(Cimon Mobile) and (Cimon SCADA)
setting at different PCs.
September 2012.
1
What you prepare
Programming software
Cimon SCADA (CimonD version 2.12 or later version)
Cimon Mobile version 1.6.3 or later version
Network
Internet
Wireless internet router used by
public IP(Ex.Iptimes)
Port forwarding
UDP 5400 + Offset
Intranet network (Private network)
CimonX
(FEP Server)
Mobile Server
(Mobile option keylock)
2
IP address (Example)
CimonX (FEP Server)
IP : 100.100.100.20
Mobile Server
IP : 100.100.100.10
3
Cimon SCADA Setting
4
Setting preparation
CimonD
Setting
Network FEP setting
User security setting
Others
There must be tags in Database.
Tags in Database
5
Network FEP setting
[Tools] [Network]
6
Network FEP setting
FEP select ENET (TCP/IP)
Write Port number and Primary IP Address
Write PC IP address which
runs CimonD and CimonX.
(Refer to Page.3)
Select one of Port number
from 0 to 99
7
Security setting
[Tools] [Security]
Click ‘New User’ to add User ID
8
Write ID name which will be
used at Mobile Application.
(iOS, Android)
(Ex. ID: KDT, Password:1234)
After saving setting, click [Tools] [Run Project]
Run CimonX
9
Save
Run CimonX
10
[View] [System Status]
Run CimonX
11
FEP server
If you see this message, FEP
server is running properly.
If IP address is not correct,
you can see this message.
Cimon Mobile setting
12
Setting preparation
13
Mobile Designer
Setting
Network setting
Tag registration
Project Configuration
The first page when
you open the project
Network setting
14
[Tool] [Network]
Write PC IP address which runs
Mobile Designer and Server.
(Ex. Refer to Page.3)
Select one of Port number from 0 to 99.
This Port number will be used when
you connect to Mobile Server from
Mobile Application.
(iOS, Android)
Network setting
15
[Tool] [Network]
Wire PC IP address which runs
CimonX.
(Ex. Refer to Page 3 & 7)
Select one of Port number from 0
to 99.
This port number must be the
same with CimonX port number.
(Ex. Refer to Page 7)
Tag Registration
16
Bring the tag list from CimonX and register for Server
Tag Registration
17
Tag Registration failure
If you see this message, the
network setting is not correct.
(Refer to page 15)
Mobile Server
18
[Tool] > [Server Execute]
Mobile Server
19
If you see this message, Mobile server is
running properly. It usually takes 1 second to
register 50 tags. (Ex. 3000tags, 3000/50 = 60sec.)
Mobile Server
20
Communication failure(1)
If you see this message, ‘Local IP Address’
setting is not correct.
(Refer to Page. 14)
Mobile Server
21
Communication failure(2)
If you see this message, ‘FEP Server IP Address’
and ‘FEP Server Port number’ are not correct.
(Refer to Page. 15)
Cimon App. setting
22
Cimon App. setting
23
Example: Android Galaxy Note.
Cimon App. setting
24
Connecting to server and downloading
1. Write ‘Local IP Address’
and ‘Local Port number’
(Refer to Page. 14)
2. Write the User ID and
Password that you register in
CimonD.
(Refer to Page. 8)
Cimon App. setting
25
Project monitoring
1. Touch (Menu) and
(Monitoring)