1www.alltemp.ca
Refrigeration Monitoring And Controls Catalogue
Vol 2.0
22
One Control
Evaporator Probe
Return Air Probe
Compressor
FanDefrost
7 ApplicationsParameter
tCType of Control
Models Replaced
Required Probes
1 On / Off thermostat - HeatingXR110C, XR01CX, XR10C, XR10CX
x 1
2 Off cycle defrost (timed)XR120C, XR02CX, XR20C, XR20CX
x 1
3Off Cycle defrost time initiated / temperature terminated
XR120C, XR02CX, XR20C-E
x 2
4Off Cycle defrost time initiated / temperature terminated, Alarm Relay
XR130C, XR03CX, XR30CX
x 2
5Electical / Hot gas defrost, time initiated / temperature terminated
XR140C, XR04CX, XR40CX
x 2
6Electical / Hot gas defrost, time initiated / temperature terminated + evap. Fan delay and control
XR160C, XR06CX, XR60CX
x 2
7Full open map of parameters,configure your own control
Your determination 1 to 3
Universal - XR ControllerU
NIV
ER
SA
L -
XR C
ON
TRO
LLE
RThe Universal-XR controller offers a 7 in 1 solution for Heating/Medium & Low Temperature/Defrost/Fans/Alarms etc. in just one control. Select one of the six preset maps in the application menu, and you now have a replacement of virtually any control. It’s the one control that is a must have on your service vehicle. Ultra simplified, one does it all. The Universal-XR Advanced Map (tC=7) allows total flexibility with inputs and outputs. Comes complete with two NTC probes, will work with existing PTC/NTC probes. TTL/Modbus communication capable with optional adapter.
Part # Description
14-XR60CX-AN1F1-UR 12/24 Volts
14-XR60CX-4N1F1-UR 120 Volts
14-XR60CX-5N1F1-UR 240 Volts
Dimensions:Frontal: 74x32mm,
70mm depth
Mounting: 71x29mm panel cutout
33
tC = 2 Cooling, Off Cycle Defrost, Time Ended tC = 3 Cooling, Off Cycle Defrost, Time Ended
tC = 1 Heating
tC = 4 Cooling, Off Cycle Defrost, Time Ended, Alarm Relay tC = 5 Cooling, Electric or Hot Gas Defrost Temp.Ended
tC = 6 Low Temp, Elec. or Hot Gas Defrost, Temp. Ended, Fan Control tC = 7 Open Map to be Configured for any Application
The One . . . And Only CONTROL THAT SHOULD BE ON YOUR TRUCKUniversal-XR Replacement Controller for all Dixell, and many other
manufacturer's models.
4
e-Class Controllers
Medium Temp Refrigeration
Low Temp Refrigeration
The e-Class series of controls are the OEM choice for economy, efficiency, and easiness. Designed for the North American market, the e-Class features high quality components built in a state-of-the-art factory in northern Italy. Simplified parameters, Hot Key programming for warming, medium, and low temp refrigeration. Extra large relays assure long life. 1/4" Fast-on Connectors ideal for OEM production assembly.
Specifications
Power: 120V / 230Vac 50/60HzOutputs: 16FLA / 96LRA, 16A Res. 10A DEF 5A FAN (see model difference)Inputs: 1 NTC / PTCRange: -40 / 230 or 302°FProtection: IP65Digital Inputs: 0-1
Display: 2 or 3 DigitsIcons: 3Connections: Probes DisconnectableOutputs: 1/4" fast-onHot Key: YesTTL: No
E-C
LAS
S C
ON
TRO
LLE
RS
Part # Description
14-XR02CX-4N4FQ 120V, NTC, No Buzzer
14-XR02CX-4N5FQ 120V, NTC, w/ Buzzer
14-XR02CX-5N4FQ 240V, NTC, No Buzzer
Part # Description
14-XR06CX-4N4F7 120V, NTC, No Buzzer
14-XR06CX-4N5F7 120V, NTC, w/ Buzzer
14-XR06CX-5N4F7 240V, NTC, No Buzzer
Dimensions:Frontal: 74x32mm, 60mm depth
Mounting: 71x29mm panel cutout
Dimensions:Frontal: 74x32mm, 70mm depth
Mounting: 71x29mm panel cutout
14-C-BoxAvailable Enclosure
5
Prime Series ControllersThe Dixell Prime Series configurable controllers provide digital solutions for both medium temperature and low temperature refrigeration units. Depending on the model the installer can adjust through the parameter menu such fields as set point, differential, short cycle protection, energy savings temperature differential, digital input configuration, fan cycling plus alarm levels and delays. Included TTL Modbus communications via Hot Key port.
PR
IME
SE
RIE
S C
ON
TRO
LLE
RS
Dimensions:Frontal: 74x32mm, 70mm depth
Mounting: 71x29mm panel cutout
SPECIFICATIONS:Power: 120V / 230Vac 50/60hzOutputs:16FLA/96LRA,10A, 5A(see model differences)Inputs: 1-3 NTC / PTCRange: -40 / 230 or 302 °F/CProtection: IP65Digital Inputs: 1
Display: 3 DigitsIcons: 8Connections: Probes disconnectableOutputs: 1/4" fast-onHot Key: YesCommunications: TTL / Modbus
4 5 6 7
9 10 11 12
Comp
Room
8Hot Key/IV Probe
TTL or X-REP output
20(8)A250V
Line
N.C.
1 2 3 4 5 6 7
9 10 11 12
CompLight/Alarm
Room
8Hot Key/IV probe
TTL or X-REP output
8(3)A250V 20(8)A250V
Line
Medium Temp Refrigeration(Off Cycle Defrost)
Low Temp RefrigerationComp/Def/Fan
Low Temp RefrigerationComp/Def/Fan/Alarm
Alarm / Defrost
N.C.Line
8(3)A250V~
1 2 3 4 5 66
9 10 11 12
5(1)A
Max20A
Comp Def
Evap
.
Room
7Hot Key/IV probe
TTL or. X-REP outputFan
8
20(8)A250V~
How to OrderPrime Series Voltage Sensor Options F/C Relay/Connectors
XR10CXXR20CXXR30CXXR40CXXR60CXXR70CX
0 = 15AC/DC1 = 24AC/DC4 = 120Vac5 = 230Vac
N = NTCP = PTC
P = PT1000(XR30 / 70 only)
0 = None1 = Buzzer
F = °FC = °C
7 = 16FLA / 1/4"Fast-ons
8 = 16/60A 1/4" Fast-ons
(XR70CX only)
Part #
14-XR20CX
Part #
14-XR60CX
Part #
14-XR70CX
Part #
14-XR30CX
14-XR40CX
6
On-Demand®Defrost – Saves Energy
Electronic SetPoint – More Accurate
Hands Free Lights – Auto Off Feature
Energy Saver Mode – Nights and Weekends
Remote Communications – Monitor via XWEB
Remote Keypad – Monitor Temps and Alarms
XW Walk-In ControlThe Dixell XW60K Walk-in controller provides an electronic solution for both medium temperature and low temperature Walk-in units. The XW60K features On-Demand® Defrost, Energy Saver Mode, Hands Free auto-off lights, Fan Cycling, Remote Keypad, and includes digital inputs for door ajar switches and other interfaces. Alarms include high and low temps, door and condenser alarms. energy savings can be up to 20-25%.
XW60K Remote KeypadXW60K Remote Keypad
P3 Discharge Air Probe
P1 Return Air Probe
P2 Evap. / Def. Probe
On-‐Demand® Defrost Output
Evap. Fan Output
Liq. Solenoid Output
Light or Alarm Output
Door Switch Input Remote ConnecIon to 100Ft.
Replaces all this
P4 Opt. Condenser Probe
XW W
ALK
-IN
CO
NTR
OL
7
Optional XW Superheat Controller
The Dixell XW Superheat controller provides an electronic solution for stepper electric expansion valves. Featuring pre-sets for all popular valves the XEV22 takes a 0/5V or 4...20mA pressure input plus a Pt1000 or NTC input to manage Superheat. Special defrost algorithm reduces defrost time. Add to the XW60K for an advanced walk-in control solution.
Medium Low Temp Refrigeration for Walk-insComp/ Def / Fan/ Light
Replaces all of these Mechanical Instruments
XW60K
Remote Keypad
Optional XEV Driver
SPECIFICATIONS:Power: 120V / 230Vac 50/60hzOutput: 16FLA/96LRA 2 x 16A 1 x 10AInputs: NTC / PTCRange: -58 /230°F PTCDisplay: 3 DigitsIcons: 8Panel Mount: 32 x 74MMConnections: Probe screw terminalsOutputs: 1/4” fast-onKeyPad: J-Box mount / IP65Communications: TTL Modbus
Part # Description
14-XW60K-4N2F0 115V Kit
14-XW60K-5N2F0 230V Kit
XW60KINCLUDES:XAW60K ControlRemote KeypadDoor SwitchUSB HotKey3 Probes8" Mounting BoxHardware
8
• High/Low temperature alarms w/ delays
• Lighting management – Auto on/Auto off
• Door open alarm w/ magnetic door switch
• Range – 40/230°F• 8ft probe• Battery back-up• Loud buzzer• Pre-wired
XWA Walk-In AlarmOperators can be certain that the temperature inside their walk-in stays in the safe zone by indicating either a high or low temperature condition with a visual alarm and pulsing buzzer. An open door alarm keeps the cold inside where it belongs. A set of alarm contacts is included for outboard signaling. The light management system will automatically turn the lights ON when you open the door and the “AUTO-OFF” feature shuts off the light after an adjustable time delay. Optional 9Vdc battery back up will allow for visual alarms for up to 96 hours.
Part # Description
14-XWA11V-25-KIT Walk-in Alarm Kit
XWA
WA
LK-I
N A
LAR
M
9
Alarm CodesHA High Temp AlarmdA Door open alarmLA Lo Temp AlarmPan Panic AlarmP1 Probe AlarmEA External Alarm
XWA11V-25-KITINCLUDES:Wall Mount EnclosureDoor SwitchExternal BuzzerPre-wired
iDial1Includes ext. relay to convert 8Aalarm relay to D.I.Includes 9/12Vdc transformerRJ11 wires and instructions9 Programmable phone no’sfor each channel
PANPushbutton backlight panicalarm. The XWA will display“Pan” and turn on alarmrelay for external buzzer orphone dialer
MGSGas leak detector for refrigerantleaks. Various gases/rangesavailable.
H300Current transformerto detect defrost.
MDSMagnetic door switch1/2” spacing magneticdoor switch to connectto digital input
STRStrobe light for visual alarmwarning
Accessories Available:iDial Phone DialerMGS Leak DetectorPAN Panic ButtonEXT/BUX External 85db buzzer
SPECIFICATIONS:Power: 120V / 230Vac 50/60hzOutput: 8A alarm / 15A LightInputs: NTCRange: -40 / 230°FDisplay: 3 DigitsIcons: 3J-Box Mount Connections: Probe 1/4" fast-onsOutputs: 1/4" fast-on
10
Anti-Sweat ControllerThe XH55P measures temperature and Humidity and calculates Dew Point. The unit then turns on and off glass door heaters to eliminate condensation on the glass. The internal 16A relay can manage between 6 and 10 doors depending on amperage draw. The units has 3 LED indicators; ON / TX / Alarm, has one Digital Input, voltage free open / closed circuit that can initiate Energy Saver Mode (i.e. turn off when the cooler is in defrost).The adjustment knob offset is a + /- 6°F Dew Point Set Point adjustment to run the control on the “Dew Point Edge”, saving energy costs and offers seasonal adjustment. An analog output (0/10V) and RS485 Modbus interface allows the XH55P to communicate to BMS Systems and is XWEB Compatible.
Part # Description
14-XH55P Anit-Sweat Controller
+ + 10 11 12
8 or 16A
HOT KEY
0 – 10V RS485 PowerSupply
n.c. c. n.oDi
gital
Inp.
Rem
ote
1 2 3 4 5 6- -
7 8 9
• Walk-in Coolers & Freezers
• Glass doors• Temperature and
Humidity Monitoring• Energy Saving
SSR Box Solid State RelayXJ485USB Wall Bracket
MountingSPECIFICATIONS:Power: 24VAC, 3VA maxOutput: 16A internal/Optional 25A SSR outboard relay Kit, and one 0/10V Analog Output.Inputs:Digital Input (open/closed circuit) that is typically used to place the unit into Energy Saving Mode ( as defined by the HES parameter)
AN
TI-S
WE
AT C
ON
TRO
LLE
R
11
XJDL Series Digital Data LoggerRecord up to 4 temperatures every 15 minutes and store up to 1 year with the XJDL Digital Data Logger. Operators can take the guesswork and human error out of HACCP recording. Record up to 4 temperatures and 4 events, such as door openings or defrost cycles on a single unit. Data transfer to a PC with ease using a standard USB drive to a .TXT file that can be uploaded to Excel. Dated security prohibits tampering. A built-in dry contact relay can be used for audible or visual alarms, phone dialer, BMS or security system interface.
Part # Description
14-XJDL40D Data Logger Kit
DIG
ITA
L D
ATA
LO
GG
ER
KIT INCLUDES:• (4) 8 ft. NTC probes included –40/230°F&C• Record every 15 minutes and store for up to 1 year• Download .TXT file to USB key/Upload to any PC & Excel®
• Hi & Low Alarm setpoints with dry contacts SPDT• 4 door switch inputs• 24V Plug-in transformer• Wall mounting enclosure
12
PR
OB
E M
ON
ITO
RIN
G M
OD
ULE
SI/O Probe Monitoring ModulesXJP60D is an acquisition module that can read up to 6 analogue inputs and 3 inputs at 230Vac (110Vac or 24Vac opt.). By means of the serial output RS485, they can be connected to the XJ500 or a ModBUS-RTU compatible monitoring system. Modules XJP, DIN RAIL format, are without display and are programmable by means of a programming keyboard KB1 PRG. The analogue inputs can be PTC, NTC 4÷20mA or 0÷10V; when the inputs are PTC or NTC the choice can be made by a parameter.It is also possible to program them with with a programming "Hot Key" and to connect them to a display device calle XJP REP which shows the main temperature and input status.
13 14 15 16 17 18 19 20 21 22 23 24
10 11 125 6 7 8 93 41 2
Part # Description
14-XJP60D-2F0N3 Monitoring Module
SPECIFICATIONS:Housing: self extinguishing ABS.Case: 4 DIN modules 70x85mm; depth 61mm.Mounting: DIN RAIL mounted in an omega (3) din rail.Connections: Screw terminal block ≤ 2.5mm2 wiring.Power Supply: 230Vac, ± 10% 50/60Hz;24Vac, ± 10% 50/60Hz.Power Absorbtion: 3 VA max.Analogue Inputs: 6 probes PTC or NTC inputs 4÷20mA or 0÷10V.Inputs: 3 power supply inputs.RS485 Outputs: RS485 serial output with ModBUS-RTU protocol.Data Storing: on the non-volatile memory(EEPROM)Operating Temperature: 0÷60°CStorage Temperature: -30÷85°CRelative Humidity: 20÷85%Mesuring and Regulation Range: PTC: -50÷150°C (-58÷302°F) NTC: -40÷110°C (-58÷230°F) or according to the probe.Resolution: 0.1°C or 1°F (selectable)Accuracy of the Controller at 25°C: ±0.3°C ± 1 digit
13
Part # Description
14-XJR40D Relay Module
SPECIFICATIONS:Housing: self extinguishing ABS.Case: 4 DIN modules 70x85mm; depth 61mm.Mounting: DIN RAIL mounted in an omega (3) din rail.Connections: Screw terminal block ≤ 2.5mm2 wiring.Power Supply: 230Vac, ± 10% 50/60Hz (opt. 115Vac, ± 10% 50/60Hz; 24Vac, ± 10% 50/60Hz.)Power Absorbtion: 6 VA.Digital Inputs: 4 free voltage contactRS485 Outputs: RS485 serial output with ModBUS-RTU protocol.Data Storing: on the non-volatile memory(EEPROM)Operating Temperature: 0÷60°CStorage Temperature: -30÷85°CRelative Humidity: 20÷85% ( no condensing)
LIG
HTI
NG
CO
NTR
OLL
ER
4 Zone Light ControllerXJR40D is a module with 4 on-board relays and 4 digital Input free voltage contact (DI). All the outputs can be switched by the local or remote keyboard. This module is equipped with the serial output RS485, so it can be connected to the XWEB series or to a ModBUS-RTU compatible monitoring system. XJR, DIN RAIL format, is without display and has to be programmed by means of the keyboard KB1 PRG. It is also possible to program it with a programming "Hot key”
PowerSupplyRS485
1917 18 22 2313 14 16 20 21
8(3)A/250Vac
1 2 3 4 5 8 976 11 12
15 24
8(3)A/250Vac 8(3)A/250Vac 8(3)A/250Vac
Load2 Load3 Load4Load1Line
14
XC10CX Features:• Controls based on Suction Pressure, Cut
In/Cut Out• 0/150psi Brass transducer 1/4 SAE female
connection• PSI Display reading• High pressure switch input for safety (auto
& manual reset)• Optional temp input for high temp alarm• Bump Start function (after being idle for
over 4 years)
XC30CX Features:• Fan Management – up to 2 fans• Equalizes fan run time• 0/500psi SST transducer ¼ SAE female
connection• 0/150psi Brass transducer ¼ SAE female
connection
Alarm Recording• Number of high pressure alarms• Number of high temperature alarms• Number of manual restarts
SensorsXC10CX - W528-150-S-F2A 1/4 SAE (7/6-20UNF-2A) internal thread with Schrader deflator. Range 0-150psi. It has a three wire disconnectable metro-pack connector with 12" flying leads
SensorsXC30CX - W528-150-S-F2A 1/4 SAE (7/6-20UNF-2A). Additional ranges and material are available
Service Menu• Number of compressor starts• Compressor running hours• First fan working hours• Second fan working hours
CO
ND
ENSI
NG
UN
IT C
ON
TRO
LLER
XC Condensing Unit ControllerThe Dixell XC10 & 30CX Controls replace old mechanical pressure switches that are inaccurate, difficult and time consuming to set up.The XC Controls can directly control a compressor and up to 2 fans (XC30CX model).It is possible to control the pressure values of the suction and discharging lines by using a new low cost ratio-metric pressure sensor input. With the addition of a fixed pressure switch you can shut down (and save) the compressor on high pressure alarm conditions. The XC30CX will also control up to two condenser fans, rotating them for equal run times. A service menu records information on starts, run times, manual starts, and alarms.
Part # Description
14-XC10CX-4P00G Compressor Control
Part # Description
14-XC30CX-4P004HU Compressor + 2 fans, Control only
14-XC30CX-4P004H-KITXC30CX w/ 2 transducers, a box, harness and High
pressure switch
15
XC10CX XC30CX
Circuits 1 1
Compressors 1 1
Fans 0 1-2
PSI Sensor 1 2
Ratio-Metric Transducer
SPECIFICATIONS:Housing: self extinguishing ABSCase: frontal 32x74 mm; depth 70mmMounting: panel mounting in a 71x29mm panel cut-outProtection: IP20Frontal protection: IP65Connections: spade on terminal blocks 6.2mmPower supply: according to the model: 230Vac 10%, 50/60Hz, 110Vac 10%, 50/60HzPower absorption: 3VA maxDisplay: 3 digits, red LED, 14.2 mm highInputs: up to 3 probesDigital input: free voltage contactRelay outputs: Compressor: SPST 20(8) A, 250VacData storing: on the non-volatile memory (EEPROM)Kind of action: 1BPollution degree: 2Software class: ARated impulsive voltage: 2500VOvervoltage Category: IIOperating temperature: -10 to 55°C (14 to 131°F)Storage temperature: -30 to 85°C (-22 to 185°F)Relative humidity: 20 to 85% (no condensing)Measuring and regulation range: NTC probe: -40 to 110°C (-40 to 230°F) PTC 990ohm probe: -50 to 150°C (-58 to 302°F)Resolution: 0.1°C or 1°C or 1°F (selectable)Accuracy (ambient temp. 25°C): ±0.7°C ±1 digit
16
XC650CX XC645CX XC1015D
Circuits 1 1 2
Compressors 2-5 2-5 2-15
Digital Scroll no yes opt.
Fans 1-3 1-3 1-15
Unloaders yes yes yes
XC Rack ControlsDixell offers a full line of Compressor Rack Controllers for systems of all sizes. Project specifications may include working with multiple stages, compressors of differing power, condenser fans, digital scroll management, proportional band or dead band adjustments. Options on certain models can include alarm relay and analog outputs. Tell us about your next project.
XC R
AC
K C
ON
TRO
LS
Part # Description
14-XC650C-1C02E Up to 5 comps and/or fans
Part # Description
14-XC645C-1C0F1 1 Digital Scroll + up to 4 comps and/or fans
Part # Description
14-XC1015D-1F01F Advanced Rack Control15 Relay outs + 4 analog outs
17
MGS Gas Leak DetectorThe MGS is either a stand alone leak detector which utilizes a range of sensor types to detect most gases or as part of a remote monitoring system. The MGS detects most gases using a variety of sensor technologies: Semiconductor, Electrochemical or Infrared, depending on the type of gas monitoring required. The MGS continuously determines the gas level present in an area, room, zone, air space or airflow. A Universal gas detection solution interfaces with the XWEB using the XJP60D or any controller, BMS or SCADA system through selectable analogue outputs: 0-5V,1-5V, 0-10V, 2-10V or 4-20mA. A Relay Output rated at 1A SPDT is included along with an internal buzzer.
Part # Description
14-MGS-R404A Infared Gas Sensor - R404A
GA
S L
EA
K D
ETE
CTO
R
MODEL MGS OVERVIEWThe Sensor detects various gas leaks in PPM (parts per million) and will alarm at 50% of the range and send an analog out-put 0-5V, 1-5V, 0-10V, 2-10V or 4..20mA to a Monitoring system. Specify specific gas when ordering.MOUNTING: The product is wall mounted using multiple wall mounting options on the back of the 3.39" x 4.73" case.SENSORS: The product shall have Semi-conductor, Electromechanical or Infrared sensors, depending on the gas to be detected. POWER: The product shall be powered by 12 - 24Vac/dc - 91mA max.OUTPUTS: The MGS has one 1A SPDT relay output, and a 0/10V, 05V or 4...20Ma analog output. The MGS is compatible with the XJP60D and XWEB.
Applications include detection of:• Refrigerant gases including: Ammonia,
Carbon Dioxide, Hydrocarbons, Halocarbons HFCs, HCFCs, CFCs, for refrigeration, air-conditioning.
• Combustible gases such as Methane, LPG, Propane, Butane, and Hydrogen for industrial heating, landfills and power generation.
• Toxic gases such as: Carbon Dioxide and Ammonia in refrigeration, Hydrogen Sulphide in sewage treament plants and Carbon Monoxide in underground parking garages.
• Volatile Organic Compounds such as: Acetone, Benzene, Carbon Tetrachloride, Chloroform, Ethanol, Toluene, Trichloroethylene, for process and general industrial.
• Detect small leaks before they become big problems.
• Reduce costs of replacement refrigerant, service calls and product loss.
Other refrigerants available by replacing "R404A" with required refrigerant.
18
iStat/ProThe HVAC system can represent up to 25% of an operators utility costs. The thermostat is the key component to save on heating or cooling system costs. The requirements are: First it must look good on the wall, be very easy to use and meet all the needs of the user and the equipment it is controlling. Second it must be able to adapt to all the different control variations required (single or multi stage heat/cool systems, single or multiple fan speed + Heat Pump and emergency heat applications. Initially the operator has to be able to “lock-out” local control in favor of remote control, while maintaining comfort and eliminate energy wasting adjustments.
The installer is able to configure the iStat/Pro to control Heat pump systems, (with auxiliary or emergency heating if necessary) gas/oil heating systems with add on cooling, plus control high and low balance points (using external sensors as well as the number of heating and cooling stages needing precise control. It can even adapt to manage the number of fan speeds it can control. The operator can choose The iStat/Pro to be in programmable or manual mode with single or multiple set points. By networking multiple iStat/Pro's with our XWEB Internet Monitoring and Control System, the iStat/Pro can be remotely Monitored and Controlled keeping HVAC costs under control.
Part # Description
iStat/pro Manual/Programmable Thermostat
Features:• Selectable as Manual or Programmable• Up to 2 stage Heat/Cool or heat pump• Single or 3 speed fan control• Keyboard and/or Temperature Locks• Occupancy sensor input• Economizer function• 24V powered with battery backup• Large backlit LCD Touch Screen Display• Remote temperature sensors available• Integrated Remote Communications• Replaces almost all 24V thermostats• XWEB Compatible
ISTA
T P
RO
19
Installer Options: Wiring
20
Model No.24DT0=Thermometer onlyS = SST CoverL = with Light SwitchPower0=12Vac./dc4=110Vac.5=230Vac.DisplayF = °F -40/230°FC = °C -40/110°CUpdate Time*0 = 1 Second1 = 1 Minute3 = 3 MinuteEx: 24DT-L-4F1Wall Plate Thermometer / 120 Vac / Light Switch / 1 Minute Update
How to Order LED Thermometers
Model No. Mounting20DT U = U-Clamp F = Front Flange
Power0 = 12 Vac/dc4 = 120 VacDisplayF = -40/230°FC = -40/110°CUpdate Time*0 = 1 Second1 = 1 Minute*3 = 3 Minute*Order Entry Example: 20DTF-4F12" Front Flange / 120 Vac / °F / 1 Second Update*Display changes 1° every 1 or 3 minutes on increase of temperature – on decreasing temperature, the display will change every second, regardless of time.
24DT 20DT 24DT-S 24DT-L
ThermometersThe New Generation LED Thermometers include our exclusive Direct Power Feature eliminating the need for an external transformer. Powered by 120Vac, (230Vac,12Vac, optional) not only makes the unit easier to install but adds reliability and life to the instrument. With UL and NSF Listing, both designs can be ordered with 1 second,1 minute or 3 minute display update times to eliminate temperature fluctuations from repeated door openings. Each unit has a detachable sensor and power fast-ons to speed up installation. With an extended range of –40 to 230°F our LED units are well suited to many applications. Includes Temperature Probe and Wiring Harness.*
THER
MO
MET
ERS
21
APPLICATIONS FOR FOOD SAFETY AND ENERGY SAVINGSCHOOLS • FOOD WAREHOUSES • INSTITUTIONAL FOOD SERVICE • C-STORES
HOTEL KITCHENS • FOOD PROCESS • RESTAURANTS • SUPERMARKETSDixell Monitoring & Control Applications via the Internet
see diagram on back cover
SU
PE
RV
ISO
R A
ND
MO
NIT
OR
ING
SY
STE
MS
XWEB EVOThe XWEB EVO is the new system family for the optimum management of Retail field and HVAC/R applications. New innovative tools to improve the efficiency of both small and large applications are available such as the advanced graphical one to facilitate the data analysis. Furthermore, systems are provided with a customizable web user interface to make navigation easier and without any additional software. XWEB EVO is designed to obtain energy savings, thereby reducing running costs and helping to preserve the environment. Our solutions are synonymous with quality, user-friendliness and efficiency because they are focused to meet end user needs.
A powerful hardware platform with USB, Ethernet, RS485 ports, and more, offers the maximum level of connectivity.
HIGHCONNECTIVITY
The user interface is available for modern Web browsers without the need to install additional software. XWEB EVO is also compatible with HD and touch-screen technologies and tablets.
HIGHINTEGRATION
An effective alarm management system easily detects and signals alarm status so prompt intervention can restore optimum functioning of the application.
ALARMMANAGEMENT
Constant data recording, HACCP reports and timely alarm notifi cation guarantee high quality of fresh and frozen food and is in compliance with the UNI EN 12830 rule.
FOODQUALITY
Special algorithms and continuous tracking of energy usage optimizes the application’s effi ciency by increasing energy savings and reducing costs.
ENERGYSAVING
With our eco-friendly solutions, innovation and effi ciency means respecting the environment by optimizing consumption and reducing pollution, gas emission and waste.
ENVIRONMENTALLYFRIENDLY
Part # Description
XWEB300D EVO 6 or 18 device installations
XWEB500 EVO 20, 36, 50, or 100 device installations
XWEB500D EVO 20, 36, 50, or 100 device installations
22
ProbesPR
OB
ES
Nickel Brass 1.8" x ¼" Molded / Potted Probe18NB-NTC-1.5M 05ft18NB-NTC-2.5M 08ft18NB-NTC-4.5M 15ft18NB-NTC-6.0M 20ft
Standard 10K Ohm NTC Thermistor -40/230°F
SST 3.0" x ¼" Molded / Potted Probe30SS-NTC-x.xM Lengths noted above, max length 300ft.Other lengths, NPT Fittings and Thermo-wells available.
Pipe Mount Condenser Molded ProbePMT6-67-1.5M 5ft. 1/8" to 11/8" Pipe PT-1000NT6-67-1.5M 5ft. 1/8" to 11/8" Pipe NTC
XH10P 30-90%RH +/- 5% 4…20mAXH20P 0-99%RH +/- 3% 4…20mA
PP11 0-160psi +/- 1% 4….20mAPP30 0-435psi +/- 1% 4….20mA
PPR15 0-218psi +/- 1.2% 0/5VPPR30 0-435psi +/- 1.2% 0/5V
W528-150 0-150psi +/- 1.5% 0/5VW528-500 0-500psi +/- 1.5% 0/5V
wall mount
7/16”-20 male
7/16”-20 female
7/16”-20 female
Nickle Brass Probes
Stainless Steel Probes
Humidity Probes
Pressure Transducers
23
TEMPERATURE TO RESISTANCECHART NTC THERMISTOR
Temp C Temp F Resistance Ohms-50 -58 329.5-45 -50 247.7-40 -40 188.5-35 -31 144.1-30 -22 111.3-25 -12.5 86.43-20 -4 67.77-15 5 53.41-10 14 42.47-5 23 33.90 32 27.285 41 22.0510 50 17.9615 59 14.6920 68 12.0925 77 1030 86 8.31335 95 6.9440 104 5.82745 13 4.91150 122 4.1655 131 3.53660 140 3.0265 149 2.58870 158 2.22875 167 1.92480 176 1.66885 185 1.45190 194 1.26695 203 1.108100 212 0.9731105 221 0.8572110 230 0.7576
All Resistance is k or (x1000)
Refrigeration Monitoring And Controls Catalogue