+ All Categories
Transcript
Page 1: Mountainview Generating Station (MVGS) - SAWPA

Mountainview Generating Station (MVGS) A Southern California Edison Company (SCE)

Wastewater • Adjudicated water rights (1969)

• California Energy Commission permit allows for 7,500 ac-ft/year from mid-aquifer

• California Energy Commission permit allows for 750 ac-ft/year from deep aquifer

• MGVS uses 50-50 blend of cooling water make-up • Tertiary-treated municipal effluent (City of

Redlands) • Non-potable groundwater

• Near-zero wastewater discharge • 85% of wastewater is recovered and reused • Brine discharge is sent via the Inland

Empire Brine Line • 2012 Water usage and discharge

• Reclaimed water = 2,300 AF/Yr • Mid-Aquifer = 2,220 AF/Yr • Deep Wells = 414 AF/Yr • Wastewater = 144,806 MG/Yr = 444 AF/Yr

• Clarifier solid waste = 2,074 tons/Yr

2492 West San Bernardino Avenue Redlands, CA 92374 Steve Johnson, Technical Manager

MVGS (SCE)

• Power plant uses gas turbines and steam turbines for a more efficient plant.

• Turbines generate 1,054 mega watts • Southern California Edison owns

property and operated power generation on the site since 1956

Reclaimed Water2,297 gpm

Groundwater2,297 gpm

112,277 gpmto/from Unit 3 or 4

Condensers

Evaporation Loss 4,416 gpm

Side

stre

am

27 TPD Dewatered Solids to Landfill

Wastewater to IEBL169 gpm (0.432 MGD Max )

Cooling TowerReturn

Total Treated forPlant Reuse1,625 gpm

Water Plant

Total Make-up4,594 gpm

Cooling Tower Blow Down1,798 gpm

Cooling Tower

April 2014

Water Treatment and Recovery

Page 2: Mountainview Generating Station (MVGS) - SAWPA

Mountainview Generating Station (MVGS) A Southern California Edison Company

ہ Water Supplies ہ Water Treatment ہ Wastewater Discharge

This presentation.....

MVGS Redlands, CA

Page 3: Mountainview Generating Station (MVGS) - SAWPA

Mountainview Site

San Bernardino Substation

Mountainview Generating Station

San Bernardino

Loma Linda

Redlands

Page 4: Mountainview Generating Station (MVGS) - SAWPA

Plant Output

Gas Turbine A

Gas Turbine B

Steam Turbine Total

Unit 3 197 MW 165 MW 165 MW 527 MW

Unit 4 197 MW 165 MW 165 MW 527 MW Total Plant 1,054 MW

MVGS is a 4 x 2 combined cycle power plant using GE 7FA.03 Gas Turbines and D-11 Steam Turbines.

Nominal generation:

Commercial Operation December 2005 and January 2006

Page 5: Mountainview Generating Station (MVGS) - SAWPA

MVGS Units 3 & 4

4B GT/

HRSG 4A GT/

HRSG 3B GT/

HRSG

4 ST

3A GT/

HRSG

3 ST

Water Treatment

Water Conservation Basin

Cooling Tower

Page 6: Mountainview Generating Station (MVGS) - SAWPA

MVGS is a Unique Water-Cooled Power Plant

Adjudicated Water Rights (1969) CEC permit for 7,500 acft/year mid-aquiferہ CEC permit for 750 acft/year deep aquiferہ 50-50 Blend of Cooling Water Make-up Tertiary-treated municipal effluent (City of Redlands)ہ Non-potable groundwaterہ Near-zero Wastewater Discharge of wastewater is recovered and reused %85ہ Brine discharge is sent via the Inland EmpireہBrine Line (IEBL) to Pacific Ocean.

Page 7: Mountainview Generating Station (MVGS) - SAWPA

Water Usage and Discharge (2012)

Reclaimed = 2,300 AF/Y Mid-Aquifer = 2,220 AF/Y Deep Wells = 414 AF/Y Wastewater = 144,806 Mgal/yr = 444 AF/Y Clarifier solid waste = 2,074 TPY (Plant Capacity Factor = 71%)

Page 8: Mountainview Generating Station (MVGS) - SAWPA

MVGS Site Deep Well #1

900 gpm

5MM Gallon Make-up Water & Waste Water Storage Tanks

Deep Well #2 900 gpm

Mid-Aquifer Well A 2500 gpm

Mid-Aquifer Well B 4000 gpm

WATER SYSTEMS PLOT PLAN FOR

MOUNTAINVIEW GENERATING STATION

N

1 2

Cooling Towers

Water & Wastewater Treatment

Power Block

Page 9: Mountainview Generating Station (MVGS) - SAWPA

SARI Chemistry (MVGS)

TDS Average = 9,785 (Min 6,820; Max 13,410)

pH Average = 9.9 (Min 7.5; Max 10.9)

BOD Average = 4 (Min <0.6; Max 20)

O&G Average = 2.2 (Min <1.4; Max 5)

TSS Average = 26 (Min 4; Max 70)

VSS Average = 7 (Min 2; Max 42)

Page 10: Mountainview Generating Station (MVGS) - SAWPA

Water Treatment & Recovery MVGS Design Basis (Full Load, 82F DB, 63F WB)

Reclaimed Water 2,297 gpm

Groundwater 2,297 gpm

112,277 gpm to/from Unit 3 or 4

Condensers

Evaporation Loss 4,416 gpm

Side

str

eam

27 TPD Dewatered

Solids to Landfill Wastewater to IEBL

169 gpm (0.432 MGD Max )

Cooling Tower Return

Total Treated for Plant Reuse 1,625 gpm

Water Plant

Total Make-up 4,594 gpm

Cooling Tower Blow Down 1,798 gpm

Cooling Tower

Page 11: Mountainview Generating Station (MVGS) - SAWPA

High Efficiency Reverse Osmosis (HERO)

Permeate to Cooling Towers

Reject to IEBL

Permeate for Back Wash & WAC Regen

Decarbonator Weak-Acid Cation Exchangers (WACs)

Vent

Air

Reactor-Clarifier Package Gravity Filters

Cooling Tower Blow Down

and Water Plant Backwash

Sludge to Thickening & Dewatering

Return to Cooling Towers

Simplified Waste Water Treatment & Recovery Process MVGS

The waste water treatment plant at MVGS recovers up to 85% of the water for reuse that would otherwise require disposal.

Page 12: Mountainview Generating Station (MVGS) - SAWPA

Water Plant Overview

Page 13: Mountainview Generating Station (MVGS) - SAWPA

Infilco-Degremont System

Premix Feed FeCl3 @ 30-45 ppm

Premix Tank (left) Accelator Clarifier/Softener (center)

Thickener (Right)

Process Map

Page 14: Mountainview Generating Station (MVGS) - SAWPA

Reactor Clarifier (foreground) Thickener (background)

Process Map

Clarifier Feeds Polymer @ 2 ppm

Na2CO3 @ 354 ppm (CaCO3)

NaOH @ 500 ppm (CaCO3) to pH 11

Clarifier Sludge 1.4 % Solids

Page 15: Mountainview Generating Station (MVGS) - SAWPA

Reactor Clarifier Effluent Launder

(Waste Water Day Tank Upper Right)

Process Map

pH Adjusted to 8.5 with H2SO4

Outlet Flow Splitter – 1,380 gpm to Clarified Water Tanks

580 gpm to HERO system

Page 16: Mountainview Generating Station (MVGS) - SAWPA

Andritz-Netzsch Plate and Frames 20 Cubic Yard Roll-off Bins

Process Map

Sludge Filter Presses

Page 17: Mountainview Generating Station (MVGS) - SAWPA

Filter Press

Process Map

Thickener Outlet 6% Solids

Filter Press

33% Solids

Solids Trucked To Double-

Lined Landfill

Solids Calcium Carbonate

70% Magnesium Hydroxide/

Silicates 25%

Page 18: Mountainview Generating Station (MVGS) - SAWPA

Package Gravity Filters

Process Map

Multimedia Sand/Gravel/Anthracite <5 micron, 1 NTU max

NaOCl for bio-growth followed by NaHSO3

Page 19: Mountainview Generating Station (MVGS) - SAWPA

Weak Acid Cation Exchangers

Process Map

Lead-Lag Configuration Purolite C-104+ resin

<0.5 ppm Total Hardness Regenerated with 0.8% H2SO4 &

4% NaOH

Page 20: Mountainview Generating Station (MVGS) - SAWPA

Neutralization System

Process Map

Self neutralized WAC waste 8-10 pH Range

Page 21: Mountainview Generating Station (MVGS) - SAWPA

Decarbonator

Process Map

WAC effluent

Adjusted to 4.1-4.5 pH with H2SO4

Page 22: Mountainview Generating Station (MVGS) - SAWPA

Aquatech High Efficiency Reverse Osmosis Unit

Process Map

Influent pH Adjusted to 10.5

with NaOH

Biocide Addition

Brine discharge to SARI Day Tank

Page 23: Mountainview Generating Station (MVGS) - SAWPA

MVGS SARI DISCHARGE

MVGS pH Meter

Automatic Control and Shutoff

30,000 gallon SARI Day Tank

SARI pH Meter

SARI Pipeline to IEBL

SARI Sample Point

Page 24: Mountainview Generating Station (MVGS) - SAWPA

The End

Brine Discharged

Here

Page 25: Mountainview Generating Station (MVGS) - SAWPA

QUESTIONS? Answers?