Hoval Uno-3 (50-90)Boiler for oil and gas firingwith or without calorifier

Description

Uno-3 Range of outputTyp kW

50 35-5062 46-6275 53-7590 60-90

Hoval Uno-3 b-i(Oil burner integrated)

Boiler• 3-pass steel boiler for oil firing• With Bizonal-technic for low temperature

work• Thermolytic secondary heating surface

with built-in flue gas regulators on request• Double joint boiler doormounted on

the right hand side• Insulation 80mm mineral wool mat and

special fabric

• Casing made of steel plates, red/orangepowder coated

• instruction manual

Oil burner• Automatic 1-stage oil burner• With motorized air damper• Pre-wired with plug connection• Oil burner tested by Hoval

Adjusted by Hoval for < 1000 m above sealevel1.2% output reduction per 100 mhigher level

Sound absorber hood• Sound absorber hood for burner and boiler

door for heat and sound absorpation

Optional• control panel with different regulators and

functions• Calorifier on the boiler

Delivery• Boiler insulated and cased

Burners and absorber hood are separatelypacked and delivered.

Hoval Uno-3Oil / gas boiler

as Uno-3 b-i, but without burner and soundabsorber hood

Delivery• Boiler insulated and cased

Calorifier EWE

• Calorifier and heat exchanger out ofdouble enamelling

• Heat exchanger fixed• Calorifier Type 300-600 l• Built on the boiler• Anode• Insulation with CFC-free cellular plastic

heat insulation, 70 mm (λ=0.025W/mK)• Casing out of aluminium, red powder

coated• Including temperature sensor

Loading group for calorifier• complete installed and wired

consists of:– Loading pump– Non-return valve– Piping and fittings

Delivery• Calorifier, insulation and casing, loading

group separately packed and delivered

At place• Mounting of insulation and casing

30

Subject to alterations

Hoval Uno-3 (50-90)Boiler for oil and gas firingwith or without calorifier

Description

Control panel• Boiler without calorifier, control panel on

the top of the boiler• Boiler with calorifier, control panel placed

on the right or left side

Control panel with:• Main switch «on/off»• Boiler safety limit thermostat 110°C• Fuse 6.3A• Trouble indication „burner“• Plug connection for 2-stage Burner

1x230V• Change over switch nominal/maximum

output• boiler sensors

Control panel with TopTronic regulator– For 1 or 2 mixing circuit– Operation switch– Temperature adjustment “Day/Night”– Adaption with microcomputer– Automatic switch summer/winter– Regulation of boiler temperature– Calorifier loading control– Digital display– Burner running time meter and count-up

counter• Outside sensor AF 100N• Flow temperature sensor VF 100N

• Optional possibility for second regulator for1 or 2 additional mixing circuit

Control panel with thermostat

T2.1• Wired version for external control

commands

T0.1-110• Unwired version for external control

commands

Delivery• Control panel separately packed and

delivered

At place• Mouting of control panel

Heating armature groupType HA 40-4R

• For systems with 1 heating group• For mounting right hand side• To Uno-3 (90) with TopTronic regulator• If the heating armature group is direct fitted

at the boiler, no boiler circulation pumpmust be used

• Complete installed and wiredconsists of:– Heating circuit pump– motorized 4-Way-mixing valve– 2 ball valves with thermometer– Non return valve– Piping and fittings size 11/2“– Power supply 1x230V

Type HA 40-4L

• As heating armature group HA 40-4R

At place• Modification for mounting left hand side

Heating armature groupType HA 32-4R

• For systems with 1 heating group• For mounting right hand side• To Uno-3 (50-75) with TopTronic regulator• If the heating armature group is direct fitted

at the boiler, no boiler circulation pumpmust be used

• Complete installed and wiredconsists of:– Heating circuit pump– Motorized 4-way-mixing valve– 2 ball valves with thermometer– Non return valve– Piping and fittings size 11/4“– Power supply 1x230V

Type HA 32-4L

• As heating armature group HA 32-4R

At place• Modification for mounting left hand side

31

Subject to alterations

Hoval Uno-3 (50-90)

Oil boilerUno-3 b-i

Price

with 1-stage light oil burner

Part no.

Oil-/Gas boilerUno-33-pass low temperature boiler for oil/gas firing,without control panel. Boiler insulated andcased.

Uno-3 Burner OutputType Type kW

b-i 50 R20-L 35-50b-i 62 R20-L 46-62b-i 75 R20-L 53-75b-i 90 R20-L 60-90

Uno-3 OutputType kW

50 35-50 800080762 46-62 800080875 53-75 800080990 60-90 8000810

3-pass-low temperature boiler with light oilburner and sound absorber hood, withoutcontrol panel. Boiler insulated and cased.Burner and absorber hood separately packedand delivered

32

Subject to alterations

Hoval Uno-3 (50-90)

Preise

Oil boiler Uno b-i (50-90) withtop mounted calorifier

Oil/Gas boiler Uno-3 with topmounted calorifier

Uno-3 OutputType kW

50/300 35-50 8000811

62/300 46-62 800081262/450 46-62 8000813

75/300 53-75 800081475/450 53-75 8000815

90/450 60-90 800081690/600 60-90 8000817

with 1-stage light oil burner

Uno-3 Burner OutputType Type kW

50/300 R20-L 35-5050/450 R20-L 35-50

62/300 R20-L 46-6262/450 R20-L 46-62

75/300 R20-L 53-7575/450 R20-L 53-75

90/450 R20-L 60-9090/600 R20-L 60-90

Part no.

3-pass-low temperature boiler with light oilburner and sound absorber hood, withoutcontrol panel.Calorifier made of double enamelling and builton the boiler.Boiler insulated and cased. Light oil burner,calorifier and loading group are separatelypacked and delivered

3-pass-low temperature boiler for gas/oilfiring, without control panel.Calorifier made of double enamelling and builton the boiler.Boiler insulated and cased. Calorifier andloading group separately are packed anddelivered

33

Subject to alterations

Hoval Uno-3 (50-90)

Price

Control panel with TopTronicregulator for Uno-3 with orwithout calorifier and 1 to 4mixing circuits.

Standard control panel:M3.1For external on/off and nominal/maximumoutput control with TopTronic or otherregulators. Boiler temperature sensor KT10for regulation already integrated.

Part no.

Regulator set:

TopTronic 2B(without mixing circuit)Automatical regulation of boiler watertemperature for heating systems with 1 stageburner, including sensors

TopTronic 23B1 stage burner controlRegulation of 1 mixing circuit, 1 direct heatingcircuit without mixing valve and hot water loadingcircuit, incl. sensors.

TopTronic 223B2 stage burner controlRegulation of 1 mixing circuit, 1 direct heatingcircuit without mixing valve and hot water loadingcircuit, incl. sensors.

To Uno-3Burner 1-stage

– with 7-pin plug connectionmounted on the boiler AW4263mounted at the side AW4272

To Uno-3– Burner 2-stage– with 7- + 4-pin plug connection

mounted on the boiler AW4264mounted at the side AW4305

691238

TopTronic 203Bmodulating burner controlRegulation of 1 mixing circuit, 1 direct heatingcircuit without mixing valve and hot water loadingcircuit, incl. sensors.

691208

691494

691493

34

Subject to alterations

Hoval Uno-3 (50-90)

Price

Additional regulators:

TopTronic 3for 1 additonal mixing circuit, including sensors

TopTronic 233Bfor 2 additional mixing circuit, including sensors

Additonal equipment ZM1Adapter set for second regulator

TopTronic 233B1 stage burner controlRegulation of 2 mixing circuit, 1 direct heatingcircuit without mixing valve and hot water loadingcircuit, incl. sensors.

691335

691282

691138

691282

Part no.

TopTronic 2233B2 stage burner controlRegulation of 2 mixing circuit, 1 direct heatingcircuit without mixing valve and hot water loadingcircuit, incl. sensors. 691435

35

Subject to alterations

Hoval Uno-3 (50-90)

Price

Part no.

Control panel without heatingregulator

T 2.1 (pre-wired solution)- for systems without TopTronic regulator- for direct burner control- For external calorifier or external heating

commands

To Uno-3 (75-90)- 2 stage burner- with 7- + 4-pin plug connection- 2 burner running hour meter- 2 burner running hour meter and count-up

counter

To Uno-3 (50-75)- 1 stage burner- with 7 pin plug connection- 1 burner running hour meter- 1 burner running hour meter and count-up

counter

AW 4606AU 2970

AU 3268

AW 4261AU 2969

AU 3255

T0.1-110 (for external control)- for systems without TopTronic regulator- for boiler sequence control- for special control functions- without built-on calorifier- 1 burner running hour meter- 1 burner running hour meter and count-up

counter

- 2 burner running hour meter- 2 burner running hour meter and count-up

counter

- Additional sensor for external TopTronicregulator

AW 4260AU 3321

AU 3322

AU 3323

AU 3324

6001396

36

Subject to alterations

Hoval Uno-3 (50-90)

Price

Accessories for heating controlsystem TopTronic

Part no.

Room station RS 10for one mixing circuit with room sensor,information, program and correction key

Flow temperature guardRAM 342.001for for floor heating incl. cable and plug

Flow temperature safety thermostatfor floor heating(per heating circuit 1 thermostat)- Thermostat with pocket 619.0015- Thermostat 692.1120

Sensor VF100N

Temperature sensor KT 10-40 Swith 4 m cabel for calorifier or external heataquisition

Flue gas temperature sensor PT1000/4

Additional outer temperature sensorAF 100Nfor one mixing circuit (per heating circuit1 separate outer temperature sensor ispossible)

Room temperature sensor RF 40for one mixing circuit

Remote control RFF 60Sfor one mixing circuit with room sensor, easyprogram switch and temperature adjustment

687997

242190242217

242647

242371

242681

242646

242679

2000754

242634

37

Subject to alterations

Hoval Uno-3 (50-90)

Price

Heating armature groupPart no.

1) only for Uno-3 without top mounted calorifier

Connection setto HA 40R/L 639372

Boiler PumpHA-Type Type Type

HA 40-4R/L 90 M14-2 AW4528

HA-goup, 1 heating circuit Ø 1½“

Connection setto HA-32 639288

Boiler PumpHA-Type Type Type

HA 32-4R/L 50-75 M14-2 AW4522

HA-group, 1 heating circuit Ø 1¼“

For systems with heating groups withmotorized 4-way mixing valve for Uno-3 (50-90) with TopTronic regulator.

Connection setto HA 40on the back1) 639371

Connection setto HA-32on the back1) 639370

38

Subject to alterations

Hoval Uno-3 (50-90)

Price

Accessories

Service

Commissioning

Part no.

Flue gas thermometerØ 80–150 241133

Oil volume counter VZO 4Kwith filter 6003163

Oil-filter OVENTROP 25-40µ CG0107

Type

width 530 mm (plastic cover cap)Uno-3 (50-90) 6001077

width 750 mm (steel cover cap) Uno-3 (50-90)

Sound absorber hood for light oil burnerfor heat and sound absorpation

39

Subject to alterations

Hoval Uno-3 (50-90)

Technical data

Uno-3

Type 50 62 75 90

• Nominal output kW1 50 62 75 90• Range of output kW 35-50 46-62 53-75 60-90• Maximum burner output kW 53,7 66,6 81,5 98,0

• Max. boiler working temperature2 °C 90 90 90 90• Min. boiler working temperature °C 483 483 483 483

• Min. return flow temperature °C 383 383 383 383

• Min. flue gas temperature Oil EL °C 130 130 130 130Oil L °C 140 140 140 140

• Safety limit temperature °C 110 110 110 110• Working / test pressure bar 3 /4,5 3 /4,5 3 /4,5 3/4,5

• Flue gas regulators 2R5/290 3R5+2R3/290 3R5+2R3/290 4R5+1R3/290• Boiler efficiency at 80/60 °C % 93 93 93 93• Stand-by deficiency qB at 70 °C Watt 340 340 340 350

• Flue gas resistance at nominal output (+/- 20 %) mbar 0,22 0,36 0,47 0,75• Flue gas mass flow Oil EL kg/h 85 105,4 133

• Flow resistance boiler 6 z-value 3,22 3,22 3,22 1,50• Water resistance at 10K mbar 59,53 91 133 90

• Boiler content Liter 105 105 105 115• Boiler gas volume m³ 0,125 0,125 0,125 0,135• Insulation boiler body mm 80 80 80 80• Insulation boiler door mm 30 30 30 30• Weight (incl. casing) kg 247 247 247 268

• Acoustic capacity incl. sound absorber hood 5

– Heating noise dB(A) 70 67 67 71 – Chimney noise dB(A) 79 82 85 87

• Fire room dimension Ø x length mm ø410x725 ø410x725 ø410x725 ø410x835• Fire room volume m³ 0,0872 0,0872 0,0872 0,1002

• Dimension width mm 710 710 710 710 (without burner and sound absorber hood) length mm 1082 1082 10821192

height mm 1072 1072 1072 1072

1 kW= Flue gas deficiency according to guideline LRV 92 (Boiler water 80°C)2 Limited to 90 °C with control panel3 Valid by flue gas temperature min. 110°C4 Valid by flue gas temperature min. 130 °C5 Valid for Uno-3 b-i6 Flow resistance in mbar = volume flow (m³/h)2 x z

40

Subject to alterations

Hoval Uno-3 (50-90)

Technical data

Calorifier EWE

Type 300 450 600

• Volume dm3 300 450 600• Working / test pressure bar 10 / 15 10 / 15 10 / 15• Max. working temperature °C 75 75 75• Insulation mm 70 70 70• Thermal conductivity λ Watt/mK 0,025 0,025 0,025• Weight kg 158 182 231• Anode Correx Correx Correx

• Dimension diameter mm Ø 600 Ø 700 Ø 700 without insulation length mm 1420 1540 1965

Heating register• Heating surface m2 2,1 2,4 3,4• Water capacity dm3 15,0 17,0 24,0• Loading pump Biral Type M13-2 M13-2 M15-2• Working / Test pressure bar 10 / 15 10 / 15 10 / 15• Working temperature °C 90 90 90

Hot water output / flow temperature 80°C

Uno-3 / EWE Hot water capacity Flats Weight Stand-by deficiencydm3/10 min 1 dm3/h 2 dm3/h 2 Flow Uno-3 with EWE qB (70°C)

Type 45°C 45°C 60°C kW 5 m³/h Quantity 3 kg Watt 4

b-i (50) 300 420 1230 730 50 2,0 8 410 460b-i (50) 450 580 1230 730 50 2,0 12 465 450

b-i (62,75) 300 420 1420 810 58 2,6 9 427 460b-i (62,75) 450 580 1450 830 59 2,8 14 482 450

b-i (90) 450 580 1450 830 59 2,8 14 493 480b-i (90) 600 780 1960 1040 80 3,8 23 550 516

1 Peak hot water output in 10 minutes. Calorifier heated to 60°C2 Continuous hot water output per hourCold water 10°C, flow temperature 80°C

3 Flat (3–4 rooms with 3-4 Persons)4 Uno-3 and EWE without loading line5 Power consumption at 45/10°C(min. required boiler output)

Oil burner to Uno-3 b-i 50 b-i 62 b-i 75 b-i 90

• Oil burner Typ R20-L R20-L R20-L R20-L• Output kW 38-55 49-68 57-82 65-99• Oil compustion kg/h 4.65 5.75 6.95 8.40

41

Subject to alterations

Hoval Uno-3 (50-90)

Heating armature group

Flow resistance Uno-3 (50-90) with heating armaturegroup

HA-32-4-R/L z = 7,3HA-40-4-R/L z = 3,4

HA-R = group rightHA-L = group left

mbar = (m3/h)2 x z

mbar = Flow resistancem3/h = Volume flow

Technical data

If the normal heating armature group heatingsurface (water flow > 3,5 m³/h) is used, a boilercircuit pump must be used.

42

Subject to alterations

Hoval Uno-3 (50-90)

Uno-3

Dimension

1 Flow R1 1/4" (Typ 50 - 75), R1 1/2" (Typ 90)2 Return R1 1/4" (Typ 50 - 75), R1 1/2" (Typ 90)3 Safety flow (expansion) R1"4 Drain R1"5 Flue gas outlet Ø149 mm6 Cleaning opening7 Control panel8 Burner plug9 Cable connection

43

Subject to alterations

Hoval Uno-3 (50-90)

b2z3

z4

Uno-34 x M8

e205,5

b1

l1l2

h1

z1

z2

x y

l3

d

bi-Ausf. 530

r

q

p

o

it

w

u

f

gj1

k m

n

a

Fremdbrennerhaube 750(mit Füssen)

600

h2 h3

c

øj 2

s

Dimension

Uno-3 (50-90) with top mounted calorifier

Uno-3 l1 l2 l3 h1 h2 h3 b1 b2 a c d e f g i j1 øj2 k m

50,62,75/300 2012 1460 1082 866 1266 1651 710 770 574 360 125 150 151,5 450 495 638,5 149 761 77250,62,75,/450 2046 1580 1082 866 1316 1751 710 870 574 360 125 150 151,5 450 495 638,5 149 761 77290/450 2156 1580 1192 866 1316 1751 710 870 574 360 125 150 151,5 450 495 638,5 149 761 77290/600 2156 2010 1192 866 1316 1751 710 870 574 360 125 150 151,5 450 495 638,5 149 761 772

Uno-3 n o p q r s t u v w x y z1 z2 z3 z4

50,62,75/300 1021 170 175 79 75 225 480 115 450 130 133,5 915 32,5 82,5 35 214,550,62,75/450 1096 150 155 135 50 185 480 115 450 130 133,5 915 32,5 82,5 35 248,590/450 1096 150 155 135 50 185 480 115 450 130 133,5 1025 32,5 82,5 35 248,590/600 1096 150 155 135 50 185 480 115 450 130 133,5 1025 32,5 82,5 35 248,5

12

13

14

8

10

9

5

15

11

2

6

7

3

1

2

1

}1 Flow2 Return3 Safety flow R1"4 Drain R1"5 Flow calorifier6 Return calorifier7 Cold water8 Hot water9 Circulation R1"

10 Flue gas outlet Ø 149 mm11 Cleaning opening12 Control panel (optional right or left)13 Boiler door swivelling right14 Burner plug15 Cable connection

Typ 50 - 75 / 300, 450 R1 1/4"Typ 90 / 450, 600 R1 1/2"

Typ 50 - 75 / 300 R1 1/4"Typ 50 - 90 / 450, 600 R1 1/2"

R1 1/4"}}

4

44

Subject to alterations

Hoval Uno-3 (50-90)

Basis sizes and space requirements

Attention• The calorifier will be packed and delivered

separately and must be mounted at place

Uno-3 b-i / Uno-3 B1 B2 B3 H1 H2 H3 H4 L1 L2 L3 L4 L5 L6

50,62,75/300 610 707 600 821 1616 1266 795 1180 915 1410 156 133 16650,62,75/450 610 707 700 821 1721 1316 900 1180 915 1540 241 167 16690/450 610 707 700 821 1721 1316 900 1290 1025 1540 131 167 16690/600 610 707 700 821 1721 1316 900 1290 1025 1965 558 167 166

B3

H1

B1

B2

H3H2

L3

L5 L4

L6 L2

L1

H4

Weights

Boiler Weight Calorifier Weight Boiler and Calorifier WeightType kg Type kg Type kg

50 217 300 158 50/300 37562,75 217 450 182 50/450 39990 233 600 231

62,75/300 37562,,75/450 399

90/450 41590/600 464

• Optional flue gas collector and boiler outletwill be delivered separately

45

Subject to alterations

Hoval Uno-3 (50-90)

Dimension with heating armature group

Uno-3 a b c d e f

50, 62,75 1517 450 311 30 160 67,590 1654 450 311 30 160 67,5

Uno-3 a* a** b c d e f

90 1694 1724 450 311 30 160 67,5

Uno-3 a b c d e f

50, 62,75 /300, 450 1443 450 311 373 160 67,590 / 450, 600 1507 450 311 381 160 67,5

Uno-3 a* a** b c d e f

90 / 450, 600 1547 1577 450 311 381 160 67,5

e

d

a

b

c

f

a

b

c

d

e

f

160

275,5

d

a

b

c

e

f

a

b

c

d

e 160

275,5

* Pump L = 220** Pump L = 250

(all measurements in mm)

46

Subject to alterations

Hoval Uno-3 (50-90)

Boiler door swivelling and soundabsorber hood dimension

(All measurements in mm)

Space requirement / Dimensions

If the burner will not be deliveredby Hoval, the required spacemust be checked with the burnersupplier.

Distances

a= Min. space for swivelling of theburner door

b= Min. space for soundabsorberhood mounting

Uno-3 b-i Uno-3 b-i withcalorifier a b

50/62/75 without 600 50090 without 600 500

50/62/75 300/450 600 50090 450 600 50090 600 600 700

Burner assembling- The burner must be mounted,

that the boiler door canswivel 90°.

ba

d

c

a

b

Sound absorber hoodType a b c d Burner

Uno-3 b-i (50) 402 530 486 517Uno-3 b-i (62,75) 402 530 486 517Uno-3 b-i (90) 402 530 486 517

47

Subject to alterations

Hoval Uno-3 (50-90)

Flue gas - output diagram

Uno-3 b-i (50) / Uno-3 (50)Boiler temperature Flow/Return 80/60°C

Uno-3 b-i (62) / Uno-3 (62)Boiler temperature Flow/Return 80/60°C

110

120

130

140

150

160

170

180

190

200

210

35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50

A

B

110

120

130

140

150

160

170

180

190

200

210

46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62

B

A

°C

k W

k W

°C

48

Subject to alterations

Hoval Uno-3 (50-90)

Flue gas - output diagram

Boiler temperature Flow/Return 80/60°C

Uno-3 b-i (75) / Uno-3 (75)

kW = Boiler output°C = Flue gas temperature, boiler water

temperature 80°C (DIN 4702).

110

120

130

140

150

160

170

180

190

200

210

220

230

240

250

53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75

B

A

Boiler temperature Flow/Return 80/60°C

Uno-3 b-i (90) / Uno-3 (90)

110

120

130

140

150

160

170

180

190

200

210

220

60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90

B

A

A = without flue gas regulatorsB = with flue gas regulators

°C

k W

°C

k W

49

Subject to alterations

Hoval Uno-3 (50-90)

Standards and GuidelinesFollowing standards and guidelines must berespected:

- Technical information and installationmanual of company Hoval

- Hydraulic and technical control regulationsof the local gas supply authority

- Firing guidelines of local gas works

- Fire protection standards

- Gas directives G1 of the SVGW

- Directives SWKI 97-1 «Water treatment forheating, steam and air conditioninginstallations»

- Ventilation and air supply for the boilerinstallation room according to directivesSWIKI 91-1

- Directives SWKI- 93-1 „Safety equipmentfor heating systems“.

- Directives Procal/FKR "Electric plugconnections at heating boilers and burners".

- Procal Data Sheet "Corrosion throughhalogen compounds".

- Procal Data sheet "Corrosion damage inheating installations" and the brochure"Protectionagainst corrosion and boilerscale formation in heating and service waterinstallation".

Water treatment- Old installations must be well flushed before

filling.

- The water quality must be tested at leastonce a year

Heating systemCombustion Air- The combustion air supply must be

warranted. Opening must not be lockable.

- Minimal free cross section for air opening6.5 cm2 per 1 kW boiler output.

Oil burner mounting- The burner connection plug must be mounted

opposite the burner door hinges.

- It should be possible to swivel the boilerdoor incl. burner by 90°.

- The space between burner and boiler doormust be insulated by the additional deliveredinsulation material

Electric connection of the burner- 1 x 230 V, 50 Hz, 10 A.

- For safety reasons the electric cable ofthe burner must be that short that the plugmust be removed when swivelling boilerdoor.

Sound absorptionSound absorption is possible through thefollowing steps:

- Walls, ceilings and floor should be verysolidly built, a sound absorber should bemounted into the air inlet. Pipe holders andsupport should be protected by means ofanti-vibration sleeves.

- Install sound absorber hood for burner.

- If living rooms are located above or underthe boiler room, vibration absorbers have to be mounted to the boiler base. Pipes andflue gas tube must be connected flexiblewith compensators.

- Pumps have to be connected withcompensators to the pipes.

- For damping of flame noise it is possible toinstall a silencer into the flue gas tube(Space should be foreseen for laterinstallation).

Heating armature groupIf the normal heating armature group forheating surface (water volume > 3,0 m3 /h,Euro-3 37, 48) is used, a boiler circuit pumpmust be fitted.

Chimney / Flue gas sustem

Flue gas tube- The flue gas tube must be led into the

chimney with an angle of 30-45 °.

- If the flue gas tube is longer than 1m, itmust be insulated.

- The inlet of the flue gas tube into thechimney has to be carried out in such way,that no condensate can flow from thechimney into the flue gas tube and boiler

Engineering

- A closeable flue gas measuring socket withan inner diameter of 10-21 mm must beforeseen.

Chimney- The chimney must be water proof, acid

resistant and suitable for flue gastemperature > 160°C

- For existing chimney installation therestoration must be carried out accordingto the instructions of the chimneyconstructor.

- The cross sections are to be calculated forboilers without draft requirements.

Required chimney diameterBasic: Smooth chimneys made of stainlesssteel, Flue gas tube < 2,5 m,Σζ = 2,2, flue gas tube and chimney insulated.Height above sea level < 1000 m,Outside temperature < 30°C.

Uno-3Typ 50 62,75 90

Chimney Chimney and flue gasHeight tube Ømmm

25 125 150 15020 125 150 15015 125 150 150

10 150 150 150 5 150 150 175

m = Chimney hight (m)Ø = min. Ø of flue gas tube and chimney.

D

D

2xD2D

1D

50

Subject to alterations

Hoval Uno-3 (50-90)

Piping

- The boiler Uno-3 can only be used for 1line systems. Maximum suction hight withoutpump 3.5m, maximum length of pipe system40m.

- The pipes must be fitted that the boiler doorcan be swivelled 90°.

- At the end of the fixed piping a shut off valvemust be installed (by „Oventrop“ filteralready included).

- A Filter (20-40 µ) must be installed in frontof the burner in the piping.

- The highest point of the piping should bemax. 3.5m above the tank suction pipe.

- The piping must be installed that no fluidcan get into the pipes, when the system isnot working.

- If the highest oil level in the tank is higherthen the lowest point of the piping system,

max.3.5 m

5

1

2

45 35

H

5 55

6

max.3.5 m

2

1

45 3

Max. oil level higher than the lowestpoint of the piping system

Max. oil level lower as the lowestpoint of the piping system.

1 Hoval-burner for 1-line connection withreturn flow

2 Oil pump3 Burner oil hoses4 Filter with filter element 20 - 40 µ5 Shut-off valve

a solenoid vlave must be installed at thehighest point of the system (next to the oiltank).

6 solenoid valve

H = Suction height [m] (system with max. 4bows, 1 shut-off valve with non returnvalve.

Height above sea level max. 1000 m)

Expansion tank- If ia 4 way mixing valve is used in your

system you have to install an expansiontank

- In the case of a system with open expansiontank, it must be assured that the pressure inthe suction pipe of the pump will be not lowerthe allowed.

Safety valve- At the safety flow a safety valve must be

installed.

Sanitary installation- The installation must be carried out

according to the regulation of local waterworks.

- Pressure safety limit max 8 bar.

Engineering

Boiler Type Uno-3 b-i (50) Uno-3 b-i (62,75) Uno-3 b-i (90)

Output 50 kW 62/75 kW 90 kW

Piping Øin mm 4 6 8 4 6 8 6 8

Height Hm

1,5 11 30 – 9 30 – 30 –2 8 30 – 7 30 – 27 –

2,5 6 31 – – 25 30 19 303 – 18 35 – 13 35 11 30

Example for sanitaryconnection

1 Cold water2 Hot water3 Optional circulation

4 Drain5 Height min 300mm6 Anode

Calorifier- If the capacity of the calorifier is higher

than the boiler output, a by-pass at thecalorifier loading line must be used.

62

3

15

4

52

subject to alterations

Hoval Uno-3 (110-320)Boiler for oil / gas firingwith or without calorifier

Description

Hoval Uno-3 b-i

Boiler• 3-pass steel boiler for oil firing• Secondary heating surface

- Type 110-280 Thermolytic heating surface with built in flue gas regulators on request- Type 320 with Sicken pipes

• Double joint boiler door swivelledto the right

• Insulation 80mm mineral wool mat andspecial fabric

• Casing made of steel plates, red/orangepowder coated

• Flue gas outlet and heating connections onthe back

• Instruction manual

Oil burner• Automatic 1-stage oil burner• With motorized air damper• Pre-wired with plug connection• Oil burner tested by Hoval

Adjusted by Hoval for < 1000 m above sealevel1.2% output reduction per 100 mhigher level

Absorber hood• Cover cap for burner and boiler door for

heat and sound absorbation

Optional• Control panel with different regulators and

functions• Calorifier on the boiler

Delivery• Boiler insulated and cased

Boiler, burner and absorber hood areseparately packed

At place• Mounting of insulation and casing

• Burner electro connection

Hoval Uno-3Oil / gas Boiler

as Boiler Uno-3 b-i but without burner andabsorber hood

Delivery• Boiler, insulation and casing will be packed

and delivered separately

At place• Mounting of insulation and casing

Uno-3 b-i OutputType kW

110 70-110125 70-125150 85-150175 95-175220 135-220250 150-250280 160-280320 192-320

Calorifier EWE

• Storage tank and heat exchanger out ofdouble enamelling

• Heat exchanger fixed• Calorifier Type 300-600 l• Built on the boiler• Magnesium anode• Insulation with CFC-free cellular plastic

heat insulation, 70 mm (λ=0.025W/mK)• Casing out of aluminium, red enamelled• Including temperature sensor

Loading group calorifier• Complete installed and wired

consists of:– Loading pump– Non-return valve– Piping and fittings

Delivery• Calorifier, insulation and casing, loading

group separately packed and delivered

At place• Mounting of insulation and casing

53

subject to alterations

Hoval Uno-3 (110-320)Boiler for oil / gas firingwith or without calorifier

Description

Control panel• Boiler without calorifier, control panel built

on the boiler• Boiler with calorifier, control panel placed

on the right or left side

Control panel with:• Main switch «on/off»• Boiler safety limit thermostat 110°C• Fuse 6.3A• Trouble indication „burner“• Plug connection for 2-stage Burner

1x230V• Change over switch nominal/maximal

output• Boiler sensors

Control panel with TopTronic regulator– For 1 or 2 mixing circuit– Operation switch– Temperature adjustment “Day/Night”– Adaption with micro computer– Automatic switch summer/winter– Heat temperature regulation– Calorifier loading control– Digital display– Burner running time meter and count-up

counter• Outside sensor AF 100N• Flow temperature sensor VF 100N

• Optional possibility for second regulator for1 or 2 additional mixing circuit

Control panel with thermostat

T2.1• wired version with external requirements

T0.1-110• unwired version with external alter

statement

Delivery• Control panel separately packed and

delivered

At place• Mouting of control panel

Heating armature groupType HA 226/326-40

• For systems with 1 heating group• For mounting right hand side• To Uno-3 (110,125) with TopTronic

regulator

• Complete installed and wiredconsists of:– Heating circuit pump and boiler circuit pump– Motorized 4-way-mixing valve– 2 ball valves– Non-return valve– Piping and fittings size 11/2“– Power supply HA 226 1x230V

HA 326 3x400V

Delivery• Heating armature group separately

packed and delivered

At place• Delivery and mounting of insulation

Heating armature groupType HA 228/328-50

• As heating armature group HA 226/326-40but size 2”

• To Uno-3 (150) with TopTronic regulator

Delivery• Heating armature group separately packed

and delivered

At place• Delivery and mounting of insulation

54

Subject to alterations

Hoval Uno-3 (110-320)

BoilerUno-3 b-i

3-pass-low temperature boiler with oil burnerand absorber hood, without control panel.Boiler, insulation, casing, burner and absorberhood separately packed and delivered.

Price

1082 (Typ 50 - 62)

1192 (Typ 80)

915 (Typ 50 - 62)

1025 (Typ 80)

125

360

150

4 x M8

1071,5

866

82,5

32,5

Ø149 -

10

31

710

Uno-3

Variante Fremdbrennerhaube 750(mit Füssen)

bi-Ausführung 530

480

495

772

761

638,5

450

151,5

450

574

7

8

9

13

5

1

26

4

2

Part no.

Uno-3 Output Working pressureType kW bar

110 70-110 3 1A22038

125 75-125 3 1A22039

150 85-150 3 1A220405 1A22041

175 95-175 4 1A221326 1A22134

220 135-220 4 1A221336 1A22135

250 150-250 4 1A220466 1A22047

280 126-280 4 1A220486 1A22049

320 145-320 4 1A22074

3-pass-low temperature boiler with oil burnerand absorber hood, without control panel.Boiler, insulation and casing separatelypacked and delivered.

Oil / gas boilerUno-3

Uno-3 WorkingBurner Output pressure

Type Type kW bar

b-i 110 BT14GW 70-110 3

b-i 125 BT14GW 75-125 35

b-i 150 SPARK18W 85-150 35

b-i 175 SPARK18W 95-175 46

b-i 220 SPARK26W 135-220 46

b-i 250 SPARK26W 150-250 46

b-i 280 SPARK35W 160-280 46

b-i 320 BT UO DSG 192-320 4

55

Subject to alterations

Hoval Uno-3 (110-320)

Price

BoilerUno-3 b-i (110-280) withbuilt on calorifier

Uno-3 WorkingBurner Output pressure

Type Type kW bar

b-i 110/450 BT14GW 70-110 3b-i 110/600 BT14GW 70-110 3

b-i 125/450 BT14GW 75-125 3b-i 125/600 BT14GW 75-125 3

b-i 150/600 SPARK18W 85-150 35

b-i 150/800 SPARK18W 85-150 35

b-i 175/600 SPARK18W 95-175 46

b-i 175/800 SPARK18W 95-175 46

b-i 220/600 SPARK26W 135-220 46

b-i 220/800 SPARK26W 135-220 46

b-i 250/600 SPARK35W 150-250 46

b-i 250/800 SPARK35W 150-250 46

b-i 280/600 BT40DSG 160-280 46

b-i 280/800 BT40DSG 160-280 46

Part no.

3-pass-low temperature boiler with oil burnerand absorber hood, without control panel.Calorifier made of double enamelling and builton the boiler.Boiler, insulation, casing, burner, calorifier andloading group separately packed anddelivered.

56

Subject to alterations

Hoval Uno-3 (110-320)

Price

Oil / Gas boilerUno-3 (110-280) withbuilt on calorifier

Part no.

Uno-3 Output Working pressureType kW bar

110/450 70-110 3 1A22050110/600 70-110 3 1A22051

125/450 75-125 3 1A22052

125/600 75-125 3 1A22053

150/600 85-150 3 1A220545 1A22055

150/800 85-150 3 1A220565 1A22057

175/600 95-175 4 1A240016 1A24005

175/800 95-175 4 1A240026 1A24006

220/600 135-220 4 1A240036 1A24007

220/800 135-220 4 1A240046 1A24008

250/600 150-250 4 1A220666 1A22067

250/800 150-250 4 1A220686 1A22069

280/600 160-280 4 1A220706 1A22071

280/800 160-280 4 1A220726 1A22073

3-pass-low temperature boiler with oil burnerand absorber hood, without control panel.Calorifier made of double enamelling and builton the boiler.Boiler, insulation, casing, calorifier and loadinggroup separately packed and delivered.

57

Subject to alterations

Hoval Uno-3 (110-320)

Price

Control panel with TopTronicregulator for Uno-3 with orwithout calorifier and 1 to 4mixing circuits.

Standard control panel:Part no.

Regulator set:

TopTronic 2B(without mixing circuit)Automatic regulation of boiler water temperaturefor heating systems with 1 stage burner,including sensors.

TopTronic 23B1 stage burner controlRegulation of 1 mixing circuit, 1 direct heatingcircuit without mixing valve and hot water loadingcircuit, incl. sensors.

TopTronic 223B2 stage burner controlRegulation of 1 mixing circuit, 1 direct heatingcircuit without mixing valve and hot water loadingcircuit, incl. sensors.

691238

TopTronic 203BModulating burner controlRegulation of 1 mixing circuit, 1 direct heatingcircuit without mixing valve and hot water loadingcircuit, incl. sensors.

691208

691494

691493

M3.1For external on/off and nominal/maximaloutput control with TopTronic or otherregulator. Boiler temperature sensor KT10 forregulation already integrated.

– with 7- + 4-pin plug connection for burnercontrol AW 4472

58

Subject to alterations

Hoval Uno-3 (110-320)

Price

Part no.

Additional regulator:

TopTronic 3for 1 additonal mixing circuit, including sensors.

TopTronic 233Bfor 2 additional mixing circuit, including sensors.

Additonal equipment ZM1Adapter set for second regulator.

TopTronic 233B1 stage burner controlRegulation of 2 mixing circuit, 1 direct heatingcircuit without mixing valve and hot water loadingcircuit, incl. sensors.

691335

691282

691138

691282

691435

TopTronic 2233B2 stage burner controlRegulation of 2 mixing circuit, 1 direct heatingcircuit without mixing valve and hot water loadingcircuit, incl. sensors.

59

Subject to alterations

Hoval Uno-3 (110-320)

Price

Thermostat control panel:(Optional to standard controlpanel with TopTronic regulator)

T 2.1 (Pre-wired solution)- for systems without TopTronic regulator- for direct 2 stage burner control- For external calorifier or external heating

commands

- 2 burner running hour meter- 2 burner running hour meter and count up

counter- Flue gas thermometer

T0.1-110 (for external control)- for systems without TopTronic regulator- for boiler cascade control- for special control units

Consitst of:- Main switch 0 / 1- Boiler temperature limiter 130°C- 3 boiler temperature guard 50-110°C- Without burner plug connection

- 2 burner running hour meter- 2 burner running hour meter and count up

counter- Flue gas thermometer

- Additional sensor for external TopTronicregulator

Part no.

AW 4473

AU 3323

AU 3324AU 3351

6001396

AW 4471

AU 2970

AU 3268AU 3351

60

Subject to alterations

Hoval Uno-3 (110-320)

Price

Accessories for heating controlsystem TopTronic

Part no.

Flow temperature guardRAM 342.001for floor heating incl. cable and plug

Flow temperature guardfor floor heating(per heating circuit 1 guard)- Thermostat with pocket 619.0015- Thermostat 692.1120

Sensor VF100N

Temperature sensor KT 10-40with 4 m cabel for calorifier or external heataquisition

Flue gas temperature sensor PT1000/4

Additional outer temperature sensorAF 100Nfor one mixing circuit (per heating circuit1 separate outer temperature sensor ispossible)

Room temperature sensor RF 40for one mixing circuit

Remote control RFF 60Sfor one mixing circuit with room sensor, easyprogram switch, tempreture adjustment

Room station RS 10for one mixing circuit with room sensor,information, program and correction key.

687997

242190242217

242647

242371

242681

242646

242679

2000754

242634

61

Subject to alterations

Hoval Uno-3 (110-320)

Price

Heating armature group

For systems with 1 heating group to Uno-3(110-150) with integrated TopTronic regulator

Part no.

Boiler PumpHA-Type Type Type

HA 328-50 150 LX 402 AW4503

HA-compact group, 1 Heating circuitØ 2“ with 4-way mixing valve

Boiler PumpHA-Type Type Type

HA 326-40 110-125 LX 323 AW4500

HA-326-328 with Pump 3x400 V

HA-compact group, 1 Heating circuitØ 1½“ with 4-way mixing valve

Boiler PumpHA-Type Type Type

HA 228-50 150 LX 402 AW4483

HA-compact group, 1 Heating circuitØ 2“ with 4-way mixing valve

Boiler PumpHA-Type Type Type

HA 226-40 110-125 LX 323 AW4480

HA-226-228 with pump 1x230 V

HA-compact group, 1 Heating circuitØ 1½“ with 4-way mixing valve

62

Subject to alterations

Hoval Uno-3 (110-320)

Price

HA-326-328 with Pump 3x400 VPart no.

Boiler PumpHA-Type Type Type

HA 328-50 150 LX 402 AW4503

HA-compact group, 1 Heating circuitØ 2“ with 4-way mixing valve

Boiler PumpHA-Type Type Type

HA 326-40 110-125 LX 323 AW4500

HA-compact group, 1 Heating circuitØ 1½“ with 4-way mixing valve

63

Subject to alterations

Hoval Uno-3 (110-320)

Price

Accessories Part no.

Walkable casingto Uno-3 (110-150)to Uno-3 (175-220)to Uno-3 (250-280)to Uno-3 (320)

638885638886638887638884

Flue gas thermometerØ 80–150 (mounting at place) 241133

Oil volume counter VZO 4Kwith filter (mounting at place) 6003163

Oil filter > 5,4 dm3/h OVENTROP 50-100 µ CG0107

Boiler door left swivelledto Uno-3 (110-320) AU3350

Flue gas collectorwith flow and return flow outlet, separatelydelivered (welded at place) ZY2863

To Uno-3 LengthType Size mm

110-175 and 110-125/450 1 100 239704220-280 and 110-125/600 2 150 239705150-280/600 and150-280/800 / 320 3 200 239706

Vibration elements for boiler socket4 vibration elements for the boiler socket,made of unvulcanized rubber. Diameter 80/50mm.

To Uno-3 with oil burnerType width height

110-125 (Out of plastic/steel plates) 530 780 6001077

110-125 (Steel plates) 750 780 638492150-320 (Steel plates) 800 910 637851

Absorber hood b-iOut of steel plates, red/orange powdercoated.

64

Subject to alterations

Hoval Uno-3 (110-320)

Price

Service

Commissioning

Part no.

65

Subject to alterations

Hoval Uno-3 (110-320)

Technical data

Uno-3

Type 110 125 150 175

• Nominal output kW1 110 125 150 175• Range of output kW 70-110 75-125 85-150 95-175• Maximum burner output kW 118,3 135,8 161,3 188,2

• Max. boiler working temperature 2 °C 110 110 110 110• Min. boiler working temperature °C 503 503 503 503

• Min. return flow temperature °C 383 383 383 383

• Min. flue gas temperature °C 130 130 130 130• Safety limit temperature °C 130 130 130 130• Working / test pressure bar 3,0/4,5 3,0/4,5 3,0/4,5 4,0/6,0

bar - 5,0/7,5 5,0/7,5 6,0/9,0

• Flue gas regulators for 160°C 3R5+ 9R3/290 6R5/290 6R5+ flue gas temperature 2R3/290 6R2/290• Boiler efficiency at 80/60°C % 91 90,2 89,2 90,1• Stand-by deficiency qB at 70°C Watt 400 440 440 570

• Flue gas resistance at nominal output 160°C flue gas temperature, 12.5% CO2 , 500m above sea level (+/- 20%) mbar 0,7 0,93 0,89 0,81• Flue gas mass flow at nominal output 12.5% CO2 Oil kg/h 188 222 257 299

• Flow resistance boiler 4 z-value 0,2 0,2 0,2 0,1• Water resistance at 10K mbar 17,90 25 33,28 22,65• Water resistance at 20K mbar 4,47 6,25 8,32 5,66• Water flow volume at 10K m³/h 9,46 11,18 12,9 15,05• Water flow volume at 20K m³/h 4,73 5,59 6,45 7,53

• Boiler water capacity Liter 250 250 270 362• Boiler gas volume m³ 0,1848 91848 0,236 0,322• Insulation boiler body mm 80 80 80 80• Weight (incl. casing) kg 391 391 495 635• Weight (incl. casing) 5 or 6 bar model kg - - 552 719

• Fire room dimension Ø x Length mm ø440x974 ø440x974 ø440x974 ø490x974• Fire room volume m³ 0,148 0,148 0,148 0,184

• Dimension width mm 780 910 780 910 (without burner and absorber hood) length mm 1536 1548 1536 1565

height mm 1255 1403 1255 1563

1 kW= Flue gas deficiency according to guidline LRV 92 (Boiler water 80°C)2 Limited to 90°C with control unit3 Valid by flue gas temperature 130°C4 Flow resistance boiler in mbar = volume flow (m3/h)2 x z

66

Subject to alterations

Hoval Uno-3 (110-320)

Technical data

Uno-3

Type 220 250 280 320

• Nominal output kW1 220 250 280 320• Range of output kW 135-220 150-250 160-286 145-320• Maximum burner output kW 236,6 269,1 303,4 344

• Max. boiler working temperature 2 °C 110 110 110 110• Min. boiler working temperature °C 503 503 653 653

• Min. return flow temperature °C 383 383 553 553

• Min. flue gas temperature °C 130 130 130 130• Safety limit temperature °C 130 130 130 130• Working / test pressure bar 4,0/6,0 4,0/6,0 4,0/6,0 4,0/6,0

bar 6,0/9,0 6,0/9,0 - -

• Flue gas regulators for 160 °C 9R5/290 6R5+3R3/290 6R5+3R3/290 - flue gas temperature• Boiler efficiency at 80/60°C % 92,6 92,8 93,1 93,2• Stand-by deficiency qB at 70°C Watt 570 610 670 670

• Flue gas resistance at nominal output 160°C flue gas temperature, 12.5% CO2 , 500 m above sea level (+/- 20%) 5 mbar 1,23 1,4 1,9 3,0• Flue gas mass flow at nominal output 12.5% CO2 oil kg/h 375 426 484 542

• Flow resistance boiler 4 z-value 0,1 0,1 0,1 0,022• Water resistance at 10K mbar 35,8 46,23 57,6 16,66• Water resistance at 20K mbar 8,95 11,56 14,4 4,17• Water flow volume at 10K m³/h 18,92 21,50 24,51 27,52• Water flow volume at 20K m³/h 9,46 10,75 12,26 13,76

• Boiler water capacity Liter 362 480 480 625• Boiler gas volume m³ 0,322 0,428 9428 0,402• Insulation boiler body mm 80 80 80 80• Weight (incl.casing) kg 635 880 880 920• Weight (incl. casing) 6 bar modell kg 719 1023 1023 -

• Fire room dimensions Ø x Length mm ø490x974 ø488x1434 ø488x1434 ø488x1634• Fire room volume m³ 0.184 0.268 0.268 0.3056

• Dimension width mm 910 910 910 910 (without burner and absorber hood) length mm 1565 2050 2050 2147

height mm 1563 1563 1563 1563

1 kW= Flue gas deficiency according to guidline LRV 92 (Boiler water 80°C)2 Limited to 90°C with control unit3 Valid by flue gas temperature 130°C4 Durchflusswiderstand Heizkessel in mbar = Volumenstrom (m3/h)2 x z

(in the case of gas firing the min. return flowtemperature must be 10°C higher thanmentioned above)

}

67

Subject to alterations

Hoval Uno-3 (110-320)

Technical data

Calorifier EWE

Type 450 600 800

• Volume dm3 450 600 810• Working / test pressure bar 10 / 15 10 / 15 10 / 15• Max. working temperature °C 75 75 75• Insulation mm 70 70 70• Thermal conductivity λ Watt/mK 0,025 0,025 0,025• Weight without insulation kg 182 231 348• Anode Correx Correx Correx

• Dimension diameter mm Ø 700 Ø 700 Ø 780without insulation length mm 1539 1946 2165

Heating register• Heating surface m2 2,4 3,4 5,2• Loading pump Biral type M13-2 M15-2 M15-2• Flow 1 m³/h 2,8 3,8 5,5• Working / test pressure bar 10 / 15 10 / 15 10 / 15• Working temperature °C 90 90 90

Hot water capacity EWE with Uno-3, flow 80°C

Stand-byUno-3 / EWE Hot water capacity Weight deficiency

dm3/10 min 1 dm3/h 2 dm3/h 2 Flow Flats Uno-3 with EWE qB (70°C)Type 45°C 45°C 60°C kW 5 m³/h Quantity3 kg Watt 4

b-i (110-125) 450 580 1450 830 59 2,8 14 632 510b-i (110-125) 600 780 2080 1110 85 3,8 24 688 550

b-i (150) 600 780 2080 1110 85 3,8 24 797/854 6 590b-i (150) 800 1020 3080 1680 126 5,5 36 927/984 6 630

b-i (175) 600 780 2080 1110 85 3,8 24 955/1039 7 720b-i (175) 800 1020 3080 1680 126 5,5 36 1085/1169 7 760

b-i (220) 600 780 2080 1110 85 3,8 24 955/1039 7 720b-i (220) 800 1020 3080 1680 126 5,5 36 1085/1169 7 760

b-i (250-280) 600 780 2080 1110 85 3,8 24 1200/1343 7 760b-i (250-280) 800 1020 3080 1680 126 5,5 36 1330/1473 7 800

1 Max. hot water capacity in 10 min, according to Procal tests.Calorifier temperature 60°C

2 Hot water continuous output per hourCold water 10°C, Boiler water temperature 80°C

3 Flat (3–4 rooms for 3-4 Persons)4 Uno-3 and EWE without loading line5 Power consumption at 45/10°C(min. required boiler output)

6 Working pressure 3/5 bar7 Working pressure 4/6 bar

68

Subject to alterations

Hoval Uno-3 (110-320)

Heating armature group Uno-3 (110-150)

Flow resistance Uno-3 (110-150) with HA-group

HA-group Boiler circuit 1 Heating circuit 2

Ø z z

1½’’ 2,4 1,272’’ 1,48 0,51

1 Pump boiler circuit = 2 Pump heating circuit =flow resistance of flow resistance in the mixing ball

valve (without heating circuit)HA-group incl. boiler

mbar = (m3/h)2 x z

mbar = flow resistancem3/h = volume flow

Technical data

Oil burner 1-stage to Uno-3 b-i110 b-i 125 b-i 150 b-i 175

• Burner Type BT14GW BT14GW SPARK18W SPARK18W• Output kW 75-121 75-137 91-165 102-192• Fuel consumption kg/h 10,25 11,60 14,00 16,25

Oil burner 1-stage to Uno-3 b-i 220 b-i 250 b-i 280

• Burner Type SPARK26W SPARK 26W SPARK35W• Output kW 145-242 161-275 172-308• Fuel consumption kg/h 20,50 23,25 26,05

Oil burner 2-stage to Uno-3 b-i 320

• Burner Type BT40DSG• Output kW 206-352• Fuel consumption kg/h 29,80/20,85

69

Subject to alterations

Hoval Uno-3 (110-320)

Uno-3 b-i (110-280)

Dimension

Uno-3 b-i (320)

1 Flow DN 50 PN6 (110-150) DN 65 PN6 (175-280)2 Return3 Safety flow (expansion) R1 1/4" (110-125) R1 1/2" (150-280)4 Flow for calorifier R1 1/4"5 Return for calorifier R1 1/4"6 Drain R1" (110-125) R1 1/2" (150-280)7 Flue gas outlet Ø outer,

8 Cleaning opening 9 Control panel: 110-125 => built on

150 - 320 => optional10 Socket: width 50 mm11 Boiler door right swivelled (optional left swivelled)12 Flue gas collector-cleaning opening R1" (110-280 )13 Optional vibration damper, width 80 mm, height 50 mm14 Absorber hood (b-i version)

Uno-3 l b h a d e f g i k m n o p q r s t uType Ø

110-125 1328 780 1050 680 87 400 140 170;4xM8 140 545 799 980 250 – 179 130 1080 104 233150 1411 910 1198 680 50 450 190 220/270;4xM10 220 680 863 1072 265 546 179 158 1080 81 137175-220 1431 910 1358 750 50 450 240 270;4xM10 195 675 950 1218 310 621 199 178 1080 81 134250-280 1916 910 1358 750 50 450 240 270;4xM10 195 675 950 1218 310 596 249 178 1535 76 134

}

d

7

9

7

lts

2

8

11

13

u

v

12 12

6

7

5q

4

10

205

205

i

g

e

800

860

1210 388

h

a

b

k

mf

b

Uno-3 l b h a d e f g i k m q* s t u vType Ø

320 2070 910 1358 750 50 450 240 270:4xM10 195 684 1100 249 178 1736 77 123

1 Flow DN 80, PN 62 Return DN 80, PN 63 Thermostat - Pocket 3/4"4 Drain R 1 1/2"5 Flue gas outlet Ø outer,6 Cleaning opening 455/95 mm

7 Control panel right/left or built on8 Socket, width 50 mm9 Boiler door right swivelled (optional left

swivelled)10 Flue gas collector - cleaning opening R1"

11 Absorber hood (b-i version)12 Optional vibration damper, width 80 mm,

height 50 mm

70

Subject to alterations

Hoval Uno-3 (110-320)

Dimension

Uno-3 (110-280) with built-on calorifier

1 Flow DN 50 PN6 (110-150) DN 65 PN6 (175-280)2 Return3 Safety flow R1 1/4" (110-125) R 1 1/2" (150-280)4 Drain5 Flow calorifier6 Return calorifier7 Cold water 450, 600 R1 1/2"8 Hot water 800 R 2"9 Circulation R1"

10 Flue gas outlet Ø outer11 Cleaning opening12 Control panel optional right or left13 Boiler door right swivelled (optional left swivelled)14 Flue gas collecter - cleaning opening R1"15 Optional vibration damper, width 80 mm, height 50 mm16 Absorber hood (b-i version)

Uno-3/EWE l1 l2 l3 h1 h2 h3 a b1 b2 c d e f g1 g2 i k m n

110-125/450 2050 1581 1328 1050 1500 1935 680 780 870 87 400 140 170:4xM8 140 – 545 799 980 1280110-125/600 2050 2010 1328 1050 1500 1935 680 780 870 87 400 140 170:4xM8 140 – 545 799 980 1280150/600 2370 2010 1410 1198 1648 2078 680 910 870 50 450 190 220:4xM8 220 546 680 863 1072 1428150/800 2370 2010 1410 1198 1702 2182 680 910 960 50 450 190 220:4xM8 220 546 680 863 1072 1422

175-220/600 2390 2010 1430 1358 1808 2238 750 910 870 50 450 240 270:4xM10 195 621 675 950 1218 1588175-220/800 2390 2210 1430 1358 1862 2342 750 910 960 50 450 240 270:4xM10 195 621 675 950 1218 1582250-280/600 2865 2010 1915 1358 1808 2238 750 910 870 50 450 240 270:4xM10 195 596 675 950 1218 1588250-280/800 2865 2210 1915 1358 1862 2342 750 910 960 50 450 240 270:4xM10 195 596 675 950 1218 1582

Uno-3/EWE o p q r s t Øu v w x1 x2 y z

110-125-/450 150 155 135 50 250 185 179 118 1080 27 35 192 104110-125/600 150 155 135 50 250 185 179 118 1080 27 40 192 104150/600 150 155 135 50 265 185 179 158 1080 67 40 137 81150/800 195 155 210 85 265 185 179 158 1080 67 40 137 81

175-220/600 150 155 135 50 310 185 199 178 1080 67 40 134 81175-220/800 195 155 210 85 310 185 199 178 1080 67 50 134 81250-280/600 150 155 135 50 310 185 249 178 1535 42 40 134 78250-280/800 195 155 210 85 310 185 249 178 1535 42 50 134 78

}

71

Subject to alterations

Hoval Uno-3 (110-320)

B

H1

L2

L1

Base size and space requirement

Lengthwith flue without flue

Uno-3 Width gas collector gas collector Height WeightType B L1 L2 H kg

110-125 680 1513 1080 1084 350150 680 1515 1210 1180 430

175-220 750 1535 1230 1335 530 250-280 750 2015 1685 1335 760

Uno-3Type Width Length Length Height Weight

B L1 L2 H kg

320 750 2114 1886 1481 800

Uno-3 (320)

Uno-3 (110-280) Boiler with built on calorifier

Uno-3/EWE B1 B2 H1 H2 H3 H4 L1 L2 L3 L4

110-125/450 680 700 1084 1500 1906 900 1513 1080 1539 1691110-125/600 680 700 1084 1500 1906 900 1513 1080 1964 2116

150/600 680 700 1180 1648 2054 900 1565 1260 1946 2042150/800 680 780 1180 1702 2148 995 1565 1260 2165 2250

175-220/600 750 700 1335 1808 2214 900 1585 1280 1946 2062175-220/800 750 780 1335 1862 2308 995 1585 1280 2165 2270250-280/600 750 700 1335 1808 2214 900 2065 1735 1946 2062250-280/800 750 780 1335 1862 2308 995 2065 1735 2165 2270

Uno-3 (110-280) boiler without calorifier

B2

H4

H3

H2

B1

L4

L3

H1

L2

L1

B

H

L2L1

Attention• The calorifier will be packed and delivered

separately and must be mounted at place• Optional flue gas collector and boiler outlet

will be delivered separately

WeightUno-3/EWE kg

110-125/450 532110-125/600 581

150/600 661150/800 778

175-220/600 761175-220/800 878250-280/600 991250-280/800 1108

72

Subject to alterations

Hoval Uno-3 (110-320)

ba

d

c

Base size and space requirement

Required min. door and corridormeasurement(min. calculated measurements)

BK = x L

T

BT = x L

K

Examples:Door width T = 800

Uno-3 110-125 K = 680 x 1513 = Corridor width > 1286800

Uno-3 150 K = 750 x 1515 = Corridor width > 1421800

Uno-3 175 - 220 K = 750 x 1535 = Corridor width > 1439800

Uno-3 250-280 K = 750 x 2015 = Corridor width > 1890800

Uno-3 320 K = 750 x 2114 = Corridor width > 1982800

T = Door widthK = Corridor widthB = Boiler widthL = Max. boiler length

Absorber hoodType a b c d Burner

Uno-3 b-i (110) 449 530 558 541Uno-3 b-i (125) 404 530 558 496Uno-3 b-i (150) 433 830 584 511Uno-3 b-i (175) 433 830 602 539

Uno-3 b-i (220) 667 830 606 775Uno-3 b-i (250) 667 830 606 775Uno-3 b-i (280) 667 830 606 775Uno-3 b-i (320) 772 830 606 830

K

T

< 150B

L

Boiler door swivelling and absorber hood dimension

73

Subject to alterations

Hoval Uno-3 (110-320)

1 Transport plate (not incl.)2 Pipes as rolls (not incl.)

3 Boiler door (dismountable)4 Door mounting

Boiler height

with flue without flueUno-3 gas collector gas collector Width LengthType H1 H2 B L

110-125 1513 1080 680 1084150 1515 1210 680 1180175-220 1535 1230 750 1335250-280 2015 1685 750 1335320 2114 1886 750 1481

Minimum placing dimensionBoiler verticalBoiler without calorifier, transport with rolls

Measurments boiler door

Example

Door T = 800

Uno-3 110-125 K = 680 x 1084 = corridor width > 922800

Uno-3 150 K = 680 x 1180 = corridor width > 1003800

Uno-3 175 - 280 K = 750 x 1335 = corridor width > 1252800

Uno-3 320 K = 750 x 1481 = corridor width > 1389800

Uno-3 Floor distance

Max. width with boiler door without boiler doorType a b c

110-125 490 50 175150-280 540 50 195320 540 50 195

Base size and space requirement

74

Subject to alterations

Hoval Uno-3 (110-320)

a c

b

d

e

480160

f

120

d

a

b

c

e

462160

120

f

Dimension with heating groups

Uno-3 (110-125) Uno-3 (110-125/EWE 450/600)HA 226-40, HA 326-40

Pump DimensionBoiler circuit Heating circuit a b c d e fVL + RL

LX 323 LX 323 1676 545 435 203 250 295 1 1/2"or LX 325 1676 545 435 213 250 295 1 1/2"LX 325 LX 326 1676 545 435 213 250 295 1 1/2"

HX 321 1676 545 435 213 250 295 1 1/2"HX 322 1676 545 435 213 250 295 1 1/2"LXE 326 1676 545 435 213 250 295 1 1/2"

Uno-3 (110-125) Uno-3 (110-125/EWE 450/600)HA 227-50, HA 327-50

Pump DimensionBoiler Heating a b c d e f Flow+circuit circuit Return

LX 401 LX 401 1709 545 435 190 250 282 2"LX 402 1709 545 435 190 250 282 2"LX 403 1739 545 435 190 250 282 2"LX 504 1759 545 435 190 250 282 2"HX 402 1709 545 435 190 250 282 2"HX 501 1759 545 435 190 250 282 2"LXE 403 1739 545 435 190 250 282 2"LXE 504 1759 545 435 190 250 282 2"

Uno-3 b-i (110-125) / Uno-3 (110-125)with calorifier.

75

Subject to alterations

Hoval Uno-3 (110-320)

Dimension with heating armature group

Uno-3 (150) Uno-3 (150/EWE 600/800)HA 228-50, HA 328-50

Pump DimensionBoiler Heating a b c d e f Flow+circuit circuit Return

LX 402 LX 401 1801 680 392 125 265 229 2"LX 402 1801 680 392 125 265 229 2"LX 403 1831 680 392 125 265 229 2"LX 504 1851 680 392 125 265 229 2"HX 402 1801 680 392 125 265 229 2"HX 501 1851 680 392 125 265 229 2"HX 502 1851 680 392 125 265 229 2"LXE 403 1831 680 392 125 265 229 2"LXE 504 1851 680 392 125 265 229 2"

e

d

a

b

c

409205

64

f

Uno-3 b-i (150) / Uno-3 (150)with calorifier

76

Subject to alterations

Hoval Uno-3 (110-320)

Flue gas / output diagram

Boiler water 80/60°C

Flue gas regulators

Uno-3 Type 110 / b-i 110Regulators 3R5+2R3/290

Uno-3 Type 150 / b-i 150 Uno-3 Type 175 / b-i 175 Uno-3 Type 220 / b-i 220 Uno-3 Type 250 / b-i 250Regulators 6 R5/290 Regulators 6R5+6R2/290 Regulators 9R5/290 Regulatos 6R5+3R3/290

Uno-3 320no regulators required

kW = Boiler output°C = Flue gas temperature, Boiler water

temperature 80°C (DIN 4702).

- Operated with oil EL,λ = 1,22 with max. burner output(CO2 Oil EL = 12,5 %)

Uno-3 Type 280/b-i 280= as Uno-3 250

Uno-3 Type 125 / b-i 125= as Uno-3 110

100

110

120

130

140

150

160

170

180

50 100 150 200 250 300 350

kW

°C110

125150

175 220

250

280

320

oo

100

110

120

130

140

150

160

170

180

190

200

210

220

230

240

50 100 150 200 250 300 350

kW

°C

125

150

175 220

250

280

320

110 o

o

withflue gas regulators

withoutflue gasregulators

77

Subject to alterations

Hoval Uno-3 (110-320)

Standards and GuidelinesFollowing standards and guidelines must berespected:

- Technical information and installationmanual of company Hoval

- Hydraulic and technical control regulationsof the local gas supply authority

- Firing guidelines of local gas works

- Fire protection standards

- Gas directives G1 of the SVGW

- Directives SWKI 97-1 «Water treatment forheating, steam and air conditioninginstallations»

- Ventilation and air supply for the boilerinstallation room according to directivesSWIKI 91-1

- Directives SWKI- 93-1 „Safety equipmentfor heating systems“.

- Directives Procal/FKR "Electric plugconnections at heating boilers and burners".

- Procal Data Sheet "Corrosion throughhalogen compounds".

- Procal Data sheet "Corrosion damage inheating installations" and the brochure"Protectionagainst corrosion and boilerscale formation in heating and service waterinstallation".

Water treatment- Old installations must be well flushed before

filling.

- The water quality must be tested at leastonce a year

Heating systemCombustion Air- The combustion air supply must be

warranted. Opening must not be lockable.

- Minimal free cross section for air opening6.5 cm2 per 1 kW boiler output.

Insulation and Casing- To mount the insulation and casing you

need about 40 cm space on the left andright side. After the boiler is cased nospace on the side is required.

- 2 boiler can be placed with out spacebetween them. (The door of the left boilermust swivelling to the left and the the rightdoor to the right).

Heating armature group- Min. volume of mixing valve:

H4G-1½’’ = 1,5 m³/h,H4G 2’’ = 2,2 m³/h.

Oil burner mounting- The burner connection plug must be

mounted opposite the burner door hinges.

- It should be possible to swivel the boilerdoor incl. burner by 90°.

- The space between burner and boiler doormust be insulated by the additional deliveredinsulation material

Electric connection of the burner- 1 x 230 V, 50 Hz, 10 A.

- For safety reasons the electric cable ofthe burner must be that short that the plugmust be removed when swivelling boilerdoor.

Sound absorbationSound absorbation is possible through thefollowing steps:

- Walls, ceilings and floor should be verysolidly built, a sound absorber should bemounted into the air inlet. Pipe holders andsupport should be protected by means ofanti-vibration sleeves.

- Install sound absorber hood for burner.

- If living rooms are located above or underthe boiler room, vibration absorbers have tobe mounted to the boiler base. Pipes and

Engineering

flue gas tube must be connected flexiblewith compensators.

- Pumps have to be connected withcompensators to the pipes.

- For damping of flame noise it is possible toinstall a silencer into the flue gas tube(Space should be foreseen for laterinstallation).

78

Subject to alterations

Hoval Uno-3 (110-320)

Chimney / Flue gas system

Flue gas tube- The flue gas tube must be led into the

chimney with an angle of 30-45 °.- If the flue gas tube is longer then 1m, it

must be insulated.- The inlet of the flue gas tube into the

chimney has to be carried out in such away, that no condensate can flow from thechimney into the flue gas tube and boiler

Chimney- The chimney must be water proof, acid

resistant and suitable for flue gastemperature > 160°C

- For existing chimney installation therestoration must be carried out accordingto the instructions of the chimneyconstructor.

- The cross sections are to be calculated forboilers without draft requirements

Required chimney diameterBasic: Smooth chimneys made of stainlesssteel, Flue gas tube < 2,5 m,Σζ = 2,2, flue gas tube and chimney insulated.Height above sea level < 1000 m,Outside temperature < 30°C.

Height Chimney and flue gas tube Ø mm

25 m 175 175 175 175 200 225 225 25020 m 175 175 175 200 200 225 225 25015 m 175 175 175 200 225 225 250 250

10 m 175 175 200 200 225 225 250 300 5 m 175 175 200 200 225 250 300 300

Uno-3 Type 110 125 150 175 220 250 280 320

m =Chimney height

Engineering

D

2 x D 1D

< 2D

D

- A closeable flue gas measuring socket withan inner diameter of 10-21 mm must beforeseen.

79

Subject to alterations

Hoval Uno-3 (110-320)

Piping

- The boiler Uno-3 can only be used for 1line systems. Maximum suction heightwithoutpump 3.5m, maximum lenght of pipe system40m.

- The pipes must be fitted that the boiler doorcan be swivelled by 90°.

- At the end of the fixed piping a shut off valvemust be installed (by „Oventrop“ filteralready included).

- A filter (20-40 µ) must be installed in frontof the burner in the piping.

- The highest point of the piping should bemax. 3.5m above the tank suction pipe.

- The piping must be installed that no fluidcan get into the pipes, when the system isnot working.

- If the highest oil level in the tank is higherthan the lowest point of the piping system,

max.3.5 m

5

1

2

45 35

H

5 55

6

max.3.5 m

2

1

45 3

Max. oil level higher than the lowestpoint of the pipe system

Max. oil level lower than the lowestpoint of the pipe system

1 Hoval-burner for 1-line connection withreturn flow.

2 Oil pump3 Burner oil hoses4 Filter with filter element 20 - 40 µ5 Shut-off valve

a solenoid valve must be installed at thehighest point of the system (next to the oiltank).

6 Solenoid valve

H = Suction height [m] (system with max. 4bows, 1 shut-off valve with non returnvalve. Height above sea levelmax. 1000 m)

Engineering

1 Line system, max. pipe length in mm

Pipe Ø inside 6/8 mm

H Uno- 3 Type

m 110 125 150 175 220 250 280 320

1.5 25 22 18 16 12 11 9 82.0 18 15 14 12 9 8 7 -2.5 12 10 10 8 6 6 - -3.0 6 - - - - - - -

Pipe Ø inside 8/10 mm Pipe Ø inside 10/12 mm

H Uno- 3 Type H Uno- 3 Type

m 110 125 150 175 220 250 280 320 m 110 125 150 175 220 250 280 320

1.5 - - - 30 30 30 30 28 1.5 - - - - - - - -2.0 - 30 30 30 30 27 24 21 2.0 - - - - - - - -2.5 30 30 30 28 22 19 17 15 2.5 - - - - 30 30 30 303.0 25 22 19 16 13 11 10 8 3.0 30 30 30 30 31 28 24 21

H = suction height [m] (system with max. 4bows, 1 shut-off valve with non returnvalve. Height above sea level max. 1000 m)

80

Subject to alterations

Hoval Uno-3 (110-320)

Expansion tank- If a 4 way mixing valve is used in your

system, you have to install an expansiontank

- In the case of a system with openexpansion tank, it must be assured that thepressure in the suction pipe of the pump willbe not lower than allowed.

Safety valve- At the safety flow a safety valve must be

installed.

Sanitary installation- The installation must be carried out

according to the regulation of local waterworks.

- Pressure safety limit max 8 bar.

Example for sanitaryconnection

1 Cold water2 Hot water3 Op. circulation

4 Drain5 Height

min. 300 mm6 Anode

Engineering

62

3

15

4

81

Subject to alterations

Hoval Uno-3 (110-320)

Assembly andmounting on-site

Assembly and mounting on-site Uno-3 (150-320)

At a favourable all inclusive price Hoval offerson-site assembly of boiler in complete ofcomponent form as well as mounting in boilerroom ready to be connected. Mountingaccording to the strict quality standards of theassembly department.

• In case of an order, please add in yourorder „assembly and mounting on site“

• Prices on request

Boiler front with fire room cylinder 1

Uno-3Type a b c d kg

150 680 1155 1140 807 130175-220 750 1145 1275 867 160250-280 750 1606 1275 867 230320 750 1649 1275 867 250

Water wall 2

Uno-3Type e f g kg

150 632 1030 911 110175-220 734 1030 1094 160250-280 738 1490 1092 280320 738 1690 1092 318

Calorifier 6

Type h i kgØ

600 1946 700 231800 2165 780 348

1 Front plate with fireroom cylinder

2 Water walls3 Boiler door4 Boiler back wall5 Flue gas collector,

detachable6 Calorifier

3

4

12

Dimension and weight

d

c

a b

1

5

ef

g

2

i

h

6

82

Subject to alterations

Hoval Uno-3 (110-320)

Assembly andmounting on-site

Place requirement for assembly and mounting on-site

BoilerUno-3 Min. room dimenson

Type Length Width Height

150-175 1800 2000 2000

220-280 2000 2000 2100

320 2400 2200 2300