inSTaLLaTion and mainTenanCe inSTruCTionS
Selectable output Strobes, Horns, and Horn/Strobes3825 Ohio Avenue, St. Charles, Illinois 60174
800/736-7672, FAX: 630/377-6495www.systemsensor.com
D690-03-00 1 I56-2769-015R
For use with the following models: P2R, P2RH, P2RK, P2RHK, P2W, P2WK, P2WH, P2WHK, P4R, P4RH, P4RK, P4W, P4WK, P4WHK, SR, SRH, SRK, SRHK, SW, SWK, SWH, SWHK, SW-CLR-ALERT, PC2R, PC2RH,PC2RK, PC2RHK, PC2W, PC2WK, PC2WH, PC2WHK, PC4R, PC4RH, PC4W, PC4WK, PC4WHK, SCR, SCRH, SCRK, SCRHK, SCW, SCWK, SCWH, SCWHK, SCW-CLR-ALERT, HR, HRK, HW, SR-P, SW-P, SRH-P, SWH-P,P2R-P, P2W-P, P2WH-P, P4W-P, SCW-P, PC2R-P, PC2W-P, PC2WH-P, SRK-P, SRHK-P, P2RK-P, P2RHK-P, SWK-P, SWHK-P, P2WK-P, P2WHK-P, SR-SP, P2R-SP, PC2W-SP, SRK-R, SWK-R, SRHK-R, SWHK-R, P2RK-R, P2WK-R, P2RHK-R, P2WHK-RNOTE: All -R models are specifically designed for use with the WTP Series of Weatherproof platesNOTE: When replacing outdoor units; device and back box must be replacedproduCT SpeCiFiCaTionS
Operating Temperature: Standard Products 32°F to 120°F (0°C to 49°C)
K Series –40°F to 151°F
Humidity Range: Standard Products 10 to 93% Non-condensing
K Series Meets NEMA 4X requirements
Strobe Flash Rate: 1 flash per second
Nominal Voltage: Regulated 12VDC/FWR or regulated 24DC/FWR
Operating Voltage Range (includes fire alarm panels with built in sync): 8 to 17.5V (12V nominal) or 16 to 33V (24V nominal)
Operating Voltage with MDL Sync Module: 9 to 17.5V (12V nominal) or 17 to 33V (24V nominal)
Input terminal wire gauge: 12 to 18 AWG
NOTE : Strobes will operate at 12 V nominal for 15 & 15/75 candela settings only. Switching between ranges is automatic.dimenSionS For produCTS and aCCeSSorieS
WALL PRODUCTS LENGTH WIDTH DEPTH CEILING PRODUCTS DIAMETER DEPTH
Strobes and Horn/Strobes(including lens)
5.6˝ 4.7˝ 2.5˝ Strobes and Horn/Strobes(including lens)
6.8˝ 2.5˝
142 mm 119 mm 64 mm 173 mm 64 mm
Horns5.6˝ 4.7˝ 1.3˝ SA-WBBC Weatherproof Back Box
SA-WBBCW Weatherproof Back Box7.1˝ 2.0˝
142 mm 119 mm 33 mm 180 mm 51 mm
SA-WBB Weatherproof Back BoxSA-WBBW Weatherproof Back Box
5.7˝ 5.1˝ 2.0˝ BBSC-2BBSCW-2Back Box Skirt
7.1˝ 2.2˝
145 mm 130 mm 51 mm 180 mm 57 mm
BBS-2BBSW-2Back Box Skirt
5.0˝ 5.9˝ 2.2˝NOTE: SA-WBB, SA-WBBW, SA-WBBC and SA-WBBCW dimensions do not include the two mounting tabs130 mm 152 mm 57 mm
mounTing box opTionS
2-Wire Indoor Products 4-Wire Indoor Products K Series Products
4 × 4 × 11/2, Single Gang, Double Gang, 4˝ Octagon 4 × 4 × 11/2, Double Gang, 4˝ Octagon SA-WBB/W (wall), SA-WBBC/CW (ceiling)
generaL deSCripTionThe SpectrAlert Advance series of notification appliances offers a wide range of horns, strobes, and horn/strobes, for wall and ceiling applications, indoors and outdoors. They are designed to be used in 12 or 24 volt, DC or FWR (full wave rectified) systems. These products are electrically backward compat-ible with the previous generation of SpectrAlert notification appliances. Horn/strobe products are available in two versions. The 2-wire products fit systems where a single NAC controls both horn and strobe. The 4-wire products are in-tended for systems which have separate wiring circuits for the horn and strobe. All SpectrAlert Advance products are suitable for use in synchronized systems. The System Sensor MDL module may be used to provide synchronization.
K Series products are designed to be used over a wider range of temperatures and are suitable for use in wet locations.
Wall and ceiling products may be used interchangeably (wall products may be used on the ceiling and ceiling products may be used on the wall.)
Fire aLarm SYSTem ConSideraTionSThe National Fire Alarm Code, NFPA 72, requires that all horns, used for building evacuation produce temporal coded signals. Signals other than those used for evacuation purposes do not have to produce the temporal coded sig-nal. System Sensor recommends spacing notification appliances in compli-ance with NFPA 72.
Loop deSign and WiringThe system designer must make sure that the total current drawn by the de-vices on the loop does not exceed the current capability of the panel supply, and that the last device on the circuit is operated within its rated voltage. The current draw information for making these calculations can be found in the tables within this manual. For convenience and accuracy, use the voltage drop calculator on the System Sensor website (www.systemsensor.com) or CD-ROM.
When calculating the voltage available to the last device, it is necessary to consider the voltage drop due to the resistance of the wire. The thicker the wire, the smaller the voltage drop. Wire resistance tables can be obtained from electrical handbooks. Note that if Class A wiring is installed, the wire length may be up to twice as long as it would be for circuits that are not fault tolerant.
NOTE: The total number of strobes on a single NAC must not exceed 40 for 24 volt applications or 12 for 12 volt applications. Loop resistance on a single NAC should not exceed 120 ohms for 24 volt and 30 ohms for 12 volt systems.
For 4-Wire installations, terminals 1, 2, and 3 connect to the strobe; terminals 4 and 5 connect to the horn. The horn and strobe circuits must be wired in-dependently, and each circuit must be terminated with the appropriate EOL device. Removal of a notification device will result in an open circuit indica-tion on the strobe loop.
I56-2769-015R
NOTICE: This manual shall be left with the owner/user of this equipment.
D690-03-00 2 I56-2769-015R
Figure 1. Wiring 2-Wire produCTS:
+ –
+ –
INPUT FROM FACPOR PRIOR DEVICE
OUTPUT TO NEXTDEVICE OR EOL
A0367-01Figure 2. Wiring 4-Wire produCTS:
+–
INPUT FROM FACP OR PRIOR STROBE
INPUT FROMFACP OR PRIOR HORN
+–
+–+–
OUTPUT TO NEXT STROBE OR EOL
OUTPUT TO NEXT HORN OR EOL
A0366-00Figure 3. SHorTing Spring:
SHORTING SPRING
A0368-00NOTE: A shorting spring is provided between terminals 2 and 3 of the mount-ing plate to enable wiring checks after the system has been wired, but prior to installation of the final product. This spring will automatically disengage when the product is installed, to enable supervision of the final system.
CandeLa SeLeCTionAdjust the slide switch on the rear of the product to position the desired can-dela setting in the small window on the front of the unit. All products meet the light output profiles specified in the appropriate UL Standards. For K series products used outdoors at low temperatures, listed candela ratings must be re-duced in accordance with Table 2. Use Table 1 to determine the current draw for each candela setting. WIRING DIAGRAMS
NOTE: SpectrAlert products set at 15 and 15/75 candela automatically work on either 12V or 24V power supplies. The products are not listed for 12V op-erating voltages when set to any other candela settings. For 4-Wire products, total current draw may be determined by adding current draw for the specific candela selection in Table 1 with the current draw for the specific horn selec-tion in Table 3.
TabLe 1. STrobe CurrenT draW ( ) For S, SC, p4 & pC4 SerieS:
Candela8–17.5 Volts 16–33 VoltsDC FWR DC FWR
Standard Candela Range 15 123 128 66 7115/75 142 148 77 81
30 NA NA 94 9675 NA NA 158 15395 NA NA 181 176110 NA NA 202 195115 NA NA 210 205
High Candela Range 135 NA NA 228 207150 NA NA 246 220177 NA NA 281 251185 NA NA 286 258
TabLe 2. CandeLa deraTing:
Listed CandelaCandela rating at –40°F
(K Series Outdoor Applications Only)15
Do not use below 32°F15/753075 4495 70110 110115 115135 135150 150177 177185 185
Horn SeLeCTionTurn the rotary switch on the back of the product to the desired setting. For horn and 4-wire horn/strobe products, the current draw for each setting is listed in Table 3. For 2-wire horn/strobe products (P2 series), current draws are listed in Tables 4 and 5. The sound output measurement for each horn setting is shown in Table 6.
TabLe 3. Horn CurrenT draW ( ) For H, p4 & pC4 SerieS:
Pos Sound Pattern dA Out8–17.5 Volts 16–33 Volts
DC FWR DC FWR1 Temporal High 57 55 69 752 Temporal Medium 44 49 58 693 Temporal Low 38 44 44 484 Non-temporal High 57 56 69 755 Non-temporal Medium 42 50 60 696 Non-temporal Low 41 44 50 507 Coded High 57 55 69 758 Coded Medium 44 51 56 699 Coded Low 40 46 52 50
NOTE: In positions 7, 8, and 9, temporal coding must be provided by the NAC. If the NAC voltage is held constant, the horn output will remain constantly on. Positions 7, 8, and 9 are not available on 2-wire horn/strobe products.
ma
ma
TabLe 4. 2-Wire Horn/STrobe CurrenT draW ( ) For p2 and pC2 STandard CandeLa SerieS:
DC Input8–17.5 Volts 16–33 Volts
15 cd 15/75 cd 15 cd 15/75 cd 30 cd 75 cd 95 cd 110 cd 115 cdTemporal High 137 147 79 90 107 176 194 212 218Temporal Medium 132 144 69 80 97 157 182 201 210Temporal Low 132 143 66 77 93 154 179 198 207Non-temporal High 141 152 91 100 116 176 201 221 229Non-temporal Medium 133 145 75 85 102 163 187 207 216Non-temporal Low 131 144 68 79 96 156 182 201 210FWR InputTemporal High 136 155 88 97 112 168 190 210 218Temporal Medium 129 152 78 88 103 160 184 202 206Temporal Low 129 151 76 86 101 160 184 194 201Non-temporal High 142 161 103 112 126 181 203 221 229Non-temporal Medium 134 155 85 95 110 166 189 208 216Non-temporal Low 132 154 80 90 105 161 184 202 211
TabLe 5. 2-Wire Horn/STrobe CurrenT draW ( ) For p2 and pC2 HigH CandeLa range SerieS:
Sound Pattern16–33 Volts Volts DC 16–33 Volts Volts FWR
135 cd 150 cd 177 cd 185 cd 135 cd 150 cd 177 cd 185 cd
Temporal High 245 259 290 297 215 231 258 265
Temporal Medium 235 253 288 297 209 224 250 258
Temporal Low 232 251 282 292 207 221 248 256
Non-temporal High 255 270 303 309 233 248 275 281
Non-temporal Medium 242 259 293 299 219 232 262 267
Non-temporal Low 238 254 291 295 214 229 256 262
TabLe 6. Horn ouTpuT ( ba) in uL reverberanT room:
Switch Position
Sound Pattern dA8–17.5 Volts** 16–33 Volts**
24 V Nominal MeasurementsReverberant Anechoic
DC FWR DC FWR DC FWR DC FWR1 Temporal High 78 78 84 84 88 88 99 982 Temporal Medium 75 75 80 80 86 85 96 963 Temporal Low 71 71 76 76 81 79 94 894 Non-temporal High 82 82 88 88 93 92 100 1005 Non-temporal Medium 78 78 85 85 90 89 98 986 Non-temporal Low 75 75 81 81 86 84 96 927* Coded High 82 82 88 88 93 92 101 1018* Coded Medium 78 78 85 85 90 89 97 989* Coded Low 74 75 81 81 85 83 96 92
*Horn & 4-wire Horn/Strobe only. ** Minimum dB rating for Operational Voltage Range as per UL 464.
k SerieS mounTing1. K Series products may be used indoors or outdoors. They must be in-
stalled using the proper SpectrAlert Advance weatherproof back box (SA-WBB, SA-WBBW, SA-WBBC or SA-WBBCW). Do not attempt to use boxes other than the ones supplied with the product.
2. The wall mount box (SA-WBB or SA-WBBW) must be mounted with its internal post in the lower left corner, as shown in Figure 8.
3. Threaded holes are provided in the sides of the box for ¾-inch conduit adapters. Knockout plugs in the back of the box can be used for ¾-inch rear entry. Unused holes must be sealed. Plugs and O-Rings are provided with the box for this purpose.
4. It is the responsibility of the installer to make sure that all openings and connections are sealed properly. Outdoor installations that are protected from direct exposure to rain are still subject to condensation or leakage through hidden areas, such as a soffit.
5. Water may pool on the back box due to condensation or direct exposure to rain or snow. Use watertight fittings for all wiring connections, includ-ing the knockout plugs on the back of the box. When using plastic plugs to fill unused threaded holes, apply teflon tape and/or silicone sealant to reduce the chance of leakage.
6. Attach the mounting plate to the weatherproof back box using the four unpainted screws.
7. Follow steps 2 – 6 of the indoor mounting instructions to wire and attach the product.
mounTing indoor WaLL or CeiLing produCTS1. Attach mounting plate to junction box as shown in Figures 4 and 5. The
mounting plate is compatible with 4-inch square, double gang, and 4-inch octagon junction boxes (2-wire products may be used with a single gang box). If using a back box skirt, attach the mounting plate to the skirt and then attach the entire assembly to the junction box (see Figures 6 and 7).
2. Connect field wiring to terminals, as shown in Figures 1 and 2.
3. If the product is not to be installed at this point, use the paint cover to prevent contamination of the mounting plate. (For indoor models only)
4. To attach product to mounting plate, remove the paint cover, then hook tabs on the product housing into the grooves on mounting plate.
5. Then, swing product into position to engage the pins on the product with the terminals on the mounting plate. Make sure that the tabs on the back of the product housing fully engage with the mounting plate.
6. Secure product by tightening the single mounting screw in the front of the product housing. For tamper resistance, the standard captivated mounting screw may be replaced with the enclosed Torx screw.
ma
d
ma
D690-03-00 3 I56-2769-015R
D690-03-00 4 I56-2769-015R ©2010 System Sensor
The horn and/or strobe will not work without power. The horn/strobe gets its power from the fire/security panel monitoring the alarm system. If power is cut off for any reason, the horn/strobe will not provide the desired audio or visual warning.
The horn may not be heard. The loudness of the horn meets (or exceeds) current Underwriters Laboratories’ standards. However, the horn may not alert a sound sleeper or one who has recently used drugs or has been drinking alcoholic bever-ages. The horn may not be heard if it is placed on a different floor from the person in hazard or if placed too far away to be heard over the ambient noise such as traffic, air conditioners, machinery or music appliances that may prevent alert persons from hearing the alarm. The horn may not be heard by persons who are hearing impaired.
NOTE: Strobes must be powered continuously for horn operation.
The signal strobe may not be seen. The electronic visual warning signal uses an extremely reliable xenon flash tube. It flashes at least once every second. The strobe must not be in-stalled in direct sunlight or areas of high light intensity (over 60 foot candles) where the visual flash might be disregarded or not seen. The strobe may not be seen by the visually impaired.
The signal strobe may cause seizures. Individuals who have positive photoic response to visual stimuli with seizures, such as persons with epilepsy, should avoid prolonged exposure to environments in which strobe signals, including this strobe, are activated.
The signal strobe cannot operate from coded power supplies. Coded power supplies produce interrupted power. The strobe must have an uninterrupted source of power in order to operate correctly. System Sensor recommends that the horn and signal strobe always be used in combination so that the risks from any of the above limitations are minimized.
WARNING
The Limitations of Horn/Strobes
Three-Year Limited WarrantySystem Sensor warrants its enclosed product to be free from defects in ma-terials and workmanship under normal use and service for a period of three years from date of manufacture. System Sensor makes no other express war-ranty for this product. No agent, representative, dealer, or employee of the Company has the authority to increase or alter the obligations or limitations of this Warranty. The Company’s obligation of this Warranty shall be limited to the replacement of any part of the product which is found to be defective in materials or workmanship under normal use and service during the three year period commencing with the date of manufacture. After phoning System Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return Authorization number, send defective units postage prepaid to: System Sensor, Returns
Department, RA #__________, 3825 Ohio Avenue, St. Charles, IL 60174. Please include a note describing the malfunction and suspected cause of failure. The Company shall not be obligated to replace units which are found to be defective because of damage, unreasonable use, modifications, or alterations occurring after the date of manufacture. In no case shall the Company be liable for any consequential or incidental damages for breach of this or any other Warranty, expressed or implied whatsoever, even if the loss or damage is caused by the Company’s negligence or fault. Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to you. This Warranty gives you specific legal rights, and you may also have other rights which vary from state to state.
FCC StatementSpectrAlert Strobes and Horn/Strobes have been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses,
and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.
Please refer to insert for the Limitations of Fire Alarm Systems
Figure 4. WaLL mounT produCT:
A0348-00Figure 5. CeiLing mounT produCT:
A0369-00Figure 6. WaLL mounT produCT WiTH baCk box SkirT:
A0349-00
4-wire mounting plate
2-wire mounting plate
Figure 7: CeiLing mounT produCT WiTH baCk box SkirT:
A0370-00Figure 8. WaLL mounT Horn/STrobe WiTH WeaTHerprooF baCkbox:
Figure 9. WaLL and CeiLing mounT WeaTHerprooF baCkboxeS:
NOTE: Wall and Ceiling models may be used interchangeably (wall products may be used on the ceiling and ceiling products may be used on the wall).
NOTE: Use all four mounting plate screws when installing outdoor units. A0418-00
A0417-00