Dr. Sahar Abd El Moneim Moussa 1
Pharos UniversityEE-385
Electrical Power & Machines“Electrical Engineering Dept”
Prepared By:Dr. Sahar Abd El Moneim Moussa
Dr. Sahar Abd El Moneim Moussa 2
OHTLOVERHEAD TRANSMISSION
LINE(Part 2)
Dr. Sahar Abd El Moneim Moussa 3
CLASSIFICATION OF T.L ACCORDING TO LENGTH
According to length , T.L. can be classified as follows:
1- Short T.L. : up to 80 km( 50 miles) 2- Medium T.L. : >80 km <240 km 3- Long T.L. : > 240 km
Dr. Sahar Abd El Moneim Moussa 4
Representation of a transmission line by a two port Network
ABCD phSV phRV
RI SI
Dr. Sahar Abd El Moneim Moussa 5
The General equation is :
Vs = A VR + B IR
IS = C VR + D IR
In Matrix Form :
VS A B VR
IS = C D IR
Dr. Sahar Abd El Moneim Moussa 6
Where,
VS = sending- end phase (line –to-neutral) voltage
VR = receiving - end phase (line –to-neutral) voltage
Is = sending-end phase current.
IR = receiving-end phase current.
Dr. Sahar Abd El Moneim Moussa 7
1- Short OHTL: (up to 80 km)
Equivalent Circuit:
Dr. Sahar Abd El Moneim Moussa 8
The General equation is:
Vs= VR+ Z IR
Is=IR
In Matrix Form :
VS = 1 Z VR
IS = 0 1 IR
Dr. Sahar Abd El Moneim Moussa 9
The ABCD Parameters of a short T.L: A=D=1, B=Z, C=0
Where,Z = R+ jXL = zL = rL +jxL Ω
Z= total series impedance per-phase in ohms.z = series impedance of one conductor in ohms per unit lengthXL = total inductive reactance of one conductor in ohms.
X = inductive reactance of one conductor in ohms per unit length L = length of the line.
Dr. Sahar Abd El Moneim Moussa 10
Efficiency:
x100%
Voltage Regulation:It is the change of voltage at the receiving end of the line when the load varies from no-load to a specified full load at a specified power factor while the sending end voltage is held constant.
= x100
Dr. Sahar Abd El Moneim Moussa 11
Where,
VRNL = magnitude of receiving end voltage at no-load
VRFL = magnitude of receiving end voltage at full-load with
constant Vs
Dr. Sahar Abd El Moneim Moussa 12
Example 9:A three-phase, 50 Hz overhead 40 km T.L. has a line voltage of 23 kV at the receiving end, a total impedance of 2.48+j6.57 per phase, and a load of 9 MW with receiving end lagging pf of 0,85. Calculate:a) Line to neutral voltage at the sending endb) Efficiency of the linec) Voltage regulation of the line
Dr. Sahar Abd El Moneim Moussa 13
Solution:a)
Cos R= 0.85 lagging , R=31.8 lagging= -31.8
Is=IR=265.8 -31.8 A= 225.9 –j140.1 A
Vs= VR+Z IR= 132790 + (2.48 +j 6.57)* (225.9 –j 140.1)
=13279 + 560.2 –j347.5 +j1484.2 +920.5= 14759.7 + j 1136.7 = 148034.4 V
Dr. Sahar Abd El Moneim Moussa 14
b) %= s=Vs - Is = 4.4 –(-31.8)= 36.2
%=
c) = x100
VR%=
Dr. Sahar Abd El Moneim Moussa 15
2- Medium OHTL: ( from 80 km to 240 km)
The medium OHTL can be represented either by:
.i - equivalent circuit ii. T- equivalent circuit
Dr. Sahar Abd El Moneim Moussa 16
i- - Circuit:Equivalent Circuit:
j X
VS VR
IS R
C/2C/2
Ics I ICR
Ir
Dr. Sahar Abd El Moneim Moussa 17
The General equation is:
In Matrix Form : VS = 1+ Z
VR
IS = 1+ IR
Dr. Sahar Abd El Moneim Moussa 18
The ABCD Parameters of a short T.L:A=D= 1+, B=Z, C=
Efficiency: x100%
Voltage Regulation: = x100
Dr. Sahar Abd El Moneim Moussa 19
i- T- Circuit:Equivalent Circuit:
Dr. Sahar Abd El Moneim Moussa 20
The General equation is:
In Matrix Form : VS = 1+ Z VR
IS = 1+ IR
Dr. Sahar Abd El Moneim Moussa 21
The General equation is:
In Matrix Form : VS = 1+ VR
IS = 1+ IR
Dr. Sahar Abd El Moneim Moussa 22
The ABCD Parameters of a short T.L:A=D= 1+, B= Z, C=
Efficiency: x100%
Voltage Regulation: = x100
Dr. Sahar Abd El Moneim Moussa 23
Example 10A 50 Hz 200 km, transmission line has 132 kV between the lines at the receiving end and has per phase R=0.1 /km , L=0.828 mH/kmAnd C= 0.005 F/km. the line is supplying a load of 30MW at 0.85 lagging pf. Find using approximated -model:
a) A,B,C and D constants of the lineb) V and I at the sending end of the line)c and VR of the line
Dr. Sahar Abd El Moneim Moussa 24
Solution:Z= R+ j L= 0.1 x 200 + j 2 x x 50 x 0.828 x 10-3 x 200 = 20 + j 52 = 55 69 Y= j C= j 2 x x 50 x 0.005 x 10-6 x 200 = j 314 x 10-6 mho= 314x10-6 90 mhoYZ= -0.016 + j 0.00628 ( 1)
a) A= D= 1
B= Z= 20 + j 52 = 55 69
C= Y = j 314 x 10-6 mho= 314x10-6 90 mho
Dr. Sahar Abd El Moneim Moussa 25
b) Vs= A VR + B IR = VR + Z IR
VR (ph)=
IR= =
Vs= 76210 0 + 55.7 69 x 154 -31.8= 83200 3.6 V
Is= C VR= + DIR= Y VR + I R
= 314 x 10-6 90 x 76210 0 + 154 -31.8= 143 -23.5 A
Dr. Sahar Abd El Moneim Moussa 26
c) PR= 30 MW
PS = 3 x VSph x Is x Cos S
S= VS - IS= 3.6 –(23.5) = 27.1
PS= 3 x 83200 x 143 x cos 27.1= 31.77 MW
%=
VR% =