GAMMASTONE FIRE TEST REPORT SCOPE OF WORK NFPA 285 TESTING ON EXTERIOR NON-LOAD-BEARING WALL ASSEMBLY CONTINING GAMMASTONE NATURAL AIR COMPOSITE PANEL REPORT NUMBER H4215.01-121-24-R1 TEST DATE(S) 09/22/17
ISSUE DATE REVISION DATE 10/20/17 10/08/19 RECORD RETENTION END DATE 09/22/21 PAGES 51 DOCUMENT CONTROL NUMBER ATI 00587 (07/24/17) RT-R-AMER-Test-2781 © 2017 INTERTEK
130 Derry Court York, Pennsylvania 17406
Telephone: 717-764-7700
Facsimile: 717-764-4129 www.intertek.com/building
TEST REPORT FOR GAMMASTONE Report No.: H4215.01-121-24-R1 Date: 10/20/17 Revision Date: 10/08/19
This report is for the exclusive use of Intertek's Client and is provided pursuant to the agreement between Intertek and its Client. Intertek's responsibility and liability are limited to the terms and conditions of the agreement. Intertek assumes no liability to any party, other than to the Client in accordance with the agreement, for any loss, expense or damage occasioned by the use of this report. Only the Client is authorized to permit copying or distribution of this report and then only in its entirety. Any use of the Intertek name or one of its marks for the sale or advertisement of the tested material, product or service must first be approved in writing by Intertek. The observations and test results in this report are relevant only to the sample(s) tested. This report by itself does not imply that the material, product, or service is or has ever been under an Intertek certification program.
Version: 07/24/17 Page 2 of 51 RT-R-AMER-Test-2781
REPORT ISSUED TO GAMMASTONE Via Flaminia 148 00068 Rignano Flaminio Rome, Italy SECTION 1 SCOPE Intertek Building & Construction (B&C) was contracted by GammaStone, Via Flaminia 148 00068 Rignano Flaminio Rome, Italy to evaluate the flame propagation characteristics of an exterior, non-load-bearing wall assembly containing GammaStone Natural Air Composite Panel. Testing was conducted at the Intertek B&C test facility in York, PA Results obtained are tested values and were secured by using the designated test method(s). A summary of test results and the complete graphical test data is reported herein. This report does not constitute certification of this product nor an opinion or endorsement by this laboratory. SECTION 2 SUMMARY OF TEST RESULTS Wall System: Exterior Non-load-bearing Wall Assembly Combustible Components: Carlisle Barritech™ VP, 2 in. thick Roxal comfort board, GammaStone Natural Air Composite panel NFPA 285 Test Results The assembly described and tested in this report did meet the Conditions of Acceptance of NFPA 285. Construction of the full assembly is summarized in Section 7 of this test report. For INTERTEK B&C:
COMPLETED BY: Scott Gingrich REVIEWED BY: Ethan Grove
TITLE:
Senior Technician – Fire Testing TITLE: Manager – Fire Testing
SIGNATURE:
SIGNATURE:
DATE: 10/08/19 DATE: 10/08/19 sdg:ddr
130 Derry Court York, Pennsylvania 17406
Telephone: 717-764-7700
Facsimile: 717-764-4129 www.intertek.com/building
TEST REPORT FOR GAMMASTONE Report No.: H4215.01-121-24-R1 Date: 10/20/17 Revision Date: 10/08/19
Version: 07/24/17 Page 3 of 51 RT-R-AMER-Test-2781
SECTION 3 TEST METHOD The assembly was evaluated in accordance with the following:
NFPA 285-12, Standard Fire Test Method for Evaluation of Fire Propagation Characteristics of Exterior Non-Load-Bearing Wall Assemblies Containing Combustible Components
ASTM C1396/C1396M-14a, Standard Specification for Gypsum Board
ASTM C1177/C1177M-13, Standard Specification for Glass Mat Gypsum Substrate for Use as Sheathing
SECTION 4 MATERIAL SOURCE/INSTALLATION The components of the test assembly were provided by the client except for the core wall components that were acquired and assembled by Intertek B&C personnel. SECTION 5 LIST OF OFFICIAL OBSERVERS
NAME COMPANY
Luca Pietrantuono GammaStone
Gabriele Girolami GammaStone
Scott Gingrich Intertek B&C
Tim Feltman Intertek B&C
Mark Dluzeski Intertek B&C
SECTION 6 TEST PROCEDURE The wall assembly was instrumented with thermocouples (TCs) in accordance with figures 6.1(a) and 6.1(b) of NFPA 285 test method. 18-gauge Type “K” TCs were used in the burn room and 20-gauge Type “K” was used on exterior façade and cavity air space. The window burner was positioned in the center of the opening and 3 in. off the exterior face of the wall assembly. Testing was performed on 09/22/2017 in accordance with NFPA 285 test method. Ambient conditions were 75°F and 68% relative humidity. An anemometer was used to verify airflow across test assembly was less than 4 ft./sec as specified in the test method. Video recording, digital photographs, visual observations, and data collection were performed prior, during, and after testing was completed. Temperature data was recorded every 15 seconds. The test was
130 Derry Court York, Pennsylvania 17406
Telephone: 717-764-7700
Facsimile: 717-764-4129 www.intertek.com/building
TEST REPORT FOR GAMMASTONE Report No.: H4215.01-121-24-R1 Date: 10/20/17 Revision Date: 10/08/19
Version: 07/24/17 Page 4 of 51 RT-R-AMER-Test-2781
performed at 09:46 AM with the burners on for 30 minutes. All observations are recorded in the table located in Section 8. SECTION 6 (Continued) TEST PROCEDURE The apparatus is considered to be under calibrated conditions when the time average temperatures and the time average heat flux readings obtained for a calibration wall match the requirements of Table 8.1.6 of NFPA 285. Calibration was performed on February 15, 2017 with natural gas as the fuel source and the window burner placed 3 inches from the exterior surface of the assembly. Table 6.1 of this section shows the average burner flow and heat flux. Table 6.2 shows the time average temperatures obtained during the calibration test. Table 6.1 Average Burner Output Information
TIME INTERVAL (MIN:SEC)
ROOM BURNER (SCFM)
WINDOW BURNER (SCFM)
2 FT FLUX (W/cm²)
3 FT FLUX (W/cm²)
4 FT FLUX (W/cm²)
0:00-5:00 35.4 0 1.1 0.9 0.8
5:00-10:00 35.5 4 2 1.8 1.7
10:00-15:00 43.8 5.6 2.7 2.6 2.3
15:00-20:00 43.6 8 2.9 2.8 2.8
20:00-25:00 43.6 11 3.1 3 2.8
25:00-30:00 47.3 15.6 3.6 3.5 3.5
Table 6.2 Average Time Temperature Values for Calibration
THERMOCOUPLE LOCATIONS
TIME INTERVAL (MIN:SEC)
BURN ROOM (°F)
INT. WALL (°F)
1FT (°F)
2FT (°F)
3FT (°F)
4FT (°F)
5FT (°F)
6FT (°F)
0:00-5:00 1100 1033 633 756 679 610 560 484
5:00-10:00 1301 1260 829 1002 972 933 877 780
10:00-15:00 1466 1431 981 1129 1130 1070 1008 905
15:00-20:00 1512 1485 1009 1169 1181 1145 1107 1012
20:00-25:00 1536 1511 1043 1178 1202 1202 1162 1071
25:00-30:00 1605 1578 1090 1252 1302 1305 1236 1152
130 Derry Court York, Pennsylvania 17406
Telephone: 717-764-7700
Facsimile: 717-764-4129 www.intertek.com/building
TEST REPORT FOR GAMMASTONE Report No.: H4215.01-121-24-R1 Date: 10/20/17 Revision Date: 10/08/19
Version: 07/24/17 Page 5 of 51 RT-R-AMER-Test-2781
SECTION 7 TEST ASSEMBLY DESCRIPTION Interior Cladding
The full interior surface of the wall assembly was clad with 5/8 in. thick National Gypsum Gold
Bond® Fire-Shield® gypsum board meeting the requirements of ASTM C1396. The gypsum board
was fastened to the wall framing with #6 x 1-1/4 in. long, bugle head, self-drilling screws with a
nominal spacing of 8 in. around the board perimeter and 12 in. in the field. Drywall orientation
on the burn floor consisted of four pieces of gypsum board fastened to the core wall, with the run
edge running parallel with the framing and the cut edge perpendicular to the framing. Drywall
orientation on the second floor consisted of vertically oriented boards with the run edge running
parallel with the framing and the cut edge perpendicular to the framing. Drywall orientation for
the areas above the top support angle and below the bottom support angle consisted of boards
that were oriented with the run edge perpendicular with the framing. All joints were taped with
USG Sheetrock® Brand paper joint tape and spackled with USG Sheetrock® Brand joint compound.
All fastener heads were spackled with USG Sheetrock® Brand joint compound.
Framing
The core wall was consisted of 18 ft. long, 3-5/8 in. deep, 16 gauge galvanized steel studs fastened
to 14 ft. length, 3-5/8 in. deep, 16 gauge galvanized steel track every 16 inches on center. The
studs were connected to the track with one #6 x 1/2 in. long self-drilling, pan head fastener per
stud flange. Two additional 18 ft. long, 3-5/8 in. deep, 16 gauge studs were used as king studs for
the window opening jambs. Johns Manville MinWool® Safing pieces with a nominal density of 4.0
lb. /cu. ft. were installed per the manufacturer’s installation instructions to fit into each stud cavity
placed at the second story floor line. The safing length dimensions were no less than the
apparatus floor slab thickness of 8 in.
Exterior Sheathing
5/8 in. thick National Gypsum Gold Bond® eXP® exterior gypsum sheathing, meeting the
requirements of ASTM C1177, was placed horizontally across the full exterior surface of the
assembly. A vertical joint offset of 16 in. was utilized during installation. The gypsum sheathing
was fastened to the wall framing with #6 x 1-1/4 in. long, bugle head, self-drilling screws with a
nominal spacing of 8 in. around the board perimeter and 12 in. in the field.
130 Derry Court York, Pennsylvania 17406
Telephone: 717-764-7700
Facsimile: 717-764-4129 www.intertek.com/building
TEST REPORT FOR GAMMASTONE Report No.: H4215.01-121-24-R1 Date: 10/20/17 Revision Date: 10/08/19
Version: 07/24/17 Page 6 of 51 RT-R-AMER-Test-2781
SECTION 7 (Continued) TEST ASSEMBLY DESCRIPTION
Water-resistive Barrier
Carlisle Cav-Grip 3 was sprayed around the perimeter and on the surface of the window opening.
Carlisle 705FR-A flashing was applied around the window opening. The flashing was folded in
half. Half was on the exterior sheathing while the remaining haft covered the window opening.
Carlisle BarriBond Liquid Flashing and Detail Sealant was applied to all the exterior sheathing
joints. This sealant was tooled to cover and overlap the joints by 1/4 in. This sealant was added
to the corners of the window header and window sill at 1/4 in. bead. Carlisle Barritech™ VP was
roller applied to cover the entire surface of the exterior sheathing. This Air & Vapor barrier was
applied in two coats allowing each coat to dry firm between each. The coats were applied at a 30
wet mils thickness. Verification of the thickness was checked during the application.
Window Opening
A 78 in. wide x 30 in. tall window opening was made from 20 gauge galvanized steel track. The
opening was centered on the vertical centerline of the wall assembly with the finished sill located
30 in. above the first story floor line. The steel track sections were mechanically fastened with
#6 x 1/2 in. long self-drilling, pan head fasteners at each corner. Upon the completion of the
exterior sheathing, Carlisle Cav-Grip 3 was sprayed around the perimeter and on the surface of
the window opening. Carlisle 705FR-A flashing was applied around the window opening. The
flashing was folded in half. Half was on the exterior sheathing while the remaining haft covered
the window opening. Carlisle BarriBond Liquid Flashing and Detail Sealant was applied to the
corners of the window header and window sill at 1/4 in. bead.
Exterior Insulation
2 in. thick 24 in. x 48 in. Roxul™ ComfortBoard 80 was used as the exterior insulation. The
insulation was friction fit over the GammaStone installed aluminium clips. The insulation
covered the entire exterior surface.
130 Derry Court York, Pennsylvania 17406
Telephone: 717-764-7700
Facsimile: 717-764-4129 www.intertek.com/building
TEST REPORT FOR GAMMASTONE Report No.: H4215.01-121-24-R1 Date: 10/20/17 Revision Date: 10/08/19
Version: 07/24/17 Page 7 of 51 RT-R-AMER-Test-2781
SECTION 7 (Continued) TEST ASSEMBLY DESCRIPTION
Exterior Cladding
Aluminium clips were the first step to install the exterior cladding to the assembly. These had a 2
in. leg, which was used to secure the clip to the core wall and a 4 in. leg that a vertical aluminium
T-profile attached to. These clips were secured to the core wall at locations determined by the
drawing referenced in Section 14. All of these locations were on a vertical stud. These clips used
a #12 x 1-1/2 in. long self-drilling hex head fastener. After the clips were installed the insulation
was friction fit into place then vertical aluminium T-profile was attached to the clips using 1 in.
long truss head self-drilling #8 fasteners were used to secure the T-profile to each clip. The
T-profile was 2 in. deep x 2-3/8 in. wide. Once all the vertical T-profiles were mounted horizontal
panel rails were then mounted to the vertical T-profiles. The panel attachment rails were placed
on the vertical T-profiles as per the drawings in Section 14 using the #8-1 in. long truss head
self-drilling fasteners to secure the rails to the vertical T’s. Once the rails were all mounted the
panels were then mounted to the panel rails. The panels were factory installed with Aluminum
rails that fit into the panel rails on the vertical T-profiles. The panels maintained a 3mm (± 2mm)
open joint between each panel interstation during installation.
SECTION 8 TEST OBSERVATIONS
TIME (Min:Sec)
OBSERVATIONS
00:00 Ignition of room burner.
01:42 Interior gypsum ignition.
02:20 Window header flashing warping.
05:00 Ignition of window opening burner.
08:01 Ignition at the window header.
10:44 Smoke from 5 ft. at panel joint.
16:39 Panel cracks above the window header.
16:49 Flames emitting from the surface of the exterior face of the assembly reach a height of 4 ft. above the top of the window opening.
23:30 Panel face above the window opening header falls from assembly.
30:00 Burners Extinguished. Post-test 10-minute observation period begins.
30:01 Flames continue to emit above the window header.
34:00 Flames stop emitting from surface.
40:00 Post-test 10-minute observation period ends; test concluded.
130 Derry Court York, Pennsylvania 17406
Telephone: 717-764-7700
Facsimile: 717-764-4129 www.intertek.com/building
TEST REPORT FOR GAMMASTONE Report No.: H4215.01-121-24-R1 Date: 10/20/17 Revision Date: 10/08/19
Version: 07/24/17 Page 8 of 51 RT-R-AMER-Test-2781
SECTION 9 TEST RESULTS
TEST REQUIREMENTS TEST RESULTS PASS/FAIL
Flames did not reach 10 ft. above the window opening header.
Flames did not reach 10 ft. above the window opening header.
PASS
Flames did not reach a lateral distance of 5 ft. from the vertical centerline.
Flames did not reach a lateral distance of 5 ft. from the vertical centerline.
PASS
Flames did not propagate beyond the limits of the first story test room.
Flames did not propagate beyond the limits of the first story test room.
PASS
No visible flaming in the second story test room
No visible flaming in the second story test room.
PASS
TC’s 11 and 14-17 (1000°F limit)
TC’s 11 and 14-17 did not exceed their 1000ᵒF limit.
PASS
TC’s 18-19, 28, and 31-40 (1000°F limit)
TC’s 18-19, 28, and 31-40 did not exceed their 1000ᵒF limit.
PASS
TC’s 49-54 (500°F above ambient)
TC’s 49-54 did not exceed 500ᵒF above their ambient temperatures.
PASS
130 Derry Court York, Pennsylvania 17406
Telephone: 717-764-7700
Facsimile: 717-764-4129 www.intertek.com/building
TEST REPORT FOR GAMMASTONE Report No.: H4215.01-121-24-R1 Date: 10/20/17 Revision Date: 10/08/19
Version: 07/24/17 Page 9 of 51 RT-R-AMER-Test-2781
SECTION 10 SKETCH OF EXTERIOR CLADDING BURN PATTERN
130 Derry Court York, Pennsylvania 17406
Telephone: 717-764-7700
Facsimile: 717-764-4129 www.intertek.com/building
TEST REPORT FOR GAMMASTONE Report No.: H4215.01-121-24-R1 Date: 10/20/17 Revision Date: 10/08/19
Version: 07/24/17 Page 10 of 51 RT-R-AMER-Test-2781
SECTION 11 PHOTOGRAPHS
Photo No. 1
Core Wall, Exterior Gypsum, and Joint Sealant Installed
Photo No. 2
AVB Installed
130 Derry Court York, Pennsylvania 17406
Telephone: 717-764-7700
Facsimile: 717-764-4129 www.intertek.com/building
TEST REPORT FOR GAMMASTONE Report No.: H4215.01-121-24-R1 Date: 10/20/17 Revision Date: 10/08/19
Version: 07/24/17 Page 11 of 51 RT-R-AMER-Test-2781
Photo No. 3
Aluminum Clips Installed
Photo No. 4
Insulation Installed
130 Derry Court York, Pennsylvania 17406
Telephone: 717-764-7700
Facsimile: 717-764-4129 www.intertek.com/building
TEST REPORT FOR GAMMASTONE Report No.: H4215.01-121-24-R1 Date: 10/20/17 Revision Date: 10/08/19
Version: 07/24/17 Page 12 of 51 RT-R-AMER-Test-2781
Photo No. 5
Aluminum Vertical T-Profiles Installed
Photo No. 6
Panel Rails Installed
130 Derry Court York, Pennsylvania 17406
Telephone: 717-764-7700
Facsimile: 717-764-4129 www.intertek.com/building
TEST REPORT FOR GAMMASTONE Report No.: H4215.01-121-24-R1 Date: 10/20/17 Revision Date: 10/08/19
Version: 07/24/17 Page 13 of 51 RT-R-AMER-Test-2781
Photo No. 7
Panel Rails Mounted to Panels (Typical)
Photo No. 8
Final Assembly
130 Derry Court York, Pennsylvania 17406
Telephone: 717-764-7700
Facsimile: 717-764-4129 www.intertek.com/building
TEST REPORT FOR GAMMASTONE Report No.: H4215.01-121-24-R1 Date: 10/20/17 Revision Date: 10/08/19
Version: 07/24/17 Page 14 of 51 RT-R-AMER-Test-2781
Photo No. 9
Panel Rails Interlocked after Install.
Photo No. 10
Burner Ignited (Start of Test)
130 Derry Court York, Pennsylvania 17406
Telephone: 717-764-7700
Facsimile: 717-764-4129 www.intertek.com/building
TEST REPORT FOR GAMMASTONE Report No.: H4215.01-121-24-R1 Date: 10/20/17 Revision Date: 10/08/19
Version: 07/24/17 Page 15 of 51 RT-R-AMER-Test-2781
Photo No. 11
Window Burner Ignited
Photo No. 12
Flame Propagation (During Test)
130 Derry Court York, Pennsylvania 17406
Telephone: 717-764-7700
Facsimile: 717-764-4129 www.intertek.com/building
TEST REPORT FOR GAMMASTONE Report No.: H4215.01-121-24-R1 Date: 10/20/17 Revision Date: 10/08/19
Version: 07/24/17 Page 16 of 51 RT-R-AMER-Test-2781
Photo No. 13
Burners Turned Off
Photo No. 14
Assembly Post-test
130 Derry Court York, Pennsylvania 17406
Telephone: 717-764-7700
Facsimile: 717-764-4129 www.intertek.com/building
TEST REPORT FOR GAMMASTONE Report No.: H4215.01-121-24-R1 Date: 10/20/17 Revision Date: 10/08/19
Version: 07/24/17 Page 17 of 51 RT-R-AMER-Test-2781
Photo No. 15
First and Second Floors Interior Surface
Photo No. 16
Exterior Panels Removed
130 Derry Court York, Pennsylvania 17406
Telephone: 717-764-7700
Facsimile: 717-764-4129 www.intertek.com/building
TEST REPORT FOR GAMMASTONE Report No.: H4215.01-121-24-R1 Date: 10/20/17 Revision Date: 10/08/19
Version: 07/24/17 Page 18 of 51 RT-R-AMER-Test-2781
Photo No. 17
Exterior Insulation Removed
Photo No. 18
Window Header Detail (Post-Test)
130 Derry Court York, Pennsylvania 17406
Telephone: 717-764-7700
Facsimile: 717-764-4129 www.intertek.com/building
TEST REPORT FOR GAMMASTONE Report No.: H4215.01-121-24-R1 Date: 10/20/17 Revision Date: 10/08/19
Version: 07/24/17 Page 19 of 51 RT-R-AMER-Test-2781
SECTION 12 GRAPHS
Graph No. 1
Assembly Centerline (Assembly Exterior)
Graph No. 2
Assembly Centerline (Assembly Exterior)
0
200
400
600
800
1000
1200
1400
1600
00:00 05:00 10:00 15:00 20:00 25:00 30:00
Tem
pe
ratu
re °
F
Time (Min:Sec)
T/C 1
T/C 2
T/C 3
T/C 4
T/C 5
T/C 6
0
200
400
600
800
1000
1200
1400
00:00 05:00 10:00 15:00 20:00 25:00 30:00
Tem
pe
ratu
re °
F
Time (Min:Sec)
T/C 7
T/C 8
T/C 9
T/C 10
T/C 12
T/C 13
130 Derry Court York, Pennsylvania 17406
Telephone: 717-764-7700
Facsimile: 717-764-4129 www.intertek.com/building
TEST REPORT FOR GAMMASTONE Report No.: H4215.01-121-24-R1 Date: 10/20/17 Revision Date: 10/08/19
Version: 07/24/17 Page 20 of 51 RT-R-AMER-Test-2781
Graph No. 3
10 ft. above the Window Opening Header (Assembly Exterior)
Graph No. 4
Assembly Centerline (Air Cavity Space)
0
100
200
300
400
500
600
700
800
900
00:00 05:00 10:00 15:00 20:00 25:00 30:00
Tem
pe
ratu
re °
F
Time (Min:Sec)
T/C 11
T/C 14
T/C 15
T/C 16
T/C 17
0
100
200
300
400
500
600
700
800
00:00 05:00 10:00 15:00 20:00 25:00 30:00
Tem
pe
ratu
re °
F
Time (Min:Sec)
T/C 20
T/C 21
T/C 22
T/C 23
T/C 24
130 Derry Court York, Pennsylvania 17406
Telephone: 717-764-7700
Facsimile: 717-764-4129 www.intertek.com/building
TEST REPORT FOR GAMMASTONE Report No.: H4215.01-121-24-R1 Date: 10/20/17 Revision Date: 10/08/19
Version: 07/24/17 Page 21 of 51 RT-R-AMER-Test-2781
Graph No. 5
Assembly Centerline (Air Cavity Space)
Graph No. 6
10 ft. above the Window Opening Header (Air Cavity Space)
0
100
200
300
400
500
600
700
00:00 05:00 10:00 15:00 20:00 25:00 30:00
Tem
pe
ratu
re °
F
Time (Min:Sec)
T/C 25
T/C 26
T/C 27
T/C 29
T/C 30
0
100
200
300
400
500
600
00:00 05:00 10:00 15:00 20:00 25:00 30:00
Tem
pe
ratu
re °
F
Time (Min:Sec)
T/C 28
T/C 34
T/C 35
T/C 39
T/C 40
130 Derry Court York, Pennsylvania 17406
Telephone: 717-764-7700
Facsimile: 717-764-4129 www.intertek.com/building
TEST REPORT FOR GAMMASTONE Report No.: H4215.01-121-24-R1 Date: 10/20/17 Revision Date: 10/08/19
Version: 07/24/17 Page 22 of 51 RT-R-AMER-Test-2781
Graph No. 7
Left of Assembly Centerline (Air Cavity Space)
Graph No. 8
Right of Assembly Centerline (Air Cavity Space)
0
50
100
150
200
250
00:00 05:00 10:00 15:00 20:00 25:00 30:00
Tem
pe
ratu
re °
F
Time (Min:Sec)
T/C 18
T/C 31
T/C 32
T/C 33
0
50
100
150
200
250
00:00 05:00 10:00 15:00 20:00 25:00 30:00
Tem
pe
ratu
re °
F
Time (Min:Sec)
T/C 19
T/C 36
T/C 37
T/C 38
130 Derry Court York, Pennsylvania 17406
Telephone: 717-764-7700
Facsimile: 717-764-4129 www.intertek.com/building
TEST REPORT FOR GAMMASTONE Report No.: H4215.01-121-24-R1 Date: 10/20/17 Revision Date: 10/08/19
Version: 07/24/17 Page 23 of 51 RT-R-AMER-Test-2781
Graph No. 9
First-story Test Room Ceiling
Graph No. 13
First-story Interior Wall Surface
0
500
1000
1500
2000
00:00 05:00 10:00 15:00 20:00 25:00 30:00
Tem
pe
ratu
re °
F
Time (Min:Sec)
Room T/C 41
Room T/C 42
Room T/C 43
Room T/C 44
Room T/C 45
0
200
400
600
800
1000
1200
1400
1600
1800
00:00 05:00 10:00 15:00 20:00 25:00 30:00
Tem
pe
ratu
re °
F
Time (Min:Sec)
T/C 46
T/ C 47
T/C 48
130 Derry Court York, Pennsylvania 17406
Telephone: 717-764-7700
Facsimile: 717-764-4129 www.intertek.com/building
TEST REPORT FOR GAMMASTONE Report No.: H4215.01-121-24-R1 Date: 10/20/17 Revision Date: 10/08/19
Version: 07/24/17 Page 24 of 51 RT-R-AMER-Test-2781
Graph No. 14
Second-story Interior Wall Surface
74
76
78
80
82
84
86
88
90
92
00:00 05:00 10:00 15:00 20:00 25:00 30:00
Tem
pe
ratu
re °
F
Time (Min:Sec)
T/C 49
T/C 50
T/C 51
T/C 52
T/C 53
T/C 54
130 Derry Court York, Pennsylvania 17406
Telephone: 717-764-7700
Facsimile: 717-764-4129 www.intertek.com/building
TEST REPORT FOR GAMMASTONE Report No.: H4215.01-121-24-R1 Date: 10/20/17 Revision Date: 10/08/19
Version: 07/24/17 Page 25 of 51 RT-R-AMER-Test-2781
SECTION 13 NUMERICAL DATA
TIME (Min:Sec)
ROOM GAS FLOW
WINDOW GAS FLOW
T/C 1 T/C 2 T/C 3 T/C 4 T/C 5 T/C 6 T/C 7 T/C 8 T/C 9
00:00 0.1 0.0 76 75 75 75 75 75 76 76 76
00:15 7.4 0.0 83 80 79 78 77 77 77 77 76
00:30 33.8 0.0 629 387 435 437 423 388 339 311 264
00:45 36.0 0.0 832 576 644 613 584 530 458 411 356
01:00 36.4 0.0 885 635 686 644 594 531 452 411 364
01:15 36.4 0.0 945 650 705 657 603 544 464 417 375
01:30 36.4 0.0 979 669 716 666 613 541 468 413 369
01:45 36.5 0.0 1006 685 739 707 652 586 500 451 386
02:00 36.5 0.0 1054 749 805 761 693 629 533 477 426
02:15 36.4 0.0 1060 746 802 746 666 591 507 453 405
02:30 36.5 0.0 1061 721 785 747 683 630 536 485 430
02:45 36.5 0.0 1083 715 776 749 701 633 540 480 432
03:00 36.4 0.0 1057 721 797 771 721 665 562 488 429
03:15 36.4 0.0 1067 723 793 765 708 652 558 499 433
03:30 36.5 0.0 1082 730 790 764 711 647 552 494 429
03:45 36.5 0.0 1051 745 811 748 684 617 535 483 437
04:00 36.4 0.0 1075 748 822 776 724 643 547 490 427
04:15 36.5 0.0 1100 741 825 788 728 661 582 517 445
04:30 36.4 0.0 1090 745 815 762 701 640 563 517 463
04:45 36.5 0.0 1089 740 816 783 733 666 584 537 475
05:00 36.5 0.0 1086 747 832 786 721 654 563 508 450
05:15 36.4 0.1 1100 739 820 785 728 667 579 517 453
05:30 36.4 1.0 1139 787 896 873 810 721 614 541 475
05:45 36.4 4.3 1167 794 916 966 963 958 836 746 650
06:00 36.5 4.3 1161 792 916 983 985 954 817 738 640
06:15 36.4 4.3 1166 810 948 1007 998 923 788 696 613
06:30 36.5 4.3 1164 850 1002 1045 999 912 772 683 607
06:45 36.5 4.4 1160 850 1008 1061 1029 953 809 705 608
07:00 36.4 4.4 1170 853 1010 1049 1008 950 808 708 609
07:15 36.5 4.4 1165 863 1011 1057 1016 933 795 686 608
07:30 36.4 4.4 1180 873 1014 1052 983 899 764 673 595
07:45 36.4 4.5 1158 876 1001 1051 1026 954 792 699 613
08:00 36.5 4.5 1164 883 1032 1103 1069 1005 855 754 667
08:15 36.5 4.5 1189 889 1050 1109 1037 965 810 713 622
08:30 36.5 4.4 1189 895 1055 1101 1041 931 795 705 613
08:45 36.5 4.3 1183 883 1013 1045 995 895 776 693 615
09:00 36.4 4.3 1174 899 1018 1070 1028 938 816 717 619
09:15 36.4 4.4 1175 898 1026 1054 1019 927 805 721 639
09:30 36.4 4.4 1179 900 1009 1030 979 892 768 691 610
09:45 36.5 4.4 1174 898 1020 1030 974 908 801 716 635
10:00 36.5 4.4 1196 901 1017 1039 986 892 760 676 593
130 Derry Court York, Pennsylvania 17406
Telephone: 717-764-7700
Facsimile: 717-764-4129 www.intertek.com/building
TEST REPORT FOR GAMMASTONE Report No.: H4215.01-121-24-R1 Date: 10/20/17 Revision Date: 10/08/19
Version: 07/24/17 Page 26 of 51 RT-R-AMER-Test-2781
TIME (Min:Sec)
ROOM GAS FLOW
WINDOW GAS FLOW
T/C 1 T/C 2 T/C 3 T/C 4 T/C 5 T/C 6 T/C 7 T/C 8 T/C 9
10:15 36.5 4.4 1178 885 1012 1046 1003 955 821 736 658
10:30 40.6 5.0 1228 932 1092 1129 1094 1009 884 789 686
10:45 44.8 5.7 1248 951 1106 1160 1110 1047 910 813 715
11:00 44.9 5.7 1274 947 1086 1118 1076 1006 875 785 681
11:15 44.9 5.8 1278 963 1104 1153 1108 1035 884 780 672
11:30 44.9 5.8 1282 982 1131 1161 1119 1040 906 809 703
11:45 44.9 5.8 1303 982 1116 1144 1103 1010 880 791 695
12:00 44.9 5.7 1319 991 1129 1175 1124 1050 905 811 707
12:15 44.9 5.7 1301 994 1135 1197 1169 1100 968 843 711
12:30 44.9 5.7 1329 997 1129 1171 1139 1067 923 810 704
12:45 44.9 5.7 1338 995 1124 1160 1119 1070 935 838 731
13:00 44.9 5.7 1328 991 1110 1173 1151 1081 957 862 753
13:15 44.9 5.7 1338 990 1117 1175 1142 1095 948 846 736
13:30 44.9 5.7 1330 992 1127 1193 1165 1105 956 854 742
13:45 44.9 5.8 1340 981 1105 1178 1155 1089 940 851 748
14:00 44.9 5.7 1320 982 1107 1178 1151 1095 959 864 758
14:15 44.9 5.7 1328 997 1123 1187 1152 1092 947 829 721
14:30 44.9 5.7 1334 1011 1135 1186 1140 1042 901 790 694
14:45 44.9 5.7 1334 1003 1111 1159 1110 1023 896 801 710
15:00 44.9 5.7 1333 979 1092 1156 1111 1049 936 833 732
15:15 44.9 5.7 1341 982 1108 1173 1135 1071 933 838 741
15:30 44.8 6.9 1347 995 1133 1224 1204 1133 1005 905 785
15:45 44.7 8.4 1357 1005 1165 1220 1182 1131 991 895 778
16:00 44.7 8.3 1359 1011 1152 1233 1192 1124 987 889 791
16:15 44.8 8.3 1354 1010 1158 1241 1206 1150 1017 928 822
16:30 44.7 8.3 1350 1023 1158 1245 1210 1163 1025 929 814
16:45 44.7 8.3 1361 1037 1172 1249 1230 1185 1026 912 804
17:00 44.7 8.2 1362 1300 1234 1243 1248 1202 1177 1007 849
17:15 44.7 8.3 1416 1476 1277 1257 1243 1261 1152 1056 925
17:30 44.7 8.3 1386 1463 1258 1242 1262 1324 1231 1144 1024
17:45 44.7 8.3 1407 1316 1220 1210 1213 1168 1215 1128 1002
18:00 44.8 8.3 1399 1274 1204 1170 1172 1124 1198 1050 904
18:15 44.8 8.3 1411 1263 1192 1177 1161 1094 1117 994 870
18:30 44.7 8.3 1408 1252 1203 1200 1145 1092 1059 940 827
18:45 44.8 8.4 1398 1258 1212 1215 1152 1094 1054 941 830
19:00 44.7 8.3 1414 1277 1240 1261 1173 1114 1061 956 833
19:15 44.8 8.3 1390 1269 1253 1256 1173 1127 1068 970 858
19:30 44.8 8.3 1405 1281 1269 1250 1175 1127 1074 973 836
19:45 44.8 8.3 1399 1288 1290 1300 1184 1145 1081 984 864
20:00 44.7 8.3 1424 1315 1300 1283 1168 1094 1056 944 814
20:15 44.7 8.4 1408 1304 1287 1270 1152 1071 1026 940 835
20:30 44.7 10.0 1425 1323 1323 1310 1186 1142 1070 982 868
20:45 44.7 11.2 1443 1324 1320 1303 1197 1169 1091 985 859
21:00 44.7 11.3 1410 1326 1333 1324 1211 1186 1084 987 868
21:15 44.7 11.2 1424 1336 1337 1337 1222 1169 1079 984 868
130 Derry Court York, Pennsylvania 17406
Telephone: 717-764-7700
Facsimile: 717-764-4129 www.intertek.com/building
TEST REPORT FOR GAMMASTONE Report No.: H4215.01-121-24-R1 Date: 10/20/17 Revision Date: 10/08/19
Version: 07/24/17 Page 27 of 51 RT-R-AMER-Test-2781
TIME (Min:Sec)
ROOM GAS FLOW
WINDOW GAS FLOW
T/C 1 T/C 2 T/C 3 T/C 4 T/C 5 T/C 6 T/C 7 T/C 8 T/C 9
21:30 44.7 11.2 1411 1347 1338 1374 1241 1205 1099 1004 895
21:45 44.8 11.2 1414 1340 1339 1370 1254 1214 1110 1005 879
22:00 44.8 11.3 1400 1346 1322 1350 1242 1221 1115 1013 901
22:15 44.6 11.3 1434 1358 1339 1355 1242 1202 1095 995 895
22:30 44.7 11.3 1415 1369 1338 1371 1241 1172 1071 982 851
22:45 44.7 11.3 1430 1394 1343 1367 1254 1224 1123 1018 894
23:00 44.7 11.3 1432 1403 1342 1364 1258 1206 1119 1026 914
23:15 44.7 11.3 1433 1399 1342 1386 1272 1246 1109 1003 886
23:30 44.7 11.3 1443 1419 1363 1365 1265 1218 1105 994 878
23:45 44.7 11.3 1288 1270 1299 1280 1187 1142 1018 907 805
24:00 44.7 11.3 1178 1102 1173 1215 1138 1155 1033 958 867
24:15 44.7 11.3 1170 1044 1172 1256 1172 1210 1068 980 865
24:30 44.7 11.3 1159 1022 1177 1262 1173 1174 1043 952 857
24:45 44.7 11.3 1145 1019 1182 1269 1180 1215 1077 974 864
25:00 44.6 11.3 1142 1018 1181 1246 1152 1158 1023 917 809
25:15 44.9 11.5 1198 1007 1154 1240 1146 1160 1031 928 822
25:30 47.0 14.3 1215 1031 1213 1305 1197 1213 1077 979 877
25:45 48.7 16.0 1230 1016 1204 1321 1226 1240 1073 942 835
26:00 48.8 16.0 1247 1031 1201 1326 1223 1278 1127 1024 902
26:15 48.5 16.0 1226 1008 1170 1302 1203 1261 1130 1047 924
26:30 48.6 16.1 1197 1029 1212 1322 1209 1248 1125 1025 911
26:45 48.7 16.0 1245 1040 1230 1311 1210 1228 1111 1014 901
27:00 48.5 16.0 1277 1045 1247 1358 1239 1293 1140 1026 909
27:15 48.5 16.0 1269 1025 1211 1340 1239 1271 1127 1011 895
27:30 48.5 16.0 1253 1044 1244 1356 1242 1254 1120 1027 918
27:45 48.6 16.0 1313 1052 1206 1348 1237 1244 1117 1035 914
28:00 48.6 16.0 1315 1039 1223 1355 1265 1277 1146 1049 932
28:15 48.7 16.1 1338 1044 1208 1343 1247 1273 1141 1046 932
28:30 48.5 16.0 1345 1053 1211 1340 1224 1261 1143 1057 946
28:45 48.5 16.0 1370 1055 1207 1328 1235 1278 1141 1054 948
29:00 48.6 16.1 1349 1062 1217 1352 1243 1292 1165 1087 982
29:15 48.5 16.1 1338 1053 1226 1356 1231 1238 1115 1022 915
29:30 48.5 16.0 1347 1053 1216 1337 1243 1285 1139 1046 929
29:45 48.5 16.1 1365 1046 1203 1306 1213 1261 1141 1059 957
30:00 48.5 16.0 1367 1055 1214 1353 1246 1308 1181 1078 950
130 Derry Court York, Pennsylvania 17406
Telephone: 717-764-7700
Facsimile: 717-764-4129 www.intertek.com/building
TEST REPORT FOR GAMMASTONE Report No.: H4215.01-121-24-R1 Date: 10/20/17 Revision Date: 10/08/19
Version: 07/24/17 Page 28 of 51 RT-R-AMER-Test-2781
TIME (Min:Sec)
T/C 10 T/C 11 T/C 12 T/C 13 T/C 14 T/C 15 T/C 16 T/C 17 T/C 18 T/C 19
00:00 76 76 76 75 75 74 75 75 75 75
00:15 77 77 76 75 76 74 75 75 75 75
00:30 261 237 224 211 93 160 180 99 75 75
00:45 339 297 275 262 106 200 219 121 75 75
01:00 356 319 295 280 119 211 216 118 75 75
01:15 367 326 304 284 122 216 231 112 76 75
01:30 357 315 294 276 119 208 228 121 76 75
01:45 377 330 305 284 123 220 225 125 77 75
02:00 422 371 338 311 118 221 222 119 77 75
02:15 397 356 330 308 128 232 223 129 77 75
02:30 403 358 334 319 127 228 240 135 77 75
02:45 417 365 335 315 123 244 229 125 78 76
03:00 420 370 344 328 129 225 243 124 78 76
03:15 417 372 348 331 126 221 251 120 78 76
03:30 415 364 341 320 125 223 253 126 78 76
03:45 426 382 355 334 124 224 253 127 78 76
04:00 409 364 335 317 126 235 235 124 79 76
04:15 418 376 349 329 118 209 247 126 79 76
04:30 448 392 363 340 119 214 241 126 79 77
04:45 460 403 372 349 115 213 257 126 79 77
05:00 443 390 359 343 118 232 253 127 80 77
05:15 442 394 366 346 117 213 243 126 80 77
05:30 465 413 385 363 129 280 299 140 80 77
05:45 620 534 487 452 134 292 293 140 80 77
06:00 612 537 488 456 123 284 299 133 81 78
06:15 588 517 471 448 128 302 296 137 81 78
06:30 589 518 465 437 117 302 314 150 81 78
06:45 567 493 438 415 124 326 318 147 82 78
07:00 569 497 454 421 126 298 303 136 82 79
07:15 584 517 472 441 127 297 318 143 82 79
07:30 564 501 460 435 128 316 330 135 83 79
07:45 582 515 468 440 125 311 320 137 83 79
08:00 631 553 504 463 127 292 315 141 84 80
08:15 582 515 465 439 135 315 322 150 84 80
08:30 579 510 464 433 141 341 330 147 85 80
08:45 584 512 466 435 146 336 335 158 86 81
09:00 587 516 461 434 142 332 299 149 87 81
09:15 608 536 484 446 139 316 314 151 87 82
09:30 584 521 467 436 156 333 317 151 88 82
09:45 614 549 494 455 155 348 308 142 89 83
10:00 562 507 466 431 152 344 326 148 90 83
10:15 631 561 504 471 152 334 317 144 90 84
10:30 635 562 515 472 162 334 336 148 91 84
10:45 684 599 536 487 166 347 339 143 92 85
11:00 642 565 516 480 167 360 347 153 93 85
11:15 628 553 505 459 166 344 344 151 94 86
130 Derry Court York, Pennsylvania 17406
Telephone: 717-764-7700
Facsimile: 717-764-4129 www.intertek.com/building
TEST REPORT FOR GAMMASTONE Report No.: H4215.01-121-24-R1 Date: 10/20/17 Revision Date: 10/08/19
Version: 07/24/17 Page 29 of 51 RT-R-AMER-Test-2781
TIME (Min:Sec)
T/C 10 T/C 11 T/C 12 T/C 13 T/C 14 T/C 15 T/C 16 T/C 17 T/C 18 T/C 19
11:30 646 572 514 479 167 362 360 149 95 87
11:45 643 571 518 474 164 364 341 145 96 87
12:00 666 580 521 475 163 369 346 147 96 88
12:15 651 571 513 475 182 362 381 159 97 89
12:30 674 584 524 472 170 354 375 162 98 90
12:45 666 576 527 476 158 372 370 160 99 90
13:00 712 611 554 504 161 372 349 159 100 91
13:15 693 608 539 492 163 358 370 158 100 92
13:30 696 612 548 506 157 359 361 153 101 92
13:45 699 624 572 534 158 354 394 162 102 93
14:00 703 612 552 508 158 353 369 166 103 94
14:15 670 587 542 507 162 367 365 163 103 94
14:30 659 592 539 488 170 365 353 167 104 95
14:45 654 583 525 481 173 359 375 168 104 96
15:00 672 590 531 485 175 362 356 168 105 96
15:15 691 608 557 513 179 377 368 164 106 97
15:30 744 656 589 541 186 360 387 154 106 98
15:45 704 615 563 529 183 398 387 170 107 98
16:00 748 658 592 545 184 372 362 165 108 99
16:15 771 686 624 574 184 380 385 159 108 99
16:30 777 678 611 554 178 362 390 161 109 100
16:45 769 673 607 550 181 365 383 149 110 100
17:00 760 673 609 553 182 367 403 170 112 101
17:15 854 738 659 586 173 396 402 165 115 102
17:30 909 811 722 663 168 408 408 183 117 102
17:45 870 764 673 618 173 400 375 161 120 103
18:00 803 695 620 568 174 380 400 176 123 103
18:15 783 696 617 563 177 391 405 158 125 104
18:30 732 653 586 547 185 393 387 158 127 104
18:45 759 676 600 544 181 381 391 165 129 105
19:00 750 657 587 538 182 375 390 156 130 105
19:15 775 699 625 568 166 376 357 156 132 106
19:30 765 685 615 565 169 388 394 166 135 106
19:45 788 703 632 567 166 374 394 164 137 106
20:00 745 665 603 547 179 368 400 164 139 107
20:15 757 677 610 558 181 383 424 177 141 108
20:30 798 711 635 581 183 380 405 173 142 109
20:45 790 702 634 585 192 390 374 170 144 110
21:00 781 699 635 579 174 399 403 168 145 110
21:15 783 691 617 565 175 398 400 166 146 110
21:30 818 735 656 601 174 400 400 178 147 111
21:45 802 721 649 586 172 401 395 172 148 111
22:00 823 728 656 597 178 389 408 178 150 111
22:15 815 734 654 583 175 411 379 178 151 111
22:30 765 685 621 572 174 431 411 181 152 111
22:45 802 710 623 563 172 417 411 177 153 111
130 Derry Court York, Pennsylvania 17406
Telephone: 717-764-7700
Facsimile: 717-764-4129 www.intertek.com/building
TEST REPORT FOR GAMMASTONE Report No.: H4215.01-121-24-R1 Date: 10/20/17 Revision Date: 10/08/19
Version: 07/24/17 Page 30 of 51 RT-R-AMER-Test-2781
TIME (Min:Sec)
T/C 10 T/C 11 T/C 12 T/C 13 T/C 14 T/C 15 T/C 16 T/C 17 T/C 18 T/C 19
23:00 835 747 666 610 174 416 412 175 155 112
23:15 804 714 638 570 173 397 406 176 156 112
23:30 797 715 642 591 176 428 404 177 157 112
23:45 740 665 592 544 196 446 410 190 158 112
24:00 811 726 645 598 185 452 428 184 158 110
24:15 816 722 642 596 179 442 435 179 159 109
24:30 797 714 632 576 173 457 443 174 159 108
24:45 801 727 651 604 178 461 447 190 160 107
25:00 766 703 638 602 176 472 443 191 161 106
25:15 773 703 624 586 172 479 441 176 162 106
25:30 823 749 657 620 180 506 453 192 163 106
25:45 777 700 634 591 184 531 478 201 164 106
26:00 849 761 686 638 201 480 470 191 165 106
26:15 891 804 704 657 190 479 480 187 166 106
26:30 860 773 691 643 200 483 485 194 167 106
26:45 842 744 664 630 197 509 486 192 169 106
27:00 850 762 685 652 191 488 453 207 170 106
27:15 838 757 675 640 189 486 476 200 171 107
27:30 883 806 732 687 187 463 472 192 173 107
27:45 854 762 678 627 194 490 472 189 174 107
28:00 882 796 708 668 206 492 462 197 175 107
28:15 880 784 709 662 205 505 479 190 177 108
28:30 893 802 726 677 207 492 455 189 178 108
28:45 877 787 698 658 206 489 445 190 178 108
29:00 936 841 753 703 214 484 440 198 180 109
29:15 867 787 707 668 221 477 462 184 181 109
29:30 892 815 731 696 222 457 476 195 182 109
29:45 888 801 720 684 213 480 457 196 183 110
30:00 882 794 719 671 206 498 459 197 184 110
130 Derry Court York, Pennsylvania 17406
Telephone: 717-764-7700
Facsimile: 717-764-4129 www.intertek.com/building
TEST REPORT FOR GAMMASTONE Report No.: H4215.01-121-24-R1 Date: 10/20/17 Revision Date: 10/08/19
Version: 07/24/17 Page 31 of 51 RT-R-AMER-Test-2781
TIME (Min:Sec)
T/C 20 T/C 21 T/C 22 T/C 23 T/C 24 T/C 25 T/C 26 T/C 27 T/C 28 T/C 29
00:00 75 75 75 74 74 74 75 75 75 75
00:15 75 75 75 74 74 74 75 75 75 75
00:30 75 75 92 84 81 87 83 84 81 80
00:45 79 78 115 97 91 97 92 94 92 89
01:00 85 82 126 103 96 102 97 98 96 94
01:15 87 83 131 108 100 105 100 101 99 96
01:30 88 85 136 110 102 108 104 103 101 99
01:45 91 87 142 114 105 110 106 106 104 102
02:00 93 89 147 120 110 115 110 110 107 105
02:15 93 89 152 123 114 119 113 113 109 108
02:30 94 90 152 123 114 120 116 115 112 109
02:45 91 88 157 129 120 125 120 118 114 112
03:00 90 88 158 129 120 127 121 120 116 114
03:15 90 88 161 133 124 128 123 121 116 114
03:30 90 89 161 132 124 128 124 122 118 116
03:45 89 89 162 132 123 129 125 123 119 116
04:00 90 89 164 133 125 129 126 124 120 117
04:15 90 89 163 133 125 130 127 125 122 119
04:30 92 92 160 131 124 131 128 125 122 119
04:45 93 92 161 131 124 131 129 126 123 120
05:00 94 94 157 130 123 129 128 126 123 121
05:15 94 94 162 131 123 130 128 127 124 122
05:30 96 95 166 134 126 131 130 129 125 123
05:45 99 96 174 137 128 136 133 132 129 126
06:00 100 98 183 141 131 138 136 134 131 128
06:15 101 100 183 140 131 140 137 137 133 131
06:30 103 101 191 143 135 142 140 140 136 133
06:45 108 104 196 148 137 144 141 140 137 134
07:00 112 106 202 151 138 146 143 143 140 136
07:15 118 110 207 153 141 146 144 144 140 138
07:30 124 116 208 156 145 149 145 145 142 139
07:45 126 117 214 160 146 153 148 148 144 142
08:00 129 120 219 160 148 153 149 148 145 143
08:15 133 124 218 162 151 154 150 150 147 145
08:30 184 170 228 182 175 184 170 170 163 159
08:45 202 185 233 190 183 194 179 178 172 167
09:00 208 192 237 194 186 194 182 180 174 170
09:15 219 199 242 199 193 202 188 186 179 176
09:30 220 197 240 200 193 204 191 189 183 180
09:45 216 197 238 199 191 201 190 186 181 179
10:00 222 203 241 204 197 206 193 190 185 182
10:15 225 204 240 207 197 207 196 193 187 185
10:30 235 210 247 211 202 212 199 197 191 189
10:45 272 242 262 232 222 229 212 209 202 197
11:00 285 254 272 240 233 241 223 219 211 207
11:15 308 272 285 250 243 251 232 227 219 214
130 Derry Court York, Pennsylvania 17406
Telephone: 717-764-7700
Facsimile: 717-764-4129 www.intertek.com/building
TEST REPORT FOR GAMMASTONE Report No.: H4215.01-121-24-R1 Date: 10/20/17 Revision Date: 10/08/19
Version: 07/24/17 Page 32 of 51 RT-R-AMER-Test-2781
TIME (Min:Sec)
T/C 20 T/C 21 T/C 22 T/C 23 T/C 24 T/C 25 T/C 26 T/C 27 T/C 28 T/C 29
11:30 310 276 289 255 247 255 237 231 224 218
11:45 303 266 285 251 246 256 239 233 226 223
12:00 302 270 286 253 246 256 240 234 227 224
12:15 306 274 287 257 251 259 243 237 230 226
12:30 284 257 279 246 240 251 239 234 228 225
12:45 274 250 274 243 239 249 238 233 228 225
13:00 264 241 270 239 235 247 237 233 228 226
13:15 258 235 268 238 237 249 238 235 230 228
13:30 261 236 267 237 235 248 238 237 232 231
13:45 261 235 267 238 235 249 239 238 234 233
14:00 265 237 500 240 238 252 241 241 236 236
14:15 264 235 500 238 235 252 242 241 237 237
14:30 263 235 500 238 236 250 241 241 237 237
14:45 267 237 500 238 235 249 241 240 237 237
15:00 268 234 500 234 232 246 239 239 236 236
15:15 269 235 500 233 230 244 237 238 235 236
15:30 271 238 500 235 230 242 236 237 235 235
15:45 276 244 500 239 233 246 239 240 238 238
16:00 283 251 500 246 239 251 242 245 242 242
16:15 298 264 500 257 248 261 250 251 249 247
16:30 313 278 500 267 256 269 258 258 255 253
16:45 323 289 500 275 264 279 265 264 261 259
17:00 322 294 500 344 330 350 314 316 309 299
17:15 348 326 500 427 388 393 353 348 338 323
17:30 389 359 500 463 417 421 381 370 358 344
17:45 417 387 500 488 440 440 404 389 377 364
18:00 440 408 500 482 448 455 419 405 393 381
18:15 463 436 500 480 460 470 427 412 398 384
18:30 484 457 500 482 471 481 436 420 404 389
18:45 499 474 500 489 482 492 444 428 413 398
19:00 510 487 500 491 481 496 448 433 417 403
19:15 522 498 500 496 488 503 454 439 423 409
19:30 533 510 500 500 497 510 460 444 428 413
19:45 541 519 500 503 502 513 465 448 433 418
20:00 551 525 500 501 499 510 465 448 432 418
20:15 555 530 500 503 500 510 467 450 435 421
20:30 566 539 500 505 501 512 470 453 438 424
20:45 566 543 500 511 504 514 472 457 442 428
21:00 575 553 500 519 507 514 474 458 444 430
21:15 580 559 500 526 513 514 477 461 446 432
21:30 589 565 500 543 525 520 483 466 450 436
21:45 595 576 500 560 537 530 493 474 458 444
22:00 610 591 500 572 548 539 503 481 465 451
22:15 617 601 500 576 554 547 511 489 473 459
22:30 626 611 500 581 561 555 519 499 481 466
22:45 634 618 500 589 567 561 525 505 487 472
130 Derry Court York, Pennsylvania 17406
Telephone: 717-764-7700
Facsimile: 717-764-4129 www.intertek.com/building
TEST REPORT FOR GAMMASTONE Report No.: H4215.01-121-24-R1 Date: 10/20/17 Revision Date: 10/08/19
Version: 07/24/17 Page 33 of 51 RT-R-AMER-Test-2781
TIME (Min:Sec)
T/C 20 T/C 21 T/C 22 T/C 23 T/C 24 T/C 25 T/C 26 T/C 27 T/C 28 T/C 29
23:00 640 627 500 599 573 570 531 511 494 478
23:15 648 634 500 611 581 577 538 517 500 483
23:30 656 641 500 617 585 584 544 522 506 490
23:45 650 638 500 605 575 579 542 520 504 490
24:00 632 619 500 594 566 568 536 513 497 484
24:15 617 608 500 585 560 562 532 508 495 483
24:30 607 601 500 585 557 562 533 509 496 483
24:45 602 594 697 583 557 563 533 509 495 483
25:00 596 589 500 581 558 562 532 510 496 484
25:15 592 584 500 576 555 560 532 509 496 484
25:30 592 583 500 575 558 563 533 510 497 485
25:45 595 585 500 573 558 565 535 512 499 486
26:00 595 588 500 575 560 567 536 514 500 486
26:15 598 592 500 589 567 571 539 517 503 490
26:30 600 598 500 604 573 575 544 520 507 493
26:45 604 602 500 604 572 580 547 523 509 495
27:00 607 605 500 617 581 587 552 528 514 499
27:15 612 609 500 620 581 590 555 531 517 503
27:30 610 608 500 620 583 592 557 534 519 505
27:45 612 613 500 649 599 605 565 542 527 512
28:00 613 616 500 653 601 610 569 546 531 515
28:15 615 619 500 642 596 609 570 547 532 517
28:30 619 621 500 644 600 614 573 551 536 521
28:45 623 626 500 655 611 619 578 555 540 524
29:00 629 632 500 654 606 622 580 559 543 526
29:15 632 636 500 650 607 625 582 560 544 529
29:30 635 639 500 660 613 631 587 565 548 533
29:45 638 645 500 668 616 641 594 573 555 539
30:00 646 654 500 667 619 645 596 576 558 541
130 Derry Court York, Pennsylvania 17406
Telephone: 717-764-7700
Facsimile: 717-764-4129 www.intertek.com/building
TEST REPORT FOR GAMMASTONE Report No.: H4215.01-121-24-R1 Date: 10/20/17 Revision Date: 10/08/19
Version: 07/24/17 Page 34 of 51 RT-R-AMER-Test-2781
TIME (Min:Sec)
T/C 30 T/C 31 T/C 32 T/C 33 T/C 34 T/C 35 T/C 36 T/C 37 T/C 38 T/C 39
00:00 75 75 74 74 74 74 75 76 74 76
00:15 75 75 74 74 74 74 75 76 74 76
00:30 78 75 74 74 74 74 75 76 75 76
00:45 85 75 73 75 75 76 75 75 76 77
01:00 90 75 74 76 76 78 76 75 76 77
01:15 93 75 74 76 76 79 76 75 77 78
01:30 95 75 74 77 77 80 76 75 77 79
01:45 98 76 74 77 77 81 77 76 78 79
02:00 100 76 74 78 78 82 77 76 78 80
02:15 102 76 74 79 79 83 78 77 79 80
02:30 104 76 74 79 80 85 78 77 79 81
02:45 107 76 74 80 80 86 78 78 79 81
03:00 108 77 74 80 81 87 78 79 80 82
03:15 109 77 75 81 82 87 79 80 80 82
03:30 110 77 75 81 82 88 79 81 80 83
03:45 111 77 75 81 83 89 79 82 81 83
04:00 112 77 75 81 83 90 80 82 81 83
04:15 114 77 75 82 84 91 80 83 81 84
04:30 115 78 76 82 84 92 80 84 82 84
04:45 115 78 76 82 85 92 80 85 82 84
05:00 116 78 76 82 85 93 81 86 82 85
05:15 117 78 76 83 86 93 81 86 83 85
05:30 118 78 76 83 86 94 81 87 83 86
05:45 121 79 77 83 87 95 81 88 84 87
06:00 123 79 77 84 88 96 82 89 84 87
06:15 125 79 77 84 89 97 82 91 85 88
06:30 127 80 77 85 89 98 82 92 85 89
06:45 128 80 78 85 90 99 83 93 85 90
07:00 130 80 78 86 91 100 83 94 86 90
07:15 132 81 78 86 91 101 83 95 86 91
07:30 133 81 78 87 92 102 84 96 87 92
07:45 136 81 79 87 93 103 84 97 87 92
08:00 137 82 79 88 93 104 84 99 88 93
08:15 139 82 79 88 94 105 84 100 88 94
08:30 150 83 80 89 96 109 85 100 90 95
08:45 157 83 80 91 98 112 87 101 91 97
09:00 160 84 80 92 99 114 87 102 92 98
09:15 165 85 81 93 101 116 88 102 93 100
09:30 170 85 81 94 103 118 89 103 94 102
09:45 171 86 81 94 104 119 89 104 95 103
10:00 174 87 82 95 105 121 90 105 96 104
10:15 176 87 82 96 106 122 90 106 97 105
10:30 180 88 83 97 107 124 91 107 97 107
10:45 186 88 83 98 109 126 92 108 98 108
11:00 194 89 83 99 111 130 93 109 100 110
11:15 200 90 83 101 113 133 93 110 101 112
130 Derry Court York, Pennsylvania 17406
Telephone: 717-764-7700
Facsimile: 717-764-4129 www.intertek.com/building
TEST REPORT FOR GAMMASTONE Report No.: H4215.01-121-24-R1 Date: 10/20/17 Revision Date: 10/08/19
Version: 07/24/17 Page 35 of 51 RT-R-AMER-Test-2781
TIME (Min:Sec)
T/C 30 T/C 31 T/C 32 T/C 33 T/C 34 T/C 35 T/C 36 T/C 37 T/C 38 T/C 39
11:30 205 91 84 102 115 135 94 111 102 114
11:45 211 92 84 103 117 138 96 112 104 116
12:00 213 92 85 104 119 139 96 112 105 118
12:15 216 93 85 105 120 141 97 114 105 119
12:30 216 94 86 106 121 142 98 115 106 121
12:45 218 94 86 107 122 144 99 117 107 122
13:00 219 95 87 108 123 144 99 118 108 123
13:15 221 96 87 109 125 146 100 119 109 125
13:30 225 96 88 109 126 147 101 120 110 126
13:45 227 97 88 110 127 149 102 120 111 128
14:00 230 98 89 112 129 151 103 121 113 129
14:15 232 98 89 112 130 152 104 121 114 131
14:30 234 99 89 113 131 153 105 122 114 132
14:45 234 99 90 114 132 155 106 123 116 134
15:00 234 100 90 115 133 156 106 123 117 135
15:15 234 100 90 115 134 157 107 124 117 136
15:30 234 101 91 116 134 157 107 125 118 137
15:45 236 102 91 118 135 159 108 126 119 139
16:00 239 102 92 119 137 161 109 126 120 140
16:15 243 103 92 120 139 163 109 126 121 141
16:30 249 104 93 122 141 166 110 127 123 143
16:45 254 104 94 124 143 168 112 127 124 145
17:00 284 106 95 126 148 179 114 126 127 149
17:15 304 107 96 130 154 189 116 125 130 155
17:30 322 110 97 134 161 197 118 124 133 160
17:45 340 112 98 138 167 207 119 124 136 165
18:00 357 114 99 143 173 216 121 123 139 169
18:15 361 116 101 146 177 221 123 122 142 174
18:30 366 118 101 150 181 226 125 120 146 180
18:45 372 120 102 154 186 231 127 119 150 185
19:00 379 122 103 157 190 234 129 118 153 189
19:15 384 123 103 160 193 239 130 117 156 193
19:30 389 125 104 164 197 245 131 117 159 197
19:45 394 127 104 167 201 251 133 116 161 201
20:00 396 129 104 171 204 258 134 115 164 205
20:15 398 130 104 174 207 264 136 115 166 209
20:30 400 131 104 176 210 268 137 115 169 212
20:45 404 132 105 179 213 272 138 115 171 215
21:00 406 133 105 181 216 275 139 114 173 218
21:15 408 134 104 183 218 279 141 114 175 221
21:30 413 135 105 184 221 283 141 113 177 224
21:45 421 136 104 186 224 286 142 113 179 226
22:00 428 137 105 187 227 289 144 113 181 229
22:15 435 138 105 189 230 292 145 113 183 232
22:30 442 139 105 190 233 296 147 113 185 235
22:45 448 140 104 192 235 300 148 113 187 238
130 Derry Court York, Pennsylvania 17406
Telephone: 717-764-7700
Facsimile: 717-764-4129 www.intertek.com/building
TEST REPORT FOR GAMMASTONE Report No.: H4215.01-121-24-R1 Date: 10/20/17 Revision Date: 10/08/19
Version: 07/24/17 Page 36 of 51 RT-R-AMER-Test-2781
TIME (Min:Sec)
T/C 30 T/C 31 T/C 32 T/C 33 T/C 34 T/C 35 T/C 36 T/C 37 T/C 38 T/C 39
23:00 453 141 104 194 238 304 149 112 189 241
23:15 458 142 104 196 241 307 150 113 191 244
23:30 462 144 103 198 244 310 152 114 192 247
23:45 463 144 101 200 246 311 152 115 193 249
24:00 460 144 98 200 248 311 152 115 193 250
24:15 461 145 97 201 249 312 153 117 194 251
24:30 461 145 95 201 250 312 153 118 194 252
24:45 461 145 94 202 253 313 154 119 194 254
25:00 462 145 94 203 255 315 155 119 195 256
25:15 462 146 94 204 256 317 156 120 195 257
25:30 462 146 93 207 259 320 156 121 196 259
25:45 462 147 93 208 261 325 157 121 197 261
26:00 463 148 93 211 264 329 157 122 198 263
26:15 466 148 93 212 267 331 158 123 199 265
26:30 470 149 93 215 267 329 159 123 199 267
26:45 472 150 93 217 268 329 160 123 201 269
27:00 475 152 93 219 270 330 161 124 202 271
27:15 477 153 93 221 272 331 161 125 202 272
27:30 480 154 93 222 274 334 162 125 203 274
27:45 486 155 93 223 277 336 163 126 205 275
28:00 488 156 93 226 280 340 164 125 206 277
28:15 491 157 93 227 282 344 165 126 208 280
28:30 494 158 93 228 286 347 166 126 210 282
28:45 496 158 93 229 288 351 167 126 211 284
29:00 499 159 93 231 290 353 168 127 213 285
29:15 502 160 94 233 292 355 169 127 214 288
29:30 505 160 94 234 294 358 170 127 215 290
29:45 507 161 94 235 296 359 171 127 217 292
30:00 510 162 94 237 299 362 172 127 218 294
130 Derry Court York, Pennsylvania 17406
Telephone: 717-764-7700
Facsimile: 717-764-4129 www.intertek.com/building
TEST REPORT FOR GAMMASTONE Report No.: H4215.01-121-24-R1 Date: 10/20/17 Revision Date: 10/08/19
Version: 07/24/17 Page 37 of 51 RT-R-AMER-Test-2781
TIME (Min:Sec)
T/C 40 T/C 41 T/C 42 T/C 43 T/C 44 T/C 45 T/C 46 T/C 47 T/C 48 T/C 49
00:00 75 103 91 109 119 97 500 83 88 77
00:15 75 202 134 198 206 135 500 98 111 78
00:30 77 981 778 903 830 635 500 424 611 78
00:45 82 1144 974 1087 978 833 500 718 870 78
01:00 86 1241 1033 1125 1036 895 500 852 948 78
01:15 89 1226 1124 1123 1048 932 500 911 969 78
01:30 91 1212 1130 1170 1066 990 500 950 1018 78
01:45 93 1227 1154 1191 1085 996 500 997 1033 77
02:00 94 1242 1153 1211 1097 1019 500 1086 1075 78
02:15 96 1285 1166 1201 1128 1025 500 1152 1167 78
02:30 97 1282 1176 1215 1154 1035 500 1100 1208 78
02:45 97 1302 1181 1230 1159 1040 500 1082 1236 78
03:00 98 1269 1197 1225 1143 1057 500 1072 1186 78
03:15 98 1294 1209 1229 1146 1065 500 1091 1133 78
03:30 99 1322 1232 1245 1160 1077 500 1099 1121 78
03:45 100 1335 1266 1264 1160 1097 500 1115 1138 78
04:00 101 1304 1256 1264 1157 1103 500 1134 1150 78
04:15 101 1317 1257 1292 1168 1108 500 1151 1171 78
04:30 102 1296 1265 1315 1174 1124 500 1178 1179 78
04:45 102 1326 1285 1336 1187 1144 500 1178 1181 78
05:00 103 1330 1273 1313 1178 1149 500 1197 1201 78
05:15 104 1364 1283 1320 1208 1150 500 1198 1205 78
05:30 106 1355 1286 1313 1224 1142 500 1202 1207 78
05:45 108 1429 1319 1367 1228 1178 500 1199 1215 78
06:00 110 1466 1341 1395 1250 1192 500 1223 1240 78
06:15 111 1432 1367 1398 1267 1210 500 1261 1283 78
06:30 112 1423 1352 1395 1276 1200 500 1253 1264 78
06:45 114 1451 1327 1393 1281 1208 500 1244 1251 78
07:00 115 1408 1319 1385 1278 1196 500 1245 1245 78
07:15 116 1399 1355 1383 1284 1203 500 1249 1258 78
07:30 117 1423 1350 1382 1275 1204 500 1263 1274 78
07:45 118 1386 1363 1379 1262 1201 500 1265 1271 79
08:00 119 1367 1360 1400 1253 1213 500 1275 1255 79
08:15 120 1391 1357 1368 1244 1206 500 1266 1263 79
08:30 125 1412 1339 1384 1266 1210 500 1264 1262 79
08:45 129 1412 1334 1370 1275 1218 500 1256 1256 79
09:00 132 1413 1330 1391 1288 1219 500 1249 1262 79
09:15 135 1443 1355 1396 1275 1224 500 1263 1269 79
09:30 139 1467 1334 1386 1298 1219 500 1258 1264 79
09:45 138 1406 1351 1387 1300 1219 500 1250 1271 79
10:00 141 1410 1350 1401 1299 1239 500 1254 1266 79
10:15 141 1421 1374 1389 1295 1235 500 1268 1278 79
10:30 143 1485 1421 1485 1349 1264 500 1317 1328 79
10:45 146 1524 1472 1499 1377 1300 500 1362 1367 79
11:00 149 1563 1479 1532 1392 1311 500 1381 1386 79
11:15 153 1534 1490 1501 1428 1317 500 1395 1391 80
130 Derry Court York, Pennsylvania 17406
Telephone: 717-764-7700
Facsimile: 717-764-4129 www.intertek.com/building
TEST REPORT FOR GAMMASTONE Report No.: H4215.01-121-24-R1 Date: 10/20/17 Revision Date: 10/08/19
Version: 07/24/17 Page 38 of 51 RT-R-AMER-Test-2781
TIME (Min:Sec)
T/C 40 T/C 41 T/C 42 T/C 43 T/C 44 T/C 45 T/C 46 T/C 47 T/C 48 T/C 49
11:30 156 1531 1534 1542 1427 1332 500 1410 1419 80
11:45 159 1560 1521 1565 1426 1346 500 1416 1421 80
12:00 159 1566 1536 1531 1436 1348 500 1431 1438 80
12:15 161 1589 1527 1537 1445 1355 500 1433 1440 80
12:30 162 1574 1501 1560 1444 1371 500 1456 1465 80
12:45 162 1602 1529 1557 1443 1371 500 1453 1460 80
13:00 163 1592 1550 1559 1452 1381 500 1469 1465 80
13:15 165 1590 1551 1574 1452 1382 500 1468 1477 80
13:30 167 1586 1567 1602 1432 1389 500 1465 1479 80
13:45 170 1587 1558 1588 1434 1399 500 1477 1476 81
14:00 173 1591 1572 1604 1435 1404 500 1489 1485 81
14:15 175 1616 1581 1606 1441 1414 500 1481 1484 81
14:30 178 1619 1549 1582 1456 1400 500 1479 1492 81
14:45 180 1623 1540 1586 1469 1395 500 1479 1494 81
15:00 182 1644 1552 1585 1470 1407 500 1493 1503 81
15:15 182 1643 1552 1584 1473 1404 500 1469 1478 81
15:30 183 1643 1543 1592 1484 1407 500 1496 1494 81
15:45 184 1631 1549 1607 1480 1417 500 1508 1498 82
16:00 187 1620 1559 1601 1460 1414 500 1496 1507 82
16:15 190 1662 1552 1597 1486 1415 500 1482 1495 82
16:30 193 1624 1555 1591 1475 1420 500 1495 1498 82
16:45 195 1635 1570 1620 1481 1425 500 1496 1506 82
17:00 206 1641 1605 1613 1475 1428 500 1506 1520 82
17:15 216 1637 1586 1625 1484 1442 500 1516 1537 82
17:30 225 1642 1570 1619 1487 1429 500 1505 1511 83
17:45 233 1633 1596 1638 1484 1438 500 1518 1545 83
18:00 241 1654 1581 1637 1505 1445 500 1515 1536 83
18:15 249 1657 1594 1638 1510 1441 500 1517 1539 83
18:30 257 1655 1570 1645 1521 1445 500 1521 1527 83
18:45 264 1677 1573 1636 1503 1446 500 1520 1540 83
19:00 272 1656 1585 1643 1509 1449 500 1541 1537 83
19:15 277 1678 1604 1639 1518 1456 500 1533 1547 84
19:30 282 1665 1599 1652 1510 1460 500 1544 1550 84
19:45 288 1670 1593 1656 1495 1459 500 1548 1548 84
20:00 295 1650 1602 1667 1515 1460 500 1546 1552 84
20:15 299 1678 1615 1642 1507 1459 500 1536 1552 84
20:30 302 1673 1596 1658 1519 1465 500 1553 1565 84
20:45 304 1697 1584 1645 1537 1455 500 1541 1548 84
21:00 307 1697 1601 1652 1530 1464 500 1540 1561 84
21:15 310 1686 1596 1658 1522 1458 500 1550 1563 84
21:30 312 1679 1615 1658 1524 1474 500 1559 1578 84
21:45 313 1674 1624 1666 1515 1473 500 1555 1571 85
22:00 317 1699 1618 1689 1521 1485 500 1557 1560 85
22:15 319 1676 1598 1659 1530 1476 500 1558 1562 85
22:30 322 1714 1626 1673 1531 1479 500 1552 1569 85
22:45 326 1664 1615 1667 1520 1484 500 1568 1580 85
130 Derry Court York, Pennsylvania 17406
Telephone: 717-764-7700
Facsimile: 717-764-4129 www.intertek.com/building
TEST REPORT FOR GAMMASTONE Report No.: H4215.01-121-24-R1 Date: 10/20/17 Revision Date: 10/08/19
Version: 07/24/17 Page 39 of 51 RT-R-AMER-Test-2781
TIME (Min:Sec)
T/C 40 T/C 41 T/C 42 T/C 43 T/C 44 T/C 45 T/C 46 T/C 47 T/C 48 T/C 49
23:00 329 1696 1606 1664 1541 1485 500 1559 1568 85
23:15 332 1701 1626 1666 1522 1483 500 1558 1572 85
23:30 334 1698 1605 1667 1528 1479 500 1566 1583 85
23:45 336 1708 1625 1688 1544 1497 500 1561 1562 85
24:00 333 1751 1649 1649 1489 1497 500 1580 1579 86
24:15 334 1722 1621 1655 1498 1492 500 1559 1585 86
24:30 335 1647 1636 1645 1489 1484 500 1553 1578 86
24:45 334 1683 1672 1663 1493 1499 500 1554 1574 86
25:00 334 1739 1649 1633 1497 1488 500 1548 1572 86
25:15 335 1683 1631 1640 1500 1483 500 1553 1590 86
25:30 338 1701 1685 1673 1526 1513 500 1574 1611 86
25:45 340 1734 1689 1664 1526 1511 500 1586 1614 86
26:00 343 1723 1683 1660 1527 1516 500 1599 1628 87
26:15 346 1721 1689 1669 1520 1516 500 1597 1623 87
26:30 348 1782 1701 1670 1525 1527 500 1613 1640 87
26:45 350 1721 1696 1681 1532 1528 500 1608 1630 87
27:00 352 1708 1696 1664 1524 1529 500 1613 1639 87
27:15 353 1738 1711 1687 1531 1531 500 1615 1641 87
27:30 355 1744 1712 1670 1532 1530 500 1618 1650 87
27:45 359 1784 1707 1680 1538 1535 500 1621 1654 87
28:00 362 1787 1707 1680 1539 1547 500 1620 1649 87
28:15 364 1798 1705 1682 1537 1544 500 1634 1668 87
28:30 368 1757 1709 1701 1541 1542 500 1629 1661 88
28:45 371 1794 1701 1699 1546 1548 500 1634 1673 88
29:00 375 1768 1707 1698 1543 1548 500 1635 1668 88
29:15 378 1791 1703 1697 1534 1547 500 1636 1657 88
29:30 381 1776 1717 1682 1534 1555 500 1639 1671 88
29:45 384 1804 1731 1707 1545 1559 500 1657 1677 88
30:00 387 1807 1721 1696 1540 1555 500 1645 1668 88
130 Derry Court York, Pennsylvania 17406
Telephone: 717-764-7700
Facsimile: 717-764-4129 www.intertek.com/building
TEST REPORT FOR GAMMASTONE Report No.: H4215.01-121-24-R1 Date: 10/20/17 Revision Date: 10/08/19
Version: 07/24/17 Page 40 of 51 RT-R-AMER-Test-2781
TIME (Min:Sec)
T/C 50 T/C 51 T/C 52 T/C 53 T/C 54
00:00 76 77 81 77 76
00:15 76 77 81 77 76
00:30 76 77 81 77 76
00:45 76 77 81 77 76
01:00 76 77 81 77 76
01:15 76 77 81 77 76
01:30 76 77 81 77 76
01:45 76 77 81 77 76
02:00 76 77 81 77 76
02:15 76 77 81 77 76
02:30 76 77 81 77 76
02:45 76 78 81 77 76
03:00 76 78 81 77 76
03:15 76 78 81 77 76
03:30 77 78 81 77 76
03:45 77 78 81 77 76
04:00 77 78 81 78 76
04:15 77 78 81 77 76
04:30 77 78 81 78 76
04:45 77 78 81 78 76
05:00 77 78 82 78 76
05:15 77 78 82 78 76
05:30 77 78 82 78 76
05:45 77 78 82 78 76
06:00 77 78 82 78 76
06:15 77 78 82 78 76
06:30 77 78 82 78 77
06:45 77 78 82 78 77
07:00 77 78 82 78 77
07:15 78 78 82 78 77
07:30 78 78 82 78 77
07:45 78 78 82 78 77
08:00 78 79 82 79 77
08:15 78 79 82 79 77
08:30 78 79 82 79 77
08:45 78 79 82 79 77
09:00 78 79 82 79 77
09:15 78 79 82 79 78
09:30 78 79 82 79 78
09:45 78 79 82 79 78
10:00 79 79 82 80 78
10:15 79 80 82 80 78
10:30 79 80 82 80 78
10:45 79 80 82 80 78
11:00 79 80 82 80 78
11:15 79 80 82 80 78
130 Derry Court York, Pennsylvania 17406
Telephone: 717-764-7700
Facsimile: 717-764-4129 www.intertek.com/building
TEST REPORT FOR GAMMASTONE Report No.: H4215.01-121-24-R1 Date: 10/20/17 Revision Date: 10/08/19
Version: 07/24/17 Page 41 of 51 RT-R-AMER-Test-2781
TIME (Min:Sec)
T/C 50 T/C 51 T/C 52 T/C 53 T/C 54
11:30 79 80 82 80 78
11:45 79 80 82 80 78
12:00 79 80 82 80 79
12:15 79 80 82 80 79
12:30 80 81 82 81 79
12:45 80 81 82 81 79
13:00 80 81 82 81 79
13:15 80 81 82 81 79
13:30 80 81 82 81 79
13:45 81 81 82 82 80
14:00 81 81 82 82 80
14:15 81 82 82 82 80
14:30 81 82 82 82 80
14:45 81 82 82 82 81
15:00 82 82 82 82 81
15:15 82 82 82 83 81
15:30 82 82 82 83 81
15:45 82 83 82 83 81
16:00 82 83 82 84 81
16:15 83 83 82 84 82
16:30 83 83 82 84 82
16:45 83 83 83 84 82
17:00 83 83 83 84 82
17:15 83 84 83 84 82
17:30 83 84 83 84 82
17:45 84 84 83 85 82
18:00 84 84 83 85 82
18:15 84 84 83 85 83
18:30 84 84 83 85 83
18:45 84 85 83 85 83
19:00 84 85 83 85 83
19:15 84 85 83 85 83
19:30 85 85 83 85 83
19:45 85 85 83 85 83
20:00 85 85 83 85 83
20:15 85 85 83 85 84
20:30 85 85 83 86 84
20:45 85 85 83 86 84
21:00 85 85 83 86 84
21:15 85 85 83 86 84
21:30 86 85 83 86 84
21:45 86 85 83 86 84
22:00 86 86 83 87 84
22:15 86 86 83 86 84
22:30 86 86 83 87 85
22:45 86 86 83 87 84
130 Derry Court York, Pennsylvania 17406
Telephone: 717-764-7700
Facsimile: 717-764-4129 www.intertek.com/building
TEST REPORT FOR GAMMASTONE Report No.: H4215.01-121-24-R1 Date: 10/20/17 Revision Date: 10/08/19
Version: 07/24/17 Page 42 of 51 RT-R-AMER-Test-2781
TIME (Min:Sec)
T/C 50 T/C 51 T/C 52 T/C 53 T/C 54
23:00 86 86 83 87 85
23:15 86 87 83 87 85
23:30 87 87 83 87 85
23:45 87 87 83 87 85
24:00 87 87 83 88 85
24:15 87 87 83 88 85
24:30 87 87 83 88 85
24:45 87 87 83 88 86
25:00 88 88 83 88 86
25:15 88 88 83 88 86
25:30 88 88 83 88 85
25:45 88 88 83 88 86
26:00 88 88 83 88 86
26:15 88 88 83 89 86
26:30 88 88 83 89 86
26:45 88 88 83 89 86
27:00 88 89 83 89 86
27:15 89 89 83 89 86
27:30 89 89 83 89 86
27:45 89 89 83 90 86
28:00 89 89 83 89 86
28:15 89 89 83 90 86
28:30 89 90 83 90 86
28:45 89 90 83 90 87
29:00 89 90 83 90 87
29:15 90 90 83 90 87
29:30 90 90 83 90 87
29:45 90 90 83 90 87
30:00 90 90 83 90 87
130 Derry Court York, Pennsylvania 17406
Telephone: 717-764-7700
Facsimile: 717-764-4129 www.intertek.com/building
TEST REPORT FOR GAMMASTONE Report No.: H4215.01-121-24-R1 Date: 10/20/17 Revision Date: 10/08/19
Version: 07/24/17 Page 43 of 51 RT-R-AMER-Test-2781
SECTION 14 DRAWINGS The test specimen drawings which follow have been reviewed by Intertek B&C and are representative of the test specimen(s) reported herein. Test specimen construction was verified by Intertek B&C per the drawings included in this report. Any deviations are documented herein or on the drawings.
130 Derry Court York, Pennsylvania 17406
Telephone: 717-764-7700
Facsimile: 717-764-4129 www.intertek.com/building
TEST REPORT FOR GAMMASTONE Report No.: H4215.01-121-24-R1 Date: 10/20/17 Revision Date: 10/08/19
Version: 07/24/17 Page 44 of 51 RT-R-AMER-Test-2781
Standard TC Locations
130 Derry Court York, Pennsylvania 17406
Telephone: 717-764-7700
Facsimile: 717-764-4129 www.intertek.com/building
TEST REPORT FOR GAMMASTONE Report No.: H4215.01-121-24-R1 Date: 10/20/17 Revision Date: 10/08/19
Version: 07/24/17 Page 45 of 51 RT-R-AMER-Test-2781
130 Derry Court York, Pennsylvania 17406
Telephone: 717-764-7700
Facsimile: 717-764-4129 www.intertek.com/building
TEST REPORT FOR GAMMASTONE Report No.: H4215.01-121-24-R1 Date: 10/20/17 Revision Date: 10/08/19
Version: 07/24/17 Page 46 of 51 RT-R-AMER-Test-2781
130 Derry Court York, Pennsylvania 17406
Telephone: 717-764-7700
Facsimile: 717-764-4129 www.intertek.com/building
TEST REPORT FOR GAMMASTONE Report No.: H4215.01-121-24-R1 Date: 10/20/17 Revision Date: 10/08/19
Version: 07/24/17 Page 47 of 51 RT-R-AMER-Test-2781
130 Derry Court York, Pennsylvania 17406
Telephone: 717-764-7700
Facsimile: 717-764-4129 www.intertek.com/building
TEST REPORT FOR GAMMASTONE Report No.: H4215.01-121-24-R1 Date: 10/20/17 Revision Date: 10/08/19
Version: 07/24/17 Page 48 of 51 RT-R-AMER-Test-2781
Assembly Drawings
130 Derry Court York, Pennsylvania 17406
Telephone: 717-764-7700
Facsimile: 717-764-4129 www.intertek.com/building
TEST REPORT FOR GAMMASTONE Report No.: H4215.01-121-24-R1 Date: 10/20/17 Revision Date: 10/08/19
Version: 07/24/17 Page 49 of 51 RT-R-AMER-Test-2781
130 Derry Court York, Pennsylvania 17406
Telephone: 717-764-7700
Facsimile: 717-764-4129 www.intertek.com/building
TEST REPORT FOR GAMMASTONE Report No.: H4215.01-121-24-R1 Date: 10/20/17 Revision Date: 10/08/19
Version: 07/24/17 Page 50 of 51 RT-R-AMER-Test-2781
130 Derry Court York, Pennsylvania 17406
Telephone: 717-764-7700
Facsimile: 717-764-4129 www.intertek.com/building
TEST REPORT FOR GAMMASTONE Report No.: H4215.01-121-24-R1 Date: 10/20/17 Revision Date: 10/08/19
Version: 07/24/17 Page 51 of 51 RT-R-AMER-Test-2781
SECTION 10 REVISION LOG
REVISION # DATE PAGES REVISION
0 10/20/17 N/A Original Report Issue
1 10/08/19 7 Corrected “as tested” open cladding joints.