Page 1: Mov Manual

DIN ISO 9001/EN 29001

Certificate Registration No.12 100 4269

Multi-turn actuatorsSARV 07.1 - SARV 10.1AUMA VARIOMATIC

Operation instructions

Page 2: Mov Manual

2

Multi-turn actuators SARV 07.1 - SARV 10.1AUMA VARIOMATIC Operation instructions

Scope of these instructions: These instructions are valid for multi-turn actuators SARV 07.1 - SARV 10.1with integral controls AUMA VARIOMATIC.These operation instructions are only valid for ”clockwise closing”, i.e. drivenshaft turns clockwise to close the valve.

Table of contents1. Safety instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41.1 Range of application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41.2 Short description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41.3 Commissioning (electrical connection) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41.4 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41.5 Warnings and notes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41.6 Further notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

2. Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

3. Transport and storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

4. Mounting to valve / gearbox . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

5. Manual operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

6. Electrical connection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

7. Test run . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

8. Setting of the limit switching. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118.1 Settings for end position CLOSED (black section) . . . . . . . . . . . . . . . . . . . . . . . . . . . 118.2 Settings for end position OPEN (white section) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

9. Setting of DUO limit switching (option) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129.1 Settings for direction CLOSE (black section) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129.2 Settings for direction OPEN (white section) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

10. Setting of torque switching . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

11. Setting of mechanical position indicator (option) . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

12. Setting of the potentiometer (option) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

13. Setting of the electronic position transmitter RWG (option). . . . . . . . . . . . . . . . . . . . . . 1 513.1 Setting for 2-wire system 4 - 20 mA and 3- /4-wire system 0 - 20 mA. . . . . . . . . . . . . . . . . . 1613.2 Setting for 3- / 4- wire system 4 - 20 mA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1713.3 Inverse operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

14. Programming AUMA VARIOMATIC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1814.1 Programming with BUS board installed (MODBUS, PROFIBUS and INTERBUS S). . . . . . . . . . 19

15. Electronic positioner (option) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2015.1 Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2015.2 Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2015.3 Programming of the positioner board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2015.4 Positioner adjustment end position CLOSED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2115.5 Positioner adjustment end position OPEN. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2215.6 Setting of the sensitivity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

Page 3: Mov Manual

3

Multi-turn actuators SARV 07.1 - SARV 10.1Operation instructions AUMA VARIOMATIC

16. Setting of the operating time (output speed) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2316.1 Setting of the operating time via internal command signal . . . . . . . . . . . . . . . . . . . . . . . 2316.2 Setting of the operating time via the speed-interface board (option) . . . . . . . . . . . . . . . . . . 2416.3 Further functions of the speed-interface board in conjunction with the positioner (option) . . . . . . . 26

17. Signal board (option) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27

18. Fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27

19. Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28

20. Certificate of conformity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29

21. Declaration of incorporation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30

Page 4: Mov Manual

1. Safety instructions1.1 Range of application AUMA actuators are designed for the operation of industrial valves, e.g.

globe valves, gate valves, butterfly valves and ball valves.For other applications, please consult us. AUMA is not liable for any possi-ble damages resulting from use in other than the designated applications.Such risk lies entirely with the user.Observance of these operation instructions is considered as part of the ac-tuator’s designated use.

1.2 Short description AUMA multi-turn actuators type SARV 07.1 - SARV 10.1 have a modulardesign. Multi-turn actuators are driven by an electric motor and controlledwith the electronic controls AUMA VARIOMATIC, which are included in thescope of supply. The limitation of travel is realised via limit switches in bothend positions. Torque seating is also possible in both end positions. Thetype of seating is stated by the valve manufacturer.

1.3 Commissioning(electrical connection)

During electrical operation certain parts inevitably carry lethal voltages.Work on the electrical system or equipment must only be carried out by askilled electrician himself or by specially instructed personnel under the con-trol and supervision of such an electrician and in accordance with the appli-cable electrical engineering rules.Recommended fuses in mains: 16 A

1.4 Maintenance The maintenance instructions (refer to page 28) must be observed, other-wise a safe operation of the actuator is no longer guaranteed.

1.5 Warnings and notes Non-observance of the warnings and notes may lead to serious injuries ordamages. Qualified personnel must be thoroughly familiar with all warningsand notes in these operation instructions.Correct transport, proper storage, mounting and installation, as well as care-ful commissioning are essential to ensure a trouble-free and safe operation.The following refererences draw special attention to safety-relevant proce-dures in these operation instructions. Each is marked by the appropriatepictograph.

This pictograph means: Note!Note marks activities or procedures which have major influence on the cor-rect operation. Non-observance of these notes may lead to consequentialdamage.

This pictograph means: Electrostatically endangered parts (ESD)!If this pictograph is attached to a printed circuit board, it contains partswhich may be damaged or destroyed by electrostatic discharges. If theboards need to be touched during setting, measurement or for exchange, itmust be assured that immediately before a discharge through contact withan earthed metallic surface (e.g. the housing) has taken place.

This pictograph means: Warning!Warning marks activities or procedures which, if not carried out correctly,can affect the safety of persons or material.

1.6 Further notes This pictograph means: Procedure may already be performed byvalve manufacturer !If actuators are delivered mounted to a valve, this step has been done in thevalve manufacturer’s plant.Setting must be checked during commissioning!

4

Multi-turn actuators SARV 07.1 - SARV 10.1AUMA VARIOMATIC Operation instructions

MOV

M

Page 5: Mov Manual

2. Technical data

Recommended fuses in mains: 16 A.

5

Multi-turn actuators SARV 07.1 - SARV 10.1Operation instructions AUMA VARIOMATIC

Type of duty: Intermittent duty S5 - 40 % ED - 1500 c/h (according to VDE 0530)Limit switching: Counter gear mechanism for end positions CLOSED / OPENTorque switching: Adjustable torque switching for closing and opening directionOperating time: Output speed adjustable via controls AUMA VARIOMATICHeater in switch compartment: 5 - 20 W, 110 V - 250 V or 24 - 48 V, external supply.Motors: Electronically commutated special AUMA motor.Motor protection: Thermistor motor protection.Electrical connection: Standard: AUMA plug/socket connector 100 with screw cable terminations.Wiring diagram: Refer to name plate.Ambient temperature: − 25 °C to + 60 °CEnclosure protection: Standard: IP 67 according to EN 60 529Finish coating: Standard: two-component iron-mica combination

Technical data1-phase AC (standard voltages and frequencies)

V 220 - 240 220 - 240Hz 50 60

Torque formodulating

Trippingtorque 1)

bothdirections

Valvemountingflange

Stemdiameter

AUMAmodulating actuatortype

Numberofstarts 2)

Minimumdurationof im-pulse 3)

Backlash

Handwheeldiameter

Hand-wheelreduc-tion

Weight 4)

max.Nm

min.Nm

max.Nm

StandardISO 5210(Special

DIN 3210)max.mm

speedmin/max

1/minmax.c/h ms

min.ms mm

kg(approx.)

15 15 30F 07F 10(G 0)

26SARV 07.1-...3/32

1500 50 75 1608:1

23SARV 07.1-...4/45 4:1

30 30 60F 07F 10(G 0)

26SARV 07.5-...3/32

1500 50 75 1608:1

23SARV 07.5-...4/45 4:1

30 30 60F 10(G 0) 40

SARV 10.0-...3/321500 50 75 200

8:127

SARV 10.0-...4/45 4:1

60 60 120F 10(G 0) 40

SARV 10.1-...1,5/161500 50 75 200

8:127

SARV 10.1-...2/22 4:1

Electrical data

Torque formodulating

Trippingtorque 1)

bothdirections

Valvemountingflange

Stemdiameter

AUMAmodulating actuatortype

Motor type Electr. powerconsumptionat max.torque 5)

Current atmax. speed andmax. torque

max.Nm

min.Nm

max.Nm

StandardISO 5210(Special

DIN 3210)max.mm

speedmin/max

1/min approx. W

220 - 240 V50 / 60 Hz

max. A

15 15 30F 07F 10(G 0)

26SARV 07. 1-...3/32

VEC 56-12-32-R500 4

SARV 07. 1-...4/45 600 5

30 30 60F 07F 10(G 0)

26SARV 07.5-...3/32

VEC 56-12-32-R700 6

SARV 07.5-...4/45 900 7

30 30 60F 10(G 0) 40

SARV 10.0-...3/32VEC 56-12-32-R

700 6

SARV 10.0-...4/45 900 7

60 60 120F 10(G 0) 40

SARV 10.1-...1,5/16VEC 56-12-32-R

700 6

SARV 10.1-...2/22 900 7

1) adjustable2) with 40% ED, for nominal voltage and

20 °C ambient temperature

3) for identical direction of rotation4) with motor, output drive B 1 and

controls AUMA VARIOMATIC

5) motor and controls

Page 6: Mov Manual

3. Transport and storage .Transport to place of installation in sturdy packing..Do not attach ropes or hooks to the handwheel for the purpose of lifting byhoist.. If multi-turn actuator is mounted on valve, attach ropes or hooks for thepurpose of lifting by hoist to valve and not to multi-turn actuator..Store in well-ventilated, dry room..Protect against floor dampness by storage on a shelf or on a woodenpallet..Cover to protect against dust and dirt..Apply suitable corrosion protection agent to unfinished surfaces.

If multi-turn actuators are to be stored for a long time (more than 6 months),the following points must be observed additionally:

.Prior to storage: Protect unfinished surfaces, especially of output driveparts and mounting surface with long-term corrosion protection agent..Check for corrosion approximately every 6 months. If first signs ofcorrosion show, apply new corrosion protection.

After mounting, connect actuator immediately to electrical system, so thatcondensation is prevented by the heater.

4. Mounting to valve / gearbox

.Prior to mounting the multi-turn actuator must be checkedfor damage..Damaged parts must be replaced by original spare parts.

The easiest position for mounting is when the valve shaft / gearbox shaftpoints upright. But mounting can be done in any other position as well.

The multi-turn actuator is delivered ex works in position CLOSED (limitswitch CLOSED tripped).

.Check if mounting flange fits the valve/gearbox.

Spigot at flanges should be loose fit!

For output drive type A (figure A), thread must match valve stem. If not or-dered explicitly with threads, stem nut is unbored or with pilot bore when de-livered. Finish machining of stem nut refer to page 7.

6

Multi-turn actuators SARV 07.1 - SARV 10.1AUMA VARIOMATIC Operation instructions

MOV

M

80.3

80.2

80.01/ 80.02

Output drive type Astem nut

Figure A

Page 7: Mov Manual

The output drive types B1, B2, B3 or B4 (figure B) are delivered with boreand keyway (usually according to ISO 5210).

.Check if bore and keyway match input shaft of valve/gearbox..Thoroughly degrease mounting faces of multi-turn actuator and valve /gearbox..Apply a small quantity of grease to input shaft of valve / gearbox..Place actuator on valve / gearbox and fasten. Fasten bolts (at leastquality 8.8, refer to table 1) evenly crosswise.

Finish machining of stem nut (output drive type A):

The output drive flange does not have to be removed from the actuator.

.Remove spigot ring (80.2, figure A) with help of wrench or similar toolfrom the mounting flange..Take off stem nut (80.3) together with thrust bearing (80.01) and thrustbearing races (80.02)..Remove thrust bearing and thrust bearing races from stem nut..Drill and bore stem nut and cut threadWhen fixing in the chuck, make sure stem nut runs true!.Clean the machined stem nut..Apply ball bearing grease to thrust bearing and race and place them onstem nut..Re-insert stem nut with thrust bearings into the mounting flange. Ensurethat dogs are placed correctly in the slots of the hollow shaft..Screw in spigot ring until it is firm against the shoulder..Press a few squirts of grease into the grease nipple with a grease gun.

7

Multi-turn actuators SARV 07.1 - SARV 10.1Operation instructions AUMA VARIOMATIC

Output drive type B 1 / B 2plug sleeve

Output drive type B 3 / B 4bore with keyway

Figure B

8.8 TA (Nm)

M 6 10

M 8 25

M 10 50

M 12 87

M 16 220

Table 1

Page 8: Mov Manual

5. Manual operation Manual operation may only be engaged when motor is notrunning. Switching over while motor is running can lead todamage at multi-turn actuator (figure C)!

.Lift change-over lever in the center of the handwheel up to max. 85°, whileslightly turning the handwheel until manual operation enganges (figure D).

Manual force is sufficient for operating the change-overlever. Using an extension is neither necessary norpermitted. If too much force is applied, this may damage thechange-over mechanism.

.Release change-over lever (snaps back into initial position by springaction). If change-over lever does not snap back, assist with hand, so thatchange-over lever is brought back into initial position (figure E).

.Manual operation remains engaged until motor is started again. Thenmotor operation is engaged automatically.

. Turn handwheel into desired direction (figure F).

Only operate manually when change-over lever is in initialposition!

.Manual operation is automatically disengaged when motor is started

8

Multi-turn actuators SARV 07.1 - SARV 10.1AUMA VARIOMATIC Operation instructions

Figure DFigure C

Figure FFigure E

Page 9: Mov Manual

AUMA plug/socket connector(customer connection XK)

Switchcompartment cover

AUMA VARIOMATIC

6. Electrical connection Work on the electrical system or equipment must only becarried out by a skilled electrician himself or by speciallyinstructed personnel under the control and supervision ofsuch an electrician and in accordance with the applicableelectrical engineering rules.

AUMA actuators SARV are operated by the electronic controlsAUMA VARIOMATIC. The controls may either be mounted di-rectly to the actuator or to a separate wall bracket.

The electrical connection to the power supply is made at aplug / socket connector with screw cable terminations asstandard.

When installing the AUMA VARIOMATIC on a wall bracket, ob-serve the following points:1) For position feedback an electronic position transmitter

(RWG) in 3-wire system must be used.2) For the connection of actuator and AUMARVARIOMATIC on

wall bracket, use additionally suitable flexible and screenedconnecting cables.

3) The max. permissible cable length between multi-turnactuator and AUMA VARIOMATIC is 25 m.

.Check if type of current, supply voltage and frequencycorrespond to motor data (refer to motor name plate)..Remove plug cover (AUMA plug / socket connector)(figure G)..Loosen screws and remove socket carrier from plugcover.. Insert cable glands suitable for connecting cables.

.Enclosure protection IP 67 is only ensured if suitablecable glands are used.

.Connect cables according to order related wiring diagram CI S. . . KMS14TP . . .. The wiring diagram belonging to the actuator is attached to thehandwheel in a weather-proof bag, together with the operationinstructions. In case the wiring diagram is not available, it can be obtainedfrom AUMA (state commission no., refer to name plate).Cross sectional areas: controls cables max. 2,5 mm2,

power supply max. 6 mm2..Connect heater via external voltage source so that condensation isprevented..Only the same potential can be switched through the two circuits of theswitch. Different potentials require tandem switches.Versions with gold-plated microswitches (option) may only be loaded withsmall voltages (50 V DC / 400 mA).

.The valve manufacturer specifies whether switching off in the endpositions should be via limit switch (limit seating) or torque switch(torque seating).

.For the connection of position transmitters (potentiometers) screenedcables must be used.. Insert socket carrier and fasten..Clean sealing faces at plug cover, terminal compartment cover and checkif O-ring is o.k.. Apply a thin film of non-acidic grease (e.g. Vaseline) tothe sealing faces..Place cover and fasten 4 bolts evenly crosswise..Fasten cable glands securely to ensure enclosure protection IP 67.

9

Multi-turn actuators SARV 07.1 - SARV 10.1Operation instructions AUMA VARIOMATIC

MOV

M

Figure G

Page 10: Mov Manual

7. Test run These operation instructions are valid for ”clockwise closing”, i.e. drivenshaft turns clockwise to close the valve.

.Set selector switch to position ‘OFF’ (figure H)..Switch on supply voltage..Engage manual operation as described under clause 5 on page 8..Move actuator manually into both end positions of the valve..Check if limit switching is set correctly. When limit switching is setcorrectly, the appropriate LED at the local controls is illuminated for eachend position (figure H). If both LEDs are illuminated at the same time or ifno LED is illuminated when the end position is reached, the limit settingmust be set as described in clause 8 on page 11.

When limit switching is set correctly:.Perform test run at local controls with selector switch in position ”LOCAL”via push-buttons

10

Multi-turn actuators SARV 07.1 - SARV 10.1AUMA VARIOMATIC Operation instructions

Selector switch:LOCAL-OFF-REMOTE

Push-buttons:OPENSTOPCLOSE

LEDs:OPENFAULTCLOSED

AUMA plug/socket connector(Customer connection XK)

Switchcompartment cover

Local controls

AUMA VARIOMATIC

Figure H

Page 11: Mov Manual

8. Setting of the limit switching

.Engage manual operation as described underclause 5 on page 8.

.Remove switch compartment cover and, ifinstalled, pull off indicator disc (figure J1). Openend spanner (ca. 10 mm) may be used as lever.

8.1 Settings for end position CLOSED (black section)

.Turn handwheel clockwise until valve is closed..Press down and turn setting spindle A (figure J2) with screw driver (5 mm)in direction of arrow, thereby observe pointer B. While a ratched is feltand heard, the pointer B moves 90° every time up to point C.When pointer B is 90° from point C, continue turning slowly. If pointer Bdoes not move anymore, stop turning and release setting spindle. In caseof having turned too far, continue turning and approach switching pointanew.

8.2 Settings for end position OPEN (white section).Turn handwheel counter-clockwise until valve is open, then turn backapproximately 1/2 a turn..Press down and turn setting spindle D (figure J3) with screw driver (5mm) in direction of arrow, thereby observe pointer E. While a ratched isfelt and heard, the pointer E moves 90° every time up to point F.When pointer R is 90° from point F, continue turning slowly. If pointer Edoes not move anymore, stop turning and release setting spindle. In caseof having turned too far, continue turning and approach switching pointanew.

11

Multi-turn actuators SARV 07.1 - SARV 10.1Operation instructions AUMA VARIOMATIC

Mark

CoverIndicator discFigure J1

MOV

M

D

F

Figure J2

MOV

M

Page 12: Mov Manual

.Perform electrical test run to check seating in the end position.

Red test buttons T and P (figure J2) serve for operating the microswitchesof torque and limit switching. In case a fault occurs, perform emergencyswitch-off by turning both test buttons the appropriate direction of the arrowDÖL/DSR.

9. Setting of DUO limit switching (option)

Switching point (intermediate position) must be approachedfrom the same direction as afterwards in electricaloperation.

.Move valve to desired intermediate position.

9.1 Settings for direction CLOSE (black section).Turn setting spindle G (figure J3) with screw driver (5 mm) in direction ofarrow, thereby observe pointer H. While a ratched is felt and heard, thepointer H moves 90° every time up to point C.When pointer H is 90° from point C, continue turning slowly. If pointer Hdoes not move anymore, stop turning and release setting spindle. In caseof having turned too far, continue turning and approach switching pointanew.

9.2 Settings for direction OPEN (white section).Turn setting spindle K (figure J3) with screw driver (5 mm) in direction ofarrow, thereby observe pointer L. While a ratched is felt and heard, thepointer L moves 90° every time up to point F.When pointer L is 90° from point F, continue turning slowly. If pointer Ldoes not move anymore, stop turning and release setting spindle. In caseof having turned too far, continue turning and approach switching pointanew..Perform electrical test run to check correct setting for the intermediatepositions.

12

Multi-turn actuators SARV 07.1 - SARV 10.1AUMA VARIOMATIC Operation instructions

MOV

M

*) Option

Figure J3

Page 13: Mov Manual

10. Setting of torque switching

.Set torque must suit the valve!.When multi-turn actuator is delivered by a valvemanufacturer, setting was made during testing..This setting should only be changed with the consent ofthe valve manufacturer!

.Loosen both lock screws O at the torque dial (figure K)..Turn torque dial (P) to set it to the required torque (1 da Nm = 10 Nm).Example:Figure K shows the following setting:

3,5 da Nm = 35 Nm for direction CLOSE3,5 da Nm = 35 Nm for direction OPEN.Tighten lock screws O again

.The torque switches can also be operated in manualoperation. When appropriately controlled electrically, thetripping of the torque switch is stored and thus anelectrical start in a specific direction is prevented..The torque switching acts as overload protection over fulltravel, also when stopping in the end positions by limitswitch.

. If applicable, press indicator disc on shaft and perform setting asdescribed under clause 11, page 14..Clean sealing faces at cover and housing; check if O-ring is in goodcondition. Apply a thin film of non-acidic grease to the sealing faces..Place cover on switch compartment and fasten hex. bolts evenlycrosswise.

13

Multi-turn actuators SARV 07.1 - SARV 10.1Operation instructions AUMA VARIOMATIC

MOV

M

P OO P

Setting CLOSED Setting OPEN

Figure K

Page 14: Mov Manual

11. Setting of mechanical position indicator (option)

Indicator disc rotates approximately 180° at full travel from OPEN to CLOSEor vice versa.A suitable reduction gearing was installed in our works. If the turns perstroke need to be changed at a later date, the reduction gearing may haveto be exchanged, too.

.Move valve to end position CLOSED..Turn lower indicator disc until symbol CLOSED is in alignment with themark on the indicator glass of the cover (figure L)..Move actuator to end position OPEN..Hold lower indicator disc in position and turn upper disc with symboluntil it is in alignment with the mark on the indicator glass of the cover.

12. Setting of the potentiometer (option)

.Move valve to end position CLOSED..Remove switch compartment cover and, if installed, pull off indicator discas described under clause 8, page 11..Turn potentiometer (R2) clockwise to end position (Figure M, page 15).End position CLOSED corresponds to 0 %, end position OPEN to 100 %.

Due to the ratio of the reduction gearings for the positiontransmitter the complete resistance range is not alwaysutilized for the whole travel. Therefore an external possibilityfor adjustment (setting potentiometer) must be provided.

.Perform fine-tuning of the zero point at external setting potentiometer..When using AUMA power supply unit PS 01 and indication instrumentwith percentage scale, perform fine-tuning of zero point at power supplyunit..Operate valve in motor mode to end position OPEN..Perform fine-tuning of maximum value at external setting potentiometer..When using AUMA power supply unit PS 01 and indication instrumentwith percentage scale, perform fine-tuning of maximum value at powersupply unit.. If applicable, press indicator disc on shaft and perform setting asdescribed under clause 11..Clean sealing face, check O-Ring, apply a thin film of non-acidic grease tosealing face..Fit and fasten switch compartment cover.

14

Multi-turn actuators SARV 07.1 - SARV 10.1AUMA VARIOMATIC Operation instructions

Mark

CoverIndicator discFigure L

MOV

M

Page 15: Mov Manual

13. Setting of the electronic position transmitter RWG (option)

The electronic position transmitter is set in our factory according to the sig-nal range stated in the order. Perform a subsequent adjustment accordingto subclause 13.1 or 13.2.

After mounting the multi-turn actuator on the valve check setting and adjust,if necessary.

15

Multi-turn actuators SARV 07.1 - SARV 10.1Operation instructions AUMA VARIOMATIC

Technicaldata

RWG 4020

3-/4- wire system 2-wire system

Output I 0 - 20 mA, 4 - 20 mA 4 - 20 mA

Supplyvoltage

Uv24 V DC, ±15%

smoothed14 V DC + (I x RB),

max. 30 V

max. current drawn I24 mA at 20 mAoutput current

20 mA

max. ext. resistance RB 600 Ω (Uv - 14 V) / 20 mA

1 2 3 4

5 6 7

BK

YE

RD

Measuringpoint 1

+

3- and 4- wire system

R2N M

max(20 mA)(0/4 mA)

2- wire system

For change-over also change wiring

0/4 - 20 mA

Measuring-point 2-

Figure N: Positioner board

Cover plate

R2

Figure M

Page 16: Mov Manual

13.1 Setting for 2-wire system 4 - 20 mA and 3- /4-wire system 0 - 20 mA.Connect voltage to AUMA VARIOMATIC..Move valve to end position CLOSED..Remove switch compartment cover and, if installed, pull offindicator disc as described under clause 8, page 11..For actuators with measuring points not accessible from theoutside, remove cover plate (figure O)..Connect ammeter for 0 - 20 mA to measuring points (figure N,page 15 or figure O).In end position CLOSED of 3- or 4-wire system, the value aftersetting is 0 mA, for 2-wire system it is 4 mA.

The circuit (external load) must be connected (observemax. ext. resistance R B), or the appropriate poles at theAUMA plug/socket connector must be linked (refer towiring diagram C IS...KMS 14TP...), otherwise it is notpossible to measure a value.

.Turn potentiometer (R2) clockwise to initial position.Turn potentiometer (R2) whilst decreasing output signal until stop is felt..Turn trimmer potentiometer (N) clockwise, until output current starts toincrease..Turn back trimmer potentiometer (N), until a residual current ofapprox. 0,1 mA (or 4,1 mA in case of 2-wire system) is reached. Thisensures that the signal remains above the dead and live zero point..Move valve to end position OPEN..Set to end value 20 mA with trimmer potentiometer (M)..Approach end position CLOSED anew and check minimum value (0 mAor 4 mA). If necessary, correct the setting.. In case cover plate (figure O) has been removed, fit anew.. If applicable, press indicator disc on shaft and perform setting asdescribed under clause 11, page 14..Clean sealing face, check O-Ring, apply a thin film of non-acidic grease tosealing face..Fit and fasten switch compartment cover.

If the maximum value is not reached, the selection of thereduction gearing must be checked.

16

Multi-turn actuators SARV 07.1 - SARV 10.1AUMA VARIOMATIC Operation instructions

Cover plate

Measuringpoint 2 (–)0/4 - 20 mA

Measuringpoint 1 (+)0/4 - 20 mA

R2N (0/4 mA) M (20 mA)

Figure O

Page 17: Mov Manual

13.2 Setting for 3- / 4- wire system 4 - 20 mA

.Connect voltage to AUMA VARIOMATIC..Move valve to end position CLOSED..Remove switch compartment cover and, if installed, pull offindicator disc as described under clause 8, page 11..For actuators with measuring points not accessible from theoutside, remove cover plate (figure O)..Connect ammeter for 0 - 20 mA to measuring points (figure N,page 15 or figure O).

The circuit (external load) must be connected (observemax. ext. resistance R B), or the appropriate poles at theAUMA plug/socket connector must be linked (refer towiring diagram C IS...KMS 14TP...), otherwise it is notpossible to measure a value.

.Turn potentiometer (R2) clockwise to initial position.Turn potentiometer (R2) whilst decreasing output signal until stop is felt..Turn trimmer potentiometer (N) clockwise, until output current starts toincrease..Turn back potentiometer (N), until a rest current of approx. 0,1 mAis reached..Move valve to end position OPEN..Set to end value 16 mA with trimmer potentiometer (M)..Move valve to end position CLOSED..Set potentiometer (N) from 0,1 mA to initial value 4 mA.

This results in a simultaneous shift of the end value by 4 mA, so that therange is now 4 - 20 mA..Approach both end positions anew and check setting. If necessary,correct the setting.. In case cover plate (figure O) has been removed, fit anew.. If applicable, press indicator disc on shaft and perform setting asdescribed under clause 11, page 14..Clean sealing face, check O-Ring, apply a thin film of non-acidic grease tosealing face..Fit and fasten switch compartment cover.

If the maximum value is not reached, the selection of thereduction gearing must be checked.

13.3 Inverse operation For inverse operation exchange the connections 7 (red/RD) and 5(black/BK) at positioner board (figure N, page 15).

17

Multi-turn actuators SARV 07.1 - SARV 10.1Operation instructions AUMA VARIOMATIC

Page 18: Mov Manual

14. Programming AUMA VARIOMATIC

.Remove 4 screws at VARIOMATIC (Figure P / 8.1) and take off cover.

. In the factory push-to-run operation REMOTE and push-to-run operationLOCAL are programmed (refer to table 2).

.The type of seating - limit or torque seating (DIP switch S1 pos. 5 andpos. 6) must be determined by the valve manufacturer.

.Set desired programming according to table 2 at DIP switch S1(figure Q).

If no positioner (figure S, page 20) or speed-interface board(figure W, page 24) is fitted, the DIP switch S1 pos. 7 mustalways be in position ”ON”.

.Replace cover and fasten 4 bolts (figure P / 8.1) evenly crosswise.

18

Multi-turn actuators SARV 07.1 - SARV 10.1AUMA VARIOMATIC Operation instructions

MOV

M

DIP switch S1for programming

Cover platestandard

ON12

34

56

7

Potentiometerfor setting ofOPERATING TIME

Diagnosis LED (green):Illuminated whenready

Diagnosis LED (red):Motor protectiontripped

Diagnosis LED (green):Enable REMOTE (option)always installed,illuminated during normaloperation

Diagnosis LEDs foractive REMOTEcontrol commands:run command STOP (red)run command OPEN (green)run command CLOSE (yellow)

Logic board

Figure Q: VARIOMATIC standard

Switchcompartment cover

AUMA VARIOMATIC

Local controls

Figure P: Actuator SAR with controls AUMA VARIOMATIC

Page 19: Mov Manual

14.1 Programming with BUS board installed (MODBUS, PROFIBUS and INTERBUS S)

Refer to separate instructions for appropriate bus system.

1) PROFIBUS-FMS and Set switch position S1 pos. 7 to ”ON”.MODBUS (no nominal output speed possbible via bus)Profibus DP andINTERBUS-S switch position S1 pos. 7 to OFF.

19

Multi-turn actuators SARV 07.1 - SARV 10.1Operation instructions AUMA VARIOMATIC

DIP switch S1(on logic board)

Programming

Self-retaining REMOTE (not applicable for BUS systems)

Push-to-run operationREMOTE

Self-retaining LOCAL

Push-to-run operation LOCAL

Type of seatingfor end position

CLOSEDfor end position

OPEN

limit seating

torque seating

external (via Bus) internal

Nominal output speed 1)

Table 3

1 2 3 4 5 6 7

ONOFF

1 2 3 4 5 6 7

ONOFF

1 2 3 4 5 6 7

ONOFF

1 2 3 4 5 6 7

ONOFF

1 2 3 4 5 6 7

ONOFF

1 2 3 4 5 6 7

ONOFF

1 2 3 4 5 6 7

ONOFF

1 2 3 4 5 6 7

ONOFF

1 2 3 4 5 6 7

ONOFF

DIP switch S1(on logic board)

Programming

Direction CLOSE Direction OPEN

Self-retaining REMOTE

Push-to-run operationREMOTE

Self-retaining LOCAL

Push-to-run operationLOCAL

Type of seatingfor end position

CLOSEDfor end position

OPEN

limit seating

torque seating

For installed positioner:

Speed dependenton error variable

Speed not dependenton error variable

Table 2

ON

1 2 3 4 5 6 7OFF

1 2 3 4 5 6 7

ONOFF

1 2 3 4 5 6 7

ONOFF

1 2 3 4 5 6 7

ONOFF

1 2 3 4 5 6 7

ONOFF

1 2 3 4 5 6 7

ONOFF

1 2 3 4 5 6 7

ONOFF

1 2 3 4 5 6 7

ONOFF

1 2 3 4 5 6 7

ONOFF

1 2 3 4 5 6 7

ONOFF

1 2 3 4 5 6 7

ONOFF

1 2 3 4 5 6 7

ONOFF

1 2 3 4 5 6 7

ONOFF

1 2 3 4 5 6 7

ONOFF

Page 20: Mov Manual

15. Electronic positioner (option)15.1 Technical data Command signal (input sig. E1, nominal value) 0/4 - 20 mA (option 0 - 5 V)

Feedback (input signal E2, actual value) 4 - 20 mA (option 0 - 5 V)Sensitivity (dead band) ∆E 0,25 - 2,5 %Time delay toff 0,5 - 10 sInput resistance 250 Ohm

15.2 Setting .To set the positioner, remove 4 screws (figure P / 8.1, page 18) and takeoff cover..For the functions of the LEDs installed on positioner board: refer tofigure S..Check programming of the logic board according to pages 18/19, clause14: DIP switch S1 on the logic board: Pos. 1 and pos. 3 must be in pos.”OFF” (figure S).If no speed variation is desired, the DIP switch S1 pos. 7 must be inposition ”ON”. If an error-dependent speed variation is required (figure R),set DIP switch S1 pos. 7 to ”OFF”.

1) Enable REMOTE (option) see corresponding wiring diagram:Analogue command signal or run command via local controls arenot accepted without external enable signal (24V DC).

15.3 Programming of the positionerboard

.Remove cover plate (Figure S)..Set switch S2 pos. 5 (figure T1, page 22) according to input signal E1(nominal value):0 - 20 mA: position ”OFF”4 - 20 mA: position ”ON”.Set switch S2 pos. 6 for E2 (actual value) = 4 mA to position ”ON”.(for E2 position feedback via potentiometer 0 - 5 V in position ”OFF”)

In standard version switch S3 (figure T1, page 22) for command signal E1= 0/4 - 20 mA, i.e. end position ”OPEN” = 20 mA, must be in position 1.Version for inverse operation (i.e. end position ”OPEN” = 0/4 mA) must beordered accordingly from the factory.

20

Multi-turn actuators SARV 07.1 - SARV 10.1AUMA VARIOMATIC Operation instructions

MOV

M

oper

atin

gsp

eed

100%

control deviation (error) 100%

Figure R: Speed dependent on error variable

1)Diagnosis LED (green)Enable REMOTE (option)always installed,illuminated during normaloperation

V24: Run command OPEN (green)

V23: Run command CLOSE (yellow)

V35: Permissible number of startsexceeded (red)

V37: Signals E1 or E2not available (red)

R88: Delay time

12

34

56

7

DIP switch S1for programming

Cover platepositioner

Potentiometerfor setting ofOPERATING TIME

Diagnosis LED (green):Illuminated whenready

Logic board

Diagnosis LED (red):Motor protectiontripped

Figure S: VARIOMATIC with positioner

Page 21: Mov Manual

Programming for faults:Behaviour on loss of input signal E1 and / or

on loss of feedback signal E2.Pre-condition: Signals 4 - 20 mA

Before commencing the positioner adjustment it must beensured that the limit and torque switching of the actuator(clauses 8-10) as well as the feedback (clauses 12 and 13)have been set.

15.4 Positioner adjustmentend position CLOSED

.Set selector switch (local controls) to position I (LOCAL)..Run multi-turn actuator by depressing push-button to end positionCLOSED..Connect input signal E1(nominal value) (0 or 4 mA).Missing signal E1 and / or E2 is indicated by LED E1/E2 < 4 mA(figures T1+T2 / V37)..To measure the nominal value E1 connect Voltmeter (0 - 5 V) to themeasuring points M1 and M2 (figure T1, page 22).For E1 (nominal value) = 0 mA: measure 0 V.For E1 (nominal value) = 4 mA: measure 1 V..To measure the actual value E2 connect voltmeter to measuring pointsM3 and M4.For E2 (actual value) = 4 mA: measure 1 V.If measured value is not correct: Perform feedback adjustment accordingto page 14 clause 12, or page 15 clause 13..Set potentiometer R35 (∆E) and R31 (sens) to minimal value by turningcounter-clockwise.

Process related (desired)behaviour:

Programming :(Figure T1, page 22)

fail as is , i.e. actuator stops imme-diately and remains at this position.

fail close , i.e. actuator drives valveto position CLOSED.

fail open , i.e. actuator drives valveto position OPEN.

21

Multi-turn actuators SARV 07.1 - SARV 10.1Operation instructions AUMA VARIOMATIC

If Possible LED indications:(refer to figures T1 and T2)

Then Required setting in end position CLOSED:(refer to figures T1 and T2)

LEDs are not illuminated Turn potentiometer “0” (R25) slightly clockwise untilLED (V23 yellow) lights up

LED (V24 green) isilluminated

Turn potentiometer “0” (R25) slightly clockwise untilLED (V24) goes out and LED (V23 yellow) lights up

LED (V23 yellow) isilluminated

Turn potentiometer “0” (R25) counter-clockwise until LED(V23) goes out.Then turn potentiometer “0" (R25) slightly clockwise until LED(V 23 gelb) lights up again.

Page 22: Mov Manual

15.5 Positioner adjustment end

position OPEN

.Run multi-turn actuator by depressing push-button (local controls) toend position OPEN ..Measure 5 V at measuring points M4 and M3. (Figure T1).If measured value is not correct: Perform feedback adjustment accordingto page 14 clause 12, or page 15 clause 13 and continue with page 21subclause 15.4..Connect max. command signal E1 = 20 mA..Measure 5 V at measuring points M1 and M2. (Figure T1)If measured value is not 5 V, check the externally supplied commandsignal.

15.6 Setting of the sensitivity .Set selector switch to position II (REMOTE) at local controls (figure P,page 18)..Supply command signal to any value between 0/4 and 20 mA..Set dead band with potentiometer ∆E (P9) so that multi-turn actuator doesnot readjust after a single control operation:- turning clockwise results in reduced sensitivity (dead band increased)

When setting E the following must be observed by allmeans:If the number of starts is too high, this can lead tounnecessary wear at the valve and actuator. Therefore thehighest possible sensitivity (dead band) which is permittedfor the process must be set.

.To prevent an exceeding of the max. permissible number of starts(1 500 c/h) in extreme cases, a time delay between 0,5 s (left stop) and10s (right stop) may be set with potentiometer t-off (R88).

22

Multi-turn actuators SARV 07.1 - SARV 10.1AUMA VARIOMATIC Operation instructions

If LED indications:(refer to figures T1 and T2)

Then Required setting in end position OPEN:(refer to figures T1 and T2)

LED's are not illuminated Turn potentiometer „max” (R28) slightly counter-clockwise untilLED (V24 green) lights up.

LED (V24 green) isilluminated

Turn potentiometer „max” (R28) clockwise until LED (V24)goes out.Then turn potentiometer „max” (R28) slightly counter-clockwise untilLED (V24) lights up again.

LED (V23 yellow) isilluminated

Turn potentiometer „max” (R28) slightly counter-clockwise untilLED (V23) goes out and LED (V24 green) lights up.

R28

R25

R31

R35

V24

STELLZEITOPERATINGTIME

ENABLEFREIGABE

READYBEREIT V23

V35V37

R88

J

- +

Bild T2: Cover plate positioner

R28

R25

R31

R35

M4M3M2M1E1

Mess-punkte

S3

S2

V24V23V35V37

R88

E2

Figure T1: Positioner board

Page 23: Mov Manual

16. Setting of the operating time (output speed)16.1 Setting of the operating time via internal command signal

.Loosen 4 screws (8.1) and remove cover (figure U)..Set required operating time at potentiometer ”OPERATING TIME”(figure V).Short operating time: turn counter-clockwise.Long operating time: turn clockwise.Speed ranges see technical data sheet.Replace cover and fasten 4 bolts (8.1) evenly crosswise.

23

Multi-turn actuators SARV 07.1 - SARV 10.1Operation instructions AUMA VARIOMATIC

Switchcompartment cover

AUMA VARIOMATIC

Local controls

Figure U: Actuator SAR with controls AUMA VARIOMATIC

DIP switch S1for programming

Cover platestandard

ON12

34

56

7

Potentiometerfor setting ofOPERATING TIME

Diagnosis LED (green):Illuminated whenready

Diagnosis LED (red):Motor protectiontripped

Diagnosis LED (green):Enable REMOTE (option)always installed,illuminated during normaloperation

Diagnosis LEDs foractive REMOTEcontrol commands:run command STOP (red)run command OPEN (green)run command CLOSE (yellow)

Logic board

Figure V: VARIOMATIC standard

Page 24: Mov Manual

16.2 Setting of the operating time via the speed-interface board (option)

(refer to order-related wiring diagram CI S...KMS 14TP...)With the speed-interface board the operating time (speed) can also bepre-determined through an external signal, either analogue (command sig-nal E3 = 0 - 20 mA or 4 - 20 mA) or binary (command signal n1, n2).

The simultaneous use of the analogue and the digitaloperating time set signal is not possible!

.Loosen 4 screws (8.1) and remove cover (figure U, page 23)..The speed-interface board (figure W) is situated directly above the logicboard. Depending on the version (with or without positioner), remove theboards above it (cover plate, positioner board and additional board).

Settingon logic board:

.Check on the logic board whether the DIP switch S1, pos. 7 (nominaloutput speed) is in position ”OFF”. If necessary, correct the switch position(see clause 14, pages 18/19)..Set the potentiometer ”OPERATING TIME” (figure V, page 23) on thelogic board to the fully clockwise position (max. speed) to make use of theentire range of operating time. If the minimal operating time (max. speed)has to be limited to a higher value as the operating time possible by theactuator (see technical data sheet), set potentiometer to this value (e.g. toavoid water hammer).

Setting on thespeed-interface board:

When using the option positioner (see clause 15, page 20) set the selectorswitch S2-2.2 (figure W) on the speed-interface board to position‘positioner’. For all other versions the switch S2-2.2 has to be set to position‘speed-interface board’.

24

Multi-turn actuators SARV 07.1 - SARV 10.1AUMA VARIOMATIC Operation instructions

DIP switch S1for programming

LED’s:V4: nominal operating

time n1V6: nominal operating

time n2

Logic board

ON

Speed-interfaceboard

Range switch S1-2.2(component A2.2)for analogue nominaloperating time E3

Range switch S2-2.2(component A2.2)for analogue nominaloperating time E3

Dot visible:4 - 20 mA

Dot visible:positioner

Dot not visible:0 - 20 mA

Dot not visible:interface board

Potentiometer R9:for setting of the binarynominal operating time n1

Potentiometer R16:adjustment analoguenominal operating time E3

Potentiometer R10:for setting of the binarynominal operating time n2

Measuring point MP2 Measuring point MP1

FigureW: Speed-interface board

Page 25: Mov Manual

Analoguenominal operating time E3:

The analogue operating time range E3 (refer to wiring diagram CI S...KMS14TP...) can be set with the switch S1-2.2 (figure W) to either 0 - 20 mA or4 - 20 mA.After a change, adjustment of the max. value (20 mA) is necessary.The adjustment is performed as follows:.Connection of 24 V DC +/- 10 % to the analogue input of the

speed-interface board (see wiring diagram CI S...KMS 14TP...)max. current input ≤ 30mA.Connection of 20 mA at nominal operating time E3 of the speed-interfaceboard (see wiring diagram CI S...KMS 14TP...).Measure voltage between MP1 and MP2 (figure W)..Adjust the voltage to 10,00 V +/- 0,01 V by using the potentiometer R16(figure W).

Binarynominal operating n1, n2

Two inputs are available for the setting of the operating time via binary sig-nals.The adjustment of the two operating times is performed as follows:Control of the binary nominal operating time n1 by.Connection of 24 V DC to the binary input n1 of the speed-interface board

(see wiring diagram CI S...KMS 14TP...)A visual check of the connected signal with LED V4 is possible (figure W)..The setting of the operating time is done via potentiometer R9 (figure W),clockwise rotations equals higher speed = shorter operating time.

Control of the binary nominal operating time n2 by.Connection of 24 V DC to the binary input n2 of the speed-interface board(see wiring diagram CI S...KMS 14TP...)A visual check of the connected signal with LED V6 is possible (figure W)..The setting of the operating time is done via potentiometer R10 (figureW), clockwise rotations equals higher speed = shorter operating time.

.During simultaneous control of n1 and n2, the shortestoperating time has priority..Without control of n1 and n2, the max. operating time isavailable.

.When operated via local controls, the actuator always runswith max. speed (shortest operating time)..Control of the set speed (operating time) is only possiblevia REMOTE commands.

25

Multi-turn actuators SARV 07.1 - SARV 10.1Operation instructions AUMA VARIOMATIC

Page 26: Mov Manual

16.3 Further functions of the speed-interface board in conjunction with the positioner (option)

.Remote change-over of the nominal operating time

This function is only possible in combination with theanalogue or binary nominal operating time (selector switchS2-2.2 in position ‘positioner’, figure W).

The nominal operating time can be changed between theoperating time determined by the positioner and by the customer via thespeed-interface board with a + 24 V DC signal from Remote.

.Change-over AUTO/REMOTE

The positioner can be completely switched off remotely with a + 24 V DCsignal. This permits the use of the binary control signals (OPEN, STOP,CLOSE) in conjunction with the analogue or digital nominal output speed.

1) The binary control signals must be externally deactivated(customer) as long as the positioner is active.

2) This function is only possible in combination with theanalogue or binary nominal operating time (selectorswitch S2-2.2 in position ‘positioner’, figure W, page 24).

3) If there is no external signal connected, the actuator runswith its slowest speed (i.e. its longest operating time).

26

Multi-turn actuators SARV 07.1 - SARV 10.1AUMA VARIOMATIC Operation instructions

for connectionat AUMA

plug / socketconnector

XKrefer to wiring

diagramCI S...

Voltage Function

0 V DC

internal nominal operating timeby positioner

(operating time dependent on error variable)

24 V DC

external nominal operating timeby speed interface board 3)

(analogue or binary nominal operating time)

for connectionat AUMA

plug / socketconnector XKrefer to wiring

diagramCI S...

Voltage Function

0 V DC

Run commandsby positioner1)

(operating time dependent on error variable)

24 V DC

Run commandsby binary REMOTE commands 2) 3)

(OPEN, STOP, CLOSE and analogue orbinary nominal operating time)

Page 27: Mov Manual

17. Signal board (option) Signal boards with the option Running indication (blinker transmitter) offerthe possibility to switch over from impulse to continuous signal by way of asliding switch (see wiring diagram CI S...KMS 14TP...).The signal board (figure X) is accessible after taking off the green coverplate (figure Q, page 18, or figure S, page 20).

18. Fuses Fuses (figure Y) are accessible after removing the local controls(figure P, page 18)

Recommended fuses in mains: 16 A

Disconnect actuator from the mains before changing thefuses.

27

Multi-turn actuators SARV 07.1 - SARV 10.1Operation instructions AUMA VARIOMATIC

switch for running indication (blinker transmitter)OFF ON

Figure X: Signal board

Fuses :(Figure Y)

F 1 F 2

20 x 5 20 x 5

10 A T;250 V

1 A T;250 V

F2

F1

Figure Y: Fuses

Page 28: Mov Manual

19. Maintenance After commissioning, check for damages on paint of multi-turn actuator. Doa thorough touch-up to prevent corrosion. Original paint in small quantitiescan be supplied by AUMA.

AUMA multi-turn actuators require very little maintenance.Precondition for reliable service is correct commissioning.

Seals made of elastomers are subject to aging and must therefore regularlybe checked and, if necessary, exchanged.

It is also very important that the O-rings at the covers are placed correctlyand cable glands fastened firmly to prevent ingress of dirt or water.

We recommend:

. If operated seldom, perform a test run about every 6 months. This assuresthat the actuator is always ready to operate..Approximately six months after commissioning and then every year checkbolts between actuator and valve/gearbox for tightness. If required,re-tighten applying the torques given in table 1, page 7..At intervals of approx. 6 months press in several squirts of ball bearinggrease at the lubrication nipple with grease gun.

Lubrication of the valve stem must be done separately.

The gear housing is filled with lubricant in the factory.

A grease change is recommended after 4 - 6 years.

28

Multi-turn actuators SARV 07.1 - SARV 10.1AUMA VARIOMATIC Operation instructions

Page 29: Mov Manual

20. Certificate of conformity

29

Multi-turn actuators SARV 07.1 - SARV 10.1Operation instructions AUMA VARIOMATIC

Page 30: Mov Manual

21. Declaration of incorporation

30

Multi-turn actuators SARV 07.1 - SARV 10.1AUMA VARIOMATIC Operation instructions

Page 31: Mov Manual

31

Multi-turn actuators SARV 07.1 - SARV 10.1Operation instructions AUMA VARIOMATIC

Page 32: Mov Manual

Tel 0711/34803-0 Fax 0711/34803-34

Armaturen- und MaschinenantriebeWERNER RIESTER GmbH & Co. KG

E-Mail [email protected]

SA 07.1 - SA 48.1max 32 000 Nm

SG 05.1 - SG 12.1

Part-turn actuatorsMulti-turn actuators

Our product range

AS 6 - AS 50 GST 10.1 - GST 40.1

Part-turn actuators Spur gearboxes

max 500 Nm max 16 000 Nm

GSM 40.3 - GSM 125.3 GK 10.2 - GK 40.2

Worm gearboxes Bevel gearboxes

max 5 600 Nm max 16 000 Nm

max 1 200 Nm

Y000.077/003 /1.00