NYC Department of Education
Building Condition Assessment Survey 2018-2019
M061Architectural Inspection
Inspection Type Last EditedTime InInspectionId
P.S. 61 - MANHATTAN, 610 EAST 12 STREET, MANHATTAN, NY, 10009School:
1111 2019-01-03 09:16AM 2019-01-22 12:27PMARCHITECTURAL - ASSOCIATE
1194 2019-01-03 09:25AM 2019-06-27 05:19PMARCHITECTURAL - SENIOR
Asset DataQuestion Answer
Was the Building Fully Accessible for Inspection? Yes
Principal(s) Information
Principal Name Bradley Goodman
Principal Organization PS 315- Manhattan
Meeting with Principal? No
Principal Feedback No Feedback from Principal
Principal Name Maria Velez Clare
Principal Organization P.S. 361-Manhattan
Meeting with Principal? Yes
Principal Feedback The principal provided the following comments: 1) The heating
system controls need to be corrected, or replaced. 2) The corridor
radiator needs to be the covered as it is open and can cause a
hazardous condition. 3) Radiator covers in corridors are loose and
need to be properly attached to the walls, 4) Stair wall ceramic
tile is loose and broken and needs to be repaired, 5) Very old
wiring which are no longer in use must be removed, 6) Cafeteria
Student Toilets are deteriorated and need to be renovated.
Principal Name Jeanne Bradley
Principal Organization M094 SPED - Manhattan
Meeting with Principal? No
Principal Feedback No Feedback from Principal
Custodian Alejandro Deno
Fireman Paul Delusme
Building Square Footage 75,000
Comments on the Area (Square Feet) None
Comments on the Stories (Floors) plus Basements 5 + B + PH
Comments on the Year Built 1913
Comments on the Student Population 680
Comments on the Staff Population 175
Comments on the Number of Classrooms 46
Weather Fair
Facade Photo
East 12th Street - South view
Page 1 of 32 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M061Architectural InspectionMain Entrance Photo
Facade A - East 12th Street
Roof Photo
Roof 1 - Northeast view
Have any Systems/Major Building Components been upgraded? Systems: Split mechanical system was added
Years: 2018
Systems: New DOT Concrete Sidewalk along East 12th Street
eliminated Ash Hoist Doors and frames. Sealed Vault.
Years: 2018
Systems: New Boys and Girls Toilets on 3rd Floor
Years: 2017
Systems: Complete Flashing, Coping, Plaza Decking, Windows
and Guards Replacement, Limited Exterior Doors
replacement, Masonry replacement at all Facades
except East 12th Street facade, Parapet replacement,
Chimney reconstruction .
Years: 2014
Systems: Limited Exterior Door replacement
Years: 2011
Systems: Partial Exterior Masonry repairs
Years: 2007
Systems: Complete Roofing and Plaza Decking replacement,
Limited Exterior Masonry and Bulkhead repairs.
Years: 2002
Have there been any New Building Additions? No New Construction
Tandem No Tandem
Leased Space? No
Priority Condition
Page 2 of 32 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M061Architectural InspectionExist
Last Year?
Priority
Category
Condition
Description
Component
Affected
Location
Description
Person(s)
Notified
Person(s)
Title
Photo
Image
Potential Falling
DebrisA severely corroded
section of loose metal
form may fall to the
Basement Floor causing a
hazardous condition.
Floor
Structure
Basement -
Boiler Room
(Shown); also
Storage
Room, and
other
Basement
locations
similar.
Paul
Delusme
No Fireman
Structural Engineer Required
Structural
Condition Type
Condition
Description
Component
Affected
Location
Description
Person(s)
Notified
Person(s)
Title
Photo
Image
Deteriorated Steel Columns / Beams /
Bearing Walls
Columns / Beams /
Bearing Walls
Basement -
Entrance to Vault at
North Wall
Fireman Fireman
Accessibility
Accessibility Status Question Response
Physical Breakdown Structure Exists Complies Required Deficiency
FUNCTIONAL ACCESSIBILITY
Exterior Routes
YesExterior Entrances & Exits
NoNoExterior H/C Lifts
NoNoExterior Ramps and Railings
Interior Routes
NoNoCorridor and Lobby H/C Lifts
NoYesInterior Corridor Doors And Hardware
YesInterior Corridors & Lobbies
YesYesInterior Elevators
YesInterior Lobby Doors And Hardware
NoInterior Ramps
Rooms & Spaces
Art Rooms
Yes YesRooms 305 and 413
Auditorium
Yes No1st Floor
NOT ON ACCESSIBLE ROUTE
Cafeteria
Yes Yes1st Floor
Classrooms
Yes NoNone on Accessible Route
NOT ON ACCESSIBLE ROUTE
NoComputer Rooms
NoGymnasium
Library
Yes YesRoom 408
Main Office
Page 3 of 32 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M061Architectural Inspection
Physical Breakdown Structure Exists Complies Required Deficiency
Yes NoRooms 209, 409 and 509
NOT ON ACCESSIBLE ROUTE
Multi-purpose Room
Yes No1st Floor
NOT ON ACCESSIBLE ROUTE
Nurse's Office
Yes NoRoom 213 and 552
NOT ON ACCESSIBLE ROUTE
NoPool
NoScience Lab
Toilet Rooms (boys)
Yes NoNone on Accessible Route
NOT ON ACCESSIBLE ROUTE
Toilet Rooms (girls)
Yes NoNone on Accessible Route
NOT ON ACCESSIBLE ROUTE
Toilet Rooms (staff)
Yes NoNone on Accessible Route
NOT ON ACCESSIBLE ROUTE
Building Template
Inspection
Question Response
Architectural
ATHLETIC FIELDS Does not exist
EXTERIOR Inspected
InspectedAREAWAY
Instance on AW1-AW3 Inspected
3- FairInstance Condition
Instance Quantity 3
Instance Quantity Uom EACH
AREAWAY DRAINS:CLOGGEDDeficiency
Page 4 of 32 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M061Architectural Inspection
Question Response
EXTERIOR
AREAWAY
Deficiency Location/Instance
1Deficiency Quantity
Quantity Uom EACH
Potential Action MAINTENANCE
PRIORITY 5Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Plaza Deck East
Violations No violations recorded
Does not existAWNINGS AND CANOPIES
InspectedCHIMNEY
MasonryMaterial Type(s)
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedCOPING
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedCORNICE
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedDOORS
InspectedDOOR HARDWARE
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedDOORS AND FRAMES
Condition 4- Between Fair and Poor
METAL:DETERIORATED DOOR AND FRAME - MINOR
DETERIORATION
Deficiency
Deficiency Location/Instance
3Deficiency Quantity
Quantity Uom EACH
Potential Action MAINTENANCE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Page 5 of 32 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M061Architectural Inspection
Question Response
EXTERIOR
DOORS
DOORS AND FRAMES
Deficiency Photo 1
Front Entrance
Violations No violations recorded
InspectedLINTELS
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedTRANSOM/SIDE LIGHT
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
Does not existEXTERIOR SOFFITS
InspectedEXTERIOR WALLS
MasonryMaterial Type(s)
40,000Replacement Quantity
Replacement Uom S.F.
Instance on All Facades Inspected
3- FairInstance Condition
Instance Quantity 40,000
Instance Quantity Uom S.F.
BRICK:EFFLORESCENCEDeficiency
Roof Plan Reference
Elevation
Elevation Reference Elevation B
600Deficiency Quantity
Quantity Uom S.F.
Potential Action MAINTENANCE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Page 6 of 32 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M061Architectural Inspection
Question Response
EXTERIOR
EXTERIOR WALLS
Deficiency Photo 1
Elevation B
Violations No violations recorded
BRICK:CRACKS/DISPLACED/SPALLED BRICK AT
BUILDING CORNERS
Deficiency
Roof Plan Reference
Elevation
Elevation Reference Elevation C
40Deficiency Quantity
Quantity Uom S.F.
Potential Action REMOVE AND REBUILD
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Long Elevation C
Violations No violations recorded
Does not existLOADING DOCK
InspectedLOUVER
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedPARAPETS
MasonryMaterial Type(s)
3,000Replacement Quantity
Replacement Uom C.F.
Instance on All Facades Inspected
2- Between Good and FairInstance Condition
Instance Quantity 3,000
Instance Quantity Uom CF
Page 7 of 32 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M061Architectural Inspection
Question Response
EXTERIOR
PARAPETS
No deficiencies recordedDeficiency
InspectedPLAZA DECK
Instance on Pavers:Roof 2 and 3 Inspected
3- FairInstance Condition
Instance Quantity 4,000
Instance Quantity Uom S.F.
Installation Year 2014
Source of Installation Year Documented
PAVERS:MINOR LEAKAGEDeficiency
Deficiency Location/Instance
40Deficiency Quantity
Quantity Uom S.F.
Potential Action REPAIR
PRIORITY 5Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Work underway to make corrections on Roof 3
Violations No violations recorded
PAVERS:PAVERS IN POOR CONDITIONDeficiency
Deficiency Location/Instance
500Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Plaza Deck East (Roof 3)
Violations No violations recorded
Page 8 of 32 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M061Architectural Inspection
Question Response
EXTERIOR
InspectedROOF
InspectedROOFING
Replacement Quantity 10,000
Replacement Uom S.F.
InspectedLEADERS, GUTTERS, DOWNSPOUTS, SCUPPERS
2- Between Good and FairCondition
No deficiencies recordedDeficiency
InspectedROOF BARRIER
2- Between Good and FairCondition
No deficiencies recordedDeficiency
Does not existROOF CAGE
InspectedROOF FENCE
2- Between Good and FairCondition
No deficiencies recordedDeficiency
InspectedROOF HATCH/SMOKE HATCH
2- Between Good and FairCondition
No deficiencies recordedDeficiency
InspectedROOFING
Instance on Built-Up:Roof 1 Inspected
2- Between Good and FairInstance Condition
Instance Quantity 10,000
Instance Quantity Uom S.F.
“Does the roof have major mechanical equipment sitting on Dunnage
Steel less than 18" above the Roofing?"
No
Installation Year 2014
Source of Installation Year Documented
BUILT-UP:ROOFING:MINOR LEAKAGEDeficiency
Deficiency Location/Instance
30Deficiency Quantity
Quantity Uom S.F.
Potential Action REPAIR
PRIORITY 5Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Room 207
Violations No violations recorded
InspectedROOFING DRAINS
2- Between Good and FairCondition
No deficiencies recordedDeficiency
InspectedSPECIALTIES
InspectedBULKHEAD/PENTHOUSE
Page 9 of 32 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M061Architectural Inspection
Question Response
EXTERIOR
ROOF
SPECIALTIES
BULKHEAD/PENTHOUSE
4- Between Fair and PoorCondition
BULKHEAD/PENTHOUSE WALLS/INTERIOR:GYPSUM
BOARD DAMAGED/DETERIORATED
Deficiency
Deficiency Location/Instance
35Deficiency Quantity
Quantity Uom S.F.
Potential Action MAINTENANCE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Inside Bulkhead
Violations No violations recorded
BULKHEAD/PENTHOUSE WALLS/EXTERIOR:DAMAGED
METAL SIDING
Deficiency
Deficiency Location/Instance
50Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Bulkhead 1
Violations No violations recorded
Does not existCUPOLA/ SPIRES/ TOWERS
Does not existDORMER
Does not existDUNNAGE STEEL
Page 10 of 32 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M061Architectural Inspection
Question Response
EXTERIOR
ROOF
SPECIALTIES
InspectedROOF/GRAVITY TANK
3- FairCondition
STEEL STRUCTURE:NOT IN USE - MAJOR
DETERIORATION
Deficiency
Deficiency Location/Instance
1Deficiency Quantity
Quantity Uom EACH
Potential Action REMOVE
PRIORITY 1Urgency of Action
LEVEL 1Purpose of Action
Violations No violations recorded
InspectedSKYLIGHT/ROOF VENT
Material Type(s) Glass
3- FairCondition
BROKEN GLASSDeficiency
Deficiency Location/Instance
10Deficiency Quantity
Quantity Uom S.F.
Potential Action MAINTENANCE
PRIORITY 5Urgency of Action
LEVEL 2Purpose of Action
Violations No violations recorded
InspectedSTAIRS/RAMPS: EXTERIOR
InspectedBUILDING CHEEK/FLANK WALLS
Condition 3- Fair
CAST IN PLACE CONCRETE:CRACKS/SPALLING - MINORDeficiency
Deficiency Location/Instance
18Deficiency Quantity
Quantity Uom S.F.
Potential Action REPAIR
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Page 11 of 32 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M061Architectural Inspection
Question Response
EXTERIOR
STAIRS/RAMPS: EXTERIOR
BUILDING CHEEK/FLANK WALLS
Deficiency Photo 1
Main Front Entrance
Violations No violations recorded
InspectedRAILINGS
Condition 4- Between Fair and Poor
DAMAGEDDeficiency
Deficiency Location/Instance
12Deficiency Quantity
Quantity Uom L.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Railing at Ramp
Violations No violations recorded
MISSING RAILINGDeficiency
Deficiency Location/Instance
10Deficiency Quantity
Quantity Uom L.F.
Potential Action REPLACE
PRIORITY 5Urgency of Action
LEVEL 6Purpose of Action
Page 12 of 32 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M061Architectural Inspection
Question Response
EXTERIOR
STAIRS/RAMPS: EXTERIOR
RAILINGS
Deficiency Photo 1
Facade A - Main Entrance Steps
Violations 35321669R
InspectedSTAIRS/RAMPS
Condition 4- Between Fair and Poor
CONCRETE:WORN-OUT TREAD/RISER/NOSINGDeficiency
Deficiency Location/Instance
30Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Building Front
Violations No violations recorded
InspectedWINDOWS
12,000Replacement Quantity
Replacement Uom S.F.
InspectedEXTERIOR GUARDS
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedLINTELS
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedWINDOWS
Material Type(s) Aluminum
Instance on Aluminum - Double Hung:All Facades Inspected
2- Between Good and FairInstance Condition
Instance Quantity 12,000
Instance Quantity Uom S.F.
Installation Year 2014
Source of Installation Year Documented
Page 13 of 32 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M061Architectural Inspection
Question Response
EXTERIOR
WINDOWS
WINDOWS
No deficiencies recordedDeficiency
INTERIOR Inspected
AUDITORIUM
Instance on 1st Floor Inspected
Ceiling
Instance on 1st Floor Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Door(s)
Instance on 1st Floor Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Fixed H/C Lift
Instance on 1st Floor Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Fixed Seating
Instance on 1st Floor Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Floor Finish
Instance on 1st Floor Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Sliding-folding Partition
Instance on 1st Floor Does not exist
Stage
Instance on 1st Floor Inspected
Stage
Instance on 1st Floor Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Stage Curtain Rigging
Instance on 1st Floor Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Stage Curtains
Instance on 1st Floor Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Walls
Instance on 1st Floor Inspected
2- Between Good and FairInstance Condition
PLASTER:CRACKS/SPALLINGDeficiency
Near Vestibule, Near Stage, at South of RoomDeficiency Location/Instance
20Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Page 14 of 32 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M061Architectural Inspection
Question Response
INTERIOR
AUDITORIUM
Walls
Deficiency Photo 1
Near Vestibule
Violations No violations recorded
MASONRY:CRACKS/SPALLING - ACTIVE LEAKDeficiency
Exit Vestibule near Stage AreaDeficiency Location/Instance
20Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 5Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Exit Vestibule near Stage Area
Violations No violations recorded
Window Curtains/Shades/Blinds
Instance on 1st Floor Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
CAFETERIA
Instance on 1st Floor Inspected
Ceiling
Instance on 1st Floor Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Door(s)
Instance on 1st Floor Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Fixed Equipment
Instance on 1st Floor Does not exist
Floor Finish
Instance on 1st Floor Inspected
2- Between Good and FairInstance Condition
VINYL TILES:BROKEN/DETERIORATED/MISSING TILESDeficiency
CenterDeficiency Location/Instance
10Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
Page 15 of 32 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M061Architectural Inspection
Question Response
INTERIOR
CAFETERIA
Floor Finish
LEVEL 2Purpose of Action
Deficiency Photo 1
Center
Violations No violations recorded
Sliding-folding Partition
Instance on 1st Floor Does not exist
Stage
Instance on 1st Floor Does not exist
Walls
Instance on 1st Floor Inspected
2- Between Good and FairInstance Condition
PLASTER:CRACKS/SPALLINGDeficiency
Exit to SchoolyardDeficiency Location/Instance
10Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Exit to Schoolyard
Violations No violations recorded
Window Curtains/Shades/Blinds
Instance on 1st Floor Does not exist
InspectedCLASSROOMS/CORRIDORS/ADMIN SPACES
InspectedCeiling
Condition 2- Between Good and Fair
PLASTER:CRACKS/SPALLINGDeficiency
Vestibule Near AuditoriumDeficiency Location/Instance
20Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Page 16 of 32 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M061Architectural Inspection
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Ceiling
Deficiency Photo 1
Vestibule Near Auditorium
Violations No violations recorded
InspectedDoor(s)
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedFloor Finish
Condition 2- Between Good and Fair
VINYL TILES:BROKEN/DETERIORATED/MISSING TILESDeficiency
Rooms 205, 207, 209, At Corridor near Stair A/2, CB/5, G/2, 5,
Near Rooms 412, 501, 506B, and 557
Deficiency Location/Instance
400Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
At Corridor near Stair CB/5
Violations No violations recorded
Does not existSpecialties
InspectedWalls
Condition 2- Between Good and Fair
PLASTER:CRACKS/SPALLINGDeficiency
Room 212Deficiency Location/Instance
10Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Room 212
Violations No violations recorded
Page 17 of 32 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M061Architectural Inspection
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Walls
PLASTER:CRACKS/SPALLING - ACTIVE LEAKDeficiency
Room 207, At Corridor near Room 207Deficiency Location/Instance
20Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 5Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Room 207
Deficiency Photo 2
At Corridor near Room 207
Violations No violations recorded
Does not existGYMNASIUM
InspectedINTERIOR DOOR HARDWARE
Condition 3- Fair
No deficiencies recordedDeficiency
InspectedINTERIOR GUARDS
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
KITCHEN
Instance on 1st Floor Inspected
Ceiling
Instance on 1st Floor Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Door(s)
Instance on 1st Floor Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Floor Finish
Instance on 1st Floor Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Walls
Instance on 1st Floor Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
LIBRARY
Page 18 of 32 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M061Architectural Inspection
Question Response
INTERIOR
LIBRARY
Instance on Room 408 Inspected
Built-in Furnishing
Instance on Room 408 Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Ceiling
Instance on Room 408 Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Door(s)
Instance on Room 408 Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Floor Finish
Instance on Room 408 Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Walls
Instance on Room 408 Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Does not existLOCKER ROOM
MULTI-PURPOSE ROOM
Instance on 1st Floor Inspected
Ceiling
Instance on 1st Floor Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Door(s)
Instance on 1st Floor Not required
Fixed Equipment
Instance on 1st Floor Does not exist
Floor Finish
Instance on 1st Floor Inspected
2- Between Good and FairInstance Condition
VINYL TILES:BROKEN/DETERIORATED/MISSING TILESDeficiency
Near custodian’s officeDeficiency Location/Instance
20Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Near custodian’s office
Violations No violations recorded
Page 19 of 32 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M061Architectural Inspection
Question Response
INTERIOR
MULTI-PURPOSE ROOM
Sliding-folding Partition
Instance on 1st Floor Does not exist
Stage
Instance on 1st Floor Does not exist
Walls
Instance on 1st Floor Inspected
2- Between Good and FairInstance Condition
PLASTER:CRACKS/SPALLINGDeficiency
Near Custodian’s OfficeDeficiency Location/Instance
20Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Near Custodian’s Office
Violations No violations recorded
Window Curtains/Shades/Blinds
Instance on 1st Floor Does not exist
Does not existPOOLS
Does not existSCIENCE DEMO ROOM
Does not existSCIENCE LAB
Does not existSCIENCE PREP ROOM
Does not existSHOWER ROOM
InspectedSTAIRS/RAMPS: INTERIOR
Do Letter Stair Signs Exist? 1
InspectedCeiling
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedDoor(s)
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedPartition
Condition 2- Between Good and Fair
GLASS PANEL:DAMAGED/DETERIORATEDDeficiency
Stairs BC/2, 4, F/1, and 3Deficiency Location/Instance
40Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Page 20 of 32 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M061Architectural Inspection
Question Response
INTERIOR
STAIRS/RAMPS: INTERIOR
Partition
Deficiency Photo 1
Stair F/1
Violations No violations recorded
InspectedRailings
Condition 5- Poor
METAL:MISSINGDeficiency
Stair D/2, and 3Deficiency Location/Instance
30Deficiency Quantity
Quantity Uom L.F.
Potential Action REPLACE
PRIORITY 5Urgency of Action
LEVEL 6Purpose of Action
Deficiency Photo 1
Stair D/3
Violations No violations recorded
METAL:BROKEN BRACKETDeficiency
Stair G/4Deficiency Location/Instance
1Deficiency Quantity
Quantity Uom EACH
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Stair G/4
Violations No violations recorded
InspectedStairs and Landings
Condition 3- Fair
STONE:BROKEN/MISSINGDeficiency
Main Entrance Vestibule, Vestibule to CafeteriaDeficiency Location/Instance
20Deficiency Quantity
Quantity Uom S.F.
Page 21 of 32 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M061Architectural Inspection
Question Response
INTERIOR
STAIRS/RAMPS: INTERIOR
Stairs and Landings
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Main Entrance Vestibule
Violations No violations recorded
ROLLED ASPHALT:CRACKSDeficiency
Stairs B/Bulkhead, D/Bulkhead, E/Bulkhead, F/1Deficiency Location/Instance
200Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Stair F/1
Deficiency Photo 2
Stair E/Bulkhead
Violations No violations recorded
InspectedWalls
Condition 2- Between Good and Fair
CERAMIC TILE:BROKEN/ MISSINGDeficiency
Stair C/1, G/2, 5, F/1, 2 and other locationsDeficiency Location/Instance
50Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Page 22 of 32 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M061Architectural Inspection
Question Response
INTERIOR
STAIRS/RAMPS: INTERIOR
Walls
Deficiency Photo 1
Stair F/1
Violations No violations recorded
InspectedSTRUCTURAL
InspectedCOLUMNS/BEAMS/BEARING WALLS
Condition 4- Between Fair and Poor
MASONRY BEARING WALL:OPEN JOINTSDeficiency
Boiler RoomDeficiency Location/Instance
200Deficiency Quantity
Quantity Uom S.F.
Potential Action REPOINT
PRIORITY 3Urgency of Action
LEVEL 5Purpose of Action
Deficiency Photo 1
Storage Room
Deficiency Photo 2
Wall near Storage Area
Violations No violations recorded
STEEL COLUMNS/BEAMS:DETERIORATED CONCRETE
FIREPROOFING
Deficiency
Throughout BasementDeficiency Location/Instance
30Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 4Urgency of Action
LEVEL 5Purpose of Action
Page 23 of 32 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M061Architectural Inspection
Question Response
INTERIOR
STRUCTURAL
COLUMNS/BEAMS/BEARING WALLS
Deficiency Photo 1
Boiler Room Area
Violations No violations recorded
STEEL COLUMNS/BEAMS:MAJOR RUSTINGDeficiency
BasementDeficiency Location/Instance
10Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 5Urgency of Action
LEVEL 5Purpose of Action
Deficiency Photo 1
Entrance to Vault - North Wall
Violations No violations recorded
InspectedFLOOR STRUCTURE
Condition 4- Between Fair and Poor
CONCRETE SLAB ON GRADE:MINOR CRACKSDeficiency
Throughout Boiler Room and Adjacent SpacesDeficiency Location/Instance
150Deficiency Quantity
Quantity Uom S.F.
Potential Action REPAIR
PRIORITY 3Urgency of Action
LEVEL 5Purpose of Action
Deficiency Photo 1
Boiler Room
Violations No violations recorded
CINDER CONCRETE ARCH:METAL PAN DETERIORATED,
SPALLED
Deficiency
BasementDeficiency Location/Instance
300Deficiency Quantity
Quantity Uom S.F.
Potential Action REPAIR
PRIORITY 5Urgency of Action
Page 24 of 32 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M061Architectural Inspection
Question Response
INTERIOR
STRUCTURAL
FLOOR STRUCTURE
LEVEL 6Purpose of Action
Deficiency Photo 1
Boiler Room
Violations No violations recorded
InspectedFOUNDATION WALLS
Material Type(s) Masonry
Condition 4- Between Fair and Poor
BRICK:CRACKED/SPALLEDDeficiency
BasementDeficiency Location/Instance
250Deficiency Quantity
Quantity Uom S.F.
Potential Action RESTITCH
PRIORITY 3Urgency of Action
LEVEL 5Purpose of Action
Deficiency Photo 1
Boiler Room
Violations No violations recorded
BRICK:WATER INFILTRATION IN ELECTRICAL PANEL
ROOM
Deficiency
BasementDeficiency Location/Instance
100Deficiency Quantity
Quantity Uom S.F.
Potential Action INSTALL WATERPROOFING
PRIORITY 5Urgency of Action
LEVEL 6Purpose of Action
Deficiency Photo 1
Electric Meter Room
Violations No violations recorded
InspectedROOF STRUCTURE
Condition 4- Between Fair and Poor
METAL DECK AND CONCRETE:DETERIORATEDDeficiency
Page 25 of 32 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M061Architectural Inspection
Question Response
INTERIOR
STRUCTURAL
ROOF STRUCTURE
Boiler Room and Adjacent AreaDeficiency Location/Instance
200Deficiency Quantity
Quantity Uom S.F.
Potential Action REPAIR
PRIORITY 4Urgency of Action
LEVEL 5Purpose of Action
Deficiency Photo 1
Boiler a Room Area
Violations No violations recorded
InspectedVAULTS-BUNKERS
InspectedFoundation Walls
4- Between Fair and PoorCondition
OPEN JOINTSDeficiency
Space Off the Boiler RoomDeficiency Location/Instance
60Deficiency Quantity
Quantity Uom S.F.
Potential Action REPOINT
PRIORITY 3Urgency of Action
LEVEL 5Purpose of Action
Deficiency Photo 1
Alcove off the the Boiler Room
Violations No violations recorded
InspectedSlab Structure
4- Between Fair and PoorCondition
CONCRETE SLAB ON GRADE:THRU CRACKSDeficiency
Vault RoomDeficiency Location/Instance
20Deficiency Quantity
Quantity Uom S.F.
Potential Action REPAIR
PRIORITY 4Urgency of Action
LEVEL 5Purpose of Action
Deficiency Photo 1
Page 26 of 32 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M061Architectural Inspection
Question Response
INTERIOR
STRUCTURAL
VAULTS-BUNKERS
Slab Structure
Vault Slab
Violations No violations recorded
CONCRETE SLAB ON GRADE:WATER INFILTRATION IN
NON- INSTRUCTIONAL SPACE
Deficiency
BasementDeficiency Location/Instance
30Deficiency Quantity
Quantity Uom S.F.
Potential Action INSTALL WATERPROOFING
PRIORITY 5Urgency of Action
LEVEL 5Purpose of Action
Deficiency Photo 1
Vault Slab - North Wall
Violations No violations recorded
InspectedVault/Ash Hoist Doors and Framing
3- FairCondition
MINOR RUSTINGDeficiency
East 12th StreetDeficiency Location/Instance
2Deficiency Quantity
Quantity Uom EACH
Potential Action REPAIR
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Violations No violations recorded
InspectedTOILET ROOMS - STAFF
InspectedCeiling
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedDoor(s)
Condition 3- Fair
WOOD:DAMAGED LOUVERDeficiency
Near Room 412Deficiency Location/Instance
1Deficiency Quantity
Quantity Uom EACH
Potential Action MAINTENANCE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Page 27 of 32 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M061Architectural Inspection
Question Response
INTERIOR
TOILET ROOMS - STAFF
Door(s)
Near Room 412
Violations No violations recorded
InspectedFloor Finish
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
Does not existStalls
InspectedWalls
Condition 2- Between Good and Fair
CERAMIC TILE:BROKEN/ MISSINGDeficiency
Near Room 212Deficiency Location/Instance
10Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Near Room 212
Violations No violations recorded
PLASTER:CRACKS/SPALLINGDeficiency
Near Room 212Deficiency Location/Instance
10Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Near Room 212
Violations No violations recorded
InspectedTOILET ROOMS - STUDENTS
InspectedCeiling
Condition 2- Between Good and Fair
PLASTER:CRACKS/SPALLINGDeficiency
Near Stair G/3Deficiency Location/Instance
15Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Page 28 of 32 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M061Architectural Inspection
Question Response
INTERIOR
TOILET ROOMS - STUDENTS
Ceiling
Deficiency Photo 1
Near Stair G/3
Violations No violations recorded
InspectedDoor(s)
Condition 3- Fair
WOOD:DAMAGED LOUVERDeficiency
Near Room 207Deficiency Location/Instance
1Deficiency Quantity
Quantity Uom EACH
Potential Action MAINTENANCE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Near Room 207
Violations No violations recorded
InspectedFloor Finish
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedStalls
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedWalls
Condition 2- Between Good and Fair
PLASTER:CRACKS/SPALLINGDeficiency
3rd Floor - Boys Toilet RoomsDeficiency Location/Instance
10Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Page 29 of 32 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M061Architectural Inspection
Question Response
INTERIOR
TOILET ROOMS - STUDENTS
Walls
3rd Floor - Boys Toilet Rooms
Violations No violations recorded
CERAMIC TILE:BROKEN/ MISSINGDeficiency
5th Floor - Girls Toilet Rooms, 5th Floor -Boys Toilet RoomsDeficiency Location/Instance
10Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
5th Floor - Girls Toilet Rooms
Violations No violations recorded
LIFE SAFETY Inspected
Does not existF.D. HOLDING AREA
Does not existSTEEL STAIRS
SITE Inspected
Does not existCONTAINERIZATION
InspectedDRAINAGE SYSTEM FOR ASPHALT
InspectedCatch Basins/Manhole - Surrounded by Asphalt
Condition 1- Good
No deficiencies recordedDeficiency
Does not existCulverts - Asphalt Covering
Does not existDRAINAGE SYSTEM FOR CONCRETE
Does not existDRAINAGE SYSTEM FOR SOIL
InspectedDRINKING FOUNTAINS
Condition 1- Good
No deficiencies recordedDeficiency
InspectedFENCES
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
Does not existIRRIGATION SYSTEM
InspectedPAVING
InspectedDOT Sidewalk
Does not existAsphalt
InspectedConcrete
1- GoodCondition
No deficiencies recordedDeficiency
Does not existPavers
InspectedSite Sidewalks & Walkways
InspectedAsphalt
2- Between Good and FairCondition
No deficiencies recordedDeficiency
Does not existConcrete
Does not existPavers
Page 30 of 32 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M061Architectural Inspection
Question Response
SITE
PAVING
InspectedStudent Non-Use
Gravel Exists? No
InspectedAsphalt
3- FairCondition
CRACKS - MINORDeficiency
West of schoolDeficiency Location/Instance
200Deficiency Quantity
Quantity Uom S.F.
Potential Action MAINTENANCE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
West of school
Violations No violations recorded
InspectedConcrete
2- Between Good and FairCondition
No deficiencies recordedDeficiency
Does not existPavers
InspectedStudent Use
Gravel Exists? No
InspectedAsphalt
1- GoodCondition
No deficiencies recordedDeficiency
InspectedConcrete
1- GoodCondition
No deficiencies recordedDeficiency
InspectedPavers
1- GoodCondition
No deficiencies recordedDeficiency
InspectedPLAYGROUNDS
SchoolyardInstance
Benches
Instance on Schoolyard Does not exist
Fence
Instance on Schoolyard Does not exist
Pavement
Instance on Schoolyard Does not exist
Play Equipment
Instance on Schoolyard Inspected
1- GoodInstance Condition
No deficiencies recordedDeficiency
Safety Surfacing
Instance on Schoolyard Inspected
1- GoodInstance Condition
No deficiencies recordedDeficiency
Page 31 of 32 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M061Architectural Inspection
Question Response
SITE
PLAYGROUNDS
Unpaved Area
Instance on Schoolyard Does not exist
InspectedPLAYING SURFACE
InspectedPlaying Field
Condition 1- Good
No deficiencies recordedDeficiency
SchoolyardInstance
Does not existRunning Track
Does not existRETAINING WALLS
InspectedSEATING
InspectedBenches
Does not existConcrete
InspectedMetal/Wood/Plastic
1- GoodCondition
No deficiencies recordedDeficiency
Does not existBleachers
Does not existSITE WALLS (NOT RETAINING WALLS)
Does not existSTAIRS/RAMPS: EXTERIOR
Page 32 of 32 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)