Figure G3Caryville
Battery PlantG:\FDOTGC\Battery Replacement\I-10 Replacement 2013\Appendix\FigG3_Caryville_BatteryPlant.vsd
03/12/13
Vendor Shall install new battery in existing rack.
Page G6 of 6 64
FLORIDA DEPARTMENT OF TRANSPORTATION
I-10 BATTERY PLANT REPLACEMENT
Appendix H – Chipley DOT
65
FLORIDA DEPARTMENT OF TRANSPORTATION
I-10 BATTERY PLANT REPLACEMENT
Page H2 of 7
Appendix H – Table of Contents – Figures and Drawings
Figure H1 – Chipley DOT Shelter Floor Plan ............................................................ H4 of 7
Figure H2 – Chipley DOT -48VDC Power Distribution Rack Profile .......................... H5 of 7
Figure H3 – Chipley DOT West Interior Wall ............................................................ H6 of 7
Figure H4 – Chipley DOT Battery Plant Photo.......................................................... H7 of 7
66
FLORIDA DEPARTMENT OF TRANSPORTATION
I-10 BATTERY PLANT REPLACEMENT
Page H3 of 7
Chipley DOT Site Requirements
The Vendor shall furnish and install the following equipment at the Chipley DOT site located at 1074 US-90, Chipley, FL.
A. One Exide Absolyte GP series battery plant model number M87-024-05009-R19ACLV shall
be installed in accordance with this Appendix and Section 2.2 of this Scope of Services.
The new battery plant shall be installed in the same location as the removed battery plant.
The Vendor shall replace the existing cable with 1/0 AWG stranded. Red jacketed cable
shall be used for -48 VDC connections and black jacketed cable shall be used for the return.
B. The Generex BACS battery management system shall be installed in accordance with this
Appendix and Section 2.3 of this Scope of Services. The DIN Rail, Webmanager, DC/DC
Converter, and SPDs shall be mounted on the West Interior Wall in accordance with this
Appendix. The DIN rail shall be installed no more than 10” away from the ground halo at the
shelter and shall be grounded in accordance with manufacturer’s recommendations.
IP Address: 172.16.4.22
Subnet Mask: 255.255.254.0
Gateway: 172.16.4.19
TABLE H1 – MAJOR EQUIPMENT LIST
Model Number Description QTY.
M87-024-05009-R19ACLV Exide Battery 19" rack mount 1
AMGBACS 1001 24-2V Master Kit
Generex BACS management system including webmanager, C40 modules with temperature sensor, measuring cables, and bus cables
1
TCL 024-112DC TracoPower DC/DC Converter 1
DR21649 Atlantic Scientific 17.5” DIN Rail 1
ZB24540 Atlantic Scientific Ethernet SPD 2
67
G:\FDOTGC\Battery Replacement\I-10 Replacement 2013\Appendix A\FigH1_ChipleyDOT_ShelterFloorPlan_20050401.vsd07/19/13
Scale: 1/2" = 1'-0"
Woo
den
She
lfw
/ Dra
wer
MAS Call Box Base Station Rack (FR1)
-48 VDCPower
Distribution Rack
Channel Bank Rack (FR6)
ASN / DACCRack (FR5)
DVM6-45MW TerminalRack (FR2)
DVM6-45MW TerminalRack (FR3)
FDOT 47 MHzGE MASTRIIBase Station
Passport 15000Rack (FR4)
Page H4 of 7
BPS 2000 Location
68
Figure H2Chipley DOT (3-3428)
-48 VDC Power Distribution RackG:\FDOTGC\Battery Replacement\I-10 Replacement 2013\Appendix A\FigH2_ChipleyDOT_-48VDCPowerDistributionRack_20051231.vsd
04/12/13
Empty
TWINPACKPLUS
25A
TWINPACKPLUS
25A
Scale: 1 1/4" = 1'-0"
1 2 9 10
4 3 8 11
5 6 7 12
20 19 18 13
21 22 17 14
24 23 16 15
Page H5 of 7
+
-
69
C:\Users\danielle morales.RCC-SEREGION\Desktop\I-10 Replacement 2013\Appendix A\FigH3_ChipleyDOT_InteriorWestWall_20050401.vsd04/15/13
Figure H3Chipley DOT (3-3428)
Interior West Wall
Scale: 1/2" = 1'-0"
Main Braker Panel2 of 2
VoIP
Main Braker Panel1 of 2
Alarm66 Block
BACS
WebManager
DC/DC
Converter
Ethernet
SPD
Page H6 of 7 70
Figure H4Chipley DOTBattery Plant
G:\FDOTGC\Battery Replacement\I-10 Replacement 2013\Appendix A\FigH4_Chipley_BatteryPlant.vsd04/12/13
Vendor Shall install new battery in existing rack.
Page H7 of 7 71
FLORIDA DEPARTMENT OF TRANSPORTATION
I-10 BATTERY PLANT REPLACEMENT
Appendix I – Marianna FHP
72
FLORIDA DEPARTMENT OF TRANSPORTATION
I-10 BATTERY PLANT REPLACEMENT
Page I2 of 7
Appendix I – Table of Contents – Figures and Drawings
Figure I1 – Marianna FHP Shelter Floor Plan ........................................................... I5 of 7
Figure I2 – Marianna FHP -48VDC Power Distribution Rack Profile ......................... I6 of 7
Figure I3 – Marianna FHP Battery Plant Photo......................................................... I7 of 7
73
FLORIDA DEPARTMENT OF TRANSPORTATION
I-10 BATTERY PLANT REPLACEMENT
Page I3 of 7
Marianna FHP Site Requirements
The Vendor shall furnish and install the following equipment at the Marianna FHP site located at 3613 US-90, Marianna, FL.
A. One Exide Absolyte GP series battery plant model number M87-024-05005-R19AALV shall
be installed in accordance with this Appendix and Section 2.2 of this Scope of Services.
The new battery plant shall be installed in the same location as the removed battery plant.
The Vendor shall replace the existing cable with 1/0 AWG stranded. Red jacketed cable
shall be used for -48 VDC connections and black jacketed cable shall be used for the return.
B. The Generex BACS battery management system shall be installed in accordance with this
Appendix and Section 2.3 of this Scope of Services.
IP Address: 172.16.76.22
Subnet Mask: 255.255.254.0
Gateway: 172.16.76.19
C. One Eltek Flatpack2 Rectifier System shall be installed in accordance with this Appendix
and Section 2.4 of this Scope of Services. The new rectifier system shall be installed in the
same location as the removed rectifier system. The two rectifiers shall be wired to separate
20A double pole Square D circuit breakers appropriate for the Square D model
QO140L200G load center. The main load center circuit breakers shall be furnished and
installed by the Vendor. All wiring shall be new and installed. Conduit may be reused.
IP Address: 172.16.76.20
Subnet Mask: 255.255.254.0
Gateway: 172.16.76.19
74
FLORIDA DEPARTMENT OF TRANSPORTATION
I-10 BATTERY PLANT REPLACEMENT
Page I4 of 7
TABLE I1 – MAJOR EQUIPMENT LIST
Model Number Description QTY.
M87-024-05005-R19AALV Exide Battery 19" rack mount 1
AMGBACS 1001 24-2V Master Kit
Generex BACS management system including webmanager, C40 modules with temperature sensor, measuring cables, and bus cables
1
TCL 024-112DC TracoPower DC/DC Converter 1
DR 24500 Atlantic Scientific DIN Rail to Mount BACS Webmanager
1
Q4820N-F19DB01-VC Integrated Power System 1
225840 Flatpack2 FP2-48/150A 2B 4L LVBD 2AC
1
502666 100A Battery Disconnect breaker 1
502658 35A Circuit breaker 1
241115.105 Flatpack2 Rectifier 2
236408 Flatpack2 Blind Panels 2
507173 LUG, #1AWG, 2 hole 2
LG1D2A8A110 LUG,DH, 5/8" SP,1/4 STUD, 2/0AWG 2
ZB24540 Atlantic Scientific Ethernet SPD 4
75
Forestry Base
StationCB + NMS Rack ER-6
47 MHz Repeater
47 MHz Base Station
DVM6-45 MW
Repeater Rack ER-2
MACBS ER-1
G:\FDOTGC\Battery Replacement\I-10 Replacement 2013\Appendix A\FigI1_MariannaFHP_ShelterFloorPlan_20110524.vsd07/19/13
Scale: 3/8" = 1'-0"
-48V DCBattery Plant
Duplexer
Page I5 of 7
BPS 2000 Location
76
Scale: 1 1/4" = 1'-0"
Figure I2Marianna FHP
-48VDC Power Distribution RackG:\FDOTGC\Battery Replacement\I-10 Replacement 2013\Appendix A\FigI2_MariannaFHP-PwrPlantRack_20130724.vsd
07/24/13
Absolyte Battery Bank
Absolyte Battery Bank
Absolyte Battery Bank
Absolyte Battery Bank81 9 16 17 24
72 10 15 18 23
63 11 14 19 22
54 12 13 20 21
+-
Page I6 of 7
BACS
WebManager
DC/DC Converter
PCP -48 VDC Power Systems
2 RU Panel
Smart Pack BATT LOAD
Flatpack2
Rectifier System
77
Figure I3Marianna FHPBattery Plant
G:\FDOTGC\Battery Replacement\I-10 Replacement 2013\Appendix A\FigI3_Marianna_BatteryPlant.vsd04/12/13
Vendor Shall install new battery in existing rack.
Page I7 of 7 78
FLORIDA DEPARTMENT OF TRANSPORTATION
I-10 BATTERY PLANT REPLACEMENT
Appendix J – Sneads Weigh Station
79
FLORIDA DEPARTMENT OF TRANSPORTATION
I-10 BATTERY PLANT REPLACEMENT
Page J2 of 6
Appendix J – Table of Contents – Figures and Drawings
Figure J1 – Sneads Weigh Station Shelter Floor Plan .............................................. J4 of 6
Figure J2 – Sneads Weigh Station -48VDC Power Distribution Rack Profile ............ J5 of 6
Figure J3 – Sneads Weigh Station Battery Plant Photo ............................................ J6 of 6
80
FLORIDA DEPARTMENT OF TRANSPORTATION
I-10 BATTERY PLANT REPLACEMENT
Page J3 of 6
Sneads Weigh Station Site Requirements
The Vendor shall furnish and install the following equipment at the Sneads Weigh Station site located 2 miles west of SR-286 and I-10 at East Bound side of weigh station.
A. One Exide Absolyte GP series battery plant model number M87-024-05005-R19AALV shall
be installed in accordance with this Appendix and Section 2.2 of this Scope of Services.
The new battery plant shall be installed in the same location as the removed battery plant.
The Vendor shall replace the existing cable with 1/0 AWG stranded. Red jacketed cable
shall be used for -48 VDC connections and black jacketed cable shall be used for the return.
B. The Generex BACS battery management system shall be installed in accordance with this
Appendix and Section 2.3 of this Scope of Services.
IP Address: 172.16.74.22
Subnet Mask: 255.255.254.0
Gateway: 172.16.74.19
TABLE J1 – MAJOR EQUIPMENT LIST
Model Number Description QTY.
M87-024-05005-R19AALV Exide Battery 19" rack mount 1
AMGBACS 1001 24-2V Master Kit
Generex BACS management system including webmanager, C40 modules with temperature sensor, measuring cables, and bus cables
1
TCL 024-112DC TracoPower DC/DC Converter 1
DR 24500 Atlantic Scientific DIN Rail to Mount BACS Webmanager
1
ZB24540 Atlantic Scientific Ethernet SPD 2
81
G:\FDOTGC\Battery Replacement\I-10 Replacement 2013\Appendix A\FigJ1_Sneads-FloorPlanShelter-20061102.vsd
07/19/13
Scale: 1/2" = 1'-0"
-48 VDCDistribution
Rack
Channel Bank Rack QR-6
DVM6-45 MW Repeater
Rack QR-5
Page J4 of 6
BPS 2000 Location
82
Figure J2
Sneads Weigh Station (3-3510)
-48 VDC Power Distribution RackG:\FDOTGC\Battery Replacement\I-10 Replacement 2013\Appendix A\FigJ2_SneadsWeighStation_-48VDCPowerDistributionRack.vsd
04/12/13
EMPTY EMPTYTWINPACKPLUS
COVER PLATE
HI/LO DC ALARM PANEL
SSD2 PANEL
NAME TAG
COVER PLATE
CONNECTOR PLATE(CONNECTS ON BACK)
COVER PLATE
DIGITAL EQUALIZER
Scale: 1 1/4" = 1'-0"
BREAKER PANEL
Absolyte Battery Bank
Absolyte Battery Bank
Absolyte Battery Bank
Absolyte Battery Bank81 9 16 17 24
72 10 15 18 23
63 11 14 19 22
54 12 13 20 21
+-
Page J5 of 6
BACS
WebManager
DC/DC Converter
83
Figure J3Sneads Weigh Station
Battery PlantG:\FDOTGC\Battery Replacement\I-10 Replacement 2013\Appendix\FigJ3_SneadsWeighStation_BatteryPlant.vsd
03/12/13
Vendor Shall install new battery in existing rack.
Page J6 of 6 84
FLORIDA DEPARTMENT OF TRANSPORTATION
I-10 BATTERY PLANT REPLACEMENT
Appendix K – Aspalaga
85
FLORIDA DEPARTMENT OF TRANSPORTATION
I-10 BATTERY PLANT REPLACEMENT
Page K2 of 6
Appendix K – Table of Contents – Figures and Drawings
Figure K1 – Aspalaga Shelter Floor Plan ................................................................. K4 of 6
Figure K2 – Aspalaga -48VDC Power Distribution Rack Profile ............................... K5 of 6
Figure K3 – Aspalaga Battery Plant Photo ............................................................... K6 of 6
86
FLORIDA DEPARTMENT OF TRANSPORTATION
I-10 BATTERY PLANT REPLACEMENT
Page K3 of 6
Aspalaga Site Requirements
The Vendor shall furnish and install the following equipment at the Aspalaga site located 3.5 miles east of SR-286 and I-10 interchange at rest area (off east-bound on-ramp), Aspalaga, FL.
A. One Exide Absolyte GP series battery plant model number M87-024-05005-R19AALV shall
be installed in accordance with this Appendix and Section 2.2 of this Scope of Services.
The new battery plant shall be installed in the same location as the removed battery plant.
The Vendor shall replace the existing cable with 1/0 AWG stranded. Red jacketed cable
shall be used for -48 VDC connections and black jacketed cable shall be used for the return.
B. The Generex BACS battery management system shall be installed in accordance with this
Appendix and Section 2.3 of this Scope of Services.
IP Address: 172.16.72.22
Subnet Mask: 255.255.254.0
Gateway: 172.16.72.19
TABLE K1 – MAJOR EQUIPMENT LIST
Model Number Description QTY.
M87-024-05005-R19AALV Exide Battery 19" rack mount 1
AMGBACS 1001 24-2V Master Kit
Generex BACS management system including webmanager, C40 modules with temperature sensor, measuring cables, and bus cables
1
TCL 024-112DC TracoPower DC/DC Converter 1
DR 24500 Atlantic Scientific DIN Rail to Mount BACS Webmanager
1
ZB24540 Atlantic Scientific Ethernet SPD 2
87
CB/NMSRack
-48 VDCDistribution
Rack
MACBSEAST RACK
DVM6-45REPEATER
RACK
MACBSWESTRACK
BO
OK
CA
SE
+
+
+
Figure K1Aspalaga
Shelter Floor Plan
G:\FDOTGC\Battery Replacement\I-10 Replacement 2013\Appendix A\FigK1_Aspalaga_ShelterFloorPlan_20111228.vsd07/19/13
Page K4 of 6
BPS 2000 Location
88
Figure K2
Aspalaga (3-3426)
-48 VDC Power Distribution RackG:\FDOTGC\Battery Replacement\I-10 Replacement 2013\Appendix A\FigK2_Aspalaga_-48VDCPowerDistributionRack_20061002.vsd
04/12/13
Empty
TWIN
PACK
PLUS
25A
TWIN
PACK
PLUS
25A
Scale: 1 1/4" = 1'-0"
Absolyte Battery Bank
Absolyte Battery Bank
Absolyte Battery Bank
Absolyte Battery Bank81 9 16 17 24
72 10 15 18 23
63 11 14 19 22
54 12 13 20 21
+-
Page K5 of 6
BACS
WebManager
DC/DC Converter
89
Figure K3Aspalaga
Battery PlantG:\FDOTGC\Battery Replacement\I-10 Replacement 2013\Appendix\FigK3_Aspalaga_BatteryPlant.vsd
03/12/13
Vendor Shall install new battery in
existing rack.
Page K6 of 6 90
FLORIDA DEPARTMENT OF TRANSPORTATION
I-10 BATTERY PLANT REPLACEMENT
Appendix L – Quincy FHP
91
FLORIDA DEPARTMENT OF TRANSPORTATION
I-10 BATTERY PLANT REPLACEMENT
Page L2 of 7
Appendix L – Table of Contents – Figures and Drawings
Figure L1 – Quincy FHP Shelter Floor Plan ............................................................. L5 of 7
Figure L2 – Quincy FHP -48VDC Power Distribution Rack Profile............................ L6 of 7
Figure L3 – Quincy FHP Battery Plant Photo ........................................................... L7 of 7
92
FLORIDA DEPARTMENT OF TRANSPORTATION
I-10 BATTERY PLANT REPLACEMENT
Page L3 of 7
Quincy FHP Site Requirements
The Vendor shall furnish and install the following equipment at the Quincy FHP site located at 18290 US-90, Quincy, FL.
A. One Exide Absolyte GP series battery plant model number M87-024-05005-R19AALV shall
be installed in accordance with this Appendix and Section 2.2 of this Scope of Services.
The new battery plant shall be installed in the same location as the removed battery plant.
The Vendor shall replace the existing cable with 1/0 AWG stranded. Red jacketed cable
shall be used for -48 VDC connections and black jacketed cable shall be used for the return.
B. The Generex BACS battery management system shall be installed in accordance with this
Appendix and Section 2.3 of this Scope of Services.
IP Address: 172.16.70.22
Subnet Mask: 255.255.254.0
Gateway: 172.16.70.19
C. One Eltek Flatpack2 Rectifier System shall be installed in accordance with this Appendix
and Section 2.4 of this Scope of Services. The new distribution center shall be installed in
the same location as the removed distribution center. The two rectifiers shall be wired to
separate 20A double pole Square D circuit breakers appropriate for the Square D model
QO140L200G load center. The main load center circuit breakers shall be furnished and
installed by the Vendor. All wiring shall be new and installed. Conduit may be reused.
IP Address: 172.16.70.20
Subnet Mask: 255.255.254.0
Gateway: 172.16.70.19
93
FLORIDA DEPARTMENT OF TRANSPORTATION
I-10 BATTERY PLANT REPLACEMENT
Page L4 of 7
TABLE L1 – MAJOR EQUIPMENT LIST
Model Number Description QTY.
M87-024-05005-R19AALV Exide Battery 19" rack mount 1
AMGBACS 1001 24-2V Master Kit
Generex BACS management system including webmanager, C40 modules with temperature sensor, measuring cables, and bus cables
1
TCL 024-112DC TracoPower DC/DC Converter 1
DR 24500 Atlantic Scientific DIN Rail to Mount BACS Webmanager
1
Q4820N-F19DB01-VC Integrated Power System 1
225840 Flatpack2 FP2-48/150A 2B 4L LVBD 2AC
1
502666 100A Battery Disconnect breaker 1
502658 35A Circuit breaker 1
241115.105 Flatpack2 Rectifier 2
236408 Flatpack2 Blind Panels 2
507173 LUG, #1AWG, 2 hole 2
LG1D2A8A110 LUG,DH, 5/8" SP,1/4 STUD, 2/0AWG 2
ZB24540 Atlantic Scientific Ethernet SPD 4
94
48V DCDistribution
Rack
DOF159 MHz
Base Station
Channel Bank
Rack CR-5
FHPFilter
Duplexer
FHP Tx/Rx #1Motorola
FHP Tx/Rx #2Motorola
DVM6-45 MW
Repeater Rack CR-2
MAS Call Box Base Station
Rack CR-1
G:\FDOTGC\Battery Replacement\I-10 Replacement 2013\Appendix A\FigL1_QuincyFHP_ShelterFloorPlan_20040422.vsd07/19/13
Figure L1Quincy FHP (3-3425)
Shelter Floor Plan
Scale: 3/8" = 1'-0"
RWIS Rack
Page L5 of 7
BPS 2000 Location
95
Scale: 1 1/4" = 1'-0"
Figure L2Quincy FHP
-48VDC Power Distribution RackG:\FDOTGC\Battery Replacement\I-10 Replacement 2013\Appendix A\FigL2_QuincyFHP-PwrPlantRack_20130723.vsd
07/24/13
Absolyte Battery Bank
Absolyte Battery Bank
Absolyte Battery Bank
Absolyte Battery Bank81 9 16 17 24
72 10 15 18 23
63 11 14 19 22
54 12 13 20 21
+-
Page L6 of 7
BACS
WebManager
DC/DC Converter
PCP -48 VDC Power Systems
2 RU Panel
Smart Pack BATT LOAD
Flatpack2
Rectifier System
96