7/27/2019 Itcc Bms Io Hvac
1/40
Project : ITTC - MOSQUE
Subject : BMS Input / Output List
AI DI AO DO
Energy transfer Station (ETS)
1 Chilled Water Meters 1 1 Water Flow Meter
2 Differential Pressure Transmitter 1 Liquid Differential Pressure Sensor
3 Motorized Valve (HX) 1 VFC from Valve Limit Switch (valve by others)
4 By-Pass Motorized Valve 1 VFC from Valve Limit Switch (valve by others)
5 Pressure Indicator 1 Liquid Pressure Sensor
6 Temperature Indicator 1 Immersion Temperature Sensor
Total per Unit 3 1 3 0
Total for all Units 3 1 3 0
Total ETS Points
Tertiary Chilled Water System
1 Tertiary Common Chilled Water Supply Temperature 1 Immersion Temperature Sensor
2 Tertiary commom Chilled Water Return Temperature 1 Immersion Temperature Sensor
3 Tertiary Chilled Water Flow 0 Flow Meter(By Others)
5 Tertiary Loop Chilled Water Differential Pressure in Loop 1 Liquid Differential Pressure Sensor
Total per Unit 3
Tertiary Chilled Water Pump VFD Feedback 1 0-10V From Pump VFD Control Panel
6 Tertiary Chilled Water Pump Run Status 0 VFC From Pump Control Panel
7 Tertiary Chilled Water Pump VFD Trip 1 VFC From Pump Control Panel
8 Tertiary Chilled Water Pump VFD Auto / Manual 1 VFC From Pump Control Panel
9 Tertiary Chilled Water Pump VFD Control 1 0-10V DC Signal From BMS
10 Tertiary Chilled Water Pump Enable / Disable 1 Relay Output From BMS
Total per Unit 1 2 1 1
Total for all Units 6 6 3 3
Total Tertiary Chilled Water System points 18
OPC Client
1
BACnet
Network
Thermostat
Item Point DescriptionQty.
1
3
RemarksSoftware
Integration
7
Required Points
1 of 40
7/27/2019 Itcc Bms Io Hvac
2/40
Project : ITTC - MOSQUE
Subject : BMS Input / Output List
AI DI AO DOOPC Client
BACnet
Network
Thermostat
Item Point DescriptionQty. RemarksSoftware
Integration
Required Points
Point List - Through OSP/BACnet connection (cont.)
1 Frequency Output (in Hz) -
2 Percent Output -
3 Speed (in RPM) -
4 Current (in Amps) -5 Torque (in %) -
6 Power(in %) -
7 Run Time hours -
8 Run/Stop Status -
9 VSD Fault Alarm -
10 Current Limit(in %) -
11 Accel Time (in sec) -
12 Decel Time(in sec) -
13 VSD speed modulate -14 start/stop command -
Total per Unit 0 0 0 0 1
Total for all Units 0 0 0 0 3
3
1 Through OSP/BACnet Connection3
Total Point List-Through OSP/BACnet connection (cont.) 0
2 of 40
7/27/2019 Itcc Bms Io Hvac
3/40
Project : ITTC - MOSQUE
Subject : BMS Input / Output List
AI DI AO DOOPC Client
BACnet
Network
Thermostat
Item Point DescriptionQty. RemarksSoftware
Integration
Required Points
FAHU( CAV )
1 Supply Air Temperature 1
2 Outside Air Temperature 1
3 Chilled water supply temperature 1
4 Chilled water return temperature 15 2-Way Cooling Valve Position feedback 1
6 Final Filter Status 1
7 Pre Filter Status 1
8 Supply Fan Status 1
9 Supply fan air flow status 1
10 Supply Fan Trip 1
11 Supply Fan Auto / Manual 1
12 Fresh air Damper Open / Close Feedback 1
13 Smoke Detector 1
14 2-Way Cooling Valve Control 1
15 Supply Fan Start/Stop 1
16 Fresh air Damper open / close Command 1
Total per Unit 5 8 1 2
Total for all Units 5 8 1 2
Total AHU (CAV) Points
1
16
3 of 40
7/27/2019 Itcc Bms Io Hvac
4/40
Project : ITTC - MOSQUE
Subject : BMS Input / Output List
AI DI AO DOOPC Client
BACnet
Network
Thermostat
Item Point DescriptionQty. RemarksSoftware
Integration
Required Points
AHU( CAV ) with Electric Heater
1 Space Temperature 0
2 Return Air Temperature 1
3 Return Air Humidity 1
4 Return Air Carbon Dioxide 1
5 Mixed Air Temperature 1
6 Supply Air Temperature 1
7 Outside Air Temperature 1
8 Chilled water supply temperature 1
9 Chilled water return temperature 1
10 2-Way Cooling Valve Position feedback 1
11 Final Filter Status 1
12 Pre Filter Status 1
13 Supply Fan Status 1
14 Supply fan air flow status 1
15 Supply Fan Trip 1
16 Supply Fan Auto / Manual 1
17 Fresh air Damper Open / Close Feedback 1
18 Return air Damper Open / Close Feedback 1
19 Smoke Detector 1
20 2-Way Cooling Valve Control 1
21 Supply Fan Start/Stop 1
22 Fresh air Damper open / close Command 1
23 Return air Damper open / close Command 1
24 Electric Heater Status 4
25 Electric Heater Current Switch 4
26 Electric Heater Auto / Manual 4
27 Electric Heater Start / Stop 4
Total per Unit 9 21 1 7
Total for all Units 27 63 3 21
Total AHU (CAV) Points 114
3
4 of 40
7/27/2019 Itcc Bms Io Hvac
5/40
Project : ITTC - MOSQUE
Subject : BMS Input / Output List
AI DI AO DOOPC Client
BACnet
Network
Thermostat
Item Point DescriptionQty. RemarksSoftware
Integration
Required Points
Fan Coil Units (FCU)
1 Return Air Temperature 1
2 Air Flow Filter Status 1
3 Supply Fan Status 1
4 Supply Fan Auto / Manual 15 Supply Fan Air Flow Switch 1
6 Supply Fan Start / Stop 1
7 2- Way Control Valve Open / Close Command 1
Total per Unit 1 4 0 2
Total for all Units 5 20 0 10
Total Fan Coil Units (FCU) Points
Exhaust Fans1 Fan Status 1
2 Fan Trip 1
3 Fan Auto/Manual 1
4 Fan Start/Stop 1
5 Fan Air Flow Status 1
Total per Unit 0 4 0 1
Total for all Units 0 16 0 4
TOTAL EXHAUST FANS POINTS 20
35
4
5
5 of 40
7/27/2019 Itcc Bms Io Hvac
6/40
Project : ITTC - MOSQUE
Subject : BMS Input / Output List
AI DI AO DOOPC Client
BACnet
Network
Thermostat
Item Point DescriptionQty. RemarksSoftware
Integration
Required Points
Impulse Fans
1 Start/Stop Control 0 1 0 0
2 Contactor Status 1
3 Air Flow Monitoring 1
4 Motor Fail/Trip 1 Relay Output From BMSTotal per Unit 0 3 0 1
Total for all Units 0 30 0 10
Total Impulse fans points
Closed Expansion Tanks
1 1 Tank Pressure 3 Air Pressure Sensor
Total per Unit 3 0 0 0
Total for all Units 3 0 0 0
Total Closed Expansion Tanks Points
Air Separator
1 1 Pressure 1 Air Pressure Sensor
Total per Unit 1 0 0 0
Total for all Units 1 0 0 0
Total Air Separator Points
3
1
40
10
6 of 40
7/27/2019 Itcc Bms Io Hvac
7/40
Project : ITTC - COMM . STORES
Subject : BMS Input / Output List
AI DI AO DO
Energy transfer Station (ETS)
1 Chilled Water Meters 1 1 Water Flow Meter
2 Differential Pressure Transmitter 1 Liquid Differential Pressure Sensor
3 Motorized Valve (HX) 1 VFC from Valve Limit Switch (valve by others)
4 By-Pass Motorized Valve 1 VFC from Valve Limit Switch (valve by others)
5 Pressure Indicator 1 Liquid Pressure Sensor
6 Temperature Indicator 1 Immersion Temperature Sensor
Total per Unit 3 1 3 0
Total for all Units 3 1 3 0
Total ETS Points
Tertiary Chilled Water System
1 Tertiary Common Chilled Water Supply Temperature 1 Immersion Temperature Sensor
2 Tertiary commom Chilled Water Return Temperature 1 Immersion Temperature Sensor
3 Tertiary Chilled Water Flow 0 Flow Meter(By Others)
5 Tertiary Loop Chilled Water Differential Pressure in Loop 1 Liquid Differential Pressure Sensor
Total per Unit 3
Tertiary Chilled Water Pump VFD Feedback 1 0-10V From Pump VFD Control Panel
6 Tertiary Chilled Water Pump Run Status 0 VFC From Pump Control Panel
7 Tertiary Chilled Water Pump VFD Trip 1 VFC From Pump Control Panel
8 Tertiary Chilled Water Pump VFD Auto / Manual 1 VFC From Pump Control Panel
9 Tertiary Chilled Water Pump VFD Control 1 0-10V DC Signal From BMS
10 Tertiary Chilled Water Pump Enable / Disable 1 Relay Output From BMS
Total per Unit 1 2 1 1
Total for all Units 6 6 3 3
Total Tertiary Chilled Water System points
Software
Integration
7
18
Item Point DescriptionQty.
1
RemarksOPC Client
1
Required Points
3
BACnet
Network
Thermostat
7 of 40
7/27/2019 Itcc Bms Io Hvac
8/40
Project : ITTC - COMM . STORES
Subject : BMS Input / Output List
AI DI AO DO
Software
IntegrationItem Point DescriptionQty. RemarksOPC Client
Required Points BACnetNetwork
Thermostat
Point List - Through OSP/BACnet connection (cont.)
1 Frequency Output (in Hz) -
2 Percent Output -
3 Speed (in RPM) -
4 Current (in Amps) -5 Torque (in %) -
6 Power(in %) -
7 Run Time hours -
8 Run/Stop Status -
9 VSD Fault Alarm -
10 Current Limit(in %) -
11 Accel Time (in sec) -
12 Decel Time(in sec) -
13 VSD speed modulate -14 start/stop command -
Total per Unit 0 0 0 0 1
Total for all Units 0 0 0 0 3
3
Through OSP/BACnet Connection13
0Total Point List-Through OSP/BACnet connection (cont.)
8 of 40
7/27/2019 Itcc Bms Io Hvac
9/40
Project : ITTC - COMM. STORES
Subject : BMS Input / Output List
AI DI AO DO
Software
IntegrationItem Point DescriptionQty. RemarksOPC Client
Required Points BACnetNetwork
Thermostat
AHU( CAV ) with Electric Heater
1 Space Temperature 0
2 Return Air Temperature 1
3 Return Air Humidity 1
4 Return Air Carbon Dioxide 1
5 Mixed Air Temperature 1
6 Supply Air Temperature 1
7 Outside Air Temperature 1
8 Chilled water supply temperature 1
9 Chilled water return temperature 1
10 2-Way Cooling Valve Position feedback 1
11 Final Filter Status 1
12 Pre Filter Status 1
13 Supply Fan Status 1
14 Supply fan air flow status 1
15 Supply Fan Trip 1
16 Supply Fan Auto / Manual 1
17 Fresh air Damper Open / Close Feedback 1
18 Return air Damper Open / Close Feedback 1
19 Smoke Detector 1
20 2-Way Cooling Valve Control 1
21 Supply Fan Start/Stop 1
22 Fresh air Damper open / close Command 1
23 Return air Damper open / close Command 1
24 Electric Heater Status 4
25 Electric Heater Current Switch 4
26 Electric Heater Auto / Manual 4
27 Electric Heater Start / Stop 4
Total per Unit 9 21 1 7
Total for all Units 18 42 2 14
Total AHU (CAV) Points
2
76
9 of 40
7/27/2019 Itcc Bms Io Hvac
10/40
Project : ITTC - COMM. STORES
Subject : BMS Input / Output List
AI DI AO DO
Software
IntegrationItem Point DescriptionQty. RemarksOPC Client
Required Points BACnetNetwork
Thermostat
FAHU( CAV ) with Exhaust Air Fan
1 Supply Air Temperature 1
2 Outside Air Temperature 1
3 Chilled water supply temperature 1
4 Chilled water return temperature 15 2-Way Cooling Valve Position feedback 1
6 Final Filter Status 1
7 Pre Filter Status 1
8 Supply & Exhaust Fan Status 2
9 Supply & Exhaust fan air flow status 2
10 Supply & exhaust Fan Trip 2
11 Supply & Exhaust Fan Auto / Manual 2
12 Fresh air Damper Open / Close Feedback 1
13 Exhaust air Damper Open / Close Feedback 1
14 Smoke Detector 1
15 2-Way Cooling Valve Control 1
16 Supply & Exhaust Fan Start/Stop 2
17 Fresh air Damper open / close Command 1
18 Exhaust air Damper open / close Command 1
Total per Unit 5 13 1 4
Total for all Units 5 13 1 4
TOTAL AHU (CAV) with Return Fan Points 23
1
10 of 40
7/27/2019 Itcc Bms Io Hvac
11/40
Project : ITTC - COMM. STORES
Subject : BMS Input / Output List
AI DI AO DO
Software
IntegrationItem Point DescriptionQty. RemarksOPC Client
Required Points BACnetNetwork
Thermostat
Fan Coil Units (FCU) with Electric Heater
1 Return Air Temperature 1
2 Air Flow Filter Status 1
3 Supply Fan Status 14 Supply Fan Auto / Manual 1
5 Supply Fan Air Flow Switch 1
6 Supply Fan Start / Stop 1
7 2- Way Control Valve Open / Close Command 1
8 Electric Heater Status 1
9 Electric Heater Current Switch 1
10 Electric Heater Auto / Manual 1
11 Electric Heater Start / Stop 1
Total per Unit 1 7 0 3
Total for all Units 68 476 0 204
Total Fan Coil Units (FCU) with Electric Heater Points
Exhaust Fans
1 Fan Status 1
2 Fan Trip 1
3 Fan Auto/Manual 1
4 Fan Start/Stop 1
5 Fan Air Flow Status 1
Total per Unit 0 4 0 1
Total for all Units 0 16 0 4
TOTAL EXHAUST FANS POINTS
Pressurization Fans
1 Fan Status 1
2 Fan Trip 1
3 Fan Auto/Manual 1
4 Fan Air Flow Status 1
5 Air Damper Open / Close Feedback 1
6 Air Damper Open / Close Command 1
Total per Unit 0 5 0 1
Total for all Units 0 10 0 2
Total Pressurization Fans Points
748
68
2
12
4
20
11 of 40
7/27/2019 Itcc Bms Io Hvac
12/40
Project : ITTC - COMM . STORES
Subject : BMS Input / Output List
AI DI AO DO
Software
IntegrationItem Point DescriptionQty. RemarksOPC Client
Required Points BACnetNetwork
Thermostat
Impulse Fans
1 Start/Stop Control 0 1 0 0
2 Contactor Status 1
3 Air Flow Monitoring 1
4 Motor Fail/Trip 1 Relay Output From BMSTotal per Unit 0 3 0 1
Total for all Units 0 24 0 8
Total Impulse fans points
Closed Expansion Tanks
1 1 Tank Pressure 3 Air Pressure Sensor
Total per Unit 3 0 0 0
Total for all Units 3 0 0 0
Total Closed Expansion Tanks Points
Air Separator
1 1 Pressure 1 Air Pressure Sensor
Total per Unit 1 0 0 0
Total for all Units 1 0 0 0
Total Air Separator Points
3
1
32
8
12 of 40
7/27/2019 Itcc Bms Io Hvac
13/40
Project : ITTC - COMM . CENTER
Subject : BMS Input / Output List
AI DI AO DO
Energy transfer Station (ETS)
1 Chilled Water Meters 1 1 Water Flow Meter
2 Differential Pressure Transmitter 1 Liquid Differential Pressure Sensor
3 Motorized Valve (HX) 1 VFC from Valve Limit Switch (valve by others)
4 By-Pass Motorized Valve 1 VFC from Valve Limit Switch (valve by others)
5 Pressure Indicator 1 Liquid Pressure Sensor
6 Temperature Indicator 1 Immersion Temperature Sensor
Total per Unit 3 1 3 0
Total for all Units 3 1 3 0
Total ETS Points
Tertiary Chilled Water System
1 Tertiary Common Chilled Water Supply Temperature 1 Immersion Temperature Sensor
2 Tertiary commom Chilled Water Return Temperature 1 Immersion Temperature Sensor
3 Tertiary Chilled Water Flow 0 Flow Meter(By Others)
5 Tertiary Loop Chilled Water Differential Pressure in Loop 1 Liquid Differential Pressure Sensor
Total per Unit 3
Tertiary Chilled Water Pump VFD Feedback 1 0-10V From Pump VFD Control Panel
6 Tertiary Chilled Water Pump Run Status 0 VFC From Pump Control Panel
7 Tertiary Chilled Water Pump VFD Trip 1 VFC From Pump Control Panel
8 Tertiary Chilled Water Pump VFD Auto / Manual 1 VFC From Pump Control Panel
9 Tertiary Chilled Water Pump VFD Control 1 0-10V DC Signal From BMS
10 Tertiary Chilled Water Pump Enable / Disable 1 Relay Output From BMS
Total per Unit 1 2 1 1
Total for all Units 6 6 3 3
Total Tertiary Chilled Water System points
3
7
18
1
1
OPC ClientRequired Points BACnet
Network
Thermostat
RemarksSoftware
IntegrationItem Point DescriptionQty.
13 of 40
7/27/2019 Itcc Bms Io Hvac
14/40
Project : ITTC - COMM. CENTER
Subject : BMS Input / Output List
AI DI AO DOOPC Client
Required Points BACnetNetwork
Thermostat
RemarksSoftware
IntegrationItem Point DescriptionQty.
Point List - Through OSP/BACnet connection (cont.)
1 Frequency Output (in Hz) -
2 Percent Output -
3 Speed (in RPM) -
4 Current (in Amps) -5 Torque (in %) -
6 Power(in %) -
7 Run Time hours -
8 Run/Stop Status -
9 VSD Fault Alarm -
10 Current Limit(in %) -
11 Accel Time (in sec) -
12 Decel Time(in sec) -
13 VSD speed modulate -14 start/stop command -
Total per Unit 0 0 0 0 1
Total for all Units 0 0 0 0 3
3Total Point List-Through OSP/BACnet connection (cont.)
3
0
1 Through OSP/BACnet Connection
14 of 40
7/27/2019 Itcc Bms Io Hvac
15/40
Project : ITTC - COMM. CENTER
Subject : BMS Input / Output List
AI DI AO DOOPC Client
Required Points BACnetNetwork
Thermostat
RemarksSoftware
IntegrationItem Point DescriptionQty.
AHU( CAV ) with Electric Heater
1 Space Temperature 0
2 Return Air Temperature 1
3 Return Air Humidity 1
4 Return Air Carbon Dioxide 15 Mixed Air Temperature 1
6 Supply Air Temperature 1
7 Outside Air Temperature 1
8 Chilled water supply temperature 1
9 Chilled water return temperature 1
10 2-Way Cooling Valve Position feedback 1
11 Final Filter Status 1
12 Pre Filter Status 1
13 Supply Fan Status 1
14 Supply fan air flow status 1
15 Supply Fan Trip 1
16 Supply Fan Auto / Manual 1
17 Fresh air Damper Open / Close Feedback 1
18 Return air Damper Open / Close Feedback 1
19 Smoke Detector 1
20 2-Way Cooling Valve Control 1
21 Supply Fan Start/Stop 1
22 Fresh air Damper open / close Command 1
23 Return air Damper open / close Command 1
24 Electric Heater Status 4
25 Electric Heater Current Switch 4
26 Electric Heater Auto / Manual 4
27 Electric Heater Start / Stop 4
Total per Unit 9 21 1 7
Total for all Units 54 126 6 42
Total AHU (CAV) Points 228
6
15 of 40
7/27/2019 Itcc Bms Io Hvac
16/40
Project : ITTC - COMM. CENTER
Subject : BMS Input / Output List
AI DI AO DOOPC Client
Required Points BACnetNetwork
Thermostat
RemarksSoftware
IntegrationItem Point DescriptionQty.
FAHU( CAV ) with Exhaust Air Fan
1 Supply Air Temperature 1
2 Outside Air Temperature 1
3 Chilled water supply temperature 1
4 Chilled water return temperature 15 2-Way Cooling Valve Position feedback 1
6 Final Filter Status 1
7 Pre Filter Status 1
8 Supply & Exhaust Fan Status 2
9 Supply & Exhaust fan air flow status 2
10 Supply & exhaust Fan Trip 2
11 Supply & Exhaust Fan Auto / Manual 2
12 Fresh air Damper Open / Close Feedback 1
13 Exhaust air Damper Open / Close Feedback 114 Smoke Detector 1
15 2-Way Cooling Valve Control 1
16 Supply & Exhaust Fan Start/Stop 2
17 Fresh air Damper open / close Command 1
18 Exhaust air Damper open / close Command 1
Total per Unit 5 13 1 4
Total for all Units 5 13 1 4
TOTAL AHU (CAV) with Return Fan Points
1
23
16 of 40
7/27/2019 Itcc Bms Io Hvac
17/40
Project : ITTC - COMM. CENTER
Subject : BMS Input / Output List
AI DI AO DOOPC Client
Required Points BACnetNetwork
Thermostat
RemarksSoftware
IntegrationItem Point DescriptionQty.
Fan Coil Units (FCU) with Electric Heater
1 Return Air Temperature 1
2 Air Flow Filter Status 1
3 Supply Fan Status 14 Supply Fan Auto / Manual 1
5 Supply Fan Air Flow Switch 1
6 Supply Fan Start / Stop 1
7 2- Way Control Valve Open / Close Command 1
8 Electric Heater Status 1
9 Electric Heater Current Switch 1
10 Electric Heater Auto / Manual 1
11 Electric Heater Start / Stop 1
Total per Unit 1 7 0 3
Total for all Units 110 770 0 330
Total Fan Coil Units (FCU) with Electric Heater Points
Exhaust Fans
1 Fan Status 1
2 Fan Trip 1
3 Fan Auto/Manual 1
4 Fan Start/Stop 1
5 Fan Air Flow Status 1
Total per Unit 0 4 0 1
Total for all Units 0 48 0 12
TOTAL EXHAUST FANS POINTS
Pressurization Fans
1 Fan Status 1
2 Fan Trip 1
3 Fan Auto/Manual 1
4 Fan Air Flow Status 1
5 Air Damper Open / Close Feedback 1
6 Air Damper Open / Close Command 1
Total per Unit 0 5 0 1
Total for all Units 0 10 0 2
Total Pressurization Fans Points
110
12
60
1210
2
12
17 of 40
7/27/2019 Itcc Bms Io Hvac
18/40
Project : ITTC - COMM . CENTER
Subject : BMS Input / Output List
AI DI AO DOOPC Client
Required Points BACnetNetwork
Thermostat
RemarksSoftware
IntegrationItem Point DescriptionQty.
Impulse Fans
1 Start/Stop Control 0 1 0 0
2 Contactor Status 1
3 Air Flow Monitoring 1
4 Motor Fail/Trip 1 Relay Output From BMSTotal per Unit 0 3 0 1
Total for all Units 0 36 0 12
Total Impulse fans points
Closed Expansion Tanks
1 1 Tank Pressure 3 Air Pressure Sensor
Total per Unit 3 0 0 0
Total for all Units 3 0 0 0
Total Closed Expansion Tanks Points
Air Separator
1 1 Pressure 1 Air Pressure Sensor
Total per Unit 1 0 0 0
Total for all Units 1 0 0 0
Total Air Separator Points
12
1
48
3
18 of 40
7/27/2019 Itcc Bms Io Hvac
19/40
Project : ITTC - SPORTS CLUB
Subject : BMS Input / Output List
AI DI AO DO
Energy transfer Station (ETS)
1 Chilled Water Meters 1 1 Water Flow Meter
2 Differential Pressure Transmitter 1 Liquid Differential Pressure Sensor
3 Motorized Valve (HX) 1 VFC from Valve Limit Switch (valve by others)
4 By-Pass Motorized Valve 1 VFC from Valve Limit Switch (valve by others)5 Pressure Indicator 1 Liquid Pressure Sensor
6 Temperature Indicator 1 Immersion Temperature Sensor
Total per Unit 3 1 3 0
Total for all Units 3 1 3 0
Total ETS Points
Tertiary Chilled Water System
1 Tertiary Common Chilled Water Supply Temperature 1 Immersion Temperature Sensor
2 Tertiary commom Chilled Water Return Temperature 1 Immersion Temperature Sensor
3 Tertiary Chilled Water Flow 0 Flow Meter(By Others)
5 Tertiary Loop Chilled Water Differential Pressure in Loop 1 Liquid Differential Pressure Sensor
Total per Unit 3
Tertiary Chilled Water Pump VFD Feedback 1 0-10V From Pump VFD Control Panel
6 Tertiary Chilled Water Pump Run Status 0 VFC From Pump Control Panel
7 Tertiary Chilled Water Pump VFD Trip 1 VFC From Pump Control Panel
8 Tertiary Chilled Water Pump VFD Auto / Manual 1 VFC From Pump Control Panel
9 Tertiary Chilled Water Pump VFD Control 1 0-10V DC Signal From BMS
10 Tertiary Chilled Water Pump Enable / Disable 1 Relay Output From BMS
Total per Unit 1 2 1 1
Total for all Units 6 6 3 3
Total Tertiary Chilled Water System points
Software
Integration
7
18
1
OPC Client
3
BACnet
Network
Thermostat
Remarks
1
Required PointsItem Point DescriptionQty.
19 of 40
7/27/2019 Itcc Bms Io Hvac
20/40
Project : ITTC - SPORTS CLUB
Subject : BMS Input / Output List
AI DI AO DO
Software
IntegrationOPC Client
BACnet
Network
Thermostat
RemarksRequired Points
Item Point DescriptionQty.
Point List - Through OSP/BACnet connection (cont.)
1 Frequency Output (in Hz) -
2 Percent Output -
3 Speed (in RPM) -
4 Current (in Amps) -5 Torque (in %) -
6 Power(in %) -
7 Run Time hours -
8 Run/Stop Status -
9 VSD Fault Alarm -
10 Current Limit(in %) -
11 Accel Time (in sec) -
12 Decel Time(in sec) -
13 VSD speed modulate -14 start/stop command -
Total per Unit 0 0 0 0 1
Total for all Units 0 0 0 0 3
3
Through OSP/BACnet Connection3
Total Point List-Through OSP/BACnet connection (cont.)
1
0
20 of 40
7/27/2019 Itcc Bms Io Hvac
21/40
Project : ITTC - SPORTS CLUB
Subject : BMS Input / Output List
AI DI AO DO
Software
IntegrationOPC Client
BACnet
Network
Thermostat
RemarksRequired Points
Item Point DescriptionQty.
AHU( CAV ) with Electric Heater & Return Air Fan
1 Space Temperature 0
2 Return Air Temperature 1
3 Return Air Humidity 1
4 Return Air Carbon Dioxide 15 Mixed Air Temperature 1
6 Supply Air Temperature 1
7 Outside Air Temperature 1
8 Chilled water supply temperature 1
9 Chilled water return temperature 1
10 2-Way Cooling Valve Position feedback 1
11 Final Filter Status 1
12 Pre Filter Status 1
13 Supply & Return Fans Status 2
14 Supply & Return fans air flow status 2
15 Supply & Return Fans Trip 2
16 Supply & Return Fans Auto / Manual 2
17 Fresh air Damper Open / Close Feedback 1
18 Return air Damper Open / Close Feedback 1
19 Exhaust air Damper Open / Close Feedback 1
20 Smoke Detector 1
21 2-Way Cooling Valve Control 1
22 Supply & Return Fans Start/Stop 2
23 Fresh air Damper open / close Command 1
24 Return air Damper open / close Command 1
25 Exhaust air Damper open / close Command 1
26 Electric Heater Status 4
27 Electric Heater Current Switch 4
28 Electric Heater Auto / Manual 4
29 Electric Heater Start / Stop 4
Total per Unit 9 26 1 9
Total for all Units 18 52 2 18
TOTAL AHU (CAV) with Return Fan Points
2
90
21 of 40
7/27/2019 Itcc Bms Io Hvac
22/40
Project : ITTC - SPORTS CLUB
Subject : BMS Input / Output List
AI DI AO DO
Software
IntegrationOPC Client
BACnet
Network
Thermostat
RemarksRequired Points
Item Point DescriptionQty.
FAHU( CAV ) with Exhaust Air Fan
1 Supply Air Temperature 1
2 Outside Air Temperature 1
3 Chilled water supply temperature 1
4 Chilled water return temperature 15 2-Way Cooling Valve Position feedback 1
6 Final Filter Status 1
7 Pre Filter Status 1
8 Supply & Exhaust Fan Status 2
9 Supply & Exhaust fan air flow status 2
10 Supply & exhaust Fan Trip 2
11 Supply & Exhaust Fan Auto / Manual 2
12 Fresh air Damper Open / Close Feedback 1
13 Exhaust air Damper Open / Close Feedback 114 Smoke Detector 1
15 2-Way Cooling Valve Control 1
16 Supply & Exhaust Fan Start/Stop 2
17 Fresh air Damper open / close Command 1
18 Exhaust air Damper open / close Command 1
Total per Unit 5 13 1 4
Total for all Units 20 52 4 16
TOTAL AHU (CAV) with Return Fan Points
4
92
22 of 40
7/27/2019 Itcc Bms Io Hvac
23/40
Project : ITTC - SPORTS CLUB
Subject : BMS Input / Output List
AI DI AO DO
Software
IntegrationOPC Client
BACnet
Network
Thermostat
RemarksRequired Points
Item Point DescriptionQty.
AHU( VAV )
1 Return Air Temperature 1
2 Return Air Humidity 1
3 Return Air Carbon Dioxide 1
4 Mixed Air Temperature 15 Supply Air Temperature 1
6 Supply Duct static pressure 1
7 Outside Air Temperature 1
8 2-Way Cooling Valve Position feedback 1
9 Chilled water supply temperature 1
10 Chilled water return temperature 1
11 Supply Fan VFD Feedback 1
12 Supply Fan status 1
13 Supply fan air flow status 114 Supply Fan Auto / Manual 1
15 Supply Fan General Alarm 1
16 Fresh air Damper Open / Close Feedback 1
17 Return air Damper Open / Close Feedback 1
18 Smoke Detector 1
19 Supply fan VFD control 1
20 2-Way Cooling Valve Control 1
21 Supply Fan Start/Stop 1
22 Final Filter Status 1
23 Pre Filter Status 1
24 Fresh air Damper open/close Command 1
25 Return air Damper Open / Close Command 1
Total per Unit 11 9 2 3
Total for all Units 55 45 10 15
Total AHU (VAV) Points 125
5
23 of 40
7/27/2019 Itcc Bms Io Hvac
24/40
Project : ITTC - SPORTS CLUB
Subject : BMS Input / Output List
AI DI AO DO
Software
IntegrationOPC Client
BACnet
Network
Thermostat
RemarksRequired Points
Item Point DescriptionQty.
AHU( VAV ) with Return/Exhaust Air Fan
1 Return Air Temperature 1
2 Return Air Humidity 1
3 Return Air Carbon Dioxide 1
4 Mixed Air Temperature 15 Supply Air Temperature 1
6 Supply Duct static pressure 1
7 Outside Air Temperature 1
8 2-Way Cooling Valve Position feedback 1
9 Chilled water supply temperature 1
10 Chilled water return temperature 1
11 Supply Fan VFD Feedback 1
12 Supply Fan status 1
13 Supply fan air flow status 1
14 Supply Fan Auto / Manual 1
15 Supply Fan General Alarm 1
16 Fresh air Damper Open / Close Feedback 1
17 Return air Damper Open / Close Feedback 1
18 Smoke Detector 1
19 Supply fan VFD control 1
20 2-Way Cooling Valve Control 1
21 Supply Fan Start/Stop 1
22 Final Filter Status 1
23 Pre Filter Status 1
24 Fresh air Damper open/close Command 1
25 Return air Damper Open / Close Command 1
26 Return Fan VFD Feedback 1
27 Return Fan status 1
28 Return fan air flow status 1
29 Return Fan Auto / Manual 1
30 Return Fan General Alarm 1
31 Return fan VFD control 1
32 Return Fan Start/Stop 1
33 Exhaust air Damper Open / Close Feedback 1
34 Exhaust air Damper open/close Command 1
Total per Unit 12 14 3 5
Total for all Units 12 14 3 5
Total AHU (VAV) with Return Air Fan Points
1
34
24 of 40
7/27/2019 Itcc Bms Io Hvac
25/40
Project : ITTC - SPORTS CLUB
Subject : BMS Input / Output List
AI DI AO DO
Software
IntegrationOPC Client
BACnet
Network
Thermostat
RemarksRequired Points
Item Point DescriptionQty.
Fan Coil Units (FCU)
1 Return Air Temperature 1
2 Air Flow Filter Status 1
3 Supply Fan Status 1
4 Supply Fan Auto / Manual 15 Supply Fan Air Flow Switch 1
6 Supply Fan Start / Stop 1
7 2- Way Control Valve Open / Close Command 1
Total per Unit 1 4 0 2
Total for all Units 25 100 0 50
Total Fan Coil Units (FCU) Points
Fan Coil Units (FCU) with Electric Heater
1 Return Air Temperature 12 Air Flow Filter Status 1
3 Supply Fan Status 1
4 Supply Fan Auto / Manual 1
5 Supply Fan Air Flow Switch 1
6 Supply Fan Start / Stop 1
7 2- Way Control Valve Open / Close Command 1
8 Electric Heater Status 1
9 Electric Heater Current Switch 1
10 Electric Heater Auto / Manual 1
11 Electric Heater Start / Stop 1
Total per Unit 1 7 0 3
Total for all Units 13 91 0 39
Total Fan Coil Units (FCU) with Electric Heater Points
175
25
143
13
25 of 40
7/27/2019 Itcc Bms Io Hvac
26/40
Project : ITTC - SPORTS CLUB
Subject : BMS Input / Output List
AI DI AO DO
Software
IntegrationOPC Client
BACnet
Network
Thermostat
RemarksRequired Points
Item Point DescriptionQty.
VAV Box with Electric Heater
1 Space Temperature sensor with set point with fan speed selector 1
Space Temperature Sensor with set point and fan
speed selector
2 Damper Actuator modulate 1 0-10v Signal to Damper Actuator
3 Enable/Disable Stages of Electric Heater 1 Relay Output From BMS
Total per Unit 1 0 1 1
Total for all Units 28 0 28 28
Total VAV Box with Electric Heater points
Exhaust Fans
1 Fan Status 1
2 Fan Trip 1
3 Fan Auto/Manual 1
4 Fan Start/Stop 1
5 Fan Air Flow Status 1
Total per Unit 0 4 0 1
Total for all Units 0 24 0 6
TOTAL EXHAUST FANS POINTS
Pressurization Fans
1 Fan Status 12 Fan Trip 1
3 Fan Auto/Manual 1
4 Fan Air Flow Status 1
5 Air Damper Open / Close Feedback 1
6 Air Damper Open / Close Command 1
Total per Unit 0 5 0 1
Total for all Units 0 15 0 3
Total Pressurization Fans Points
3
30
18
6
28
84
26 of 40
7/27/2019 Itcc Bms Io Hvac
27/40
Project : ITTC - SPORTS CLUB
Subject : BMS Input / Output List
AI DI AO DO
Software
IntegrationOPC Client
BACnet
Network
Thermostat
RemarksRequired Points
Item Point DescriptionQty.
Impulse Fans
1 Start/Stop Control 0 1 0 0
2 Contactor Status 1
3 Air Flow Monitoring 1
4 Motor Fail/Trip 1 Relay Output From BMS
Total per Unit 0 3 0 1
Total for all Units 0 30 0 10
Total Impulse fans points
Closed Expansion Tanks
1 1 Tank Pressure 3 Air Pressure Sensor
Total per Unit 3 0 0 0
Total for all Units 3 0 0 0
Total Closed Expansion Tanks Points
Air Separator
1 1 Pressure 1 Air Pressure Sensor
Total per Unit 1 0 0 0
Total for all Units 1 0 0 0
Total Air Separator Points
3
10
1
40
27 of 40
7/27/2019 Itcc Bms Io Hvac
28/40
Project : ITTC - SCHOOL
Subject : BMS Input / Output List
AI DI AO DO
Energy transfer Station (ETS)
1 Chilled Water Meters 1 1 Water Flow Meter
2 Differential Pressure Transmitter 1 Liquid Differential Pressure Sensor
3 Motorized Valve (HX) 1 VFC from Valve Limit Switch (valve by others)
4 By-Pass Motorized Valve 1 VFC from Valve Limit Switch (valve by others)5 Pressure Indicator 1 Liquid Pressure Sensor
6 Temperature Indicator 1 Immersion Temperature Sensor
Total per Unit 3 1 3 0
Total for all Units 3 1 3 0
Total ETS Points
Tertiary Chilled Water System
1 Tertiary Common Chilled Water Supply Temperature 1 Immersion Temperature Sensor
2 Tertiary commom Chilled Water Return Temperature 1 Immersion Temperature Sensor
3 Tertiary Chilled Water Flow 0 Flow Meter(By Others)
5 Tertiary Loop Chilled Water Differential Pressure in Loop 1 Liquid Differential Pressure Sensor
Total per Unit 3
Tertiary Chilled Water Pump VFD Feedback 1 0-10V From Pump VFD Control Panel
6 Tertiary Chilled Water Pump Run Status 0 VFC From Pump Control Panel
7 Tertiary Chilled Water Pump VFD Trip 1 VFC From Pump Control Panel
8 Tertiary Chilled Water Pump VFD Auto / Manual 1 VFC From Pump Control Panel
9 Tertiary Chilled Water Pump VFD Control 1 0-10V DC Signal From BMS
10 Tertiary Chilled Water Pump Enable / Disable 1 Relay Output From BMS
Total per Unit 1 2 1 1
Total for all Units 6 6 3 3
Total Tertiary Chilled Water System points
RemarksSoftware
IntegrationOPC Client
BACnet
Network
Thermostat
Item Point DescriptionQty.
1
Required Points
7
18
1
3
28 of 40
7/27/2019 Itcc Bms Io Hvac
29/40
Project : ITTC - SCHOOL
Subject : BMS Input / Output List
AI DI AO DORemarks
Software
IntegrationOPC Client
BACnet
Network
Thermostat
Item Point DescriptionQty.Required Points
Point List - Through OSP/BACnet connection (cont.)
1 Frequency Output (in Hz) -
2 Percent Output -
3 Speed (in RPM) -
4 Current (in Amps) -
5 Torque (in %) -
6 Power(in %) -
7 Run Time hours -
8 Run/Stop Status -
9 VSD Fault Alarm -
10 Current Limit(in %) -
11 Accel Time (in sec) -
12 Decel Time(in sec) -
13 VSD speed modulate -14 start/stop command -
Total per Unit 0 0 0 0 1
Total for all Units 0 0 0 0 3
3
Through OSP/BACnet Connection13
Total Point List-Through OSP/BACnet connection (cont.) 0
29 of 40
7/27/2019 Itcc Bms Io Hvac
30/40
Project : ITTC - SCHOOL
Subject : BMS Input / Output List
AI DI AO DORemarks
Software
IntegrationOPC Client
BACnet
Network
Thermostat
Item Point DescriptionQty.Required Points
FAHU( CAV ) with Exhaust Air Fan
1 Supply Air Temperature 1
2 Outside Air Temperature 1
3 Chilled water supply temperature 1
4 Chilled water return temperature 15 2-Way Cooling Valve Position feedback 1
6 Final Filter Status 1
7 Pre Filter Status 1
8 Supply & Exhaust Fan Status 2
9 Supply & Exhaust fan air flow status 2
10 Supply & exhaust Fan Trip 2
11 Supply & Exhaust Fan Auto / Manual 2
12 Fresh air Damper Open / Close Feedback 1
13 Exhaust air Damper Open / Close Feedback 114 Smoke Detector 1
15 2-Way Cooling Valve Control 1
16 Supply & Exhaust Fan Start/Stop 2
17 Fresh air Damper open / close Command 1
18 Exhaust air Damper open / close Command 1
Total per Unit 5 13 1 4
Total for all Units 5 13 1 4
TOTAL AHU (CAV) with Return Fan Points
1
23
30 of 40
7/27/2019 Itcc Bms Io Hvac
31/40
Project : ITTC - SCHOOL
Subject : BMS Input / Output List
AI DI AO DORemarks
Software
IntegrationOPC Client
BACnet
Network
Thermostat
Item Point DescriptionQty.Required Points
Fan Coil Units (FCU)
1 Return Air Temperature 1
2 Air Flow Filter Status 1
3 Supply Fan Status 1
4 Supply Fan Auto / Manual 15 Supply Fan Air Flow Switch 1
6 Supply Fan Start / Stop 1
7 2- Way Control Valve Open / Close Command 1
Total per Unit 1 4 0 2
Total for all Units 35 140 0 70
Total Fan Coil Units (FCU) Points
Exhaust Fans1 Fan Status 1
2 Fan Trip 1
3 Fan Auto/Manual 1
4 Fan Start/Stop 1
5 Fan Air Flow Status 1
Total per Unit 0 4 0 1
Total for all Units 0 16 0 4
TOTAL EXHAUST FANS POINTS
Closed Expansion Tanks
1 1 Tank Pressure 3 Air Pressure Sensor
Total per Unit 3 0 0 0
Total for all Units 3 0 0 0
Total Closed Expansion Tanks Points
Air Separator
1 1 Pressure 1 Air Pressure Sensor
Total per Unit 1 0 0 0
Total for all Units 1 0 0 0
Total Air Separator Points 1
245
35
20
3
4
31 of 40
7/27/2019 Itcc Bms Io Hvac
32/40
Project : ITTC- ETS ROOM FOR VILLAS
Subject : BMS Input / Output List
AI DI AO DO
Energy transfer Station (ETS)
1 Chilled Water Meters 1 1 Water Flow Meter
2 Differential Pressure Transmitter 1 Liquid Differential Pressure Sensor
3 Motorized Valve (HX) 1 VFC from Valve Limit Switch (valve by others)
4 By-Pass Motorized Valve 1 VFC from Valve Limit Switch (valve by others)5 Pressure Indicator 1 Liquid Pressure Sensor
6 Temperature Indicator 1 Immersion Temperature Sensor
Total per Unit 3 1 3 0
Total for all Units 3 1 3 0
Total ETS Points
Tertiary Chilled Water System
1 Tertiary Common Chilled Water Supply Temperature 1 Immersion Temperature Sensor
2 Tertiary commom Chilled Water Return Temperature 1 Immersion Temperature Sensor
3 Tertiary Chilled Water Flow 0 Flow Meter(By Others)
5 Tertiary Loop Chilled Water Differential Pressure in Loop 1 Liquid Differential Pressure Sensor
Total per Unit 3
Tertiary Chilled Water Pump VFD Feedback 1 0-10V From Pump VFD Control Panel
6 Tertiary Chilled Water Pump Run Status 0 VFC From Pump Control Panel
7 Tertiary Chilled Water Pump VFD Trip 1 VFC From Pump Control Panel
8 Tertiary Chilled Water Pump VFD Auto / Manual 1 VFC From Pump Control Panel
9 Tertiary Chilled Water Pump VFD Control 1 0-10V DC Signal From BMS
10 Tertiary Chilled Water Pump Enable / Disable 1 Relay Output From BMS
Total per Unit 1 2 1 1
Total for all Units 6 6 3 3
Total Tertiary Chilled Water System points
1
Required Points
7
18
1
3
BACnet
Network
Thermostat
Item Point DescriptionQty. RemarksSoftware
IntegrationOPC Client
32 of 40
7/27/2019 Itcc Bms Io Hvac
33/40
Project : ITTC- ETS ROOM FOR VILLAS
Subject : BMS Input / Output List
AI DI AO DO
Required Points BACnetNetwork
Thermostat
Item Point DescriptionQty. RemarksSoftware
IntegrationOPC Client
Point List - Through OSP/BACnet connection (cont.)
1 Frequency Output (in Hz) -
2 Percent Output -
3 Speed (in RPM) -
4 Current (in Amps) -
5 Torque (in %) -
6 Power(in %) -
7 Run Time hours -
8 Run/Stop Status -
9 VSD Fault Alarm -
10 Current Limit(in %) -
11 Accel Time (in sec) -
12 Decel Time(in sec) -
13 VSD speed modulate -
14 start/stop command -
Total per Unit 0 0 0 0 1
Total for all Units 0 0 0 0 3
3
3
0Total Point List-Through OSP/BACnet connection (cont.)
Through OSP/BACnet Connection1
33 of 40
7/27/2019 Itcc Bms Io Hvac
34/40
Project : ITTC- ETS ROOM FOR VILL AS
Subject : BMS Input / Output List
AI DI AO DO
Required Points BACnetNetwork
Thermostat
Item Point DescriptionQty. RemarksSoftware
IntegrationOPC Client
Fan Coil Units (FCU) @ Tenants Area
1 1 BACnet Network Thermostat
Total per Unit 0 0 0 0 1
Total for all Units 1
Exhaust Air Fans
1 Fan Status 1
2 Fan Trip 1
3 Fan Auto/Manual 1
4 Fan Start/Stop 1 Relay Output From BMS
5 Fan Air Flow Status 1
Total per Unit 0 4 0 1
Total for all Units 0 4 0 1
Total Exhaust Air Fans Points
Closed Expansion Tanks
1 1 Tank Pressure 3 Air Pressure Sensor
Total per Unit 3 0 0 0
Total for all Units 3 0 0 0
Total Closed Expansion Tanks Points
Air Separator1 1 Pressure 1 Air Pressure Sensor
Total per Unit 1 0 0 0
Total for all Units 1 0 0 0
Total Air Separator Points
5
3
1
1
34 of 40
7/27/2019 Itcc Bms Io Hvac
35/40
Project : ITTC - APARTMENT TYPES (C,D,E,F& H) ETS ROOM
Subject : BMS Input / Output List
AI DI AO DO
Energy transfer Station (ETS)
1 Chilled Water Meters 1 1 Water Flow Meter
2 Differential Pressure Transmitter 1 Liquid Differential Pressure Sensor
3 Motorized Valve (HX) 1 VFC from Valve Limit Switch (valve by others)
4 By-Pass Motorized Valve 1 VFC from Valve Limit Switch (valve by others)5 Pressure Indicator 1 Liquid Pressure Sensor
6 Temperature Indicator 1 Immersion Temperature Sensor
Total per Unit 3 1 3 0
Total for all Units 3 1 3 0
Total ETS Points
Tertiary Chilled Water System
1 Tertiary Common Chilled Water Supply Temperature 1 Immersion Temperature Sensor
2 Tertiary commom Chilled Water Return Temperature 1 Immersion Temperature Sensor 3 Tertiary Chilled Water Flow 0 Flow Meter(By Others)
5 Tertiary Loop Chilled Water Differential Pressure in Loop 1 Liquid Differential Pressure Sensor
Total per Unit 3
Tertiary Chilled Water Pump VFD Feedback 1 0-10V From Pump VFD Control Panel
6 Tertiary Chilled Water Pump Run Status 0 VFC From Pump Control Panel
7 Tertiary Chilled Water Pump VFD Trip 1 VFC From Pump Control Panel
8 Tertiary Chilled Water Pump VFD Auto / Manual 1 VFC From Pump Control Panel
9 Tertiary Chilled Water Pump VFD Control 1 0-10V DC Signal From BMS
10 Tertiary Chilled Water Pump Enable / Disable 1 Relay Output From BMS
Total per Unit 1 2 1 1
Total for all Units 12 12 6 6
Total Tertiary Chilled Water System points
BACnet
Network
Thermostat
Item Point DescriptionQty.
1
2
RemarksSoftware
IntegrationOPC Client
6
Required Points
7
36
35 of 40
7/27/2019 Itcc Bms Io Hvac
36/40
Project : ITTC - APARTMENT TYPES (C,D,E,F&H ) ETS ROOM
Subject : BMS Input / Output List
AI DI AO DO
BACnet
Network
Thermostat
Item Point DescriptionQty. RemarksSoftware
IntegrationOPC Client
Required Points
Point List - Through OSP/BACnet connection (cont.)
1 Frequency Output (in Hz) -
2 Percent Output -
3 Speed (in RPM) -
4 Current (in Amps) -
5 Torque (in %) -
6 Power(in %) -
7 Run Time hours -
8 Run/Stop Status -
9 VSD Fault Alarm -
10 Current Limit(in %) -
11 Accel Time (in sec) -
12 Decel Time(in sec) -
13 VSD speed modulate -
14 start/stop command -
Total per Unit 0 0 0 0 1
Total for all Units 0 0 0 0 6
6
16
Total Point List-Through OSP/BACnet connection (cont.)
Through OSP/BACnet Connection
0
36 of 40
7/27/2019 Itcc Bms Io Hvac
37/40
Project : I TTC - APARTMENT TYPES (C,D,E,F& H) ETS ROOM
Subject : BMS Input / Output List
AI DI AO DO
BACnet
Network
Thermostat
Item Point DescriptionQty. RemarksSoftware
IntegrationOPC Client
Required Points
Fan Coil Units (FCU) @ Tenants Area
1 1 BACnet Network Thermostat
Total per Unit 0 0 0 0 1
Total for all Units 1
Closed Expansion Tanks
1 1 Tank Pressure 3 Air Pressure Sensor
Total per Unit 3 0 0 0
Total for all Units 3 0 0 0
Total Closed Expansion Tanks Points
Air Separator
1 1 Pressure 1 Air Pressure Sensor
Total per Unit 1 0 0 0
Total for all Units 1 0 0 0
Total Air Separator Points 1
3
37 of 40
7/27/2019 Itcc Bms Io Hvac
38/40
Project : ITTC - APARTMENT TYPES (A&B) ETS ROOM
Subject : BMS Input / Output List
AI DI AO DO
Energy transfer Station (ETS)
1 Chilled Water Meters 1 1 Water Flow Meter
2 Differential Pressure Transmitter 1 Liquid Differential Pressure Sensor
3 Motorized Valve (HX) 1 VFC from Valve Limit Switch (valve by others)
4 By-Pass Motorized Valve 1 VFC from Valve Limit Switch (valve by others)5 Pressure Indicator 1 Liquid Pressure Sensor
6 Temperature Indicator 1 Immersion Temperature Sensor
Total per Unit 3 1 3 0
Total for all Units 3 1 3 0
Total ETS Points
Tertiary Chilled Water System
1 Tertiary Common Chilled Water Supply Temperature 1 Immersion Temperature Sensor
2 Tertiary commom Chilled Water Return Temperature 1 Immersion Temperature Sensor 3 Tertiary Chilled Water Flow 0 Flow Meter(By Others)
5 Tertiary Loop Chilled Water Differential Pressure in Loop 1 Liquid Differential Pressure Sensor
Total per Unit 3
Tertiary Chilled Water Pump VFD Feedback 1 0-10V From Pump VFD Control Panel
6 Tertiary Chilled Water Pump Run Status 0 VFC From Pump Control Panel
7 Tertiary Chilled Water Pump VFD Trip 1 VFC From Pump Control Panel
8 Tertiary Chilled Water Pump VFD Auto / Manual 1 VFC From Pump Control Panel
9 Tertiary Chilled Water Pump VFD Control 1 0-10V DC Signal From BMS
10 Tertiary Chilled Water Pump Enable / Disable 1 Relay Output From BMS
Total per Unit 1 2 1 1
Total for all Units 6 6 3 3
Total Tertiary Chilled Water System points
BACnet
Network
Thermostat
Item Point DescriptionQty.
1
1
RemarksSoftware
IntegrationOPC Client
3
Required Points
7
18
38 of 40
7/27/2019 Itcc Bms Io Hvac
39/40
Project : ITTC - APARTMENT TYPES (A&B) ETS ROOM
Subject : BMS Input / Output List
AI DI AO DO
BACnet
Network
Thermostat
Item Point DescriptionQty. RemarksSoftware
IntegrationOPC Client
Required Points
Point List - Through OSP/BACnet connection (cont.)
1 Frequency Output (in Hz) -
2 Percent Output -
3 Speed (in RPM) -
4 Current (in Amps) -
5 Torque (in %) -
6 Power(in %) -
7 Run Time hours -
8 Run/Stop Status -
9 VSD Fault Alarm -
10 Current Limit(in %) -
11 Accel Time (in sec) -
12 Decel Time(in sec) -
13 VSD speed modulate -
14 start/stop command -
Total per Unit 0 0 0 0 1
Total for all Units 0 0 0 0 3
3
13
Total Point List-Through OSP/BACnet connection (cont.)
Through OSP/BACnet Connection
0
39 of 40
7/27/2019 Itcc Bms Io Hvac
40/40
Project : ITTC - APARTMENT TYPES (A&B) ETS ROOM
Subject : BMS Input / Output List
AI DI AO DO
BACnet
Network
Thermostat
Item Point DescriptionQty. RemarksSoftware
IntegrationOPC Client
Required Points
Fan Coil Units (FCU) @ Tenants Area
1 1 BACnet Network Thermostat
Total per Unit 0 0 0 0 1
Total for all Units 1
Closed Expansion Tanks
1 1 Tank Pressure 3 Air Pressure Sensor
Total per Unit 3 0 0 0
Total for all Units 3 0 0 0
Total Closed Expansion Tanks Points
Air Separator
1 1 Pressure 1 Air Pressure Sensor
Total per Unit 1 0 0 0
Total for all Units 1 0 0 0
Total Air Separator Points 1
3
40 of 40