Alpha Technologies> Company Overview
Alpha Technologies pioneered the concept of reliable standby power for the cable television industry,
and in the process has set a 30-year precedent for visionary, market-driven power solutions. Today,
Alpha continues to focus on providing the communications industry with the most reliable, innovative
and cost-effective powering solutions available. Hundreds of dedicated Alpha engineers, technicians,
craftspeople and field specialists share this focus. These are inspired people creating proactive
solutions that help shape the future of the industry and Alpha itself - a company where people and
power come together.
> The Alpha GroupThe Alpha Group represents an alliance of independent companies sharing a common philosophy - to
create world-class powering solutions. Collectively, Alpha Group members develop and manufacture
AC and DC power conversion, protection and standby products. Applications for these products
include broadband, telecom, AC/UPS, commercial, industrial and renewable energy for a worldwide
customer base. In addition, our companies provide a range of installation and maintenance services.
Members of The Alpha Group include Alpha Technologies, Alpha Energy, Alpha Industrial Power, Argus
Technologies, Alpha Technologies Services and G.B. Enterprises.
3
Table o
f Co
nten
ts
Table of Contents> DC Power Systems 5-25
Matrix of Cordex™ DC Power Systems ..................6
Cordex Controller Features ...................................7
Cordex Comparison Chart ....................................8
Cordex CXCR/CXCP .............................................9
Cordex CXCM4 ...................................................10
Cordex CXCM2 ...................................................10
Cordex CXCM ..................................................... 11
Cordex CXCI ........................................................ 11
Cordex 400 and 650W ........................................ 12
Cordex 1kW ......................................................... 14
Cordex 1.8kW ......................................................16
Cordex 3.6kW ..................................................... 17
Cordex System .................................................... 18
CXPS 48-1T .........................................................20
CXPS 48-2T .........................................................21
CSM01 and CSM02 ............................................22
Distribution Centers .............................................23
DC Accessories ...................................................24
> Headend batteries 27-31
Headend Batteries ..............................................28
AlphaGuard™ .......................................................30
Battery Testing Equipment ..................................31
> Dc to ac inverters 33-41
SMI 3300 Inverter Series .....................................34
Tebevert Inverter Series .......................................35
INEX Inverter System ...........................................36
S4 Inverter Series ................................................38
DSP Inverter Series .............................................39
S5 Inverter Series ................................................40
MS Power Inverter Series .................................... 41
> netbotz® Monitoring 43
> Single and Three Phase uPS 45-63
SmartUPS® XL.....................................................46
SmartUPS RT ......................................................48
Symmetra® ..........................................................52
Symmetra LX .......................................................53
1600EP Series .....................................................56
Triniti™ 4200 Series ..............................................57
Galaxy..................................................................58
Galaxy 4000 ........................................................59
Symmetra PX .......................................................60
Galaxy PW Series ................................................62
EPS 7000.............................................................63
> alphaTVSS™ Surge Suppression 65
> alpha Technologies Services 67
> FTTx Power 69-77
FlexPoint™ 1230 Series ........................................70
FlexPoint AX Series .............................................71
FlexNet™ FMPS .................................................... 74
FlexNet FiberUPS ................................................75
PMR and GMR Series .........................................76
Radium MiniBay™ ................................................77
> alpha enclosures 79-85
Tempest Te25 / Te25xh .......................................80
Tempest Te15 ......................................................81
Tempest Te17 ......................................................82
Tempest Te20 ......................................................83
Tempest Te20b ....................................................84
Tempest Te21 ......................................................85
> racks and rack accessories 87-93
SX 42RU Rack .....................................................88
SX 48RU Rack .....................................................89
4 Post Open Frame Racks ..................................90
In Row Rack Cooling ...........................................91
Rack Air Distribution Unit .....................................92
Rack Air Removal Unit .........................................92
Rack Hardware and Accessories ........................93
> alphagen™ generators 95-97
AlphaGen 3.5kW to 2MW Systems .....................96
AlphaGen Telecom ..............................................97
> alpha building Systems 99
> notes 100
5
DC
Po
wer S
ystems
DC Power SystemsThe Alpha Group has more than 30 years of experience providing a wide variety of fully integrated
power system solutions. With options for standardized systems and custom DC system integration,
The Alpha Group has the flexibility to provide DC power solutions perfect for a wide range of power
needs and various site installation requirements.
Integrated shelf systems are available for all small power rectifier models providing a complete power
solution in a single rackmount package. These systems incorporate a Cordex™ controller, rectifiers and
DC distribution options in a compact shelf design. Optional accessories such as LVDs, shunts and
temperature compensation are available.
For medium to large system applications, The Alpha Group can provide both standard and custom DC
system solutions designed to maximize space and cost savings. Systems can be integrated with a
wide array of options including various rack solutions, custom DC distribution configurations, multiple
voltage output designs and front access.
Coupling advanced Cordex power technology with an enormous selection of system components,
The Alpha Group can easily provide optimal system solutions up to 8,000 Amps.
6
DC
Po
wer
Sys
tem
s
48-3.6kwMulti bay
48-3.6kwSingle bay
48-1.8kwSingle shelfwith expansion
48-1kwSingle shelf
48-650wSingle shelfwith expansion
24-400wSingle shelfwith expansion
20a
AMPS (not to scale)
14a
140a
75a
2000a
13a
65a
130a
37a
187a
Dc Power Systems 48V 24V
CXCM4 CXCP
CXCICXCM2CXCR
CXCMCXCR
CXCI
CXCI
500a
8000a
CXCR
6000a
4000a
2000a
450a
900a
1350a
8000
6000
4000
2000
1000
800
600
400
200
175
150
125
100
75
50
25
0
120a
70a
375a
Matrix of Dc Power Systems
7
DC
Co
ntro
llers
cordex™ controller Features
> Main• WebbasedGUIInterface:Webbrowsersupportforlocalor
remote control and monitoring
• Singlepointsetupandcontrol
• Autovoltageadjustmentandloadsharing
• Analogdigitalinputs
• ConfigurableFormCrelayoutputs
• Variouspresetalarmsandabilitytoconfigureupto
20 customized alarms
• Userprogrammablelogicstatements
• LegacyPowerSystemUpgrade:ControlslegacyPathfinder
based systems and can be used as a site monitor for any 3rd
party DC power system
• CANCommunications:Commonplatformforpowerelectronics
and peripherals, rugged and field proven protocol
• FailSafeSystemOperation:IntheeventofCXCfailure,
rectifiers continue to run with default settings, fail alarm is
generated and LVDs (if equipped) remain energized
• PowerSaveFunction:Improvesoperationalefficiencyby
running the minimum number of rectifier modules required
per system load
• SystemStartDelay:AllowsdelayforotherACpowered
equipment to start before rectifiers
• RampTestControl:Disablesfailalarmonno-loadconditions.
• SNMPSupport:Networkmanagementservicesupportfor
managing multiple systems in a single network
• EmailnotificationsviaTCP/IP
• CordexPeripheralSupport:Optionaladd-onsforindividualcell
and temperature monitoring and controller I/O expansion
• MultilanguagesupportincludingChinesecharacters
> Battery Management• TemperatureCompensatedFloatVoltage:Increasesvoltagein
temperatures below 25˚C / 77˚F and decreases charge voltage
above 25˚C / 77˚F. Maximizes life and capacity of battery and
prevents thermal runaway
• BatteryEqualize:Manual,automaticandperiodicequalize
charge modes, optional Battery Current Terminate function to
prevent over charging of battery
• BatteryBoostMode:Offlinehigh-voltageequalizechargewith
interlock safety feature
• DynamicChargeCurrentControl:Limitsbatteryrecharge
current to a fixed value, helps prevent thermal runaway
• BatteryTest:Setsrectifiervoltagelowandperformssafe
discharge of batteries through the connected system loads
• BatteryCapacityPrediction:Calculatescurrentbattery
capacity after a discharge
• BatteryRuntimePrediction:Basedoncurrentbatterycapacity
and system load
• BatteryLogging:Retainupto40recordsofbattery
statistics and events
> Maintenance• DataLogger:Recordanysysteminput(s),andsetsamplerate
of record on deviation, store up to 500 events via manual or
auto start/stop
• Typicaldatalogapplications:Detailedbattery
discharge information, AC voltage watch dog and outdoor
cabinet thermal performance
• EasyRemoteSoftwareUpgrades:Fail-safeprotected
upgrades for controllers, rectifiers and peripherals
> The Cordex CXC is the latest generation of advanced digital controllers for DC power system monitoring and control. Cordex supervisory controllers come in a wide array of modular designs for compact integration into Alpha Group DC systems. Standalone rackmount versions are also available for DC systems, legacy controller upgrades and site monitoring. A graphic LCD display with state-of-the-art touch-screen interface allows simple and convenient set up, control and monitoring. Innovative IP technology allows complete configuration and monitoring from any location via the Internet using a standard web browser.
8
DC
Co
ntr
olle
rs
cordex controller Series
CXCR/CXCP CXCM4 CXCM2 CXCM CXCI
Specifications
Screen:Full Graphic LCD 160 x 160 pixels
Full Graphic LCD 160 x 160 pixels
Full Graphic LCD 160 x 160 pixels
Full Graphic LCD 160 x 160 pixels
Basic Current / Volts Display Only
Inputs
analog: 2V, 2T, 4C, 2BIV 2V, 2T, 4C, 2BIV 1V, 2T, 2C, 4BIV 2V, 2T, 1C, 1BIV 1V, 1C, 2T
Digital: 8 4 6 3 2
alarm relay outputs: 8 Form C 8 Form C 6 Form C 8 Form C 4 Form C
Dimensions
Height x width x Depth (in/mm):
5.1 x 16.9 x 3.9 / 131 x 431 x 100
7 x 3.4 x 10.1 / 177 x 87 x 257
3.4 x 5 x 9.7 / 86.4 x 128 x 247
6.9 x 2.9 x 10 / 177 x 74 x 255
3.5 x 1 x 11 / 88 x 26 x 280
Rectifier Shelf Option Availability
3.6kw (48Vdc): Yes Yes
1.8kw (48Vdc): Yes Yes Yes
1kw (48Vdc): Yes Yes
650w (48Vdc): Yes
400w (24Vdc): Yes
cordex™ comparison chart
> Cordex Controllers come standard with several advanced battery management features to allow for significant savings of capital and operational expenses. Some additional features include user definable alarms with custom algorithms, digital and analog input monitoring, data logging, integrated SNMP and CAN bus communications. The Cordex CXC is designed for effortless operation of the Cordex rectifier family, making time consuming and complicated set up and monitoring of DC power systems a thing of the past.
9
DC
Co
ntro
llers
cordex cXcr/cXcP
Features
Display:LCD Touchscreen Display (160 x 160 Pixels), “OK/Major/Minor”3-Color,LEDDisplay,WebBased GUI Via Ethernet
communication Ports:RJ45 Ethernet Port (Front Accessible Rear Port), RS232 Craft Port (Front), RS232 Modem Port (Optional)
Controller I/O
Voltage inputs: 2
Temperature inputs: 2
current inputs: 4
bi Voltage inputs: 2
Digital inputs: 8
relay outputs: 8
Electrical
input Voltage: 17 to 65Vdc
current: <100mA @ 48Vdc or < 200mA @ 24Vdc
Mechanical
Dimensions (Plus 19" or 23" Mounting bracket) (in/mm):
5.1 x 16.9 x 3.9 / 131 x 431 x 100
Mounting:CXCR with 19" or 23" rackmounting CXCP panel mount
weight (lb/kg): 13.8 / 6.2
cordex™ cXcr/cXcPSystem Controller
> LCD touch-screen user interface
> Internet ready, integrated SNMP
> High reliability CAN bus communication
> User definable alarms
> Flexible battery management features
> Smart peripheral monitoring features
> 19" and 23" Universal rack or panel mount configurations
CXCR Rackmount Controller
Environmental
extended Temperature: -40 to 65°C / -40 to 149°F
Humidity: 0 to 95% non-condensing
Standards
Safety:
CSA C22.2 No 60950-1-03 UL 60950-1 1st Edition CE marked IEC/EN 60950-1
eMc: ETSI 300 386
emissions:
CFR47 (FCC) Part 15 Class B ICES-03 Class B EN55022 (CISPR 22) Class B C-tick (Australia)
immunity:
EN 61000-4-2 EN 61000-4-3 EN 61000-4-4 EN 61000-4-5 EN 61000-4-6
10
DC
Co
ntr
olle
rs
cordex cXcM2
Features
Display:LCD Touchscreen Display (160x160 pixels), “OK / Major/Minor”3-Color,LEDDisplay,WebBasedGUI Via Ethernet
communication Ports: RJ45 Ethernet Port (Front)
Controller I/O
Voltage inputs: 1 + 1 Internal
Temperature inputs: 2
current inputs: 2
Digital inputs: 6
relay outputs: 6
Electrical
input Voltage: 17 to 65Vdc
current: <100mA @ 48Vdc or <200mA @ 24Vdc
Mechanical
Dimensions (in/mm): 3.4 x 5 x 9.7 / 96.4 x 128 x 247
Mounting: Modular controller for 1.8kW shelves
Environmental
extended Temperature: -40 to 65°C / -40 to 149°F
Humidity: 0 to 95% non-condensing
Standards
Safety:CSA C22.2 No 60950-1-03 UL 60950-1 1st Edition CE marked
cordex cXcM2System Controller
> LCD touch-screen user interface
> Internet ready, integrated SNMP
> High reliability CAN bus communication
> 2RU modular CXC for 1.8kW rectifiers
CXCM2
cordex™ cXcM4System Controller
> User definable alarms and data logging
> Flexible battery management features
> Smart peripheral monitoring features
> 4RU modular CXC for 3.1/3.6kW rectifiers
cordex cXcM4
Features
Display:LCD Touchscreen Display (160x160 pixels), “OK / Major/Minor”3-Color,LEDDisplay,WebBasedGUI Via Ethernet
communication Ports: RJ45 Ethernet Port, RS232 Craft Port (Front)
Controller I/O
Voltage inputs: 1 + 1 Internal
Temperature inputs: 2
current inputs: 4
bi Voltage inputs: 2
Digital inputs: 4
relay outputs: 8
Mechanical
Dimensions (in/mm): 7.0 x 3.4 x 10.1 / 177 x 87 x 257
weight (lb/kg): 3.9 / 1.8
Mounting: Modular controller for 3.1kW and 3.6kW shelves
Environmental
extended Temperature: -40 to 65°C (-40 to 149°F)
Humidity: 0 to 95% non-condensing
Standards
Safety:
CSA C22.2 No 60950-1-03 UL 60950-1 1st Edition CE marked IEC/EN 60950-1
eMc: ETSI 300 386
emissions:
CFR47 (FCC) Part 15 Class B ICES-03 Class B EN55022 (CISPR 22) Class B C-tick (Australia)
immunity:
EN 61000-4-2 EN 61000-4-3 EN 61000-4-4 EN 61000-4-5 EN 61000-4-6
CXCM4
11
DC
Co
ntro
llers
cordex™ cXcMSystem Controller
> LCD touch-screen user interface
> Internet ready, integrated SNMP
> High reliability CAN bus communication
> User definable alarms and data logging
> 4RU modular CXC for 1kW rectifiers
cordex cXci
Features
integrated option on 1.8kw, 650w, 400w, and 250w shelves
Display:4LCDforV/IDisplay,“OK/Major/Minor”3-Color, LED Display, Web Based GUI Via Ethernet
communication Ports:RJ45 Ethernet Port (Front), RS232 Modem Port (Front)
Controller I/O
Voltage inputs: 1 + 1 Internal
Temperature inputs: 2
current inputs: 1
Digital inputs: 4
relay outputs: 4
Electrical
input Voltage: 17 to 65Vdc
current: <100mA @ 48Vdc or < 200mA @ 24Vdc
Mechanical
Dimensions (in/mm): 3.5 x 1 x 11 / 88 x 26 x 280
Mounting: Integrated on Cordex 2RU series 19" and 23" shelves
Environmental
Temperature: -40 to 65°C / -40 to 149°F
Humidity: 0 to 95% non-condensing
Standards
Safety:CSA C22.2 No 60950-1-03UL 60950-1 1st EditionCE marked
> Control and monitor via Internet Explorer browser
> Flexible battery management features
> Smart peripheral monitoring features
> Integrated controller for 2RU rectifiers
cordex cXciSystem Controller
CXCI
cordex cXcM
Features
Display:LCD Touchscreen Display (160 x 160 Pixels), “OK/Major/Minor”3-Color,LEDDisplay, Web Based GUI Via Ethernet
communication Ports:RJ45 Ethernet Port (Front Accessible Rear Port) RS232 Craft Port (Front) RS232 Modem Port (Optional)
Controller I/O
Voltage inputs: 1 + 1 Internal
Temperature inputs: 2
current inputs: 1
bi Voltage inputs: 1
Digital inputs: 3
relay outputs: 8
Mechanical
Dimensions (in/mm): 6.9 x 2.9 x 10 / 177 x 74 x 255
weight (lb/kg): 3.9 / 1.8
Mounting: Modular controller for 1kW rectifier
Environmental
extended Temperature: -40 to 65°C / -40 to 149°F
Humidity: 0 to 95% non-condensing
Standards
Safety:
CSA C22.2 No 60950-1-03 UL 60950-1 1st Edition CE marked IEC/EN 60950-1
eMc: ETSI 300 386
emissions:
CFR47 (FCC) Part 15 Class B ICES-03 Class B EN55022 (CISPR 22) Class B C-tick (Australia)
immunity:
EN 61000-4-2 EN 61000-4-3 EN 61000-4-4 EN 61000-4-5 EN 61000-4-6
CXCM
12
DC
Rec
tifi
ers
cordex™ 400 and 650wModular Switched Mode Rectifier
Mechanical
Dimensions (in/mm): 3.4 x 2.8 x 9.5 / 88.4 x 71.6 x 242
weight (lb/kg): 3 / 1.4
Features
indicators:AC mains OK — green LED Module alarm — red LED
cooling: Natural convection
adjustments(via cXci controller):
Float and equalize voltageBattery test voltage High and low voltage alarms High voltage shutdown Current limit Start delay time Slope %
Protection:
Current limit/short circuit Input/output fuses Output high voltage shutdown Output power limiting Thermal foldback/shutdown Input transient AC low line foldback/shutdown AC high voltage shutdown
Environmental
operation Temperature: -40 to 50°C / -40 to 122°F (power derated up to 70°C / 158°F)
Storage Temperature: -40 to 85°C / -40 to 185°F
Humidity: 0 to 95% non-condensing
elevation: -500 to 3000m / -1640 to 9840ft
Heat Dissipation: <94BTU per hour
Standards
Safety:
CSA C22.2 No 60950-1-03 UL 60950-1 1st Edition CE marked IEC/EN 60950-1
eMc: ETSI 300 386
emissions:
CFR47 (FCC) Part 15 Class BICES-03 Class BEN55022 (CISPR 22) Class BC-tick (Australia)EN 61000-3-2EN 61000-3-3
immunity:
EN 61000-4-2 EN 61000-4-3 EN 61000-4-4 EN 61000-4-5 EN 61000-4-6 EN 61000-4-11 ANSI/IEEE C62.41 Cat B3
CXRC 24-400W
> Available in 13.5A @ 48Vdc and 14A @ 24Vdc
> High power density
> Power limiting and wide range AC input
> 91% efficiency and power factor correction
> Hot swappable, 2RU ultra compact design
cordex 400w rectifier Module
Electrical
input Voltage: 90 to 320Vac
Power output: 400W
input Frequency: 45 to 70Hz
Power Factor: >99%
THD: <5%
efficiency: >90%
output Voltage: 20 to 29Vdc
output current: 14A @ 27Vdc (14A max)
load regulation:Static <±0.5%, Dynamic <±2% for 50 to 100%
load step, 2ms recovery time
line regulation:Static <±0.1%. Dynamic <±1% for any change
within rated limitsNoise
wide band noise: <30mVrms, <150mVp-p
Psophometric noise: <1mV
cordex 650w rectifier ModuleElectrical
Input Voltage (120Vac model)
operating: 90 to 140Vac (output power 650W)
extended: 90 to 70Vac (derated output power)
Power output: 650W at nominal 120Vac
Input Voltage (Universal 100 to 240Vac model)
operating: 176 to 320Vac (output power 650W)
extended: 176 to 90Vac (derated output power)
operating: 100 to 140Vac (output power 500W)
Power output: 650W at nominal 208 to 240Vac and 500W at nominal 120Vac
Nominal Specifications
input Frequency: 45 to 70Hz
Power Factor: >99%
THD: <5%
efficiency: >91% (1% loss for 120Vac model)
output Voltage: 42 to 58Vdc
output current: 12A @ 54Vdc (13.5A max)
load regulation:Static <±0.5%, Dynamic <±2% for 50 to 100%
load step, 2ms recovery time
line regulation:Static <±0.1%. Dynamic <±1% for any change
within rated limits
Noise
wide band noise: <30mVrms, <150mVp-p
Psophometric noise: <1mV
13
DC
Rec
tifiers
cordex 24-400w rectifier ShelvesRectifiers Controllers Distribution
19" 2RU Flush Mount
4 x CXRC 24-400W
1 x CXCI(4) AM Bullet type breakers
19" 2RU Flush Mount
5 x CXRC 24-400W
1 x CXCI
Bulk power for external distribution panel
19" and 23" Shelf Systems
650W Cordex 2.6kW shelf power system with CXCI controller and bullet breaker distribution
650W Cordex 3.2kW bulk power system with CXCI controller. Optional LVD shunt with battery breaker
650W Cordex 2.6kW front access shelf power system with CXCI controller and breaker/fuse distribution
400W Cordex 1.6kW shelf power system with CXCI controller and bullet breaker distribution
400W Cordex 2kW bulk power system with CXCI controller
cordex 48-650w rectifier ShelvesRectifiers Controllers Distribution
19" 2RU Flush Mount
4 x CXRC 48-650W
1 x CXCI(4) AM bullet type breakers
19" 2RU Flush Mount
5 x CXRC 48-650W
1 x CXCI
Bulk power for external distribution panel
23" 2RU Center Mount Front Access
4 x CXRC 48-650W
1 x CXCI(4) AM bullet(10) GMT fuse
19" Shelf SystemsMechanical
Dimensions (in/mm): 3.5 x 17.1 x 11.9 / 89 x 435 x 302
weight (lb/kg): 15.5 / 6.9
Note:Weights DO NOT include modules. Dimensions DO NOT include mounting bracket.
23" Shelf Systems
Mechanical
Dimensions (in/mm): 3.5 x 21.4 x 12 / 89 x 544 x 307
Mounting: Center mount; 1.75" and 1" racks
weight (lb/kg): 37 / 16.8 (Fully equipped with four rectifiers)
Note:Weights DO NOT include modules. Dimensions DO NOT include mounting bracket.
Communication Ports
can: Interface to control rectifiers. Smart peripherals.
ethernet: 10/100 Base-T for TCIP/SNMP features.
Environmental
operating Temperature: -40 to 50°C / -40 to 122°F
Storage Temperature: -40 to 85°C / -40 to 185°F
Humidity: 0 to 95% non-condensing
elevation: -500 to 3000m / -1640 to 9840ft
cooling: Natural or forced convection, vertical airflow
cordex™ 400w/650wRectifier Shelf Systems
> Integrated DC distribution with optional LVD
> Integrated 24 and 48Vdc shelf power systems up to 2.6kW
> Bulk 24 and 48Vdc power systems up to 3.2kW
> 19" and 23" rackmounting solutions
> Designed for CSA, UL, CE, FCC and C-tick standards
Cordex 48V-2.6kW Shelf System
Cordex 24V-1.6kW Shelf System
14
DC
Rec
tifi
ers
cordex™ 1kwModular Switched Mode Rectifier
cordex 1kw
Electrical
nominal input Voltage: 208 to 277Vac
operating input Voltage: 150 to 320Vac
extended input Voltage: 150 to 90Vac (derated power)
input Frequency: 45 to 66Hz
Power output: 1000W continuous/module
Power Factor: >0.99
efficiency: >92%
output Voltage: 42 to 60Vdc
output current: 18.5A @ 54Vdc (20.8A maximum)
load regulation: <±0.5% (static)
line regulation: <±0.1% (static)
Transient response: ±1% for 50 to 100% load step, 2ms recovery time
Noise
Voice band: <32dBrnC
wide band: <5mVrms, <100mVp-p
Psophometric: <1mV
Mechanical
Dimensions (in/mm): 6.9 x 2.8 x 9.8 / 177 x 71 x 250
weight (lb/kg): 6.4 / 2.9
Features
indicators:AC mains OK — green LED Module OK — green LED Module alarm — red LED
cooling: Natural convection
adjustments (via cXc controller):
Float and equalize voltage Battery test voltage High and low voltage alarms High voltage shutdown Current limit Start delay timers Slope %
Protection:
Current limit/short circuit Start delay Input/output fuses Output high voltage shutdown Output power limiting Thermal foldback/shutdown Input transient AC low line foldback/shutdown AC high voltage shutdown
Environmental
operation Temperature: -40 to 50°C / -40 to 122°F (with short periods up to 70°C / 158°F)
Storage Temperature: -40 to 85°C / -40 to 185°F
Humidity: 0 to 95% non-condensing
elevation: -500 to 4000m / -1640 to 13120ft
Heat Dissipation: <295BTU per hour
Standards
Safety:
CSA C22.2 No 60950-1-03 UL 60950-1 1st Edition CE marked IEC/EN 60950-1
eMc: ETSI 300 386
emissions:
CFR47 (FCC) Part 15 Class B ICES-03 Class B EN55022 (CISPR 22) Class B C-tick (Australia) EN 61000-3-2 EN 61000-3-3
immunity:
EN 61000-4-2 EN 61000-4-3 EN 61000-4-4 EN 61000-4-5 EN 61000-4-6 EN 61000-4-11 ANSI/IEEE C62.41 Cat B3
> Available in 20.8A @ 48Vdc
> Power limiting and wide range AC input
> 92% efficiency and power factor correction
> Convection cooled
> Hot swappable, 4RU ultra compact design
CXRC 48-1kW
15
DC
Rec
tifiers
cordex™ 1kwModular Rectifier Shelf Systems
> Integrated 48Vdc shelf power systems up to 4kW
> Bulk 48Vdc power systems up to 6kW
> Distribution modules available for DIN or bullet type breakers
> 19" and 23" rackmounting solutions
> Designed for CSA, UL, CE and C-tick standards
cordex 1kw rectifier Shelves
Rectifiers Controllers Distribution
19" Flush Mount 5 x CXRC 48-1kW CXCM Bulk power for external distribution panel
19" Flush Mount 6 x CXRC 48-1kW Requires CXCR rackmount controller Bulk power for external distribution panel
23" Center Mount 4 x CXRC 48-1kW CXCM Integrated bullet type breakers and GMT fuse option
19" Shelf Systems
(Flush Mount) Cordex 5kW bulk power system with plug in controller.
(Flush Mount) Cordex 6kW bulk power system.
23" Shelf Systems
(Center Mount) Cordex 4kW shelf power system with plug in controller and bullet type breaker distribution.
19" Shelf Systems
Mechanical
Dimensions (in/mm): 6.9 x 17.5 x 11.9 / 177 x 444 x 302
weight (lb/kg): 16.5 / 7.5
Note:Shelf P/Ns DO NOT include rectifier modules or distribution breakers.Weights DO NOT include modules.Dimensions DO NOT include mounting brackets.
23" Shelf SystemsMechanical
Dimensions (in/mm): 6.9 x 21.4 x 11.9 / 177 x 543 x 302
weight (lb/kg): 22.5 / 10.2
Note:Shelf P/Ns DO NOT include rectifier modules or distribution breakers.Weights DO NOT include modules.Dimensions DO NOT include mounting brackets.
Communication Ports
can: Interface to control rectifiers
ethernet: 10/100 Base-T for TCIP/SNMP features
Cordex 48V-1kW Shelf System
16
DC
Rec
tifi
ers
cordex™ 1.8kwModular Switched Mode Rectifier and Shelf
> Available in 37.5A @ 48Vdc
> High power density, fan cooled
> Power limiting and wide range AC input
> 91% efficiency and power factor correction
> Bulk 48Vdc power systems up to 9kW
cordex 1.8kw
Electrical
nominal input Voltage: 208 to 277Vac
operating input Voltage: 176 to 312Vac
extended input Voltage: 176 to 90Vac (derated power)
input Frequency: 45 to 66Hz
Power output: 1800W continuous/module
Power Factor: >0.99 (50 to 100% load)
THD: <5%
efficiency: >91%
output Voltage: 42 to 60Vdc
output current: 33.3A @ 54Vdc (37.5A max 48V)
load regulation: <±0.5% (static)
line regulation: <±0.1% (static)
Transient response: ±2% for 50 to 100% load step, 2ms recovery time
Noise
Voice band: <32dBrnC
wide band:<30mVrms (10kHz to 10MHz), <150mVp-p (10kHz to 100MHz)
Psophometric: <1mV
acoustic: <60dBA @ 1m / 3ft
Mechanical
Dimensions (in/mm): 3.3 x 3.94 x 9.25 / 84 x 100 x 235
weight (lb/kg): 6.2 / 2.8
Features
indicators:AC mains OK — green LEDModule OK — green LEDModule fail — red LED
controls: CAN interface to CXC Controller
adjustments (via cXc controller):
Float voltage, Equalize voltage, High voltage alarm, Low voltage alarm, High voltage shutdown, Current limit, Slope, Start delay timers
Protection:
Current limit/short circuit, Start delay, Input/output fuses, Output high voltage shutdown, Power limiting, Thermal foldback/shutdown, Input transient, AC low line foldback/shutdown, AC high voltage shutdown
Environmental
operating Temperature: -40 to 65°C / -40 to 149°F
Storage Temperature: -40 to 85°C / -40 to 185°F
Humidity: 0 to 95% non-condensing
elevation: -500 to 2800m / -1640 to 9186ft
Heat Dissipation: <608BTU per hour
Standards
Safety:
CSA C22.2 No 60950-1-03UL 60950-1 1st EditionCE markedIEC/EN 60950-1
eMc: ETSI 300 386
emissions:
CFR47 (FCC) Part 15 Class BICES-03 Class BEN55022 (CISPR 22) Class BC-tick (Australia)EN 61000-3-2EN 61000-3-3
immunity:
EN 61000-4-2EN 61000-4-3EN 61000-4-4EN 61000-4-5EN 61000-4-6EN 61000-4-11ANSI/IEEE C62.41 Cat B3
19" and 23" Shelf Systems
Mechanical
Dimensions (in/mm): 3.5 x 17.2 x 12.2 / 89 x 438 x 310
Mounting: 19" flush or center mount, 23" center mount only
weight (lb/kg): 19 / 8.5
23" Shelf Systems
Mechanical
Dimensions (in/mm): 3.5 x 21.3 x 12.2 / 89 x 541 x 310
Mounting: 23" flush or center mount
weight (lb/kg): 22 / 10
Connections
input: Terminal Block. Mini-fit connectors (23" only)
output: Bus adapters with ⅜" on 1" centers
chassis ground: ¼" studs on ⅝" centers
can communication: RJ12 offset
Rectifiers Controllers Distribution
19" Flush Mount 3 x CXCR 48-1.8kW CXCM
Bulk power for external distribution panel
19" Flush Mount 4 x CXCR 48-1.8kW CXCI
23" Center Mount 4 x CXCR 48-1.8kW CXCM
23" Center Mount 5 x CXCR 48-1.8kW CXCI
Cordex 48-1.8kW
Typical 7.2kW 23" Shelf with CXCM2
17
DC
Rec
tifiers
cordex™ 3.6kwModular Switched Mode Rectifier
cordex 3.6kw
Electrical
nominal input Voltage: 208 to 277Vac
operating input Voltage: 176 to 312Vac
extended input Voltage: 176 to 90Vac (derated power)
input Frequency: 45 to 70Hz
Power output: 3600W continuous/module
Power Factor: >0.99 (50 to 100% load)
THD: <5%
efficiency: >92%
output Voltage: 42 to 60Vdc
Flood Voltage: 48 to 58Vdc
output current: 66A @ 54Vdc (75A max 48V)
load regulation: <±0.5% (static)
line regulation: <±0.1% (static)
Transient response: ±2% for 50 to 100% load step, 2ms recovery time
Noise
Voice band: <32dBrnC
wide band:<30mVrms (10kHz to 10MHz), <150mVp-p (10kHz to 100MHz)
Psophometric: <1mV
acoustic: <60dBA @ 1m / 3ft
Mechanical
Dimensions (in/mm): 6.3 x 3.4 x 11.8 / 160 x 87 x 300
weight (lb/kg): 10 / 4.6
Features
indicators:AC mains OK — green LED Module OK — green LED Module fail — red LED
controls: CAN interface to CXC Controller
adjustments (via cXc controller):
Float voltage, Equalize voltage, High/Low voltage alarm, High voltage shutdown, Current limit, Slope, Start delay
Protection:
Current limit/short circuit, Start delay, Input/output fuses, Output high voltage shutdown, Power limiting, Thermal foldback/shutdown, Input transient, AC low line foldback/shutdown
Environmental
operating Temperature: -40 to 65°C / -40 to 149°F
Storage Temperature: -40 to 85°C / -40 to 185°F
Humidity: 0 to 95% non-condensing
elevation: -500 to 4000m / -1640 to 13120ft
Heat dissipation: <1176BTU per hour
Standards
Safety:
CSA C22.2 No 60950-1-03UL 60950-1 1st EditionCE markedIEC/EN 60950-1
eMc: ETSI 300 386
emissions:
CFR47 (FCC) Part 15 Class BICES-03 Class BEN55022 (CISPR 22) Class BC-tick (Australia)EN 61000-3-2EN 61000-3-3
immunity:
EN 61000-4-2EN 61000-4-3EN 61000-4-4EN 61000-4-5EN 61000-4-6EN 61000-4-11ANSI/IEEE C62.41 Cat B3
nebS:GR-1089 CORE GR-69 CORE
> Available in 75A @ 48Vdc
> High power density, over 21kW per 23" shelf
> Power limiting and wide range AC input
> High efficiency and power factor correction
> Hot swappable, 4RU ultra compact design
Cordex 48-3.6kW
18
DC
Po
wer
Sys
tem
s
> 2000 to 8000A Capacity
> Designed for central offices and cable headend facilities
> Cordex 3.6kW modular rectifiers
> Circuit breaker and TPL fuse options
> Internal Bay-to-Bay copper busswork
> Expandable power and distribution bays
cordex 48V 8000a Power Systems
Electrical
ac input:Single Phase, 208 to 277Vac Dual 3 Phase, 208 to 240Vac (w/o neutral) Dual 3 Phase, 360 to 480Vac (with neutral)
rectifier Voltage:208 to 277Vac45 to 70Hz
Max. bus capacity:8000A system bus 2000A per bay
Distribution
Fuses - TPl: 2 position, 100 to 800A
Breakers
gJ/gJ1P:1 pole up to 225A 2 pole 250 to 400A 3 pole 450 to 700A
Output termination
TPl Fuse:2 hole ½" dia. on 1¾" centers or 2 hole ⅜" dia. on 1" centers
gJ breaker: 1 pole and 2 pole are ⅜” on 1” centers, 3 pole are 2 hole, ½” dia. on 1¾” centers or ⅜” dia. on 1” centers
ground bar:Overhead buss ground, 15 sets of 2 hole ½" dia. on 1¾" centers (basic system)
Mechanical
enclosure: 1.095mm (14 gauge) steel
Mounting:Standard 23" relay rack (flush rackmount) in box bay
Dimensions (in/mm): 84 x 28 x 28 / 2133 x 710 x 710
weight (lb/kg): Approx. 600 / 272 per bay (no rectifiers)
Environmental
Temperature: 0 to 50°C / 32 to 122°F
Humidity: 0 to 95% non-condensing
elevation: -500 to 2800m / -1640 to 9186ft
Features
System level alarms/controls:Alarms/control parameters are user-programmable through built-in digital supervisory unit
indicators:
LCD with touch screen System OK — green LED System minor alarm — yellow LED Systemmajoralarm—redLED
load Disconnect: 48Vdc/1200A x N mounted on load side
Alarm
connections: 0.34 to 2.5mm2 (14 to 22AWG)
Smart Peripheral Modules
Shunt Mulitplexer: 16 shunts per module
battery cell Monitor: 1 string, 2V cells per module
battery cell Monitor: 4 strings, 12V blocks per module
cordex™ System48V 8000A Power Systems
Cordex 48V 4000A
19
DC
Po
wer S
ystems
> Up to 2000A systems
> Cordex modular rectifiers
> User-configurable, modular distribution tiers
> Intelligent system control and communication
cordex 48V 2000a Power Systems
Electrical
ac input:Single Phase, 208 to 277Vac Dual 3 Phase, 208 to 240Vac (w/o neutral) Dual 3 Phase, 360 to 480Vac (with neutral)
rectifier Voltage: 208 to 277Vac 45 to 70Hz
output Voltage: 42 to 58Vdc (Cordex rectifiers)
output current: 66A @ 54Vdc per 3.6kW rectifier
Power: 21.6kW per rectifier shelf
Max. bus capacity:2000A system bus 600A max. per distribution tier
Mechanical
Dimensions (in/mm): 84 x 28.1 x 19 / 2133 x 714 x 483
weight (lb/kg):Approx. 902 / 410 with 4 tier distribution center and 5 fully loaded Cordex shelves
Environmental
Temperature: 0 to 50°C / 32 to 122°F
Humidity: 0 to 95% non-condensing
elevation: -500 to 2800m / -1640 to 9186ft
Related Components
rectifiers:
Choose up to six Cordex 48V rectifiers per shelf Choose up to six field-expandable shelves per system
low Voltage Disconnect:LVD optional 48Vdc/600A (one per distribution tier)
Distribution:Choose distribution center for 1 tier, 2 tier or 4 tierTerminations (breaker options for tiers 1 through 4)
aM-type/TPS bullet Style: 2 x ¼-20 studs on ⅝" centers per pole
gJ breaker:2 x ⅜-16 studs on 1" centers per pole; i.e., 2-pole breaker will have two sets
cordex controller: The system’s monitoring and control center
battery options:2V Battery cell monitor (1 string) 12V Battery cell monitor (4 strings) Battery tray with breaker (12V blocks)
Tier 1 can be equipped with:24-position AM-type bullet style breakers * 20-position bullet style breakers* with LVD
Tiers 2 to 4 can be equipped with:24-position AM-type bullet style breakers* 20-position bullet style breakers* with LVD 3-position GJ (with or without LVD)
* Bullets style TPS fuse holder and GMT fuse blocks available
cordex™ System48V 2000A Power Systems
Cordex 48V 2000A
3 positions gJ breaker tier rated at 600 amps
3 positions gJ breaker tier with lVD rated at 600 amps
24 position bullet breaker tier rated at 600 amps
20 position bullet breaker tier with lVD rated at 600 amps
20
DC
Po
wer
Sys
tem
s
cXPS 48-1T48V 375A Power Systems
> 48Vdc systems using high density 3.6kW rectifiers
> Front access DC connections
> CXCM4 advanced modular controller
> Flexible integrated rack options
> Optional DC to DC converter upgrade kits
> Integrated system shunt and LVD
cXPS 48-1T
Configurations
053-392-20-000: Base system with 23" mounting
053-392-20-010: System mounted in 22RU (½ height) battery mount rack
053-392-20-020: System mounted in 44RU Zone 4 seismic rack
053-392-20-030: System mounted in 44RU Zone 4 seismic rack with 3x battery trays for 3x 48V strings
rectifier: Up to 5x 48V-3.6kW rectifier positions
Distribution:
18x AM plug-in breaker positions 10x GMT type fuse positions Shunt Low voltage disconnect
controller: CXCM4 modular controller
Electrical
input Voltage: 176 to 320Vac
current: 16.8A @ 240Vac nominal (per rectifier module)
Frequency: 45 to 66Hz
Power Factor: >0.99
output Voltage: 42 to 60Vdc
current:System:375A (expandable to 600A with additional CXRF shelf) Rectifier:75A@48Vdc
Power:System:18kW (expandable to 28.8kW with additional CXRF shelf) Rectifier:3600Wmax
Environmental
Temperature:-40 to 65°C / -40 to 146°F -40 to 75°C / -40 to 167°F derated output
Humidity: 0 to 95% non-condensing
elevation:-500 to 2800m / -1640 to 9186ft -500 to 4000m / -1640 to 13124ft with derated output
Mechanical
Dimensions (in/mm): 19.25 x 23 x 18.8 / 488 x 584 x 477
Mounting: 23" center mount
weight (lb/kg): 110 / 49.8
Connections
load breaker:Hot:¼"-20studson⅝" centers Return:¼"holeson⅝" centers
gMT Fuses: Screw terminal 1.31mm2 to 0.128mm2 (#16 to #26 AWG)
battery Terminations:⅜" holes on 1" centers 4x Sets per polarity
rectifier input: ⅜" holes on 1" centers
alarm connections: Screw terminal 1.31mm2 to 0.128mm2 (#16 to #26 AWG)
access:Cable:toporbottom User:frontaccessafterinstallation
Related Components
010-567-20: Cordex 48V-3.6kW rectifier
038-276-20: CSM02 DC-DC converter kit
CXPS 48-1T Internal Distribution
CXPS 48V 375A
21
DC
Po
wer S
ystems
cXPS 48-2T48V 825A Power Systems
> 48Vdc systems using high density 3.6kW rectifiers
> Front access DC connections
> CXCM4 advanced modular controller
> Flexible integrated rack options
> Optional DC to DC converter upgrade kits
> Integrated system shunt and LVD
cXPS 48-2T
Configurations
053-392-20-000: Base system with 23" mounting
053-392-20-010: System mounted in 22RU (½ height) battery mount rack
053-392-20-020: System mounted in 44RU Zone 4 seismic rack
053-392-20-030: System mounted in 44RU Zone 4 seismic rack with 3x battery trays for 3x 48V strings
rectifier: Up to 11 x 48V-3.6kW rectifier positions
Distribution:
38x AM plug-in breaker positions 10x GMT type fuse positions Shunt Low voltage disconnect
controller: CXCM4 modular controller
Electrical
input Voltage: 176 to 320Vac
current: 16.8A @ 240Vac nominal (per rectifier module)
Frequency: 45 to 66Hz
Power Factor: >0.99
output Voltage: 42 to 60Vdc
current:System:825A (expandable to 1200A with additional CXRF shelf) Rectifier:75A@48Vdc
Power:System:39.6kW (expandable to 57.6kW with additional CXRF shelf) Rectifier:3600Wmax
Environmental
Temperature:-40 to 65°C / -40 to 146°F -40 to 75°C / -40 to 167°F derated output
Humidity: 0 to 95% non-condensing
elevation:-500 to 2800m / -1640 to 9186ft -500 to 4000m / -1640 to 13124ft with derated output
Mechanical
Dimensions (in/mm): 29.7 x 23 x 18.8 / 755 x 584 x 477
Mounting: 23" center mount
weight (lb/kg): 155 / 70.3
Connections
load breaker:Hot:¼"-20studson⅝" centers Return:¼"holeson⅝" centers
gMT Fuses: Screw terminal 1.31mm2 to 0.128mm2 (#16 to #26 AWG)
battery Terminations:⅜" holes on 1" centers 4x Sets per polarity
rectifier input: ⅜" holes on 1" centers
alarm connections: Screw terminal 1.31mm2 to 0.128mm2
(#16 to #26 AWG)
access:Cable:toporbottom User:frontaccessafterinstallation
Related Components
010-567-20: Cordex 48V-3.6kW rectifier
038-276-20: CSM02 DC-DC converter kit
CXPS 48-2T Internal Distribution
CXPS 48V 825A
22
DC
Co
nver
ters
cSM01 and cSM02Modular DC to DC Converters
> 48Vdc to 24Vdc, 10A output
> 24Vdc to 48Vdc, 5A output
> Accommodates up to six, 10A power modules per system
> Isolated input and output
> Optional supervisory control module
> Scalable hot plug-in operation
> Convection cooled
cSM01 and cSM02 nominal Specifications
Noise
Voice band: <22dBrnC
wide band:<10mVrms (10kHz to 10MHz), <150mVp-p (10kHz to 100MHz)
acoustic: 45dBA at 1m (3ft)
Environmental
Temperature:0 to 50°C / 32 to 122°F with specified ventilation, -40 to 50°C / -40 to 122°F (optional)
Humidity: 0 to 95% non-condensing
elevation: -500 to 2800m / -1640 to 9186ft
Features
indicators:
Power on Output over voltage protection trip Bar graph output current Converter fail Current limit Circuit breaker trip
alarms:Converter fail alarm* Circuit breaker trip alarm*
adjustments: Output voltage
Distribution Fuse
indicators: Output fuse fail
alarms: Output fuse alarm*
Fuse block: 8 position 0 to 10A GMT fuses (50 and 60A versions), 4 position 0 to 10A GMT fuses (20A version)
connections: Terminal block 0.75 mm2 to 4 mm2 (#18 to #12 AWG)
Protection:
Input fuse Input inrush current limiting Over temperature limiting Input high and low voltage shutdown Output paralleling diode Current limit/short circuit protection
Analog Supervisory
indicators:
System over voltage protection trip System high voltage alarm Majoralarm System low voltage alarm Test mode Digital voltmeter/ammeter
alarms:Majoralarm* Low voltage alarm* High voltage alarm*
adjustments:
Over voltage protection High voltage alarm Low voltage alarm Test/normal selector
* Jumper selectable form A/B contacts
Mechanical
input/output: Two ¼" studs on ⅝" centers
alarm/control: Terminal block, 0.5mm2 to 1.5mm2 (#20 to 16AWG)
10A (2 Module Horizontal 19")
weight (lb/kg): 18.5/8.4 w/ 2 power modules
Dimensions (in/mm): 3.5 x 17 x 12 / 90 x 432 x 305
15A (3 Module Horizontal 23")
weight (lb/kg): 24/10.9 w/ 3 power modules
Dimensions (in/mm): 3.5 x 20 x 12 / 90 x 508 x 305
20A (2 Module Horizontal 19"
weight (lb/kg): 18.5/8.4 w/ 2 power modules
Dimensions (in/mm): 3.5 x 17 x 12 / 90 x 432 x 305
25A (5 Module Horizontal 19")
weight (lb/kg): 36/16.6 w/ 5 power modules
Dimensions (in/mm): 7 x 17 x 12 / 178 x 432 x 305
30A (6 Module Horizontal 23")
weight (lb/kg): 43/19.5 w/ 6 power modules
Dimensions (in/mm): 7 x 20 x 12 / 178 x 508 x 305
30A (3 Module Horizontal 23")
weight (lb/kg): 24/10.9 w/ 3 power modules
Dimensions (in/mm): 3.5 x 20 x 12 / 90 x 508 x 305
50A (5 Module Horizontal 19")
weight (lb/kg): 36/16.6 w/ 5 power modules
Dimensions (in/mm): 7 x 17 x 12 / 178 x 432 x 305
60A (6 Module Horizontal 23")
weight (lb/kg): 43/19.5 w/6 power modules
Dimensions (in/mm): 7 x 20 x 12 / 178 x 508 x 305
Electrical
input Voltage: 20 to 30Vdc 40 to 60Vdc
output Voltage: 44 to 52Vdc 22 to 26Vdc
output current: 5A 10A
efficiency: >85% (100% load) >85% (100% load)
regulation:-1%, ±0.1% load (static), ±0.1% line (static), <2%
deviation for 50 to 100% load step (dynamic)
response Time: 2 ms to 0.1% of output for 50 to 100% load step
Standards
en: 55022 - Class A (radiated)
Fcc: Part 15 Class A (radiated)
CSM02
23
Distribution centers
> Various modular distribution configurations
> Complete front access
> Integrated Cordex™ system controller
> Integrated shunt and LVD options
> AM plug-in breaker, GJ breaker and GMT fuse options
Distribution Panel overview
Part Number
Fuse Position
Fuse Type
Breaker Position
Breaker Type
Capacity MountingFront Access
RUAdditional Options
universal Distribution centers
020-584-20 16* TPS* 16AM Plug-In
400A 19/23 Partial 4Controller, LVD, Shunt, Batt Disconnect
Vista Distribution centers
020-645-2020-24* 10
TPS* GMT
20-24AM Plug-In**
800A 23 Yes 7Controller, LVD, Shunt
020-646-2040-48* 10
TPS* GMT
40-48AM Plug-In**
1000A 23 Yes 9Controller, LVD, Shunt
020-635-2080-96* 10
TPS* GMT
80-96AM Plug-In**
2000A 23 Yes 17Controller, LVD, Shunt
Modular Distribution Tier Options
Single Voltage:
24 Position AM plug-in (TPS plug in available) 20 Position AM plug-pn w/ 600A LVD 3 Position GJ 3 Position GJ w/ 600A LVD
Dual Voltage:
12x Primary and 10x secondary (AM plug-in) 16x Primary and 6x secondary (AM plug-in) 8x Primary (w/ LVD) and 10x secondary (AM plug-in) 12x Primary (w/ LVD) and 6x secondary (AM plug-in)
Notes:* TPS Fuses with AM plug-in breaker cartridges may be used as alternative to breakers** Compatible with multiple pole AM plug-in breakers (110 to 250A)
Vista Two Tier UDC
Universal Distribution Center
DC
Distrib
utio
n Cen
ters
24
DC
Acc
esso
ries
Dc accessories
gMT Fuse Panels
GMT 50 Series
19"/23" rackmount, 1RU highFlush mount and center positionsStandardcapacity:50AperinputBright, color coded LED indicators for A/B input power status, A/B fuse failure alarmsForm-C alarm contacts for A/B input power fail, A/B fuse fail (4 relays)Singleinputanddualinput: •10GMToutput •10A/10Boutput •20GMToutput
GMT 100/High Capacity Series
19"/23" rackmount, 1RU highFlush mount and center positionsBright, color coded LED indicators for A/B input power status, A/B fuse failure alarmsSingle input, A/B insolated input and A/B/C redundant configuration availableIncluded LED indicators, form-C alarm contacts
100 SeriesHighpowerdensityandampacity: •100Aperinput:(singleinput,A/Binput) •70A:(A/B/C-source)Form-C alarm•16GMToutputs •16A/16BGMToutputs C-output diode routed, 32 fused redundant outputs
High capacity Series24 GMT fuse sockets150A input bus ratingConfigurationsinclude:•Singleinput,24fuses•A/Binput,12A/12B fuses, A/B/C version, 24 fuses
TPA Fuse Panel
1RU, 19"/23" rackmountSingle input, A/B isolated input and A/B/C redundant configurations available12 TPA fuse sockets200A input bus ratingIncludes LED indicators, form-C alarm contacts
curcuit breaker Panel
KTK Fuse Panel
19"/23" rackmount, 1RU highHigh power densityHighampacity:120AperA/BinputBright, color coded LED indicators for A/B input power status, A/B fuse failure alarmsForm-C alarm contacts for A/B input power fail, A/B fuse fail (4 relays)Dualinput:4A/4BandKTK30Afuseoutputs
HDDC: High Density
19"/23" rackmount, 3RU highSingle inputA/B isolated inputA/B inputC-output redundant diode routedHigh breaker count to support VOD server redundant power supply circuit requirements and combined high current loadHighpowerdensityandampacity: •200Aperinput:(singleinput,A/Binput) •200Acombinedload:(A/B/C-source)Accepts up to 22 plug-in bullet terminal circuit breakersAlphanumeric LCD display for voltage, load current per bus, breaker status Form-CalarmcontactsforMajorandMinoralarms
> Rackmount power sources including integrated distribution fuses save space and provide flexibility
> Distribution systems from 50A GMT fuse panels to 800A circuit breaker distribution centers
> 19"/23" universal rackmount
HDDC:HighDensity
25
DC
Accesso
ries
Dc accessories
DCX Series
400, 600, 800, 1000 and 1200A modelsDirect Battery Terminal mounting options for most battery configurations. Bus adapter and hardware kits provided for individual battery cell size configurations.LED indicators for On Line/Off Line status, EPO trip and general fault alarm statusForm-C relay contact output for remote monitoring of statusIntegrated EPO function for remote trip
Super HDX
2RU, 19"/23" rackmountSingle input, A/B insolated input configurations available300A input bus ratingUses AM series bullet terminal circuit breakers (Breaker choices available from 5A to 100A)16 circuit breaker positionNo GMT fuses (unlike standard HDX)Targeted at Cisco 7609 installations
Matrix Breaker Panel
1RU, 19"/23" rackmountSingle input, A/B insolated input and A/B/C redundant configurations available200A input bus ratingUsesnew“slimline”1RUcircuitbreakers(Breakerchoicesavailablefrom 5A to 100A)Includes LED indicators, form-C alarm contactsConfigurationsinclude:•Singleinput,20breakers•A/Binput,10A/10Bbreakers,A/B/Cversion,16breakers
HDX Compact
19"/23" rackmount, 2RU highSingle inputA/B isolated inputHighpowerdensityandampacity: •300Aperinput:(singleinput,A/Binput) •300Acombinedload:(A/B/C-source) •Acceptsupto12plug-inbulletterminalcircuitbreakersStandard unit includes front panel with A and B input LED indicators and breaker/fuse trip indicator LEDForm-CalarmcontactsforMajorandMinoralarms
> Compact, high power density DC distribution fuse panels and circuit breaker panels
> High current, high fuse/breaker count in a small RU footprint
> Battery disconnect for circuit breaker protection of the entire facility DC plant
HDX Compact
27
Batteries
Headend BatteriesAlpha’s Headend battery line includes three distinct types of models: 20-year batteries, 10-year
telecom front and top terminal, and flame retardant UPS batteries. These batteries provide
improved performance, longer runtimes and extended service life. The front terminal models allow
for easier access to the batteries during installation and routine maintenance. Alpha’s Headend
batteries are ideal for broadband, cellular, electric utility, PCS, customer premise, long distance
and distributed power.
> AlphaGuard™
AlphaGuard monitors and protects your batteries by spreading the charge voltage equally across all
the batteries in the string, ensuring that every battery, whether old or new, is properly charged. With an
ideal voltage across each battery, life and runtime are optimized. Individual batteries in a string can be
replaced as they fail, allowing batteries to be left in service longer.
> Battery Testing EquipmentA fast, reliable and affordable testing process is now available with the development of conductance
based battery measurement technology. By coupling conductance testing with a simple utility load
test, the system operator is armed with the quality of data necessary to know the status of their
installed standby batteries and budget their replacement with confidence.
28
Bat
teri
es
Headend batteries
> 20-year design life batteries with VRLA technology
> 10-year design life batteries with front or top terminals
> High rate flame retardant AGM UPS batteries for all standby applications
10 and 20 year life batteries
C&D MS Endur 345 to 2038Ah
Part number# cells/Module
# Plates/cell
nom ah cap(8hr)
System # of cells
System Voltage
Model Volts
Dimensions (in/mm)weight(lb/kg)
cell layout w x H
raa64024ce01 3 7 345 24 48 6 21.4 x 44.7 x 23.1 / 545 x 1136 x 587.5 1970 / 894 6 X 4
rbb46024ce01 3 9 480 24 48 6 18.7 x 64.5 x 23.1 / 476 x 1642 x 587.5 2470 / 1120 4 X 6
rbb64024ce01 3 9 480 24 48 6 26.1 x 44.7 x 23.1 / 664 x 1136 x 587.5 2410 / 1093 6 X 4
rcc46024ce01 3 11 599 24 48 6 21.4 x 64.5 x 23.1 / 545 x 1642 x 587.5 2920 / 1324 4 X 6
rDF38024ce01 3 15 839 24 48 6 30.4 x 44.7 x 23.1 / 773 x 1136 x 587.5 2850 / 1293 3 X 8
rDF46024ce01 3 15 839 24 48 6 21.4 x 84.4 x 23.1 / 545 x 2148 x 587.5 3860 / 1751 4 X 6
reH38024ce01 3 19 1079 24 48 6 27.9 x 64.5 x 23.1 / 708 x 1642 x 587.5 3790 / 1719 3 X 8
reH46024ce01 3 19 1079 24 48 6 26.1 x 84.4 x 23.1 / 664 x 2148 x 587.5 4740 / 2150 4 X 6
rFK38024ce01 3 23 1319 24 48 6 33.5 x 64.5 x 23.1 / 850 x 1642 x 587.5 4670 / 2118 3 X 8
rFK46024ce01 3 23 1319 24 48 6 30.4 x 84.5 x 23.1 / 773 x 2148 x 587.5 5620 / 2549 4 X 6
rHP38024ce01 3 27 1559 24 48 6 39.5 x 64.5 x 23.1 / 1004 x 1642 x 587.5 5550 / 2517 3 X 8
rHP46024ce01 3 27 1559 24 48 6 34.4 x 84.4 x 23.1 / 875 x 2148 x 587.5 6550 / 2971 4 X 6
rJS38024ce01 3 35 2038 24 48 6 45.5 x 64.5 x 23.1 / 1157 x 1642 x 587.5 6540 / 2966 3 X 8
rJS46024ce01 3 35 2038 24 48 6 43.6 x 84.4 x 23.1 / 1108 x 2148 x 587.5 8320 / 3774 4 X 6
East Penn Unigy II 760 to 2000Ah
Part number# cells/Module
# Plates/cell
nom ah cap(8hr)
System # of cells
System Voltage
Model Volts
Dimensions (in/mm)weight(lb/kg)
cell layout w x H
24aVr95-17 3 17 760 24 48 6 21.9 x 68.3 x 27.1 / 556 x 1735 x 689 3260 / 1479 3 x 8
24aVr95-19 3 19 855 24 48 6 24.2 x 68.3 x 27.1 / 613 x 1735 x 689 3612 / 1638 3 x 8
24aVr95-21 3 21 950 24 48 6 26.4 x 68.3 x 27.1 / 671 x 1735 x 689 3956 / 1794 3 x 8
24aVr95-23 3 23 1045 24 48 6 28.7 x 68.3 x 27.1 / 728 x 1735 x 689 4308 / 1954 3 x 8
24aVr95-25 3 25 1140 24 48 6 30.1 x 68.3 x 27.1 / 785 x 1735 x 689 4652 / 2110 3 x 8
24aVr95-27 3 27 1235 24 48 6 33.2 x 68.3 x 27.1 / 842 x 1735 x 689 4972 / 2255 3 x 8
24aVr95-29 3 29 1330 24 48 6 35.4 x 38.3 x 27.1 / 899 x 1735 x 689 5348 / 2426 3 x 8
24aVr95-31 3 31 1425 24 48 6 37.7 x 68.3 x 27.1 / 956 x 1735 x 689 5668 / 2571 3 x 8
24aVr95-33 3 33 1520 24 48 6 39.9 x 68.3 x 27.1 / 1013 x 1735 x 689 6020 / 2737 3 x 8
24aVr125-33 2 33 2000 24 48 4 53.2 x 71.4 x 28.6 / 1351 x 1814 x 727 8616 / 3908 (2x6)x2
Note:Add“S”forStandardPolypropyleneor“L”forFlameRetardantPolypropylenes,suffixtomodulenumber.(ex.24AVR95-17-S)
GNB Absolyte IIP 696 to 1600Ah
Part number# cells/Module
# Plates/cell
nom ah cap(8hr)
System # of cells
System Voltage
Model Volts
Dimensions (in/mm)weight(lb/kg)
cell layout w x H
100a-15 3 15 696 24 48 6 22.2 x 72.7 x 26.4 / 563 x 1846 x 670 2992/1357 3 x 8
100a-17 3 17 800 24 48 6 24.5 x 72.7 x 26.4 / 622 x 1846 x 670 3392/1539 3 x 8
100a-19 3 19 896 24 48 6 26.8 x 72.7 x 26.4 / 679 x 1846 x 670 3760/1706 3 x 8
100a-21 3 21 1000 24 48 6 29 x 72.7 x 26.4 / 737 x 1846 x 670 4120/1869 3 x 8
100a-23 3 23 1096 24 48 6 31.3 x 72.7 x 26.4 / 794 x 1846 x 670 4488/2036 3 x 8
100a-25 3 25 1200 24 48 6 33.5 x 72.7 x 26.4 / 851 x 1846 x 670 4864/2206 3 x 8
100a-27 3 27 1296 24 48 6 35.8 x 72.7 x 26.4 / 908 x 1846 x 670 5224/2370 3 x 8
100a-29 3 29 1400 24 48 6 38 x 72.7 x 26.4 / 965 x 1846 x 670 5632/2555 3 x 8
100a-31 3 31 1496 24 48 6 40.3 x 72.7 x 26.4 / 1022 x 1846 x 670 6000/2722 3 x 8
100a-33 3 33 1600 24 48 6 42.5 x 72.7 x 26.4 / 1080 x 1846 x 670 6360/2885 3 x 8
Note:Add“L”forFlameRetardantPolypropylenes,suffixtomodulenumber(ex.100A-31-L).
MsEndur
29
Batteries
Headend batteries
> Take advantage of your cable buying power on batteries
> Alpha offers cable companies the most competitive pricing on UPS and DC plant batteries including C&D, GNB and East Penn 10 and 20 year VRLA batteries
> Alpha Technical Services offers removal, replacement and recycling of UPS Batteries
> Most UPS brands serviced
Front and Top Terminal batteries
East Penn ET Series
Part number Model Volts capacity @ 8hr rate @ 1.75V/c Dimensions (in/mm) weight (lb/kg) Terminal Type
12aVr100-3eT 12 96 20.1 x 4.3 x 9.4 / 510.5 x 109.2 x 238.7 75 / 34 Threaded Insert
12aVr150-eT 12 150 22 x 4.9 x 11.75 / 558.8 x 124.5 x 298.5 115 / 52 Threaded Insert
GNB Marathon
Part number Model Volts capacity @ 8hr rate @ 1.75V/c Dimensions (in/mm) weight (lb/kg) Terminal Type
M12V90FT 12 90 156 x 4.1 x 10.6 / 395 x 105 x 270 68 / 31 Threaded Insert
M12V105FT 12 104 20.1 x 4.3 x 9.4 / 511 x 110 x 238 79 / 35.8 Threaded Insert
M12V125FT 12 125 22 x 4.9 x 11.1 / 559 x 124 x 283 105 / 47.6 Threaded Insert
M12V155FT 12 155 22 x 4.9 x 11.1 / 559 x 124 x 283 119 / 53.8 Threaded Insert
AlphaCell™ SMU-F
Part number Model Volts capacity @ 8hr rate @ 1.75V/c Dimensions (in/mm) weight (lb/kg)Top access Stud Hole Size
Front access Stud Size
SMu12-155Fr 12 150 21.9 x 4.9 x 11.1 / 558 x 125 x 283 119 / 54 8mm 6mm
SMu12-170Fr 12 172 21.9 x 4.9 x 12.2 / 558 x 124 x 310 129.8 / 59 8mm 6mm
Tel Series 10 Year Batteries - Top Terminal
Part number Model Volts capacity @ 8hr rate @ 1.75V/c Dimensions (in/mm) weight (lb/kg) Terminal Type
Tel12-30 12 30 7.8 x 5.2 x 6.8 / 197.4 x 131.9 x 172.7 27 / 12 Threaded Insert
Tel12-45 12 46 8.9 x 5.4 x 8.1 / 228.3 x 138.9 x 205.6 40 / 18 Threaded Insert
Tel12-70 12 69 10.3 x 6.8 x 8 / 260.5 x 173.4 x 203.6 55 / 25 Threaded Insert
Tel12-80 12 79 12.0 x 6.8 x 8.1 / 305.8 x 173.4 x 205.3 68 / 31 Threaded Insert
Tel12-90 12 88 13.5 x 6.8 x 8.5 / 343.1 x 171.7 x 216.2 72 / 33 Threaded Insert
Tel12-105 12 102 20.1 x 4.3 x 9.4 / 511 x 110 x 238 79 / 36 Threaded Insert
Tel12-125 12 127 13.6 x 6.8 x 10.9 / 344.7 x 171.7 x 277.7 100 / 45 Threaded Insert
Note:SLCversionsavailablewithCableAssemblyTerminalType.Modelnumbersinclude/SLCafterthemodel(ex.Tel12-30/SLC)
AGM UPS - Flame Retardant High Rate Series
Part number Model Volts watts per cell Dimensions (in/mm) weight (lb/kg) Terminal Type
uPS12-100Mr 12 91 6.5 x 5.2 x 6.9 / 166.2 x 131.3 x 174.3 21 / 10 Flag terminal
uPS12-150Mr 12 148 7.8 x 5.2 x 6.8 / 197.1 x 131.9 x 172.7 27 / 12 Threaded Insert
uPS12-210Mr 12 206 9.0 x 5.5 x 8.1 / 228.6 x 139.2 x 205.1 40 / 18 Threaded Insert
uPS12-300Mr 12 300 10.3 x 6.8 x 8.0 / 260.9 x 173.4 x 203.5 57 / 26 Threaded Insert
uPS12-350Mr 12 350 12.0 x 6.8 x 8.1 / 305.8 x 173.4 x 204.8 67 / 30 Threaded Insert
uPS12-400Mr 12 400 13.4 x 6.8 x 8.5 / 340.9 x 172.7 x 216.4 74 / 34 Threaded Insert
uPS12-490Mr 12 488 13.6 x 6.8 x 10.9 / 344.7 x 172.7 x 277.7 10 / 45 Threaded Insert
uPS12-540Mr 12 537 12.6 x 6.9 x 8.9 / 320.8 x 177 x 227.2 100 / 45 Threaded Insert
uPS6-620Mr 6 620 12.6 x 6.9 x 9.9 / 321 x 177 x 253 72 / 33 Threaded Insert
12AVR100-3ET
30
alphaguard
Models
ag-cMT-4: AlphaGuard Charge Management SC, 48V —including 48Vdc battery string interface cable
Configuration
Quantity: One (1) AlphaGuard is required per battery string
Service location: With the battery string
Mechanical
Housing Material: High impact plastic
Dimensions (in/mm): 1.44 x 4.82 x 4.25 / 36 x 122 x 108
weight (lb/kg): 0.8 / .36
Electrical
batteries: Individual 12Vdc nominal batteries configured into 36 or 48Vdc strings
circuit Protection: Single blow fuse, reverse polarity protected
environmental: -40 to 55°C / -40 to 131°F, 5 to 95% humidity
Quiescent current Draw: 1mA max (Current consumed by AlphaGuard after low voltage total shutdown)
charge Management: Most effective during float period of charge
Max current: 2A @ 25°C / 77°F
Quality of Final balance: ±100mV max between any two (2) batteries
charging efficiency: 80 to 90%
charge balance: ±100mV typical
low Voltage cutoff: 34.5Vdc/46Vdc ±5%
communication to XM2: AlphaGuard configured DSM status monitoring card
Voltage Sense regulation: ±100mV
warranty: 5 years
The AlphaGuard employs a patented Charge Management
Technology (CMT) to shuttle excess charge current to batteries
requiring a greater charge. The entire unit is contained in a
small plastic enclosure that installs directly on top of one the
batteries in the string. A short service cable connects the
AlphaGuard to each of the batteries in the string. One
AlphaGuard is required per string.
An AlphaGuard configured with the optional voltage sense
cabling and interface module (DSM, ESM, EDSM or External
DOCSIS®) allows the AlphaGuard to interface with a status-
monitoring module. Two AlphaGuard modules can be
connected to an interface module. Refer to individual interface
module documentation for additional information.
alphaguard™
Battery Charge Management System
> Extends battery life
> Replace single batteries, not the entire string
> Spreads charge voltage equally across batteries
> Compensates for battery differences as they age
> Safe unattended operation designed to CSA C22.2 No. 107.1 and UL 1778 standards
> Optional Potted AlphaGuard available
Optional Battery Cable
48V 6ft
AlphaGuard CMT-4
Bat
teri
es
31
Batteries
battery Testing equipmentAlphaCell™ Battery Testing Equipment
> Complete battery life trending through conductance tests
> Non-intrusive conductance measurements do not reduce string life
> Quick, accurate measurements and data recording reduce on-site time
> Simple pinpoint testing requires only access to two battery posts or straps
> Enables early detection of questionable batteries in the network
battery Testing equipment
Model: Celltron Ultra Celltron Advanced™
Model number:CTU-6000 (w/ temp. sensor)
CTA-4000 (kit) CTA-2000 (analyzer only)
applications:
Tests individual lead acid cells or monoblocs (up to 16V) in any common configuration, approximately 10-6000Ah
Tests individual lead acid cells or monoblocs (up to 16V) in any common configurations
Voltage: 1.5 to 20Vdc 1 to 20Vdc
conductance: 100 to 19990 Siemens 100 to 19990 Siemens
Test Data Storage:500 string locations of 480 test results stored internally
16 string locations of 480 test results stored internally
accuracy: +2% across test range +2% across test range
Voltmeter resolution: 5mVdc 5mVdc
environmental: 0 to 40°C / 32 to 104°F, 95% non-condensing
Conductance Technology/Industry Approvals and Recommendations:
IEEE Standards 1188 and 484EPRI Guide for testing stationary batteries International Telecommunications Energy ConferenceBellcore T1Y1Presentation for American National Standards InstituteInternational Lead Zinc Research OrganizationBattery Council International
Applications
Cable TV/Broadband Power Networks
•OutsidePlantBatteries•HeadendDC/ACBatteries•PremiseBackup Supplies (FTTx)
6/12V, 5 to 600Ah Stationary Batteries
Security system batteries
Emergency lighting batteries
Features and Benefits
Simple - One-steptesting,noinstrumentinputsoradjustmentsrequired.
Quick - Battery voltage and conductance displayed in less than 10 seconds.
Test an entire 48V string in less than 1 minute.
Safe - Utilizes patented conductance technology, a passive method that
minimizes technician risk.
accurate - Field test proven to ±2% accuracy across test range. Conductance
method recognized by IEEE standard for the testing of lead-acid batteries with
proven correlation to battery capacity.
economical - Efficient and accurate battery tester priced to fit into every
technician’s tool kit.
Kit contents
Celltron Ultra Kit CTA-6000AT Celltron Advanced Kit CTA-4000ATcontains:Digital multimeterInfrared strip printerLighted probesClamps and probes
contains:Protective bootRechargeable battery packInfrared PC data receiver and softwareInfrared printerInfrared temperature sensorProtective carrying caseBoth clamp and probe cablesSpare fuses, printer paper, probe tips
Optional Equipment:
Handheld PrinterInfrared Module for PC
Celltron UltraCTU-6000
33
DC
to A
C Inverters
DC to AC InvertersAlpha Technologies offers a full line of modular inverter systems providing a new level of scalability, maintainability, compactness, reliability and performance. Alpha’s scalable DC to AC inverter is recognized as the industry standard for critical AC power by many of the world’s leading communications companies.
> SMI 3300 Inverter SeriesSMI 3300 inverter modules are hot swappable and readily accessible, leading to an extremely low mean time to repair and easy system expansion for increased power and/or redundancy. Advanced PWM switchmode technology as well as thorough input and output filtering results in a highly efficient, compact and quiet telecom grade inverter system with excellent dynamic response characteristics.
> TEBEVERT Inverter SeriesThe TEBEVERT DSP inverter system featuring Digital Signal Processing technology can be used in a wide array of telecommunications and industrial applications. The introduction of enhanced DSP controls and higher semi-conductor switching frequencies improves power density and operating efficiency while dramatically reducing physical size and weight.
> INEX Inverter SystemINEX inverter series is an integrated telecommunication power system, including inverter, static switch, LCDdisplaycontroller,andinterfacemodules.Withversatile“buildingblock”designandN+1redundant configuration, the INEX inverter system facilitates complex telecommunication and industrial power demands and provides ultimate flexibility for your current and future requirements. N+1 parallel redundancyallowspowercapacityexpandableupto24kVA.INEX“allmaster”dynamicmechanismautomatically shares and re-organizes critical loads to prevent interruption should any inverter module fail. The DSP-microprocessing controller gives real-time system status through comprehensive LCD display, and allows program settings through the display panel. With a communication interface module installed, you can further control and monitor the system remotely.
> S4 Inverter SeriesAlpha’s S4 3.5kVA inverter power modules can be stacked in an N+1 redundant configuration for optimum reliability up to 21kVA. This modular scalability makes the S4 ideal for overlay applications wherefuturepowergrowthisanticipated.Allmodulesarepackagedintoa“hotswap”receivercabinetallowing rapid and safe exchange of any component without interruption to the critical load.
> DSP Inverter SeriesThe DSP inverter system is designed to address the critical AC powering requirements of telecommunications applications, Voice over Internet Protocol (VoIP) and servers. The system can be scaled in 1kVA or 2.5kVA increments up to 27.5kVA in an N+1 redundant configuration. These units have been NEBS Level 3 Certified by a nationally recognized testing lab to meet the stringent requirements of the telecommunications industry.
> S5 Inverter SeriesAlpha’s S5 is designed for telecommunication, IT and industrial applications. The S5 inverter packs 1500W of power into a light and compact package that is 19" rackmountable and 1RU, with four models for different input (24 and 48Vdc) and output (115 and 230Vac) voltage combinations. Features include an integrated controller and an optional internal Static Transfer Switch, enabling flexible and scalable systems for true plug and play with no external subsystems needed.
> MS Power Inverter SeriesMS Inverters feature an integrated utility bypass, and can be cascaded for redundancy. Designed for long mean time between failure, these inverters provide the dependable AC power your networks demand. The compact 2RU mounting package makes this model the right selection for limited space applications. These intelligent, dependable inverters provide economical AC power for all of your network needs.
34
SMi 3300 inverter Series3.3 to 52.8kVA Inverter System
> Scalable system size from 3.3 to 52.8kVA
> Hot swappable and readily accessible
> Advanced PWM switchable technology
SMi 3300 inverter Series
Electrical
output waveform:True sine wave, <1% distortion (unity PF) <3% distortion(3:1crestfactortestload)
output Voltage/frequency
SMi-3300-12060: 120Vac/60Hz nominal
SMi-3300-24050: 240Vac/50Hz nominal
output Power:3300VA / 2750W, with 120% continuous overload capability
load-line regulation: Within ±2.5% combined
crest Factor Handling: 3:1
input Voltage: -48Vdc nom; accepts 42 to 60Vdc range
input current: Nominalfullload:60A@54Vdc
battery Feedback noise: <30dBrnC
efficiency: >90% from 50 to 100% full load
Protection :
Reverse DC polarity protection, output short circuit/ over current protection, over temperature, DC input magnetic circuit breaker, DC input low voltage shutdown
leD indicators:Battery On/Reversed, Inverter On/Fail, Tri-level inverter loading indicator
approvals:UL 1778 Listed, CE Mark on 50Hz version FCC Class A subpart 15J, EN55022 Class A
Mechanical
Module Dimensions (in/mm): 5.13 x 9.38 x 14.25 / 130 x 238 x 362
Mounting: “MSeries”cageassemblies
Module weight (lb/kg): 20.5 / 9.3
Finish: Black fine texture powder coat
Environmental
operating Temperature: 0 to 50°C / 32 to 122°F (Forced-air fan cooling)
Humidity: 0 to 95% non-condensing
elevation: 3000m / 10000ft before derating
noise: <51dBA at 1 meter
Heat output: 1403BTU/hr per module at full load
Cage Assemblies and Other Inverter System Components
Cages to Fit in Any 19/23" Rack Space
“M Series” cage assemblies are available that house up to 2, 3, or 4 SMi3300 inverter modules. The M6.6 is a low profile, 23" rackmount, module unit. The M9.9 is a 19" rackmount, 3 module unit and the M13.2 is a 23" rackmount, 4 module unit. all cage assemblies are 22" (559 mm) deep.
Fully Equipped Single Cage Inverter Systems
The “-F” cage assemblies are fully equipped with automatic bi-directional transfer logic, a fast “eTS” transfer switch and alarm logic to comprise a single cage inverter system. all Dc input, ac in/out and alarm connections are made via rear access terminal blocks and connections in the “-F” cage assemblies. alarm outputs include inverter Module Failure, overload and Transfer Switch Status. The following single phase fully equipped cages are available: M6.6- 12060-F, M9.9-12060-F and M13.2-12060-F. a dual phase split-cage system can be configured (specify M13.2-24060-F). it accommodates single and dual phase loads together.
Multi-Cage Inverter Systems
The “-S” cage assemblies, M9.9-12060-S and M13.2-12060-S, are not equipped with a transfer switch or alarm logic. They are used with a junction control panel or transfer and metering panel which combines the ac output from all cages in multi-cage systems. The system transfer, metering and alarm functions are located in these panels. Single phase systems can utilize up to 3 “-S” cage assemblies for a maximum capacity of 39.6kVa. Dual phase systems can utilize either 2 or 4 “-S” cage assemblies for a capacity of up to 52.8kVa. The l1-n-l2 output will accommodate single phase 120Vac and dual phase 240Vac loads together.
SMI 3300
DC
to
AC
Inve
rter
s
SMI 3300 Inverter System
35
DC
to A
C Inverters
TebeVerT inverter Series5 to 25kVA Inverter System
> NEBs level 3 certified to assure compatibility with the telecommunications environment
> Hot swap 5kVA inverter modules
> Hot swap static switch module
> Integrated maintenance bypass switch
> Automatic master-slave operation
> Up to five inverter modules can be paralleled as load increases
TebeVerT DSP inverter Series
60Hz Models
output capacity: 5 to 25kVA
Maximum number of Modules: 5
Input
nominal bypass ac input: 120Vac 208, 220, 240, 480Vac
number of bypass ac Phases:
1 2
bypass ac input wiring: L, N, PE L1, L2, PE
nominal Dc input: -48Vdc or 120Vdc (requires different inverter modules)
Dc input range: -15% +20%
reflected Dc ripple (48Vdc) (120Vdc):
<2mV reverse smoothing, <5% RMS
<2mV reverse smoothing, <5% RMS
Output
nominal ac output Voltage: 120Vac 120Vac
optional ac output Voltage: 120/240Vac 120/240Vac
output Voltage regulation: ±5% for all combinations of line, load and temperature
output Power Factor: 0.7 lagging to 0.8 leading
output Voltage waveform: PWM Sine wave PWM Sine wave
output crest Factor: 2.8:1 2.8:1
output Voltage Distortion: <3% @ 100% rated linear load
output overcurrent Protection: Electronic current limiting
overload rating (inverters): 200% for approx. 75 cycles (1.25 seconds)
overload rating (Static bypass): 500% for 100ms 500% for 100ms
System operating efficiency: >85% (on-line mode) / >97% (off-line mode)
Frequency Stability: ±0.1% free running, ±3% when AC present
Module capacity: 5kVA/4kW 5kVA/4kW
Static Switch Transfer Time: <2ms <2ms
60Hz Models
120, 208, 220, 240, 480Vac
output capacity: 5 to 25kVA
cooling: Temperature controlled fans
Maintenance bypass Switch:
Standard make-before-break mechanically interlocked switch provided on all models equipped with the static bypass module
remote alarming:(1) Form-C Summary Alarm, Optional Relay Card (8 Alarms), Optional SNMP
leD indicators (inverter Modules):
Output present, fault, overload, AC synchronized, parallel operation
leD indicators (Static bypass Module):
Power flow diagram, normal, fault, AC present, DC present, overload, load on bypass, load on inverter
Metering:(4) segment LCD display switchable between output voltage and current
cabinet Dimensions (in/mm): 84 x 23.6 x 23.6 / 2134 x 600 x 600
Standards
radio interference: Certified to Telecordia GR-1089
Safety listing: UL60950, UL, cUL Pending
Product certification: NEBS Level 3
Environmental
Seismic rating: NEBS Level 3, Seismic Zone 4 Optional
elevation: 1800m / 6000ft, 4000m / 1300ft at 30°C/86°F
operating Temperature: -5 to 50°C / 23 to 122°F
operating Humidity: 0 to 95% non-condensing
Module Data: 5kVA
Power rating: 5000VA / 4000W
nominal input current (-48Vdc): 98A
Max. input current (-48Vdc): 115.4A
output current (120Vac): 41.6A
TEBEVERT DSP
36
DC
to
AC
Inve
rter
s
> Hot-pluggable operation allows module addition or removal without powering down
> High power density and high efficiency (89%)
ineX System 48V Modular inverter System
Electrical
Inverter Module DC Input
nominal Voltage: 48Vdc
operating range: 40.5Vdc to 58Vdc
input Protection: Reverse Polarity Protection
Psophometric noise Voltage: <1.0mV ITU-T O.41 (16.66~6000Hz)
Inverter Module AC Output
Power rating: 1000VA / 800W, 1500VA / 1200W
waveform: Pure sine wave
Power Factor: 0.8
nominal output Voltage: 110/115/120Vac, 208/220/230/240Vac
Voltage Variation: Max ±2%
output Frequency: 50/60Hz
crest Factor: 3:1
THD:<3%, linear load<5%, non-linear load
efficiency: Min 89%
isolation ac-enclosure: Basic isolation (Pri-Gnd) 2121Vdc/1min
Dynamic response: <±10%
over load Protection:1.5*Inom >20s1.25*Inom temperature controlled
STS Module Input
over Voltage Threshold:
120Vac-Adjustablebetween127 to 138Vac, default 132Vac
220Vac-Adjustablebetween233 to 252Vac, default 242Vac
under Voltage Threshold:
120Vac-Adjustablebetween100 to 114Vac, default 108Vac
220Vac-Adjustablebetween176 to 209Vac, default 198Vac
backfeed Protection: Comply with safety requirement
redundant Power: Startup power-on by priority
Design: Source or alternative
STS Module Output
nominal output Voltage:Same as utility or the output ofInverter modules
Permissible Frequency area: Max. ±/-2.5% (inverter synchronization)
Transfer Time: Typical 1/4cycle
rated Power:50A for 110/115/120Vacand 208/220/230/240Vac
operation Methods: Inverter priority/Mains priority
Standards
ul, ce, roHS
Environmental
operating Temperature:-20 to 70°C / -4 to 158°F-5 to 58°C / 23 to 122°Fwith full performance
Storage Temperature: -40 to 85°C / -40 to 185°F
Humidity: 90% non-condensing
noise: 55dBa
Controller Module
Input
nominal Voltage: 48Vdc
operating range: 30 to 72Vdc
over current Protection: 2A Fuse
Human Interface
lcDResolution (Line X Array)4 x 16 Charactor
leD indicator3 Colored indicators for normal, warning and fault display
alarm Audio alarm when inverter, STS, controller module
System Parameter
baud rate: Setting controller com port baud rate
Keypad Tones: Setting keypad tones
Time and Date: Setting current time and date
Setting Password: Setting system password
brightness: Setting LCD brightness
Default: Change current system parameters to default value
battery calibration: Calibration battery voltage
Mechanical
Dimensions (in/mm) weight (lb/kg)
inverter Module: 10.6 x 8.5 x 1.7 / 270 x 215 x 43.8 5.5 / 2.5
STS Module: 10.6 x 8.5 x 1.7 / 270 x 215 x 43.8 4.4 / 2
controller Module: 10.9 x 3.5 x 1.7 / 277 x 88 x 43.5 2.2 / 1Hot-Swap chassis:19/23" Mouning bracketsinverter chassis
12.6 x17.3 x 1.7 / 320 x 440 x 44 5.5 / 2.5
STS and controller chassis: 12.6 x 17.3 x 1.7 / 320 x 440 x 44 7.5 / 3.4
Communication Interface
rS-232x1: Communicate with PC
rS-485x2: Communicate with supervision
Dry contactx5: Communicate with external Monitor
uSbx1: Communicate with PC
ineX inverter System48V Modular Inverter System
INEX Inverter System
37
DC
to A
C Inverters
> Versatile modular design provides flexibility for different power applications
> Expandable capacity up to 24kVA with N+1 redundancy configuration
>“Allmaster”dynamicmechanismeliminatessingle point failure to optimize reliability
INEX Inverter Module
ineX inverter System48V Modular Inverter System
ineX 48V Modular inverter System
Inverter Module
INEX inverter module provides pure sine wave AC power output for critical telecommunication equipment. Adopting N+1 redundancy design, INEX Inverter can operate up to 24 units in parallel. INEX inverter module is specially designed with compact size of maximized power density and can reach up to 5.57W/inch3 for INEX 1000 and 8.36W/inch3 for INEX1500. 1RU height designallows the module to be installed onto a standard ETSI 300mm Rack. INEX module provides the revolutionary telecom power solution in terms of maximum flexibility and reliability.
INV-4810E
Pure sine waveHot-swap replacement in shelfHigh efficiency >89%DSP design for higher system reliabilityLower audible noise <55dBASmart fan speed controlN+1 redundancy system, load sharing difference < 5%High power densityEmergency Power Off function embeddedCAN Bus interface embedded-48Vdc Telecom system applicationWide operation temperature range, -20 to 70˚C / -4 to 158˚F
STS Module
INEX STS (Static Transfer Switch) module increases system reliability by automatic power transfer between the inverter output and the AC mains. By setting up the priority of operation mode, users can change the systemstatus of “on line mode” or “off line mode”. The on line mode will keep the input power provided by inverter line and when inverter fails, the line will switch to AC utility line. In off line mode, the system power is always connected to the AC utility line and will switch to inverter power line when AC utility fails. The transfer time is less than 1/4 cycle which prevents the power interruption.The reliable performance of INEX STS module will provide the maximum protection to the connected telecommunication equipment against possible damage caused by the system power failure.
STS-050
Universal input rangeHot-swap replacement in shelfBack-feed protectionRedundant fan designRedundant power supply designOperation Priority Setup of transfer side by setting in Control ModuleFast transfer time, typically less than 1/4 cycleWide operation temperature range, -20 to 70˚C / -4 to 158˚FLower audible noise <55dBAEmergency Power Off function embeddedNo-cross connectOptional maintenance bypass switch functionCAN Bus interface embedded
Controller Module
INEX controller module allows users to monitor the system status in real time. The superior design enables users to manage the inverter and STS module status including voltage, current, frequency, capacity and temperature. With a user-friendly interface design, users can easily manage the inverter and STS module settings including voltage, frequency, redundancy (for inverter module), and priority (STS module). The controller module can also record the alarm history which can help to understand the operating status while maintaining the system or making further adjustments to improve system performance.
CAN Bus protocol for module communicationRelay contact output for customized alarmsHot-swappable designReal time clock embeddedComprehensive LCD & LED for status displayAudible alarm function
Communication Interface
The communication interface includes several options for wider applications which facilitates the remote managing to the system. The standard portsinclude relay contacts, RS-232, RS-485, USB. Relay contacts provide five programmable settings to display customized information. RS-232 & USB ports provide the serial connection to PC for software monitoring. RS-485 provides long distance connection for direct monitoring. The optional SNMP offers remote monitoring capability using a browser interface. The communication interface provides powerful monitoring and managing solutions to the system manager.
Relay contactsRS-232RS-485SNMP (Optional)USB
Telecom Power Monitoring Software
TelecomPower is a monitoring software which supports either stand alone computer or network connected computers.
Monitoring to each module in the inverter system in real timeProvides panoramic view of all the related information of utility power, system status, STS statusAuto search function with any inverter power modules in LANPassword security protectionInstall and uninstall is easy and clear
INV-4810E
38
DC
to
AC
Inve
rter
s
S4 inverter
Electrical
input Voltage: -48Vdc (40 to 60Vdc)
output Voltage:100, 110, 115, 120, 200, 220, 230, 240 (user selectable)
Output Frequency
user-Selectable: 50 or 60Hz (±0.02%)
output waveform: High resolution PWM sine wave
inverter Technology: IGBT PWM
regulation: <±1%
Static Switch
Transfer Time: <3ms
efficiency:88% typical (online mode) to 97% typical(off line eco mode)
Transient response: 5% deviation with 1ms recover from zero to full load
overload capability: 120% of continuous rated VA/W at 20˚C/68˚F
Short circuit current (Scc): 300% for more than 4 cycles
audible noise: Less than 50dBA
eMi emission: <30dBmc
Total Harmonic Distortion:<1% for linear loads, <3% for crest factor loads upto3:1
Monitoring:LCD with true RMS metering and LED status display, dry contacts, RS232
calibration: Digitally controlled/automatic
Altitude
operating Temperature:0 to 55°C / 32 to 131°F -40 to 75°C / -40 to 167°F shipping
operating Humidity: 0 to 90% relative, without non-condensing
operating altitude: <3000m / 10000ft without derating
Standards
agency approvals:UL/CSA 60950 (listed) and European Standard EN60950, CE, TUV, FCC class A certified
installation: 19", 23", 25" rack or floor mounted
Finish: RAL 902 off-white
System Height 17"W x 18.5"D*
Receiver Cabinet Capacity kVA
Inverter Capacity kVA/kW
Quantity Inverters
Power kVA/kW
DC Input (A) max
Output (A) @ 115Vac*
Approx. System Weight (lb)
Max BTU
DC Breaker (A) Suggested
AC Input Breaker (A) at 115Vac
21" 7 3.5 1 3.5/3 88 26 114 1,807 125 30
(min./max Inverter qty 1-2) 7 2 7/6 176 52 182 3,614 250 60
31.5" 14 10.5 3 10.5/9 265 78 241 5,421 375 100
(min./max Inverter qty 2-4) 14 4 14/12 353 104 299 7.227 500 125
42" 21 17.5 5 17.5/15 441 130 357 9.034 650 150
(min./max Inverter qty 3-6) 21 6 21/18 529 157 418 10.841 750 200
* Transformer will add to system weight
S4 receiver cabinet Size
Model: 7kVA 14kVA 21kVA
Dimensions (in/mm):
21 x 17 x 19 / 553.4 x 431.8 x 482.6
31 x 17 x 19 / 787.4 x 431.8 x 482.6
42 x 17 x 19 / 1066.8 x 431.8 x 482.6
Min. inverters:
1 x 3.5kVA (3.5kVA) 2 x 3.5kVA (7kVA) 3 x 3.5kVA (10.5kVA)
Max inverters:
2x3.5kVA (7kVA) 4 x 3.5kVA (14kVA) 6 x 3.5kVA (21kVA)
S4 inverter Series7 to 21kVA Inverter System
> Constructed to NEBS/Telecom industry standards
>Truemodularscalability:3.5to21kVA(3.5kVAmodules) — add modules as your system grows
> Parallel for N+1 redundancy or capacity
> Full front accessibility
> LCD status display module S4 Inverter with maintenance bypass and AC distribution
panel
S4 Inverter
39
DC
to A
C Inverters
DSP inverter Series1 to 15kVA Inverter System
> Nebs level 3 certified to assure compatibility with the telecommunications environment
> Fourth generation DSP architecture utilizing SMD for high reliability and MTBF
> Hot swap EUE static switch and inverter modules
> 6 or 15kVA EUE static switch available
DSP inverter Series
Inverter Module Rating: 1kVA 2.5kVA
nominal System output capacity with one rack Shelf: 1 to 5kVA (6kVA w/o EUE) 2.5 to 12.5kVA (15kVA w/o EUE)
nominal bypass ac input: 120Vac 120Vac
number of bypass ac Phases: 1 1
bypass ac input wiring: L, N, PE L, N, PE
bypass Voltage Tolerance: ±10%(Adjustable±5%to±15%) ±10%(Adjustable±5%to±15%)
Maximum System capacity with Two rack Shelves, without eue:
12kVA 30kVA
nominal Dc input: -48Vdc -48Vdc
Dc input range: 40.8 to 60Vdc 40.8 to 60Vdc
Output
nominal ac output Voltage: 120Vac 120Vac
output Voltage regulation: ±5% for all combinations of line, load and temperature
output Power Factor: 0.7 lagging to 0.8 leading 0.7 lagging to 0.8 leading
output Voltage waveform: DSP Sine wave DSP Sine wave
output crest Factor: 2.8:1 2.8:1
output Voltage Distortion: <3% @ 100% rated linear load <3% @ 100% rated linear load
output overcurrent Protection: Electronic current limiting Electronic current limiting
overload rating (inverters): 110% continuous, 120% for ~1 minute, 200% for ~4 seconds
overload rating (Static bypass): 500% for 100mS 500% for 100mS
optional Maintenance bypass Switch:Internally mounted, Make-before-break mechanically interlocked switch provided on all models equipped with the EUE
static bypass module
inverter Module rating: 1kVA 2.5kVA
remote alarming: (1) Form-C Inverter fault, (1) Form-C Static Switch fault
leD indicators (inverter Modules): On, Output present, DC Input OK, Inverter Fault, Parallel Operation, Overload, Bar graph for output power
Display/Metering (eue, Static bypass Module): Graphic Display (Menu Driven, password protected), Power flow diagram, LED’s (Normal, fault)
Mechanical
rack Shelf Dimensions (in/mm): 12.25 x 23 x 19.8 / 311 x 584 x 503 12.25 x 23 x 25.25 / 311 x 584 x 590
radio interference: Certified to Telecorodia GR-1089 Certified to Telecorodia GR-1089
Safety listing: UL60950 UL60950
Product certification: NEBS Level 3, Seismic Zone 4 NEBS Level 3, Seismic Zone 4
elevation: <3000m / 10000ft without derating <3000m / 10000ft without derating
operating Temperature: 0 to 55°C / 32 to 131°F 0 to 55°C / 32 to 131°F
operating Humidity: 0 to 95% non-condensing 0 to 95% non-condensing
Power rating: 1000VA / 800W 2500VA / 2000W
nominal input current (-48Vdc): 19A 47A
Maximum input current: 22.5A 55A
output current (120Vac): 8.33A 20.83A
weight (lb/kg): 11 / 5 17.6 / 8
DSP inverter
40
DC
to
AC
Inve
rter
s
S5 inverter Series1500W Inverter System
> Ultra, compact 1RU module, 19" rackmountable
> Paralleable output with current share and synchronization of multiple inverters working in parallel (N+1)
> Split phase output (120/240Vac)
S5 inverter
Input Characteristics
input Voltage range: 40A to 72Vdc (48Vdc); 20A to 36Vdc (24Vdc)
input current: 48A at 36Vdc (48Vdc); 100A at 18Vdc (24Vdc)
inrush current: ETSI EN 300 132-2 V2.1.2 clause 4.7
input over current Protection:
Internal fuse, 70A (48Vdc), Internal fuse, 140A (24Vdc)
input over Voltage Protection: 74V (48Vdc); 37V (24Vdc)
input under Voltage Protection: 36V (48Vdc); 18V (24Vdc)
Output Characteristics
output Power: 1500W
output Voltage range:230Vacmodels:200to240Vac 115Vacmodels:110to120Vac
Frequency: 50 or 60Hz
overload:230Vacmodels:1800VA 115Vacmodels:1650VA
Surge:230Vacmodels:2300VAfor200ms 115Vacmodels:1650VAfor200ms
efficiency: up to 93%
load Power Factor: 0.33 lagging or leading
load crest Factor: 4
regulation load: -3 to 1% over full operating range
regulation line: ±0.1% over full operating range
output noise and ripple: 2% Vp-p (20Hz/20MHz)
Distortion: <2% on resistive load
over Voltage Protection: All outputs set at 115% ±2% of nominal
under Voltage Protection: All outputs set at 85% ±2% of nominal
over current Protection: 230Vacmodels:1to8Aselectable 115Vacmodels:2to15Aselectable
Safety Over Current Protection
by Safety circuit breaker: 230Vacmodels:10A,115Vacmodels:15A
Short-circuit Protection: 230Vacmodels:30A,115Vacmodels:60A
over Temperature Protection:
at Tamb >65˚C / 149˚F and Tint>100˚C / 212˚F (visual and acoustic indication 5˚C / 41˚F before shutdown)
Protection restore Modes:The restore mode of each protection can be individuallyselectedto“latch”or“autorestart”
Signal and Controls
lcD Panel: 2 line LCD panel with keypad for menu navigation
leD indicator:4:Green(powerON),Red(genericfault,OT,fanfail), Input OV, UV, OC Output OV, V, OC
general alarm Signal: By a photo-relay (open if in fault mode)
communications: RS-485 or CANBUS communications interface
Environmental
operating Temperature range: -25 to 55˚C / -13 to 131˚F
operating Humidity: 0 to 90% non-condensing
Storage: -40 to 85˚C / -40 to 185˚F
MTbF: >250000hrs at 40˚C / 104˚F
Altitude
operating: 3963m / 13000ft
non operating: 12192m / 40000ft
Output Voltage
Power Derating @ 75w/˚c: 55 to 65˚C / 131 to 149˚F
Temperature coefficient: 0.02% per C˚ within rated load
Safety agency compliance: cCSAus, Kema, CB report, CE mark
Isolations
Pri-Sec: 3000Vrms
Sec-gnD: 1500Vrms
Pri-gnD: 1000Vrms
Signal-gnD: 0Vrms
Mechanical Specifications
Dimensions (in/mm): 19 x 1.71 x 14.94 / 482.6 x 43.5 x 379.5
weight (lb/kg): 12.34 / 5.6
Warranty
2 years from date of shipment, standard product only
DC in AC out
Sync
DC
AC
DC
AC
DC
AC
S5 1500W Inverter
41
DC
to A
C Inverters
MS Power inverter Series1 and 2kVA Inverter System
> Standard 19"/23", 2RU rackmount
> 1kVA/800W and 2kVA/1600W
> Pure sine wave output
> Utility bypass function
> UL/cUL approved
> RS-232 communication
>Internal“overtemperature”protection
> Input reverse polarity protection
> Output overload protection
Majorsine Power inverter
Models Majorsine1000-24-2U Majorsine1000-48-2U Majorsine2000-48-2U
DC Input
Voltage: 20 to 30Vdc 40 to 60Vdc 40 to 60Vdc
rated current: 50A 25A 50A
Protection: Fuse and DC Breaker Fuse and DC Breaker Fuse and DC Breaker
efficiency: >85% (full linear load), 24Vdc I/P, 120Vac O/P
Output (Backup)
capacity: 1kVA / 800W 1kVA / 800W 2kVA / 1600W
Voltage: 110, 115, 120, 125Vac 110, 115, 120, 125Vac 110, 115, 120, 125Vac
Voltage regulation: ±2% ±2% ±2%
Frequency: 50/60Hz ±0.2Hz 50/60Hz ±0.2Hz 50/60Hz ±0.2Hz
waveform: Pure sine wave Pure sine wave Pure sine wave
THD (linear load): 3% 120V/100% 3% 120V/100% 3% 120V/100%
THD (SPS load): 5% 120V/100% 5% 120V/100% 5% 120V/100%
crest Factor: 3:1 3:1 3:1
receptacles: (4) NEMA 5-15R outlets (4) NEMA 5-15R outlets (4) NEMA 5-20R outlets
Utility Power (Bypass)
Voltage (nominal): 120Vac 120Vac 120Vac
Frequency: 60 ±5Hz 60 ±5Hz 60 ±5Hz
Protection: AC Circuit Breaker AC Circuit Breaker AC Circuit Breaker
Interface
communication: RS232 / Dry-contact RS232 / Dry-contact RS232 / Dry-Contact
leD Display: Inverter ON, Overload, DC Abnormal Inverter ON, Overload, DC Abnormal Inverter ON, Overload, DC Abnormal
lcD Display:Inverter ON, Output Voltage and Frequency, Input Voltage, Load Percentage, DC Voltage, System Model, Internal Environment Temp., Utility
status, Short circuit, Over Temp.
Protection
Short: For 1 second; Switch to Bypass, then shutdown
overload: 105 to 125% for 3 minutes; 126 to 150% for 3 seconds; >150% for 1 second; Switch to bypass
Temperature: 55˚ ±5˚C (Inside the case) 131˚ ±41˚F 55˚ ±5˚C (Inside the case) 131˚ ±41˚F 55˚ ±5˚C (Inside the case) 131˚ ±41˚F
Environment
operating Temperature: 0 to 50˚C / 32 to 122˚F 0 to 50˚C / 32 to 122˚F 0 to 50˚C / 32 to 122˚F
Storage Temperature: -20 to 70˚C / -4 to 158˚F -20 to 70˚C / -4 to 158˚F -20 to 70˚C / -4 to 158˚F
Humidity: 0 to 90˚C / 32 to 194˚F non-condensing 0 to 90˚C / 32 to 194˚F non-condensing 0 to 90˚C / 32 to 194˚F non-condensing
acoustic noise: 46dBA @ 1 M 46dBA @ 1 M 46dBA @ 1 M
Safety: UL / cUL UL / cUL UL / cUL
eMi / rFi: FCC Class A FCC Class A FCC Class A
Mechanical
Dimensions (in/mm): 17.32 x 11.81 x 3.46 / 440 x 300 x 88, 2RU
weight (lb/kg): 17.6 / 8 15.4 / 7 15.4 / 7
MS Power Inverter
43
NetBotz® Monitoring
> Improve response time to incident via troubleshooting, early detection and automated threat response
> Reduce staffing requirements by augmenting with remote eyes and ears
> Reduce operating costs with early problem detection
> Reduce operating costs through fewer service calls
> Improve business decision support via trend monitoring
> Improve customer service through increased system and information availability
The NetBotz system includes a base station appliance, environmental sensors, color camera and
integrated software that assess the severity of threats and provides notification. The Centralized
Management console is a central station platform that can communicate with, configure, manage,
archive and provide trend analysis on data coming from as many as 500 NetBotz appliances
throughout a distributed enterprise. Users receive alarms and notification via e-mail, phone or
pager, and in the form of text messages or video clips. NetBotz is the only product available today
that leverages your current IT infrastructure and the power of the Web. Our award-winning,
patented IP-based technology means no custom install, no hassles and no extra expense. The
solution integrates fully with industry-leading network monitoring systems.
Top Three risk Factors for your network
> EnvironmentalThe #1 cause of downtime for remote locations, environmental problems go beyond worries of
fires and floods. Cooling and power are key points of exposure that become more important as
equipment density increases.
> Human ErrorWecallthisthe“unspokenepidemic”becausenoonelikestodiscusshumanerrorandthe
tremendous impact it can have on availability. But the fact is, it’s the second greatest cause of
downtimeinremoteorunsupervisedlocationsbecausesystemsareoftenhousedinjanitorclosets,
wiring closets or other less than optimal settings.
> Physical TheftAs assets become smaller and more efficient with hot swappable drives, they become more attractive
targets that are easier to steal. Physical attacks against digital assets are often overlooked and are a
source of real concern.
NetB
otz M
on
itorin
g
45
Sin
gle an
d T
hree P
hase U
PS
Single and Three Phase UPS> SmartUPS® XL
The SmartUPS XL protects your data by supplying reliable, network-grade power and scalable runtime in tower or rackmount form. Typical applications requiring longer runtime include critical application servers and storage, IP and PBX based voice networks, and enterprise network switches and hubs. The SmartUPS XL adds the advantage of unsurpassed runtime capability for those business applications that demand continual uptime.
> SmartUPS RTThe SmartUPS RT is a family of high-density, performance UPSs for voice and data networks, medical labs and light industrial applications. Capable of supporting 10kVA in a 6RU rack/tower convertible form, users can support power hungry blade servers or heavily loaded equipment racks. Customers with harsh power environments looking for extremely tight voltage and frequency regulation, internal bypass and input power factor correction typical of double conversion online topology will get them in the SmartUPS RT.
> Symmetra®
Engineered to deliver the highest level of business continuity possible, Symmetra uses a modular, redundant architecture that can scale power and runtime as demand increases or when higher levels of availability are required. Typical applications include Web and other key application servers, IP based and traditional PBX voice solutions, and enterprise type network switches.
> Symmetra LXWith built-in network manageability, rack-optimization and tower models available from 4 to 16kVA N+1 redundant, the online Symmetra LX is the ideal choice to protect high-performance IT and Telecom equipment in business-critical server and network rooms. A flexible rack/stack design offers unmatched runtime and power capacity in space-constrained environments.
> 1600EP SeriesAlpha’s 1600EP Series incorporates dual conversion technology that provides power conditioning for sensitive headend electronics, regardless of the quality of utility or generator input power. This topology has power factor correction on the input circuit that provides compatibility with all generators, even when the UPS is sized near generator capacity.
> Triniti™ 4200 SeriesThe Alpha Triniti Series three phase UPS incorporates dual conversion technology designed to provide power conditioning for sensitive headend electronics, regardless of the quality of the utility or generator input power. Its unique active front end design provides power factor correction. In addition to providing utility cost savings, this feature provides compatibility with most existing headend generators, including those with mechanical governors running at near capacity.
> GalaxyThe Galaxy Series is the world’s first data-center grade UPS designed specifically for mid-range enterprise level applications. The AlphaSource Galaxy delivers the optimum level of reliability, availability and scalability demanded by the new generation of critical enterprise applications.
> Symmetra PXThe Symmetra PX is a world class, redundant and scalable power protection system. Seamlessly integrating into today’s state-of-the-art data center designs, the Symmetra PX is a true modular system. Made up of dedicated and redundant modules-power, intelligence, battery and bypass, this architecture can scale power and runtime as demand grows or as higher levels of availability are required.
> EPS 7000The EPS 7000 has unparalleled reliability and performance with time tested architecture and one of the smallest footprints in the industry. Engineered with high output power, fault tolerant architecture and redundant paralleling logic, the robust EPS 7000 incorporates the best innovative technology in the three phase UPS marketplace.
46
Sin
gle
Ph
ase
UP
S
SmartuPS Xl
Models: Smart-UPS 750T Smart-UPS 1000T Smart-UPS 1400RM Smart-UPS 1500RMT Smart-UPS 2200RM Smart-UPS 2200RMT
configuration: Tower Tower Rackmount Rackmount/Tower Rackmount Rackmount/Tower
Output
output Power capacity: 750VA / 600W 1000VA / 800W 1400VA / 1050W 1440VA / 1425W 1850VA / 1850W 1850VA / 1850W
Max configurable Power: 750VA / 600W 1000VA / 800W 1400VA / 1050W 1440VA / 1425W 2200VA / 1980W 2200VA / 1980W
nominal output Voltage: 120V 120V 120V 120V 120V 120V
waveform Type: Sine wave Sine wave Sine wave Sine wave Sine wave Sine wave
output connections: (8) NEMA 5-15R (8) NEMA 5-15R (6) NEMA 5-15R (8) NEMA 5-15R (9) NEMA 5-15R, (2) NEMA 5-20R
Input
nominal input Voltage: 120V 120V 120V 120V 120V 120V
input Frequency (auto sensing): 50/60Hz ±3Hz 50/60Hz ±3Hz 50/60Hz ±3Hz 50/60Hz ±3Hz 50/60Hz ±3Hz 50/60Hz ±3Hz
input connections: NEMA 5-15P NEMA 5-15P NEMA 5-15P NEMA 5-15P NEMA 5-20P NEMA 5-20P
cord length: 1.8m / 5.9ft 1.8m / 5.9ft 1.8m / 5.9ft 3.1m / 10.2ft 2.4m / 7.9ft 2.4m / 7.9ft
bypass: - - - - - -
Batteries and Runtime
battery Type: Maintenance-free sealed Lead-Acid, leakproof VRLA Maintenance-free sealed Lead-Acid, leakproof
Typical recharge Time (hrs): 3 2 3 3 3 3
replacement battery cartridge: RBC7 RBC7 RBC25 RBC43 RBC105 RBC55
rbc™ Quantity: 1 1 1 1 1 1
runtime Full / Half load (min): 16.6 / 50.6 9.6 / 33.3 6.6 / 23.5 11.9 / 28.3 8.2 / 29.4 7.4 / 27.1
Communication and Management
interface Port(s): DB-9, RS-232, SmartSlot, USB DB-9, RS-232DB-9, RS-232, RJ-45 10/100 Base-T, USB
DB-9, RS-232, SmartSlot, USB
SmartSlot™ interface Qty: 1 1 1Network Mgmt Card w/ Environmental Monitoring
1 1
control Panel: LED status display with load and battery bar-graphs and On Line, On Battery, Replace Battery, and Overload Indicators
audible alarm: Alarm when on battery, low battery alarm
Mechanical
Dimensions (in/mm):8.5 x 6.7 x 17.3 / 216 x 170 x 439
8.5 x 6.7 x 17.3 / 216 x 170 x 439
5.1 x 17 x 15.5 / 130 x 431.8 x 394
3.4 x 17 x 26.7 / 86.4 x 431.8 x 678.2
5.2 x 19 x 26 / 133 x 483 x 660
17 x 7.7 x 19.8 / 431.8 x 196 x 503
rack Height: - - 3RU 2RU 3RU 5RU
net weight (lb/kg): 53 / 24 60 / 27.2 70 / 31.8 103 / 46.7 124 / 56.2 121 / 54.9
Environmental
Temperature: 0 to 40˚C / 32 to 104˚F
Humidity: 0 to 95% 0 to 95% 0 to 85% 0 to 95% 0 to 95% 0 to 95%
elevation: 0 to 1524m / 0 to 5000ft 0 to 3000m / 0 to 10000ft
Storage Temperature: -15 to 56.1˚C / 5 to 133˚F -5 to 55˚C / 23 to 131˚F -15 to 56.1˚C / 5 to 133˚F
audible noise at 1 Meter: 42dBA 42dBA 48dBA 55dBA 53dBA 53dBA
online Thermal Dissipation: 100BTU/hr 120BTU/hr 155BTU/hr 300BTU/hr 375BTU/hr 305BTU/hr
Conformance
regulatory approvals: BSMI, CSA, FCC Part 15 Class A, UL 1778 BSMI, CSA, UL 1778BSMI, CSA, FCC Part 15 Class A, UL 1778, NOM, VCCI
CSA, FCC Part 15 Class A, UL 1778, UL 1449
CSA, FCC Part 15 Class A, UL 1778
reference: SUA750XL SUA1000XL SU1400RMXLB3U SU1500RMXL2U SUA2200RMXL3U SUA2200XL
Options:extendedbatteryruntimes,interfacecables,NetBotz® accessories and sensors, SmartSlot expansion chassis, UPS dry-contact management, UPS environmental monitoring card, UPS interface expanders, UPS network management cards, UPS out-of-band management, rack enclosures and accessories, NetShelter 2 post open frame racks, NetShelter 4 post open frame racks, NetShelter SX enclosures, NetShelter VX enclosures, rack fan tray, basic rack PDU, metered rack PDU, power cords, rack automatic transfer switch, switched rack PDU, replacement batteries, extended warranty, installation services, on site service, remote monitoring service, StruXure manager, powerchute business edition, and UPS remote power off interface
SmartuPS® XlSingle Phase UPS
> Scalable runtime
> Boost and trim Automatic Voltage Regulation (AVR)
> Temperature-compensated battery charging
> Automatic restart of loads after UPS shutdown
> Standard 2 year warrantySUA1000XL
47
Sin
gle P
hase U
PS
SmartuPS® XlSingle Phase UPS
> Hot-swappable batteries
>Adjustablevoltage-transferpoints
> LED status indicators
> Generator compatible
SUA1000XL
SmartuPS Xl
Models:Smart-UPS 2200 RMT208
Smart-UPS 3000 RMTSmart-UPS 3000 RMT208
Smart-UPS 3000 RMTMOD
Smart-UPS 3000 RM
configuration: Rackmount Rackmount/Tower Rackmount/Tower Rackmount/Tower Rackmount
Output
output Power capacity: 2200VA / 1600W 3000VA / 2700W 3000VA / 2700W 3000VA / 2850W 2700VA / 3000W
Max configurable Power: 2200VA / 1600W 3000VA / 2700W 3000VA / 2700W 3000VA / 2850W 2700VA / 3000W
nominal output Voltage: 208V 120V 208V 120V 120Vwaveform Type: Sine wave Sine wave Sine wave Sine wave Sine wave
output connections:(2) NEMA 5-15R, (1) NEMA L6-20R, (2) NEMA L6-30R
(9) NEMA 5-15R, (2) NEMA 5-20R
(2) NEMA L6-20R, (2) NEMA L6-30R
(6) NEMA 5-15R, (2) NEMA 5-20R
(9) NEMA 5-15R, (2) NEMA 5-20R
Input
nominal input Voltage: 208V 120V 208V 120V 120V
input Frequency (auto sensing): 50/60Hz ±3Hz 50/60Hz ±3Hz 50/60Hz ±3Hz 50/60Hz ±3Hz 50/60Hz ±3Hz
input connections: NEMA L6-20P NEMA L5-30P NEMA L6-20P NEMA L5-30P NEMA L5-30P
cord length: 2m / 6.6ft 2.4m / 7.9ft 2m / 6.6ft 3.1m / 10.2ft 2.4m / 7.9ft
bypass: - - - Internal Bypass (Auto/man) -
Batteries and Runtime
battery Type: Maintenance-free sealed Lead-Acid, leakproof VRLAMaintenance-free sealed
Lead-Acid, leakproof
Typical recharge Time (hrs): 3 3 3 3 3replacement battery cartridge: RBC11 RBC55 RBC55 RBC43 APCRBC105rbc™ Quantity: 1 1 1 1 1runtime Full / Half load (min): 9.7 / 34.3 5.5 / 13.6 5.5 / 13.5 3.5 / 11.9 5.4 / 15
Communication and Management
interface Port(s):DB-9, RS-232, SmartSlot
DB-9, RS-232, SmartSlot
DB-9, RS-232, SmartSlot
DB-9, RS-232, RJ-45 10/100 Base-T, USB
DB-9, RS-232, SmartSlot
SmartSlot™ interface Qty: 1 1 1Network Mgmt Card w/ Environmental Monitoring
1
control Panel: LED status display with load and battery bar-graphs and On Line, On Battery, Replace Battery, and Overload Indicators
audible alarm: Alarm when on battery, low battery alarm
Mechanical
Dimensions (in/mm):8.8 x 19 x 17.8 / 223.5 x 482.6 x 452.1
17 x 7.7 x 19.8 / 431.8 x 196 x 503
17 x 7.7 x 19.8 / 431.8 x 196 x 503
3.4 x 17 x 26.7 / 86.4 x 431.8 x 678.2
5.3 x 19 x 26 / 134.6 x 482.6 x 660.4
rack Height: 5RU 5RU 5RU 2RU 3RU
net weight (lb/kg): 132 / 59.9 121 / 54.9 121 / 54.9 103 / 46.7 124 / 56.2
Environmental
Temperature: 0 to 40˚C / 32 to 104˚F
Humidity: 0 to 95% 0 to 95% 0 to 95% 0 to 95% 0 to 95%
elevation: 0 to 3000m / 0 to 10000ftStorage Temperature: -15 to 56.1˚C / 5 to 133˚F -5 to 55˚C / 23 to 131˚F -15 to 56.1˚C / 5 to 133˚F
audible noise at 1 Meter: 53dBA 53dBA 53dBA 55dBA 53dBA
online Thermal Dissipation: 305BTU/hr 305BTU/hr 275BTU/hr 300BTU/hr 375BTU/hr
Conformance
regulatory approvals: CSA, FCC Part 15 Class A, UL 1778BSMI, CSA, FCC Part 15 Class A, UL 1778, NOM, VCCI
CSA, FCC Part 15 Class A, UL 1778, UL 1449
reference: SU2200RMXLTNET SUA3000XL SUA3000XLT SUM3000RMXL2U SUA3000RMXL3U
Options:extendedbatteryruntimes,interfacecables,NetBotz® accessories and sensors, SmartSlot expansion chassis, UPS dry-contact management, UPS environmental monitoring card, UPS interface expanders, UPS network management cards, UPS out-of-band management, rack enclosures and accessories, NetShelter 2 post open frame racks, NetShelter 4 post open frame racks, NetShelter SX enclosures, NetShelter VX enclosures, rack fan tray, basic rack PDU, metered rack PDU, power cords, rack automatic transfer switch, switched rack PDU, replacement batteries, extended warranty, installation services, on site service, remote monitoring service, StruXure manager, powerchute business edition, and UPS remote power off interface
48
Sin
gle
Ph
ase
UP
S
SmartuPS® rTSingle Phase UPS
> Automatic internal bypass
> Intelligent battery management
> Hot-swappable batteries
> Standard 2 year warranty
SURTA2000XL
SmartuPS rT
Models:Smart-UPS RT 1500T Smart-UPS RT 1500RM
Smart-UPS RT 2000T Smart-UPS RT 2000RM
Smart-UPS RT 3000T Smart-UPS RT 3000RM
Smart-UPS RT 3000T208 Smart-UPS RT 3000RM208
configuration: Rackmount/Tower Rackmount/Tower Rackmount/Tower Rackmount/Tower
Output
output Power capacity: 1500VA / 1050W 2000VA / 1400W 3000VA / 2100W 3000VA / 2100W
Max configurable Power: 1500VA / 1050W 2000VA / 1400W 3000VA / 2100W 3000VA / 2100W
nominal output Voltage: 120V 120V 120V 208V or 240V
waveform Type: Sine wave Sine wave Sine wave Sine wave
output connections: (6) NEMA 5-15R (6) NEMA 5-15R (6) NEMA 5-15R, (2) NEMA 5-20R (2) NEMA L6-20R, (2) NEMA L6-30R
Input
nominal input Voltage: 120V 120V 120V 208V
input Frequency (auto sensing): 50/60Hz ±3Hz 50/60Hz ±3Hz 50/60Hz ±3Hz 50/60Hz ±3Hz
input connections: NEMA 5-15P NEMA 5-20P NEMA L5-30P NEMA L6-30P
cord length: 1.8m / 5.9ft 1.8m / 5.9ft 3.1m / 10.2ft 3.1m / 10.2ft
bypass: Built-in Bypass Built-in Bypass Internal Bypass (Automatic and Manual)
Batteries and Runtime
battery Type: Maintenance-free sealed Lead-Acid, leakproof
Typical recharge Time (hrs): 3 3 2.5 2.5
replacement battery cartridge: RBC57 RBC57 RBC44 RBC44
rbc™ Quantity: 1 1 1 1
runtime Full / Half load (min): 8.6 / 22.2 5 / 15.2 14.1 / 33.9 14.1 / 33.9
Communication and Management
interface Port(s): DB-9, RS-232, SmartSlot, USB
SmartSlot™ interface Qty: 1 1 1 1
control Panel: LED status display with load and battery bar-graphs and On Line, On Battery, Replace Battery, Overload and Bypass Indicators
audible alarm: Alarm when on battery, low battery alarm, overload alarm
emergency Power off (ePo): Yes Yes Yes Yes
Mechanical
Dimensions - rackmount (in/mm): 3.4 x 17 x 22 / 86.4 x 431.8 x 558.8 5.1 x 17 x 26 / 129.5 x 431.8 x 660.4
rack Height: 2RU 2RU 3RU 3RU
net weight (lb/kg): 53 / 24 60 / 27.2 70 / 31.8 103 / 46.7
Environmental
Temperature: 0 to 40˚C / 32 to 104˚F 0 to 40˚C / 32 to 104˚F 0 to 40˚C / 32 to 104˚F 0 to 40˚C / 32 to 104˚F
Humidity: 0 to 95% 0 to 95% 0 to 95% 0 to 95%
elevation: 0 to 3000m / 0 to 10000ft 0 to 3000m / 0 to 10000ft 0 to 3000m / 0 to 10000ft 0 to 3000m / 0 to 10000ft
Storage Temperature: -20 to 50˚C / -4 to 122˚F -20 to 50˚C / -4 to 122˚F -15 to 45˚C / 5 to 113˚F -15 to 45˚C / 5 to 113˚F
audible noise at 1 Meter: 45dBA 45dBA 55dBA 55dBA
online Thermal Dissipation: 393BTU/hr 700BTU/hr 655BTU/hr 655BTU/hr
Conformance
regulatory approvals: BSMI, CSA, FCC Part 15 Class A, UL 1778 CSA, FCC Part 15 Class A, UL 1778
reference: SURTA1500RMXL, SURTA1500XL SURTA2000RMXL, SURTA2000XL SURTA3000RMXL, SURTA3000XL SURTD3000RMXLT, SURTD3000XLT
Options:extendedbatteryruntimes,interfacecables,NetBotz® accessories and sensors, SmartSlot expansion chassis, UPS dry-contact management, UPS environmental monitoring card, UPS interface expanders, UPS network management cards, UPS out-of-band management, rack enclosures and accessories, NetShelter 2 post open frame racks, NetShelter 4 post open frame racks, NetShelter SX enclosures, NetShelter VX enclosures, rack fan tray, basic rack PDU, metered rack PDU, power cords, rack automatic transfer switch, switched rack PDU, replacement batteries, extended warranty, installation services, on site service, remote monitoring service, StruXure manager, powerchute business edition, and UPS remote power off interface
49
Sin
gle P
hase U
PS
SmartuPS® rTSingle Phase UPS
> Automatic restart of loads after UPS shutdown
> Temperature-compensated battery charging
> LED Status IndicatorsSURT6000RMXLT
SmartuPS rT
Models:Smart-UPS RT 3000T208/120 Smart-UPS RT 3000RM208/120
Smart-UPS RT 5000T Smart-UPS RT 5000RM
Smart-UPS RT 5000T208/120 Smart-UPS RT 5000RM208/120
configuration: Rackmount/Tower Rackmount/Tower Rackmount/Tower
Output
output Power capacity: 3000VA / 2100W 5000VA / 3500W 5000VA / 3500W
Max configurable Power: 3000VA / 2100W 5000VA / 3500W 5000VA / 3500W
nominal output Voltage: 120 / 280, 240V 208V or 240V 120 / 280, 240V
waveform Type: Sine wave Sine wave Sine wave
output connections:(12) NEMA 5-20R, (2) NEMA L6-20R, (1) NEMA 5-20R
(2) NEMA L6-20R, (2) NEMA L6-30R(12) NEMA 5-20R, (2) NEMA L6-20R, (1) NEMA 5-20R
Input
nominal input Voltage: 208V 208V 208V
input Frequency (auto sensing): 50/60Hz ±3Hz 50/60Hz ±3Hz 50/60Hz ±3Hz
input connections: NEMA L6-30P NEMA L6-30P NEMA L6-30P
cord length: 3.1m / 10.2ft 3.1m / 10.2ft 3.1m / 10.2ft
bypass: Internal Bypass (Automatic and Manual)
Batteries and Runtime
battery Type: Maintenance-free sealed Lead-Acid, leakproof
Typical recharge Time (hrs): 2.5 2.5 2.5
replacement battery cartridge: RBC44 RBC44 RBC44
rbc™ Quantity: 1 1 1
runtime Full / Half load (min): 14.4 / 33.9 5 / 15.4 5 / 15.4
Communication and Management
interface Port(s): DB-9, RS-232, SmartSlot, USB
SmartSlot™ interface Qty: 1 UPS Network Management Card w/ Environmental Monitoring
control Panel: LED status display with load and battery bar-graphs and On Line, On Battery, Replace Battery, Overload and Bypass Indicators
audible alarm: Alarm when on battery, low battery alarm, overload alarm
emergency Power off (ePo): Yes Yes Yes
Mechanical
Dimensions - rackmount (in/mm): 8.6 x 19 x 26 / 218.4 x 482.6 x 660.4 5.1 x 17 x 26 / 129.5 x 431.8 x 660.4 8.6 x 17 x 26 / 218.4 x 431.8 x 660.4
rack Height: 5RU 3RU 5RU
net weight (lb/kg): 221 / 100.2 120 / 54.4 221 / 100.2
Environmental
Temperature: 0 to 40˚C / 32 to 104˚F 0 to 40˚C / 32 to 104˚F 0 to 40˚C / 32 to 104˚F
Humidity: 0 to 95% 0 to 95% 0 to 95%
elevation: 0 to 3000m / 0 to 10000ft 0 to 3000m / 0 to 10000ft 0 to 3000m / 0 to 10000ft
Storage Temperature: -15 to 45˚C / 5 to 113˚F -15 to 45˚C / 5 to 113˚F -15 to 45˚C / 5 to 113˚F
audible noise at 1 Meter: 55dBA 55dBA 55dBA
online Thermal Dissipation: 655BTU/hr 1040BTU/hr 1040BTU/hr
Conformance
regulatory approvals: CSA, FCC Part 15 Class A, UL 1778 CSA, FCC Part 15 Class A, UL 1778 CSA, FCC Part 15 Class A, UL 1778
reference: SURTD3000RMXLT-1TF5, SURTD3000XLT-1TF5 SURTD5000RMXLT, SURTD5000XLT-1TF5 SURTD5000RMXLT-1TF5, SURTD5000XLT-1TF5
Options:extendedbatteryruntimes,interfacecables,NetBotz® accessories and sensors, SmartSlot expansion chassis, UPS dry-contact management, UPS environmental monitoring card, UPS interface expanders, UPS network management cards, UPS out-of-band management, rack enclosures and accessories, NetShelter 2 post open frame racks, NetShelter 4 post open frame racks, NetShelter SX enclosures, NetShelter VX enclosures, rack fan tray, basic rack PDU, metered rack PDU, power cords, rack automatic transfer switch, switched rack PDU, replacement batteries, extended warranty, installation services, on site service, remote monitoring service, StruXure manager, powerchute business edition, and UPS remote power off interface
50
Sin
gle
Ph
ase
UP
S
SmartuPS® rTSingle Phase UPS
> Flash-upgradeable firmware
> Frequency and voltage regulation
> Input power factor protectionSURT8000RMXLT
SmartuPS rT
Models:Smart-UPS RT 6000T Smart-UPS RT 6000RM
Smart-UPS RT 6000T208/120 Smart-UPS RT 6000RM208/120
Smart-UPS RT 8000T Smart-UPS RT 8000RM
configuration: Rackmount/Tower Rackmount/Tower Rackmount/Tower
Output
output Power capacity: 6000VA / 4200W 6000VA / 4200W 8000VA / 6400W
Max configurable Power: 6000VA / 4200W 6000VA / 4200W 8000VA / 6400W
nominal output Voltage: 208V or 240V 120 / 280, 240V 208V or 240V
waveform Type: Sine wave Sine wave Sine wave
output connections: (2) NEMA L6-20R, (2) NEMA L6-30R(12) NEMA 5-20R, (2) NEMA L6-20R, (1) NEMA L6-30R
(1) Hard Wire 3-wire, (2) NEMA L6-20R, (2) NEMA L6-30R
Input
nominal input Voltage: 208V 208V 208V
input Frequency (auto sensing): 50/60Hz ±3Hz 50/60Hz ±3Hz 50/60Hz ±3Hz
input connections: NEMA L6-30P NEMA L6-30P Hard Wire 3-wire
cord length: 3.1m / 10.2ft 3.1m / 10.2ft 3.1m / 10.2ft
bypass: Internal Bypass (Automatic and Manual)
Batteries and Runtime
battery Type: Maintenance-free sealed Lead-Acid, leakproof
Typical recharge Time (hrs): 2.5 2.5 2.5
replacement battery cartridge: RBC44 RBC44 RBC44
rbc™ Quantity: 1 1 2
runtime Full / Half load (min): 5.3 / 15.8 5.3 / 15.8 6.3 / 17.9
Communication and Management
interface Port(s): DB-9, RS-232, SmartSlot, USB DB-9, RS-232, RJ-45 10/100 Base-T, SmartSlot
SmartSlot™ interface Qty: UPS Network Management Card w/ Environmental Monitoring
control Panel: LED status display with load and battery bar-graphs and On Line, On Battery, Replace Battery, Overload and Bypass Indicators
audible alarm: Alarm when on battery, low battery alarm, overload alarm
emergency Power off (ePo): Yes Yes Yes
Mechanical
Dimensions - rackmount (in/mm): 5.1 x 17 x 26 / 129.5 x 431.8 x 660.4 8.6 x 17 x 26 / 218.4 x 431.8 x 660.4 10.4 x 17 x 26.1 / 264.2 x 431.8 x 663.4
rack Height: 3RU 5RU 6RU
net weight (lb/kg): 120 / 54.4 221 / 100.2 244 / 110.7
Environmental
Temperature: 0 to 40˚C / 32 to 104˚F 0 to 40˚C / 32 to 104˚F 0 to 40˚C / 32 to 104˚F
Humidity: 0 to 95% 0 to 95% 0 to 95%
elevation: 0 to 3000m / 0 to 10000ft 0 to 3000m / 0 to 10000ft 0 to 3000m / 0 to 10000ft
Storage Temperature: -15 to 45˚C / 5 to 113˚F -15 to 45˚C / 5 to 113˚F -15 to 45˚C / 5 to 113˚F
audible noise at 1 Meter: 55dBA 55dBA 55dBA
online Thermal Dissipation: 1040BTU/hr 1040BTU/hr 1535BTU/hr
Conformance
regulatory approvals: CSA, FCC Part 15 Class A, UL 1778
reference: SURT6000RMXLT, SURT6000XLT SURT6000RMXLT-1TF5, SURT6000XLT-1TF5 SURT8000RMXLT, SURT8000XLT
Options:extendedbatteryruntimes,interfacecables,NetBotz® accessories and sensors, SmartSlot expansion chassis, UPS dry-contact management, UPS environmental monitoring card, UPS interface expanders, UPS network management cards, UPS out-of-band management, rack enclosures and accessories, NetShelter 2 post open frame racks, NetShelter 4 post open frame racks, NetShelter SX enclosures, NetShelter VX enclosures, rack fan tray, basic rack PDU, metered rack PDU, power cords, rack automatic transfer switch, switched rack PDU, replacement batteries, extended warranty, installation services, on site service, remote monitoring service, StruXure manager, powerchute business edition, and UPS remote power off interface
51
Sin
gle P
hase U
PS
SmartuPS® rTSingle Phase UPS
> Generator compatible
> Cold-start capable
> Resettable circuit breakers SURT8000XLT
SmartuPS rT
Models:Smart-UPS RT 8000T208/120 Smart-UPS RT 8000RM208/120
Smart-UPS RT 1000T Smart-UPS RT 1000RM
Smart-UPS RT 1000T208/120 Smart-UPS RT 1000RM208/120
configuration: Rackmount/Tower Rackmount/Tower Rackmount/Tower
Output
output Power capacity: 8000VA / 6400W 10000VA / 8000W 10000VA / 8000W
Max configurable Power: 8000VA / 6400W 10000VA / 8000W 10000VA / 8000W
nominal output Voltage: 120 / 280, 240V 208V or 240V 120 / 280, 240V
waveform Type: Sine wave Sine wave Sine wave
output connections:(1) Hard Wire 3-wire, (12) NEMA 5-20R, (2) NEMA L6-20R, (1) NEMA L6-30R
(1) Hard Wire 3-wire, (2) NEMA L6-20R, (1) NEMA L6-30R
(24) NEMA 5-20R, (2) NEMA L6-20R
Input
nominal input Voltage: 208V 208V 208V
input Frequency (auto sensing): 50/60Hz ±3Hz 50/60Hz ±3Hz 50/60Hz ±3Hz
input connections: Hard Wire 3-wire Hard Wire 3-wire Hard Wire 3-wire
cord length: 3.1m / 10.2ft 3.1m / 10.2ft 3.1m / 10.2ft
bypass: Internal Bypass (Automatic and Manual)
Batteries and Runtime
battery Type: Maintenance-free sealed Lead-Acid, leakproof
Typical recharge Time (hrs): 2.2 2.2 2.2
replacement battery cartridge: RBC44 RBC44 RBC44
rbc™ Quantity: 2 2 2
runtime Full / Half load (min): 6.3 / 17.9 4 / 13.2 4 / 13.2
Communication and Management
interface Port(s): DB-9, RS-232, RJ-45 10/100 Base-T, SmartSlot
SmartSlot™ interface Qty: UPS Network Management Card w/ Environmental Monitoring
control Panel: LED status display with load and battery bar-graphs and On Line, On Battery, Replace Battery, Overload and Bypass Indicators
audible alarm: Alarm when on battery, low battery alarm, overload alarm
emergency Power off (ePo): Yes Yes Yes
Mechanical
Dimensions - rackmount (in/mm): 13.9 x 17 x 26 / 353.1 x 431.8 x 663.4 10.4 x 17 x 26.1 / 264.2 x 431.8 x 663.4 17.4 x 17 x 26.1 / 442 x 431.8 x 663.4
rack Height: 8RU 6RU 10RU
net weight (lb/kg): 345 / 156.5 224 / 110.7 440 / 199.6
Environmental
Temperature: 0 to 40˚C / 32 to 104˚F 0 to 40˚C / 32 to 104˚F 0 to 40˚C / 32 to 104˚F
Humidity: 0 to 95% 0 to 95% 0 to 95%
elevation: 0 to 3000m / 0 to 10000ft 0 to 3000m / 0 to 10000ft 0 to 3000m / 0 to 10000ft
Storage Temperature: -15 to 45˚C / 5 to 113˚F -15 to 45˚C / 5 to 113˚F -15 to 45˚C / 5 to 113˚F
audible noise at 1 Meter: 55dBA 55dBA 55dBA
online Thermal Dissipation: 1535BTU/hr 2216BTU/hr 2216BTU/hr
Conformance
regulatory approvals: CSA, FCC Part 15 Class A, UL 1778
reference: SURT8000RMXLT-1TF5, SURT8000XLT-1TF5 SURT10000RMXLT, SURT10000XLT SURT10000RMXLT-2TF5, SURT10000XLT-2TF5
Options:extendedbatteryruntimes,interfacecables,NetBotz® accessories and sensors, SmartSlot expansion chassis, UPS dry-contact management, UPS environmental monitoring card, UPS interface expanders, UPS network management cards, UPS out-of-band management, rack enclosures and accessories, NetShelter 2 post open frame racks, NetShelter 4 post open frame racks, NetShelter SX enclosures, NetShelter VX enclosures, rack fan tray, basic rack PDU, metered rack PDU, power cords, rack automatic transfer switch, switched rack PDU, replacement batteries, extended warranty, installation services, on site service, remote monitoring service, StruXure manager, powerchute business edition, and UPS remote power off interface
52
Sin
gle
Ph
ase
UP
S
SYH4K6RMT-P1
Symmetra®
Single Phase UPS
> Configurable for N+1 internal redundancy> Hot-swappable power modules and batteries> Power modules and battery modules connected in parallel> Standard 2 year warranty> Automatic internal bypass> Emergency power off
Symmetra
Models: Symmetra 2000RMSymmetra 2000RM120/208
Symmetra 4000RMSymmetra 4000RM120/208
Symmetra 6000RM
Symmetra 6000RM120/208
configuration: Rackmount Rackmount Rackmount Rackmount Rackmount Rackmount
Output
output Power capacity: 2000VA / 1400W 2000VA / 1400W 4000VA / 2800W 4000VA / 2800W 6000VA / 4200W 6000VA / 4200W
Max configurable Power: 6000VA / 4200W 6000VA / 4200W 6000VA / 4200W 6000VA / 4200W 6000VA / 4200W 6000VA / 4200W
nominal output Voltage: 208V, 240V 120V, 208 / 240V 208V, 240V 120V, 208 / 240V 208V, 240V 120V, 208 / 240V
waveform Type: Sine wave Sine wave Sine wave Sine wave Sine wave Sine wave
output connections:(2) NEMA L6-20R, (1) NEMA L6-30R
(12) NEMA 5-20R, (2) NEMA L6-20R
(2) NEMA L6-20R, (1) NEMA L6-30R
(12) NEMA 5-20R, (2) NEMA L6-20R
(2) NEMA L6-20R, (1) NEMA L6-30R
(12) NEMA 5-20R, (2) NEMA L6-20R
Input
nominal input Voltage: 208V 208V 208V 208V 208V 208V
input Frequency (auto sensing): 50/60Hz ±3Hz 50/60Hz ±3Hz 50/60Hz ±3Hz 50/60Hz ±3Hz 50/60Hz ±3Hz 50/60Hz ±3Hz
input connections: Hard Wire 3-wire, NEMA L6-30P
cord length: 1.8m / 5.9ft 1.8m / 5.9ft 1.8m / 5.9ft 1.8m / 5.9ft 1.8m / 5.9ft 1.8m / 5.9ft
bypass: Internal Bypass (Auto and Manual)
Batteries and Runtime
battery Type: Maintenance-free sealed Lead-Acid, leakproof
Typical recharge Time (hrs): 4 4 4 4 4 3
replacement battery cartridge: SYBT2 SYBT2 SYBT2 SYBT2 SYBT2 SYBT2
rbc™ Quantity: 1 to 4 1 to 4 1 to 2 1 to 2 - -
runtime Full / Half load (min): 12.6 / 29.8 12.3 / 28.4 12.7 / 30.2 12.5 / 29.5 12.7 /30.3 12.6 / 29.8
Communication and Management
interface Port(s):DB-9, RS-232, RJ-45 BaseT ethernet for webb/SNMP mgmt
UPS Network Management Card w/ Environmental Monitoring, DB-9, RS-232, RJ-45 Base-T ethernet for web/ SNMP management
SmartSlot™ interface Qty: 2 1 1 1 1 1
control Panel: LED status display with load and battery bar-graphs and On Line, On Battery, Replace Battery, and Overload Indicators
audible alarm: Alarm when on battery, low battery alarm
Mechanical
Dimensions (in/mm):14 x 19 x 28.8 / 355.6 x 482.6 x 731.5
17.5 x 19 x 28.8 / 444.5 x 482.6 x 731.5
14 x 19 x 28.8 / 355.6 x 482.6 x 731.5
17.5 x 19 x 28.8 / 444.5 x 482.6 x 731.5
14 x 19 x 28.8 / 355.6 x 482.6 x 731.5
17.5 x 19 x 28.8 / 444.5 x 482.6 x 731.5
rack Height: 8RU 10RU 8RU 10RU 8RU 10RU
net weight (lb/kg): 164 / 74.4 259 / 117.5 229 / 103.9 324 / 147 294 / 133.4 389 / 176.4
Environmental
Temperature: 0 to 40˚C / 32 to 104˚F
Humidity: 0 to 95% 0 to 95% 0 to 85% 0 to 95% 0 to 95% 0 to 95%
elevation: 0 to 3000m / 0 to 10000ft
Storage Temperature: -15 to 45˚C / 5 to 113˚F
audible noise at 1 Meter: 60dBA 60dBA 60dBA 60dBA 60dBA 60dBA
online Thermal Dissipation: 430BTU/hr 843BTU/hr 1181BTU/hr 1686BTU/hr 1771BTU/hr 2529BTU/hr
Conformance
regulatory approvals: CSA, FCC Part 15 Class A, UL 1778
reference: SYH2K6RMT SHY2K6RMT-P1 SYH4K6RMT SHY4K6RMT-P1 SYH6K6RMT SHY6K6RMT-P1
Options:extendedbatteryruntimes,interfacecables,NetBotz® accessories and sensors, SmartSlot expansion chassis, UPS dry-contact management, UPS environmental monitoring card, UPS interface expanders, UPS network management cards, UPS out-of-band management, rack enclosures and accessories, NetShelter 2 post open frame racks, NetShelter 4 post open frame racks, NetShelter SX enclosures, NetShelter VX enclosures, rack fan tray, basic rack PDU, metered rack PDU, power cords, rack automatic transfer switch, switched rack PDU, replacement batteries, extended warranty, installation services, on site service, remote monitoring service, StruXure manager, powerchute business edition, and UPS remote power off interface
53
Sin
gle P
hase U
PS
Symmetra® lXSingle Phase UPS
> Modular design
> Power modules and battery modules connected in parallel
> Standard 2 year repair or replace
> Emergency power off SYA12K16P
Symmetra lX
Models: Symmetra 4/8KLX Symmetra 4/8LX-RM Symmetra 8/8KLX Symmetra 8/8KLX-RM Symmetra 8/16KLX
configuration: Tower Rackmount Tower Rackmount Tower
Output
output Power capacity: 4000VA / 3200W 4000VA / 3200W 8000VA / 6400W 8000VA / 6400W 8000VA / 6400W
Max configurable Power: 8000VA / 6400W 8000VA / 6400W 8000VA / 6400W 8000VA / 6400W 16kVA / 12.8kW
nominal output Voltage: 120V, 208V, Configurable for 120/208 or 120/240 output voltage
waveform Type: Sine wave Sine wave Sine wave Sine wave Sine wave
output connections:(1) Hard Wire 4-wire (2PH+N+G)
(1) Hard Wire 4-wire (2PH+N+G), (2) NEMA L14-30R, (4) NEMA L5-20R
(1) Hard Wire 4-wire (2PH+N+G)
(1) Hard Wire 4-wire (2PH+N+G), (2) NEMA L14-30R, (4) NEMA L5-20R
(1) Hard Wire 4-wire (2PH+N+G)
Input
nominal input Voltage: 208V, 240V 208V, 240V 208V, 240V 208V, 240V 208V, 240V
input Frequency (auto sensing): 45 to 65Hz 45 to 65Hz 45 to 65Hz 45 to 65Hz 45 to 65Hz
input connections: Hard Wire 4-wire (2PH+N+G)
bypass: Internal Bypass (Auto and Manual)
Batteries and Runtime
battery Type: Maintenance-free sealed Lead-Acid, leakproof
included battery Modules: 1 1 2 2 2
available battery Slots: 1 1 2 2
Typical recharge Time (hrs): 3 3 3 3 3
replacement battery cartridge: SYBT5 SYBT5 SYBT5 SYBT5 SYBT5
runtime Full / Half load (min): 5.9 / 16.9 5.9 / 16.9 5.9 / 17 5.9 / 17 5.9 / 17
Communication and Management
interface Port(s): DB-9 RS-232, Smart-Slot DB-9 RS-232, Smart-Slot DB-9 RS-232, Smart-Slot DB-9 RS-232, Smart-Slot DB-9 RS-232, Smart-Slot
SmartSlot™ interface Qty: UPS Network Management Card w/ Environmental Monitoring
control Panel: Multi-function LCD status and control console
audible alarm: Audible and visible alarms prioritized by severity
Mechanical
Dimensions (in/mm):26 x 4 x 28.6/ 660 x 483 x 726
22.5 x 18.6 x 27.1 / 572 x 472 x 688
23.7 x 19 x 28.6 / 602 x 483 x 726
22.5 x 18.6 x 27.1 / 572 x 472 x 688
36.8 x 19 x 28.6 / 937 x 483 x 726
rack Height: - 13RU - 13RU -
net weight (lb/kg): 347.7 / 157.7 295.6 / 134.1 444.9 / 201.8 392.8 / 178.2 484 / 219.6
Environmental
Temperature: 0 to 40˚C / 32 to 104˚F
Humidity: 0 to 95% 0 to 95% 0 to 95% 0 to 95% 0 to 95%
elevation: 0 to 3000m / 0 to 10000ft
Storage Temperature: -15 to 45˚C / 5 to 113˚F
audible noise at 1 Meter: 62dBA 62dBA 62dBA 62dBA 62dBA
online Thermal Dissipation: 3485BTU/hr 3707BTU/hr 3485BTU/hr 3707BTU/hr 4995BTU/hr
Conformance
regulatory approvals: CSA, FCC Part 15 Class A, UL 1778
reference: SYA4K8P SYA4K8RMP SYA8K8P SYA8K8RMP SYA8K16P
Options:extendedbatteryruntimes,interfacecables,NetBotz® accessories and sensors, SmartSlot expansion chassis, UPS dry-contact management, UPS environmental monitoring card, UPS interface expanders, UPS network management cards, UPS out-of-band management, rack enclosures and accessories, NetShelter 2 post open frame racks, NetShelter 4 post open frame racks, NetShelter SX enclosures, NetShelter VX enclosures, rack fan tray, basic rack PDU, metered rack PDU, power cords, rack automatic transfer switch, switched rack PDU, replacement batteries, extended warranty, installation services, on site service, remote monitoring service, StruXure manager, powerchute business edition, and UPS remote power off interface
54
Sin
gle
Ph
ase
UP
S
Symmetra® lXSingle Phase UPS
> Configurable for N+1 internal redundancy
> Hot-swappable power modules and batteries
> Automatic internal bypass
SYA4K8P
Symmetra lX
Models: Symmetra 8/16KLX-E Symmetra 8/16KLX-RM Symmetra 12/16KLX Symmetra 12/16KLX-E
configuration: Tower Rackmount Tower Tower
Output
output Power capacity: 8000VA / 6400W 8000VA / 6400W 12kVA / 9600W 12kVA / 9600W
Max configurable Power: 16kVA / 12.8kW 16kVA / 12.8kW 16kVA / 12.8kW 16kVA / 12.8kW
nominal output Voltage: 120V, 208V, Configurable for 120/208 or 120/240 output voltage
waveform Type: Sine wave Sine wave Sine wave Sine wave
output connections:(1) Hard Wire 4-wire (2PH+N+G)
(1) Hard Wire 4-wire (2PH+N+G), (4) NEMA L14-30R, (8) NEMA L5-20R
(1) Hard Wire 4-wire (2PH+N+G)
Input
nominal input Voltage: 208V, 240V 208V, 240V 208V, 240V 208V, 240V
input Frequency (auto sensing): 45 to 65Hz 45 to 65Hz 45 to 65Hz 45 to 65Hz
input connections: Hard Wire 4-wire (2PH+N+G)
bypass: Internal Bypass (Auto and Manual)
Batteries and Runtime
battery Type: Maintenance-free sealed Lead-Acid, leakproof
included battery Modules: 9 2 3 9
available battery Slots: 4 2 1 4
Typical recharge Time (hrs): 7.5 3 3 7.5
replacement battery cartridge: SYBT5 SYBT5 SYBT5 SYBT5
runtime Full / Half load (min): 49.3 / 106.4 5.9 / 17 6 / 17.1 30.1 / 66.9
Communication and Management
interface Port(s): DB-9 RS-232, Smart-Slot DB-9 RS-232, Smart-Slot DB-9 RS-232, Smart-Slot DB-9 RS-232, Smart-Slot
SmartSlot™ interface Qty: UPS Network Management Card w/ Environmental Monitoring
control Panel: Multi-function LCD status and control console
audible alarm: Audible and visible alarms prioritized by severity
Mechanical
Dimensions (in/mm): 59.7 x 19 x 28.6 / 1516 x 483 x 726 32.9 x 18.6 x 27.1 / 836 x 472 x 688 36.8 x19 x 28.6 / 937 x 483 x 726 59.7 x 19 x 28.6 / 1516 x 483 x 726
rack Height: - 19RU - -
net weight (lb/kg): 1044.2 / 473.6 438 / 198.7 581.2 / 263.6 1077.3 / 488.6
Environmental
Temperature: 0 to 40˚C / 32 to 104˚F 0 to 40˚C / 32 to 104˚F 0 to 40˚C / 32 to 104˚F 0 to 40˚C / 32 to 104˚F
Humidity: 0 to 95% 0 to 95% 0 to 95% 0 to 95%
elevation: 0 to 3000m / 0 to 10000ft 0 to 3000m / 0 to 10000ft 0 to 3000m / 0 to 10000ft 0 to 3000m / 0 to 10000ft
Storage Temperature: -15 to 45˚C / 5 to 113˚F -15 to 45˚C / 5 to 113˚F -15 to 45˚C / 5 to 113˚F -15 to 45˚C / 5 to 113˚F
audible noise at 1 Meter: 62dBA 62dBA 62dBA 62dBA
online Thermal Dissipation: 4995BTU/hr 4995BTU/hr 4995BTU/hr 4995BTU/hr
Conformance
regulatory approvals: CSA, FCC Part 15 Class A, UL 1778
reference: SYA8K16PXR SYA8K16RMP SYA12K16P SYA12K16PXR
Options:extendedbatteryruntimes,interfacecables,NetBotz® accessories and sensors, SmartSlot expansion chassis, UPS dry-contact management, UPS environmental monitoring card, UPS interface expanders, UPS network management cards, UPS out-of-band management, rack enclosures and accessories, NetShelter 2 post open frame racks, NetShelter 4 post open frame racks, NetShelter SX enclosures, NetShelter VX enclosures, rack fan tray, basic rack PDU, metered rack PDU, power cords, rack automatic transfer switch, switched rack PDU, replacement batteries, extended warranty, installation services, on site service, remote monitoring service, StruXure manager, powerchute business edition, and UPS remote power off interface
55
Sin
gle P
hase U
PS
Symmetra® lXSingle Phase UPS
> Automatic restart of loads after UPS shutdown
> Field-replaceable power distribution panel
> Scalable power capacity and runtime
Symmetra lX
Models: Symmetra 12/16KLX-RM Symmetra 16/16KLX Symmetra 16/16KLX-E Symmetra 16/16KLX-RM
configuration: Rackmount Tower Tower Rackmount
Output
output Power capacity: 12kVA / 9600W 16kVA / 12.8kW 16kVA / 12.8kW 16kVA / 12.8kW
Max configurable Power: 16kVA / 12.8kW 16kVA / 12.8kW 16kVA / 12.8kW 16kVA / 12.8kW
nominal output Voltage: 120V, 208V, Configurable for 120/208 or 120/240 output voltage
waveform Type: Sine wave Sine wave Sine wave Sine wave
output connections:(1) Hard Wire 4-wire (2PH+N+G), (4) NEMA L14-30R, (8) NEMA L5-20R
(1) Hard Wire 4-wire (2PH+N+G)
(1) Hard Wire 4-wire (2PH+N+G)
(1) Hard Wire 4-wire (2PH+N+G), (4) NEMA L14-30R, (8) NEMA L5-20R
Input
nominal input Voltage: 208V, 240V 208V, 240V 208V, 240V 208V, 240V
input Frequency (auto sensing): 45 to 65Hz 45 to 65Hz 45 to 65Hz 45 to 65Hz
input connections: Hard Wire 4-wire (2PH+N+G)
bypass: Internal Bypass (Auto and Manual)
Batteries and Runtime
battery Type: Maintenance-free sealed Lead-Acid, leakproof
included battery Modules: 3 4 9 4
available battery Slots: 1 - 4 -
Typical recharge Time (hrs): 3 3 7.5 3
replacement battery cartridge: SYBT5 SYBT5 SYBT5 SYBT5
runtime Full / Half load (min): 6 / 17.1 6 / 17.1 20.8 / 47.8 6 / 17.1
Communication and Management
interface Port(s): DB-9 RS-232, Smart-Slot DB-9 RS-232, Smart-Slot DB-9 RS-232, Smart-Slot DB-9 RS-232, Smart-Slot
SmartSlot™ interface Qty: UPS Network Management Card w/ Environmental Monitoring
control Panel: Multi-function LCD status and control console
audible alarm: Audible and visible alarms prioritized by severity
Mechanical
Dimensions (in/mm): 32.9 x 18.6 x 27.1 / 836 x 472 x 688 36.8 x 19 x 28.6 / 726 x 483 x 726 59.7 x 19 x 28.6 / 726 x 483 x 726 36.8 x 19 x 28.6 / 726 x 483 x 726
rack Height: 19RU - - 19RU
net weight (lb/kg): 535.1 / 242.7 678.4 / 307.7 1110.3 / 503.6 632.3 / 286.8
Environmental
Temperature: 0 to 40˚C / 32 to 104˚F 0 to 40˚C / 32 to 104˚F 0 to 40˚C / 32 to 104˚F 0 to 40˚C / 32 to 104˚F
Humidity: 0 to 95% 0 to 95% 0 to 95% 0 to 95%
elevation: 0 to 3000m / 0 to 10000ft 0 to 3000m / 0 to 10000ft 0 to 3000m / 0 to 10000ft 0 to 3000m / 0 to 10000ft
Storage Temperature: -15 to 45˚C / 5 to 113˚F -15 to 45˚C / 5 to 113˚F -15 to 45˚C / 5 to 113˚F -15 to 45˚C / 5 to 113˚F
audible noise at 1 Meter: 62dBA 62dBA 62dBA 62dBA
online Thermal Dissipation: 4995BTU/hr 4995BTU/hr 4995BTU/hr 4995BTU/hr
Conformance
regulatory approvals: CSA, FCC Part 15 Class A, UL 1778
reference: SYA12K16RMP SYA16K16P SYA16K16PXR SYA16K16RMP
Options:extendedbatteryruntimes,interfacecables,NetBotz® accessories and sensors, SmartSlot expansion chassis, UPS dry-contact management, UPS environmental monitoring card, UPS interface expanders, UPS network management cards, UPS out-of-band management, rack enclosures and accessories, NetShelter 2 post open frame racks, NetShelter 4 post open frame racks, NetShelter SX enclosures, NetShelter VX enclosures, rack fan tray, basic rack PDU, metered rack PDU, power cords, rack automatic transfer switch, switched rack PDU, replacement batteries, extended warranty, installation services, on site service, remote monitoring service, StruXure manager, powerchute business edition, and UPS remote power off interface
SYA8K16RMP
56
Sin
gle
Ph
ase
UP
S
1600eP SeriesSingle Phase UPS
> Freestanding configurations 3.6 to 22kVA
> Compact footprint and high-power density
> Hot swappable batteries and slide-out battery trays
> Standard external battery connector for extended runtime
> Optional features include modular receptacle panel and Internal SNMP/web browser interface
1600eP Series
1600EP Series Dual Conversion
3600EP 6000EP 8000EP 10000EP 14000EP 18000EP 22000EP
output Power rating: 3.6kVA / 3.06kW 6kVA / 5.1kW 8kVA / 6.8kw 10kVA / 8.5kW 14kVA / 11.9kW 18kVA / 15.3kW 22kVA / 18.7kW
output Power Factor: 0.85 0.85 0.85 0.85 0.85 0.85 0.85
input Voltage: 208/240Vac 208/240Vac 208/240Vac 208/240Vac 208/240Vac 208/240Vac 208/240Vac
output Voltage: 120/208/240Vac 120/208/240Vac 120/208/240Vac 120/208/240Vac 120/208/240Vac 120/208/240Vac 120/208/240VacTypical efficiency- ac/ac 100% load:
85% 85% 85% 85% 85% 85% 85%
Typical Heat output (bTu/hr): 1588 2610 3482 4352 6092 7832 9600
Mechanical
Dimensions (in/mm):10 x 27.5 x 33 / 254 x 698.5 x 838.2
10 x 27.5 x 33 / 254 x 698.5 x 838.2
13 x 28.3 x 33.5 / 330.2 x 717.6 x 222.3
13 x 28.3 x 33.5 / 330.2 x 717.6 x 850.9
17.5 x 39 x 34.8 / 444.5 x 993 x 883.9
17.5 x 39 x 34.8 / 444.5 x 993 x 883.9
17.5 x 39 x 34.8 / 444.5 x 993 x 883.9
weight (lb/kg): 365 / 169.6 385 / 174.6 490 / 222.3 490 / 222.3 620 / 281.2 750 / 340.2 755 / 343
Internal Battery Runtime
Full load @ .85 Power Factor: 14min 7min 7min 5min 7min 5min 3min
Half load @ .85 Power Factor: 42min 21min 21min 15min 21min 15min 9minNote:Internalruntimeat.7powerfactorisapproximately30%more.Externalbatteryruntimeoptionsareavailablefrom30minutesto8hours.PleasecontactyourAlphasalesrepresentativeformore information.
Specifications
input Frequency: 45 to 65Hz Auto sensing
output Frequency: 60Hz, ±0.1%
operating input Voltage range: -30 to 10%
output Voltage regulation: ±3% Max., ±1% Typical
overload capacity: 125% for 10min, 150% for 10sec, 1000% for 1 Cycle
Status and control Features:
LCDReadout:ACinputandoutputvoltage, input and output frequency, output current, battery voltage and test results, number of discharges and faultsTouch pad UPS/Bypass operationEmergency power off terminalsUPS inverter/bypass mode
Standard Features:
UPS operation Alarm reset operation Slide out battery trays LED display with key pad status LEDs Hot swappable batteries Internal SNMP device with optional SNMP/Web slide in cardRS-232 interface External battery interface
optional Features:Maintenance bypass Internal SNMP/Web slide-in card Modular receptacle
Warranty
uPS:Three-year parts and labor on-site in continental US only
batteries: Two-year full
1600EP Series
57
Th
ree Ph
ase UP
S
Triniti™ 4200 SeriesThree Phase UPS
Triniti 4200 Series
Power Ratinginput Power Factor correction:
>0.95 PF (lagging)
input Harmonic currents: <3% THD (typical)
input Frequency range: 60Hz, ±5%
load crest Factor: ≤3
overload capacity inverter: 125% for 90sec, 150% for 30sec
overload capacity bypass: 125% for 10ms, 1000% for 1 cycle
neutral conductor Size: 1.73 x conductor
load inrush current Protection:Automatically transfers to bypass then retransfers to inverter
Typical efficiency ac/ac: 87%
output Frequency: 60Hz, ±0.1%
Status and Control
ac input Present: Input and output frequency
inverter operating: Operating status menu
uPS on bypass: Diagnostic status menu
uPS on battery: DB9 dry contact interface
Fault: RS232 communications
input and output Voltage: Emergency power off switch
output current indicator: Run/Stop key switch
battery Voltage indicator:Terminal block (input/output power connector) Internal maintenance bypass (except on 80kVA)
optional Features: External maintenance bypass, SNMP
Warranty
3 year parts and labor, 2 years on batteries. See warranty statement for further details, conditions and limitations.
Model Triniti 15 Triniti 25 Triniti 50 Triniti 80
output Power rating: 15kVA / 12kW 25kVA / 20kW 50kVA / 40kW 80kVA / 64kW
input Voltage (-15 to 10%; -30% if derated): 208/120 4 wire + gnd 208/480 3 wire + gnd 208/480 3 wire + gnd 208/480 3 wire + gnd
output Voltage (±2% regulation balanced load): 208/120 4 wire + gnd 208/120 4 wire + gnd 208/120 4 wire + gnd 208/120 4 wire + gnd
input circuit breaker @ 208V: 60A 90A 175A 300A
output current Per Phase @ 208/120V: 41.7A 69.4A 138A 222A
Typical Heat output (KbTu/Hr): 5.73 7.6 17.73 24.27
audible noise at 1 Meter From Front Panel: <60dBA <60dBA <65dBA <65dBA
Internal Battery Runtime
Full load @ 0.7 Power Factor: 10min 5min 5min External Battery
Half load @ 0.7 Power Factor: 30min 15min 15min Pack Options*
Mechanical
Dimensions (in/mm): 20 x 36.3 x 59.8 / 508 x 922 x 1518.9
20 x 36.3 x 59.8 / 508 x 922 x 1518.9
35.6 x 37.6 x 59.8 /904.2 x 939.8 x 1518.9
44 x 31 x 74 / 1117.6 x 787.4 x 1879.6
weight (lb/kg): 900 / 408.2 910 / 412.7 2548 / 1155.8 2450 / 111.3
* 4 to 64min runtime options
> 15, 25, 50 and 80kVA power ratings
> 100% front access
> Internal maintenance bypass (except on 80kVA)
>“ActiveFrontEnd”providestotalpowerfactor correction and utility cost savings
> Internal batteries reduce footprint for easy installation (except on 80kVA)
Triniti 80kVA
Triniti 15kVA
58
Th
ree
Ph
ase
UP
S
galaxyThree Phase UPS
> Power ranges 10, 15, 20 and 30kVA
> True online double conversion technology
> Network-based power management
> Input Power Factor Correction (PFC)
> All-in-one complete solution
> Parallel Ready
galaxy
Output Power Rating 10kVA 15kVA 20kVA 30kVA
Input
Voltage: 208 / 220 / 480 / 600V 208 / 220 / 480 / 600V 208 / 220 / 480 / 600V 208 / 220 / 480 / 600V
Frequency: 60Hz (-25 to 8%) 60Hz (-25 to 8%) 60Hz (-25 to 8%) 60Hz (-25 to 8%)
Power Factor: <0.99 <0.99 <0.99 <0.99
current Distortion (THD): <3% <3% <3% <3%
current (a @ 208V): 28 42 56 83
breaker (@208): 40 60 80 125
Output
Voltage: 208 (220 / 480 / 600) 208 (220 / 480 / 600) 208 (220 / 480 / 600) 208 (220 / 480 / 600)
Frequency: 60Hz (±1 to 4% selectable) 60Hz (±1 to 4% selectable) 60Hz (±1 to 4% selectable) 60Hz (±1 to 4% selectable)
Transient response: ±3% for 0 to 100% to 0% ±3% for 0 to 100% to 0% ±3% for 0 to 100% to 0% ±3% for 0 to 100% to 0%
Voltage Distortion THD: <3% L-L and L-N <3% L-L and L-N <3% L-L and L-N <3% L-L and L-N
inverter overload: 120% for 1min - 145% for 30 sec 120% for 1min, 145% for 30 sec 120% for 1min, 145% for 30 sec 120% for 1min, 145% for 30 sec
bypass overload: 10x nominal current - 1 cycle 10x nominal current - 1 cycle 10x nominal current - 1 cycle 10x nominal current - 1 cycle
output current (a @ 208V): 28 42 56 83
Heat rejection (max bTus): 4,821 7,232 8,895 13,342
Batteries
backup Time (minutes)1: 11 / 39 / 60 7 / 22 / 35 / 55 15 / 24 / 38 8 / 12 / 21
Mechanical
cabinet Mechanical Dimensions (in/cm):32.8 x 40.1 x 62.4 / 83.8 x 101.8 x 158.5
32.8 x 40.1 x 62.4 / 83.8 x 101.8 x 158.5
32.8 x 40.1 x 62.4 / 83.8 x 101.8 x 158.5
32.8 x 40.1 x 62.4 / 83.8 x 101.8 x 158.5
Max. weight2 (lb/kg): 2565 / 1163.5 2565 / 1163.5 2565 / 1163.5 2565 / 1163.5
Micro Cabinet3 Dimensions
Micro cabinet3 Dimensions (in/cm):23 x 35.5 x 48.5 / 58.4 x 90.2 x 123.2
23 x 35.5 x 48.5 / 58.4 x 90.2 x 123.2
— —
Max. weight (lb/kg): 830 / 376.5 830 / 376.5 — —
Auxiliary Cabinets
Maintenance bypass cabinet (in/cm):18.8 x 41.1 x 62.4 / 47.7 x 104.4 x 158.5
18.8 x 41.1 x 62.4 / 47.7 x 104.4 x 158.5
18.8 x 41.1 x 62.4 / 47.7 x 104.4 x 158.5
18.8 x 41.1 x 62.4 / 47.7 x 104.4 x 158.5
battery cabinet (in/cm): 23 x 35.5 x 62.4 / 58.4 x 90.2 x 158.5
23 x 35.5 x 62.4 / 58.4 x 90.2 x 158.5
23 x 35.5 x 62.4 / 58.4 x 90.2 x 158.5
23 x 35.5 x 62.4 / 58.4 x 90.2 x 158.5
Max. weight (lb/kg): 2723 / 1235 2723 / 1235 2723 / 1235 2723 / 1235
Standards
Standards: UL 1778, cUL, FCC Class A parts, 15 sub part J Class A, IEC 1000 level 4, IEEE C62.41-B3, NEC, ISO 9001
Notes: 1 11/7min battery times only applicable for micro cabinet. 2 Weight will vary based on battery runtime and input volt options. 3 Micro Cabinet only available in 208/208V. External maintenance bypass distribution options not available with micro cabinet.
Standard Features:
True double conversion online topology, Low audible noise fans (<53dBA), Input power factor correction (IGBT) rectifier, Casters with leveling feet, Input distortion management, Network based software for multi-server control, Digital power quality management system, Dry contact i/o card, (PWM/IGBT inverter), SNMP manageable, Step load voltage stabilization, Intelligent battery management system, color graphic display with multilingual user interface, Fault tolerant architecture, Bottom or top entry, Scalable architecture (10 and 20kVA models), Integrated maintenance bypass (single module only), No extra cabinet for isolation transformer, Four communications ports, Integrated battery bank, 12 month warranty.
Galaxy
59
Th
ree Ph
ase UP
S
galaxy 4000Three Phase UPS
> Power ranges 40, 50, 65 and 75kVA
> True online double conversion technology
> Low UPS to generator sizing
> Power surge stabilization system
> Power factor corrected input SNMP and network based power management options
galaxy 4000
Output Power Rating 40kVA / 32kW 50kVA / 40kW 65kVA / 52kW 75kVA / 60kW
Input
Voltage: 208V 208V 208V 208V
input Frequency: 60Hz (±5%) 60Hz (±5%) 60Hz (±5%) 60Hz (±5%)
Power Factor: >0.98 >0.98 >0.98 >0.98
current Distortion (THD): <3% @ Full load <3% @ Full load <3% @ Full load <3% @ Full load
current (a @ 208V): 102 127 166 191
Output
Voltage: 208V 208V 208V 208V
Frequency: 60Hz (±1 to 4% selectable) 60Hz (±1 to 4% selectable) 60Hz (±1 to 4% selectable) 60Hz (±1 to 4% selectable)
Transient response: ±5% for 0 to 100% to 0% ±5% for 0 to 100% to 0% ±5% for 0 to 100% to 0% ±5% for 0 to 100% to 0%
Voltage Distortion THD: <1% L-L and L-N <1% L-L and L-N <1% L-L and L-N <1% L-L and L-N
inverter overload 130%: 1min 1min 1min 1min
inverter overload 145%: 30 sec 30 sec 30 sec 30 sec
bypass overload: 10x nominal current - 1 cycle 10x nominal current - 1 cycle 10x nominal current - 1 cycle 10x nominal current - 1 cycle
output current (a @ 208V): 111 139 180 208
Heat rejection (max bTus): 14,900 18,700 24,200 28,000
Runtimes @ 100% Load
1 x 285w/cell: 12 9 6 -
1 x 370w/cell: 20 14 9 8
1 x 500w/cell: 28 22 15 11
2 x 370w/cell: 47 36 25 22
2 x 500w/cell: 67 52 38 31
3 x 500w/cell: 98 85 60 53
4 x 500w/cell: 136 115 85 72
Mechanical Specifications
Standard cabinet Dimensions (in/mm):33.5 x 35.6 x 72.1 / 850 x 901 x 1831
33.5 x 35.6 x 72.1 / 850 x 901 x 1831
33.5 x 35.6 x 72.1 / 850 x 901 x 1831
33.5 x 35.6 x 72.1 / 850 x 901 x 1831
weight (lb/kg): 1235 / 560 1235 / 560 1235 / 560 1235 / 560
battery cabinet Dimensions (in/mm):26.5 x 35.5 x 72.1 / 673 x 901 x 1831
26.5 x 35.5 x 72.1 / 673 x 901 x 1831
26.5 x 35.5 x 72.1 / 673 x 901 x 1831
26.5 x 35.5 x 72.1 / 673 x 901 x 1831
weight (lb/kg): 2045 / 928 2045 / 928 2045 / 928 2045/928
battery cabinet Dimensions (in/mm):33.5 x 35.6 x 72.1 / 850 x 901 x 1831
33.5 x 35.6 x 72.1 / 850 x 901 x 1831
33.5 x 35.6 x 72.1 / 850 x 901 x 1831
33.5 x 35.6 x 72.1 / 850 x 901 x 1831
weight (lb/kg): 2745 / 1245 2745 / 1245 2745 / 1245 2745 / 1245
Standards
Standards: ISO 9001, UL 1778, cUL, FCC Part 15, subpart J, Class A, NEMA PE 1, NEMA 250, NFPA 70, IEC 10000 (801) level 4, OSHA
Standard Features:
True double conversion online topology, Input power factor correction (IGBT rectifier), Dual input, Input distortion management, Digital power quality management system (PWM/IGBT inverter), Step load voltage stabilization, Intelligent battery management system, Fault tolerant architecture, Casters with stabilizing feet, Network based software for multi-server control, Dry contact I/O card, SNMP manageable, Graphic display with multilingual user interface, Bottom or top entry, Four communications ports.
Galaxy 4000
60
Th
ree
Ph
ase
UP
S
Symmetra® PXThree Phase UPS
> Configurable for N+1 internal redundancy
> Redundant intelligence modules
> Power modules and battery modules connected in parallel
> Scalable power capacity and runtime
> Emergency power off SY10K40F
Symmetra PX
Models:Symmetra 80/80PX
Symmetra 70/80PX
Symmetra 60/80PX
Symmetra 50/80PX
Symmetra 40/80PX
Symmetra 40/40PX
Output
output Power capacity: 80kVA / 80kW 70kVA / 70kW 60kVA / 60kW 50kVA / 50kW 40kVA / 40kW 40kVA / 40kW
Max configurable Power: 80kVA / 80kW 80kVA / 80kW 80kVA / 80kW 80kVA / 80kW 80kVA / 80kW 40kVA / 40kW
nominal output Voltage: 120V, 208V, 208V 3PH 120V, 208V, 208V 3PH 120V, 208V, 208V 3PH 120V, 208V, 208V 3PH 120V, 208V, 208V 3PH 120V, 208V, 208V 3PH
waveform Type: Sine wave Sine wave Sine wave Sine wave Sine wave Sine wave
output Frequency (sync to mains): 57 to 63Hz for 60Hz nominal
output connections: (1) Hard Wire 5-wire (3PH + N + G), (1) Screw Terminal
output Voltage Tolerance: - - - - - -
Input
nominal input Voltage: 208V 3PH 208V 3PH 208V 3PH 208V 3PH 208V 3PH 208V 3PH
input Frequency (auto sensing): 50/60Hz ±5Hz 50/60Hz ±5Hz 50/60Hz ±5Hz 50/60Hz ±5Hz 50/60Hz ±5Hz 50/60Hz ±5Hz
input connections: Hard Wire 5-wire (3PH + N + G)
bypass: Built-in Static Bypass Built-in Static Bypass Built-in Static Bypass Built-in Static Bypass Built-in Static Bypass Built-in Static Bypass
Max bypass input current: 162A 162A 162A 162A 162A 162A
bypass Protection Device: 175A 175A 175A 175A 175A 175A
Batteries and Runtime
battery Type: No internal battery - uses external battery system Maintenance-free sealed Lead-Acid, leakproof
included battery Modules: 8 7 6 5 4 4available battery Slots: - 1 2 3 4 -Typical recharge Time (hrs)**: 2 2 2 2 2 2replacement battery cartridge: SYBT4 SYBT4 SYBT4 SYBT4 SYBT4 SYBT4
runtime Full / Half load (min): 3.5 / 13.7 3.5 / 13.7 3.5 / 13.7 3.5 / 13.7 3.6 / 13.9 3.5 / 14
Communication and Management
interface Port(s): Contact Closure, RJ-45 10 Base-T ethernet for web/ SNMP/ Telnet management, Smart-Slot
Pre-installed SmartSlot: AP9617 AP9617 AP9617 AP9617 AP9617 AP9617
control Panel: - - - - - Multi-function LCD status and control console
audible alarm: Alarm when on battery, distinctive low battery alarm, configurable delays
Mechanical
Dimensions (in/mm):81.5 x 48 x 35.5 / 2070 x 1219 x 902
81.5 x 48 x 35.5 / 2070 x 1219 x 902
81.5 x 48 x 35.5 / 2070 x 1219 x 902
81.5 x 48 x 35.5 / 2070 x 1219 x 902
81.5 x 48 x 35.5 / 2070 x 1219 x 902
81.5 x 23.6 x 35.5 / 2070 x 600 x 902
rack Height: 42RU 42RU 42RU 42RU 42RU 42RUnet weight (lb/kg): 3262.8 / 1480 3005.3 / 1363.2 2747.8 / 1246.4 2490.2 / 1129.6 2232.7 / 1012.7 1708.6 / 775
EnvironmentalTemperature: 0 to 40˚C / 32 to 104˚F -50 to 40˚C / -58 to 104˚F 0 to 40˚C / 32 to 104˚FHumidity: 0 to 95% 0 to 95% 0 to 95% 0 to 95% 0 to 95% 0 to 95%
elevation: 0 to 3000m / 0 to 10000ft
Storage Temperature: -15 to 40˚C / 5 to 104˚Faudible noise at 1 Meter: 71dBA 71dBA 71dBA 71dBA 64dBA 64dBAonline Thermal Dissipation: 22744BTU/hr 20797BTU/hr 17826BTU/hr 14855BTU/hr 11884BTU/hr 11611BTU/hr
Conformance
regulatory approvals: cUL Listed, CSA, FCC Part 15 Class A, ISO 14001, ISO 9001, UL 1778
cUL Listed, EN 50091-1, EN 50091-2, FCC Part 15 Class A, ISO 14001, ISO 9001, UL 1778, UL 60950
reference: SY80K80F SY70K80F SY60K80F SY50K80F SY40K80F SY40K40F
**The time to recharge to 90% of full battery capacity following a discharge to shutdown using a load rated for 1/2 the full load rating of the UPS.
61
Th
ree Ph
ase UP
S
Symmetra® PXThree Phase UPS
> Front-access servicing
> Programmable frequency
> LED Status indicators
> LCD display
> Standard 1 year repair or replaceSY10K80F
Symmetra PX
Models:Symmetra 30/80PX
Symmetra 30/40PX
Symmetra 20/80PX
Symmetra 20/40PX
Symmetra 10/80PX
Symmetra 10/40PX
Output
output Power capacity: 30kVA / 30kW 30kVA / 30kW 20kVA / 20kW 20kVA / 50kW 10kVA / 10kW 10kVA / 10kW
Max configurable Power: 80kVA / 80kW 40kVA / 40kW 80kVA / 80kW 40kVA / 40kW 80kVA / 80kW 40kVA / 40kW
nominal output Voltage: 120V, 208V, 208V 3PH 120V, 208V, 208V 3PH 120V, 208V, 208V 3PH 120V, 208V, 208V 3PH 120V, 208V, 208V 3PH 120V, 208V, 208V 3PH
waveform Type: Sine wave Sine wave Sine wave Sine wave Sine wave Sine wave
output Frequency (sync to mains): 57 to 63Hz for 60Hz nominal
output connections: (1) Hard Wire 5-wire (3PH + N + G), (1) Screw Terminals
output Voltage Tolerance: - - - - - ±1% static and ±5% at 100% load step
Input
nominal input Voltage: 208V 3PH 208V 3PH 208V 3PH 208V 3PH 208V 3PH 208V 3PH
input Frequency (auto sensing): 50/60Hz ±5Hz 50/60Hz ±5Hz 50/60Hz ±5Hz 50/60Hz ±5Hz 50/60Hz ±5Hz 50/60Hz ±5Hz
input connections: Hard Wire 5-wire (3PH + N + G)bypass: Built-in Static Bypass Built-in Static Bypass Built-in Static Bypass Built-in Static Bypass Built-in Static Bypass Built-in Static BypassMax bypass input current: 162A 162A 162A 162A 162A 162Abypass Protection Device: 175A 175A 175A 175A 175A 175A
Batteries and Runtime
battery Type: No internal battery - uses external battery system
Maintenance-free sealed Lead-Acid, leakproof
No internal battery - uses external battery system
Maintenance-free sealed Lead-Acid, leakproof
No internal battery - uses external battery system
Maintenance-free sealed Lead-Acid, leakproof
included battery Modules: 3 3 2 2 1 1available battery Slots: 5 1 6 2 7 3Typical recharge Time (hrs)**: 2 2 2 2 2 2replacement battery cartridge: SYBT4 SYBT4 SYBT4 SYBT4 SYBT4 SYBT4runtime Full / Half load (min): 3.5 / 13.7 3.7 / 14.2 3.5 / 13.6 3.5 / 13.5 3.6 / 13.8 3.4 / 13.5
Communication and Management
interface Port(s): Contact Closure, RJ-45 10 Base-T ethernet for web/ SNMP/ Telnet management, Smart-Slot
RJ-45 10 Base-T ethernet for web/ SNMP/ Telnet management, SmartSlot
Contact Closure, RJ-45 10 Base-T ethernet for web/ SNMP/ Telnet management, Smart-Slot
Pre-installed SmartSlot: AP9617 AP9617 AP9617 AP9617 AP9617 AP9617
control Panel: - Multi-function LCD status and control console - Multi-function LCD status
and control console - Multi-function LCD status and control console
audible alarm: Alarm when on battery, distinctive low battery alarm, configurable delays
Mechanical
Dimensions (in/mm):81.5 x 48 x 35.5 / 2070 x 1219 x 902
81.5 x 23.6 x 35.5 / 2070 x 600 x 902
81.5 x 48 x 35.5 / 2070 x 1219 x 902
81.5 x 23.6 x 35.5 / 2070 x 600 x 902
81.5 x 48 x 35.5 / 2070 x 1219 x 902
81.5 x 23.6 x 35.5 / 2070 x 600 x 902
rack Height: 42RU 42RU 42RU 42RU 42RU 42RU
net weight (lb/kg): 1975.1 / 895.9 1438 / 652.27 1717.6 / 779.1 1167.5 / 529.6 1460.1 / 662.3 897 / 406.8
Environmental
Temperature: 0 to 40˚C / 32 to 104˚F -50 to 40˚C / -58 to 104˚F 0 to 40˚C / 32 to 104˚F
Humidity: 0 to 95% 0 to 95% 0 to 95% 0 to 95% 0 to 95% 0 to 95%
elevation: 0 to 3000m / 0 to 10000ft
Storage Temperature: -15 to 40˚C / 5 to 104˚Faudible noise at 1 Meter: 64dBA 64dBA 64dBA 64dBA 64dBA 64dBAonline Thermal Dissipation: 8913BTU/hr 8913BTU/hr 5942BTU/hr 5942BTU/hr 3381BTU/hr 3381BTU/hr
Conformance
regulatory approvals:
cUL Listed, CSA, FCC Part 15 Class A, ISO 14001, ISO 9001, UL 1778
cUL Recognized, EN 50091-1, EN 50091-2, FCC Part 15 Class A, ISO 14001, ISO 9001, UL 1778, UL 60950
cUL Listed, CSA, FCC Part 15 Class A, ISO 14001, ISO 9001, UL 1778
cUL Listed, EN 50091-1, EN 50091-2, FCC Part 15 Class A, ISO 14001, ISO 9001, UL 1778, UL 60950
cUL Listed, CSA, FCC Part 15 Class A, ISO 14001, ISO 9001, UL 1778
cUL Listed, EN 50091-1, EN 50091-2, EN 50091-3, FCC Part 15 Class A, ISO 14001, ISO 9001, UL 1778, UL 60950
reference: SY30K80F SY30K40F SY20K80F SY20K40F SY10K80F SY10K40F**The time to recharge to 90% of full battery capacity following a discharge to shutdown using a load rated for 1/2 the full load rating of the UPS.
62
Th
ree
Ph
ase
UP
S
galaxy Pw SeriesThree Phase UPS
> Parallel modules for capacity or redundancy
> 0.9 output power factor
> Modular design for easy upgrading or expansion
> Field upgradeable power output**
> Generator friendly for low UPS to generator sizing ratios
> Advanced battery management system with automatic self testing
** on 100-200 kVA modules only
galaxy Pw Series
Power Rating 100 kVA/90kW 130 kVA/117kW 150 kVA/135kW
input Voltage: 208 480 480 600 208 480 480 600 208 480 480 600
output Voltage: 208 208 480 600 208 208 480 600 208 208 480 600
nominal input current: 312 135 135 108 415 180 180 144 485 210 210 168
nominal output current: 279 279 121 97 362 362 157 126 418 418 181 145
Dccurrent at nominal Voltage: — — 219 — — 283 — — — — 331 —
efficiency at 100%: — — 92.5% — — 93% — — — — 93% —
Full load Heat rejection (bTus): 40,185 33,929 27,673 40,185 49,661 41,258 33,396 49,661 57,301 47,917 38,534 57,301
uPS Module weight (lb/kg): — — 3050*/1383* — — 3050*/1383* — — — — 3050*/1383* —
Module width (75"H x 33"D): — — 48" — — 48" — — — — 48" —
180 kVA/162kW 200 kVA/180kW 225 kVA/202.5kW
input Voltage (V): 208 480 480 600 208 480 480 600 208 480 480 600
output Voltage (V): 208 208 480 600 208 208 480 600 208 208 480 600
nominal input current (a): 600 260 260 208 692 300 300 240 692 300 300 240
nominal output current (a): 501 501 217 174 556 556 241 217 625 625 271 217
Dc current at nominal Voltage (a): — — 392 — — 438 — — — — 442 —
efficiency at 100%: — — 93% — — 93.5% — — — 93.5% — —
Full load Heat rejection (bTus): 68,762 57,501 46,240 68,762 72,477 59,965 47,453 72,477 73,383 60,715 48,046 73,383
uPS Module weight (lb/kg): — — 3050*/1383* — — 3050*/1383* — — — — 3050*/1383* —
Module width (75"H x 33"D): — — 48" — — 48" — — — — 48" —
*UPS module only, including 50lb. pallet ~ does not include transformer and auxiliary cabinets.
Battery Cabinets 100kVA 130kVA 150kVA 180kVA 200kVA 225kVA
1 x 285w 7 – – – – –
1 x 370w 12 8 6 – – –
1 x 500w 16 10 7 – – –
2 x 285w 21 14 11 8 7 6
2 x 370w 30 22 19 14 12 12
3 x 285w 38 26 21 16 14 13
2 x 500w 45 31 26 19 17 16
3 x 370w 51 37 32 24 22 22
4 x 285w 54 38 32 26 21 21
3 x 500w 75 448 45 37 31 31
4 x 370w 82 54 46 36 33 32
4 x 500w 105 77 63 51 45 44
Standards
Standards: ISO 9001, UL 1778, cUL, NEMA PE 1, NEMA 250, NFPA 70, IEEE 587-1980/ANSI C62.41, OSHA
Standard Features:IGBT/PWM inverter, Low kVAR input filter, LED mimic diagram, Guided operator interface, Advanced battery management system, Modular power assemblies, Front access design, Computer aided self diagnostics, Dry contact relay status array, Top to bottom access models.
Galaxy PW
63
Th
ree Ph
ase UP
S
ePS 7000Three Phase UPS
> High output power factor (0.9 pƒ)
> Low kVAR input filter
> No leading power factor
> High energy efficiency
> Reduced footprint
> High power density
> Fault tolerant architectur
Standard Features
IGBT/PWM inverter, Low kVAR solid state input filter, K-20 output transformer, Redundant fans, Advanced battery management system, Detailed metering system, Fault current management circuitry, Two stage input current limit, Serial and dry contact interface, Local and remote E.P.O circuit, High capacity 100% rated static transfer switch
DC Rating
nominal Voltage: 480Vdc
Environmental Specifications
acoustical noise level: 75dBA at 5ft
operating Temperature: 0 to 40°C / 32 to 104°F
Storage Temperature: -20 to 45°C / -4 to 113°F
Humidity: 0 to 90% non-condensing
Dimensions uPS Module (in/mm):
69 x 82 x 39 / 1752.6 x 2082.8 x 990.6
weight (lb/kg): 6900 / 3129.8
Maintenance bypass cabinet (in/mm) (lb/kg):
22.75 x 82 x 39 / 557.9 x 2082.8 x 990.6 540 / 224.9
bottom entry cabinet (in/mm) (lb/kg):
14 x 82 x 39 / 355.6 x 2082.8 x 990.6 190 / 86.2
Transformer cabinet (in/mm) (lb/kg):
44.75 x 82 x 39 / 1136.7 x 2082.8 x 990.6 3600 / 1632.9
Options:inputisolationtransformer,outputdistribution,externalmaintenancebypass,bottomcable entry, remote alarm status panel, seismic anchors, battery monitoring, battery disconnect, SNMP/Network management card, critical bus synchronization module, graphical user interface with network connection, continuous duty and momentary duty static switch cabinets (SSC)
Input
Voltage: 480 or 600Vac, ±10%, 3 phase, 3 wire + ground
Frequency: 60Hz + 5%
Power Factor: 0.9 lagging with filter
THDi: 7% THDI at full load
reactive current (kVar): <15% of nominal input current
inrush current: up to 600% nominal current for less than one cycle
Power walk-in: 0 to 100% over a 10 second period
Bypass Input
Voltage:Must match rectifier input, ±10% UPS Output Voltage (3 phase, 3/4 wire + ground)
Frequency: 60Hz (±0.25Hz up to 2Hz)
Output
Voltage: 480 or 600Vac, ±3%, 3 Phase, 3 or 4 wire + ground
Power Factor: 0.9 at nominal kVA/up to unity at rated nominal kW
Frequency:60Hz + 0.1% free running synchronized with bypass (selectable in 0.25Hz increments)
Voltage regulation: ±0.5% steady state
Voltage recovery Time: ±1% of the steady state value within 1 cycle
Voltage Distortion: 2% L-L (4% L-N) THDI max
inverter overload: 125% for 10min, 150% for 1min
unbalanced load:Up to 100% 120° ±3% maximum angle displacement, ±3% maximum voltage deviation
ePS 7000
300kVA/270kW 400kVA/360kW 500kVA/450kW 300kVA/270kW 400kVA/360kW 500kVA/450kW
input/output Voltage: 480/480V 480/480V 480/480V 600/600V 600/600V 600/600V
nominal input current: 371A 508A 656A 322A 441A 569A
Maximum input current: 543A 688A 840A 466A 586A 711A
nominal bypass current: 361A 481A 601A 289A 385A 481A
uPS output current: 361A 481A 601A 289A 385A 481A
input cb Trip/Frame Size: 1000/1200A 1000/1200A 1000/1200A 1000/1200A 1000/1200A 1000/1200A
Maintenance bypass Trip / Frame Size (a):
800/1200A 800/1200A 800/1200A 700/1200A 700/1200A 700/1200A
Dc current (Max): 721 962 1195 721 962 1195
Dc breaker Trip/ Frame Size (a):
700/1200A 1000/1200A 1200/1200A 700/1200A 1000/1200A 1200/1200A
System efficiency: 94% 94% 93% 94% 94% 93%
Full load Heat rejection (bTus):
59400 78100 110750 65000 86000 112000
EPS 7000
65
Su
rge S
up
pressio
n
AlphaTVSS™
Transient Voltage Surge Suppression
> Safe operation – no explosions, no smoke, no fumes and no flames
> Isolates the load from damaging transients and other abnormal line conditions
> Lifetime of 20+ years
> NEMA 4X rated enclosure
> UL recognized surge suppression component (UL 1449 2nd edition Feb. 2007)
The Strikesorb™ surge suppression module incorporates state-of-the-art developments in metal oxide
technology to provide superior protection throughout its long service life. It has been designed to
withstand repeated surges, providing cost-effective and maintenance-free operation in harsh
environments. Strikesorb is the only UL (1449 – 2nd edition) recognized surge protection module rated for
safe operation without the use of additional internal fuses. This technology, combined with the capability
to be connected directly on the power lines (feed-through connection) make Strikesorb the most reliable
surge protection device available.
alphaTVSS
Models ATVSS-2-120 ATVSS-3-120/240 ATVSS-4-120/208 ATVSS-2-240 ATVSS-4-220/380
Electrical Characteristics
nominal operation Voltage: 120V 120V/240V 120V/208V 240V 220V/380V
Maximum continuous operating Voltage:
150V 150V 150V 300V 480V
Vref (Peak) @ 5ma ac (Peak): 263V 263V 263V 526V 833V
operating Frequency range: 25 to 500Hz 25 to 500Hz 25 to 500Hz 25 to 500Hz 25 to 500Hz
leakage current at Vn: 0.30mA 0.30mA 0.30mA 0.35mA 0.45mA
Surge Protection Levels
Surge Voltage rating: 500V 500V 500V 800V 1500V
response Time: <1ns <1ns <1ns <1ns <1ns
Maximum Surge current: 140kA 140kA 140kA 140kA 140kA
Maximum lightning current: 7.5kA 7.5kA 7.5kA 7.5kA 7.5kA
Let through Voltage
For Surge current 10ka (8/20): 435V 435V 435V 895V 1355V
Enclosure IP65-NEMA4 IP65-NEMA4 IP65-NEMA4 IP65-NEMA4 IP65-NEMA4
Dimensions (in/mm):6 x 8 x 6 / 152 x 203 x 152
10 x 12 x 6 / 254 x 305 x 152
10 x 12 x 6 / 254 x 305 x 152
6 x 8 x 6 / 152 x 203 x 152
10 x 12 x 6 / 254 x 305 x 152
operating Temperature: -40 to 85°C / -40 to 185°F
large Thermal capacity electrodes:Absorb heat generated during surges and decelerate MOV ageing
Strong aluminum Housing:Prevents explosions
1500+ Pounds of Pressure:Results in very low dynamic resistance
no Fuel to burn:Prevents fire and smoke emission
Single, Distribution-grade Varistor:Contributes to reliability, long lifetime, avoiding parallel connected MOVs
Coaxial symmetry and uniform surge current distributionStrikesorb Module
67
Alp
ha Tech
no
log
ies Services
> Turn-Key Installation Alpha’s complete power system integration and turn-key installation services include right-of-way and
easement procurement, site preparation, equipment installation, utility hookup coordination, system
turn-up and system testing.
• Alpha performs all site negotiations
• Alphacoordinatesutilitiesandconstructionpermittingprocess
• CorrectinstallationandmaintenanceofHeadend,DCPlantandOutsidePlantpowersolutions
• CustomersbenefitfromAlpha’sprofessionalprojectmanagementandqualitycontrol
> Turn-Up and Test Services Turn-up and test services for Headend, DC Plant and Outside Plant installations performed by Alpha
specialists represent a significant first step in ensuring long-term system reliability. Services include
verification of proper installation, completion of Alpha start-up procedures and system testing.
• Turn-up and test completed by Alpha technicians
• Certifiedinstallationinspections
• Coordinatedproductandserviceordering,trackingandbilling
• Extendedwarrantyavailability
• Allowscustomerstofocusonfiberandtransmissionequipment
> Field Service Calls Trained Alpha field service engineers are dispatched 24 hours per day, 7 days per week in
specially equipped and stocked Alpha service vehicles to perform routine system
maintenance or emergency repair service.
> Preventative Maintenance An on-going preventative maintenance program helps ensure optimum system reliability and equipment
life. Alpha’s service plan options include performing routine scheduled maintenance, testing of local and
remote alarm operation, and analyzing local data for special requirements. Local service logs are
updated and information is uploaded to Alpha’s central database.
• Develophistorical data file for each power system component
• Completepreventativemaintenancechecklists
• Performmechanicalmaintenance
• Checkaccuracyofmonitoringsystemreadoutsandalarmsetpoints
• Documentroutine service or callouts
> Alpha Depot Repair Services Alpha’s repair depots are located across the country to easily serve our customers. Alpha’s repair and
development laboratories are designed for product repair and refurbishment, product improvement,
research and modification, to assist with our customer’s specific needs.
• Warranty and non-warranty repair
• CompleterepairandrefurbishmentofallAlphaproductlines
• EasyonlineRMAprocess(withlinktoonlinepart)
• RepairofnonAlphaproductsfor:cable,headend,fiberoptics,linegear,powersupplies and test equipment
• Onsitecalibrationandrepairoftestequipment
• Alphacertifiedtechnicians
• Multiplelocations:Bellingham,Washington;Suwanee,Georgia;andGarland,Texas
Alpha Technologies Services
69
Fib
er Po
wer S
ystems
FTTx PowerAlpha Technologies offers a complete portfolio of fiber-to-the-home powering options with the
FlexPoint™ line of 12Vdc single-family solutions (SFU) and the FlexNet™ line of 48Vdc multiple dwelling
(MDU) and small office home office (SOHO) power supplies.
> FlexPoint 1230 Series The FlexPoint 1230, 30W, 12Vdc standby power supply is an environmentally hardened standby power
supply intended to be placed in indoor or outdoor sheltered locations providing the service provider
flexibility in locating the product. The FP1230 is compact allowing placement in the most densely
populated structured media enclosures. The FP1230 includes a unique emergency battery reserve
function that provides greater lifeline service availability by preserving 25% of the usable battery
capacity for user initiated emergency telephone calls.
> FlexPoint AX Series Alpha’s FlexPoint AX Series fiber-to-the-premises optical network terminal (ONT) power supply system,
provides network operators a highly reliable, scalable set of solutions for full or partial outdoor
installations. This system provides service technicians 24/7 access to the power system FlexPoint AX
home converters and power ring converters provide 12Vdc support for indoor and outdoor
applications not requiring standby power. As voice or critical data services are subscribed 7.2 or 17Ah
battery backup power supplies (BBPS) can be easily added.
> FlexNet FMPS The FTTx Multipurpose Power Supply (FMPS) is an outdoor or indoor system providing 150W of 48Vdc
power to MDU and SOHO optical network terminals. The FlexNet FMPS is an environmentally
hardened wall mount enclosure system with dual ONT connections supported with one or two 48Vdc
strings of 7.2Ah batteries. The system includes one or two parallel outputs and alarm connections,
supporting distances of up to 100ft between the FMPS and ONT, allowing the FMPS to be located
close to existing power outlets.
> FlexNet FiberUPS The FlexNet FiberUPS is a 300W, 48Vdc battery backup power module supporting a variety of indoor
and outdoor applications. Installed in pole, wall or ground mount rainproof enclosures along with
Alpha’s 85GXL 50Ah batteries, the FlexNet FiberUPS will keep field distributed electronics up and
running during power disturbances and outages.
> FlexNet PMR and GMR Series The FlexNet PMR and GMR series is comprised of two sizes of pole mount and two sizes of ground
mount factory configured and regulatory certified rainproof enclosure systems. PMR and GMR are
highlyconfigurablesystemsincluding19"adjustableorpulloutswingracks,ACserviceentranceand
distribution, surge suppression, fiber management, power bypass cabling, FiberUPS DC power
supply, DC distribution and 50Ah AlphaCell™ batteries.
> Radium MiniBay™ Series The Radium MiniBay is a highly configurable enclosure system supporting a wide range of applications
including bulk power, hub, secondary hub and remote terminal. Also ideal for remote optical transition
applications including optical amplification, downstream DWDM demultiplexing, narrowcast combining
and return path aggregation providing services to remote communities. The Radium MiniBay is
configured to order.
70
Fib
er P
ow
er S
yste
ms
FlexPoint™ 1230 SeriesIndoor 12Vdc 30W UPS
> Telecommunications grade power system provides 30W of 12Vdc primary and standby power for FTTx actives
> Easy customer replaceable hot swappable 7.2 or optional 12Ah battery
> Emergency battery reserve for greater E911 availability
> Battery management system engineered to provide optimum service life and runtime
> Coax F-Style packet cable interface options
FlexPoint 1230 Series
Models Description
FP-1230-01-a: 120Vac US Domestic 3-conductor power cord (NEMA 5-15)
FP-1230F-01-a: 120Vac US Domestic 3-conductor power cord (NEMA 5-15) F-connector output
Input OPS
ac input Voltage: 120Vac or 240Vac
ac input Frequency: 50/60Hz
Surge Protection:ANSI/IEEE Std. C62.41 to Category A, B, orCrequirements,usinga“RingWave”or“Combination”waveform,atalevelof6kV
Output
operational output Power:30W max continuous (ONT load + battery charge + heater*)
output Voltage: 12Vdc Nominal (Battery voltage upon loss of AC)
output Power loading:Following GR-909 telephone lines in various states, e.g., ringing, off-hook, on-hook, data, and video operation requirements
auxiliary input Voltage: 10.5 to 20Vdc
Physical
Housing Size (in/cm): 8.75 x 7.75 x 3 / 22.4 x 17.7 x 7.62
weight (lb/kg): 3 / 1.4
battery 7.2ah (lb/kg): 5.7 / 2.6
battery 12ah (lb/kg): 8.4 / 3.8
Battery
battery Type: Maintenance free, leak-proof, sealed VRLA (valve regulated lead acid)
Visual Indicators
System: Green LEDPower is available at the output (AC, battery or auxiliary)
battery: Green LEDBattery discharging to 25% SOC (main or auxiliary)
Green FlashAt 40% SOC (main battery) the indicator begins to flash
replace battery: Red LED Battery not present or failed self test
auxiliary Power Source: Green LED Valid auxiliary power source connected
Audible Status Indicators
loss of input Power: Single, one second chirp
low battery: Single chirp every 15 seconds at 40% SOC
replace battery: Double chirp spaced fifteen minutes apart
Push Buttons
Silence alarm: Suppresses the audible alarm for 24 hours
battery emergency use: Accesses reserve battery capacity
Standards
System:FCC part 15 Class B, CSA-NRTL\C (CSA60950), CE, C-Tic, RoHS to EU 2002/95/EC, Seismic Zone 4 rated per GR-63
Environmental
Storage Temperature: -40 to 55°C / -40 to 127°F
operating Temp w/out Heater: -20 to 55°C / -4 to 127°F
operating Temp w/ Heater: -30 to 55°C / -22 to 127°F
Note:OperatingtemperaturesbasedonAX-LONGBAT-7.
Humidity: 0 to 95%
operating elevation Max: 3000m / 10000ft Derate at 2°C per 1000ft above 6000ft
Storage elevation Max: 15000m / 50000ft
Interface
Dc output and alarm:Removable Screw Terminal Plug accepts seven (2) 16AWG and (7) 24AWG wires
auxiliary Dc input:3.5mm (OD), 1.3mm (Pin, positive) coaxial barrel connector
ac input: IEC320/C6 Receptacle
line cord:NEMA 1 to 15 to IEC 320 C5 (Other cords available upon request)
Warranty
FlexPoint 1230: 3 years repair or replace
batteries available: 1 year or 3 year
Supporting Options
aX-STDbaT-7 — Battery 7.2AH AGM, 1 year warrantyaX-longbaT-7 — Battery 7.2AH AGM, 3 year warrantyaX-STDbaT-12 — Battery 12AH AGM, 1 year warrantyFP1230-cVr — FlexPoint 1230 12AH battery cover with strapFP1230-HK — FlexPoint 1230 heater kitFTTH-cbl — ONT hook-up cable, 2x16AWG and 5x24AWG, CMX UL listedauX-cbl — Cable, auxiliary power plug 3m long
FlexPoint 1230 shown with cover removed, battery, auxiliary power cable
and ONT hook-up cable
FlexPoint 1230 withCoax F-Style Interface
FlexPoint 1230 connector interface and cable strain relief
FlexPoint 1230
71
Fib
er Po
wer S
ystems
FlexPoint™ aX SeriesOutdoor/Indoor 12Vdc 30W UPS
> Scalable FTTP/FTTx power supply systems with and without standby
> Full or partial outdoor configurations
> Outdoor rated including battery for 24/7 availability
> Utility meter base provides most reliable source of AC power at home
> No homeowner appointments needed for access
> Safe, low-voltage distribution
> 30W with battery module, 24W without battery module
FlexPoint aX Series
Input
ac input Voltage (aX30-12D-Hc): 85 to 132Vac (120Vac Nominal)
ac input Voltage (aX-30-12D-Pc): 170 to 264Vac (230Vac Nominal)
ac input Frequency: 50 to 60Hz
Note:International AC selections and line cords available.
Output
DC Output Voltage
Pc/Hc + bbPS (uPS System): 10.5 to 14.4Vdc
Pc/Hc (non uPS): 11.6Vdc
Continuous Output Power
Pc/Hc + bbPS (uPS System): 30W at nominal battery float voltage
Pc/Hc (non uPS): 24W
Max output Power (uPS System): (<10s) 45W
Max output Power (non uPS): 2.4A current limit (HC/PC)
Short circuit Protection: Electronic
Dc ripple: 150mV
Environmental
Operating Temperature Range
aX-30-12D-Pc + bbPS: -40 to 65°C / -40 to 149°F
aX-30-12D-Hc + bbPS:HC:-40to45°C/-40to113°F, BBPS:-40to65°C/-40to149°F
aX-30-12D-Hc: -40 to 45°C / -40 to 113°F
Humidity: 0 to 95%
battery Storage: -15 to 65°C / 5 to 149°F, 0 to 95% humidity
operating elevation Max: 3000m / 10000ft
Storage elevation Max: 15000m / 50000ft
FlexPoint UPS Runtimes (minutes) over Temperature
7.2Ah
load/Temp. -40°c/-40°F -20°c/-4°F 25°c/77°F
7w 360 560 800
10w 160 360 500
15w 110 195 320
18w 80 156 240
20w 60 130 210
25w 50 100 170
30w 30 80 130
Battery
Type:Maintenance-free, leak-proof, sealed VRLA (valve regulated lead acid)
recharge Time:AX-12D-BBPS-7.2:<16hrswith24W
AX-12D-BBPS-17 load <36hrs with 24W load
Regulatory Approvals
Home converter: UL-Listed System, FCC Part 15, Class B, EN55022, Class B
Power ring: UL-Recognized Components
Power ring converter: UL-Recognized Components
bbPS Modules: CSA
Warranty
electronics: 2 years
battery–Standard: 1 years
battery–long life: 3 years
Status Alarms
Local (LED Indicators)
green Steady Output OK
green blinking Standby Operation
red Steady Replace Battery
red blinking Battery Missing/Battery Low
Remote (Status Alarms – PacketCable Compliant)
ac Fail Output Power drawn from battery
replace battery Battery has failed periodic self-test
battery Missing Battery is disconnected
battery low Battery has 20% remaining runtime
FlexPoint UPS Runtimes (minutes) over Temperature
17Ah
load/Temp. -40°c/-40°F 20°c/-4°F 25°c/77°F
10w 750 1080 1240
15w 400 680 940
20w 60 440 680
25w 160 340 480
30w 140 232 400
FlexPoint PowerRing converter with 7.2Ah Battery Enclosure
72
Fib
er P
ow
er S
yste
ms
FlexPoint™ aX SeriesOutdoor/Indoor 12Vdc 30W UPS
Module Descriptions
Power-Ring
Compatible with ring and ringless style meter sockets it provides a receiving socket for the FlexPoint AC to DC Power-Ring Converter module. Depending on the model the Power-Ring can tap the AC power before or after the meter and comes supplied with a blanking plate.
Models: 200A Continuous, 240A RatedAX-POWER-RING-A (power tap after meter) —P/N 021-053-21AX-POWER-RING-B (power tap before meter) — P/N 021-053-20
320A Continuous, 400A RatedAX-400ARING-A (power tap after meter) — P/N 021-053-30 AX-400ARING-B (power tap before meter) — P/N 021-053-31
Dimensions (in/mm): 4.75H x 7Dia / 120H x 178Dia
weight (lb/kg): 1.5 / 0.68
Power-Ring Converter
Contains highly-reliable environmentally-hardened 240Vac to 12Vdc converter circuitry in a pluggable housing. Outputs 24W and 11.6Vdc as a stand-alone module, or supports 30W and 11.6 to 16Vdc battery backup power supply (BBPS) module output
Model: AX30-12D-PC — P/N 010-318-31
Dimensions (in/mm): 8 x 2 x 2 / 209 x 51 x 51
weight (lb/kg): 0.7 / 0.32
Home Converter
Contains highly-reliable environmentally-hardened 120Vac to 12Vdc converter circuitry in a wall mount housing. Comes with a two-conductor AC line cord and should be mounted in locations sheltered from rain or snow. Outputs 24W and 11.6Vdc as a stand-alone module or supports 30W and 11.6 to 16Vdc battery backup power supply (BBPS) module output.
Model: AX30-12D-HC — P/N 010-318-37
Dimensions (in/mm): 8.25 x 2.75 x 1.5 / 209 x 70 x 38
weight (lb/kg): 0.7 / 0.32
The UPS Modules
Provides the Network Operator the capability to place the battery management element inside other enclosures located at the subscriber’s home. UPS modules contain the same electronics used in the AX-12D-BBPS products without the battery heater and are to be used with FlexPoint Home Converter and Power-Ring Converter.
Models: AX-12D-7.2Ah (for 7.2Ah battery) — P/N 745-816-21
AX-12D-17Ah (for 17Ah battery) — P/N 745-816-20
Module Descriptions
Battery Modules
The Battery Backup Power Supply (BBPS) module outputs 30W of continuous power and includes a microprocessor-based battery charge management system providing the correct charge voltage to the battery over a wide temperature range, while performing periodic battery capacity testing and status reporting to the ONT and customer. The onboard battery heater provides extended standby runtimes in cold conditions to -40°C. The 7.2Ah battery model provides standard runtimes and the 17Ah model provides extended runtimes.
Models: AX-12D-BBPS-7.2 — P/N 031-264-20
Dimensions (in/mm): 8 x 9 x 4 / 203 x 230 x 102
weight (lb/kg): 1.5 / .68
AX-12D-BBPS-17 — P/N 031-192-30
Dimensions (in/mm): 14 x 9.5 x 5 / 355 x 241 x 127
weight (lb/kg): 4.5 / 2.04
Batteries
The FlexPoint AX battery modules use maintenance-free sealed-lead acid.
Models: AX-STDBAT-7 — P/N 181-036-10Standard-Life 7.2AH AGM Battery, 1-year Warranty
AX-LONGBAT-7 — P/N 181-063-10Long-Life 7.2AH AGM Battery, 3-year Warranty
weight (lb/kg): 5 / 2.27
AX-STDBAT-17 — P/N 181-022-10Standard Life 17AH AGM Battery, 1-year Warranty
weight (lb/kg): 13 / 5.9
73
Fib
er Po
wer S
ystems
FlexPoint™ aX SeriesOutdoor/Indoor 12Vdc 30W UPS
Applications
Indoor Powering – Non-UPS
OperationalTemperatureRange:-40to45°C/-40to113°F
11.6Vdc Nominal
Indoor Powering – UPS
OperationalTemperatureIndoorRange:-40to45°C/-40to113°FOperationalTemperatureOutdoorRange:-40to65°C/-40to149°F
Outdoor Powering – Non-UPS
OperationalTemperatureRange:-40to65°C/-40to149°F
Outdoor Powering – UPS
OperationalTemperatureRange:-40to65°C/-40to149°F
74
Fib
er P
ow
er S
yste
ms
Flexnet™ FMPSOutdoor 48Vdc 150W UPS
> Fiber-to-the-Premise UPS for Multiple Dwelling, Multiple Tenant and Small Business Unit applications
> Supports one or two MDU/SBU ONTs located up to 100ft from FMPS
> Battery management performs periodic battery capacity testing and status reporting to the ONT and customer
> Battery heater option provides extended runtime for applications in cold weather conditions
> Hybrid 16AWG and alarm cable minimizes installation labor
> Status indicators and audible alarm provide local status
Flexnet FMPS
Input
ac input Voltage: 90 to 320Vac
ac input Frequency: 45 to 66Hz
Surge Protection: ANSI/IEEE Std. C62.41 to Category A, B, or C requirements,usinga“RingWave”or“Combination”waveform, at a level of 6kV
Output
operational output Power: 150W continuous to 170W, 10sec max
output Voltage: 48 to 58Vdc w/AC power, 42 to 58Vdc with battery
output current: 3.1A typical (crowbar limited beyond 5A DC)
output Power loading:Following GR-909 telephone lines in various states, e.g., ringing, off-hook, on-hook, data, and video operation requirements.
ripple: Less than 3mVrms
noise: Less than 100mVp-p
output connection:Two terminal blocks accepting 16AWG, parallel connections
Local Alarms
System leD: Green Steady = System Output Normal, DC OutputOff = No AC or Battery Power
battery leD: Yellow Steady = System on BatteryOff = Normal Mode
replace battery:Red Steady = Replace One or Two Battery StringsOff = Batteries Within Parameters
replace battery a and b (internal):
Steady Red = Replace One or Both Battery StringsOff = Batteries Within Parameters
Remote Alarms
connection: Two five position IDC 24AWG, parallel connections
Pin 1 alarm return: Open collector return reference
Pin 2 ac Fail: On battery
Pin 3 replace battery: One or both battery strings failed periodic self test
Pin 4 Missing battery: Less than eight batteries
Pin 5 battery low: Battery string voltage is less than 46.8Vdc
Local - Audible Indicator
alarm on:“AlarmEnable/Disable”toggleswitchlocatedonUPS Batteries Below Voltage Parameters
Mechanical
FMPS
Dimensions(in/mm): 14 x 23.75 x 5.5 / 355.6 x 603.3 x 139.7
Weight(lb/kg): 25 / 11.3
FMPS + Shipping Carton
Dimensions(in/mm): 17 x 28.5 x 11.75 / 431.8 x 723.9 x 298.5
Weight(lb/kg): 30 / 13.6
Battery
BatteryType:Four or eight 7.2Ah Valve Regulated Lead Acid (VRLA) (Batteries sold separately)
Environmental
operating (with heater option): -40 to 46°C / -40 to 115°F plus solar loading, 0 to 95%
(without heater option):-10 to 46°C / 14 to 115°F plus solar loading, 0 to 95% humidity, 0 to 3000m / 0 to 10000ft elevation
Storage:-15 to 85°C / -5 to 185°F, 0 to 95% humidity, 0 to 15000m / 0 to 50000ft elevation
Standards
CSA/UL 60950, EN 60950, EN 55022 Class B, FCC Part 15 Class B, GR 63 Sect 4.2 Fire Resistance, GR-1089 Sect 3 Emissions, Sect 4 Lightning and AC Power Fault, Sect 7 Electrical Safety
Warranty
3 year repair or replace
FMPS with cover removed and two 7.2Ah battery strings installed
FlexNet FMPS
75
Fib
er Po
wer S
ystems
Flexnet™ FiberuPSOutdoor/Indoor 48Vdc 300W UPS
> Power modules can be used in a variety of Alpha enclosures
> Rugged 48Vdc UPS for outdoor or indoor applications
> Temperature compensated battery charging for extended battery life
> Visual and electrical indicators for on-site and remote reporting
> Flexible cabinet mounting
Flexnet FiberuPS
Model ELPM 300 – 48D
Input
Voltage range: 85 to 170 or 132 to 264Vac (selectable)
Frequency: 50 or 60Hz
Output
Voltage: 48Vdc (42 to 54Vdc)
output Power Max: 300W
Transfer characteristics: Uninterrupted output
Dc ripple: 500mV
Battery
String Voltage: 48Vdc
Typical capacity: Four 50Ah (85GXL)
Type: Sealed lead acid GEL, maintenance free
battery charging: Temperature compensated
backup Time approx.: 8hrs @ 275W load
Mechanical
Dimensions (in/mm): 6 x 10.1 x 3.25 / 152 x 256.5 x 82.6
weight (lb/kg): 10 / 4.5
Mounting configuration: Bracket mounted inside enclosure
Environmental
operating Temperature: -40 to 65°C / -40 to 149°F
Storage Temperature: -50 to 70°C / -58 to 158°F
Humidity: 0 to 95% non-condensing
LED Indicators
green: Output
green blinking: Standby
red blinking: Low/missing battery
red: Replace battery
Alarm Indicators
AC FAIL (TELM 1)Replace Battery (TELM 2)Battery Missing (TELM 3)Battery Low (TELM 4)
Note: Compliant with PacketCable™ UPS Specifications. Embedded MTA Primary Line Support Specification (PKT-SP-EMTA-Primary-101-001128)
Standards
FCC part 15 Class B CSA–NRTL\C (CSA950)
Standard Features
No audible noise Reverse battery polarity protection
Warranty
3 years repair or replace
FlexNet FiberUPS
FlexNet FiberUPS withMounting Hardware
76
Fib
er P
ow
er E
ncl
osu
res
PMR
GMR
PMr and gMr SeriesPole and Ground Mount Enclosures
> Supports field deployment of FTTx Optical Line Terminals (OLT)
> FlexNet™ 300W UPS provides over 10hrs of runtime
> Thermostatically controlled 48 or 120Vdc fan and heater options
>Adjustable19"EIAequipmentracks
> All aluminum construction, durable powdercoat finish, stainless steel hardware
PMr and gMr Series
Enclosure Weight and Dimensions
Models: PMr-S1 gMr-S1 PMr-S2 gMr-S2
Mounting: Pole Ground Pole Ground
Dimensions (in/mm):
26 x 32.2 x 19.2 / 660 x 818 x 489
27.5 x 31 x 20 / 699 x 787 x 508
30 x 37 x 19.25 / 762 x 940 x 489
31 x 38 x 20 / 787 x 965 x 508
weight (lb/kg): 40 / 18 49 / 22 47 / 21 63 / 29
Material: Powdercoated aluminum
Vent Screen (in/mm):
Stainless steel fabric with .005 x .005 / .12 x .12 opening size to minimize snow, water and dust ingress
Door and lid Seal:
Poron gasketing
Hardware: Stainless steel
color: Gray (Custom colors available)
Tamper Switch: Optional
Grounding
internal ground bar: Five usable lugs
Safety ground:AdjacenttoACoutlets (Optional stainless steel ground stud)
lid: Removable (PMR Series includes lanyard)
Door(s)
PMr Series: Hinged removable with stainless steel spring latch and door open prop rod
gMr Series: Removable lift-off front and rear door
Enclosure Mounting
PMr Series:Galvanized steel brackets for wood, and concrete Pole-mount and wall mount
gMr Series:Precast polymer concrete pad or PS-6/PS-6XL pedestal systems
Thermal Management
cooling: 120Vac and 48Vdc fan options
Heating: 120Vac and 48Vdc heater options
Internal Mounting Rails
rackmounting: EIA 19" mounting rails using Tinnerman mounting clips
grounding: Rails grounded to chassis
adjustment: 1" increments over 6" when batteries are not installed.
Enclosure Environmental Rating
equipment Mounting area:
Designed to IP X5 per IEC 529 Dust Ingress controlled by screen opening IP X5 applies to the equipment mounting area The service entrance is rated 3R
Fiber Management Options
Fiber Strain relief Tie bar (optional):
19" mounting provides ability to strain relief fiber cable plugged into the front of communications equipment
Splice Tray (optional):
Splice Tray Kit (12 count), includes Splice tray with Elastomer Splice Block, Felt Tape, Tie Wraps, Cover and Recording Label
Fiber Management Panel (optional):
Provides fiber slack storage and secures a splice tray using a Velcro strap. Tie wrap slots on sides permit securing fiber cables to panel
Power Supply and Batteries
Model:
FlexNet300-48/48Vdc UPS Power Supply Module - including 60" output power cable, remote temp sensor, wall mounting brackets and alarm output connector
batteries:48Vdc string of 85 GXL (50Ah) positioned on ends (negative terminal side down) with battery retaining bar option
battery cable Kit: Fused
battery Heater: Optional
ac Service:External 70A rainproof SUSE rated breaker box with internal 120Vac 20A receptacles
regulatory: CSA-NRTL/C (CSA 60950)Notes: 1. Additional rack space capacity if batteries are not installed2. Runtime of 10hrs based on 212W load and new batteries discharged to 1.75VPC at 25°C/77°F
Shown with FTTX actives installed
77
Fib
er Po
wer E
nclo
sures
radium Minibay™
Environmentally Controlled Enclosures
> Highly configurable, scalable, environmentally controlled enclosure system
> Factory integrated power with agency certification
> Ideal for remote optical transition applications
> High reliability 24 or 48Vdc high efficiency air conditioner
> Natural gas or propane DC generator system for indefinite operation in emergency conditions
> Powdercoated aluminum construction for long life
> Installation and service programs available
The Radium MiniBay is a modular, highly configurable Telecom
grade enclosure system including fully scalable power to 4,000W
and 1240Ah of battery capacity with ample rack space for
communications electronics. The MiniBay system benefits from
more than 30 years of Alpha’s Outside Plant (OSP) powering
experience. The MiniBay integrates Alpha’s comprehensive line of
power solutions for today’s complex Hub and environmentally
controlled enclosure requirements including Alpha’s AC UPS,
Cordex™ rectifiers, and the AlphaGen™ series of telephony grade
DC generators. Features for the Radium MiniBay include: front and
rear accessible 19" or 23" equipment racks providing up to 46
rackmount spaces, durable powdercoated aluminum construction,
battery storage modules isolated from the equipment section each
supporting up to four 155Ah batteries for a 19A load for 8hrs.
Typical CSA-NRTL marked configurations include integrated AC
service entrance, surge protection, AC distribution, DC distribution,
standby generator interface, heat exchanger, fan/filter or air
conditioner thermal management, rectifiers or AC UPS equipment.
Standards
environmental rating:
NEMA 3R when configured with door mounted fans and filter system. Designed to meet IP55 when configured with heat exchanger or air conditioning system.
Seismic rating:Consult factory. A seismic rating is based on a set system configuration with defined mounting locations and equipment types.
Design Standards:Following NEC and Telcordia Technologies (Bellcore) GR-487, GR-63 and GR-108 guidelines.
compliance:Third party approval from National Recognized Testing Laboratory (NRTL).
Material: High strength corrosion resistant aluminum
Finish: Almond color powdercoat finish
Weight and Dimensions
weight (lb/kg): Dimensions (in/cm):
equipment enclosure: 195 / 88.5 32 x 44 x 30 / 81.3 x 106.7 x 76.2
battery Storage Module: 130 / 59 32 x 14 x 30 / 81.3 x 35.6 x 76.2
riser Module: 102 / 46.3 32 x 14 x 30 / 81.3 x 35.6 x 76.2
Side chamber Sc1: 100 / 45.4 12 x 72 x 32 / 30.5 x 81.3 x 131.1
Side chamber Sc2: 89 / 40.4 12 x 72 x 32 / 30.5 x 81.3 x 131.1
Fans and Filters
The most basic thermal management system supporting the MiniBay utilizes conformal-coated, variable speed and alarm monitored 48Vdc fans with electrostatic air filters. This configuration has a NEMA 3R rating.•48Vdcfansprovideupto1000Wthermaldissipationwitha15°C/59°Frise over ambient with 32W maximum power draw•VariablespeedcontrolledDCfanscontinuetooperateduringautilityoutage•Conformal-coatedfans•Electrostaticandwashableairfilters•Fieldreplaceablefans•FormCdrycontactalarmreportfanfail,openonalarm•ACsystemsavailable•ACthermalmanagementoptionsavailable
Heat Exchanger
An airtight rear door and a heat exchanger equipped hinged front door. This configuration is designed to meet the IP55 standard and has a NEMA 3R rating.•Coolingcapacityof690Wdissipatedwith15°C/59°Friseoverambientwitha maximum power draw 120W.•Variablespeedfantemperaturecontrolandlowvoltagedisconnect.Fans turn off below 23°C Fans turn on at 25°C and run from 25% to 100% with increased enclosure temperature from 25 to 45°C / 77 to 113°F.•FormCdrycontactalarms(Minor:Fanfail,openonalarmandMajor: Enclosure over-temp fixed at 60°C/140°F, open on alarm). •Variablespeed48Vdcfanscontinuetooperateduringautilityoutage•Fieldreplaceablefans•ACheatexchangesavailable
DC Air Conditioner
The MiniBay is supported by 48Vdc or 24Vdc variable speed highly efficient variable speed air conditioner systems for applications requiring reliable below ambient cooling and dehumidifying support with seamless performance through extended utility outages.•Coolingcapacityof878Wdissipatedat43°C/109°Foutdoorambientand maximum internal ambient temperature of 40°C/104°F.•Variablespeedbrushlessmotorcompressortemperaturecontrolandlow voltage disconnect•Adjustableenclosuretemperaturesetpoints•FormCdrycontactalarms(Minor:Highcondensingtempand/orenclosure over-temp,openonalarmandMajor:coolingsystemfailed,openonalarm).•Maximumpowerdraw500W.
MiniBay with Fiber Management
Rack space for customer supplied equipment
RSM 48/10 Rectifiers with distribution
Battery drawer
48Vdc air conditioner
Radium MiniBay
79
DC
Po
wer E
nclo
sures
Alpha EnclosuresTempest brings convenience, strength and versatility to outdoor power system enclosures. The fully
integrated modular design combines AC, DC and backup battery power into one space. All are
designed to serve ASDL, TI and fiber optic transmission system (FOTS) facility applications.
> Tempest Te25 SeriesThe Te25 is designed to meet the requirements for service providers with remote outdoor or
secure indoor applications. Welded aluminum construction provides structural integrity that
will withstand seismic events and harsh weather conditions.
> Tempest Te15The Tempest Te15’s compact footprint is an ideal, economical solution for microwave, fiber and E911
applications. The optional integrated solar shield, heater, and air conditioner protect the batteries and
equipment from severe environmental conditions. Fully secure pad-lockable doors and intrusion
alarms keep equipment safe and secure.
> Tempest Te17Tempest brings convenience and versatility to outdoor power system enclosures. In addition to ADSL,
TI and fiber optic transmission system (FOTS) facility applications, the Te17 is designed to meet the
requirements of WiMax service providers.
> Tempest Te20 SeriesMore battery power in a compact cabinet. The Tempest Te20 Series is an innovative environmentally
controlled outdoor enclosure system that provides maximum backup power. Service providers will
save money and valuable lease space with this cabinet’s ability to house up to 20 batteries in a single,
secure cabinet solution.
> Tempest Te21The Tempest Te21’s compact footprint is an ideal, economical solution for microwave, fiber and E911
applications. Lower compartment air conditioning protects the batteries and customer equipment from
severe environmental conditions. Upper compartment fan cooling provides adequate cooling for
65˚C/149˚F temperature hardened power systems.
80
DC
Po
wer
En
clo
sure
s
Tempest Te25 / Te25xhOutdoor System Enclosure
> Designed for outdoor or secure indoor applications
> Easily transportable
> Durable aluminum construction
> Pedestal, wall, pole or rackmount
> Compact footprint
Tempest Te25 / Te25xh
Electrical
Contact Alpha for AC load center options for specific equipment requirements
Mechanical
Te25 cabinet Dimensions (in/mm):
20.3 x 21.4 x 20.4 / 516 x 544 x 518
Te25 weight (lb/kg): 65 / 29 approx without customer equipment
Te25xh cabinet Dimensions (in/mm):
36 x 21.4 x 20.4 / 914 x 544 x 518
Te25xh weight (lb/kg): 90/41 approx. without customer equipment
options:
Wall mount Pole mount Pedestal mount Rackmount AC distribution Meter base Generator connector and transfer switch GMT fuse block Surge arrestor
Dc connections: Multiple connection
chassis ground: Multiple connection Buss bar located in cabinet
Security: Lockable front door
Alarm
connection: Terminal block
Description: Intrusion
Tempest Te25xh
Standards
cSa:C22.2 No 60950-01-03Std. No 60950-01 NEMA Type 3R (CSA C22.2 No 94-M91)
Seismic: Designed to meet Zone 4 requirements
Related Components
Heating and cooling: Optional DC fan cooling option (standard design is vented with filters)
Tempest Te25 (with batteries)
Tempest Te25xh (open)
Tempest Te25
81
DC
Po
wer E
nclo
sures
Tempest Te15Modular Enclosure
> Modular design for single or multiple
> Cabinet configurations
> Welded aluminum construction
> 39RU of rack space
> Heating and cooling options
> Compact footprint
Tempest Te15
Electrical
input Voltage:120/240Vac 200A single phase 120Vac 100A single phase
number of breakers: 18 maximum
Transfer Switch/generator connector:
Optional
TVSS: Optional
Mechanical
Top Compartment
Dimensions (in/mm): 8 x 32 x 32 / 203 x 813 x 813
Main Compartment
Dimensions (in/mm): 69 x 32 x 32 / 1753 x 813 x 813
Bottom Compartment
Dimensions (in/mm): 8 x 32 x 32 / 203 x 813 x 813
Solar Shield
Dimensions (in/mm): 2 x 32 x 32 / 76 x 813 x 813
Dc connections: Multiple connection
chassis ground: Multiple connection Buss bar located in cabinet
Security: Lockable front door
rack Space: 23" rails, 39RU
Alarm
connection: Terminal block
Description: High/Low Temperature Intrusion
Standards
cSa:C22.2 No 60950-01-03Std. No 60950-01 NEMA Type 3R (CSA C22.2 No 94-M91)
Seismic: Designed to meet Zone 4 requirements
Related Components
Heating and cooling: 600W
air conditioning: Up to 8000BTU
Fan cooling: Optional
Heat exchanger: Optional
Tempest Te15 (open)
Tempest Te15 Side mounted
AC distribution
82
DC
Po
wer
En
clo
sure
s
Tempest Te17Outdoor Enclosure
> Designed for outdoor network applications
> Easily transportable
> Durable welded aluminum construction
> Variety of configurations possible with 23RU of space
> Compact footprint
Tempest Te17
Electrical
Consult factory on AC load center options for specific equipment requirements
Mechanical
Main Compartment
Dimensions (in/mm): 43 x 30 x 28 / 1092 x 762 x 711
Bottom Compartment
Dimensions (in/mm): 14 x 30 x 28 / 356 x 762 x 711
Enclosure Assembly
Dimensions (in/mm): 58 x 30 x 28 / 1473 x 762 x 711
Solar Shield
Dimensions (in/mm): 1 x 30 x 28 / 25 x 762 x 711
rack units: 23" rack 23RU
weight (lb/kg): 450 / 204 (approx without customer equipment)
Dc connections: Multiple connection
chassis ground: Multiple connection Buss bar located in cabinet
Security: Lockable front door
Alarm
connection: Terminal block
Description: High/low temperature intrusion
Standards
cSa:C22.2 No 60950-01-03Std. No 60950-01 NEMA Type 3R (CSA C22.2 No 94-M91)
Seismic: Designed to meet Zone 4 requirements
Related Components
Heating and cooling:Contact factory on HVac options for specific environmental conditions
Tempest Te17 (shown configured to customer specification)
Tempest Te17 (shown with 5000BTU air conditioner,
bottom compartment, and solar shield)
83
DC
Po
wer E
nclo
sures
Tempest Te20Power Enclosure
> Available in 24 and 48Vdc, 1200A
> Designed for outdoor applications
> Air conditioned battery and customer equipment compartment
> Fan cooled DC power equipment compartment
> NEMA 3R rating
> Compatible with base mounting and cable interface
Tempest Te20Tempest Te20
Electrical
input Voltage:120/240Vac, connected direct to site AC distribution panel, option to mount external AC panel
Mechanical
Dimensions (in/mm):: 84 x 30 x 30 / 2137 x 762 x 762
weight (lb/kg): 828 / 379 (no batteries)
chassis ground: Multiple connection Buss bar located in cabinet
Security: Lockable front door
Dc Distribution:1 x 1200A 20 position bullet breaker, 4 x 600A load shedding capability
batteries: 3 shelves 4 battery/shelf
customer equipment: 7RU available
Alarm
connection: Terminal block
Description: High/low temperature intrusion
Cabinet Backup Capacity
number of batteries: 12
battery amp Hour: 150Ah each
runtime (@ 25 to 175°c / 77 to 347°F VPc 24V)
20 min: 1246A
2 hrs: 332A
4 hrs: 185A
Standards
Safety:C22.2 No 60950-01-03Std. No 60950-01 NEMA Type 3R (CSA C22.2 No 94-M91)
Seismic: Designed to meet Zone 4 requirements
Related Components
Heater: 600W (optional)
air conditioning: Up to 58000BTU
Fan cooling: Power component
Tempest Te20
84
DC
Po
wer
En
clo
sure
s
Tempest Te20bBattery Enclosure
> 10 strings @ 24Vdc, 5 strings @ 48Vdc
> 1200A Bus
> Designed for outdoor network applications
> Optimum backup power source
> Environmentally controlled
> Compact footprint
Tempest Te20b
Electrical
input Voltage: 120 or 240Vac single phase (air conditioner)
output Voltage: Battery cabinet, 24 or 48Vdc
recommended Feeder breaker: 15A time delay breaker
Mechanical
Cabinet
Dimensions (in/mm): 84 x 30 x 30 / 2137 x 762 x 762
weight (lb/kg): 700 / 318
Enclosure: Aluminium shell, Steel internal battery shelving
Battery Shelf Dimensions
Dimensions (in/mm):: 11.8 x 21.6 x 21.5 / 300 x 549 x 546
Dc connections: Multiple connection
chassis ground: Multiple connection Buss bar located in cabinet
Security: Lockable front door
Environmental
outdoor Temperature: -40 to 46˚C / -40 to 115˚F
Alarm
connection: Terminal block
Description:High/Low Temperature Intrusion
Standards
cSa:C22.2 No 60950-00Std. No 60950-2000NEMA 3R (UL50)
Seismic: Designed to meet Zone 4 requirements
Related Components
Heater: 600W
air conditioning: Up to 50000BTU
Tempest Te20b
Tempest Te20b (open)
85
DC
Po
wer E
nclo
sures
Tempest Te21Modular Enclosure
> Modular design for single or multiple cabinet configurations
> Welded aluminum construction
> Dual compartment system
> Compact footprint
> Up to 39.6kW @ 48V
> Multiple point cable access
Tempest Te21
Electrical
input Voltage:120/240Vac, connected direct to site AC distribution panel
Mechanical
Dimensions (in/mm): 84 x 30 x 30 / 2137 x 762 x 762
weight (lb/kg): 863 / 392 (no batteries)
chassis ground: Multiple connection Buss bar located in cabinet
Security: Lockable front door
Dc Distribution:2 x 1200A 20 position bullet breaker 4 x 600A load shedding capability
batteries: 2 shelves 4 battery/shelf
customer equipment: 8RU available
Alarm
connection: Terminal block
Description: High/low temperature intrusion
Standards
cSa:C22.2 No 60950-01-03Std. No 60950-01 NEMA Type 3R (CSA C22.2 No 94-M91)
Seismic: Designed to meet Zone 4 requirements
Related Components
Heater: 600W
air conditioning: Up to 58000BTU
Fan cooling: Optional
Tempest Te21
Tempest Te21 (open)
87
Racks and Rack Accessories> SX Rack
The SX Rack is the next generation rack enclosure solution influenced by 10 years of customer
feedback, addressing current IT market trends for high-density server and networking applications.
With a strong focus on cooling, power distribution, cable management and environmental monitoring,
the SX Rack provides a reliable rackmounting environment for mission-critical equipment.
> 4 Post Open Frame Rack4 Post Open Frame Racks provide simple, low cost mounting for rackmount equipment in IT
environments. Ideal for rackmount servers, networking and telecom equipment where security at the
individual rack level is not required, open frame racks provide unobstructed airflow and fast, easy
access to installed equipment.
> Rack AccessoriesRack accessories include cable management, thermal management, shelving, keyboards, keyboard
drawers and stabilization accessories required for a complete enclosure solution.
> Rack HardwareMounting hardware includes light and heavy-duty shelves, bolt-down brackets, stabilization plates,
grounding kits, keyboard drawers, mounting rails, brackets and associated hardware.
Racks an
d R
ack Accesso
ries
88
SX 42ru rack19" and 23" Rack Enclosure
AR3150AR3100
> Tool free installation and removal of roof
>Rapidadjustmentoflevelingfeet
> Tool free PDU mounting provisions
> Numbered RU positions
> Light-weight, half-height side panels
> Tool free cable management options
> 42RU models roll through 2 meter doorways
> Cable openings for overhead or underfloor applications
SX 42ru rack
AR3100
weight (lb/kg): 275.2 / 125.09
Dimensions (in/mm):42.13 x 23.62 x 78.4 / 1070 x 600 x 1991
weight capacity - Static load (lb/kg): 3000 / 1363.6
weight capacity - Dynamic load (lb/kg): 2250 / 1022.7
SX 42ru rack
AR3150
weight (lb/kg): 343.10 / 155.95
Dimensions (in/mm):42.13 x 29.53 x 78.4 / 107 x 75 x 1991
weight capacity - Static load (lb/kg): 3000 / 1363.6
weight capacity - Dynamic load (lb/kg): 2250 / 1022.7
Rac
ks
Features
compatibility: Door ventilation exceeds 919 in2 (5933 cm2);CaptiveadjustmentofVerticalMountingRails;Fits-Like-A-Gloveguaranteedcompatibility
Safety: Integrated grounding; UBC Zone 4 stabilization provisions
Protection:Lockable doors and side panels; Door access monitoring; Static weight load rating of 3000lb; Serviceability; Quick release doors; Quick release side panels; Split rear doors
adaptability:Reversible doors; Scalable cooling options; Seamless integration of environmental monitoring devices; External baying for easy deployment in rows
89
SX 48ru rack19" and 23" Rack Enclosure
> Tool free installation and removal of roof
>Rapidadjustmentoflevelingfeet
> Tool free PDU mounting provisions
> Numbered RU positions
> Light-weight, half-height side panels
> Tool free cable management options
> 48RU models roll through 2 meter doorways
> Cable openings for overhead or underfloor applications
Enclosures providing cooling, power distribution, cable management and environmental monitoring for applications in IT environments.NetShelter®
SX is the next generation rack enclosure solution influenced by 10 years of customer feedback addressing current IT market trends for high-density
server and networking applications. The NetShelter SX provides a reliable rackmounting environment for mission-critical equipment.
SX 48ru rack
AR3107
weight (lb/kg): 304.1 / 138.23
Dimensions (in/mm):42.13 x 23.62 x 88.9 / 1070 x 600 x 2258
weight capacity - Static load (lb/kg): 3000 / 1363.6
weight capacity - Dynamic load (lb/kg): 2250 / 1022.7
SX 48ru rack
AR3157
net weight (lb/kg): 372 / 169.09
Dimensions (in/mm):42.13 x 29.53 x 88.9 / 1070 x 750 x 2258
weight capacity - Static load (lb/kg): 3000 / 1363.6
weight capacity - Dynamic load (lb/kg): 2250 / 1022.7
AR3157AR3107
Racks
90
Rac
ks
4 Post open Frame racksRack Enclosure
> Numbered RU positions
> Optimized width
> Reversible stabilization plates
> Advanced power distribution and cable management features
> For server, networking and telecom applications in secure IT environments
> Unobstructed airflow and fast, easy access to installed equipment
4 Post open Frame racks
AR3100
weight (lb/kg): 275.2 / 125.09
Dimensions (in/mm):42.13 x 23.62 x 78.4 / 1070 x 600 x 1991
weight capacity - Static load (lb/kg): 3000 / 1363.6
weight capacity - Dynamic load (lb/kg): 2250 / 1022.7
NetShelter Enclosure and Rack Accessory SKUs
Description Color
Rack Enclosures Open Frame Racks
ar3100 ar3150 ar3107 ar3157 ar2105blKar100 and ar100HD
ar200 and ar201
ar203 and ar204
ar7503: NetShelter® SX 42RU 19" Wide Recessed Rail Kit Black •
ar7504: NetShelter SX 48RU 19" Wide Recessed Rail Kit Black •
ar7505: Cable Tree for NetShelter SX Black • • • •
ar7508: NetShelter SX 42RU 23" Wide Recessed Rail Kit Black •
ar7578: NetShelter SX 48RU 23" Wide Recessed Rail Kit Black •
ar7707: NetShelter SX Wide Cable Ring Set Black • •
ar8006a: Equipment Support Rails 600mm wide White-Zinc • • •
ar8013a: NetShelter SX HP Adapter Kit – L Class/RP54xx Series Black • •
ar8113a: Cable Management Rings Black • • • • • • • •
ar8122blK: Fixed Shelf 250lb/114kg Black Black • • • • • AR203 only
ar8123blK: Sliding Shelf 100lb/45kg Black Black • • • • • •
ar8136blK: 1RU Plastic Blanking Panel Kit 19" Black (Qty – 10) Black • • • • • AR203 only
ar8136blK200: 1RU Plastic Blanking Panel Kit 19" Black (Qty – 200) Black • • • • • AR203 only
ar8425a: 1RU Horizontal Cable Organizer Black • • • • • • • •
ar8426a: 2RU Horizontal Cable Organizer Black • • • • • • • •
ar8442: Vertical Cable Organizer for NetShelter 0RU Channel Black • • • • •
Rack Cooling SKUs
Description Color
Rack Enclosures Open Frame Racks
ar3100 ar3150 ar3107 ar3157 ar2105blKar100 and ar100HD
ar200 and ar201
ar203 and ar204
acF400:Rack Air Removal Unit 100-240V 50/60Hz for NetShelter SX 19" Wide Rack
Black • •
acF402:Rack Air Removal Unit 100-240V 50/60Hz for NetShelter SX 23" Wide Rack
Black • •
acF201blK: Rack Side Air Distribution 2RU 115V 60Hz Black • • • • •
acF202blK: Rack Side Air Distribution 2RU 208/230 50/60Hz Black • • • • •
91
Rack C
oo
ling
in row rack coolingAir or Water Rack Cooling
> In row precision air conditioning for medium to large data centers
> Air or water cooling options
> Ideal for high density application
> Field replaceable components
> Rack inlet temperature controlACRP100
in row rack cooling
Specifications: ACRC100 ACRP100
cooling options: Chilled water Air
air Discharge Patterns: Horizontal Horizontal
intake air: Rear return Rear return
air Flow: 2900CFM 4800CFM
condensate Pump capacity: 1.30gal/hour 8.45gal/hour
Minimum water inlet Temperature:
7°C / 45°F -
Total System waterside Pressure Drop (psi/kpa):
6.9 / 48 -
required water Flow rate (gpm/lps):
13.2 / 0.84 -
Humidification Value: - 6.6lb/hour
compressor Type: - Reciprocating
refrigerant: - R407C
cooling capacity options: - 29kW
Input ACRC100 ACRP100
nominal input Voltage: 100V,120V 200V 3PH,208V 3PH
input Power: 1100W 13.737kW
input Frequency: 50/60Hz 50/60Hz
rack Height: 42RU 42RU
input connections:NEMA L5-20P
Hard Wire 4-wire (3PH + G)
Communications and Management
control Panel: Multi-function LCD status and control console
audible alarm:Audible and visible alarms
prioritized by severity
Dimensions (in/mm):78.4 x 11.8 x 42.1 / 1991 x 300 x 300
78.4 x 23.6 x 42.1 / 1991 x 600 x 1070
weight (lb/kg): 358 / 162.73 833 / 378.64
units per Pallet: 1
Conformance
regulatory approvals:cUL Listed,FCC Part 15 Class A,ICES-
003,Industry Canada,MEA,UL Listed,VCCI
warranty 1 year (parts only)
92
Rac
k C
oo
ling
> Air distribution for networking equipment with side-to-side airflow
> Pulls air from the front of the rack and distributes it to the side air intake
> Extends equipment life by providing proper inlet temperatures
> Performance heat removal for high density equipment in rack enclosures
> Captures exhaust heat, eliminating hot spots
> Unit-mounted LCD display to monitor alarm conditionsandadjustunitsetpoints
Conformance
regulatory approvals:cUL Listed, CE, EN 55022 Class A, EN 55024, FCC Part 15 Class A, ICES-003, IEC 61000-3-2, IEC 61000-3-3, UL Listed, VDE, VCCI
Standard warranty: 2 years repair or replace
Part Number Description
acF400:100–240V 50/60Hz for NetShelter® SX 600mm wide rack
acF402:100–240V 50/60Hz for NetShelter SX 750mm wide rack
acF126: ARU Ducting kit for 24" ceiling tiles
acF127: ARU Ducting kit for 600mm ceiling tiles
acF122: ARU Door Grille Kit
Communications & Management
control Panel: Power on/off indicator
Mechanical
Dimensions (in/mm): 3.44 x 16.98 x 26.34 / 87 x 431 x 669
weight (lb/kg): 32 / 14.55 32 / 14.55
Conformance
regulatory approvals: UL recognized CE, UL recognized
Standard warranty: 2 years repair or replace
Part Number Description
acF201blK: 115Vac, 60Hz
acF202blK: 208/230Vac, 50/60HZ
ACF400
rack air Distribution unit
rack air removal unit
Specifications ACF400 ACF402
cooling capacity options: 16.5kW 16.5kW
air Discharge Patterns: Upflow, Ducted Upflow, Ducted
air Flow: 2000CFM 2000CFM
Input
nominal input Voltage: 100V,120V, 200V, 208V, 230V
input Power: 1200W 1200W
input Frequency: 50/60Hz 50/60Hz
input connections: IEC-320 C14, NEMA 5-15P
Communications
control Panel: Multi-function LCD status and control console
Mechanical
Dimensions (in/mm):75.5 x 23.5 x 10 / 1918 x 597 x 254
75.5 x 29 x 10 / 1918 x 737 x 254
weight (lb/kg): 148 / 67.27 170 / 77.27
rack air Distribution unitSpecifications ACF201BLK ACF202BLK
air Flow: 260CFM 260CFM
amp Draw nominal: 2A 1A
Input
nominal input Voltage: 120V 200V, 208V, 230V
input Power: 150W -
input Frequency: 60Hz +/- 5Hz 50/60Hz
rack Height: 2RU 2RU
input connections: C-13, NEMA 5-15P C-13, IEC-320 C14
rack air removal unit
ACF201
93
Rack A
ccessories
rack Hardware and accessoriesCable and Mounting Accessories
> Blanking panels
> Cable management rings
> SX cable ring set and cable tree
> Vertical or horizontal cable organizer
> SX recessed rail kit and support rails
> SX HP adapter kit
> Fixed and sliding shelves
1RU Blanking Panels
AR8136BLK (Qty 10)/AR8136BLK200 (Qty 200)
Modular 1RU plastic blanking panels allow
quick and easy installation in any EIA-310-D
compliant square hole mounting rail rack or
enclosure, tool free mounting.
Cable Management
Cable Management Rings AR8113A
Facilitates side/vertical cable management.
Organizes data and power cables. Includes
mounting hardware and velcro mounting straps.
SX Cable Ring Set AR7707
Deep cable management rings to facilitate
vertical cable management in typically
networking environments.
SX Cable Tree
AR7505
Cable management accessory to facilitate
rear cable management within an enclosure
or a rack. Helps to eliminate cable stress and
maintain a neat, organized cable layout. Works
in both 42RU and 48RU racks.
Cable Organizers
Vertical Cable Organizer AR8442 Tool Free, vertical cable management accessory that allows for quick installation and takes up zero RU of space within the rack. It helps to eliminate cable stress and to organize the cable layout within the rear channels of the NetShelter® enclosure.
1RU and 2RU-U Horizontal Cable OrganizerAR8425A, AR8426A Facilitates front cable management. Integrated front cable hoops. Occupies 1RU of rack space. Includes Installation Guide, Mounting hardware.
SX Recessed Rail Kit
AR7503, AR7504, AR7508, and AR7578
Enables users to mount networking and server
equipment in the same rack or enclosure.
Includes:Installationguide,mounting
hardware, rackmounting hardware.
Support Rails for 600mm Enclosures
AR8006A
The Equipment Support Rails will support
any non-Rackmount piece of equipment that
measures 16.75" (43cm) to 17.7" (45cm) wide
and has a maximum weight of 200 lb/91kg. The
Support Rails attach to the side mounting
holes of the vertical mounting rails.
SX HP Adapter Kit
AR8013A
This adapter kit allow HP’s L Class/RP54xx Series
servers to be installed in the NetShelter® SX
enclosure. This kit is configured for the
installationofoneserver.Includes:Installation
guide, mounting hardware.
Shelves
Fixed Shelf AR8122BLK (Black) (X-CertifieD)Occupies 1RU of rack space, 4 post mounting,adjustablemountingdepth, ventilated. Includes installation guide and mounting hardware. Supports 250lb / 114kg
Sliding Shelf AR8123BLK (Black)Occupies 1RU of rack space, 4 post mounting, adjustablemountingdepth,ventilated.Includesfriction pads, installation guide, mounting hardware and user manual. Supports 100lb / 45.5kg
Sliding Shelf
95
Gen
erators
AlphaGen™ GeneratorsAdding a generator to any type of power system provides additional peace of mind. For outside plant
communication networks, a generator serves as assurance that even in severe conditions, you will be
able to keep your system up and functioning. All AlphaGen systems are engineered to have significantly
reduced noise levels, high power density, and status monitoring.
> AlphaGen 8kW-2MW SystemsCritical power applications are part of every industry; protecting them starts with reliable generators,
available in diesel, gas and LP configurations. Our EPA-compliant diesel models deliver dependable
power to a wide range of output requirements. From small-load hub and small business to large
Headend or facility backup, every generator is engineered to provide maximum power, performance,
flexibility and fuel efficiency.
> AlphaGen TelecomThe AlphaGen curbside generator system is specifically designed for outside plant communication
networks. Every AlphaGen system incorporates industry leading power technology, including natural
gas or propane powered engine generators, exclusive audible noise baffling, remote status monitoring
features and durable weather resistant enclosures.
96
Gen
erat
ors
alphagen™ 3.5kw to 2Mw SystemsGenerator Systems
> Generator solutions to most CRT and Facility Requirements
> 3.5kW to 2MW
> LP/NG/Diesel
> Single phase or Three phase
> Fixed or portable
> Communications options
> Automatic Transfer Switch
Alpha has the capability to design, install and maintain industrial generators to meet your power supply needs.
Contact an Alpha represenative for more details.
AlphaGen System
97
Gen
erators
alphagen™ TelecomGenerator Systems
alphagen Telecom
Model 3.5kW 5kW 7.5kW
Dc output Voltage:39V ±0.5V @ no load 36V configuration 39V ±0.5V @ no load 36V configuration 52V ±0.5V @ no load 48V configuration
52V ±0.5V @ no load 48V configuration 52V ±0.5V @ no load 48V configuration 104V ±0.5V @ no load 96V configuration
Dc output load regulation: 0.5V 0.5V 0.5V
output current: 39V @ 90A max / 52V @ 67A max 39V @ 128A max / 52V @ 96A max 52V @ 144A max / 104V @ 72A max
engine: 398cc, Air cooled, Single OHV 10.5hp (using natural gas fuel) 642cc, Air cooled, Twin OHV 15hp (using natural gas)
rPM: (Variable Speed): 2800 to 3600RPM 2800 to 3600RPM 2800 to 3600RPM
Acoustical Noise
dba 10' @ 100% rated load: 68.7 68.5 70.3
dba 20' @ 100% rated load: 63 62.5 64.3
dba 10' @ 70% rated load: 68.3 66.9 66.4
dba 20' @ 70% rated load: 62.6 60.9 60.4
Mechanical: CE-3x2 CE-9x2 CE-3x2 CE-9x2 PN-6x
Dimensions (in/cm):44 x 26 x 24 / 111.2 x 66 x 61
52 x 52 x 24 / 132.1 x 132.1 x 61
44 x 26 x 24 /111.2 x 66 x 61
52 x 52 x 24 / 132.1 x 132.1 x 61
39 (57 with optional pedestal) x 39.25 x 24 / 99 (144) x 100 x 61
weight (lb/kg): 383 / 174 413 / 187 383 / 174 413 / 187 338 / 174 (370/168 with optional pedestal)
APU Fuel Consumption
natural gas: 1000bTu/ft.3: 60ft3/hr 80ft3/hr 156ft3/hr
Propane gas: 2520bTu/ft.3: 0.82 gal/hr to 30ft3/hr to 3.46lb/hr 1.10gal/hr to 40ft3/hr to 4.62lb/hr 1.48gal/hr to 54ft3/hr to 6.24lb/hr
exterior Surface Temperature: Meets requirements of UL/CSA
All Models
gas inlet Pressure: 0.5 to 2 PSI Inlet Pressure (Contact Alpha Engineering for additional supply resources)
ign charger Voltage: 13.5Vdc
ign charger current: 6A max
remote interface length: 75ft max Distance depends upon installation, derating and wire gauge
Standards: UL1778, UL2200, NFPA 37/54/58 and 70, CSA C22.2 No.107.1, EMC/FCC Part 15 Class A
Features
Fuel System, controls and Monitoring:
The controls and fuel system meet applicable sections of NFPA 37, 54 and 58 for automatic unattended operation of remotely located generators. Full System Control and Status Monitoring included.
Sensors: Gas Hazard, Pad Shear, Water Intrusion and Tamper
Safety Shutdowns:Low Oil Pressure, Low Fuel Pressure Shutdown (Propane only), Over Temp, Water Intrusion,
Pad Shear, Gas Hazard (Propane or Natural Gas), Over-Speed, Over-Crank
optional Feature: ColdStartKit:Providesadditionalstartingcapabilityattemperaturesbelow-18°C/0°F
Configuration Options:
CE-3x2 3.5 or 5kW CE-9x2 3.5 or 5kWCE-3/9G Propane Storage for Generator
(For 3.5 and 5kW)
PN-6x 7.5kW
(PN-6x is not compatible with CE-3/9G)
> Cost effective extended runtime solution for outdoor powering applications
> Quiet operation, small size, and low profile allow for easier installation in populated areas
> Eliminates large quantities of batteries otherwise required for extended runtime
> Telecom grade 48Vdc outputAlphaGen Telecom
99
Alp
ha B
uild
ing
System
s
Alpha Building SystemsBy MBSI
> Steel construction
> Reinforced concrete
> Professional workmanship
> On-site installation
> Environmentally sound
> Versatile finishing
We build the best, most diverse, line of equipment shelters, telecom equipment cabinets and
hazardous material storage buildings available. Whether you need wood, steel, fiberglass or bullet-
proofconcrete,youcancountonacost-efficientcustomsolution.Alphaprovides“turnkey”site
construction - nationwide - including tower and equipment installation.
Each concrete shelter is hand-built in a climate controlled environment, keeping materials dry and
construction on schedule. Your shelter will move down an assembly line where skilled workers
meticulously complete tasks they have perfected through ongoing training, repetition and strict
quality control. In addition, periodic inspections are performed by State or third-party building
inspectors. The result brings you an equipment shelter well capable of protecting your valuable
contents for many decades.
102
No
tes
alpha Technologies Due to continuing product development, Alpha reserves the right to change specifications without notice. Copyright © 2008 Alpha Technologies Inc. All Rights Reserved. Alpha is a registered trademark of Alpha Technologies. (2/2008)
www.alpha.com
Alpha Technologies Ltd.4084 McConnell CourtBurnaby BC V5A 3N7CanadaTel: +1 604 430 1476Fax: +1 604 430 8908
Alpha Technologies Europe Ltd.Twyford House Thorley Bishop’s Stortford, HertfordshireCM22 7PAUnited KingdomTel: +44 1279 501110Fax: +44 1279 659870
Alpha Technologies GmbHHansastrasse 8D 91126 SchwabachGermanyTel: +49 9122 79889 0Fax: + 49 9122 79889 21
AlphaTec Ltd.339 Saint Andrews StreetSuite 101 Andrea Chambers3307 Limassol CyprusTel: +357 25 375675Fax: +357 25 359595
AlphaTEK oooKhokhlovskiy Pereulok 16Stroenie 1 Office 403 109028 MoscowRussiaTel: +7 495 916 1854Fax: +7 495 916 1349
Alpha TechnologiesUnit 504, 5/F, Fourseas Bldg.No. 208-212 Nathan RoadKowloon, Hong KongChinaTel: +852 2736 8663Fax: +852 2199 7988
Alpha Technologies Inc.3767 Alpha WayBellingham WA 98226USATel: +1 360 647 2360Fax: +1 360 671 4936
Visit www.alpha.com for additional headend power information.