnedondemandandis subject to allother terms andconditions of anywritten
agreementor purchase order thatincorporates or relates to this drawing.
LINE REV TAG NO. PROCESS DESCRIPTIONRANGE LOW
(English)
RANGE HIGH
(English)
LIMIT DECR
(English)
LIMIT INCR
(English)ENGLISH UNIT
RANGE LOW
(Metric)
RANGE HIGH
(Metric)
LIMIT DECR
(Metric)
LIMIT INCR
(Metric)METRIC UNIT ACTION NOTE ALARM ALM DLY (S) SHUT DOWN ABORT START START PERM. CRANK PERM. MOTORS HEATERS VALVES COMMENTS
1 B
2 B
3
4 SAS_CUST_R RAISE XNSD SPEED (MANUAL) INHIBITED WHEN DSM ENABLED
5 SAS_CUST_L L OWER XNSD SPEED (MANUAL) INHIBITED WHEN DSM ENABLED
6
7 CUST_SCLK SYNC CONTROL CLOCK (CUSTOMER) OPTIONAL
8
9 CHW_STPERM PERMISSIVE START (CUSTOMER) OPTIONAL
10 CHW_RESET RESET (AL / NLO SD ONLY) (CUSTOMER) OPTIONAL
11 CHW_86TRIP 86 TRIP (CUSTOMER) ES
12 BUT_86TRIP BUS/UTILITY 86 TRIP (CUSTOMER) X OPTIONAL
13 GEN_BKR_FL GEN BREAKER FAILURE (CUSTOMER) ES CUSTOMER'S ZONE CLEAR SIGNAL. OPTIONAL
14 CHW_R_STRT REMOTE START (CUSTOMER) OPTIONAL
15 CHW_R_STP REMOTE NORMAL STOP (CUSTOMER) OPTIONAL
16 CHW_ACK A LARM ACKNOWLEDGE (CUSTOMER) OPTIONAL
17
18 CUST_T2 TURBINE INLET TEMP (T2 AVERAGE) -40.0 120.0 -40.0 48.9 OPTIONAL
19 CUST_T1 AIR FILTER INLET TEMP (T1) -40.0 120.0 -40.0 48.9 OPTIONAL
20
21 CUST_SD TURB-GEN SUMMARY SHUTDOWN (CUSTOMER) OPTIONAL
22
23
NOTES
LEGEND
1. SEE LEGEND TAB
REVISION LIST DATE:
A ORIGINAL ISSUE 07/18/1
B ROWS 1 AND 2 REMOVED 05/16/1
====== END ======
CAUSE AND EFFECT MATRIX
CUSTOMER INTERFACE
CAUSE AND EFFECT MATRIXCUSTOMER INTERFACE
ORIGINATED: 07/18/11PRINTED: 7/5/2012 1:56 PM
REV DATE: 05/16/05/16/05/16/12
DRA
SHEE
8/18/2019 Cause Effect & Matrix 07-05-2012 REV_B