ELECTRIC HEATING UNITS
FANS
AIR DISTRIBUTION DEVICES
PUMPS
FAN COIL UNITS UNITS
INDEX OF DRAWINGS
AIR CONTROL UNITS-HOT WATER
ROOM HEATING UNITS
LOUVER SCHEDULE
SHEET DESCRIPTION
ELEC. SERVICE TO THREE-PHASE UNITSTO BE THREE-WIRE UNLESS NOTED
APPROX. CABINET DIMENSIONS
DEPTH
VERIFY/COORDINATE CABINET DIMENSIONS, MOUNTING
DESCRIPTION
AND RECESS REQUIREMENTS WITH ARCHITECTURALDWGS. PRIOR TO ORDERING.
RECESSED UNITS TO HAVE FOUR(4) SIDE OVERLAP UNLESS OTHERWISE NOTED
UNITNO.
GENERAL NOTES:
BY GEN. CONT'R.
HEATING
LINTELS IN MASONRY WALLS FOR FULL &SEMI-RECESSED UNIT WALL OPENING PROVIDED
THREE(3) PHASE COIL LOADS SHALL BE DIVIDEDEVENLY ACROSS EACH PHASE.
SERVICE CFMM.B.H.
ELEC. SERVICE
VOLTKW(MIN) AMP LENGTHPHASEREFER TONOTE NO.HEIGHT RECESS
GENERAL CONTRACTOR.WALL LINTEL FOR WALL OPENING BYWHERE REQUIRED FOR DECK SUPPORT ANDSTEEL FRAMING AROUND ROOF OPENING.
PHASE
CONSIDERED MINIMUM.MOTOR HORSEPOWERS LISTED ARE TO BE
300 & 301 MEASURED AT 5 FT. FOR P.R.V.'S.SONES VALUES BASED ON A.M.C.A. BULLETINS
DESCRIPTIONUNITNO.
GENERAL NOTES
CONTRACTOR.VERIFY SIZE & COORDINATE WITH GENERALROOF & WALL OPENINGS ARE APPROXIMATE.
SERVICESONESMAX.STATIC WHEEL
PRESSCFM
DIA.
MOTOR
H.P. VOLTROOF/APPROX.
WALL OPG.
O.W.B.E. E.C.L.
FINISH KEY: "O.W.B.E."-OFF WHITE BAKED ENAMEL,"E.C.L."-ETCHED CLEAR LACQUER OR ANODIZED.
SUPPLY AIR DIFFUSERS SHALL BE 4-WAYBLOW UNLESS OTHERWISE NOTED ON DWGS.
DESCRIPTION
REFER TO SPECIFICATIONS FOR OTHER
ALL LAY-IN AIR DEVICES SHALL FIT IN24"X24" LAY-IN CEILING SYSTEM.
SYMBOL
GENERAL NOTES
MANUFACTURERS.
TYPE MOUNTING MATERIAL
SURFACELAY-IN STEEL ALUM.
PROVIDE AUX. FRAMES FOR AIR DEVICES INPLASTER, GYPSUM BOARD, GLAZED TILE ORCERAMIC TILE SURFACES.
FINISH CATALOG NUMBER SEENOTEACCESSORIES
DISCHARGESUCTION &
DESCRIPTIONUNITNO.
PERFORMANCE
GPMSERVICE
MOTOR
VOLTFT. HD. H.P.
MIN.EFF.%PHASE
REMARKS
VERIFY/COORDINATE UNIT DIMENSIONS,MOUNTING & RECESS REQUIREMENTS WITHARCHITECTURAL DWGS. PRIOR TO ORDERING.
APPROX. CABINET DIM.
WIDTH
COOLING CAPACITY BASED ON 45 ENT. WATER
HEATING CAPACITY BASED ON 70 ENT. AIR &
DESCRIPTION
& 80 DB/ 67 WB ENT. AIR TEMP.
140 ENT. WATER.
NO.UNIT
GENERAL NOTES
MAXIMUM WATER PRESS. DROP THRU COIL
SENS. TOTAL
COOLING MBH
MOTOR: 115V.-1PH. UNLESS OTHERWISE
MOUNTING CFMMBHHTG.
NOTED.
5 FT.
CLG.HTG.
G.P.M.VALVEAUTO
SIZERUNOUT
HEIGHTDEPTH
MOTOR
BASIS OF DESIGN: TITUS
FC-1 HIGH RISE VERTICALSTACK FAN COIL UNIT
FLOOR SET
NO.MODEL
240 8.8 6.6 9.1 1.1 1.8 0.75"/0.75" 2 WAY 17" 17" 88" 1/10 VSR03
FC-2 HIGH RISE VERTICALSTACK FAN COIL UNIT
FLOOR SET 300 10.1 7.5 10.5 1.2 2.1 0.75"/0.75" 2 WAY 17" 17" 88" 1/10 VSR04
INLET
TYPES - "V.V." VARIABLE VOLUME;"V.V.R." VARIABLE VOLUME REHEAT;"C.V.R." CONSTANT VOLUME REHEAT.
UNIT & COIL AT MAX. CFM.0.6" S.P. MAX. PRESS. DROP THRU
UNITNO.
TYPEDIA.
GENERAL NOTESREHEAT COIL CAPACITY BASED ONWINTER MIN. CFM, 55 ENT. AIR &140 ENT. WATER TEMPERATURE.
MBH
CFM
WINTERMAX.MIN. MIN.
SUMMER
REHEAT COIL
GPM RUNOUTSIZE
AUTO.VALVE
NOTESEE
1-1 V.V.R. 14 1310 655 325 22 1.4 0.75 2-WAY
0.751.218535106512V.V.R.1-2
12.92046092010V.V.R.1-3
0.751.31634569010V.V.R.1-4
0.752.328550110012V.V.R.1-5
13.33460063010V.V.R.1-6
0.751.4122854808V.V.R.1-7
0.751.82549097512V.V.R.1-8
0.750.892104208V.V.R.1-9
0.751.320635127012V.V.R.1-10
13.42149566010V.V.R.1-11
13.8561300130014V.V.R.1-12
13.036700142012V.V.R.1-13
0.752.31842588010V.V.R.1-14
0.752.123525105012V.V.R.1-15
0.750.892054108V.V.R.1-16
14.0501160192016V.V.R.1-17
0.751.111250480
8V.V.R.1-18 0.751.011240500
8V.V.R.1-19
0.752.12140080010V.V.R.1-20
12.6154008008V.V.R.1-21
0.751.421750150012V.V.R.2-1
0.752.926800160014V.V.R.2-2
12.8541240136014V.V.R.2-3
0.751.421650130014V.V.R.2-4
0.751.6133206358V.V.R.2-5
13.232580115512V.V.R.2-6
0.752.224560112012V.V.R.2-7
13.7551275162014V.V.R.2-8
15.8711665166514V.V.R.2-9
0.750.8102054108V.V.R.2-10
0.750.692755508V.V.R.2-11
12.931610122012V.V.R.2-12
0.750.891903808V.V.R.2-13
0.750.861452806V.V.R.2-14
0.752.32237575010V.V.R.2-15
0.750.8112154258V.V.R.2-16
13.7461330133012V.V.R.2-17
13.7551100110014V.V.R.2-18
3-WAY
3-WAY
3-WAY
3-WAY
TMSSQUARE DIFFUSER RD. NECKA1
50FEGGCRATE RETURN GRILLEJ1
BY GEN. CONT'R.
LINTELS IN MASONRY WALLS FOR FULL &
SEMI-RECESSED UNIT WALL OPENINGS PROVIDED
RECESSED UNITS TO HAVE FOUR(4) SIDE
OVERLAP UNLESS OTHERWISE NOTED.
APPROX. CABINET DIMENSIONS
HEATING CAPACITY BASED ON 60 ENT. AIR &
140 ENT. WATER.
MAXIMUM WATER PRESS. DROP THRU COIL
DESCRIPTIONNO.
UNIT
5 FT.
GENERAL NOTES
VERIFY/COORDINATE CABINET DIMENSIONS,
MOUNTING & RECESS REQUIREMENTS WITH
ARCHITECTURAL DWGS. PRIOR TO ORDERING.
MOTOR: 115V.-1PH. UNLESS OTHERWISE
CFMMOUNTING
NOTED.
RUNOUT
MBH
HTG.GPM
SIZE LENGTHVALVE/
AUTO.
DEPTH RECESSHEIGHT
230
230
230
325
230
145
325
145
325
230
450
325
230
325
145
580
145
145
230
145
325
450
450
325
145
325
325
450
450
145
145
325
145
80
230
145
325
450
EF-1
EF-2
EF-3
EF-4
EF-5
EF-6
EF-7
EF-8
EF-9
EF-10
EF-11
EF-12
POWER ROOF VENTILATOR
ROOF VENTILATOR
POWER ROOF VENTILATOR
HWP-1
HWP-2
CHWP-3
HP
INLINE RECIRC. BOOSTER PUMP
INLINE RECIRC. BOOSTER PUMP
HWP-3 INLINE PUMP
HWP-4
HWP-5
INLINE RECIRC. BOOSTER PUMP
HWP-6
INLINE RECIRC. BOOSTER PUMP
HWP-7
BASE MT'D END SUCTION
HWP-8
BASE MT'D END SUCTION
INLINE PUMP
AH-1 H.W. COIL
AH-2 H.W. COIL
CHILLER C.W. PUMP
RF-1 VANEAXIAL FAN
RF-2 VANEAXIAL FAN
NORTH 1ST FLOOR TOILETS 900 1.0" 14" 12.8 0.33 120 1 18.5" x 18.5"
SOUTH 1ST FLOOR TOILETS 750 1.0" 14" 12.8 0.33 120 1 18.5" x 18.5"
AH1 - RETURN 19,200
AH2 - RETURN
VARIBLE FREQUENCY DRIVE BY H.C.
31 13 0.25 120 1 53.7 1.25" & 1.25"
36 14 0.25 55.7 1.25" & 1.25"
RED BRICK KITCHEN HOOD-122 850
DELI-SH KITCHEN HOOD-207 1020
ENCOUNTER KITCHEN HOOD-409A/409B 3230
FIRST STOP KITCHEN HOOD-512A/512B 2890
PACIFIC RIM KITCHEN HOOD-614 2210
AMERICAS KITCHEN HOOD-722A/722B 4116
AMERICAS KITCHEN HOOD-728 880
BACK OF HOUSE KITCHEN HOOD- 3155
POT WASH HOOD-832 600
DISHWASHER HOOD-846 550
1.25 36" 84 dBA 10 460 3 -
DOAS-1 H.W. COIL 19 13 0.25 120 1 42 1" & 1"
DOAS-2 H.W. COIL 120 1 1" & 1"
1.25" 14" 14.1 0.33 120 1 18.5" x 18.5"
1.5" 14" 15.8 0.5 120 1 18.5" x 18.5"
2.25" 24" 25 3 460 3 26.5" x 26.5"
1.75" 18" 19.4 1.5 460 3 20.5" x 20.5"
2.0" 24" 17.8 1.5 460 3 26.5" x26.5"
1.75" 20" 23 3 460 3 20.5" x 20.5"
1.5" 14" 14.8 0.5 120 1 18.5" x 18.5"
1.75" 18" 20 1.5 460 3 20.5" x 20.5"
1.25" 14" 16 0.25 120 1 18.5" x 18.5"
1.0" 10" 11.4 0.25 120 1 14.5" x 14.5"
H-1 ARCH. HEAVY DUTYWALL HEATER
1st FLOOR VESTIBULE 100 6.8 2 9.6 208 1 15.8" 4" 19.2" 3"
H.W.-RESIDENTIAL 180 75 7.5 460 3 71 2.5" & 2"
460 3
13 30 0.16 120 1 - 1.5" & 1.5"
FC-3 HORIZONTAL FANCOIL UNIT
SUSPENDED
SQUARE DIFFUSER RD. NECKA2
EGGCRATE RETURN GRILLEJ2
FC-4 HORIZONTAL FANCOIL UNIT
FC-5 HORIZONTAL FANCOIL UNIT
FC-6
FC-7
220 9.5 3.2 3.9 1.0 0.8 0.75"/0.75" 25" 23" 12" 1/20 HBP02
1310 42.4 25.9 28.3 4.3 5.6 1"/1" 46" 28" 17" 2@1/4 HHP16
2000 64.7 29.1 32.8 6.6 6.5 1"/1" 51" 28" 17" 2@1/4 HHP18
500 14.7 10.5 14.2 1.8 2.8 0.75"/0.75" 20" 20" 88" 1/10 VSR06
600 18.4 13.5 17.6 2.2 3.5 0.75"/0.75" 1/4 VSR08
HEATING AUTO VALVE SHALL BE 2 WAY UNLESS OTHERWISE NOTED ON THE FLOOR PLAN.
2-WAY
2-WAY
2-WAY
2-WAY
2-WAY
2-WAY
2-WAY
2-WAY
2-WAY
2-WAY
2-WAY
2-WAY
2-WAY
2-WAY
2-WAY
2-WAY
2-WAY
2-WAY
2-WAY
2-WAY
2-WAY
2-WAY
2-WAY
2-WAY
2-WAY
2-WAY
2-WAY
2-WAY
2-WAY
2-WAY
2-WAY
2-WAY
2-WAY
2-WAY
AUTO.VLV. CV
OBD
OMNI OBD
BASIS OF DESIGN: TITUS
A3 OMNI OBD
ARCH. DIFF. ROUND PLAQUEA4 R-OMNI OBD
FLOWBAR LINEAR DIFFUSERD1 FL-10
3/4" STEEL SUPPLY GRILLEH1 300RL
3/4" SPACING RETURN GRILLEG1 350RL
50F
SPIRAL DUCT MT'D GRILLES1 S300FS
FC-8 HORIZONTAL FANCOIL UNIT
SUSPENDED 240 8.8 4.6 5.7 1.2 1.1 0.75"/0.75" 28.5" 23" 12" 1/20 HBP03
FC-9 HORIZONTAL FANCOIL UNIT
SUSPENDED 300 10.1 6.7 8.4 1.3 1.7 0.75"/0.75" 34.5" 23" 12" 1/20 HBP04
H-2
4 PIPE SYSTEM
FC-10 800 24.5 17.7 23.5 3.0 4.7 0.75"/1" 2 WAY 24" 24" 88" 1/4 VSR10
TMSSQUARE DIFFUSER RD. NECKA5
SQUARE DIFFUSER RD. NECK
0.7
0.6
1.4
0.6
1.1
1.6
0.7
0.8
0.4
0.64
1.6
1.8
1.4
1.1
1.0
0.4
1.9
0.5
0.5
1.0
1.2
0.9
0.9
1.3
0.7
0.8
1.5
1.0
1.7
2.7
0.4
0.3
1.4
0.4
0.4
1.1
0.4
1.7
1.7
0.750.851202406V.V.R.2-19 80 2-WAY0.4
13.235805161014V.V.R.2-20 450 2-WAY1.5
BORDER SHALL BE TYPE 11. AIR DEVICE SHALL MATCH GALVANIZED FINISH OF DUCT.
L-1 AH-1/KMUA-1 252"/36"/6" 0.05 31.12 19,555 INTAKE AIR
L-2 AH-1/AH-2 72"/24"/6" 0.1 5.94 5345 INTAKE AIR
L-3 AH-1/DOAS-1 240"/36"/6" 0.09 27.0 24,000 RELIEF
L-4 AH-2 252"/36"/6" 0.05 28.6 14,655 INTAKE AIR
L-5 KMUA-2 72"/36"/6" 0.05 19.1 6300 INTAKE AIR
L-6 AH-2/DOAS-2 240"/36"/6" 0.08 30.9 19,200 RELIEF AIR
HOT WATER UNIT HEATER WALL/CEILING MOUNTED 800 24.2 4.5 1.0" 3 WAY/ 21" 18.5" 21" -
SIZE
2.1"
NOTES
SUSPENDED
SUSPENDED
WEIGHTlbs.
230
230
65
175
195
270
280
70
80
310
WEIGHTlbs.
85
85
85
175
125
175
85
145
85
125
85
60
1230
821A/821B
HWP-9
HWP-10
BASE MT'D END SUCTION
BASE MT'D END SUCTION
H.W.-KITCHEN/DINING 300 78 10 460 3 77.3 3" & 2.5"
H.W.-RESIDENTIAL 75 7.5 2.5" & 2"
H.W.-KITCHEN/DINING
INLINE PUMP CHILLER H.W. PUMP 120 125 30 0.40 - 1.5" & 1.5"
CP-1
CHWP-1
INLINE PUMP - BASE BID
BASE MT'D END SUCTION
KITCHEN CONDENSER WATER
C.W.-RESIDENTIAL
53
220
65
190 25
460
460
3
3
54
62.8
1.25" & 1.25"
3" & 2"
CHWP-2 BASE MT'D END SUCTION C.W.-KITCHEN/DINING 305 193 30 460 3 62 2.5" & 2"
5434606553KITCHEN CONDENSER WATERINLINE PUMP - BASE BIDCP-2
2 WAY
2 WAY
2 WAY
2 WAY
2 WAY
2 WAY
2 WAY
ALL COOLING COIL VALVES SHALL BE 2 WAY.
7"8"22"22"12089.626.8283CEILING HEATER
H-9 FORCED FAN 1st FLOOR ENCOUNTER& LOBBY VESTIBULES
350 10.2 3 14.5 208 1 14" 7.5" 16" -ELECTRICAL ROOM
BASEMENTFORCED FAN HEATERH-17
PROVIDE DISCONNECT.
OTHERWISE.
3" & 2.5"77.334601078300
UPBLAST POWER
UPBLAST POWERROOF VENTILATORUPBLAST POWER
ROOF VENTILATORUPBLAST POWER
ROOF VENTILATORUPBLAST POWER
ROOF VENTILATOR
UPBLAST POWERROOF VENTILATORUPBLAST POWER
ROOF VENTILATORUPBLAST POWER
ROOF VENTILATORUPBLAST POWER
ROOF VENTILATORUPBLAST POWER
ROOF VENTILATOR
FANS REQUIRE AN INVERTER DUTY MOTOR.
FAN COIL UNITEXP. HORIZONTALFC-12
FAN COIL UNITFC-11 EXP. HORIZONTAL SUSPENDED
SUSPENDED
HHE14
HHE06
200
120
1/4
2@1/4
2 WAY 46" 30" 19"
2 WAY 29" 30" 19"
1"/1"4.83.423.822.327.61300
0.75"/0.75"2.01.410.09.711.3535
GENERAL NOTESA ALL BRANCH DUCTS TO AIR DEVICES AND AIR TERMINAL BOXES SHALL BE EQUAL IN SIZE TO THE NECK OF THE AIR DEVICE OR TERMINAL BOX, UNLESS OTHERWISE NOTED.
B REFER TO ARCHITECTURAL CEILING PLANS FOR EXACT LOCATION OF CEILING DEVICES.
C FLEXIBLE DUCTWORK MAY UTILIZED ONLY AS INDICATED IN THE DETAILS.
D AIR VENTS SHALL BE PROVIDED ON ALL POINTS THAT COULD TRAP AIR AND AS INDICATED IN DETAILS. PROVIDE BALL VALVE AND THREADED CONNECTION FOR VENTING.
E AIRFOIL TURNING VANES SHALL BE INSTALLED IN ALL 90 DEGREE DUCT ELBOWS EXCEPT TRANSFER DUCTS AND OPEN RETURN AIR BOOTS.
F FLOOR PLANS DO NOT INDICATE ALL POINTS OF VALVING, DEVICES, ETC. ON THE PIPING REQUIRED. REFER TO STANDARD DETAILS, FLUID FLOW DIAGRAMS AND SPECIFICATION FOR ADDITIONAL REQUIREMENTS.
G ALL BRANCH DUCT TEE FITTINGS UPSTREAM OF VAV BOXES SHALL BE OF THE CONICAL TYPE.
H ANNULAR SPACE OF PIPE, DUCT, CONDUIT, AND SIMILAR PENETRATIONS OF FIRE RATED ASSEMBLIES SHALL BE FIRESTOPPED. REFER TO ARCHITECTURAL DRAWINGS FOR CONSTRUCTION, LAYOUT, AND RATINGS OF WALLS, PARTITIONS, AND OTHER BUILDING ELEMENTS.
I HVAC CONTRACTOR SHALL COORDINATE THE LOCATION OF ALL PIPES, DUCTS, UNITS, ETC. WITH ALL OTHER TRADES. PROVIDE ADJUSTMENTS OR OFFSETS WHERE NECESSARY.
J ALL DUCTS AND PIPES TO BE RUN ABOVE CEILING. WHERE NO CEILINGS ARE INSTALLED, HOLD AS HIGH AS POSSIBLE TO STRUCTURE UNLESS OTHERWISE NOTED.
120 1
L-7 ELEC. ROOM 84"/102"/6" 0.1 8250 INTAKE AIR
12"
12"
12"
12"
12"
19,200 1.25 36" 84 dBA 10 460 3 - 1230
L-8 MECH./ELEC. 56"/48"/6" 0.08 10.3 8250 RELIEF AIR5'-0"
EF-13 MECHANICAL ROOM-B14 750 0.5" 12" 5.8 0.16 120 1 - 70INLINE CENTRIFUGAL FAN
B10/B12
LAUNDRY-B08 650 0.4" - - 300 W 120 1 - 70
BASIS OF DESIGN: FANTECH "FG" SERIES.
EF-14 INLINE DRYEREXHAUST FAN
-0117512V.V.K1-1
0194014K1-2
0173514K1-3
0189514K2-1
0
0
0
0186514K2-2 0
0247516K2-3 0
V.V.
V.V.
V.V.
V.V.
V.V.
- - -
- - - -
- - - -
- - - -
- - - -
- - - -
THIS BOX IS VAV SHUTOFF, NO REHEAT.
0
EF-15 ELECTRICAL ROOM-B12 7500 0.5" 24" 25 5 460 3 - 415INLINE CENTRIFUGAL FAN
B12
LINEAR 2 SLOT DIFFUSERM1 ML-38
180 71
31 14 46.40.33
MOTOR
HP
-
VOLT
-
PHASE
-
H-19 AIR CURTAIN STRUCTURE 8000 160 18.9 1.5" 3 WAY/ 106" 20" 18" -5.2"
2@1 hp 460 3
FLOOR SET
FLOOR SET
FLOOR SET
HIGH RISE VERTICALSTACK FAN COIL UNITHIGH RISE VERTICALSTACK FAN COIL UNIT
HIGH RISE VERTICALSTACK FAN COIL UNIT
20" 20" 88"
PROVIDE FRESH AIR OPENING.
INFLOOR HEATING PUMP 15 40 0.4 - 1.5" & 1.5"120 1
6"
H-20 AIR CURTAIN WALL 2550 52 0.5 hp 208 1 6.2 1.0 2 WAY/2.9"
46" 16.5" 14" -
1236900180014V.V.R.2-21 450 2-WAY0.95
12.036900180014V.V.R.1-22 450 2-WAY0.95
L-9 DOAS-1 72"/24"/6" 0.06 5.94 4000 INTAKE AIR
L-10 DOAS-2 72"/24"/6" 0.05 5.94 3300 INTAKE AIR
OBD
OBD
OBD
OBD
ASD
HW/CW
LOUVER SHALL BE MOUNTED IN FAUX CHIMNEY. REFER TO ARCHITECTURALPLANS FOR MOUNTING HEIGHT.
10.3 SQ. FT. THRU OPEN PORTION OF LOUVER.
CP-1 INLINE PUMP - ALT #11 KITCHEN CONDENSER WATER 20 90 2 460 3 33
33346029020KITCHEN CONDENSER WATERINLINE PUMP - ALT #11CP-2
1.25" & 1.25"
1.25" & 1.25"
1.25" & 1.25"
2
2
INSULATED
1. LOW PRESSURE SUPPLY DUCT SHALL BE OF DOUBLE WALL CONSTRUCTION WHERE NOTED ON PLANS.
24
CLASSLEAKAGE
24
12
24
X
X
X
INSULATIONEXTERNAL
LINEDINTERNALLY
X
WALLINSULATED
DOUBLE NOTREMARKS
LOW PRESSURE RETURN DUCTWORK
LOW PRESSURE SUPPLY DUCTWORK: KMUA'S,
DUCT SYSTEM
SHEET METAL DUCT, EXTERIOR INSULATION, ETC. REFER TO SPECIFICATIONS FOR DUCT CONSTRUCTION:
OUTSIDE AIR DUCTWORK/PLENUM
GENERAL EXHAUST DUCTWORK
GENERAL NOTES
B-1.5"
-1.5"
-1.0"
B
B
S.M.A.C.N.A. CLASS.
CLASSS.P. CON-
+2.0"
STRUCT.SEAL
B
CO
OLIN
G C
OIL
LEAV. AIR DB/WB
EN
ER
GY
RE
CO
VE
RY
WH
EE
LE
XH
AU
ST
FA
N
LEAV. AIR DB/WB-SUMMER
ELECTRIC PRE-HEAT REQUIRED
VIBRATION ISOLATORS
MIN OUTSIDE AIR
CAPACITY KW/VOLT/PHASE
STAGES
MAX. AIR P.D. - INCHES W.G.
LEAV. AIR DB/WB-WINTER
EXH. AIR DB/WB-WINTER
EXH. AIR DB/WB-SUMMER
EXH. AIR THRU WHEEL - CFM
OUTSIDE AIR DB/WB - WINTER
OUTSIDE AIR DB/WB - SUMMER
WHEEL OUTSIDE AIR CFM
VOLTAGE/PHASE
MOTOR HP
TOTAL S.P. - IN W.G.
EXT. S.P. IN W.G.
WHEEL TYPE/DIAMETER (IN)
MOTOR (MIN. H.P)
VFD
CFM
AUTO. VALVE MIN. CV & TYPE
GPM/PIPE RUNOUT
MAX WATER P.D.- FT.
MAX. AIR P.D.- INCHES W.G.
SU
PP
LY
FA
NH
EA
TIN
G C
OIL
HEATING COIL CAPACITY BASED ON 140 DEG ENT. WATER MOTOR - 460V - 3PHASE UNLESS NOTED OTHERWISE
S.P
.
ENT. AIR DB/WB
TOTAL MBH
SENSIBLE MBH
MIN. FACE AREA (SQ. FT.)
TOTAL S.P. - IN W.G.
AUTO. VALVE MIN. CV & TYPE
GPM/PIPE RUNOUT
MAX. WATER P.D.- FT.
MAX. AIR P.D. INCHES W.G.
WHEEL TYPE/DIAMETER (IN)
MOTOR (MIN. H.P.)
LEAV. AIR (DEG. F.)
ENT. AIR (DEG. F.)
CAPACITY MBH
MIN. FACE AREA
VFD
(SQ. FT)
COOLING COIL CAPACITY BASED ON 45 DEG ENT. WATER.
EXT. S.P. - IN W.G.
DESIGN BASIS
UNIT CONFIGURATION
GENERAL NOTES
UNIT LOCATION
AREA SERVED
CFM
UNIT NUMBER
SUMMER 93db/74wb, WINTER 0 db
ENERGY RECOVERY WHEEL O.A. CONDITIONS:
VARIABLE FREQUENCY DRIVE BY H.C.
AH-1 AH-2 KMUA-1 KMUA-2 DOAS-1 DOAS-2
2 FANS @15,000
LEGEND & SCHEDULESH001
DETAILSH003
DETAILSH004
BASEMENT FLOOR PLAN - DUCTWORKH100
FIRST FLOOR PLAN - DUCTWORKH101
SECOND FLOOR PLAN - DUCTWORKH102
THIRD FLOOR PLAN - DUCTWORKH103
4000 6600
1
2
ROOF PLANH104
FIL
TE
R
TTL. PRESS. DROP IN W.G. CLEAN
FACE AREA (SQ FT).
EFFICIENCY % / MERV
TYPE/SIZE
NORTH DINING SOUTH DINING
3RD FLOOR - NORTH 3RD FLOOR - SOUTH
TRANE TRANE
2.0
5.9
2 @ 25
PLENUM/27
YES (2)
37.5
459.3
33.8
55.0
0.085
31/2"
14.6, 3-WAY
38.5
706.4
1070.44
84/69.2
52/51.9
1.12
10.6
153/4"
72.3, 2-WAY
CART./12"
36.0
1.67"
85/13
NORTH DORM/CORR. SOUTH DORM CORR.
3RD FLOOR - NORTH 3RD FLOOR - SOUTH
TRANE TRANE
1.0
4.5
7.5
FC/12
YES
1.0
4.4
7.5
AF/15
YES
10.0 13.7
283.2 460.3
15.0 15.0
75.0 75.0
0.15 0.21
19/1.5" 31/2"
9, 2-WAY 14.6, 3-WAY
10.0 12.3
115.2 191.3
152.2 246.1
79.0/65.9 79.3/66.0
55/54.5 55/54.2
0.53 0.87
21/2" 35/2"
9.9, 2-WAY 16.5, 2-WAY
CART./4"
9.72
1.5"
85/13
CART./4"
18.9
1.4"
85/13
4352 7074
1.0 1.0
2.2 2.2
5 7.5
FC/12 FC/15
YES YES
5000 7000
93/74 93/74
0/-1 0/-1
4352 7074
75/63 75/63
70/53 70/53
79.0/65.9 79.3/66.0
55.3/44.3 53.2/43.1
0.15 1.0
0.5 0.5
460/3 460/3
YES YES
20.7/480/3 33.6/480/3
SCR CONTROL -
100% 100%59% 60%
12MEDIUM PRESSURE SUPPLY DUCTWORK +3.0" A
12 XRELIEF AIR DUCTWORK/PLENUM +1.5" B
X
2. KITCHEN HOOD EXHAUST DUCT SHALL BE CONTINUOUS WELDED SEAM LIQUID TIGHT. DUCT SHALL BE SLOPED NO LESS THAN0.25" PER 12" HORIZONTAL RUN. REFER TO SPECIFICATIONS FOR DUCT INSULATION.
-KITCHEN HOOD EXHAUST DUCTWORK -4.0" - 2
-DISHWASH/POT WASH EXHAUST DUCTWORK -2.0" -
PIPING SCHEMATICSH005
UNIT SHALL BE MOUNTED 18 INCHES AFF. BASIS OF DESIGN: Q-MARK "AWH" SERIES.1
1
PRE FILTER TYPE/SIZE/MERV PLEATED/2"/8 PLEATED/2"/8 PLEATED/2"/8
1
1
4900
NORTH KITCHENS
3RD FLOOR - NORTH
TRANE
1.5
3.9
10
FC/12
YES
6.4
425.12
0
80.0
0.73
6.33
28/2"
13.4, 2-WAY
CART./4"
9.72
1.47"
85/13
PLEATED/2"/8
6300
SOUTH KITCHENS
3RD FLOOR - SOUTH
TRANE
1.5
4.1
10
FC/15
YES
9.4
546.6
0
80.0
0.54
37/2"
17.2, 2-WAY
CART./4"
13.3
1.44"
85/13
PLEATED/2"/8
100% 100%
CONTROL DIAGRAMS
H006
CONTROL DIAGRAMS
H007
1
1
1
X
1
1
1 2
GENERAL NOTES
BY THE ARCHITECT.
COLOR TO BE SELECTED
CFM
FROM BOTTOM OF LOUVER
MOUNTING HEIGHT IS
MAX.APD.
UNIT FACEDIMENSIONS
W/H/D
NET FREE
TO FINISHED FLOOR/ROOF.
AREA (S.F.)MOUNTINGHEIGHT
SERVICE DUTYUNITNO.
VARIABLE FREQUENCY DRIVE BY H.C.1
1
1
FILTER TYPE/MERV
2 2
2.0
5.5
2 @ 25
PLENUM/27
YES (2)
37.5
542.3
30.0
55.00
0.095
36/2"
17, 2-WAY
38.5
732.4
1062.0
85.2/69.1
52/51.9
1.09
151/4"
71.3, 2-WAY
CART./12"
36.0
1.67"
85/13
PLEATED/2"/81 2
2
1
BASIS OF DESIGN: AIROLITE K6776
WALL/CEILING MOUNTING BRACKET SHALL BE PROVIDED WITH UNIT.
1 2
1 BASIS OF DESIGN: REZNOR "WS" SERIES.2
1
1
INFINITESCR CONTROL -
INFINITE
PLEATED/8 PLEATED/8
OUTDOOR AIR SHALL BE CONTROLLED BY CO2 SENSOR. REFER TO SPECIFICATIONS.
UNIT WEIGHT (lbs.) 7900 7900 1300 1600 4300 4800
1
1
2
2
2
2
2
2
2
2
2
2
2
2 BASIS OF DESIGN: Q-MARK "CDF" SERIES.
UNIT SHALL BE MOUNTED 8 FT. AFF. BASIS OF DESIGN: Q-MARK "MUH" SERIES.3
3
2
2
2
2
2
2
2
H108
H107
H106
H105
THIRD FLOOR PLAN - PIPING
SECOND FLOOR PLAN - PIPING
FIRST FLOOR PLAN - PIPING
BASEMENT FLOOR PLAN - PIPING
1
2
2
H008
CONTROL DIAGRAMS
H109 ENLARGED MECHANICAL ROOM PLAN
INTERNAL INTERNAL INTERNAL INTERNAL INTERNAL INTERNAL
3
3. WET EXHAUST DUCT SHALL BE CONTINUOUS WELDED SEAM LIQUID TIGHT. DUCT SHALL BE OF STAINLESS STEEL CONSTRUCTIONAND PITCHED BACK TO DRAIN.
UPSTREAM OF VAV BOXES
MUA'S, FC'S, & DOWNSTREAM OF VAV BOXES
AUTO. VALVE MIN. CV & TYPE
GPM/PIPE RUNOUT
MAX. WATER P.D.- FT.
MAX. AIR P.D. INCHES W.G.
LEAV. AIR (DEG. F.)
ENT. AIR (DEG. F.)
CAPACITY MBH
MIN. FACE AREA (SQ. FT) 10.0 12.5
94.4 153.4
55.0 55.0
75.0 75.0
0.15 0.15
0.25 0.37
6/1" 10/1.25"
2.8,2-WAY 4.7, 2-WAY
RE
HE
AT
CO
IL
3
3
1
1
1
1
1
1
1
1
DRAW THRU DRAW THRUDRAW THRUDRAW THRU
10.6 10.6 10.6
DRAW THRUDRAW THRU
6.336.33 6.33 6.33 6.33
SCHEDULESH002
3
BASIS OF DESIGN: MARS "HV" SERIES3
3
3
3
3
4
BASIS OF DESIGN: MARS "STD" SERIES3
H110 FIRST FLOOR RADIANT PIPING PLAN
1
1
1
3 3
FACE & BYPASS DAMPER.3
2
2
24LOCKER ROOM EXHAUST DUCTWORK -1.0" B 3X
1
FINAL FILTER CHARCOAL CHARCOAL - -- -
H009
SECTIONS & ELEVATIONS
1
1
1
1
2
2
H010
BUILDING H.W. PIPING SCHEMATIC
DESIGN TOTAL 20,000
SUPPLY FANS SIZED FOR 75%REDUNDANCY.
4
4 2 FANS @15,000DESIGN TOTAL 20,0004
1
H011
PIPING SCHEMATICS
PROVIDED UNDER BASE BID2 PROVIDED UNDER ALTERNATE #113
3
2
2
1
1
3
3
1
1
1
3
DUCT CONSTRUCTION, SEALING, & INSULATION
AIR SUPPLY UNITSLEGEND
SD
A
M
M
26/20
26"D
HWR
RL
RS
HWS
CHWS
5
D
CWS
CWR
MPS
LPC
MPC
LPS
CHWR
T
C
PRESSURE GUAGE
TEMPERATURE GAUGE OR THERMOMETER
P
UNION
CLEANOUT
STRAINER
EXPANSION JOINT
SAFETY RELIEF VALVE. FOR HYDRONIC SYSTEMS PIPE DISCHARGETO FLOOR DRAIN UNLESS NOTED OTHERWISE. FOR STEAMSYSTEMS PIPE DISCHARGE TO OUTDOORS.
THERMOSTAT. MOUNTING HEIGHT 46" TO MEET ADA REQUIREMENTS. WHENMOUNTED NEXT TO WALL SWITCH COORDINATE WITH ARCHITECT.
STRAINER WITH A BLOW DOWN VALVE AND HOSE CONNECTION
CHECK VALVE
SHUTOFF VALVE (REFER TO SPECIFICATIONS FOR REQUIRED TYPE
BASED ON APPLICATIONS.)
COMBINATION SHUTOFF AND BALANCING VALVE (REFER TO
SPECIFICATIONS FOR REQUIRED TYPE BASED ON APPLICATIONS.)
SHUTOFF VALVE (REFER TO SPECIFICATIONS FOR REQUIRED TYPE
BASED ON APPLICATIONS.)
THERMODYNAMIC STEAM TRAP AND DRIP ASSEMBLYTD
IBINVERTED BUCKET STEAM TRAP AND DRIP ASSEMBLY
FTFLOAT AND THERMOSTATIC STEAM TRAP AND DRIP ASSEMBLY
TSTHERMOSTATIC STEAM TRAP AND DRIP ASSEMBLY
BMBI-METALIC STEAM TRAP AND DRIP ASSEMBLY
10"� = NECK SIZE. 300 = REQUIRED CFM. ALL AIR DEVICE DISCHARGE4-WAY UNLESS NOTED WITH FLOW ARROWS. AIR DEVICE SHOWN IS 2-WAYSIDE THROW. METHOD OF IDENTIFICATION ALSO APPLIES TO OTHER CEILINGMOUNTED AIR DEVICES.
WALL OR DUCTWORK MOUNTED AIR DEVICE. SG1 = DESIGNATION (REFER TO AIR
DEVICE SCHEDULE). 20"X12" = DUCT CONNECTION SIZE. 200 = REQUIRED CFM.
9'-0" = MOUNTING HEIGHT FROM FLOOR TO BOTTOM OF GRILLE.
MANUAL BALANCING VALVE DAMPER WITH LOCKING DEVICE
AIR TERMINAL UNIT
T
CONCENTRIC PIPE REDUCER
MANUAL AIR VENT
AUTOMATIC AIR VENT
PRESSURE AND TEMPERATURE TEST PLUG
DETAIL: B = DETAIL DESIGNATION. H2 = SHEET WHERE DETAIL IS LOCATED.
SECTION: 1 = SECTION DESIGNATION. H2 = SHEET WHERE SECTION IS LOCATED.
EQUIPMENT REFERENCE. LETTER DESIGNATION VARIES. REFER TO SCHEDULES.OR H1
PLAN NOTE. APPLIES ONLY TO THE SHEET WHICH IT IS SHOWN UNLESS NOTEDOTHERWISE.
DETAIL NOTE. APPLIES ONLY TO THE ASSOCIATED DETAIL.
PRESSURE REDUCING VALVE
2 PORT AUTOMATIC CONTROL VALVE
3 PORT AUTOMATIC CONTROL VALVE
DUCT MOUNTED SMOKE DETECTOR FURNISHED AND INSTALLED BY OTHERS.COORDINATE LOCATION.
DRAIN VALVE WITH HOSE END CONNECTION
RECTANGULAR DUCTWORK DIMENSIONS (W X H)
ROUND DUCTWORK DIMENSIONS (DIA)
H1
2
3
B
H2
1
H2
HEATING HOT WATER SUPPLY PIPE
HEATING HOT WATER RETURN PIPE
CHILLED WATER SUPPLY PIPE
CHILLED WATER RETURN PIPE
CONDENSER WATER SUPPLY PIPE
CONDENSER WATER RETURN PIPE
STEAM SUPPLY PIPE - NUMBER INDICATES P.S.I.G.
REFRIGERANT LIQUID LINE
REFRIGERANT SUCTION LINE
DRAIN LINE. PITCH IN DIRECTION INDICATED
A-D FIRE DAMPER- A = TYPE. REFER TO DETAIL AND SPECIFICATIONS. D ORS = DYNAMIC OR STATIC
SDSMOKE DAMPER
FSCOMBINATION FIRE - SMOKE DAMPER
MEDIUM PRESSURE STEAM SUPPLY PIPE
LOW PRESSURE STEAM SUPPLY PIPE
LOW PRESSURE CONDENSATE RETURN PIPE
MEDIUM PRESSURE CONDENSATE RETURN PIPE
CO2 SENSOR. MOUNTING HEIGHT 46" TO MEET ADA REQUIREMENTS. WHENMOUNTED NEXT TO WALL SWITCH COORDINATE WITH ARCHITECT.
DATE ISSUEDPROJECT #
REVISIONS
# DATE DESCRIPTION
Heapy Engineering
Project No.
Enter address here
11
/10
/20
11 3
:40
:27
PM
C:\B
IM\M
ode
l\20
10-0
601
9-C
en
tra
l_JL
WE
TZ
EL.r
vt
H001
LEGEND & SCHEDULES
2010-06019 Nov. 11, 2011
MAPLE STREET DININGFACILITY
2010-06019
PERSONZONEUNIT
ROOM
1-1 101 - RED BRICK PIZZA 1 7.5 40 379 0.18 460 1310
20077101A - RED BRICK VESTIBULE1-2
80013526587.5101 - RED BRICK PIZZA 31-3
630100498105.0135 - BREAK ROOM1-4
1000299288257.5102 - DELI-SH 11-5
63014141957.5102 - DELI-SH 21-6
360281416207.5102 - DELI-SH 31-7
10051103A - PATISSERIE VESTIBLUE1-8
42017054557.5103 - PATISSERIE 21-9
1260581708457.5104 - ENCOUNTER 11-10
665530857367.5104 - ENCOUNTER 21-11
130010429447.5129 - ENCOUNTER KITCHEN1-12
10061105A - FIRST STOP VESTIBULE1-13
880561493487.5105 - FIRST STOP 21-14
10508281053637.5105 - FIRST STOP 31-15
205126123 - WOMENS ROOM1-16
205108
122 - FIRST STOP KITCHEN1-17
5003817945.0130 - PRODUCTION OFFICE1-18
4802618425.0128 - STUDENT MGR1-19
45017870827.5113A - NORTH KITCHEN 11-20
48013045437.5113A - NORTH KLITCHEN 21-21
0.18
0.06
0.18
0.18
0.18
0.18
0.18
0.18
0.18
0.18
0.18
0.06
0.06
0.18
0.18
18007240397 - NORTH MECHANICAL ROOM1-22
VENTILATION SCHEDULE AH-1
NO.OA CFM/
POPULTN.ZONE
(SQ. FT.)AREA
(CFM/SQ. FT.)O.A.
O.A.ZONE
SUPPLYACTUAL
CFM
945 865101 - RED BRICK PIZZA 2 7.5 4 0.18 250
6059138 - WOMENS ROOM
6079137 - MENS ROOM
6040134 - STAFF TOILET
10095102A - DELI-SH VESTIBULE
6058140 - WOMENS ROOM
6060139 - MENS ROOM
875283423207.5103 - PATISSERIE 1 0.18
1320278568167.5105 - FIRST STOP 1 0.18
124 - MENS ROOM
192021072357.5 0.18
150100131 - STORAGE
10065132 - STORAGE
10066133 - STORAGE
220181804-7.5113A - NORTH KLITCHEN 3 0.18
5059125 - STORAGE
5070126 - STORAGE
PERSONZONEUNIT
ROOM
2-1 106A - PACIFIC RIM VESTIBULE
7.5 47 722 0.18 603 1600
10047
106 - PACIFIC RIM 22-2
136021072757.5106 - PACIFIC RIM 32-3
1300778998597.5106 - PACIFIC RIM 42-4
108 - MENS ROOM2-5
1155457657337.5107 - AMERICAS 12-6
1120403665277.5107 - AMERICAS 22-7
2-8
166524675987.5107 - AMERICAS 52-9
410170338107.5107B - AMERICAS PRIVATE ROOM2-10
5002914235.0142 - RES. LIFE OFFICE2-11
100135
119 - BUSINESS OFFICE2-13
2802516125.0118 - MANAGER2-14
7506333565.0117 - ASST. MANAGER2-15
200570110 - RECEIVING2-16
22548
113B - SOUTH KITCHEN 12-17
1100297115247.5113B - SOUTH KITCHEN 22-18
19019096027.5113C - SOUTH KITCHEN 12-19
1610399690267.5107 - AMERICAS 32-20
0.18
0.18
0.18
0.18
0.18
0.18
0.06
0.06
0.06
0.18
0.18
0.18
VENTILATION SCHEDULE AH-2
NO.OA CFM/
POPULTN.ZONE
(SQ. FT.)AREA
(CFM/SQ. FT.)O.A.
O.A.ZONE SUPPLY
ACTUAL
CFM
1620399690267.5107 - AMERICAS 4 0.18
2802516425.0
121 - STAFF WC
0.06
111 - RECEIVING CLERK
133020675047.5 0.18
741 1200106 - PACIFIC RIM 1 7.5 30 0.18 448
255192
109 - WOMENS ROOM 330190
5070116 - STORAGE
5067142A - STORAGE
5084120 - STORAGE2-12
1170152115677.5141 - RESIDENTIAL LOBBY 0.06
1015.0 0.06
18007600398 - SOUTH MECHANICAL ROOM2-21
PERSONZONEUNIT
ROOM
FC-10-1 A218 - NORTH SUITE 800781
VENTILATION SCHEDULE DOAS-1
NO.OA CFM/
POPULTN.ZONE
(SQ. FT.)AREA
(CFM/SQ. FT.)O.A.
O.A.ZONE
SUPPLYACTUAL
CFM
7.5 14 0.06 190
FC-10-2 B218 - CENTRAL SUITE 8009187.5 14 0.06 200
A219 - KITCHEN 2001477.5 2 0.18 52
A220 - TRASH/RECYCLING 58 90
A221 - ACCESSIBLE RESTROOM 72 90
A222 - BATHROOM 174 180
A223 - BATHROOM 121 90
A224 - BATHROOM 114 90
A225 - BATHROOM 178 180
B219 - KITCHEN 2001277.5 2 0.18 47
B220 - BATHROOM 178 180
B221 - ACCESSIBLE RESTROOM 83 90
B222 - BATHROOM 86 90
B223 - BATHROOM 88 90
B224 - BATHROOM 174 180
B225 - TRASH/RECYCLING 75 90
299 - CORRIDOR 1 1403 580
299 - CORRIDOR 2 305 100
299 - CORRIDOR 3 305 190
302 - MENS ROOM 81 65
303 - WOMENS ROOM 125 90
399 - CORRIDOR 539 200
PERSONZONEUNIT
ROOM
FC-3 305 - STUDY 200133
VENTILATION SCHEDULE DOAS-2
NO.OA CFM/
POPULTN.ZONE
(SQ. FT.)AREA
(CFM/SQ. FT.)O.A.
O.A.ZONE SUPPLY
ACTUAL
CFM
5.0 6 0.06 47
FC-4 304A - LIVING/DINING 7354125.0 2 0.06 43
304B - MASTER BR 1702645.0 1 0.06 26
304C - SECOND BR 1201425.0 1 0.06 17
304D - BATHROOM 6592
304E - BATHROOM/LAUNDRY 22061
FC-5 300 - MULTI-PURPOSE ROOM 200018615.0 30 0.06 327
FC-6-1 202 - STUDY 5003305.0 8 0.06 75
FC-6-2 203 - STUDY 5003165.0 8 0.06 74
FC-7 204 - LAUNDRY ROOM 6002137.5 2 0.06 35
FC-10-3 C218 - SOUTH SUITE 8008287.5 14 0.06 193
FC-11 B08 - LAUNDRY 1300153
FC-12 B04 - REFRIG. EQUIPMENT 535344
B01 - RES. LIFE STORAGE 2501287
B05 - DINING STORAGE 100267
B06 - MENS LOCKER ROOM 280473
B07 - WOMENS LOCKER ROOM 280481
B11 - SECURITY 5019
B99 - CORRIDOR 4001353
201 - RESIDENTIAL LOBBY 67514377.5 6 0.06 164
299 - CORRIDOR 4 220243
299 - CORRIDOR 5 3601266
C219 - KITCHEN 2001697.5 2 0.18 57
C221 - ACCESSIBILE BATHROOM 9072
C222 - BATHROOM 180186
C223 - BATHROOM 90140
C224 - BATHROOM 90145
C225 - BATHROOM 180168
-- -
60
60
-- -
60-- -
60-- -
60-- -
-- -
-- -
205
205
-- - 255
330-- -
-- - 100
90
90
180
90
90
180
180
90
90
90
180
90
65
90
A226 - JANITORS CLOSET 50 90
205 - JANITORS CLOSET 70 65
70
B04 - JANITORS CLOSET 115128
C226 - JANITORS CLOSET 5031
GRAVITY ROOF VENTILATORS
STEEL FRAMING AROUND ROOF OPENINGS, WHERE REQUIREDFOR DECK SUPPORT, TO BE PROVIDE BY GEN. CONT'R.
NECK SIZES ARE APPROXIMATE. VERIFY SIZE & COORDINATEROOF OPENING REQUIREMENTS WITH GEN. CONT'R.
DESCRIPTIONUNITNO.
GENERAL NOTES:
CFMSERVICE NECK SIZE/STATICPRESS.
MAX.
ROOF OPG.
APPROX.
HEIGHTCURB
(INCL.CURB)HEIGHTAPPROX.
REMARKS
V-1 ELEVATOR HOISTWAY VENTING 3200ELEV 1 - 399 .02 52x52 12" 34" DO NOT PROVIDE DAMPER
EQUIPMENT DATA
H-3 (2) HOT WATER CONVERTER - SHELL & TUBE TYPE - TYPICAL OF TWOCAPACITY: HEAT 500 GPM OF WATER FROM EWT 110 DEG. TO LWT 140 DEG. THRU TUBES, WITHMAXIMUM 5 FT. OF HEAD PRESSURE DROP, WITH 15 PSIG STEAM IN THE SHELL.MINIMUM 137 SQ. FT. HEATING SURFACE AREA.FOULING FACTOR: 0.0007APPROX. DIM.: 14" DIA. x 57" LONGBASIS OF DESIGN: B&G
H-4 AIR SEPARATOR (HOT WATER SYSTEM)
H-5 EXPANSION TANK - DIAPHRAGM TYPE
H-6 HOT WATER (BUILDING) SYSTEM FILTER FEEDER
INLINE TYPE COMBINATION AIR & DIRT SEPARATOR
H-7 AUTOMATIC WATER MAKE-UP ASSEMBLY-HOT WATERPROVIDE SHUTOFF VALVE, STRAINER, UNION, PRESSURE REDUCING VALVE SETAT 30 PSIG (ADJUSTABLE), UNION, SAFETY RELIEF VALVE SET AT 75 PSIG, ANDSHUTOFF VALVE, AT 0.75" SIZE. PROVIDE 0.75" BYPASS WITH GLOBE VALVE.
H-8 SPLIT SYSTEM - COOLING ONLYINDOOR UNIT:CAPACITY: 17.2 MBH TOTAL, 12.2 MBH SENSIBLEINDOOR: 80 DEG. F. DB, 67 DEG. F. WBOUTDOOR: 95 DEG. F. DB, 75 DEG. F. WBAIRFLOW: 275 CFM-LISTED @ LOW FAN SPEEDFAN: 0.76 FLA, ELECTRIC: 1.0 MCA @ 208V,1 PHASEWEIGHT: 22 lbs.
OUTDOOR UNIT:CAPACITY: 1.5 TONSFAN: 0.93 FLA, ELECTRIC: 14 MCA, 15 MOCP @ 208V, 1 PHASEWEIGHT: 119 lbs.REFRIGERANT PIPE: 0.25"O.D. LIQUID, 0.5"O.D. SUCTIONUNIT SHALL HAVE LOW AMBIENT CONTROL, AND FAN SPEED WITH REMOTETHERMOSTAT.DISCONNECT BY E.C.BASIS OF DESIGN: MITSUBISHI - MSY
H-10 HEAT PUMP CHILLER: PACKAGED, HEAT RECOVERY HEAT PUMP CHILLER
CHILLED WATER PERFORMANCE: 169,000 BTUH OF COOLING, WITH 13 GPM OFWATER FLOW, ENTERING AT 70 DEGREES F. AND LEAVING AT 44 DEGREES F.MAXIMUM PRESSURE DROP SHALL BE 5 FT. HD.
CONDENSER WATER PERFOMANCE: 249,000 BTUH OF HEAT REJECTION, WITH25 GPM OF WATER FLOW, ENTERING AT 120 DEGREES F. AND LEAVING AT 140DEGREES F. MAXIMUM PRESSURE DROP 5 FT. HD.
POWER REQUIREMENT: UNIT MCA 38.0, 460 VOLT/3 PHASE.
BASIS OF DESIGN MULTISTACK MS15. REFER TO SPECIFICATION SECTION 23 7001 FOR COMPLETE REQUIREMENTS. EQUIPMENT PART OF ALTERNATE #11.
H-11 CONDENSER WATER EXPANSION TANK: HORIZONTAL BLADDER STYLECAPACITY: 21 GALLONS MINIMUMACCEPTANCE VOLUME: 11 GALLONS MINIMUMAIR PRESSURE: 10 PSIGAPPROX. DIMENSIONS: 16” DIA. X 29” LONG.
H-12 CONDENSER WATER AUTOMATIC WATER MAKEUP ASSEMBLY. PROVIDESHUTOFF VALVE, STRAINER UNIONS, PRESSURE REDUCING VALVE SET FOR 10PSIG (ADJUSTABLE), UNION, SHUTOFF VALVE AND SAFETY RELIEF VALVE SET AT50 PSIG, ALL 0.75” SIZE. PROVIDE0.75” BYPASS WITH GLOBE VALVE.
H-13 AIR SEPERATOR, CONDENSER WATER SYSTEM: INLINE, COMBINATION AIRAND DIRT SEPERATOR.FLOW RATE: 20 GPMLINE SIZE: 2”MAX PRESSURE DROP: 3 FT. HD AT SPECIFIED FLOW RATEAPPROXIMATE DIMENSIONS: 6” DIA. X 25” TALLSPIROTHERM VDT-1A OR APPROVED EQUAL
H-14 CHEMICAL SHOT FEEDER, CONSENSER WATER (KITCHEN) SYSTEM FEEDERSIZE 1 GALLON, WITH SHUTOFF VALVES ON INLET, OUTLET AND DRAIN.
FLOW RATE: 500 GPMLINE SIZE: 8”MAX PRESSURE DROP: 2 FT. HD AT SPECIFIED FLOW RATEAPPROXIMATE DIMENSIONS: 16” DIA. X 52” TALLSPIROTHERM VDN-800-FL OR APPROVED EQUAL
SIZE 5 GALLON, WITH SHUTOFF VALVES ON INLET, OUTLET AND DRAIN.
H-15 DOMESTIC HOT WATER HEATER CONDENSATE PUMPDUPLEX TYPE WITH 14 GALLON RECEIVER.CAPACITY: 12,000 EDR WITH 12 GPM AT 25 PSI DISCHARGEMOTOR: 0.5 HP- 120 VOLT- 1 PHASE, 3500 RPM
H-16 BUILDING SYSTEM CONDENSATE PUMPDUPLEX TYPE WITH 52 GALLON RECEIVER.CAPACITY: 45,000 EDR WITH 45 GPM AT 30 PSI DISCHARGEMOTOR: 1.5 HP- 460 VOLT- 3 PHASE, 3500 RPM
ITT DOMESTIC SERIES CC
ITT DOMESTIC SERIES CB
H-18 SPLIT SYSTEM - COOLING ONLYINDOOR UNIT:CAPACITY: 9.0 MBH TOTAL, 7.38 MBH SENSIBLEINDOOR: 80 DEG. F. DB, 67 DEG. F. WBOUTDOOR: 95 DEG. F. DB, 75 DEG. F. WBAIRFLOW: 170 CFM-LISTED @ LOW FAN SPEEDFAN: 0.76 FLA, ELECTRIC: 1.0 MCA @ 208V,1 PHASEWEIGHT: 22 lbs.
OUTDOOR UNIT:CAPACITY: 0.75 TONSFAN: 0.50 FLA, ELECTRIC: 12 MCA, 15 MOCP @ 208V, 1 PHASEWEIGHT: 66 lbs.REFRIGERANT PIPE: 0.375"O.D. LIQUID, 0.25"O.D. SUCTIONUNIT SHALL HAVE LOW AMBIENT CONTROL, AND FAN SPEED WITH REMOTETHERMOSTAT.DISCONNECT BY E.C.BASIS OF DESIGN: MITSUBISHI - MSY
PRS-1 PRESSURE REDUCING STATION #1 - 110 PSI TO 15 PSI2.5" X 4" SR VALVE @ 20 PSI, STRAINER, UNION, ECCENTRICREDUCER. PRESSURE REDUCING VALVE AT 3340 LBS/HR.,1.5" SIZE AND DIFFRACTOR NEEDLE VALVE, NOISE DIFFUSERS,PRESSURE GAGES UPSTREAM. REFER TO DETAIL.
PRS-2 PRESSURE REDUCING STATION #2 - 110 PSI TO 15 PSI4" X 6" SR VALVE @ 20 PSI, STRAINER, UNION, ECCENTRICREDUCER. PRESSURE REDUCING VALVE AT 6685 LBS/HR.,2.5" SIZE AND DIFFRACTOR NEEDLE VALVE, NOISE DIFFUSERS,PRESSURE GAGES UPSTREAM. REFER TO DETAIL.
CAPACITY: 68 GALS.ACCEPTANCE VOLUME: 34 GALS.APPROXIMATE SIZE: 24" DIA. X 48" HIGHWORKING PRESSURE: 150 PSIAMTROL AX-120V
C-1 AIR SEPARATOR (CHILLED WATER SYSTEM)INLINE TYPE COMBINATION AIR & DIRT SEPARATORFLOW RATE: 525 GPMLINE SIZE: 8"MAX. PRESSURE DROP: 2 FT. HD. AT SPECIFIED FLOW RATEAPPROXIMATE DIMENSIONS: 16"DIA. x 52" TALLSPIROTHERM VDN-800-FL OR APPROVED EQUAL.
EQUAL TO NEPTUNE FTF-5DB
C-2 EXPANSION TANK - DIAPHRAGM TYPECAPACITY: 8 GALS.ACCEPTANCE VOLUME: 2.4 GALS.APPROXIMATE SIZE: 12" DIA. X 20" HIGHWORKING PRESSURE: 150 PSIAMTROL AX-15V
H-19 AIR COOLED FLUID COOLERCAPACITY: 250 MBH AT 53 GPM FROM 80 DEG F EWT TO 70 DEG F LWT AT60 DEG F AMBIENT TEMPERATURE WITH 30% GLYCOL.MOTOR: 6 FANS EACH AT 0.25 HP, 460V-3PH, SINGLE-POINT POWER CONNECT.CONTROLS: 120V-1PHMOUNT ON TYPE A1 VIBRATION ISOLATORS AND EQUIPMENT SUPPORTRAIL.
H-20 HEAT EXCHANGER - PLATE AND FRAMECOLD SIDE CAPACITY: 50 GPM (WATER) WITH 45 DEG F EWT TO 55 DEG F LWT15 FTHD PRESSURE DROPHOT SIDE CAPACITY: 53 GPM (30% E.G.) WITH 80 DEG F EWT TO 70 DEG F LWT20 FTHD PRESSURE DROP
H-21 ETHYLENE GLYCOL FEED SYSTEM30% GLYCOL BY VOLUME, FACTORY MIXEDGLYCOL MANUFACTURER SPECIFIED IN SECTION 23 21 17.PROVIDE PORTABLE DRUM PUMP, 120V-1PH WITH 16 FT POWER CORD AND PLUGPUMP CLEAR WATER CAPACITY: 20 GPM AT 20 FTHDDRUM SHALL BE MOUNTED ON 4" HOUSEKEEPING PAD
PROVIDE REMOVABLE INSULATED BOARD CASING WITH PROTECTIVE METALJACKET
DATE ISSUEDPROJECT #
REVISIONS
# DATE DESCRIPTION
Heapy Engineering
Project No.
Enter address here
11
/10
/20
11 3
:12
:27
PM
C:\B
IM\M
ode
l\20
10-0
601
9-C
en
tra
l_JL
WE
TZ
EL.r
vt
H002
SCHEDULES
2010-06019 Nov. 11, 2011
MAPLE STREET DININGFACILITY
2010-06019
B
H003
A
H003
C
H003
E
H003
F
H003
K
H003
L
H003
M
H003
D
H003
G
H003
I
H003
J
H003
N
H003
H
H003
NECK SIZE, SEE SCHEDULE
7
8
5
4
1
6
2
3
6
4
7
8
7
6
5
4
3
2
1 BASE MOUNTED END SUCTION CENTRIFUGAL PUMP WITH
FLANGED PIPE CONNECTIONS.
CONCRETE BASE.
SUCTION DIFFUSER WITH INTEGRAL FINE MESH START-UP
STRAINER AND ADJUSTABLE SUPPORT. REMOVE MESH
AFTER PIPING IS CLEANED.
SPHERICAL FLEXIBLE PIPE CONNECTOR.
PRESSURE GAUGE WITH INTERCONNECTING PIPING AND
VALVES.
PIPE REDUCER WHEN PIPE SIZE DIFFERS FROM PUMP
CONNECTION SIZE.
SPRING HANGER.
BALANCING VALVE, SIZED FOR 3 TO 5 FT. HD. WPD AT FULLPUMP GPM. PROVIDE REDUCERS IN AND OUT. FOR PUMPS
FITTED WITH AN ADJUSTABLE FREQUENCY MOTORCONTROLLER LEAVE THE BALANCING VALVE FULL OPEN.
FLOOR
10
10
6
6
5
7
8
5
946321
9
8
7
5
4
3
2
1 CONICAL SPIN-IN BRANCH TAP FITTING, STRAIGHT SIDE.INTEGRAL INSULATION GUARD SLEEVE REQUIRED FOR
TAP FITTING TO MAIN SUPPLY DUCT WITH INTERNALINSULATION.
ROUND SHEET METAL BRANCH DUCT, SAME SIZE AS AIRTERMINAL UNIT INLET SIZE UNLESS NOTED OTHERWISE.
INSULATED FLEXIBLE DUCT. 4 FT. MAXIMUM LENGTH.STRETCH FLEXIBLE DUCT TO 90% OF FULLY EXTENDED
LENGTH.
AIR TERMINAL UNIT.
MINIMUM FOUR STRAP HANGERS FOR UNIT (CORNERPOINTS). ATTACH TO STRUCTURE.
TRANSITION WHEN REQUIRED.
MINIMUM STRAIGHT LENGTH OF DUCT SHALL BE
TERMINAL UNIT MANUFACTURER'S REQUIRED
LENGTH, BUT AT LEAST 2.0 TIMES UNIT INLETDIAMETER.
STRAP HANGER. ATTACH TO STRUCTURE.
DUCT SHALL BE FULL SIZE OF UNIT OUTLET
UNLESS NOTED OTHERWISE ON FLOOR PLANS.
REHEAT COIL WHEN SPECIFIED. REFER TO COIL
DETAIL.
SQUARE-TO-ROUND ADAPTER IF DIFFUSER NECK ISSQUARE.
INSULATED FLEXIBLE DUCT SAME DIAMETER AS BRANCH
DUCT , 7 FT. MAXIMUM TOTAL LENGTH PER AIRDEVICE. STRETCH FLEXIBLE DUCT TO AT LEAST 90% OF
FULLY EXTENDED LENGTH.
SPIN-IN BRANCH TAP FITTING, STRAIGHT SIDE WITHMANUAL DAMPER. DAMPER SHAFT IN HORIZONTAL.INTEGRAL INSULATION GUARD SLEEVE REQUIRED FOR
TAP FITTING TO MAIN DUCT WITH INTERNAL INSULATION,AND EXTENDED DAMPER SHAFT AND HANDLE WITH
STAND-OFF TO ACCOMMODATE EXTERNAL INSULATION.
DUCT STRAP HANGER. ATTACH TO STRUCTURE.
STRAP HANGER REQUIRED IF LENGTH OF FLEXIBLE DUCTIS LONGER THAN 4 FT.
MINIMUM CENTERLINE RADIUS EQUAL TO DUCTDIAMETER.
ROUND SHEET METAL BRANCH DUCT, SAME SIZE ASDIFFUSER INLET UNLESS NOTED OTHERWISE.
FLEXIBLE DUCT ELBOW SUPPORT, INSTALLED WITHNYLON BANDING PER MANUFACTURER'S INSTRUCTIONS.
A RADIUS'D SHEET METAL ELBOW MAY BE USED IN LIEU
OF A FLEXIBLE ELBOW SUPPORT WHEN CONNECTEDDIRECTLY TO AIR DEVICE.
CEILING T-BAR SUPPORT (FOR LAY-IN APPLICATIONS).
COORDINATE WITH CEILING CONTRACTOR AND VERIFYT-BAR TYPE FOR COMPATIBILITY WITH DIFFUSER.
8
44 34
5
6
9
827
10
1
6
10
9
8
7
6
5
4
7
3
2
1
8
7
6
5
4
2 65 3 7 5
4
8
1
3
7
3
2
1
ROUND SHEETMETAL BRANCH DUCT
BRANCH CFM RD. DUCT SIZE
0 TO 80 CFM 6"D
81 TO 120 CFM 7"D
121 TO 200 CFM 8"D
201 TO 400 CFM 10"D
401 TO 700 CFM 12"D
701 TO 1000 CFM 14"D
SHEET METAL PLENUM, FULL SIZE OF GRILLE NECK,
MINIMUM 4" TALLER THAN DUCT RUNOUT SIZE, WITH SAME
INTERNAL OR EXTERNAL INSULATION AS RETURN OREXHAUST DUCT.
FLEXIBLE DUCT, SAME DIAMETER AS BRANCH DUCT ,7 FT. MAXIMUM TOTAL LENGTH PER AIR DEVICE. STRETCH
FLEXIBLE DUCT TO AT LEAST 90% OF FULLY EXTENDED
LENGTH.
SPIN-IN BRANCH TAP FITTING, STRAIGHT SIDE WITH
MANUAL DAMPER. DAMPER SHAFT IN HORIZONTAL.INTEGRAL INSULATION GUARD SLEEVE REQUIRED FOR TAP
FITTING TO MAIN DUCT WITH INTERNAL INSULATION.
EXTENDED DAMPER SHAFT AND HANDLE WITH STAND-OFFREQUIRED FOR EXTERNALLY INSULATED DUCTWORK.
SPIN-IN TAP FITTING SIMILAR TO EXCEPT NO
DAMPER.
DUCT STRAP HANGER. ATTACH TO STRUCTURE.
STRAP HANGER REQUIRED IF LENGTH OF FLEXIBLE
DUCT IS LONGER THAN 4 FT.
ROUND SHEET METAL BRANCH DUCT, SIZE AS
INDICATED IN ADJACENT SCHEDULE UNLESS NOTEDOTHERWISE ON PLANS.
CEILING T-BAR SUPPORT (FOR LAY-IN APPLICATIONS).COORDINATE WITH CEILING CONTRACTOR AND
VERIFY T-BAR TYPE FOR COMPATIBILITY WITH GRILLE.
6
7
5
3 1 3 2
4
3
1
7
6
5
4
3
2
1 45 DEGREE STATIC BOOT AND MANUAL DAMPER. INTEGRALINSULATION GUARD SLEEVE REQUIRED WHEN MAIN DUCT HAS
INTERNAL INSULATION. EXTENDED DAMPER SHAFT AND
HANDLE WITH STAND-OFF REQUIRED FOR EXTERNALLYINSULATED DUCTWORK.
SHEET METAL DUCT, SIZE AS NOTED ON PLANS.
DUCT STRAP HANGER.
STATIC BOOT SIMILAR TO EXCEPT NO DAMPER.
SHEET METAL DUCT, FULL SIZE OF GRILLE NECK SIZE.
FLEXIBLE DUCT CONNECTOR.
CEILING T-BAR SUPPORT (FOR LAY-IN APPLICATIONS).
COORDINATE WITH CEILING CONTRACTOR AND VERIFY T-BAR
TYPE FOR COMPATIBILITY WITH GRILLE.
4
431
2
531
2
5
4
3
2
1 DRAIN PIPE, SAME SIZE AS UNIT DRAIN PAN
CONNECTION.
VERIFY REQUIRED HEIGHT FOR DRAIN PIPE AND
TRAP INSTALLATION. PROVIDE ADDITIONAL
BEAMS OR BACK-TO-BACK CHANNELS UNDERUNIT, IF REQUIRED, TO ATTAIN REQUIRED HEIGHT.
TEE WITH CLEANOUT PLUG.
4" MINIMUM - CENTERLINE TO CENTERLINE.
CENTERLINE DIMENSION NOT LESS THAN SUPPLY
FAN T.S.P. (INCH W.G.) + 2".
GENERAL NOTES
A. FIRE DAMPERS SHALL BE UL LABELED.
B. INSTALLATION OF FIRE DAMPERS AND ACCESSORIES SHALL CONFORM TO NFPA 90A, SMACNA AND MANUFACTURER'S INSTRUCTIONS.
C. DETAILS SHOW INSTALLATION OF FIRE DAMPER IN WALL. DAMPER INSTALLATION IN FLOOR SIMILAR. ACCESS
LOCATIONS SHALL BE COORDINATED WITH ARCHITECT AND GENERAL TRADES CONTRACTOR.
D. INSULATE RETAINING ANGLES FOR SYSTEMS REQUIRED TO BE INSULATED.
FIRE DAMPER, FOLDED BLADE CURTAIN TYPE, EXCEPT AS NOTED. VERTICAL MOUNT, GRAVITY DROP; HORIZONTALMOUNT, SPRING LOADED TO CLOSE. REFER TO SPECS FOR VELOCITY LIMITATIONS OF EACH TYPE. REFER TO
DRAWINGS FOR STATIC OR DYNAMIC REQUIREMENTS. TYPE "A" - BLADES STORED IN AIR STREAM. RECTANGULAR, ROUND OR OVAL DUCT CONNECTION.
TYPE "B" - BLADES STORED OUT OF AIR STREAM. RECTANGULAR, ROUND OR OVAL DUCT CONNECTION.
SHEET METAL WALL SLEEVE, SAME MATERIAL AS DUCT (EXCEPT GALVANIZED SHEET METAL FOR FIBERGLASS
DUCT). SHEET METAL GAUGE PER SMACNA. USE EXTENDED HEAVY GAUGE SLEEVES WHEN INSTALLED CONDITION REQUIRES.
DUCT/SLEEVE CONNECTION. BREAKAWAY TYPE SHOWN. CONNECTION MAY BE RIGID TYPE IF ALLOWED BY CODE
AUTHORITY.
RETAINING ANGLE ALL FOUR SIDES, GAUGE PER SMACNA. 1" MINIMUM OVERLAP OF WALL OPENING. LONGER LEGMAY BE REQUIRED TO ATTAIN REQUIRED OVERLAP. BOLT, SCREW OR TACK WELD TO WALL SLEEVE. SPACING OF
FASTENERS PER SMACNA.
DUCT ACCESS PANEL OR DOOR. REFER TO SPECIFICATIONS.
CEILING ACCESS PANEL IF CEILING IS NOT ACCESSIBLE.
DUCT EXTENSION ATTOP OF DAMPER
FIRE RATED WALLOR PARTITION
FIRE RATED WALLOR PARTITION
6
2
44
3
1
3
5
6
244
3
1
3
5
1
2
3
4
5
6
1
2
3
4
1
2 3
4
TYPE "A"
DUCT
3" MINIMUM 3" MINIMUM
DUCT
TYPE "B"
NOMENCLATURE
MOTOR HOUSING
ELECTRICAL CONDUIT GUIDE
WOOD NAILING STRIP
PREFABRICATEDROOF CURB
CURB CAP
SEE NOTE #1
SEE NOTE #2
ROOFSEE NOTE #2
RIGID CONDUIT TO
ACCOMMODATE
ELECTRICAL WIRES
MOTORIZED BACKDRAFT
DAMPER
TRANSITION DUCT
TO FULL SIZE OF DAMPER
SUPPLIED WITH ROOF VENTILATOR
DUCT
NOTES :
1 SECURE CURB CAP TO WOOD NAILING STRIP WITH 3/8" CADMIUM PLATED LAG
BOLTS NOT OVER 12" ON CENTER
2 SECURE ROOF CURB, DUCT AND DAMPER TO ROOF WITH EXPANSION BOLTS
(CONCRETE ROOF) OR RUST RESISTANT BOLTS (METAL DECK AND BAR JOIST ROOF).
3 SIZE OF DUCT THROUGH ROOF SHALL NOT BE LARGER THAN CURB SUPPLIED
WITH ROOF VENTILATOR.
4 RUN ELECTRIC LINES THROUGH CLEARANCE HOLE PROVIDED IN GRAVITY DAMPER,
THEN THROUGH VENTILATOR ELECTRICAL CONDUIT GUIDE.
UPBLAST EXHAUST FANSCALE: NONE
5" CONCRETE PAD REINFORCED WITH WELDED WIRE FABRIC 6x6 - W2.9 x W2.9.
IN EACH DIRECTION (NOT INCLUDING PERIMETER CURB) AND SHALL BE SET ON KINETICS NOISE CONTROL
ISOLATION BOARD SHALL BE 3/4" THICK RESILIENT MATERIAL AS RECOMMENDED BY THE MANUFACTURER.PADS, & SHALL COVER A MINIMUM OF 95% OF THE AREA BETWEEN THE ISOLATION PADS. PERIMETERDENSITY FIBERGLASS ABSORPTION MATERIAL, WITH AN NRC RATING OF .87, SHALL BE BONDED TO THE ISOLATIONPADS SHALL BE 2" THICK AND BE SPACED AS RECOMMENDED BY THE MANUFACTURER. 1-1/2" THICK LOWDENSITY MOLDED FIBERGLASS PADS INDIVIDUALLY COATED WITH A FLEXIBLE ELASTOMERIC MEMBRANE. ISOLATIONTHE KINETICS MODEL RIM FIBERGLASS ISOLATION MAT SHALL CONSIST OF HIGH& EDGES CLEANED. SEAL EXPOSED EDGE OF RIM MAT WITH PERIMETER
MODEL RIM FIBERGLASS ISOLATION MAT. OR EQUAL BY VIBRATION ELIMINATOR, KORFUND OR AMBER/BOOTH CO..
HOUSEKEEPING PADS FOR AIR HANDLING UNIT EQUIPMENT SHALL BE 4" WIDER THAN THE AIR HANDLING EQUIPMENT
654
PROVIDE #5 REBAR DOWELS & EPOXY INTO SLAB AND CURB AT 24" ON CENTER.
6" WIDE CONCRETE PERIMETER CURB, REINFORCED WITH 6 X 6 #10 W.W.F.
SILICON CAULK AROUND ENTIRE PERIMETER.
KINETICS ISOLATION MAT MODEL RIM WITH ISOLATION PADS &
2" ISOLATION PADS SPACED PER MANUFACTURER'S RECOMMENDATIONS.
1/2" PLYWOOD POURING FORM.
PERIMETER ISOLATION BOARD
(2) LAYERS 6 MIL POLYETHYLENE
8
9
FIBERGLASS INFILL.6
7
5
4
1
3
2
8
AHU HOUSEKEEPING PADS
12
3 87
9
ALL CONCRETE FLASHING FROM PAD TOWARD FLOOR OVER EXPOSED EDGE OF RIM MAT SHALL BE REMOVEDISOLATION BOARD & CAULK.
AIR HANDLER HOUSEKEEPING PADSCALE: NONE
BASE MOUNTED PUMPSCALE: NONE
AIR TERMINAL UNIT DUCT CONNECTIONSCALE: NONE
SUPPLY DUCT
TO AIR DEVICES
CEILING DIFFUSER DUCT CONNECTIONSCALE: NONE
SUPPLY DUCT
CEILING DIFFUSERCEILING
RETURN/EXHAUST DUCT
RETURN ORCEILINGEXHAUST GRILLE
RETURN/EXHAUST GRILLE DUCT CONNECTION - 2ND FLOORSCALE: NONE
RETURN/EXHAUST DUCT
RETURN ORCEILINGEXHAUST GRILLE
6" MAX.
RETURN/EXHAUST GRILLE DUCT CONNECTIONSCALE: NONE
A.H. UNIT
A.H. UNIT
TRAP
FLOOR DRAIN
TRAP
FLOOR DRAIN
DRAW-THRU UNIT
BLOW-THRU UNIT
AIR HANDLING UNIT DRAIN PIPING
SCALE: NONE
FLOOR MOUNTED
1" C TO CL L
OF DUCT IN THE FIRST 20'.
DUCT TO 20' BEYOND PLENUM
ALL PLENUM JOINTS TO BE WATER
WELDED STAINLESS STEEL DRAINPAN
WHERE STAINLESS STEEL CONNECTS TO
CONTINUE SLOPE TO DRAINABLE LOUVER,
SEAMS SHOULD NOT BE AT THE BOTTOM
GALVANIZED COMBINE WITH DISSIMILAR
DUCTWORK/PLENUM TO BE HEAVILY CAULKEDAT SEAMS ON INSIDE. SEAL OUTSIDE SEAMSWITH EXTERIOR GRADE HARDCAST.
SLOPE DRAIN PAN - 1/4" PER 1'
DUCTWORK AND/OR PLENUM TO BE WRAPPED.
DRAIN TO BE INSULATED EQUAL TO STORMJANITOR'S SINK/MECHANICAL ROOM FLOOR
TIGHT(TYPICAL) MAINTAIN WATER TIGHT
DROP 1" COPPER DRAIN PIPE DOWN TO
10
5
METAL TAPE
8
9
7
6
LOUVER
TO DRAIN.
DRAINS.
3
4
1
2
9
HINGED ACCESS DOOR.
ELBOWS AND A TEE.TRAP TO BE ASSEMBLED FROM 90 DEG.
3/4" BRASS PLUG FOR CLEANOUT ACCESS.
13
12
11
11
7
FASTENER
12
3
64
13
8
10
LOUVER PLENUM
DUCTWORK
5
2
5
BIRD SCREEN
1
LOUVER PLENUM/DUCT DRAIN DETAILSCALE: NONE
AIR SOUND BOOT DUCT.INTERNALLY LINED RETURN
12"
AIR DEVICE
DUCT SIZE, SEE SCHEDULE
24x12
RETURN AIRDEVICE
24x24
TO PLENUM
SIZE
DUCT OPEN
22x10
22x12
NECK SIZE
22x8
22x12
DUCT SIZE
1ST FLOOR PLENUM RETURN AIR SOUND BOOTSCALE: NONE
FIRE DAMPER TYPE "A"SCALE: NONE
FIRE DAMPER TYPE "B"SCALE: NONE
4
58
NOTE: REFER TO DRAWINGS FOR LOCATION OF SMOKE DAMPERS APPLIES TO ALL AIR DUCTS WITH SMOKE DAMPERS AND
12
FA
11
10
FA
7
6
13
14
15
17
2
3
1
2'-0"
12"X12" HINGED & GASKETED ACCESS DOOR
PROVIDE 1/2" RIGID INSULATION ON BACK
SEAL AND CAULK TO PREVENT AIR LEAKAGE
SMOKE DETECTOR FURNISHED BY E.C. AND
WITH LATCH.
INSTALLED BY H.C.
OF DUCTWORK THAT IS INSULATED.
AT INSERTION HOLE.
HANGER BY E.C.
15
17
16
12
13
14
CEILING.
DUCT CONNECTOR-MINIMUM OF 1" OVERLAP ON
POWER SUPPLY AND WIRING BY E.C.
MOTOR HOUSING FOR MOTOR & CONTACTS
SEAL SPACE AROUND DAMPER FRAM. SEE SPECS.
(OUT OF AIR SPACE).
ALL SIDES OF DAMPER.
REMOTE TEST STATION BY E.C. WALL MOUNT
WIRING AND CONDUIT BY E.C.
NOT USED.
18 GA. SLEEVE 16" LONG.
SMOKE WALL.7
8
10
9
11
4
6
5
DUCT.
SMOKE DAMPER. SEE SPECS.2
1
3
16
AIR VELOCITIES GREATER THAN 400 FT./MIN.
NEAR DETECTOR AT 46" M.H.
SMOKE DAMPERSCALE: NONE
STEEL PLATE4"x4"x1/4"
LAG SCREW
WOOD NAILER
FIBERGLASS INSULATION
CONCRETE DECK
EXPANSION LAGS TO DECK.
7-1/2" MIN. - 9" MAX. HEIGHT
LEG. SCREW ATTACHMENT TO DECKEXTENDS 6" BEYOND LAST EQUIP.HEAVY GAUGE CONTINUOUS SUPPORT
COUNTER-FLASHING BY H.C.
INSULATION
ROOFING
ROOF EQUIPMENT SUPPORTSCALE: NONE
5 BACKDRAFT DAMPER SHALL NOT BE PROVIDED FOR FANS SERVING KITCHEN HOODS.
WHERE POSSIBLE.
NOTE: DETAIL APPLIES TO DRAINS FROM LOUVER PLENUMS OR DUCTS CONNECTED TO LOUVER. DUCT CONNECTION TO LOUVER AND LOUVER SHAPE IS NOT TYPICAL.
DATE ISSUEDPROJECT #
REVISIONS
# DATE DESCRIPTION
Heapy Engineering
Project No.
Enter address here
11
/10
/20
11 3
:12
:30
PM
C:\B
IM\M
ode
l\20
10-0
601
9-C
en
tra
l_JL
WE
TZ
EL.r
vt
H003
DETAILS
2010-06019 Nov. 11, 2011
MAPLE STREET DININGFACILITY
2010-06019
M
M M
G
H004
H
H004
A
H004B
H004
E
H004
F
H004
I
H004
J
H004
K
H004
K
H004
P
H004
M
H004L
H004
DH004
C
H004
OH004
A
~
~~
~
~
~
P
P
V
V
LPC
HW
S
HW
R
HW
S
HW
R
CND
CH
R
CH
S
HW
R
HW
S
~
~
~
M
MM
M
M
AIR LOADING PILOT
ALTERNATE
~
~
1
2
3
2
1
3
PIPE REDUCER IF COIL CONNECTION SIZEDIFFERS FROM PIPE SIZE.
0.75" CONDENSATE DRAIN PIPE. CONNECT TOUNIT PAN WITH FLEXIBLE POLYETHYLENE
TUBING.
FACTORY ASSEMBLED PIPING PACKAGE
(OPTIONAL).
2 WAY, 2 POSITION VALVE.
1 ALL PIPING SHALL BE FULL SIZE OF MAIN
RUN-OUT PIPING UNLESS NOTED OTHERWISE.
2 REFER TO EQUIPMENT SCHEDULE FOR
AUTOMATIC CONTROL VALVE SIZE.
GENERAL NOTES:
COOLING COIL
3
2
1
HEATING COIL
PIPE REDUCER IF COIL CONNECTION SIZE DIFFERSFROM PIPE SIZE.
INSULATE PIPING UP TO SHUT-OFF VALVE.
MAXIMUM DISTANCE FROM SHUT-OFF VALVE TO
COIL IS 48".
TRUE "T" FITTING (NOT A PORT OFF ANACCESSORY).
1 ALL PIPING SHALL BE FULL SIZE OF MAIN RUN-OUT PIPING
UNLESS NOTED OTHERWISE.
2 REFER TO EQUIPMENT SCHEDULE FOR AUTOMATIC CONTROL
VALVE SIZE. VERIFY VALVE PORTING AND CONNECT PIPINGTO PROPER PORTS, PER MANUFACTURER'S
RECOMMENDATIONS.
GENERAL NOTES:
1
7
7 2
4 3
5
5
6
7
6
5
4
3
2
1 FACTORY ASSEMBLED PIPING PACKAGE
(OPTIONAL).
PIPE REDUCER IF REQUIRED.
PIPE REDUCER/INCREASER IF COIL CONNECTION
SIZE DIFFERS FROM AUTO CONTROL VALVE SIZE.
PIPING SAME SIZE AS AUTO CONTROL VALVE OR
COIL CONNECTION, WHICH EVER IS LARGER.
6" MINIMUM LENGTH INCLUDES ANY REQUIRED
ELBOWS AND OFFSETS. INSULATE PIPING FROM
COIL TO UNION.
MAXIMUM DISTANCE FROM SHUT-OFF VALVE TO
COIL IS 48".
INSULATE PIPING UP TO SHUT-OFF VALVE.
0.5" DRAIN VALVE
A. ALL PIPING SHALL BE FULL SIZE OF MAIN RUN-OUT
PIPING UNLESS NOTED OTHERWISE.
B. REFER TO AIR TERMINAL UNIT SCHEDULE FOR
AUTOMATIC CONTROL VALVE SIZE.
GENERAL NOTES:
9
8
7
6
5
4
3
1
2
8
9
1
7
7 2
4 3
5
5
6 FACTORY ASSEMBLED PIPING PACKAGE
(OPTIONAL).
PIPE REDUCER IF REQUIRED.
PIPE REDUCER/INCREASER IF COIL
CONNECTION SIZE DIFFERS FROM AUTOCONTROL VALVE SIZE.
PIPING SAME SIZE AS AUTO CONTROL VALVEOR COIL CONNECTION, WHICH EVER IS
LARGER.
6" MINIMUM LENGTH INCLUDES ANY
REQUIRED ELBOWS AND OFFSETS. INSULATE
PIPING FROM COIL TO UNION.
MAXIMUM DISTANCE FROM SHUT-OFF VALVE
TO COIL IS 48".
INSULATE PIPING UP TO SHUT-OFF VALVE.
UNION OR SCREWED VALVE FITTING.
TRUE "T" FITTING (NOT A PORT OFF ANACCESSORY).
0.5" DRAIN VALVE
A. ALL PIPING SHALL BE FULL SIZE OF MAIN RUN-OUT
PIPING UNLESS NOTED OTHERWISE.
B. REFER TO AIR TERMINAL UNIT SCHEDULE FOR
AUTOMATIC CONTROL VALVE SIZE. VERIFY VALVE
PORTING AND CONNECT PIPING TO PROPERPORTS, PER MANUFACTURER'S
RECOMMENDATIONS.
GENERAL NOTES:
HEATING COIL
GENERAL NOTES:1 ALL PIPING SHALL BE FULL SIZE OF MAIN
RUN-OUT PIPING UNLESS NOTED OTHERWISE.
2 REFER TO EQUIPMENT SCHEDULE FORAUTOMATIC CONTROL VALVE SIZE.
PIPE REDUCER IF COIL CONNECTION SIZE
DIFFERS FROM PIPE SIZE.
INSULATE PIPING UP TO SHUT-OFF VALVE.
MAXIMUM DISTANCE FROM SHUT-OFF VALVE TOCOIL IS 48".
2
1
4
4
PUMP WITH FLANGED CONNECTIONS.
SPRING HANGER.
TURNBUCKLE ADJUSTMENT.
BALANCING VALVE, SIZED FOR 3 TO 5 FT. HD. WPD ATFULL PUMP GPM. PROVIDE REDUCERS IN AND OUT. FOR
PUMPS FITTED WITH AN ADJUSTABLE FREQUENCYMOTOR CONTROLLER LEAVE THE BALANCING VALVEFULL OPEN.
REDUCER WHEN PUMP CONNECTION SIZE DIFFERSFROM PIPE SIZE.
LEAVE SPACE TO ALLOW MOTOR TO BE PULLED.
DRAIN VALVE WITH HOSE CONNECTION.
PRESSURE GAUGE WITH INTERCONNECTING PIPING AND
VALVES.
1
2
3
4
5
6
7
8
1
22
3 4
5
6
77
8
DISCHARGEPUMP
STEAM MAIN (ABOVE 15 PSIG).
COLLECTING POCKET AND DIRT LEG SAMESIZE AS MAIN.
LENGTH FROM INVERT OF MAIN TO DRIP PIPE,1-1/2 X MAIN DIAMETER, 8" MINIMUM.
THERMODYNAMIC STEAM TRAP, 0.75" SIZEUNLESS NOTED OTHERWISE.
CONDENSATE RETURN, FULL SIZE OF TRAP
DISCHARGE, 0.75" MINIMUM.
0.75" BY-PASS WITH NORMALLY CLOSEDGLOBE VALVE.
1
2
3
4
5
6
6
2
54
3
1
N.C.
N.C.
P
CONDENSATE RECEIVER.
CONDENSATE PUMPS.
DISCHARGE PIPE CONNECTIONS WITH UNION,SPRING LOADED CHECK VALVE, GLOBEVALVE, AND SHUT OFF VALVE FOR EACHPUMP.
FULL SIZE VENT CONNECTION TO OUTDOORS.
CONCRETE BASE.
FULL SIZE DRAIN TO FLOOR DRAIN.
FULL SIZE OVERFLOW DRAIN, TRAPPED AND
VENTED AND PIPED TO FLOOR DRAIN.T
(SIMPLEX SIMILAR)
1
2
3
4
5
6
7
3
71
4
2 5 6
2"
ba
DRIP.
DATA FOR CAPACITY, SIZE, ETC.
1 PRESSURE REDUCING VALVE WITH PILOT AND
RELATED CONTROL TUBING. REFER TO EQUIPMENT
FULL SIZE DIRT LEG AND 3/4" STEAM MAIN
TAPER PIPE REDUCER.
CONTROL TUBING WITH NEEDLE VALVE.
SAFETY RELIEF VALVE. REFER TO EQUIPMENT DATAFOR APPROXIMATE SIZE AND DISCHARGE SETTING.EXTEND DISCHARGE PIPE (SAME SIZE AS
S.R.V. OUTLET) TO SAFE LOCATION.
DRIP PAN ELBOW. EXTEND 3/4" DRAIN PIPING.
PRESSURE GAUGE WITH COCK AND SIPHON
LOOP.
9" LONG NIPPLE SCREWED INTO DRIP PANELBOW AND INSERTED INTO RISER PIPE.
RISER PIPE ONE OR TWO PIPE SIZES LARGERTHAN S.R.V. DISCHARGE PIPE, PERMANUFACTURERS RECOMMENDATIONS.
SUPPORT RISER PIPE INDEPENDENT OF DRIP
STEEL BELLOWS TYPE WITH WOVEN WIRE
PAN ELBOW.
FLEXIBLE PIPE CONNECTOR, STAINLESS
REINFORCING JACKET.
UNION ON BOTH SIDES OF SCREWED END
VALVE REQUIRED IF BY-PASS REQUIRED.
HORIZONTAL (PITCH TO DRAIN) OR DOWN.
VALVE.
3
4
2
6
5
7
11
8
9
12
10
COMPRESSED AIR - 10 PSIABOVE REDUCED STEAMPRESSURE
5
AIR LOADING PILOTWITH FILTER
PIPEHANGER
TO OUTDOORSEXTERNAL STEAM PILOT
OUTLET
COND. RETURN
STRAIGHT PIPE LENGTH
1/2" - 1-1/2"
INLET
aVALVE SIZE
D
2" - 4"
4'-0"
24"MAX.
5" - 8"
3'-0"
1'-6"
b
3'-0"
4
6'-0"
P
8
5'-0"
5
3
83 P
1
1311
106
122
9
7
6
STEAM MAIN (15 PSIG AND BELOW).
F. & T. STEAM TRAP, 0.75" SIZE UNLESSNOTED OTHERWISE.
COLLECTING POCKET AND DIRT LEG SAMESIZE AS MAIN.
LENGTH FROM INVERT OF MAIN TO DRAIN
PIPE, 1-1/2 X MAIN DIAMETER, 8" MINIMUM.
CONDENSATE RETURN, FULL SIZE OF TRAPDISCHARGE, 0.75" MINIMUM.
1
2
3
4
5
3
2
4
1
5
12"MIN.
AUTOMATIC THREE-PORT CONTROL VALVE.NORMALLY OPEN THRU COIL.
0.5" DRAIN VALVE.
PIPE REDUCER IF COIL CONNECTION
DIFFERS FROM PIPE SIZE.
LEAVE WIDE OPEN UNLESS NEEDED TOEVENLY DISTRIBUTE FLOW THRU COILS OR
TO BALANCE PUMP GPM.
COIL RECIRCULATING PUMP.
WITH AUTOMATIC CONTROL VALVE IN FULLBYPASS, SET BALANCING VALVE TO MATCH
PRESSURE DROP THRU COIL.
A. ALL PIPING SHALL BE FULL SIZE OF MAIN RUN-OUTPIPING UNLESS NOTED OTHERWISE. BRANCH PIPING
TO EACH COIL ONE SIZE SMALLER THAN MAINRUN-OUT PIPING, BUT NO SMALLER THAN COILCONNECTION SIZE.
B. REFER TO AIR HANDLING UNIT SCHEDULE FORAUTOMATIC CONTROL VALVE SIZE. VERIFY VALVEPORTING AND CONNECT PIPING TO PROPER PORTS,
PER MANUFACTURER'S RECOMMENDATIONS.
AUTOMATIC TWO-PORT CONTROL VALVE.NORMALLY OPEN THRU COIL.
0.5" DRAIN VALVE.
PIPE REDUCER IF COIL CONNECTION
DIFFERS FROM PIPE SIZE.
LEAVE WIDE OPEN UNLESS NEEDED TOEVENLY DISTRIBUTE FLOW THRU COILS
OR TO BALANCE PUMP GPM.
COIL RECIRCULATING PUMP.
A. ALL PIPING SHALL BE FULL SIZE OF MAIN
RUN-OUT PIPING UNLESS NOTEDOTHERWISE. BRANCH PIPING TO EACHCOIL ONE SIZE SMALLER THAN MAIN
RUN-OUT PIPING, BUT NO SMALLER THANCOIL CONNECTION SIZE.
B. REFER TO AIR HANDLING UNIT SCHEDULE
FOR AUTOMATIC CONTROL VALVE SIZE.
GENERAL NOTES:
GENERAL NOTES:
AUTOMATIC TWO-PORT CONTROL VALVE.
NORMALLY CLOSED THRU COIL.
0.5" DRAIN VALVE.
PIPE REDUCER IF COIL CONNECTIONDIFFERS FROM PIPE SIZE.
DRAIN PAN
DRAIN PIPE, SAME SIZE AS PAN
CONNECTION, WITH DEEP SEAL TRAP.REFER TO CONDENSATE DRAIN PIPINGDETAIL.
LEAVE WIDE OPEN UNLESS NEEDED TOEVENLY DISTRIBUTE FLOW THRU COILS.
A. ALL PIPING SHALL BE FULL SIZE OF MAIN RUN-OUTPIPING UNLESS NOTED OTHERWISE. BRANCH PIPINGTO EACH COIL ONE SIZE SMALLER THAN MAIN
RUN-OUT PIPING, BUT NO SMALLER THAN COILCONNECTION SIZE.
B. REFER TO AIR HANDLING UNIT SCHEDULE FOR
AUTOMATIC CONTROL VALVE SIZE.
GENERAL NOTES:
1
2
3
4
5
5
3
3
4
2
1
1
2
3
4
5
6
6
1
34
3
2
1
2
3
4
5
61
6
3
63
5
4
2
5
C. COORDINATE WITH AHU MANUFACTURERFOR # OF COIL SECTIONS AT EACH AHU.
C. COORDINATE WITH AHU MANUFACTURERFOR # OF COIL SECTIONS AT EACH AHU.
C. COORDINATE WITH AHU MANUFACTURERFOR # OF COIL SECTIONS AT EACH AHU.
9
CHECK VALVE - OMIT FOR SINGLE PUMP INSTALLATIONS.9
AUTOMATIC TWO-PORT CONTROL VALVE.
NORMALLY OPEN THRU COIL.
0.5" DRAIN VALVE.
PIPE REDUCER IF COIL CONNECTIONDIFFERS FROM PIPE SIZE.
LEAVE WIDE OPEN UNLESS NEEDED TOEVENLY DISTRIBUTE FLOW THRU COILS.
A. ALL PIPING SHALL BE FULL SIZE OF MAIN RUN-OUT PIPING UNLESS NOTED
OTHERWISE. BRANCH PIPING TO EACH
COIL ONE SIZE SMALLER THAN MAINRUN-OUT PIPING, BUT NO SMALLER THANCOIL CONNECTION SIZE.
B. REFER TO AIR HANDLING UNIT SCHEDULEFOR AUTOMATIC CONTROL VALVE SIZE.
GENERAL NOTES:
2
34
43
1
4
3
2
1
C. COORDINATE WITH AHU MANUFACTURER
FOR # OF COIL SECTIONS AT EACH AHU.
8
8
10
10
13
BUILDING ISOLATION VALVE.13
FLOOR SLAB
CONCRETE BASE, 4" DEPTH.
#3 REBAR, 12" O.C.
DOWEL BASE TO FLOOR.
1
4
23
4
3
2
1
ASME STAMPED FLASH TANK, 12" DIA. x 24"LONG.
PERFORATED STAINLESS STEEL DISPERSION TUBE,
MINIMUM 24" LONG.
0.75" DRAIN VALVE.
PRESSURE GAUGE WITH SIPHON LOOP, SNUBBERAND SHUT-OFF VALVE.
THERMOSTATIC AIR VENT. EXTEND DISCHARGEPIPE TO FLOOR DRAIN.
0.75" F. & T. TRAP ASSEMBLY.
LOW PRESSURESTEAM LINE
P
2"WATER LINE
MIN. 4"BELOWWATER LINE
4
3
4
5
2
1
6
6
5
3
2
11"
TO CONDENSATERETURN PUMP
0.75"
1"
COIL
48" MAX
4
1
4
3
2
2
COIL
48" MAX 3
1
2
23
FOR KMUA-1 & KMUA-2, HOT WATER COILIS FACE AND BYPASS TYPE.
5M
A.H. UNIT CHILLED WATER COILSCALE: NONE
FAN COIL UNIT PIPING
CND
COIL DRAIN PAN
UNIT DRAIN PAN
& AIR CURTAIN UNIT PIPING
SCALE: NONE
AIR TERMINAL UNIT REHEAT COILSCALE: NONE
6" MIN.
6" MIN.
48" MAX.
6" MIN.
6" MIN.
48" MAX.
HWR
HWS
AIR TERMINAL UNIT REHEAT COILSCALE: NONE
HWR
HWS
A.H. UNIT HOT WATER COILSCALE: NONE
A.H. UNIT HOT WATER COILSCALE: NONE
SCALE: NONE
& AIR CURTAIN UNIT PIPING
SCALE: NONE
PIPE MOUNTED PUMPSCALE: NONE
DUPLEX CONDENSATE PUMPSCALE: NONE
HIGH PRESSURE STEAM DRIPSCALE: NONE
LOW PRESSURE STEAM DRIPSCALE: NONE
STEAM PRESSURE REDUCING STATIONSCALE: NONE
AIR
FLOW
AIR
FLOW
AIR
FLOW
AIR
FLOW
AIR
FLOW
AIR
FLOW
AIR
FLOW
AIR
FLOW
DOAS 1 & DOAS 2 REHEAT COILSCALE: NONE
KMUA-1 & KMUA-2 HOT WATER COIL
CONCRETE EQUIPMENT PADSCALE: NONE
STEAM FLASH TANKSCALE: NONE
FAN COIL UNIT PIPING
CABINET UNIT HEATER PIPINGFAN COIL UNIT PIPING,
DATE ISSUEDPROJECT #
REVISIONS
# DATE DESCRIPTION
Heapy Engineering
Project No.
Enter address here
11
/10
/20
11 3
:12
:33
PM
C:\B
IM\M
ode
l\20
10-0
601
9-C
en
tra
l_JL
WE
TZ
EL.r
vt
H004
DETAILS
2010-06019 Nov. 11, 2011
MAPLE STREET DININGFACILITY
2010-06019
CHILLED WATER PIPING SCHEMATIC
TO KITCHEN/DINING
FROM KITCHEN/DINING
4"
6"
6"
4"
6"
SCALE: NONE
FROM RESIDENTIAL
EXTERIOR
TUNNEL
4"
6"
TO RESIDENTIAL
4"
CHWP-1 CHWP-2
PT
P
PT
PT
T
FLOOR
SYSTEM SYSTEM
SYSTEM
SYSTEM
T
T
F T
F T
BTU METER FORKITCHEN/DINING AREAS
BTU METER FORRESIDENTIAL AREAS
WALL
REFER TO PUMPDETAIL C/HOO2
REFER TO PUMPDETAIL C/HOO2
CHILLED WATER PUMP1
AIR/DIRT SEPARATOR2
BLADDER STYLE EXPANSION TANK3
SHUT-OFF VALVE (TYPICAL)4
1" DRAIN VALVE WITH HOSE THREAD CONNECTION5
LARGE CAPACITY AIR VENT6
MANUAL AIR VENT7
CONCRETE PAD8
1" BLOW DOWN VALVE SHALL BE PIPED TO FLOOR DRAIN9
PRESSURE RELIEF VALVE, SET AT 50 PSI.10
NOTES - CHILLED WATER
11
6"
5
C-2
3 8
9
C-1
2
6
10
4
4
P
4
7
EP
PROVIDE UPSTRAM & DOWNSTREAMPIPING CONDITIONS PER METERMANUFACTURERS DIRECTIONS
NC
4"
CHWR CHWR
CHWS CHWS
CHWS
DOMESTIC WATER HEATER STEAM PIPING SCHEMATICSCALE: NONE
H.C. HEADER SHALL DRAIN BY
3" STEAM HEADER BY H.C.
3"
3"
GRAVITY TO PUMP H-15
3"
3"
2"
2"
DIRT LEG
DWH-1
DWH-2
STEAM TRAPLOW PRESSURE
2" CONDENSATE RETURN BY
THIS POINT BACK TO STEAMPIPING AND VALVES FROM
AND CONDENSATE HEADERBY HC.
DIRT LEG
STEAM TRAPLOW PRESSURE
THIS POINT BACK TO STEAMPIPING AND VALVES FROM
AND CONDENSATE HEADERBY HC.
THIS POINT BACK TOPIPING AND VALVES FROM
CONDENSATE HEADER BY H.C.
THIS POINT BACK TOPIPING AND VALVES FROM
CONDENSATE HEADER BY H.C.
P
T
T
P
FLOOR
4" H.W. SUPPLY TO
RESIDENTIAL SYSTEM
4" H.W. RETURNFROM RESIDENTIAL SYSTEM
REFER TO PUMP DETAIL "C"
ON SHEET "H002".
HWP-7HWP-6
HOT WATER CONVERTER.
LOW PRESSURE DRIP TRAP.
1" DRAIN VALVE WITH HOSE THREAD FITTING.
HIGH PRESSURE DRIP TRAP. BEST-o-BELL, MODEL M-10.
CONDENSATE RETURN PUMP.
VENT LINE TO EXTERIOR OF BUILDING THRU AREA WELL FROM
PRESSURE REDUCING VALVE.
CONCRETE PAD.
HOT WATER PUMP. REFER TO EQUIPMENTSCHEDULE.
CHEMICAL SHOT FEEDER, VALVES OR INLET AND OUTLETNORMALLY CLOSED.
BLADDER STYLE EXPANSION TANK, REFER TO EQUIPMENTDATA. CHARGE TO SPECIFIED PRESSURE.
LARGE CAPACITY AUTOMATIC AIR VENT, PIPE DISCHARGETO FLOOR DRAIN.
AIR/DIRT SEPARATOR, REFER TO EQUIPMENT DATA.
WATER METER WITH REMOTE "GALLON" READ-OUTMOUNTED ON WALL.
AUTOMATIC MAKE-UP ASSEMBLY. REFER TO EQUIPMENTDATA.
MANUAL AIR VENT AT HIGH POINTS OF PIPING (LOCATIONS
SHOWN ARE ARBITRARY. ADJUST LOCATIONS PER ACTUALINSTALLATION.).
F & T TRAP ASSEMBLY.
PN.C.
N.C.
T T
N.C.
NOTES - STEAM/HOT WATER
SCALE: NONE
STEAM/HOT WATER PIPING SCHEMATIC0.5" VACUUM BREAKER.
2/3 CONTROL VALVE.
1/3 CONTROL VALVE.
FULL SIZE DRIP LEG WITH 1" DRAIN VALVE, PLUGGED.
PP
LPS
LPR
P
HPSTO/FROM CAMPUSSTEAM SYSTEM
0.75"
4"
1"
4"4"
0.75"
T
RPBFP
BY P.C.BY H.C.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
99
1011
8
3
3
15
16
12
13
19
19
18
22
22
3
1
2
2
21
7
74
22
6
5
8
22
18
222
20
22
9 9
HWP-8
ON SHEET "H002".
REFER TO PUMP DETAIL "C"
TT
6" 6"
6"KITCHEN/DINING SYSTEM
6" H.W. RETURN FROM
KITCHEN/DINING SYSTEM6" H.W. SUPPLY TO
17
17
23
23 BTU METER FOR RESIDENTIAL AREA.
15 PSIG STEAM PIPING TO DOMESTIC WATER HEATERS.
24
H-3
H-3
1
H-4
H-6
H-5
6"
6"
T T FT T F
6"
H-16
H-7
26
BTU METER FOR KITCHEN/DINING AREA.24
143"
1.25"
25
25 CONDENSATE RETURN LINE FROM DOMESTIC WATER HEATER.
6"
8"
3"
2.5"
HWP-9
2"
2"
26 HOT WATER SUPPLY AND RETURN LINES FROM HEAT PUMP
CHILLER. REFER TO KITCHEN COOLING SYSTEMSDIAGRAM ON THIS SHEET.
T
T
T
P
MECH. ROOM B10. DO NOT RUN VENT THRU ELEC. ROOM B12.
6"6"
6"
27 STEAM FLOW METER-PROVIDE STRAIGHT PIPE WHEN AT
28 FLASH TANK-REFER TO DETAIL ON SHEET H004.
METER PER MANUFACTURERS DIRECTIONS.
PROVIDE UPSTREAM & DOWNSTREAMPIPING CONDITIONS PER METERMANUFACTURERS DIRECTIONS.
27
27
28
PROVIDE UPSTREAM & DOWNSTREAMPIPING CONDITIONS PER METERMANUFACTURERS DIRECTIONS.
PRV-1
PRV-2
A
EP
HWS
HWS
HWR
HWS
HWRHWR
HWR HWR
HWS
M
M
P
2"
3"
6"
3"
4" 5"
3.5"
3"
8"
3"
3"
8"
8"
3.5"
5"
DATE ISSUEDPROJECT #
REVISIONS
# DATE DESCRIPTION
Heapy Engineering
Project No.
Enter address here
11
/10
/20
11 3
:45
:32
PM
C:\B
IM\M
ode
l\20
10-0
601
9-C
en
tra
l_JL
WE
TZ
EL.r
vt
H005
PIPING SCHEMATICS
2010-06019 Nov. 11, 2011
MAPLE STREET DININGFACILITY
2010-06019
EP
CWS
CWR CWR CWR
CWS
M
M
M M
M
2.5"
2.5"
CP-1
CP-2
AIR SEPARATOR
WATER CHILLER FOR KITCHENREFRIGERATION EQUIPMENT, N.I.H.C.
T
T2.5"
2.5"
EXTERIOR WALL OF BUILDING NOTES - KITCHEN COOLING SYSTEM0.75" DRAIN VALVE WITH HOSE THREAD OUTLET.
FLEXIBLE PIPE CONNECTION.
MANUAL BYPASS VALVE, NORMALLY CLOSED.
CONDENSER WATER CONTROL VALVE, FURNISHED BYOTHERS, INSTALLED BY H.C.
CHILLER IS FURNISHED AND INSTALLED BY OTHERS,
PIPING BY H.C. AS SHOWN HERE.
PIPING SHALL BE EXTENDED TO HEATING HOT WATER SYSTEM.REFER TO STEAM/HOT WATER DIAGRAM ON THIS SHEET.
REFER TO PUMP DETAIL ON SHEET H003.
PA
CONDENSER WATEREXPANSION TANK
0.75"
1
7
6
5
4
3
2
1
5
4
1
1
0.75"
1" DRAIN VALVES WITH HOSE THREAD OUTLET88
T
T
T
T
1 4
2 (TYP.)
NOTE: ALL WORK SHOWN IN THIS DETAIL IS TO BE INCLUDED AS PART OF THE BASE BID
7
7
H-13
H-11
PLATE & FRAMEHEAT EXCHANGER
H-20
FLUID COOLER
H-19
T
P T
P
T P
T P
2.5"
2.5"
AUTOMATIC 3-WAY, 2-POSITION, BYPASS VALVE9
9 9
TO CHILLED WATER
FROM CHILLED WATER
AUTOMATIC 2-WAY, MODULATING VALVE10
11
GLYCOL MAKEUP PUMP PACKAGE, REFER TO SPECIFICATION11
SECTION 23 21 17 AND EQUIPMENT DATA.
DDC SENSORS12
TP
TP
T
P
T
P1212
12
12
GLYCOL FEEDSYSTEM
H-21
T
P
6" HOUSEKEEPING PAD13
T
T
12
12
12
T
P
P
12
13 13
GRADE
KITCHEN REFRIGERATION COOLING SYSTEM DIAGRAMSCALE: NONE
H
H
EP
CWR
CWS
T
M
M T
P
2"
2"
CONDENSER WATER AUTOMATIC
MAKE-UP ASSEMBLY
CP-1
CP-2AIR SEPARATOR
CHEMICAL SHOTFEEDERWATER CHILLER FOR KITCHEN
REFRIGERATION EQUIPMENT, N.I.H.C.
CHWP-3
HEAT PUMP
CHILLER
CONDENSERWATER PUMPS
2"
1.5"
CHILLER CHILLEDWATER PUMP
T
2"
2"
2"
EXTERIOR WALL OF BUILDING
TO GEOTHERMAL
THWP-10
CHILLER HOTWATER PUMP
NOTES - KITCHEN COOLING SYSTEM0.75" DRAIN VALVE WITH HOSE THREAD OUTLET.
FLEXIBLE PIPE CONNECTION.
MANUAL BYPASS VALVE, NORMALLY CLOSED.
CONDENSER WATER CONTROL VALVE, FURNISHED BYOTHERS, INSTALLED BY H.C.
CHILLER IS FURNISHED AND INSTALLED BY OTHERS,
PIPING BY H.C. AS SHOWN HERE.
PIPING SHALL BE EXTENDED TO HEATING HOT WATER SYSTEM.REFER TO STEAM/HOT WATER DIAGRAM ON THIS SHEET.
REFER TO PUMP DETAIL ON SHEET H003.
PA
CONDENSER WATER
EXPANSION TANK
WELL FIELD - ALL
1
7
6
5
4
3
2
1
7
6
5
4
1
2
1
37
7
1
0.75"
0.75"
UNDERGROUNDPIPING SHALL BEHDPE PERSPECIFICATIONS
1" DRAIN VALVES WITH HOSE THREAD OUTLET88
T
T
T
T
1 4
2 (TYP.)
NOTE: ALL WORK SHOWN IN THIS DETAIL IS PART OF ALTERNATE #11
0.75"
2"
1.5"
H-14
H-13
H-10
H-11
H-12BY H.C.BY E.C.
KITCHEN REFRIGERATION COOLING SYSTEM DIAGRAMSCALE: NONE
DATE ISSUEDPROJECT #
REVISIONS
# DATE DESCRIPTION
Heapy Engineering
Project No.
Enter address here
11
/10
/20
11 4
:10
:34
PM
C:\B
IM\M
ode
l\20
10-0
601
9-C
en
tra
l_JL
WE
TZ
EL.r
vt
H006
PIPING SCHEMATICS
2010-06019 Nov. 11, 2011
MAPLE STREET DININGFACILITY
2010-06019
COMMENTS
M
M
FILTER
SCALE: NONE
CLG. COIL
DRIVE SPEED
START/STOP
SUPPLY FAN
SUPPLY AIR
AH-1/2
AH-1/2 2
AH-1/AH-2 CONTROL DIAGRAM
AH-1 POINTS LIST
AH-11
NUMBER NAME TYPE CONTROL MONITOR ALARM
VFD FAULT - S.F. DI X
C.W. VALVE POSITION AO X
H.W. VALVE POSITION AO X
COMMENT
S.F. SPEED AO X
S.F. START/STOP DO X
R.F. SPEED AO X
OUTDOOR AIR
HTG.COIL
O.A. DAMPER POSITION AO X
RET. AIR DAMPER POSITION AO X
VFD FAULT - R.F. DI X
R.F. START/STOP DO XRELIEF AIR RETURN AIR
AH-1/2 9
DAMPER POSITION
M
AH-1/2 11
DAMPER POSITION
M
M
T
M.A.T.
AH-1/2 14
AH-1/2 10
DAMPER POSITION
DP
FILTERHI-LIMIT
AH-1/2 18
T
LO-LIMIT
AH-1/2 19
T
COIL L.W.T.
AH-1/2 17
AH-1/2 12
START/STOP
AH-1/2 13
PUMP FAILURE
AH-1/2 8
VALVE POSITION
VALVE POSITION
AH-1/2 7VFD
VFD FAULT
AH-1/2 3
DP
HI-LIMIT
AH-1/2 20
T
S.A.T.
AH-1/2 15
DP
DUCT STATIC
AH-1/2 22
DP
LO-LIMIT
AH-1/2 21
T
R.A.T.
AH-1/2 16
DRIVE SPEED
START/STOP
AH-1/2 4
AH-1/2 5
VFD
VFD FAULT
AH-1/2 6
RETURN FAN
AH-1 2
AH-1 3
AH-1 4
AH-1 5
AH-1 6
AH-1 7
AH-1 8
AH-1 9
AH-1 10
AH-1 11
AH-1 12
AH-1 13
AH-1 14
AH-1 15
AH-1 16
AH-1 17
AH-1 18
AH-1 19
AH-1 20
AH-1 21
AH-1 22
AH-1 23
ON FAULT
ON FAULT
RELIEF DAMPER POSITION AO X
H.W. PUMP START/STOP DO X
PUMP FAILURE DI X ON FAILURE
MIXED AIR TEMP AI X
X
X
X
X
X
X
X
X
X
ON TRIP
ON TRIP
ON TRIP
LEAVING AIR TEMP AI
RETURN AIR TEMP AI
H.W. COIL L.W.T. AI
FILTER HI- LIMIT DI
FREEZE STAT DI
SUPPLY DUCT HI-LIMIT DI
RETURN DUCT LO-LIMIT DI
SUPPLY DUCT S.P. AI
SPACE CO2 LEVEL AI
AH-2 POINTS LIST
AH-21
NUMBER NAME TYPE CONTROL MONITOR ALARM
VFD FAULT - S.F. DI X
C.W. VALVE POSITION AO X
H.W. VALVE POSITION AO X
COMMENT
S.F. SPEED AO X
S.F. START/STOP DO X
R.F. SPEED AO X
O.A. DAMPER POSITION AO X
RET. AIR DAMPER POSITION AO X
VFD FAULT - R.F. DI X
R.F. START/STOP DO X
AH-2 2
AH-2 3
AH-2 4
AH-2 5
AH-2 6
AH-2 7
AH-2 8
AH-2 9
AH-2 10
AH-2 11
AH-2 12
AH-2 13
AH-2 14
AH-2 15
AH-2 16
AH-2 17
AH-2 18
AH-2 19
AH-2 20
AH-2 21
AH-2 22
AH-2 23
ON FAULT
ON FAULT
RELIEF DAMPER POSITION AO X
H.W. PUMP START/STOP DO X
PUMP FAILURE DI X ON FAILURE
MIXED AIR TEMP AI X
X
X
X
X
X
X
X
X
X
ON TRIP
ON TRIP
ON TRIP
LEAVING AIR TEMP AI
RETURN AIR TEMP AI
H.W. COIL L.W.T. AI
FILTER HI-LIMIT DI
FREEZE STAT DI
SUPPLY DUCT HI-LIMIT DI
RETURN DUCT LO-LIMIT DI
SUPPLY DUCT S.P. AI
SPACE CO2 LEVEL AI
FILTER
SCALE: NONE
DRIVE SPEED
START/STOP
SUPPLY FAN
SUPPLY AIR
KMUA-1/21
KMUA-1/2 2
KMUA-1/KMUA-2 CONTROL DIAGRAM
KMUA-1 POINTS LIST
KMUA-1 1
NUMBER NAME TYPE CONTROL MONITOR ALARM
VFD FAULT - S.F. DI X
DI X
H.W. VALVE POSITION
AI X
COMMENT
S.F. SPEED AO X
S.F. START/STOP DO X
DO X
OUTDOOR AIR
HTG.COIL
O.A. DAMPER POSITION
AI X
DI X
AO X
AO X
KMUA-1/2 5
DAMPER POSITION
M
DP
FILTERHI-LIMIT
KMUA-1/2 10
T
LO-LIMIT
KMUA-1/2 11
T
COIL L.W.T.
KMUA-1/2 9
KMUA-1/24VALVE POSITION
VFD
VFD FAULT
KMUA-1/2 3
DP
HI-LIMIT
KMUA-1/2 12
T
S.A.T.
KMUA-1/2 8
DP
DUCT STATIC
KMUA-1/2 13
ON FAULT
DI X
DI X
AI X
ON FAILUREPUMP FAILURE
LEAVING AIR TEMP
H.W. COIL L.W.T.
FILTER HI-LIMIT
FREEZE STAT
SUPPLY DUCT HI-LIMIT
SUPPLY DUCT S.P.
F & B DAMPER POSITION
ON TRIP
ON TRIP
ON TRIP
KMUA-1 2
KMUA-1 3
KMUA-1 4
KMUA-1 5
KMUA-1 6
KMUA-1 7
KMUA-1 8
KMUA-1 9
KMUA-1 10
KMUA-1 11
KMUA-1 12
KMUA-1 13
KMUA-2 POINTS LIST
KMUA-2 1
NUMBER NAME TYPE CONTROL MONITOR ALARM
VFD FAULT - S.F. DI X
DI X
H.W. VALVE POSITION
AI X
COMMENT
S.F. SPEED AO X
S.F. START/STOP DO X
DO XO.A. DAMPER POSITION
AI X
DI X
A0 X
AO X
ON FAULT
DI X
DI X
AI X
ON FAILUREPUMP FAILURE
LEAVING AIR TEMP
H.W. COIL L.W.T.
FILTER HI-LIMIT
FREEZE STAT
SUPPLY DUCT HI-LIMIT
SUPPLY DUCT S.P.
F & B DAMPER POSITION
ON TRIP
ON TRIP
ON TRIP
KMUA-2 2
KMUA-2 3
KMUA-2 4
KMUA-2 5
KMUA-2 6
KMUA-2 7
KMUA-2 8
KMUA-2 9
KMUA-2 10
KMUA-2 11
KMUA-2 12
KMUA-2 13
COIL PUMP
T
L.W.T.
HW 14
CONVERTER #2
T
L.W.T.
HW 13
CONVERTER #1
DRIVE SPEED
START/STOP
HW 1
HW 2
VFD
VFD FAULT
HW 3
PUMP
PUMP
DRIVE SPEED
START/STOP
HW 4
HW 5
VFD
VFD FAULT
HW 6
T
T
DP
SYSTEM DIFF. PRESSURE
HW 7
SCALE: NONE
STEAM & HOT WATER SYSTEM CONTROL DIAGRAM
STEAM & HOT WATER SYSTEM POINTS LIST
HW 1
NUMBER NAME TYPE CONTROL MONITOR ALARM
VFD FAULT DI X
COMMENT
PUMP SPEED AO X
PUMP START/STOP DO X
PUMP SPEED AO X
CONVERTER STEAM VALVE AO X
AO X
VFD FAULT DI X
PUMP START/STOP DO X
ON FAULT
ON FAULT
BUILD. SUPPLY WATER TEMP. AI X
BUILD. RETURN WATER TEMP. AI X
CONVERTER L.W.T. AI X
CONVERTER L.W.T. AI X
XSYSTEM DIFF. PRESSURE AI
HW 2
HW 3
HW 4
HW 5
HW 6
HW 7
HW 8
HW 18
HW 19
HW 11
HW 12
HW 13
HW 14
HW 15
HW 16
HW 17 CONVERTER STEAM VALVE
SPACE CO2(TYPICAL FOR
2-AHU-2)
AH-1/2 23
SPACE CO2(TYPICAL FOR
5-AHU-1)
CO2
SUPPLY AIR CFM
RETURN AIR CFM
AFMS
AH-1/2 24
AFMS
AH-1/2 26
AH-1 24
AH-1 25
AH-1 26 OUTSIDE AIR CFM
XAI
XAI
XAI
SUPPLY AIR CFM
RETURN AIR CFM
AH-2 24
AH-2 25
AH-2 26 OUTSIDE AIR CFM
XAI
XAI
XAI
AFMS
KMUA-1/2 14
OA DAMPER XDIKMUA-1 14 OA DAMPER XDIKMUA-2 14
XMAKE