One way joist slab (by Prof. A. Charif)
Joists (Ribs) are closely spaced T-beams. The space between the beams may be left void or filled with
light hollow blocks called Hourdis. This type of floor is very popular and offers many advantages
(lighter, more economical, better isolation).
Joists are supported by beams, which are supported by girders or columns.
ACI / SBC Conditions on joist dimensions:
Web width: mmbw 100 Web thickness: ww bh 5.3
Flange thickness:
mm
S
hf 50
12/
Spacing: mmS 800
The flange width is then: Sbb wf
ACI and SBC codes specify that concrete shear strength may be increased by 10 % in joists.
Usually stirrups are not required in joists, but are used to hold longitudinal bars. It is therefore
recommended to consider stirrups when computing longitudinal steel depth.
Analysis and design of joist slabs is equivalent to analysis and design of joist as T-beams. Shrinkage
reinforcement must then be provided in the secondary direction.
Typical joist (rib)
Vertical section
bw S
bf
hw
hf
Void or hollow
block (Hourdis)
7/29/2019 Joist Slab
2/13
Steps for the analysis and design of a joist slab:
(1) Thickness: Determine minimum thickness and:
If the thickness is unknown choose a value greater or equal to the minimum value
If the thickness is given, check that it is greater or equal to the minimum value
(2) Geometry and Loading: Check the joist dimensions anddetermine the dead and live uniform loading
on the joist (kN/m) using the given area loads (kN/m2) for live load and super imposed dead load as well
as the joist self weight. If hollow blocks (Hourdis) are present, their weight must be added to dead load.
DeadjwbjwjwcjfjfcjD ShhbbxhSDLw )( Live jfjL bxLLw
The ultimate joist load is: jLjDju www 7.14.1
(3) Flexural analysis: Determine the values of ultimate moments at major locations (exterior negative
moment, interior negative moment and positive span moment) using the coefficient method (if conditions
are satisfied) with appropriate clear lengths and moment coefficients.
(4) Flexural RC design: Perform RC design using standard methods starting with the maximum moment
value. Determine the required steel area and compare with code minimum steel area. Determine the bar
number and check bar spacing.(5) Shrinkage reinforcement:
Determine shrinkage (temperature) reinforcement and the corresponding spacing.
(6) Shear check: Perform shear check, that is, check thatuc VV with Vcincreased by 10%
If it is not checked, stirrups must be provided.
(7) Flange check: Part of the flange is un-reinforced. It must be checked as a plain concrete member.
(8) Detailing: Draw execution plans
7/29/2019 Joist Slab
3/13
One way joist slab example:
The above figure shows a one-way joist slab with beams and girders (same floor as in one
way solid slab example).
Beams are in X-direction (perpendicular to slab strip) and girders are in Y-direction
(parallel to joists). Joists are in Y-direction.
The space between joists is filled by hollow blocks (hourdis) with a density 3/12 mkNb
Concrete: 3' /2425 mkNMPaf cc Steel: MPafy 420
All beams and girders have the same section 300 x 600 mm.
All columns have the same square section 300 x 300 mm.
Superimposed dead load SDL = 1.5 kN/m
2
Live load LL = 3.0 kN/m2
All external beams and girders as well as the internal beam C support a wall with a
uniform weight of mkNwwall /4.14
4.0 m
4.0 m
4.0 m
4.0 m
8.2 m 8.1 m
A
B
C
D
E
1 2 3
T ical oist rib
500120120
50250
Joist Data (mm)
7/29/2019 Joist Slab
4/13
Solution of joist slab example:
The joist is modeled as a continuous beam with four equal spans
Step 1: Thickness use Table 9.5(a) forhmin
Table 9.5(a): Minimum thickness for beams (ribs) and one-way slabs
unless deflections are computed and checked
Simply
supported
One end
continuous
Both ends
continuous Cantilever
Solid one-
way slabL / 20 L / 24 L / 28 L / 10
Beams
or ribsL / 16 L / 18.5 L / 21 L / 8
Spans 1 and 4: One end continuous mmL
h 22.2165.18
4000
5.18min
Spans 2 and 3: Both ends continuous mmL
h 48.19021
4000
21min
Thus mmh 22.216min The total joist thickness is h = hf+ hw = 50 + 250 = 300 mm
The joist thickness is thus OK (No deflection check required)
Step 2: Geometry and Loading
a) Geometry: Check joist dimensionsWeb width: mmmmbw 100120 Web thickness: mmxbmmh ww 4201205.35.3250
Flange thickness:
mm
mmSmmhf
50
67.4112/50012/50 Spacing: mmmmS 800500
All dimension conditions are satisfied. The flange width is then: mmSbb wf 620120500
b) Loading: Dead: jwbjwjwcjfjfcjD ShhbbxhSDLw )( mkNxxxxxwjD /894.325.05.01225.012.02462.0)05.0245.1(
Live mkNxbxLLw jfjL /86.162.03
The ultimate joist load is: mkNwww jLjDju /614.87.14.1
7/29/2019 Joist Slab
5/13
Step 3: Flexural analysis
All conditions of ACI/SBC coefficient method are satisfied.
So2)( numu lwCM
2
n
uvu
lwCV
lnis the clear length wu is the factored uniform load
mln 7.32
3.0
2
3.00.4 for all spans
For shear force, span positive moment and external negative moment, lnis the clear length of the span
For internal negative moment, lnis the average of clear lengths of the adjacent spans.
Cm and Cv are the moment and shear coefficients given by ACI tables. The moment coefficients and values
are:
7/29/2019 Joist Slab
6/13
RC-SLAB1 software output is:
7/29/2019 Joist Slab
7/13
Step 4: Flexural RC design
Steel depths
b dd
hd 2
cover Cover = 20 mm
Assume bar diameterdb = 12 mm and stirrup diameterds = 8 mm
Thus mmd 2668
2
1220300
RC design for internal negative moment Mu = 11.79 kN.m
We findAs = 121.88 mm2
requiring two 12 mm bars (we may use two 10 mm bars).
We also find that one 12 mm bar is sufficient for bottom reinforcement (for positive moment) and for
external top reinforcement (external negative moment).
RC-SLAB1 design output is:
7/29/2019 Joist Slab
8/13
Step 5: Shrinkage reinforcement
As in one way solid slabs, shrinkage steel (in secondary slab direction) is equal to minimum steel.
Ashr= Asmin = 0.0018 bh = 0.0018 x 1000 x 50 = 90 mm2
(we consider 1 m strip)
We use a smaller diameter of 10 mm Thus Ab = 78.5 mm2
The spacing is mmx
A
bAS
s
b 2.87290
5.781000
Maximum spacing for shrinkage steel in slabs according to SBC / ACI is:
mmxMinmmhMinS 200)300,504()300,4(max we thus use 10 @200 mm
Step 6: Shear check
Ultimate shear force kNxLwCV njuvu 33.1827.3614.815.1
2
For joists, the nominal concrete shear strength Vc is increased by 10 %.
Thus kNNxdbf
V wc
c 26.29292602661206
251.1
61.1
'
ucc VkNVV 945.2175.0 So shear is OK. No stirrups required
Step 7: Flange check
The flange part between the webs must be checked as a plain concrete member. It is considered as fixed to
both webs with a length equal to spacing S. We consider a 1m strip.
We have a doubly fixed beam with length S= 500 mm = 0.5 m
The section is bxhf= 1000 x 50 mm
The ultimate uniform load is obtained from slab loading:
mkNmxxxmxLLhSDLw fc /88.8137.105.0245.14.117.14.1
The maximum ultimate at fixed ends is: mkNxSw
Mu .185.012
5.088.8
12
22
As the member is un-reinforced, the nominal capacity must consider concrete tension strength, which is
defined by SBC as: MPafct 5.37.0' (for ACI, it is '5.0 ct f ).
S
w
7/29/2019 Joist Slab
9/13
The nominal moment for a rectangular section with maximum stress equal to tension strength is:
mkNmmNxbh
Mf
tn .458.1.14583336
5010005.3
6
22
Strength reduction factor for plain concrete is 65.0
Therefore mkNxMn .948.0458.165.0 un MM The flange is thus OK
Step 8: Detailing
Standard execution plans conforming to ACI / SBC provisions for beams and ribs.
Ln1 Ln2 Ln3
Ln1/4
Max (Ln2/3 ,Ln3/3)Max (Ln1/3 ,Ln2/3)
Min. 150 mmBottom steel
Top steel
t
t
7/29/2019 Joist Slab
10/13
Beam loading (uniform in kN/m)
Load transferred by joists to the beam according to its tributary width ltas in one way solid slabs.
Area load (kN/m2) used for this purpose is equal to the joist load (kN/m) divided by the flange width.
In order to avoid duplication of the joist-beam joint weight, we must use the beam clear tributary width ltn.
It is obtained by subtracting the beam width: bttn bll
The dead load includes possible wall loading
Dead wallbbbctnjf
jD
bD wbxSDLhblb
ww Live tbL lxLLw
For internal beams (B, C, D) the tributary widths are: mlt 0.42
4
2
4
mltn 7.33.00.4
For beam B without wall loading:
mkNxxxwbD /008.283.05.16.03.0247.362.0
894.3 mkNxwbL /1243
The ultimate load is mkNwbu /61.59
The effective section of the beam is a T-section for internal beams and L-section for external beams.
However with small flange thicknesses, rectangular section is frequently considered.
Analysisand design of beams is performed using the same steps as in one way solid slabs.
4.0 m
4.0 m
4.0 m
4.0 m
8.2 m 8.1 m
A
B
C
D
E
1 2 3
7/29/2019 Joist Slab
11/13
Analysis and design of beam B:
The following figure is produced by RC-SLAB1 software. It performs various checks and gives the
analysis results and diagrams.
The next figure, also produced by RC-SLAB1 software, shows the flexural design results considering a T-
section or a rectangular section.
7/29/2019 Joist Slab
12/13
In theory the rectangular section and T-section designs give the same result for negative moments (flange
in tension) and different results for positive moments (flange in compression).
It can be observed that for negative external moment, rectangular and T-section designs give the same
result (four 16-mm bars). For the span positive moment, rectangular section design gives eight bars
whereas T-section design requires seven bars.
It is however worth noting that the two designs are also different for the internal negative moment. This in
fact is due to the required number of layers. The initial result of twelve bars is maintained for the T-section
because they fit in one single layer in the flange. For the rectangular section, the twelve bars require more
layers and successive design-checks are performed by RC-SLAB1 software. The final design requires
thirteen bars in three layers.
7/29/2019 Joist Slab
13/13
Girder loading (uniform and concentrated)
The girder is subjected to uniform loading as well as concentrated forces transferred from supported
beams just as in the case of one way solid slab.
Concentrated forces on columns
The internal forces in the columns may be determined as in the case of one way solid slab, using the
tributary area concept. The area load is equal to the joist line load divided by the flange width.
The dead force includes area loading as well the self weight of the webs of all beams and girders in the
tributary area. It also includes possible wall loads.
Dead tiiwallitiwiwiictjf
jD
D lwlhbAb
wP , Live tL AxLLP
For beams / girders inside the tributary area, the total web self weight and total wall load is considered
( )1i . For beams / girders on the border of the tributary area, only half is considered ( )5.0i . lti is
the member length inside the tributary area (clear length for beams and full length for girders).