UNEXCAVATED
UNEXCAVATED
UNEXCAVATED
EXISTING TUNNEL
UNEXCAVATED
UNEXCAVATED
UNEXCAVATED
1 1/2" DR UP
EXIST. DRAIN
EXIST. 3/4" DTS & DTR
EXIST EF-3
EXIST E-6"Ø
FLOOR DRAIN.SPILL OVER 1 1/2" DR
EXIST E-8x4
EXIST 1 1/2" DTS & DTR
EXIST. 4" CHWS&R AND 3" HWS&R
THRUST BLOCK
TO ALUMNI HALL
EXIST 4" CHWREXIST 4" CHWS
EXIST 3" HWSEXIST 3" HWR
EXIST UH-1
EXIST 3" DTR UP
EXIST 3" DTS UP
NEW 2" DTR
NEW 2" DTS
EXIST 3" DTR UPEXIST 3" DTS UP
3" DTR4" DTR
4" DTS
EXIST 1 1/2" DR UP
2" DTS UP
2" DTR UP
DTP-3 DTP-4
EXP-2
CONTRACTOR SHALL REMOVE SECTIONS OFEXISTING PIPING IN THIS AREA TO ALLOWACCESS FOR INSTALLATION OF NEW DTR & DTSPIPING. REMOVED PIPING SHALL BEREINSTALLED AND INSULATED TO MATCHEXISTING. ALL SHUT DOWNS SHALL BESCHEDULED WITH THE UNIVERSITY PRIOR TOANY WORK PERFORMED.
EXISTING PUMPS
EXISTING
EXPANSION TANK
REFER TO DETAIL
SHEET M2.0
REVISIONS
ISSUANCES
Motz Engineering
300 West 4th Street, Suite 300
Cincinnati, OH 45202-2666
T: 513.621.5400
F: 513.621.5407
MEP Design Security Sustainable Design
Commissioning Design/Build
DATE DESCRIPTION
SHEET TITLE
SHEET #
DATE
SCALE
DRAWN BY
PROJECT NO.
MEO
XU.2015.02
NO.
DATE DESCRIPTION
05.26.16 FOR OWNER REVIEW
HVAC
IMPROVEMENTS
FOR
SECOND FLOOR
AT
SCHMIDT HALL
Not Published. All Rights Reserved. This Document is the product
and exclusive property of the Engineer. This document and the
information it contains may not be copied or used for other than the
specific purpose for which it was prepared without express written
consent of Motz Consulting Engineers, Inc. doing business as Motz
Engineering.
Because the information stored in electronic formats can be modified
by other parties, intentionally or otherwise, Motz Engineering shall
not be held responsible or liable for any defects and/or deficiencies
that may arise as a consequence of downloading of this information.
Motz Engineering assumes no responsibility with regard to the
transmission or receipt of the information attached.
COPYRIGHT © 2017 MOTZ ENGINEERING
FOR
XAVIER UNIVERSITY
1518 HERALD AVE
CINCINNATI, OHIO
45207
AS SHOWN
03.09.17 FOR BID AND PERMIT
BASEMENT PIPING PLAN
SCALE: 1/8" = 1'-0"
N
MP1.B
MECHANICAL
PIPING
BASEMENT PLAN
GENERAL NOTES:
DRAWING NOTES:
A. UNLESS OTHERWISE NOTED, ALL PIPING SHOWN IS NEW. REMOVE ALL EXISTING PIPING NOT USED IN FINAL ARRANGEMENT.JOB SITE VISIT IS REQUIRED FOR THIS DETERMINATION.
B. PIPING CONTRACTOR SHALL CAREFULLY COORDINATE PIPING LOCATIONS WITH ALL OTHER TRADES BEFORE FABRICATINGPIPING. ALL PIPING SHALL BE INSTALLED AS TIGHT TO THE STRUCTURE AS POSSIBLE. REFER TO THE SPECIFICATIONS FORCOORDINATION.
03/09/2017
03/09/2017
1-11
1-12
1-10
FCU 1-9
1-8
FCU 1-14
1-5
1-2
1-3
FCU 1-1
1" DTS
FCU 1-4
DTR
DTS
DRDTRDTS
DR
DR
C.O.
C.O.
C.O.
C.O.
C.O.
C.O.
C.O.
C.O.
DTR
ACCU-2
C.O.
#1
C C
#4 SR A24
SR
CC
S
S
SS
S
S
S
R
R
R
R
R
R
R
#3
C C
#2 #2
#10
SR
NEW 1" DR UP
NEW WORK IN THIS AREA
NEW WORK IN THIS AREA
SEE ENLARGED PLAN THIS SHEETFOR NEW WORK
EXISTING FCU FED FROMABOVE TO REMAIN.
NEW PIPE TO BE INSTALLEDIN EXISTING CHASE. REFERTO ARCHITECTURAL PLANS.
115
116
103
101
105
106
107114
113
109
112 111
110
117
104
118
120
120A
119
122
122A
121
127
128A 128
127A
125124
123
126
108
114A
109A
S
R
EXIST 2 1/2" DTR DN
EXIST 2 1/2" DTS DNEXIST 2" DTR UP
EXIST 2" DTS UP
NEW 2" DTR DN
NEW 2" DTS DN
NEW 2" BALL VALVE(TYP.)
REVISIONS
ISSUANCES
Motz Engineering
300 West 4th Street, Suite 300
Cincinnati, OH 45202-2666
T: 513.621.5400
F: 513.621.5407
MEP Design Security Sustainable Design
Commissioning Design/Build
DATE DESCRIPTION
SHEET TITLE
SHEET #
DATE
SCALE
DRAWN BY
PROJECT NO.
MEO
XU.2015.02
NO.
DATE DESCRIPTION
05.26.16 FOR OWNER REVIEW
HVAC
IMPROVEMENTS
FOR
SECOND FLOOR
AT
SCHMIDT HALL
Not Published. All Rights Reserved. This Document is the product
and exclusive property of the Engineer. This document and the
information it contains may not be copied or used for other than the
specific purpose for which it was prepared without express written
consent of Motz Consulting Engineers, Inc. doing business as Motz
Engineering.
Because the information stored in electronic formats can be modified
by other parties, intentionally or otherwise, Motz Engineering shall
not be held responsible or liable for any defects and/or deficiencies
that may arise as a consequence of downloading of this information.
Motz Engineering assumes no responsibility with regard to the
transmission or receipt of the information attached.
COPYRIGHT © 2017 MOTZ ENGINEERING
FOR
XAVIER UNIVERSITY
1518 HERALD AVE
CINCINNATI, OHIO
45207
AS SHOWN
03.09.17 FOR BID AND PERMIT
FIRST FLOOR PIPING PLAN
SCALE: 1/8" = 1'-0"
N
MECHANICAL
PIPING
FIRST FLOOR PLAN
MP1.1
GENERAL NOTES:
DRAWING NOTES:
A. UNLESS OTHERWISE NOTED, ALL PIPING SHOWN IS NEW. REMOVE ALL EXISTING PIPING NOT USED IN FINAL ARRANGEMENT.JOB SITE VISIT IS REQUIRED FOR THIS DETERMINATION.
B. PIPING CONTRACTOR SHALL CAREFULLY COORDINATE PIPING LOCATIONS WITH ALL OTHER TRADES BEFORE FABRICATINGPIPING. ALL PIPING SHALL BE INSTALLED AS TIGHT TO THE STRUCTURE AS POSSIBLE. REFER TO THE SPECIFICATIONS FORCOORDINATION.
FIRST FLOOR PIPING ENLARGED PLAN
SCALE: 1/2" = 1'-0"
N
03/09/2017
03/09/2017
2-11
2-10B 2-10A
2-9
2-8
2-2
2-4
3/4" 1"
1 1/4"
1 1/2"
1 1/2"
DTS1 1/2"
DTS
DTR
2"
2 1/2"
1 1/4"
1 1/2"
1 1/2"
2 1/2"
2 1/2"
1"
1 1/4"
2"
1 1/2"
1"1 1/2"
1"
1"
DTS DTR
DTS
DTS
DTR
1 1/2" DTS & R
1 1/2" DRUP & DN.
1"
UP1 1/2" DR
3/4"
2-7
2-11
2-10B 2-10A
2-9
2-8
3" DTR DN2" DTR UP &
2" DTS UP &3" DTS DN
C.O.
C.O.
C.O.
C.O.
DTR
DTS
DTS
DTR
DTS DTR
DTR DTS
DTR
DTS
DR
C.O.
UP & DN.1 1/2" DR
2 1/2"
1"
C.O.
1 1/4"
3/4"
2 1/2"1 1/4"
1"
1"
1 1/2"
1 1/2"
2 1/2"
2"
2-1
3" DIESEL EXH. UP
2-5
3/4"
DN.1 1/2" DR
THRU ROOF
1 1 1
2-6C 2-6B 2-6A
P.O.R.P.O.R.
2
2
2
2
2
2
2
222
NEW WORK IN THIS AREA
NEW WORK IN THIS AREA
206
208
216
207
223
219
222
220
220B
218
221
220C
204A
209
210
214
205
201
202
212
217
204
211
213
213A
205A
203
218A
217A
215
212A
219
REVISIONS
ISSUANCES
Motz Engineering
300 West 4th Street, Suite 300
Cincinnati, OH 45202-2666
T: 513.621.5400
F: 513.621.5407
MEP Design Security Sustainable Design
Commissioning Design/Build
DATE DESCRIPTION
SHEET TITLE
SHEET #
DATE
SCALE
DRAWN BY
PROJECT NO.
MEO
XU.2015.02
NO.
DATE DESCRIPTION
05.26.16 FOR OWNER REVIEW
HVAC
IMPROVEMENTS
FOR
SECOND FLOOR
AT
SCHMIDT HALL
Not Published. All Rights Reserved. This Document is the product
and exclusive property of the Engineer. This document and the
information it contains may not be copied or used for other than the
specific purpose for which it was prepared without express written
consent of Motz Consulting Engineers, Inc. doing business as Motz
Engineering.
Because the information stored in electronic formats can be modified
by other parties, intentionally or otherwise, Motz Engineering shall
not be held responsible or liable for any defects and/or deficiencies
that may arise as a consequence of downloading of this information.
Motz Engineering assumes no responsibility with regard to the
transmission or receipt of the information attached.
COPYRIGHT © 2017 MOTZ ENGINEERING
FOR
XAVIER UNIVERSITY
1518 HERALD AVE
CINCINNATI, OHIO
45207
AS SHOWN
03.09.17 FOR BID AND PERMIT
SECOND FLOOR PIPING DEMO PLAN
SCALE: 1/8" = 1'-0"
N
MPD1.2
MECHANICAL PIPING
SECOND FLOOR DEMO
PLAN
GENERAL NOTES:
DRAWING NOTES:
1. CONTRACTOR TO REMOVE EXISTING BRANCH PIPING TO FCU'S 6A, 6B, AND 6C AND CAP EXISTING SUPPLY, RETURN, AND DRAIN PIPINGAT P.O.R. INDICATED.
2. CONTRACTOR TO REMOVE EXISTING FAN COIL UNITS. REFER TO SHEET MP1.2 FOR DETAILED WORK IN THIS AREA.
A. UNLESS OTHERWISE NOTED, ALL PIPING SHOWN IS NEW. REMOVE ALL EXISTING PIPING NOT USED IN FINAL ARRANGEMENT.JOB SITE VISIT IS REQUIRED FOR THIS DETERMINATION.
B. PIPING CONTRACTOR SHALL CAREFULLY COORDINATE PIPING LOCATIONS WITH ALL OTHER TRADES BEFORE FABRICATINGPIPING. ALL PIPING SHALL BE INSTALLED AS TIGHT TO THE STRUCTURE AS POSSIBLE. REFER TO THE SPECIFICATIONS FORCOORDINATION.
03/09/2017
03/09/2017
2-11
2-10B 2-10A
2-9
2-8
R8L-200
S8L4-280
S8L4-235 R8L-155
R8L-155
2-6C 2-6B 2-6AS8L4-185
S8L4-185R8L-155
S8L4-235
R8L-155V12L
R-14X12
S-14X12
O.A.-6X6 O.A.-10X8
2-4
COIL
DUAL TEMPERATURECOIL FOR ACU-1
2-6C 2-6A2-6B
2-7
2-11
2-10B 2-10A
2-9
2-8
2-1
2-5
2-6B 2-6AP.O.R.
1
NEW WORK IN THIS AREA
P.O.R.
206
208
216
207
223
219
222
220
220B
218
221
220C
204A
209
210
214
205
201
202
212
217
204
211
213
213A
205A
203
218A
217A
215
212A
219
REVISIONS
ISSUANCES
Motz Engineering
300 West 4th Street, Suite 300
Cincinnati, OH 45202-2666
T: 513.621.5400
F: 513.621.5407
MEP Design Security Sustainable Design
Commissioning Design/Build
DATE DESCRIPTION
SHEET TITLE
SHEET #
DATE
SCALE
DRAWN BY
PROJECT NO.
MEO
XU.2015.02
NO.
DATE DESCRIPTION
05.26.16 FOR OWNER REVIEW
HVAC
IMPROVEMENTS
FOR
SECOND FLOOR
AT
SCHMIDT HALL
Not Published. All Rights Reserved. This Document is the product
and exclusive property of the Engineer. This document and the
information it contains may not be copied or used for other than the
specific purpose for which it was prepared without express written
consent of Motz Consulting Engineers, Inc. doing business as Motz
Engineering.
Because the information stored in electronic formats can be modified
by other parties, intentionally or otherwise, Motz Engineering shall
not be held responsible or liable for any defects and/or deficiencies
that may arise as a consequence of downloading of this information.
Motz Engineering assumes no responsibility with regard to the
transmission or receipt of the information attached.
COPYRIGHT © 2017 MOTZ ENGINEERING
FOR
XAVIER UNIVERSITY
1518 HERALD AVE
CINCINNATI, OHIO
45207
AS SHOWN
03.09.17 FOR BID AND PERMIT
SECOND FLOOR SHEET METAL DEMO PLAN
SCALE: 1/8" = 1'-0"
N
MSD1.2
HVAC
SHEET METAL
SECOND FLOOR DEMO
PLAN
GENERAL NOTES:
DRAWING NOTES:
A. VERIFY CONDITIONS IN THE FIELD PRIOR TO BID AND CONSTRUCTION EFFORTS.
B. COORDINATE ALL NEW HVAC WORK WITH WORK BY OTHER TRADES PRIOR TO BEGINNING CONSTRUCTION. NO WORK IS TO BEINSTALLED OR FABRICATED UNTIL AFTER THE PROJECT COORDINATION HAS BEEN APPROVED BY THE OWNER'SREPRESENTATIVE.
C. ALL OVERHEAD DUCTWORK SHALL BE INSTALLED AS TIGHT TO THE STRUCTURE AS POSSIBLE.
D. THE HVAC CONTRACTOR SHALL PROVIDE ALL ADDITIONAL STEEL FRAMING AS REQUIRED TO INSTALL EQUIPMENT ANDDUCTWORK.
E. THE HVAC CONTRACTOR SHALL COORDINATE ALL REQUIRED WALL OPENINGS FOR DUCTWORK WITH THE GENERALCONTRACTOR PRIOR TO CONSTRUCTION OF THE NEW WALLS. ALL ADDITIONAL OPENINGS FOR DUCT PENETRATIONS SHALL BEPROVIDED BY THE HVAC CONTRACTOR IN COMPLIANCE WITH ALL CONDITIONS OF THE PROJECT SPECIFICATIONS.
F. THE HVAC CONTRACTOR SHALL PROVIDE ALL REQUIRED WALL AND FLOOR OPENINGS FOR PIPING. HVAC CONTRACTOR SHALLFIRESTOP ALL RATED OPENINGS. THE HVAC CONTRACTOR SHALL PROVIDE ALL CUTTING AND PATCHING THAT IS REQUIREDFOR PIPING PENETRATIONS THROUGH WALLS AND FLOORS.
1. CONTRACTOR TO REMOVE ALL EXISTING DUCTWORK IN THIS ROOM UP TO P.O.R. INDICATED. CONTRACTOR TO REMOVE ALL FCU'S,DIFFUSERS, AND ASSOCIATED SHEET METAL WORK IN THIS AREA.
03/09/2017
03/09/2017
2-11
2-10B 2-10A
2-9
2-8
2-2
2-4
3/4" 1"
1 1/4"
1 1/2"
1 1/2"
DTS1 1/2"
DTS
DTR
2"
2 1/2"
1 1/4"
1 1/2"
1 1/2"
2 1/2"
2 1/2"
1"
1 1/4"
2"
1 1/2"
1"1 1/2"
1"
1"
DTS DTR
DTS
DTS
DTR
1 1/2" DTS & R
1 1/2" DRUP & DN.
1"
UP1 1/2" DR
3/4"
2-7
2-11
2-10B 2-10A
2-9
2-8
3" DTR DN2" DTR UP &
2" DTS UP &3" DTS DN
C.O.
C.O.
C.O.
C.O.
DTR
DTS
DTS
DTR
DTS DTR
DTR DTS
DTR
DTS
DR
C.O.
UP & DN.1 1/2" DR
2 1/2"
1"
C.O.
1 1/4"
3/4"
2 1/2"1 1/4"
1"
1"
1 1/2"
1 1/2"
2 1/2"
2"
2-1
3" DIESEL EXH. UP
2-5
3/4"
DN.1 1/2" DR
THRU ROOF
2-12A
2-12B 2-12C
2-12D
2-12E
2-12F
2-12G
2-12H
2-12I
2-12J
NEW FAN COIL UNITS
NEW FAN COIL UNITS
NEW FAN COIL UNITS
NEW FAN COIL UNITS
1
1
111
1
1
1
1
1
EXIST 2" DTR DN
EXIST 2" DTS DN
EXIST 1 1/2" DTS
EXIST 1 1/2" DTREXIST 1 1/2" DRAIN
EXIST 1 1/2" DTS
EXIST 1 1/2" DTREXIST 1 1/2" DRAIN
EXIST DTS AND DTR DNTO 1ST FLOOR TO FEEDEXISTING FCU 1-13 TOREMAIN
2 2 2
2
2
2
2
2
2
2
NEW BALL VALVECAPPED (TYP)
2-6
1-1/8" DTS1-1/8" DTR
3/4" DR1" DR DN
NEW WORK IN THIS AREA
NEW WORK IN THIS AREA
NEW DX COIL AC-2-6
3/4" DR
3
206
208
216
207
223
219
222
220
220B
218
221
220C
204A
209
210
214
205
201
202
212
217
204
211
213
213A
205A
203
218A
217A
215
212A
219
REVISIONS
ISSUANCES
Motz Engineering
300 West 4th Street, Suite 300
Cincinnati, OH 45202-2666
T: 513.621.5400
F: 513.621.5407
MEP Design Security Sustainable Design
Commissioning Design/Build
DATE DESCRIPTION
SHEET TITLE
SHEET #
DATE
SCALE
DRAWN BY
PROJECT NO.
MEO
XU.2015.02
NO.
DATE DESCRIPTION
05.26.16 FOR OWNER REVIEW
HVAC
IMPROVEMENTS
FOR
SECOND FLOOR
AT
SCHMIDT HALL
Not Published. All Rights Reserved. This Document is the product
and exclusive property of the Engineer. This document and the
information it contains may not be copied or used for other than the
specific purpose for which it was prepared without express written
consent of Motz Consulting Engineers, Inc. doing business as Motz
Engineering.
Because the information stored in electronic formats can be modified
by other parties, intentionally or otherwise, Motz Engineering shall
not be held responsible or liable for any defects and/or deficiencies
that may arise as a consequence of downloading of this information.
Motz Engineering assumes no responsibility with regard to the
transmission or receipt of the information attached.
COPYRIGHT © 2017 MOTZ ENGINEERING
FOR
XAVIER UNIVERSITY
1518 HERALD AVE
CINCINNATI, OHIO
45207
AS SHOWN
03.09.17 FOR BID AND PERMIT
SECOND FLOOR PIPING PLAN
SCALE: 1/8" = 1'-0"
N
MP1.2
MECHANICAL
PIPING
SECOND FLOOR PLAN
GENERAL NOTES:
DRAWING NOTES:
A. UNLESS OTHERWISE NOTED, ALL PIPING SHOWN IS NEW. REMOVE ALL EXISTING PIPING NOT USED IN FINAL ARRANGEMENT.JOB SITE VISIT IS REQUIRED FOR THIS DETERMINATION.
B. PIPING CONTRACTOR SHALL CAREFULLY COORDINATE PIPING LOCATIONS WITH ALL OTHER TRADES BEFORE FABRICATINGPIPING. ALL PIPING SHALL BE INSTALLED AS TIGHT TO THE STRUCTURE AS POSSIBLE. REFER TO THE SPECIFICATIONS FORCOORDINATION.
1. CONTRACTOR TO CAREFULLY REMOVE EXISTING FAN COIL UNIT LOCATED BEHIND DECORATIVE WOOD CABINETRY. CONTRACTOR SHALLREMOVE PORTION OF CABINETRY TO ALLOW REMOVAL OF EXISTING UNITS AND INSTALLATION OF NEW UNITS. CONTRACTOR SHALLREINSTALL CABINETRY.
2. CONTRACTOR TO EXTEND EXISTING DTS, DTR, AND DRAIN PIPING TO NEW FAN COIL UNITS AND MAKE CONNECTION THERETO.
3. EXISTING VENTILATION IN THIS ROOM TO REMAIN UNCHANGED.
03/09/2017
03/09/2017
2-11
2-10B 2-10A
2-9
2-8
2-6 T
O.A.-10X10
2-4
2-3
2-7
2-11
2-10B 2-10A
2-9
2-8
2-1
2-5
P.O.C.
S10L4-280 R8L-200
V12L4-400
S-10X12 S-20X12
R-10X10 R-20X10P.O.C.
V-12X10
S-12X20 DNBELOW CEILING
R-10X20 DNBELOW CEILING
SEE ENLARGED PLAN THIS SHEETFOR NEW WORK BELOW CEILINGNEW WORK IN THIS AREA
S10L4-280 S10L4-280
S10L4-280S10L4-280
R8L-200
R8L-200R8L-200 R8L-200
1
1
206
208
216
207
223
219
222
220
220B
218
221
220C
204A
209
210
214
205
201
202
212
217
204
211
213
213A
205A
203
218A
217A
215
212A
219
2-6
NEW FCU INSTALLEDBELOW CEILING. NEWFCU TO BE SUPPORTEDON UNISTRUTATTACHED TOSTRUCTURE ABOVEACT CEILING.
S-12X20 UP
R-10X20 UP
NEW DX COIL AC-2-6210
205
204
REVISIONS
ISSUANCES
Motz Engineering
300 West 4th Street, Suite 300
Cincinnati, OH 45202-2666
T: 513.621.5400
F: 513.621.5407
MEP Design Security Sustainable Design
Commissioning Design/Build
DATE DESCRIPTION
SHEET TITLE
SHEET #
DATE
SCALE
DRAWN BY
PROJECT NO.
MEO
XU.2015.02
NO.
DATE DESCRIPTION
05.26.16 FOR OWNER REVIEW
HVAC
IMPROVEMENTS
FOR
SECOND FLOOR
AT
SCHMIDT HALL
Not Published. All Rights Reserved. This Document is the product
and exclusive property of the Engineer. This document and the
information it contains may not be copied or used for other than the
specific purpose for which it was prepared without express written
consent of Motz Consulting Engineers, Inc. doing business as Motz
Engineering.
Because the information stored in electronic formats can be modified
by other parties, intentionally or otherwise, Motz Engineering shall
not be held responsible or liable for any defects and/or deficiencies
that may arise as a consequence of downloading of this information.
Motz Engineering assumes no responsibility with regard to the
transmission or receipt of the information attached.
COPYRIGHT © 2017 MOTZ ENGINEERING
FOR
XAVIER UNIVERSITY
1518 HERALD AVE
CINCINNATI, OHIO
45207
AS SHOWN
03.09.17 FOR BID AND PERMIT
SECOND FLOOR SHEET METAL PLAN
SCALE: 1/8" = 1'-0"
N
MS1.2
HVAC
SHEET METAL
SECOND FLOOR PLAN
SECOND FLOOR SHEET METAL ENLARGED PLAN
SCALE: 1/4" = 1'-0"
N
GENERAL NOTES:
DRAWING NOTES:
A. VERIFY CONDITIONS IN THE FIELD PRIOR TO BID AND CONSTRUCTION EFFORTS.
B. COORDINATE ALL NEW HVAC WORK WITH WORK BY OTHER TRADES PRIOR TO BEGINNING CONSTRUCTION. NO WORK IS TO BEINSTALLED OR FABRICATED UNTIL AFTER THE PROJECT COORDINATION HAS BEEN APPROVED BY THE OWNER'SREPRESENTATIVE.
C. ALL OVERHEAD DUCTWORK SHALL BE INSTALLED AS TIGHT TO THE STRUCTURE AS POSSIBLE.
D. THE HVAC CONTRACTOR SHALL PROVIDE ALL ADDITIONAL STEEL FRAMING AS REQUIRED TO INSTALL EQUIPMENT ANDDUCTWORK.
E. THE HVAC CONTRACTOR SHALL COORDINATE ALL REQUIRED WALL OPENINGS FOR DUCTWORK WITH THE GENERALCONTRACTOR PRIOR TO CONSTRUCTION OF THE NEW WALLS. ALL ADDITIONAL OPENINGS FOR DUCT PENETRATIONS SHALL BEPROVIDED BY THE HVAC CONTRACTOR IN COMPLIANCE WITH ALL CONDITIONS OF THE PROJECT SPECIFICATIONS.
F. THE HVAC CONTRACTOR SHALL PROVIDE ALL REQUIRED WALL AND FLOOR OPENINGS FOR PIPING. HVAC CONTRACTOR SHALLFIRESTOP ALL RATED OPENINGS. THE HVAC CONTRACTOR SHALL PROVIDE ALL CUTTING AND PATCHING THAT IS REQUIREDFOR PIPING PENETRATIONS THROUGH WALLS AND FLOORS.
1. EXISTING VENTILATION IN THIS ROOM TO REMAIN UNCHANGED.
03/09/2017
03/09/2017
EXIST 24X36 CONN. TO O.A. LOUVER
EXH. LOUVEREXIST 24X36 CONN. TO
EXIST S-22X18 DN.
EXIST R-22X18 DN.
MUA-1
EXIST O.A.-24X14 DN.EXIST E-14X24 DN.
ACU-1
EXIST O.A.-24X30
EXIST O.A.-24X30
EXIST O.A.-±14X29
EXIST E-24X30EXIST E-±16X14
EXIST R-±16X28EXIST S-±13X14
EXIST E-±15X16EXIST O.A.-14X20
EXIST O.A.-±12X14
EXIST E-±45X20O.A.-±40X22
EXIST 24X36 CONN. TOEXH. LOUVER
EXIST R-22X18
EXIST E-14X24
EXIST E-20X20
E-24X30
EXIST 24X36 CONN. TO O.A. LOUVER
EXIST ACCU
NEW ACCU-2-6
ROOF BELOW
NEW BBD
NEW 36X24 EXHAUST LOUVERABOVE EXISTING EXH. FAN
E-20X20
SEAL AND MAKE WATERTIGHT.NEW EF-1 REFER TOM2.1 FOR DETAIL
REVISIONS
ISSUANCES
Motz Engineering
300 West 4th Street, Suite 300
Cincinnati, OH 45202-2666
T: 513.621.5400
F: 513.621.5407
MEP Design Security Sustainable Design
Commissioning Design/Build
DATE DESCRIPTION
SHEET TITLE
SHEET #
DATE
SCALE
DRAWN BY
PROJECT NO.
MEO
XU.2015.02
NO.
DATE DESCRIPTION
05.26.16 FOR OWNER REVIEW
HVAC
IMPROVEMENTS
FOR
SECOND FLOOR
AT
SCHMIDT HALL
Not Published. All Rights Reserved. This Document is the product
and exclusive property of the Engineer. This document and the
information it contains may not be copied or used for other than the
specific purpose for which it was prepared without express written
consent of Motz Consulting Engineers, Inc. doing business as Motz
Engineering.
Because the information stored in electronic formats can be modified
by other parties, intentionally or otherwise, Motz Engineering shall
not be held responsible or liable for any defects and/or deficiencies
that may arise as a consequence of downloading of this information.
Motz Engineering assumes no responsibility with regard to the
transmission or receipt of the information attached.
COPYRIGHT © 2017 MOTZ ENGINEERING
FOR
XAVIER UNIVERSITY
1518 HERALD AVE
CINCINNATI, OHIO
45207
AS SHOWN
03.09.17 FOR BID AND PERMIT
ROOF SHEET METAL PLAN
SCALE: 1/8" = 1'-0"
N
MS1.R
HVAC
SHEET METAL
ROOF PLAN
GENERAL NOTES:
DRAWING NOTES:
A. VERIFY CONDITIONS IN THE FIELD PRIOR TO BID AND CONSTRUCTION EFFORTS.
B. COORDINATE ALL NEW HVAC WORK WITH WORK BY OTHER TRADES PRIOR TO BEGINNING CONSTRUCTION. NO WORK IS TO BEINSTALLED OR FABRICATED UNTIL AFTER THE PROJECT COORDINATION HAS BEEN APPROVED BY THE OWNER'SREPRESENTATIVE.
C. ALL OVERHEAD DUCTWORK SHALL BE INSTALLED AS TIGHT TO THE STRUCTURE AS POSSIBLE.
D. THE HVAC CONTRACTOR SHALL PROVIDE ALL ADDITIONAL STEEL FRAMING AS REQUIRED TO INSTALL EQUIPMENT ANDDUCTWORK.
E. THE HVAC CONTRACTOR SHALL COORDINATE ALL REQUIRED WALL OPENINGS FOR DUCTWORK WITH THE GENERALCONTRACTOR PRIOR TO CONSTRUCTION OF THE NEW WALLS. ALL ADDITIONAL OPENINGS FOR DUCT PENETRATIONS SHALL BEPROVIDED BY THE HVAC CONTRACTOR IN COMPLIANCE WITH ALL CONDITIONS OF THE PROJECT SPECIFICATIONS.
F. THE HVAC CONTRACTOR SHALL PROVIDE ALL REQUIRED WALL AND FLOOR OPENINGS FOR PIPING. HVAC CONTRACTOR SHALLFIRESTOP ALL RATED OPENINGS. THE HVAC CONTRACTOR SHALL PROVIDE ALL CUTTING AND PATCHING THAT IS REQUIREDFOR PIPING PENETRATIONS THROUGH WALLS AND FLOORS.
03/09/2017
03/09/2017
NOTE:
PROVIDE REMOTE OPERATOR FOR MANUAL DAMPER WHENDAMPER IS NOT ACCESSIBLE THROUGH FINISHED CEILING.
SCALE: NOT TO SCALE
DETAIL - OUTLET CONNECTION
MAIN DUCT
TAP FROM BOTTOM OF DUCT
BELLMOUTH FITTING
(MAXIMUM 6'-0",FLEX DUCT
MAIN DUCT
MANUAL DAMPER
BELLMOUTH FITTING
TAP FROM SIDE OF DUCT
MANUAL DAMPER
LONG RADIUSSHEET METAL
MINIMUM 1'-0")
(MAXIMUM 6'-0",FLEX DUCT
MINIMUM 1'-0")
ELBOW
CEILING TEEOR FRAMEFOR GYP.CLG.
CEILING TEEOR FRAMEFOR GYP.CLG.
DETAIL - FAN COIL PIPING
NOT TO SCALE
RETURN AIR
CONDENSATE DRAIN, ROUTE TONEAREST APPROVED RECEPTOR, TYP.
SUPPLY DUCT
30 DEGREES MAXIMUM.
FLEXIBLE CONNECTION
SUPPORT UNIT IN ACCORDANCE W/ MFG. RECOMMENDATIONS.
FANCOIL
(TYP.)
DUAL TEMPERATURE WATER PIPING
NOT TO SCALE
FAN COIL UNIT PIPING DIAGRAM
AIR
BALANCING VALVE
NO FLOW
STRAINER WITH
HOSE FITTING CAPPED3/4" BALL DR. VA. W/
HOSE FITTING CAPPED (TYP.)
TRV (2-WAY)
C
AIR VENT
FAN COIL UNIT
DTS MAIN
DTR MAIN
BALL VALVE (TYP.)
NOTES:REFER TO FAN COIL UNITAND VENTILATION SCHEDULE,SHEET M-5.3 FOR TRV ANDLINE SIZES TO COILS.
S-20X10 FCU R-20X10
R-±28X13S-±28X13
FLEX. CONN.
FAN COIL UNIT TYPICAL DUCTWORK CONNECTION DETAILNOT TO SCALE
SET MANUAL DAMPER TODELIVER THE QUANTITYOF O.A. AS INDICATED ONTHE FAN COIL UNIT ANDVENTILATION SCHEDULE,SHEET M-4.0.
O.A. - 10X10
TO FAN COIL UNITS.
2" DTR
2" DTS
2" DTR
2" DTS
4" HIGH CONC. PAD. INITIAL
DUAL TEMPERATURE WATER PUMP #4 (STANDBY)DUAL TEMPERATURE WATER PUMP #3(INSTALLED SIMILAR TO #4)
CHARGE SETTING 20 PSI.
DUAL TEMPERATURE PIPING DIAGRAMNOT TO SCALE
2" BALL VALVE
2" CHECK VA.
VA. W/ HOSE FITTING3/4" BALL DR.
CAPPED (TYP.)
2" STEEL
2" DTS
MANUAL AIR VENTS
EXPANSION LINE
1" BALL VA.
EXPANSION TANK MTD. ON23 GAL.(ACCEPTANCE VOL.)
(SET AT 40 PSI)PRESSURE RELIEF VA.
AUTOMATIC AIR VENT
STEEL
4" AUTO B.F. VALVE
CHECK VA.
B.F. VALVE
4" AUTO B.F. VALVE
B.F. VALVE
3/4" MCW
2 AUTO B.F. VA.
3" CAMPUS HOTWATER RETURN
4" CAMPUS CHILLEDWATER RETURN
3" CAMPUS HOTWATER SUPPLY
SUPPLYCHILLED WATER4" CAMPUS
NOTE:TEMPERATURE SENSOR IN CHILLED WATER RETURN PIPE SHALL CAUSE 2" AUTO B.F. VALVE TO CLOSE IF WATER TEMPERATURE IS HOT.
(FOR MIXING)
TEMPERATURE SENSOR(EMERGENCY SHUT-OFF)
TEMPERATURE SENSOR(HOT WATER MIXING)
TEMPERATURE SENSOR(CHILLED WATER MIXING)
3" AUTO B.F. VALVE
3" AUTO B.F. VALVE
4" DTS&RTO ALUMNI HALL
2" DTS2" DTS
BUTTERFLY VALVE (TYP.)
PRESSURE GAUGE(0-100 PSI) P/T TEST PLUG
STRAINERPUMP
NOT TO SCALE
INLINE HOT WATER PUMP DETAIL
ACC RISE IN DUCTWORK
REFER TO SPECIFIC NOTE 2
FLEXIBLE DUCTWORK
S-SUPPLY
ZONE NUMBER
NECK SIZE-6"; 8"; 10"; 12"; 14"; 15" (ROUND NECK)
FAN COIL UNIT (SEE SCHEDULE SHEET M4.0)
1-ONE WAY; 2-TWO WAY; 3-THREE WAY; 4-FOUR WAY;
L-ACOUSTICAL CEILING; D-DRYWALL CEILING 5-TWO WAY CORNER
RECTANGULAR DUCT TO ROUND DUCT TRANSITION
CEILING SUPPLY OUTLET (24"x24" DIFFUSER)
ELECTRONIC ROOM TEMPERATURE SENSOR WITH ZONE INDICATED
MANUAL VOLUME DAMPER
X INDICATES 12"x12" DIFFUSER; FD INDICATES FIRE DAMPER
SUPPLY, RETURN, EXHAUST, VENT GRILLE
EXHAUST AIR (RECTANGULAR DUCT)
RETURN AIR (RECTANGULAR DUCT)
SUPPLY AIR (ROUND DUCT)
VENTILATION TRANSFER AIR (RECTANGULAR DUCT)
CALIBRATED BALANCING VALVE
2-32
CFM
SG, RG, EG, VG
S10L4-200X
3-1T
V-24X12
R-12X8
SL
E-14X10
SOUNDLINING
S-12Ø
REDUCER
BALL VALVE
BUTTERFLY VALVE
TEMPERATURE REGULATING VALVE
CONNECT NEW DUCTWORK OR PIPING TO EXISTING AT THIS LOCATION
EXISTING DUCTWORK OR PIPING TO BE REMOVED
NEW DUCTWORK OR PIPING
EXISTING DUCTWORK OR PIPING TO REMAIN
CHILLED WATER SUPPLY
CHILLED WATER RETURN
MECHANICAL CITY WATER PIPING
HOT WATER RETURN PIPING
HOT WATER SUPPLY PIPING
MCW
GATE VALVE
HWR
HWS
CHWS
CHWR
LEGEND
OUTDOOR AIR (RECTANGULAR DUCT)OA-24X12
DR DRAIN PIPING
1" CL.3"
12" X 31
2" DEEP DRILLED HOLE. FILL WITHEPOXY & INSERT #3 BENT DOWEL.
EXISTING SLAB
#3 AT 12" C/C E.W.1" CHAMFER #3 DOWEL
CONCRETE PAD31
2"
NOT TO SCALE
TYPICAL HOUSEKEEPING PAD
NOT TO SCALE
FAN COIL UNIT 2-6 CONTROL DIAGRAM
NOT TO SCALE
FAN COIL UNIT 2-12 (ALL) CONTROL DIAGRAM
INDICATED ON FLOOR PLANDUCTWORK OF SIZE AS
LOUVER AND DAMPERACCESS DOOR BETWEENAS INDICATED ON FLOOR PLANDAMPER OF SIZE AND TYPE
LOUVER BY GENERAL CONTR.
ST. STEEL
STAINLESS STEEL
MAKE WATERTIGHT CONNECTIONTO TOP OF WATERSTOP
WATERSTOP
SLOPE BOTTOM OF DUCTTO WATERSTOP
NOT TO SCALE
LOUVER CONNECTION DETAIL
(SEE SPEC)TRANSMITTERPRESSUREDIFFERENTIAL
PRESSURE TRANSMITTER
MAKE 1/4" CONNECTION
DIFFERENTIAL PRESSURE TRANSMITTER
RETURN
TO DIFFERENTIAL
SUPPLY
TYPICAL FOR HOT WATER ANDCHILLED WATER SYSTEMS. SEEFLOOR PLANS FOR LOCATIONS.
PRESSURE TEST
BALL VALVE (TYP.)
STATION (TYP.)
TRANSMITTER LINE COPPER TUBING
EQUALIZER
TRANSMITTER LINE
VALVE
NOT TO SCALE
FLEXIBLE CONNECTION
AIR COOLED CONDENSING UNIT
NOT TO SCALE
ROOF CURB DETAIL
W/ 2" MINIMUM OVERLAP OVERGALVANIZED STEEL COUNTERFLASHING
12" HIGH X 3" WIDE ROOF CURB
ROOF MEMBRANE.
DIMENSIONS BEFORE INSTALLINGVERIFY ALL EQUIPMENT
ROOF MEMBRANE
2X8" DOUBLE BLOCKING
4" FIBER CANT STRIP
ROOF MEMBRANE
FLASHING
ROOFING
DUCT WORK
FLASHING
G.I. LOCK
DUCT INSULATION
GALV. SHEET METAL
SHEET METAL SCREWS.
45°
ROOF DUCT PENETRATION/CURB DETAILNOT TO SCALE
REVISIONS
ISSUANCES
Motz Engineering
300 West 4th Street, Suite 300
Cincinnati, OH 45202-2666
T: 513.621.5400
F: 513.621.5407
MEP Design Security Sustainable Design
Commissioning Design/Build
DATE DESCRIPTION
SHEET TITLE
SHEET #
DATE
SCALE
DRAWN BY
PROJECT NO.
MEO
XU.2015.02
NO.
DATE DESCRIPTION
05.26.16 FOR OWNER REVIEW
HVAC
IMPROVEMENTS
FOR
SECOND FLOOR
AT
SCHMIDT HALL
Not Published. All Rights Reserved. This Document is the product
and exclusive property of the Engineer. This document and the
information it contains may not be copied or used for other than the
specific purpose for which it was prepared without express written
consent of Motz Consulting Engineers, Inc. doing business as Motz
Engineering.
Because the information stored in electronic formats can be modified
by other parties, intentionally or otherwise, Motz Engineering shall
not be held responsible or liable for any defects and/or deficiencies
that may arise as a consequence of downloading of this information.
Motz Engineering assumes no responsibility with regard to the
transmission or receipt of the information attached.
COPYRIGHT © 2017 MOTZ ENGINEERING
FOR
XAVIER UNIVERSITY
1518 HERALD AVE
CINCINNATI, OHIO
45207
AS SHOWN
03.09.17 FOR BID AND PERMIT
M2.0
MECHANICAL
SECTIONS AND
DETAILS
DTS
RETURN
AIR
OUTSIDE
AIR
SUPPLY
AIR
PTTS (TYP)
AO
DTR
TT
AI
M
DO
ROOM
TEMPERATURE
SENSOR
AI
T
ON/OFF
TT-1
T-1
TCV
FAN COIL UNIT TO BE PROVIDED BY MECHANICAL CONTRACTOR WITH DDC
TERMINAL CONTROLLER AND MODULATING CONTROL VALVES
DTS
RETURN
AIR
SUPPLY
AIR
PTTS (TYP)
AO
DTR
TT
AI
M
DO
ROOM
TEMPERATURE
SENSOR
AI
T
ON/OFF
TT-1
T-1
TCV
FAN COIL UNIT TO BE PROVIDED BY MECHANICAL CONTRACTOR WITH DDC
TERMINAL CONTROLLER AND MODULATING CONTROL VALVES
03/09/2017
03/09/2017
FLOOR PIPING PENETRATION DETAILNOT TO SCALE
WALL PIPING PENETRATION DETAILNOT TO SCALE
HANGER DETAILNOT TO SCALE
THROUGH-PENETRATION FIRESTOPSYSTEMSNOT TO SCALE
PATCH AND MAKE WATERTIGHT.CORE DRILL OPENING,CEILING WITHIN BLDG
NOTE:INSTALL PIPING ABOVE
WITHIN UNITREFRIGERANT PIPINGMAKE CONNECTION TO
ROOF
BUILDING ROOF
FCU 2-6
ACCU
PITCH SUCTION LINE@ 1/2" PER 10 FOOT
NOT TO SCALE
REFRIGERANT PIPING DIAGRAM
ROOF CURB
SUCTION SIZED PERMANUFACTURER'SRECOMENDATIONS.
LIQ. SIZED PERMANUFACTURER'SRECOMENDATIONS.
SUCTION SIZED PERMANUFACTURER'SRECOMENDATIONS.
LIQ. SIZED PERMANUFACTURER'SRECOMENDATIONS.
CEILING210
NOT TO SCALE
EXHAUST FAN CONTROL DIAGRAMREVISIONS
ISSUANCES
Motz Engineering
300 West 4th Street, Suite 300
Cincinnati, OH 45202-2666
T: 513.621.5400
F: 513.621.5407
MEP Design Security Sustainable Design
Commissioning Design/Build
DATE DESCRIPTION
SHEET TITLE
SHEET #
DATE
SCALE
DRAWN BY
PROJECT NO.
MEO
XU.2015.02
NO.
DATE DESCRIPTION
05.26.16 FOR OWNER REVIEW
HVAC
IMPROVEMENTS
FOR
SECOND FLOOR
AT
SCHMIDT HALL
Not Published. All Rights Reserved. This Document is the product
and exclusive property of the Engineer. This document and the
information it contains may not be copied or used for other than the
specific purpose for which it was prepared without express written
consent of Motz Consulting Engineers, Inc. doing business as Motz
Engineering.
Because the information stored in electronic formats can be modified
by other parties, intentionally or otherwise, Motz Engineering shall
not be held responsible or liable for any defects and/or deficiencies
that may arise as a consequence of downloading of this information.
Motz Engineering assumes no responsibility with regard to the
transmission or receipt of the information attached.
COPYRIGHT © 2017 MOTZ ENGINEERING
FOR
XAVIER UNIVERSITY
1518 HERALD AVE
CINCINNATI, OHIO
45207
AS SHOWN
03.09.17 FOR BID AND PERMIT
M2.1
MECHANICAL
SECTIONS AND
DETAILS
3
4B
A
4A
A
2
4A
3
2
4B
1
U.L. SYSTEM NO. CAJ1193
1. FLOOR OR WALL ASSEMBLY - MIN. 4-1/2" IN. THICK REINFORCED LIGHTWEIGHT OR NORMAL WEIGHT
(100 - 150 PCF) CONCRETE
FLOOR OR MIN. 5" THICK REINFORCED LIGHTWEIGHT OR NORMAL WEIGHT CONCRETE WALL. WALL
MAY ALSO BE
CONSTRUCTED OF ANY UL CLASSIFIED CONCRETE BLOCKS, MAX. DIAM. OF OPENING IS 10".
2. METALLIC SLEEVE - (OPTIONAL) - NOM. 16" IN DIAM. (OR SMALLER) SCHEDULE 10 (OR HEAVIER) STEEL
SLEEVE CAST OR
GROUTED IN TO FLOOR OR WALL ASSEMBLY FLUSH WITH FLOOR OR WALL SURFACES.
3. THROUGH PENETRANT - ONE METALLIC PIPE, CONDUIT OR TUBING TO BE INSTALLED EITHER
CONCENTRICALLY OR
ECCENTRICALLY WITHIN THE FIRESTOP SYSTEM. THE ANNULAR SPACE BETWEEN PIPES, CONDUITS
OR TUBING AND
PERIPHERY OF OPENING SHALL BE MIN. 1/2" TO MAX. 2-1/4". PIPE, CONDUIT OR TUBING TO BE RIGIDLY
SUPPORTED ON
BOTH SIDES OF FLOOR OR WALL ASSEMBLY. THE FOLLOWING TYPES AND SIZES OF METALLIC PIPES,
CONDUITS OR TUBING
MAY BE USED:
A. STEEL PIPE - NOM. 12" DIAM. (OR SMALLER) SCHEDULE 10 (OR HEAVIER) STEEL PIPE.
B. CONDUIT - NOM. 4" DIAM. (OR SMALLER) STEEL ELECTRICAL METALLIC TUBING OR NOM. 6" DIAM. (OR
SMALLER) STEEL
CONDUIT.
4. FIRESTOP SYSTEM - THE FIRESTOP SYSTEM SHALL CONSIST OF THE FOLLOWING:
A. PACKING MATERIAL - MIN. 4" THICKNESS OF MIN. 4 PCF MINERAL WOOL BATT INSULATION FIRMLY
PACKED INTO OPENING AS A PERMANENT FORM. PACKING MATERIAL TO BE RECESSED FROM TOP
SURFACE OF FLOOR OR FROM BOTH SURFACES OF WALL AS REQUIRED TO ACCOMMODATE THE
REQUIRED THICKNESS OF FILL MATERIAL.
B. FILL, VOID, OR CAVITY MATERIAL - CAULK - MIN. 1/2" THICKNESS OF FILL MATERIAL APPLIED WITHIN
THE ANNULUS FLUSH WITH TOP SURFACE OF FLOOR OR WITH BOTH SURFACES OF WALL
ASSEMBLY.
NELSON FIRESTOP PRODUCTS - CK N/S (NON-SAG) CAULK FOR USE IN FLOORS OR WALL OR CLK S/L
(SOFT-LEVELING) CAULK FOR USE IN WALLS ONLY.
U.L. SYSTEM NO. CAJ1193 F
RATING - 2 HR. T RATING - 0 HR.
SECTION A-A
1 1/2"
1/2" MAXIMUM
INSULATION
FIBERGLASS
SAFING INSULATION
TIGHTLY PACKED
FLOOR
FINISHED
FIRE
SEALANT
INSULATED
PIPE
UNINSULATED
PIPE
BE FLUSH WITH
FINISHED FLOOR
ALL PIPE SLEEVES
THAT FALL WITHIN
PARTITIONS SHALL
4 LOCATIONS/90 DEG. APART
2" WIDE STEEL TABS
WELDED TO SLEEVE
PIPE SLEEVE INSTALLED
IN CONCRETE SLAB.
RETARDENT
CORE DRILL OPENINGS
TO INSTALL SLEEVE.
PROVIDE PATCHING AS REQUIRED.
SEE ARCHITECTURAL DRAWINGS
FINISHED INTERIOR WALL
SAFING INSULATION
TIGHTLY PACKED
SEALANT
1 1/2"
FOR WALL TYPES.
OPENINGS AS REQUIRED.
PROVIDE PATCHING FOR
TO INSTALL SLEEVE AND
RETARDENT
INSULATED
PIPE
FIRE
UNINSULATED
PIPE
PROVIDE PIPE SLEEVE
INSTALLED WITHIN WALL.
CUT WALL OPENINGS
FIBERGLASS
INSULATION
1/2" MAXIMUM
EXCEED THE SCHEDULED
SPACING SHALL NOT
MAXIMUM DISTANCE
NUT WITH FENDER
WASHER
STEEL DECK
THREADED ROD.
DIAMETER AS
SCHEDULED.
CONCRETE
REINFORCED
3-4"
ROOM OCCUPANCY SENSOR,WHERE MULTIPLE EXHAUST FANSSHALL RUN IF ONE ROOM ISOCCUPIED.
DI
OCC
EXHAUST FAN
EAEA FROM MUA-1
DO
DI
ON/OFF
STATUS (VIA CTS)
BACKDRAFT DAMPER
WHERE APPLICABLESEE EXH. FAN SCHEDULE
EF-1
OCC-1
OCCUPANCY SENSOR TO BE PROVIDED BY LIGHTINGCONTRACTOR WITH POINT FOR CONTROLS CONTRACTORINTERFACE. FOR OCCUPANCY TYPE REFER TO ELECTRICALDRAWINGS PER SCHOOL.
03/09/2017
03/09/2017
REVISIONS
ISSUANCES
Motz Engineering
300 West 4th Street, Suite 300
Cincinnati, OH 45202-2666
T: 513.621.5400
F: 513.621.5407
MEP Design Security Sustainable Design
Commissioning Design/Build
DATE DESCRIPTION
SHEET TITLE
SHEET #
DATE
SCALE
DRAWN BY
PROJECT NO.
MEO
XU.2015.02
NO.
DATE DESCRIPTION
05.26.16 FOR OWNER REVIEW
HVAC
IMPROVEMENTS
FOR
SECOND FLOOR
AT
SCHMIDT HALL
Not Published. All Rights Reserved. This Document is the product
and exclusive property of the Engineer. This document and the
information it contains may not be copied or used for other than the
specific purpose for which it was prepared without express written
consent of Motz Consulting Engineers, Inc. doing business as Motz
Engineering.
Because the information stored in electronic formats can be modified
by other parties, intentionally or otherwise, Motz Engineering shall
not be held responsible or liable for any defects and/or deficiencies
that may arise as a consequence of downloading of this information.
Motz Engineering assumes no responsibility with regard to the
transmission or receipt of the information attached.
COPYRIGHT © 2017 MOTZ ENGINEERING
FOR
XAVIER UNIVERSITY
1518 HERALD AVE
CINCINNATI, OHIO
45207
AS SHOWN
03.09.17 FOR BID AND PERMIT
M4.0
MECHANICAL
SCHEDULES
03/09/2017
03/09/2017
UNEXCAVATED
UNEXCAVATED
UNEXCAVATED
EXISTING TUNNEL
UNEXCAVATED
UNEXCAVATED
UNEXCAVATED
EXIST EF-3
EXIST UH-1
LP-B1-10,12,14
LP-B1
LP-B1-10,12,14
VFD VFD
EXIST
DTP-3
1.5HP
208V-3Ø
NEW
DTP-4
1.5HP
208V-3Ø
NEW
1 1
REVISIONS
ISSUANCES
Motz Engineering
300 West 4th Street, Suite 300
Cincinnati, OH 45202-2666
T: 513.621.5400
F: 513.621.5407
MEP Design Security Sustainable Design
Commissioning Design/Build
DATE DESCRIPTION
SHEET TITLE
SHEET #
DATE
SCALE
DRAWN BY
PROJECT NO.
MEO
XU.2015.02
NO.
DATE DESCRIPTION
05.26.16 FOR OWNER REVIEW
HVAC
IMPROVEMENTS
FOR
SECOND FLOOR
AT
SCHMIDT HALL
Not Published. All Rights Reserved. This Document is the product
and exclusive property of the Engineer. This document and the
information it contains may not be copied or used for other than the
specific purpose for which it was prepared without express written
consent of Motz Consulting Engineers, Inc. doing business as Motz
Engineering.
Because the information stored in electronic formats can be modified
by other parties, intentionally or otherwise, Motz Engineering shall
not be held responsible or liable for any defects and/or deficiencies
that may arise as a consequence of downloading of this information.
Motz Engineering assumes no responsibility with regard to the
transmission or receipt of the information attached.
COPYRIGHT © 2017 MOTZ ENGINEERING
FOR
XAVIER UNIVERSITY
1518 HERALD AVE
CINCINNATI, OHIO
45207
AS SHOWN
03.09.17 FOR BID AND PERMIT
BASEMENT POWER PLAN
SCALE: 1/8" = 1'-0"
N
EP1.B
ELECTRIC
POWER
BASEMENT PLAN
DRAWING NOTES:
1. NEW VFD PROVIDED BY MECHANICAL CONTRACTOR INSTALLED BY ELECTRICAL CONTRACTOR.
03/09/2017
03/09/2017
206
208
216
207
223
219
222
220
220B
218
221
220C
204A
209
210
214
205
201
202
212
217
204
211
213
213A
205A
203
218A
217A
215
212A
219
1
1
1
1
1
1
1 1 1
LP-2A
LP-2B
EXISTING
EXISTING 1
REVISIONS
ISSUANCES
Motz Engineering
300 West 4th Street, Suite 300
Cincinnati, OH 45202-2666
T: 513.621.5400
F: 513.621.5407
MEP Design Security Sustainable Design
Commissioning Design/Build
DATE DESCRIPTION
SHEET TITLE
SHEET #
DATE
SCALE
DRAWN BY
PROJECT NO.
MEO
XU.2015.02
NO.
DATE DESCRIPTION
05.26.16 FOR OWNER REVIEW
HVAC
IMPROVEMENTS
FOR
SECOND FLOOR
AT
SCHMIDT HALL
Not Published. All Rights Reserved. This Document is the product
and exclusive property of the Engineer. This document and the
information it contains may not be copied or used for other than the
specific purpose for which it was prepared without express written
consent of Motz Consulting Engineers, Inc. doing business as Motz
Engineering.
Because the information stored in electronic formats can be modified
by other parties, intentionally or otherwise, Motz Engineering shall
not be held responsible or liable for any defects and/or deficiencies
that may arise as a consequence of downloading of this information.
Motz Engineering assumes no responsibility with regard to the
transmission or receipt of the information attached.
COPYRIGHT © 2017 MOTZ ENGINEERING
FOR
XAVIER UNIVERSITY
1518 HERALD AVE
CINCINNATI, OHIO
45207
AS SHOWN
03.09.17 FOR BID AND PERMIT
SECOND FLOOR POWER DEMO PLAN
SCALE: 1/8" = 1'-0"
N
EPD1.2
ELECTRIC
POWER
SECOND FLOOR DEMO
PLAN
DRAWING NOTES:
1. E.C. TO DISCONNECT EXISTING FAN COIL UNITS. FIELD COORDINATE WITH MECHANICAL CONTRACTOR.
03/09/2017
03/09/2017
206
208
216
207
223
219
222
220
220B
218
221
220C
204A
209
210
214
205
201
202
212
217
204
211
213
213A
205A
203
218A
217A
215
212A
219
1
1
1
1
1
1
1 1 1
FCU-2-6
2B-20
LP-2A
LP-2B
2
EXISTING
EXISTING 1
NEW
REVISIONS
ISSUANCES
Motz Engineering
300 West 4th Street, Suite 300
Cincinnati, OH 45202-2666
T: 513.621.5400
F: 513.621.5407
MEP Design Security Sustainable Design
Commissioning Design/Build
DATE DESCRIPTION
SHEET TITLE
SHEET #
DATE
SCALE
DRAWN BY
PROJECT NO.
MEO
XU.2015.02
NO.
DATE DESCRIPTION
05.26.16 FOR OWNER REVIEW
HVAC
IMPROVEMENTS
FOR
SECOND FLOOR
AT
SCHMIDT HALL
Not Published. All Rights Reserved. This Document is the product
and exclusive property of the Engineer. This document and the
information it contains may not be copied or used for other than the
specific purpose for which it was prepared without express written
consent of Motz Consulting Engineers, Inc. doing business as Motz
Engineering.
Because the information stored in electronic formats can be modified
by other parties, intentionally or otherwise, Motz Engineering shall
not be held responsible or liable for any defects and/or deficiencies
that may arise as a consequence of downloading of this information.
Motz Engineering assumes no responsibility with regard to the
transmission or receipt of the information attached.
COPYRIGHT © 2017 MOTZ ENGINEERING
FOR
XAVIER UNIVERSITY
1518 HERALD AVE
CINCINNATI, OHIO
45207
AS SHOWN
03.09.17 FOR BID AND PERMIT
SECOND FLOOR POWER PLAN
SCALE: 1/8" = 1'-0"
N
EP1.2
ELECTRIC
POWER
SECOND FLOOR PLAN
DRAWING NOTES:
1. CONNECT NEW FAN COIL UNIT AND NEW DISCONNECT TO EXISTING CIRCUIT, REWORK CIRCUIT AS REQUIRED. FIELD COORDINATE WITHMECHANICAL CONTRACTOR. NEW DISCONNECT PROVIDED BY MECHANICAL CONTRACTOR INSTALLED BY ELECTRICAL CONTRACTOR.
2. FCU-2-6 LOCATED ABOVE CEILING. NEW DISCONNECT PROVIDED BY MECHANICAL CONTRACTOR INSTALLED BY ELECTRICALCONTRACTOR. COORDINATE INSTALLATION WITH MECHANICAL CONTRACTOR.
03/09/2017
03/09/2017
(3A-37,39,41)
36
(3A-36)
36
EXISTINGCONTROLPANEL
(3A-38,40,42)
EXISTING PHOTO CELL MTD.
4-#8,1"C.
EXISTING CONTROL PANEL
EXISTING MAGNETIC STARTER ANDDISCONNECT SWITCH COMBINATIONS
(3A-8,10,12)
EXISTING EXHAUST FAN
EXISTING T-STAT
ROOF BELOW
NEW ACCU-2-6ON ROOF
LP-2B-21, 23
1
EXISTING NEMA 1 60A., 3P. NON-FUSIBLE DISCONNECT SWITCH
NEW EF-1
ACU-126.0 MCA
208V, 3PH.MUA-1
24.8 MCA208V, 3PH.
EX
EX
EXLP-2B-22, 24
LP-2B-25WP/GFCI
WP
VFD
2
REVISIONS
ISSUANCES
Motz Engineering
300 West 4th Street, Suite 300
Cincinnati, OH 45202-2666
T: 513.621.5400
F: 513.621.5407
MEP Design Security Sustainable Design
Commissioning Design/Build
DATE DESCRIPTION
SHEET TITLE
SHEET #
DATE
SCALE
DRAWN BY
PROJECT NO.
MEO
XU.2015.02
NO.
DATE DESCRIPTION
05.26.16 FOR OWNER REVIEW
HVAC
IMPROVEMENTS
FOR
SECOND FLOOR
AT
SCHMIDT HALL
Not Published. All Rights Reserved. This Document is the product
and exclusive property of the Engineer. This document and the
information it contains may not be copied or used for other than the
specific purpose for which it was prepared without express written
consent of Motz Consulting Engineers, Inc. doing business as Motz
Engineering.
Because the information stored in electronic formats can be modified
by other parties, intentionally or otherwise, Motz Engineering shall
not be held responsible or liable for any defects and/or deficiencies
that may arise as a consequence of downloading of this information.
Motz Engineering assumes no responsibility with regard to the
transmission or receipt of the information attached.
COPYRIGHT © 2017 MOTZ ENGINEERING
FOR
XAVIER UNIVERSITY
1518 HERALD AVE
CINCINNATI, OHIO
45207
AS SHOWN
03.09.17 FOR BID AND PERMIT
ROOF POWER PLAN
SCALE: 1/8" = 1'-0"
N
EP1.R
ELECTRIC
POWER
ROOF PLAN
DRAWING NOTES:
1. NEW WEATHER-PROOF DISCONNECT PROVIDED AND INSTALLED BY ELECTRICAL CONTRACTOR. FIELD COORDINATE LOCATION WITHMECHANICAL CONTRACTOR.
2. NEW VFD PROVIDED BY MECHANICAL CONTRACTOR INSTALLED BY ELECTRICAL CONTRACTOR.
03/09/2017
03/09/2017
REVISIONS
ISSUANCES
Motz Engineering
300 West 4th Street, Suite 300
Cincinnati, OH 45202-2666
T: 513.621.5400
F: 513.621.5407
MEP Design Security Sustainable Design
Commissioning Design/Build
DATE DESCRIPTION
SHEET TITLE
SHEET #
DATE
SCALE
DRAWN BY
PROJECT NO.
MEO
XU.2015.02
NO.
DATE DESCRIPTION
05.26.16 FOR OWNER REVIEW
HVAC
IMPROVEMENTS
FOR
SECOND FLOOR
AT
SCHMIDT HALL
Not Published. All Rights Reserved. This Document is the product
and exclusive property of the Engineer. This document and the
information it contains may not be copied or used for other than the
specific purpose for which it was prepared without express written
consent of Motz Consulting Engineers, Inc. doing business as Motz
Engineering.
Because the information stored in electronic formats can be modified
by other parties, intentionally or otherwise, Motz Engineering shall
not be held responsible or liable for any defects and/or deficiencies
that may arise as a consequence of downloading of this information.
Motz Engineering assumes no responsibility with regard to the
transmission or receipt of the information attached.
COPYRIGHT © 2017 MOTZ ENGINEERING
FOR
XAVIER UNIVERSITY
1518 HERALD AVE
CINCINNATI, OHIO
45207
AS SHOWN
03.09.17 FOR BID AND PERMIT
E3.1
ELECTRIC
SINGLE LINE AND PANEL
SCHEDULES
PANEL: LP-2A 208/120V, 3PH, 4W
LOCATION: SECOND FLOOR MAIN SIZE: 225A
MOUNTING: SURFACE MOUNT MAIN TYPE: MLO
NOTES:
KVA
1 LTS 207, 206 20/1 1.35 A 1.35 20/1 LTS 203-205, 208-210 2
3 LTS 219, 319, 222 20/1 1.35 B 1.30 20/1 LTS 216, 217 4
5 LTS 201 20/1 1.20 C 1.20 20/1 LTS 218 6
7 LTS 221 20/1 1.20 A 1.30 20/1 LTS 211-213 89 LTS 220 20/1 1.20 B 1.20 20 LTS 214 10
11 LTS 220 20/1 1.20 C 1.20 20/1 LTS 214 12
13 LTS 220 20/1 1.20 A 0.00 20/1 SPARE 14
15 LTS 223 20/1 1.20 B 0.00 16
17 LTS 223 20/1 1.20 C 0.00 60/3 SPARE DIMMER PANEL 18
19 LTS 223 20/1 1.20 A 0.00 20
21 RCPTS 206, 217, 216 20/1 0.90 B 0.72 20/1 RCPTS 217, 218 22
23 RCPTS 217, 216, 208 20/1 0.90 C 0.72 20/1 RCPTS 217, 218 24
25 COPIER 218 20/1 1.50 A 0.90 20/1 RCPTS 218, 220, 221 26
27 FRIDGE 218 20/1 1.20 B 0.90 20/1 RCPTS 218, 220, 221 28
29 RCPTS 220, 220C, 221 20/1 0.90 C 0.54 20/1 RCPTS 222 30
31 RCPTS 220, 221 20/1 0.90 A 0.54 20/1 RCPTS 222 32
33 RCPTS 222 20/1 0.90 B 0.54 20/1 RCPTS 216 34
35 FAN COILS 207, 216, 218 20/1 1.20 C 0.90 20/1 RCPTS 220 36
37 FAN COILS 210, 201, 214, 221 20/1 1.20 A 0.50 20/1 BOARDROOM BLINDS 38
39 BOARDROOM BLINDS 20/1 0.50 B 0.50 20/1 BOARDROOM BLINDS 40
41 PHONE RCPT 20/1 0.36 C 0.50 20/1 BOARDROOM BLINDS 42AMPS PER PHASE: 109.5 103.42 100.17
LOAD TYPE CONNECTED KVA DEMAND KVA
LIGHT at 125% 19.9 24.8
RECPT. (100% 1st 10KVA + 50% REMAINING) 33.5 21.7
MOTOR (100% + 25% OF LARGEST) 0.0 0.0
EQUIPMENT NON-CONTINUOUS. (100%) 0.0 0.0
EQUIPMENT CONTINUOUS. (125%) 0.0 0.0
HEAT (100%) 8.5 8.5
KITCHEN 0.0 0.0
TOTAL KVA 61.8 55.0
TOTAL AMPS 171.6 152.8
PANEL: LP-2B 208/120V, 3PH, 4W
LOCATION: SECOND FLOOR MAIN SIZE: 225A
MOUNTING: SURFACE MOUNT MAIN TYPE: MLO
NOTES:
* FURNISH AND INSTALL NEW CIRCUIT BREAKER
KVA
1 FRIDGE 209 20/1 1.00 A 1.00 20/1 MICROWAVE 209 2
3 ICE MAKER 209 20/1 1.00 B 1.00 20/1 DISHWASHER 209 4
5 DISPOSAL 209 20/1 0.80 C 1.08 20/1 RCPTS 201, 203, 206, 209, 210 6
7 RCPTS 212-214 20/1 0.90 A 1.08 20/1 RCPTS 204, 208, 210-212 89 RCPTS 212-214 20/1 0.90 B 0.90 20/1 SCREEN & RCPTS 10
11 RCPTS 209 20/1 0.90 C 1.00 20/1 ICE MAKER 209 12
13 RCPT 209 20/1 0.90 A 1.00 20/1 FRIDGE 209 14
15 RCPT 209 20/1 0.90 B 0.90 20/1 RCPT 209 16
17 RCPT 209 20/1 0.90 C 0.90 20/1 RCPT 209 18
19 RCPT 209 20/1 0.90 A 0.48 20/1 *
(NEW) FCU-2-6 20
21 (NEW) ACCU-2-6 * 30/2
1.88 B 0.92 20/2 *
(NEW) EF-1 22
23 1.88 C 0.92 24
25 ROOFTOP RCPT * 20/1 0.18 A 0.00 SPACE 26
27 SPACE 0.00 B 0.00 SPACE 28
29 SPACE 0.00 C 0.00 SPACE 30
31 SPACE 0.00 A 0.00 SPACE 32
33 SPACE 0.00 B 0.00 SPACE 34
35 SPACE 0.00 C 0.00 SPACE 36
37 SPACE 0.00 A 0.00 SPACE 38
39 SPACE 0.00 B 0.00 SPACE 40
41 SPACE 0.00 C 0.00 SPACE 42AMPS PER PHASE: 62.0 69.98 69.81
LOAD TYPE CONNECTED KVA DEMAND KVA
LIGHT at 125% 0.0 0.0
RECPT. (100% 1st 10KVA + 50% REMAINING) 18.1 14.1
MOTOR (100% + 25% OF LARGEST) 0.0 0.0
EQUIPMENT NON-CONTINUOUS. (100%) 0.0 0.0
EQUIPMENT CONTINUOUS. (125%) 0.0 0.0
HEAT (100%) 6.1 6.1
KITCHEN 0.0 0.0
TOTAL KVA 24.2 20.1
TOTAL AMPS 67.3 56.0
1. LIGHTING LOAD
1.2 LP-1A1.3 LP-1B1.4 LP-2A, LP-2B1.5 LP-3A1.6 ELP-1A1.7 SUBTOTAL LIGHTING LOAD1.8 PLUS 25% OF 44,701 VA1.9 N.E.C. TOTAL LIGHTING LOAD
2. RECEPTACLE LOAD
2.2 LP-1A2.3 LP-1B2.4 LP-2A, LP-2B2.5 LP-3A2.6 ELP-1A2.7 SUBTOTAL NON-DERATED APPLIANCE LOAD2.8 FIRST 10,000 VA AT 100%2.9 REMAINDER AT 50% (78,222VAx0.5)2.10 N.E.C. TOTAL APPLIANCE LOAD
3. AIR CONDITIONING LOAD
3.2 LP-1A3.3 LP-1B3.4 LP-2A, LP-2B3.5 LP-3A3.6 ELP-1A3.7 SUBTOTAL OF AIR CONDITIONING LOAD3.8 PLUS 25% OF LARGEST SINGLE LOAD3.9 N.E.C. TOTAL AIR CONDITIONING LOAD
4. TOTAL N.E.C. LOAD
5. CONVERT TO AMPERES AT 208V., 3 PHASE (166,638VA/360V)
5,849 VA
19,850 VA
7,473 VA
6,009 VA
4,800 VA
-
33,280 VA26,292 VA
16,620 VA
11,550 VA
8,474 VA -
18,738 VA
12,828 VA
-
44,701 VA11,175 VA
88,222 VA 10,000 VA 39,411 VA
59,258 VA 2,093 VA
55,876 VA
49,411 VA
61,351 VA
166,638 VA
462.9 AMPERES
N.E.C. CALCULATION - (DP-1)
1.1 LP-B1 720 VA
2.1 LP-B1 1,080 VA
3.1 LP-B1 19,218 VA
PANEL: LP-B1 208/120V, 3PH, 4W
LOCATION: BASEMENT MAIN SIZE: 225A
MOUNTING: SURFACE MOUNT MAIN TYPE: MLO
NOTES:
* FURNISH AND INSTALL NEW CIRCUIT BREAKER
KVA
1 EXISTING LOAD 15/1 0.36 A 0.00 2
3 EXISTING LOAD 15/1 0.36 B 0.00 100/3 EXISTING LOAD 4
5 SPACE 0.00 C 0.00 6
7 SPACE 0.00 A 0.72 20/1 EXISTING LOAD 8
9 SPACE 0.00 B 1.66 10
11 SPACE 0.00 C 1.66 20/3 *
DTP-3, DTP-4 12
13 SPACE 0.00 A 1.66 14
15 JOHNSON CORTOL FOR USD 20/1 0.18 B 0.00 SPACE 16
17 SPACE 0.00 C 0.00 SPACE 18
19 SPACE 0.00 A 0.00 SPACE 20
21 SPACE 0.00 B 0.00 SPACE 22
23 SPACE 0.00 C 0.00 SPACE 24
25 SPACE 0.00 A 0.00 SPACE 26
27 SPACE 0.00 B 0.00 SPACE 28
29 SPACE 0.00 C 0.00 SPACE 30
31 SPACE 0.00 A 2.50 32
33 SPACE 0.00 B 2.50 60/3 EXISTING LOAD 34
35 TV POWER SUPPLY 20/1 0.18 C 2.50 36
37 SPACE 0.00 A 2.25 38
39 SPACE 0.00 B 2.25 50/3 EXISTING LOAD 40
41 SPACE 0.00 C 2.25 42AMPS PER PHASE: 62.4 57.88 54.88
LOAD TYPE CONNECTED KVA DEMAND KVA
LIGHT at 125% 0.7 0.9
RECPT. (100% 1st 10KVA + 50% REMAINING) 1.1 1.1
MOTOR (100% + 25% OF LARGEST) 0.0 0.0
EQUIPMENT NON-CONTINUOUS. (100%) 0.0 0.0
EQUIPMENT CONTINUOUS. (125%) 0.0 0.0
HEAT (100%) 19.2 19.2
KITCHEN 0.0 0.0
TOTAL KVA 21.0 21.2
TOTAL AMPS 58.4 58.9
N.E.C. CALCULATION - (SWITCHBOARD)
1. HINKLE HALL LOAD
2. EDGECLIFF LOAD
3. SCHMIDT HALL (DP-1) LOAD
381.7 AMPERES
296.4 AMPERES
462.9 AMPERES
4. TOTAL N.E.C. LOAD 1,141 AMPERES
*EC TO COORDINATE FEEDER BREAKER TYPE (THERMAL MAG/M.C.P.), SIZE RATING WITH VFD MANUFACTURER
"B""A"3Ø
PANEL
OTHER INTERLOCKS OR SAFETIES**
CONTROL FROM DDC SYSTEMWIRED IN "AUTO" POSITION**
REFER TO CONTROL DIAGRAMSFOR CONTACT TYPE AND OPERATIONSEQUENCE
**CONTROL RACEWAYS AND WIRING BY CONTROLS CONTRACTOR
PER SPECIFICATIONS, PROVIDE SHIELDED1000V RATED VFD CABLE & SIGNAL CABLEVFD RATED HIGH EFFIC. DESIGN B WITHBEARING GROUNDING RINGS PER SPECIFICATIONS
PROVIDE INDIVIDUAL EUTECTIC THERMAL MOTOR OVERLOADSWHERE MULTIPLE MOTORS ARE CONNECTED TO A SINGLE OUTPUT
VFD RATING 110%AFTER DERATINGFACTORS
VFD
FUSED DISC.SW.
WIRING DIAG - VFD MOTORS
COMPONENTS, RACEWAYS & WIRING BY EC
DTP-3, DTP-4, EF-1
03/09/2017
03/09/2017