5L
1083www.crouse-hinds.com US: 1-866-764-5454 CAN: 1-800-265-0502 Copyright© 2013 Eaton’s Crouse-Hinds Business
5LEVLPF SeriesCompact FluorescentLow Profile Hazard•Gard®
Luminaires
Cl. I, Div. 1, Groups B (GB Suffix), C, DCl. I, Zone 1, Groups IIB + H2 (GB Suffix), IIB, IIACl. II, Div. 1, Groups E, F, GClass III, Simultaneous Presence
Marine & Wet Locations3, 3R, 4, 4X; IP66
Applications:Eaton's Crouse-Hinds Low ProfileHazard•Gard® luminaires are used in:• Areas where flammable or explosive
vapors or gases are present• Hazardous areas, both indoors and
outdoors, where long life and lowmaintenance costs are desired
• Petroleum refineries, chemical,petrochemical and pharmaceuticalplants, oil terminals, gas plants and otherheavy process industry facilities
• Waste treatment facilities• Drilling platforms and other coastal and
offshore hazardous areas
Features and Benefits:• Small, compact size• Two start Acme threaded construction• Lightweight copper-free aluminum
housing with powdered epoxy finish• All exterior hardware is corrosion-
resistant stainless steel• Four mounting arrangements - pendant,
ceiling, wall bracket, and stanchion• Wide range of light sources and
wattages• Marine and NEMA 4X construction• Integral ballast• High power factor (90%+) ballasts• Uses same mounting modules as the
standard Hazard•Gard®
• Internally fluted glass globes• Krydon® construction dome and angle
reflectors – won't rust, corrode, dent,chip, or peel
• Now available in components – luminairebody, mounting module, guard,reflectors
• Three wire construction is standard onfluorescent emergency lighting
• Perfect where low mounting restrictionsare a concern
• Easier assembly, installation andmaintenance
• Superior corrosion resistance• Suit any lighting layout• Meet specific lighting needs• Outdoor, hose down, marine, and
corrosive environments suitable• Lowest installed cost• Allows more luminaires per circuit• Easy retrofitting when the EVLPF is
the preferred choice• Reduces glare and distributes light
evenly – ideal for adverse environmentstypical of industrial facilities
• Easily stocked for quick shiprequirements
• For energy conservation, luminaires canbe switched off without affecting theemergency operation feature
Standard Materials:• Mounting modules, cover, ballast
housing, globe holder – copper-freealuminum
• Globe – heat- and impact-resistant glass• Exterior hardware – stainless steel• Reflectors (dome & angle) – Krydon®
fiberglass-reinforced polyester
Standard Finishes:• Copper-free aluminum – Corro-free™
powdered epoxy• Krydon – white• Stainless steel guard
Ratings (Electrical/Size):Sources/Wattage:• 52W (two 26W lamps) & 64W (two 32W
lamps)• 120–277V, 50–60Hz• 347V, 60Hz• 12, 24, 125 VDCConduit Entries:• 3/4", 1" NPT – Pendant, Wall Bracket,
Ceiling• 11/4" NPT – Stanchion
Certifications andCompliances:• NEC and CEC:
Class I, Division 1, Groups B (GB suffix), C, DClass I, Zone 1, Groups IIB + H2
(GB Suffix), IIB, IIAClass II, Class III & SimultaneousPresence(Class I and Class II)
• UL Standards:844 Hazardous (Classified) Locations1598 Luminaires1598A Marine Locations
• CSA StandardsC22.2 No. 137
Accessories:Description Cat. #
Dome reflector ................................................................................................................ RD739Angle reflector ................................................................................................................ RA739
Options:Description Suffix
Group B suitability .......................................................................................................... GBFused (not suitable for marine applications) .................................................................... S658Factory assembled with lamps ........................................................................................ FA
5L
1084 www.crouse-hinds.com US: 1-866-764-5454 CAN: 1-800-265-0502 Copyright© 2013 Eaton’s Crouse-Hinds Business
Pendant Mount
*Wall Bracket Mount
*Ceiling Mount
Stanchion Mount
Pendant Wall Bracket* Ceiling* Stanchion
Luminaire Body
Less Mounting
Module & Guard
Watt
Hub
Size (In.)
With Guard
Cat. #
With Guard
Cat. #
With Guard
Cat. #
With Guard
Cat. # Cat. #
Fluorescent—High Power Factor Ballast (Min. P.F. 90%)
52W
3/4 EVLPFA02521 EVLPFBX02521 EVLPFCX02521 EVLPF0520
1 EVLPFA03521 EVLPFBX03521 EVLPFCX03521
11/4 EVLPFJ04521
64W3/4 EVLPFA02641 EVLPFBX02641 EVLPFCX02641 EVLPF0640
1 EVLPFA03641 EVLPFBX03641 EVLPFCX03641
11/4 EVLPFJ04641
Pendant Wall Bracket* Ceiling* Stanchion
Watt
Hub
Size (In.)
Without Guard
Cat. #
Without Guard
Cat. #
Without Guard
Cat. #
Without Guard
Cat. #
Fluorescent—High Power Factor Ballast (Min. P.F. 90%)
52W
3/4 EVLPFA02520 EVLPFBX02520 EVLPFCX02520
1 EVLPFA03520 EVLPFBX03520 EVLPFCX03520
11/4 EVLPFJ04520
64W3/4 EVLPFA02640 EVLPFBX02640 EVLPFCX02640
1 EVLPFA03640 EVLPFBX03640 EVLPFCX03640
11/4 EVLPFJ04640
*Ceiling and bracket mounts have 4 hubs: 3 are plugged.
Complete Catalog Number as follows:
1. Voltages - Add suffix as follows:
Standard Voltage Ballasts - 60Hz Optional Ballasts
NEC/UL & CEC/CSA (cUL) CEC/CSA (cUL)
Voltage 120–277V 50–60Hz 347V 60 Hz 125V DC 12V DC 24V DCSuffix /UNV /347 /125VDC /012VDC /024VDC
5L EVLPF SeriesCompact FluorescentLow Profile Hazard•Gard®
Luminaires
Cl. I, Div. 1, Groups B (GB Suffix), C, DCl. I, Zone 1, Groups IIB + H2
(GB Suffix), IIB, IIACl. II, Div. 1, Groups E, F, GClass III, Simultaneous Presence
Marine & Wet Locations3, 3R, 4, 4X; IP66
5L
1085www.crouse-hinds.com US: 1-866-764-5454 CAN: 1-800-265-0502 Copyright© 2013 Eaton’s Crouse-Hinds Business
EVLPF Series Ordering By Components
Mounting Modules:Type Conduit Cat. #
Pendant3/4" EVMP2
1 EVMP3
Ceiling & Wall Box3/4" EV22
1 EV33
Wall Bracket Arm Use EV22 or EV33 box with EV87 EV87
Stanchion 11/4" EVMJ4
Guards
Fluorescent EV512
Reflectors
Dome RD739
Angle RA739
Pendant Ceiling Stanchion Ceiling Wall Bracket
EVMP2EVMP3
EV22EV33
EVMJ4 EV22EV33
EV87 & EV22 or EV33
Guards Dome Reflector Angle Reflector
EV512 RD739 RA739
Fixture Body
EVLPF0520/UNV
EVLPF0521/UNV
EVLPF0640/UNV
EVLPF0641/UNV
5L
EVLP Luminaires are available in components.
A complete light fixture consists of:I. Mounting ModuleII. Fixture BodyIII. Guard, Dome Reflector, Angle Reflector, or Exit Sign
5L
1086 www.crouse-hinds.com US: 1-866-764-5454 CAN: 1-800-265-0502 Copyright© 2013 Eaton’s Crouse-Hinds Business
Fluorescent Fixtures
Maximum Ambient
Class I, Group B
(w/GB suffix)
Groups C, D
Class I, Zone I
40°C
Class II, Groups E, F, G
Class III
Simultaneous
Presence
40°C Supply Wire °C
Minimum
Operating
Temperature
Fluorescent 52W & 64W T6 T6 75°C –18°C
5L EVLPF SeriesCompact FluorescentLow Profile Hazard•Gard®
Luminaires
Dimensions and Weights
DimensionsIn Inches:
A B C D E F
Fluorescent 15.69 14.69 18.25 18.46 22.34 21.30
Weights:Item Lbs.
Fluorescent
(EVLPF)31.5
Add Mounting Modules:
Pendant 1Ceiling 2Bracket 4.5Stanchion 2.5
Add For Reflectors & Exit Sign:
RA739 1RD739 1DMVF–EXD 5Deduct .5 lb for Wire Guard
Temperature Performance Data:
5L
1087www.crouse-hinds.com US: 1-866-764-5454 CAN: 1-800-265-0502 Copyright© 2013 Eaton’s Crouse-Hinds Business
5L
Luminaire with Globe and GuardEVLPFA03641 Two 32 W Compact Fluorescent
Photometric DataEVLPF SeriesCompact FluorescentLow Profile Hazard•Gard® Luminaires
5L
1088 www.crouse-hinds.com US: 1-866-764-5454 CAN: 1-800-265-0502 Copyright© 2013 Eaton’s Crouse-Hinds Business
Luminaire with Globe and Dome (Less Guard)EVLPFA03640RD Lamp: Two 32 W Compact Fluorescent
Luminaire with Globe and 30° Angle Reflector (Less Guard)EVLPFA03640RA Lamp: Two 32 W Compact Fluorescent
5L Photometric DataEVLPF SeriesCompact FluorescentLow Profile Hazard•Gard® Luminaires