GENERAL NOTES
LEGEND
1. Detail not suitable for all climates. Avoiding excessive moisture accumulation in exterior walls is dependent on many factors including properplacement of insulation and water, air, and vapor control layers in the wall. Confirm membranes are suitable for project specific servicetemperatures. For assistance with exterior wall design, consult with a building science professional.
2. Install all GCP products in accordance with GCP Product Data Sheets and GCP recommendations.3. GCP products are indicated in the detail legend in BOLDFACE font. Detail components by others are indicated in GRAY FONT. Install
components per manufacturer and project specific requirements.
*Refer to air barrier system product data sheet for acceptable SELF-ADHERED FLASHING* products.
LIST OF DRAWINGSWINDOW DETAILS AT MASONRY CLADDING
BASE OF WALL DETAILS AT MASONRY CLADDING
LEDGER DETAILS AT MASONRY CLADDING
PARAPET DETAILS AT MASONRY CLADDING
EXPANSION AND CONTROL JOINT DETAILS
WINDOW DETAILS AT NON-MASONRY CLADDING
NON-MASONRY CLADDING DETAILS
CURTAINWALL DETAILS AT NON-MASONRY CLADDING
PWM-001 WINDOW HEAD DETAIL MASONRY CLADDINGPWM-002 WINDOW JAMB DETAIL MASONRY CLADDINGPWM-003 WINDOW SILL DETAIL MASONRY CLADDINGPWM-003 (3D-1) WINDOW FLASHING SEQUENCE SHEET-APPLIED FLASHINGPWM-003 (3D-2) SHEET-APPLIED FLASHING PRESTRIP
PWM-004 BASE-OF-WALL DETAIL MASONRY CLADDINGPWM-004 (3D-1) BASE-OF-WALL FLASHING SEQ. (OPT. 1) MASONRY CLADDINGPWM-004 (3D-2) BASE-OF-WALL FLASHING SEQ. (OPT. 2) MASONRY CLADDINGPWM-004 (ALT 1) BASE-OF-WALL DETAIL (ALTERNATE 1) MASONRY CLADDINGPWM-004 (ALT 2) BASE-OF-WALL DETAIL (ALTERNATE 2) MASONRY CLADDING
PWM-005 FLOOR LINE DETAIL MASONRY CLADDINGPWM-005 (3D-1) FLOOR LINE FLASHING SEQ. (OPT. 1) MASONRY CLADDINGPWM-005 (3D-2) FLOOR LINE FLASHING SEQ. (OPT. 2) MASONRY CLADDINGPWM-006A MASONRY ANCHOR DETAIL CMU SUBSTRATEPWM-006B MASONRY ANCHOR DETAIL FRAMED SUBSTRATE
PWM-007 PARAPET DETAIL MASONRY CLADDING
PWM-008 EXPANSION JOINT DETAIL PWM-009 CONTROL JOINT DETAIL
PWM-010 WINDOW HEAD DETAIL NON-MASONRY CLADDINGPWM-011 WINDOW JAMB DETAIL NON-MASONRY CLADDINGPWM-012 WINDOW SILL DETAIL NON-MASONRY CLADDING
PWM-013 FLOOR LINE DETAIL NON-MASONRY CLADDINGPWM-014 CONCRETE STEM WALL DETAIL NON-MASONRY CLADDINGPWM-015 BASE-OF-WALL DETAIL AT GRADE NON-MASONRY CLADDINGPWM-016 BASE-OF-WALL DETAIL NON-MASONRY CLADDINGPWM-017 INSIDE CORNER DETAIL NON-MASONRY CLADDINGPWM-017 (ALT) INSIDE CORNER DETAIL (ALTERNATE) NON-MASONRY CLADDINGPWM-018 OUTSIDE CORNER DETAIL NON-MASONRY CLADDINGPWM-018 (ALT) OUTSIDE CORNER DETAIL (ALTERNATE) NON-MASONRY CLADDINGPWM-019 KNIFEPLATE PENETRATION DETAIL NON-MASONRY CLADDINGPWM-020 PENETRATION DETAILS NON-MASONRY CLADDING
PWM-021 CURTAINWALL HEAD DETAIL NON-MASONRY CLADDINGPWM-022 CURTAINWALL JAMB DETAIL NON-MASONRY CLADDINGPWM-023 CURTAINWALL SILL DETAIL NON-MASONRY CLADDING
DEFLECTION JOINTPWM-024 DEFLECTION JOINT NON-MASONRY CLADDING
3" = 1'
LIST OF DRAWINGS DRAWING: PWM-000
SCALE:
EFFECTIVE DATE: 2020.05.21
SUPERCEDES:
PERM-A-BARRIER® WALLMEMBRANE
NEW
GENERAL NOTES
LEGEND
1. Detail not suitable for all climates. Avoiding excessive moisture accumulation in exterior walls is dependent on many factors including properplacement of insulation and water, air, and vapor control layers in the wall. Confirm membranes are suitable for project specific servicetemperatures. For assistance with exterior wall design, consult with a building science professional.
2. Install all GCP products in accordance with GCP Product Data Sheets and GCP recommendations.3. GCP products are indicated in the detail legend in BOLDFACE font. Detail components by others are indicated in GRAY FONT. Install
components per manufacturer and project specific requirements.
*Refer to air barrier system product data sheet for acceptable SELF-ADHERED FLASHING* products.
OPTION 1
3" M
IN.
1. PERM-A-BARRIER® WALL MEMBRANE2. MASONRY ANCHOR DETAILING (SEE
DRAWING PWM-006)3. BITUTHENE MASTIC, BITUTHENE
LIQUID MEMBRANE, OR GCPAPPROVED SEALANT - 1-INCHTROWELED BEAD
4. PERM-A-BARRIER® WALL FLASHING(STAR CUT AT BOLT) - PRIMESUBSTRATE WHERE REQUIRED
5. MORTAR COLLECTION MESH6. MASONRY WEEP/VENT7. PERM-A-BARRIER® S100,
PERM-A-BARRIER® LIQUID FLASHING,BITUTHENE MASTIC, OR BITUTHENELIQUID MEMBRANE
8. CONTINUOUS SHELF ANGLESUPPORT PER STRUCTURAL
9. SHEET METAL FLASHING PER ARCH10. PERM-A-BARRIER® SELF-ADHERED
FLASHING*
3" M
IN.
OPTION 2
EXTE
RIO
R
INTE
RIO
R
SEE DETAIL OPTIONS(RIGHT)
3" M
IN.
2
5
8
6
1
7
4
7
3
10
91
4
3
3
3" = 1'
WINDOW HEAD DETAIL -MASONRY CLADDING
DRAWING: PWM-001
SCALE:
EFFECTIVE DATE: 2020.05.21
SUPERCEDES:
PERM-A-BARRIER® WALLMEMBRANE
NEW
1. PERM-A-BARRIER® WALL MEMBRANE2. MASONRY ANCHOR DETAILING (SEE
DRAWING PWM-006)3. PERM-A-BARRIER® S100,
PERM-A-BARRIER® LIQUID FLASHING,BITUTHENE MASTIC, OR BITUTHENELIQUID MEMBRANE AROUNDFASTENER IF REQUIRED
4. PERM-A-BARRIER® SELF-ADHEREDFLASHING*
5. SHEET METAL FLASHING PER ARCH6. INTERIOR AIR SEALANT OVER
BACKER ROD
6
3" MIN.
3
GENERAL NOTES
LEGEND
1. Detail not suitable for all climates. Avoiding excessive moisture accumulation in exterior walls is dependent on many factors including properplacement of insulation and water, air, and vapor control layers in the wall. Confirm membranes are suitable for project specific servicetemperatures. For assistance with exterior wall design, consult with a building science professional.
2. Install all GCP products in accordance with GCP Product Data Sheets and GCP recommendations.3. GCP products are indicated in the detail legend in BOLDFACE font. Detail components by others are indicated in GRAY FONT. Install
components per manufacturer and project specific requirements.
*Refer to air barrier system product data sheet for acceptable SELF-ADHERED FLASHING* products.
OPTION 1
EXTERIOR
INTERIORSEE DETAIL OPTIONS(RIGHT)
OPTION 2
3" MIN.
25 414 13
3" = 1'
WINDOW JAMB DETAIL -MASONRY CLADDING
DRAWING: PWM-002
SCALE:
EFFECTIVE DATE: 2020.05.21
SUPERCEDES:
PERM-A-BARRIER® WALLMEMBRANE
NEW
1. NON-FLANGED WINDOW SYSTEM2. INTERIOR AIR SEALANT OVER
BACKER ROD3. SHEET METAL FLASHING
SANDWICHED BETWEENINTERMITTENT SHIMS
4. PERM-A-BARRIER® SELF-ADHEREDFLASHING*
5. PERM-A-BARRIER® WALL MEMBRANE6. PERM-A-BARRIER® S100,
PERM-A-BARRIER® LIQUID FLASHING,BITUTHENE MASTIC, OR BITUTHENELIQUID MEMBRANE
2
3
3" M
IN.
GENERAL NOTES
LEGEND
1. Detail not suitable for all climates. Avoiding excessive moisture accumulation in exterior walls is dependent on many factors including properplacement of insulation and water, air, and vapor control layers in the wall. Confirm membranes are suitable for project specific servicetemperatures. For assistance with exterior wall design, consult with a building science professional.
2. Install all GCP products in accordance with GCP Product Data Sheets and GCP recommendations.3. GCP products are indicated in the detail legend in BOLDFACE font. Detail components by others are indicated in GRAY FONT. Install
components per manufacturer and project specific requirements.
*Refer to air barrier system product data sheet for acceptable SELF-ADHERED FLASHING* products.
GENERAL NOTES
OPTION 1
OPTION 2
EXTE
RIO
R
INTE
RIO
R
SEE DETAIL OPTIONS(RIGHT)
3" M
IN.
1
5
44
5
6
3" = 1'
WINDOW SILL DETAIL -MASONRY CLADDING
DRAWING: PWM-003
SCALE:
EFFECTIVE DATE: 2020.05.21
SUPERCEDES:
PERM-A-BARRIER® WALLMEMBRANE
NEW
1. SHEATHING SUBSTRATE2. PERM-A-BARRIER® DETAIL
MEMBRANE, NPS DETAIL MEMBRANE,ALUMINUM FLASHING, OR WALLFLASHING - PRIME SUBSTRATE WHEREREQUIRED; SEE PWM-003 (3D-2)
3. PERM-A-BARRIER® S100,PERM-A-BARRIER® LIQUID FLASHING,BITUTHENE MASTIC, OR BITUTHENELIQUID MEMBRANE - 1-INCHTROWELED BEAD
4. PERM-A-BARRIER® WALL MEMBRANE5. WINDOW PER ARCH
LEGENDSTEP 1 STEP 2
STEP 3 STEP 4
1. Detail not suitable for all climates. Avoiding excessive moisture accumulation in exterior walls is dependent on many factors including properplacement of insulation and water, air, and vapor control layers in the wall. Confirm membranes are suitable for project specific servicetemperatures. For assistance with exterior wall design, consult with a building science professional.
2. Install all GCP products in accordance with GCP Product Data Sheets and GCP recommendations.3. GCP products are indicated in the detail legend in BOLDFACE font. Detail components by others are indicated in GRAY FONT. Install
components per manufacturer and project specific requirements.
*Refer to air barrier system product data sheet for acceptable self-adhered flashing products.
GENERAL NOTES
2
3
1
4
5
4
4
· CONTINUOUS AIR AND WATER SEALAT PERIMETER OF FENESTRATION,FENESTRATION ATTACHMENT, ANDDRAINAGE OF ROUGH OPENING TOBE PER PROJECT SPECIFICREQUIREMENTS
· SEAL ALL NON-WATER SHEDDINGEDGES WITH ACCEPTABLE SEALANT
· OPTIONAL: WINDOW FLASHINGSEQUENCE CAN BE COMPLETEDAFTER FIELD APPLICATION OFPERM-A-BARRIER® WALL MEMBRANE
NOTE
3" = 1'
WINDOW FLASHING SEQUENCE -SHEET APPLIED FLASHING
DRAWING: PWM-003 (3D-1)
SCALE:
EFFECTIVE DATE: 2020.05.21
SUPERCEDES:
PERM-A-BARRIER® WALLMEMBRANE
NEW
WINDOW PRESTRIP VARIATIONS
GENERAL NOTES
LEGEND
1. Detail not suitable for all climates. Avoiding excessive moisture accumulation in exterior walls is dependent on many factors including properplacement of insulation and water, air, and vapor control layers in the wall. Confirm membranes are suitable for project specific servicetemperatures. For assistance with exterior wall design, consult with a building science professional.
2. Install all GCP products in accordance with GCP Product Data Sheets and GCP recommendations.3. GCP products are indicated in the detail legend in BOLDFACE font. Detail components by others are indicated in GRAY FONT. Install
components per manufacturer and project specific requirements.
*Refer to air barrier system product data sheet for acceptable SELF-ADHERED FLASHING* products.
3"
3"
DETAIL A
LAP BACK FLAP OFSILL CORNER PIECEO/ END DAM
CUT LINES SHOWNDASHED
FOLD LINES SHOWNSOLID
TYPICAL SILL PRESTRIPCORNER DETAILINGAT SILL BACK DAMANGLE
BACK DAM ANGLEHEIGHT PER ARCH
BACK DAM ANGLEHEIGHT PER ARCH
CORNER PATCHESINSTALLED AT TOPAND BOTTOMCORNERS OF JAMBFLASHING - CENTERPATCH AT CORNER
PRESS INTO CORNERTO CREATE TIGHTSEAL AND PREVENTPATCH FROMBRIDGING AT ALL 90DEGREE SUBSTRATEANGLE CHANGES.
DETAIL B
CORNER PATCH(SEE DETAIL A)
FOLDING TEMPLATE
V.I.F.
· WINDOW PRESTRIP PERM-A-BARRIER®
DETAIL MEMBRANE, NPS DETAILMEMBRANE, ALUMINUM FLASHING,OR WALL FLASHING
· PRIME SUBSTRATE WHERE REQUIRED
B
A
CD
A
B
C D
A. WITHOUT BACK DAM ANGLE B. WITH BACK DAM ANGLE
3"
V.I.F.
3"
3" 3"
3"
3"3"
V.I.F.
1"MIN.
3"
3"
3" 3"
3"
STEP 2
STEP 3
STEP 1
SEE DETAIL B(RIGHT)
SEE DETAIL A(RIGHT)
3"3"
V.I.F.
STEP 2
STEP 3
STEP 1
V.I.F.
3"
1"
6"
3" = 1'
SHEET-APPLIED FLASHING PRESTRIPDRAWING: PWM-003 (3D-2)
SCALE:
EFFECTIVE DATE: 2020.05.21
SUPERCEDES:
PERM-A-BARRIER® WALLMEMBRANE
NEW
1. PERM-A-BARRIER® WALL MEMBRANE2. MASONRY ANCHOR DETAILING (SEE
DRAWING PWM-006)3. BITUTHENE MASTIC, BITUTHENE
LIQUID MEMBRANE, OR GCPAPPROVED SEALANT - 1-INCHTROWELED BEAD
4. PERM-A-BARRIER® WALL FLASHING -PRIME SUBSTRATE WHERE REQUIRED
5. BELOW GRADE WATERPROOFINGSYSTEM - SEE GCPAT.COM
6. SHEET METAL FLASHING PER ARCH7. GROUT SOLID TO HEIGHT OF CURB -
SLOPE TOP8. PERM-A-BARRIER® S100,
PERM-A-BARRIER® LIQUID FLASHING,BITUTHENE MASTIC, OR BITUTHENELIQUID MEMBRANE - 1-INCHTROWELED BEAD
3" M
IN.
3" M
IN.
S
SLOPE
SEE PWM-004 (3D-1) FOR 3D DETAIL
GENERAL NOTES
LEGEND
1. Detail not suitable for all climates. Avoiding excessive moisture accumulation in exterior walls is dependent on many factors including properplacement of insulation and water, air, and vapor control layers in the wall. Confirm membranes are suitable for project specific servicetemperatures. For assistance with exterior wall design, consult with a building science professional.
2. Install all GCP products in accordance with GCP Product Data Sheets and GCP recommendations.3. GCP products are indicated in the detail legend in BOLDFACE font. Detail components by others are indicated in GRAY FONT. Install
components per manufacturer and project specific requirements.
*Refer to air barrier system product data sheet for acceptable SELF-ADHERED FLASHING* products.
SEE PWM-004 (3D-2) FOR 3D DETAIL
SEE DETAIL OPTION(RIGHT)
EXTE
RIO
R
INTE
RIO
R
OPTION 2
OPTION 1
2
6
7
1
3
4
3
4
5
1
8
4
4
5
8
3" M
IN.
3" M
IN.
3" = 1'
BASE OF WALL DETAIL -MASONRY CLADDING
DRAWING: PWM-004
SCALE:
EFFECTIVE DATE: 2020.05.21
SUPERCEDES:
PERM-A-BARRIER® WALLMEMBRANE
NEW
1. PERM-A-BARRIER® WALL MEMBRANE2. MASONRY ANCHOR DETAILING (SEE
DRAWING PWM-006)3. BITUTHENE MASTIC, BITUTHENE
LIQUID MEMBRANE, OR GCPAPPROVED SEALANT - 1-INCHTROWELED BEAD
4. PERM-A-BARRIER® WALL FLASHING -PRIME SUBSTRATE WHERE REQUIRED
5. SHEET METAL FLASHING PER ARCH6. GROUT SOLID TO HEIGHT OF CURB -
SLOPE TOP7. BELOW GRADE WATERPROOFING
SYSTEM - SEE GCPAT.COM8. MASONRY WEEP/VENT
SEE PWM-004 (OPTION 1) FOR 2D DETAIL
GENERAL NOTES
LEGEND
1. Detail not suitable for all climates. Avoiding excessive moisture accumulation in exterior walls is dependent on many factors including properplacement of insulation and water, air, and vapor control layers in the wall. Confirm membranes are suitable for project specific servicetemperatures. For assistance with exterior wall design, consult with a building science professional.
2. Install all GCP products in accordance with GCP Product Data Sheets and GCP recommendations.3. GCP products are indicated in the detail legend in BOLDFACE font. Detail components by others are indicated in GRAY FONT. Install
components per manufacturer and project specific requirements.
*Refer to air barrier system product data sheet for acceptable SELF-ADHERED FLASHING* products.
652 743 418
3" = 1'
BASE OF WALL FLASHING SEQUENCE (OPTION 1) -MASONRY CLADDING
DRAWING: PWM-004 (3D-1)
SCALE:
EFFECTIVE DATE: 2020.05.21
SUPERCEDES:
PERM-A-BARRIER® WALLMEMBRANE
NEW
1. PERM-A-BARRIER® WALL MEMBRANE2. MASONRY ANCHOR DETAILING (SEE
DRAWING PWM-006)3. PERM-A-BARRIER® S100,
PERM-A-BARRIER® LIQUID FLASHING,BITUTHENE MASTIC, OR BITUTHENELIQUID MEMBRANE - 1-INCHTROWELED BEAD
4. PERM-A-BARRIER® WALL FLASHING -PRIME SUBSTRATE WHERE REQUIRED
5. SHEET METAL FLASHING PER ARCH6. GROUT SOLID TO HEIGHT OF CURB -
SLOPE TOP7. BELOW GRADE WATERPROOFING
SYSTEM - SEE GCPAT.COM8. MASONRY WEEP/VENT
SEE PWM-004 (OPTION 2) FOR 2D DETAIL
GENERAL NOTES
LEGEND
1. Detail not suitable for all climates. Avoiding excessive moisture accumulation in exterior walls is dependent on many factors including properplacement of insulation and water, air, and vapor control layers in the wall. Confirm membranes are suitable for project specific servicetemperatures. For assistance with exterior wall design, consult with a building science professional.
2. Install all GCP products in accordance with GCP Product Data Sheets and GCP recommendations.3. GCP products are indicated in the detail legend in BOLDFACE font. Detail components by others are indicated in GRAY FONT. Install
components per manufacturer and project specific requirements.
*Refer to air barrier system product data sheet for acceptable SELF-ADHERED FLASHING* products.
65 3 74 43 12 8
3" = 1'
BASE OF WALL FLASHING SEQUENCE (OPTION 2) -MASONRY CLADDING
DRAWING: PWM-004 (3D-2)
SCALE:
EFFECTIVE DATE: 2020.05.21
SUPERCEDES:
PERM-A-BARRIER® WALLMEMBRANE
NEW
1. PERM-A-BARRIER® WALL MEMBRANE2. MASONRY ANCHOR DETAILING (SEE
DRAWING PWM-006)3. BITUTHENE MASTIC, BITUTHENE
LIQUID MEMBRANE, OR GCPAPPROVED SEALANT - 1-INCHTROWELED BEAD
4. PERM-A-BARRIER® WALL FLASHING5. SHEET METAL FLASHING PER ARCH
SLOPE
GENERAL NOTES
LEGEND
1. Detail not suitable for all climates. Avoiding excessive moisture accumulation in exterior walls is dependent on many factors including properplacement of insulation and water, air, and vapor control layers in the wall. Confirm membranes are suitable for project specific servicetemperatures. For assistance with exterior wall design, consult with a building science professional.
2. Install all GCP products in accordance with GCP Product Data Sheets and GCP recommendations.3. GCP products are indicated in the detail legend in BOLDFACE font. Detail components by others are indicated in GRAY FONT. Install
components per manufacturer and project specific requirements.
*Refer to air barrier system product data sheet for acceptable SELF-ADHERED FLASHING* products.
EXTE
RIO
R
INTE
RIO
R1'
-0"
6"
3"
2
5
1
3
4
3" = 1'
BASE OF WALL DETAIL (ALTERNATE 1) -MASONRY CLADDING
DRAWING: PWM-004 (ALT 1)
SCALE:
EFFECTIVE DATE: 2020.05.21
SUPERCEDES:
PERM-A-BARRIER® WALLMEMBRANE
NEW
1. PERM-A-BARRIER® WALL MEMBRANE2. MASONRY ANCHOR DETAILING (SEE
DRAWING PWM-006)3. BITUTHENE MASTIC, BITUTHENE
LIQUID MEMBRANE, OR GCPAPPROVED SEALANT - 1-INCHTROWELED BEAD
4. PERM-A-BARRIER® WALL FLASHING5. SHEET METAL FLASHING PER ARCH
SLOPE
GENERAL NOTES
LEGEND
1. Detail not suitable for all climates. Avoiding excessive moisture accumulation in exterior walls is dependent on many factors including properplacement of insulation and water, air, and vapor control layers in the wall. Confirm membranes are suitable for project specific servicetemperatures. For assistance with exterior wall design, consult with a building science professional.
2. Install all GCP products in accordance with GCP Product Data Sheets and GCP recommendations.3. GCP products are indicated in the detail legend in BOLDFACE font. Detail components by others are indicated in GRAY FONT. Install
components per manufacturer and project specific requirements.
*Refer to air barrier system product data sheet for acceptable SELF-ADHERED FLASHING* products.
EXTE
RIO
R
INTE
RIO
R1'
-0"
6"
3"
2
5
1
3
4
NOTE· CONSULT GCP FOR BELOW GRADE
WATERPROOFING COMPATIBILITYAND CONNECTION
3" = 1'
BASE OF WALL DETAIL (ALTERNATE 2) -MASONRY CLADDING
DRAWING: PWM-004 (ALT 2)
SCALE:
EFFECTIVE DATE: 2020.05.21
SUPERCEDES:
PERM-A-BARRIER® WALLMEMBRANE
NEW
1. PERM-A-BARRIER® WALL MEMBRANE2. MASONRY ANCHOR DETAILING (SEE
DRAWING PWM-006)3. BITUTHENE MASTIC, BITUTHENE LIQUID
MEMBRANE, OR GCP APPROVEDSEALANT - 1-INCH TROWELED BEAD
4. MORTAR COLLECTION MESH5. PERM-A-BARRIER® WALL FLASHING
(STAR CUT AT BOLT), PRIME SUBSTRATEWHERE REQUIRED
6. CONTINUOUS SHELF ANGLE SUPPORTPER STRUCTURAL
7. SHEET METAL FLASHING PER ARCH8. PERM-A-BARRIER® S100,
PERM-A-BARRIER® LIQUID FLASHING,BITUTHENE MASTIC, OR BITUTHENELIQUID MEMBRANE
3" M
IN.
84" MIN.
GENERAL NOTES
LEGEND
1. Detail not suitable for all climates. Avoiding excessive moisture accumulation in exterior walls is dependent on many factors including properplacement of insulation and water, air, and vapor control layers in the wall. Confirm membranes are suitable for project specific servicetemperatures. For assistance with exterior wall design, consult with a building science professional.
2. Install all GCP products in accordance with GCP Product Data Sheets and GCP recommendations.3. GCP products are indicated in the detail legend in BOLDFACE font. Detail components by others are indicated in GRAY FONT. Install
components per manufacturer and project specific requirements.
*Refer to air barrier system product data sheet for acceptable SELF-ADHERED FLASHING* products.
EXTE
RIO
R
INTE
RIO
R
3" M
IN.
SEE PWM-005 (3D-1) FOR 3D DETAIL
OPTION 1
SEE PWM-005 (3D-2) FOR 3D DETAIL
OPTION 2
4
2
6
7
5
1
3
1
5
1
8
8
3" = 1'
FLOOR LINE DETAIL -MASONRY CLADDING
DRAWING: PWM-005
SCALE:
EFFECTIVE DATE: 2020.05.21
SUPERCEDES:
PERM-A-BARRIER® WALLMEMBRANE
NEW
1. PERM-A-BARRIER® WALL MEMBRANE2. MASONRY ANCHOR DETAILING (SEE
DRAWING PWM-006)3. BITUTHENE MASTIC, BITUTHENE
LIQUID MEMBRANE, OR GCPAPPROVED SEALANT - 1-INCHTROWELED BEAD
4. MORTAR COLLECTION MESH5. PERM-A-BARRIER® WALL FLASHING,
PRIME SUBSTRATE WHERE REQUIRED6. CONTINUOUS SHELF ANGLE
SUPPORT PER STRUCTURAL7. SHEET METAL FLASHING PER ARCH8. PERM-A-BARRIER® S100,
PERM-A-BARRIER® LIQUID FLASHING,BITUTHENE MASTIC, OR BITUTHENELIQUID MEMBRANE
GENERAL NOTES
LEGEND
1. Detail not suitable for all climates. Avoiding excessive moisture accumulation in exterior walls is dependent on many factors including properplacement of insulation and water, air, and vapor control layers in the wall. Confirm membranes are suitable for project specific servicetemperatures. For assistance with exterior wall design, consult with a building science professional.
2. Install all GCP products in accordance with GCP Product Data Sheets and GCP recommendations.3. GCP products are indicated in the detail legend in BOLDFACE font. Detail components by others are indicated in GRAY FONT. Install
components per manufacturer and project specific requirements.
*Refer to air barrier system product data sheet for acceptable SELF-ADHERED FLASHING* products.
SEE PWM-005 (OPTION 1) FOR 2D DETAIL
7 62 4
81
3 51
3" = 1'
FLOOR LINE FLASHING SEQUENCE (OPT. 1) -MASONRY CLADDING
DRAWING: PWM-005 (3D-1)
SCALE:
EFFECTIVE DATE: 2020.05.21
SUPERCEDES:
PERM-A-BARRIER® WALLMEMBRANE
NEW
1. PERM-A-BARRIER® WALL MEMBRANE2. MASONRY ANCHOR DETAILING (SEE
DRAWING PWM-006)3. PERM-A-BARRIER® S100,
PERM-A-BARRIER® LIQUID FLASHING,BITUTHENE MASTIC, OR BITUTHENELIQUID MEMBRANE - 1-INCHTROWELED BEAD
4. MORTAR COLLECTION MESH5. PERM-A-BARRIER® WALL FLASHING,
PRIME SUBSTRATE WHERE REQUIRED6. CONTINUOUS SHELF ANGLE
SUPPORT PER STRUCTURAL7. SHEET METAL FLASHING PER ARCH
GENERAL NOTES
LEGEND
1. Detail not suitable for all climates. Avoiding excessive moisture accumulation in exterior walls is dependent on many factors including properplacement of insulation and water, air, and vapor control layers in the wall. Confirm membranes are suitable for project specific servicetemperatures. For assistance with exterior wall design, consult with a building science professional.
2. Install all GCP products in accordance with GCP Product Data Sheets and GCP recommendations.3. GCP products are indicated in the detail legend in BOLDFACE font. Detail components by others are indicated in GRAY FONT. Install
components per manufacturer and project specific requirements.
*Refer to air barrier system product data sheet for acceptable SELF-ADHERED FLASHING* products.
SEE PWM-005 (OPTION 2) FOR 2D DETAIL
7 62 4
31
35 1
3" = 1'
FLOOR LINE FLASHING SEQUENCE (OPT. 2) -MASONRY CLADDING
DRAWING: PWM-005 (3D-2)
SCALE:
EFFECTIVE DATE: 2020.05.21
SUPERCEDES:
PERM-A-BARRIER® WALLMEMBRANE
NEW
GENERAL NOTES
LEGEND
1. Detail not suitable for all climates. Avoiding excessive moisture accumulation in exterior walls is dependent on many factors including properplacement of insulation and water, air, and vapor control layers in the wall. Confirm membranes are suitable for project specific servicetemperatures. For assistance with exterior wall design, consult with a building science professional.
2. Install all GCP products in accordance with GCP Product Data Sheets and GCP recommendations.3. GCP products are indicated in the detail legend in BOLDFACE font. Detail components by others are indicated in GRAY FONT. Install
components per manufacturer and project specific requirements.
*Refer to air barrier system product data sheet for acceptable SELF-ADHERED FLASHING* products.
1. PERM-A-BARRIER® WALL MEMBRANE2. PERM-A-BARRIER® S100,
PERM-A-BARRIER® LIQUID FLASHING,BITUTHENE MASTIC, OR BITUTHENELIQUID MEMBRANE FILLETSURROUNDING WIRE TIE PENETRATION
2
1
PERSPECTIVE VIEW
SECTION VIEW
NOTE· ALL CMU JOINTS TO BE STRUCK FULL
AND FLUSH
3" = 1'
MASONRY ANCHOR DETAIL -CMU SUBSTRATE
DRAWING: PWM-006A
SCALE:
EFFECTIVE DATE: 2020.05.21
SUPERCEDES:
PERM-A-BARRIER® WALLMEMBRANE
NEW
GENERAL NOTES
LEGEND
1. Detail not suitable for all climates. Avoiding excessive moisture accumulation in exterior walls is dependent on many factors including properplacement of insulation and water, air, and vapor control layers in the wall. Confirm membranes are suitable for project specific servicetemperatures. For assistance with exterior wall design, consult with a building science professional.
2. Install all GCP products in accordance with GCP Product Data Sheets and GCP recommendations.3. GCP products are indicated in the detail legend in BOLDFACE font. Detail components by others are indicated in GRAY FONT. Install
components per manufacturer and project specific requirements.
*Refer to air barrier system product data sheet for acceptable SELF-ADHERED FLASHING* products.
1. PERM-A-BARRIER® WALL MEMBRANE2. PERM-A-BARRIER® S100,
PERM-A-BARRIER® LIQUID FLASHING,BITUTHENE MASTIC, OR BITUTHENELIQUID MEMBRANE AROUNDFASTENER AT FRONT AND BACK FACEOF MASONRY ANCHOR
2
1
PERSPECTIVE VIEW
SECTION VIEW
12
3" = 1'
MASONRY ANCHOR DETAIL -FRAMED SUBSTRATE
DRAWING: PWM-006B
SCALE:
EFFECTIVE DATE: 2020.05.21
SUPERCEDES:
PERM-A-BARRIER® WALLMEMBRANE
NEW
1. PERM-A-BARRIER® WALL MEMBRANE2. ROOF MEMBRANE AND ROOF
DETAILS3. SEE CONTROL JOINT DETAIL
PWM-0094. MASONRY WEEP/VENT
4" M
IN.
· CONSULT GCP & ROOFINGMANUFACTURER FORCOMPATIBILITY AND CONNECTIONAT ROOF INTERFACE
GENERAL NOTES
LEGEND
1. Detail not suitable for all climates. Avoiding excessive moisture accumulation in exterior walls is dependent on many factors including properplacement of insulation and water, air, and vapor control layers in the wall. Confirm membranes are suitable for project specific servicetemperatures. For assistance with exterior wall design, consult with a building science professional.
2. Install all GCP products in accordance with GCP Product Data Sheets and GCP recommendations.3. GCP products are indicated in the detail legend in BOLDFACE font. Detail components by others are indicated in GRAY FONT. Install
components per manufacturer and project specific requirements.
*Refer to air barrier system product data sheet for acceptable SELF-ADHERED FLASHING* products.
EXTE
RIO
R
INTE
RIO
R
NOTE
2
4
3
1
3" = 1'
PARAPET DETAIL -MASONRY CLADDING
DRAWING: PWM-007
SCALE:
EFFECTIVE DATE: 2020.05.21
SUPERCEDES:
PERM-A-BARRIER® WALLMEMBRANE
NEW
GENERAL NOTES
LEGEND
1. Detail not suitable for all climates. Avoiding excessive moisture accumulation in exterior walls is dependent on many factors including properplacement of insulation and water, air, and vapor control layers in the wall. Confirm membranes are suitable for project specific servicetemperatures. For assistance with exterior wall design, consult with a building science professional.
2. Install all GCP products in accordance with GCP Product Data Sheets and GCP recommendations.3. GCP products are indicated in the detail legend in BOLDFACE font. Detail components by others are indicated in GRAY FONT. Install
components per manufacturer and project specific requirements.
*Refer to air barrier system product data sheet for acceptable SELF-ADHERED FLASHING* products.
INTERIOR
EXTERIORPLAN VIEW
PERSPECTIVE VIEW
1. COMPRESSIBLE JOINT FILLER -MAXIMUM 4-INCH WIDE JOINTCAPABLE OF A MAXIMUM 50%MOVEMENT IN COMPRESSION ANDELONGATION
2. PERM-A-BARRIER® SELF-ADHEREDFLASHING*
3. PERM-A-BARRIER® S100,PERM-A-BARRIER® LIQUID FLASHING,BITUTHENE MASTIC, OR BITUTHENELIQUID MEMBRANE - 1-INCHTROWELED BEAD
4. PERM-A-BARRIER® WALL MEMBRANE5. PERM-A-BARRIER® SELF-ADHERED
FLASHING* INVERTED STRIP
NOTE· WIDTH OF THE INVERTED STRIP SHALL
BE TWICE THE WIDTH OF THEEXPANSION JOINT TOACCOMMODATE MOVEMENT - ALLSEAMS, OVERLAPS, JOINTS, ANDEDGES SEALED WITH S100
· MAXIMUM 4 INCH WIDE JOINTCAPABLE OF A MAXIMUM 50%MOVEMENT IN COMPRESSION ANDELONGATION
· CLADDING AND CLOSURE BYOTHERS NOT SHOWN FOR CLARITY
1
1
5
2
3
4
5 42 3
3" = 1'
EXPANSION JOINT DETAIL -MASONRY CLADDING
DRAWING: PWM-008
SCALE:
EFFECTIVE DATE: 2020.05.21
SUPERCEDES:
PERM-A-BARRIER® WALLMEMBRANE
NEW
1. BACKER ROD AND COMPATIBLESEALANT
2. PERM-A-BARRIER® WALL MEMBRANE
· MAX 1/2-INCH JOINT CAPABLE OFMAXIMUM 10% MOVEMENT INCOMPRESSION AND ELONGATION
GENERAL NOTES
LEGEND
1. Detail not suitable for all climates. Avoiding excessive moisture accumulation in exterior walls is dependent on many factors including properplacement of insulation and water, air, and vapor control layers in the wall. Confirm membranes are suitable for project specific servicetemperatures. For assistance with exterior wall design, consult with a building science professional.
2. Install all GCP products in accordance with GCP Product Data Sheets and GCP recommendations.3. GCP products are indicated in the detail legend in BOLDFACE font. Detail components by others are indicated in GRAY FONT. Install
components per manufacturer and project specific requirements.
*Refer to air barrier system product data sheet for acceptable SELF-ADHERED FLASHING* products.
NOTE
PLAN VIEW
PERSPECTIVE VIEW
1 2
1
2
3" = 1'
CONTROL JOINT DETAIL -MASONRY CLADDING
DRAWING: PWM-009
SCALE:
EFFECTIVE DATE: 2020.05.21
SUPERCEDES:
PERM-A-BARRIER® WALLMEMBRANE
NEW
1. PERM-A-BARRIER® WALLMEMBRANE
2. CLADDING ATTACHMENT -CONFIRM DETAILINGREQUIREMENTS WITH THEGCPAT REPRESENTATIVE
3. BITUTHENE MASTIC, BITUTHENELIQUID MEMBRANE, OR GCPAPPROVED SEALANT - 1-INCHTROWELED BEAD
4. PERM-A-BARRIER®
SELF-ADHERED FLASHING*5. SHEET METAL FLASHING PER
ARCH6. PERM-A-BARRIER® S100,
PERM-A-BARRIER® LIQUIDFLASHING, BITUTHENE MASTIC,OR BITUTHENE LIQUIDMEMBRANE - 1-INCHTROWELED BEAD
3" M
IN.
GENERAL NOTES
LEGEND
1. Detail not suitable for all climates. Avoiding excessive moisture accumulation in exterior walls is dependent on many factors including properplacement of insulation and water, air, and vapor control layers in the wall. Confirm membranes are suitable for project specific servicetemperatures. For assistance with exterior wall design, consult with a building science professional.
2. Install all GCP products in accordance with GCP Product Data Sheets and GCP recommendations.3. GCP products are indicated in the detail legend in BOLDFACE font. Detail components by others are indicated in GRAY FONT. Install
components per manufacturer and project specific requirements.
*Refer to air barrier system product data sheet for acceptable SELF-ADHERED FLASHING* products.
OPTION 1
OPTION 2
EXTE
RIO
R
INTE
RIO
R
SEE DETAIL OPTIONS(RIGHT)
2
1
3
4
5
6
4
5
4
3
3" = 1'
WINDOW HEAD DETAIL -NON-MASONRY CLADDING
DRAWING: PWM-010
SCALE:
EFFECTIVE DATE: 2020.05.21
SUPERCEDES:
PERM-A-BARRIER® WALLMEMBRANE
NEW
1. PERM-A-BARRIER® WALLMEMBRANE
2. CLADDING ATTACHMENT -CONFIRM DETAILINGREQUIREMENTS WITH THEGCPAT REPRESENTATIVE
3. PERM-A-BARRIER®
SELF-ADHERED FLASHING*4. SHEET METAL FLASHING PER
ARCH5. INTERIOR AIR SEALANT OVER
BACKER ROD
5
3" MIN.
GENERAL NOTES
LEGEND
1. Detail not suitable for all climates. Avoiding excessive moisture accumulation in exterior walls is dependent on many factors including properplacement of insulation and water, air, and vapor control layers in the wall. Confirm membranes are suitable for project specific servicetemperatures. For assistance with exterior wall design, consult with a building science professional.
2. Install all GCP products in accordance with GCP Product Data Sheets and GCP recommendations.3. GCP products are indicated in the detail legend in BOLDFACE font. Detail components by others are indicated in GRAY FONT. Install
components per manufacturer and project specific requirements.
*Refer to air barrier system product data sheet for acceptable SELF-ADHERED FLASHING* products.
OPTION 2
SEE DETAIL OPTIONS(RIGHT)
OPTION 1
EXTERIOR
INTERIOR
3" MIN.
24 413 13
3" = 1'
WINDOW JAMB DETAIL -NON-MASONRY CLADDING
DRAWING: PWM-011
SCALE:
EFFECTIVE DATE: 2020.05.21
SUPERCEDES:
PERM-A-BARRIER® WALLMEMBRANE
NEW
1. NON-FLANGED WINDOWSYSTEM
2. INTERIOR AIR SEALANT OVERBACKER ROD
3. SHEET METAL FLASHINGSANDWICHED BETWEENINTERMITTENT SHIMS
4. PERM-A-BARRIER® S100,PERM-A-BARRIER® LIQUIDFLASHING, BITUTHENE MASTIC,OR BITUTHENE LIQUIDMEMBRANE - 1-INCHTROWELED BEAD
5. PERM-A-BARRIER®
SELF-ADHERED FLASHING*6. PERM-A-BARRIER® WALL
MEMBRANE7. CLADDING ATTACHMENT -
CONFIRM DETAILINGREQUIREMENTS WITH THEGCPAT REPRESENTATIVE
2
3
3" M
IN.
GENERAL NOTES
LEGEND
1. Detail not suitable for all climates. Avoiding excessive moisture accumulation in exterior walls is dependent on many factors including properplacement of insulation and water, air, and vapor control layers in the wall. Confirm membranes are suitable for project specific servicetemperatures. For assistance with exterior wall design, consult with a building science professional.
2. Install all GCP products in accordance with GCP Product Data Sheets and GCP recommendations.3. GCP products are indicated in the detail legend in BOLDFACE font. Detail components by others are indicated in GRAY FONT. Install
components per manufacturer and project specific requirements.
*Refer to air barrier system product data sheet for acceptable SELF-ADHERED FLASHING* products.
OPTION 1
EXTE
RIO
R
INTE
RIO
R
OPTION 2
SEE DETAIL OPTIONS(RIGHT)
3" M
IN.
1
7
5
4
5
6
6
3" = 1'
WINDOW SILL DETAIL -NON-MASONRY CLADDING
DRAWING: PWM-012
SCALE:
EFFECTIVE DATE: 2020.05.21
SUPERCEDES:
PERM-A-BARRIER® WALLMEMBRANE
NEW
1. PERM-A-BARRIER® WALLMEMBRANE
2. CLADDING ATTACHMENT -CONFIRM DETAILINGREQUIREMENTS WITH THEGCPAT REPRESENTATIVE
3. BITUTHENE MASTIC, BITUTHENELIQUID MEMBRANE, OR GCPAPPROVED SEALANT - 1-INCHTROWELED BEAD
4. PERM-A-BARRIER®
SELF-ADHERED FLASHING*5. SHEET METAL FLASHING PER
ARCH3"
MIN
.
GENERAL NOTES
LEGEND
1. Detail not suitable for all climates. Avoiding excessive moisture accumulation in exterior walls is dependent on many factors including properplacement of insulation and water, air, and vapor control layers in the wall. Confirm membranes are suitable for project specific servicetemperatures. For assistance with exterior wall design, consult with a building science professional.
2. Install all GCP products in accordance with GCP Product Data Sheets and GCP recommendations.3. GCP products are indicated in the detail legend in BOLDFACE font. Detail components by others are indicated in GRAY FONT. Install
components per manufacturer and project specific requirements.
*Refer to air barrier system product data sheet for acceptable SELF-ADHERED FLASHING* products.
EXTE
RIO
R
INTE
RIO
R
3" M
IN.
3" M
IN.
2
5
4
1
3
1
DRAWING: PWM-013
SCALE:
EFFECTIVE DATE: 2020.05.21
SUPERCEDES:
PERM-A-BARRIER® WALLMEMBRANE
NEW
3" = 1'
FLOOR LINE DETAIL -NON-MASONRY CLADDING
1. PERM-A-BARRIER® WALLMEMBRANE
2. CLADDING ATTACHMENT -CONFIRM DETAILINGREQUIREMENTS WITH THEGCPAT REPRESENTATIVE
3. BITUTHENE MASTIC, BITUTHENELIQUID MEMBRANE, OR GCPAPPROVED SEALANT - 1-INCHTROWELED BEAD
4. PERM-A-BARRIER®
SELF-ADHERED FLASHING*5. TWO-PIECE SHEET METAL
FLASHING PER ARCH3"
MIN
.3"
MIN
.
· CONFIRM MAXIMUM SERVICETEMPERATURE OF PERM-A-BARRIERPRODUCTS DIRECTLY UNDEREXPOSED METAL FLASHING
3" M
IN.
GENERAL NOTES
LEGEND
1. Detail not suitable for all climates. Avoiding excessive moisture accumulation in exterior walls is dependent on many factors including properplacement of insulation and water, air, and vapor control layers in the wall. Confirm membranes are suitable for project specific servicetemperatures. For assistance with exterior wall design, consult with a building science professional.
2. Install all GCP products in accordance with GCP Product Data Sheets and GCP recommendations.3. GCP products are indicated in the detail legend in BOLDFACE font. Detail components by others are indicated in GRAY FONT. Install
components per manufacturer and project specific requirements.
*Refer to air barrier system product data sheet for acceptable SELF-ADHERED FLASHING* products.
NOTE
EXTE
RIO
R
INTE
RIO
R
2
1
3
4
5
3" = 1'
CONCRETE STEM WALL DETAIL -NON-MASONRY CLADDING
DRAWING: PWM-014
SCALE:
EFFECTIVE DATE: 2020.05.21
SUPERCEDES:
PERM-A-BARRIER® WALLMEMBRANE
NEW
1. PERM-A-BARRIER® WALLMEMBRANE
2. CLADDING ATTACHMENT -CONFIRM DETAILINGREQUIREMENTS WITH THEGCPAT REPRESENTATIVE
3. BITUTHENE MASTIC, BITUTHENELIQUID MEMBRANE, OR GCPAPPROVED SEALANT - 1-INCHTROWELED BEAD
4. PERM-A-BARRIER®
SELF-ADHERED FLASHING*5. TWO-PIECE SHEET METAL
FLASHING PER ARCH6. BELOW GRADE
WATERPROOFING SYSTEM - SEEGCPAT.COM3"
MIN
.3"
MIN
.
GENERAL NOTES
LEGEND
1. Detail not suitable for all climates. Avoiding excessive moisture accumulation in exterior walls is dependent on many factors including properplacement of insulation and water, air, and vapor control layers in the wall. Confirm membranes are suitable for project specific servicetemperatures. For assistance with exterior wall design, consult with a building science professional.
2. Install all GCP products in accordance with GCP Product Data Sheets and GCP recommendations.3. GCP products are indicated in the detail legend in BOLDFACE font. Detail components by others are indicated in GRAY FONT. Install
components per manufacturer and project specific requirements.
*Refer to air barrier system product data sheet for acceptable SELF-ADHERED FLASHING* products.
EXTE
RIO
R
INTE
RIO
R
2
5
1
3
4
6
3" = 1'
BASE-OF-WALL AT GRADE DETAIL -NON-MASONRY CLADDING
DRAWING: PWM-015
SCALE:
EFFECTIVE DATE: 2020.05.21
SUPERCEDES:
PERM-A-BARRIER® WALLMEMBRANE
NEW
1. PERM-A-BARRIER® WALLMEMBRANE
2. CLADDING ATTACHMENT -CONFIRM DETAILINGREQUIREMENTS WITH THEGCPAT REPRESENTATIVE
3. BITUTHENE MASTIC, BITUTHENELIQUID MEMBRANE, OR GCPAPPROVED SEALANT - 1-INCHTROWELED BEAD
4. PERM-A-BARRIER®
SELF-ADHERED FLASHING*5. SHEET METAL FLASHING PER
ARCH6. TERMINATION PER HORIZONTAL
WATERPROOFING SYSTEMMANUFACTURER
7. HORIZONTAL WATERPROOFINGSYSTEM - SEE GCPAT.COM
6
3" M
IN.
GENERAL NOTES
LEGEND
1. Detail not suitable for all climates. Avoiding excessive moisture accumulation in exterior walls is dependent on many factors including properplacement of insulation and water, air, and vapor control layers in the wall. Confirm membranes are suitable for project specific servicetemperatures. For assistance with exterior wall design, consult with a building science professional.
2. Install all GCP products in accordance with GCP Product Data Sheets and GCP recommendations.3. GCP products are indicated in the detail legend in BOLDFACE font. Detail components by others are indicated in GRAY FONT. Install
components per manufacturer and project specific requirements.
*Refer to air barrier system product data sheet for acceptable SELF-ADHERED FLASHING* products.
EXTE
RIO
R
INTE
RIO
R
2
1
3
4
5
7 NOTE· CONSULT GCP FOR HORIZONTAL
WATERPROOFING COMPATIBILITYAND CONNECTION
3" = 1'
BASE-OF-WALL DETAIL -NON-MASONRY CLADDING
DRAWING: PWM-016
SCALE:
EFFECTIVE DATE: 2020.05.21
SUPERCEDES:
PERM-A-BARRIER® WALLMEMBRANE
NEW
1. PERM-A-BARRIER®
SELF-ADHERED FLASHING*.PRIME SUBSTRATE WHEREREQUIRED
2. PERM-A-BARRIER® WALLMEMBRANE
3. CLADDING ATTACHMENT -DETAIL PER GCPATREQUIREMENTS
2" M
IN.
3" M
IN.
GENERAL NOTES
LEGEND
1. Detail not suitable for all climates. Avoiding excessive moisture accumulation in exterior walls is dependent on many factors including properplacement of insulation and water, air, and vapor control layers in the wall. Confirm membranes are suitable for project specific servicetemperatures. For assistance with exterior wall design, consult with a building science professional.
2. Install all GCP products in accordance with GCP Product Data Sheets and GCP recommendations.3. GCP products are indicated in the detail legend in BOLDFACE font. Detail components by others are indicated in GRAY FONT. Install
components per manufacturer and project specific requirements.
*Refer to air barrier system product data sheet for acceptable SELF-ADHERED FLASHING* products.
EXTE
RIO
R
INTE
RIO
R
31 2
3" = 1'
INSIDE CORNER DETAIL -NON-MASONRY CLADDING
DRAWING: PWM-017
SCALE:
EFFECTIVE DATE: 2020.05.21
SUPERCEDES:
PERM-A-BARRIER® WALLMEMBRANE
NEW
1. PERM-A-BARRIER® WALLMEMBRANE
2. CLADDING ATTACHMENT -DETAIL PER GCPATREQUIREMENTS
2" M
IN.
GENERAL NOTES
LEGEND
1. Detail not suitable for all climates. Avoiding excessive moisture accumulation in exterior walls is dependent on many factors including properplacement of insulation and water, air, and vapor control layers in the wall. Confirm membranes are suitable for project specific servicetemperatures. For assistance with exterior wall design, consult with a building science professional.
2. Install all GCP products in accordance with GCP Product Data Sheets and GCP recommendations.3. GCP products are indicated in the detail legend in BOLDFACE font. Detail components by others are indicated in GRAY FONT. Install
components per manufacturer and project specific requirements.
*Refer to air barrier system product data sheet for acceptable SELF-ADHERED FLASHING* products.
EXTE
RIO
R
INTE
RIO
R
21
3" = 1'
INSIDE CORNER DETAIL (ALTERNATE) -NON-MASONRY CLADDING
DRAWING: PWM-017 (ALT)
SCALE:
EFFECTIVE DATE: 2020.05.21
SUPERCEDES:
PERM-A-BARRIER® WALLMEMBRANE
NEW
1. PERM-A-BARRIER® DETAILMEMBRANE, NPS DETAILMEMBRANE, ALUMINUMFLASHING, OR WALL FLASHING.PRIME SUBSTRATE WHEREREQUIRED
2. PERM-A-BARRIER® WALLMEMBRANE
3. CLADDING ATTACHMENT -DETAIL PER GCPATREQUIREMENTS
3" M
IN.
2" MIN.
GENERAL NOTES
LEGEND
1. Detail not suitable for all climates. Avoiding excessive moisture accumulation in exterior walls is dependent on many factors including properplacement of insulation and water, air, and vapor control layers in the wall. Confirm membranes are suitable for project specific servicetemperatures. For assistance with exterior wall design, consult with a building science professional.
2. Install all GCP products in accordance with GCP Product Data Sheets and GCP recommendations.3. GCP products are indicated in the detail legend in BOLDFACE font. Detail components by others are indicated in GRAY FONT. Install
components per manufacturer and project specific requirements.
*Refer to air barrier system product data sheet for acceptable SELF-ADHERED FLASHING* products.
EXTE
RIO
R
INTE
RIO
R
32 1
3" = 1'
OUTSIDE CORNER DETAIL -NON-MASONRY CLADDING
DRAWING: PWM-018
SCALE:
EFFECTIVE DATE: 2020.05.21
SUPERCEDES:
PERM-A-BARRIER® WALLMEMBRANE
NEW
1. PERM-A-BARRIER® WALLMEMBRANE
2. CLADDING ATTACHMENT -DETAIL PER GCPATREQUIREMENTS
2" MIN.
GENERAL NOTES
LEGEND
1. Detail not suitable for all climates. Avoiding excessive moisture accumulation in exterior walls is dependent on many factors including properplacement of insulation and water, air, and vapor control layers in the wall. Confirm membranes are suitable for project specific servicetemperatures. For assistance with exterior wall design, consult with a building science professional.
2. Install all GCP products in accordance with GCP Product Data Sheets and GCP recommendations.3. GCP products are indicated in the detail legend in BOLDFACE font. Detail components by others are indicated in GRAY FONT. Install
components per manufacturer and project specific requirements.
*Refer to air barrier system product data sheet for acceptable SELF-ADHERED FLASHING* products.
EXTE
RIO
R
INTE
RIO
R
21
3" = 1'
OUTSIDE CORNER DETAIL (ALTERNATE) -NON-MASONRY CLADDING
DRAWING: PWM-018 (ALT)
SCALE:
EFFECTIVE DATE: 2020.05.21
SUPERCEDES:
PERM-A-BARRIER® WALLMEMBRANE
NEW
1. PERM-A-BARRIER® WALLMEMBRANE
2. CLADDING ATTACHMENT -CONFIRM DETAILINGREQUIREMENTS WITH THE GCPATREPRESENTATIVE
3. PERM-A-BARRIER® S100,PERM-A-BARRIER® LIQUIDFLASHING, BITUTHENE MASTIC,OR BITUTHENE LIQUID MEMBRANE- FLASHING AND CANT SEAL
4. KNIFE PLATE PENETRATION5. POLYURETHANE SEALANT OR
NON-SHRINK GROUT PERBACKUP WALL TYPE
6. JOINT TREATMENT PER DETAILPWM-009
GENERAL NOTES
LEGEND
1. Detail not suitable for all climates. Avoiding excessive moisture accumulation in exterior walls is dependent on many factors including properplacement of insulation and water, air, and vapor control layers in the wall. Confirm membranes are suitable for project specific servicetemperatures. For assistance with exterior wall design, consult with a building science professional.
2. Install all GCP products in accordance with GCP Product Data Sheets and GCP recommendations.3. GCP products are indicated in the detail legend in BOLDFACE font. Detail components by others are indicated in GRAY FONT. Install
components per manufacturer and project specific requirements.
*Refer to air barrier system product data sheet for acceptable SELF-ADHERED FLASHING* products.
PERSPECTIVE VIEW
2" M
IN.
2" M
IN.
2" MIN.
2"MIN.
2" M
IN.
2"MIN.
5
3
SECTIONVIEW
2
4
2
4
3
6
3
1
1
3" = 1'
KNIFEPLATE PENETRATION DETAIL -NON-MASONRY CLADDING
DRAWING: PWM-019
SCALE:
EFFECTIVE DATE: 2020.05.21
SUPERCEDES:
PERM-A-BARRIER® WALLMEMBRANE
NEW
1. PERM-A-BARRIER® WALLMEMBRANE
2. PERM-A-BARRIER® S100,PERM-A-BARRIER® LIQUIDFLASHING, BITUTHENE MASTIC,OR BITUTHENE LIQUIDMEMBRANE - 1-INCHTROWELED BEAD
3. AIR AND WATER TIGHT BOXAND PENETRATION
4. AIR AND WATER TIGHT PIPE ORDUCT PENETRATION
5. PERM-A-BARRIER® S100,PERM-A-BARRIER® LIQUIDFLASHING, BITUTHENE MASTIC,OR BITUTHENE LIQUIDMEMBRANE - FLASHING ANDCANT SEAL
2 1/
2" M
IN
GENERAL NOTES
LEGEND
1. Detail not suitable for all climates. Avoiding excessive moisture accumulation in exterior walls is dependent on many factors including properplacement of insulation and water, air, and vapor control layers in the wall. Confirm membranes are suitable for project specific servicetemperatures. For assistance with exterior wall design, consult with a building science professional.
2. Install all GCP products in accordance with GCP Product Data Sheets and GCP recommendations.3. GCP products are indicated in the detail legend in BOLDFACE font. Detail components by others are indicated in GRAY FONT. Install
components per manufacturer and project specific requirements.
*Refer to air barrier system product data sheet for acceptable SELF-ADHERED FLASHING* products.
EXTE
RIO
R
INTE
RIO
R
EXTE
RIO
R
INTE
RIO
R
3
4
5
1
2
1
5
2 1/
2" M
IN
3" = 1'
PENETRATION DETAILS -NON-MASONRY CLADDING
DRAWING: PWM-020
SCALE:
EFFECTIVE DATE: 2020.05.21
SUPERCEDES:
PERM-A-BARRIER® WALLMEMBRANE
NEW
1. PERM-A-BARRIER® WALL MEMBRANE2. CLADDING ATTACHMENT -
CONFIRM DETAILING REQUIREMENTSWITH THE GCPAT REPRESENTATIVE
3. BITUTHENE MASTIC, BITUTHENELIQUID MEMBRANE, OR GCPAPPROVED SEALANT - 1-INCHTROWELED BEAD
4. PERM-A-BARRIER® SELF-ADHEREDFLASHING*
5. SHEET METAL FLASHING PER ARCH6. INTERIOR AIR SEALANT OVER
BACKER ROD7. PERM-A-BARRIER® S100,
PERM-A-BARRIER® LIQUID FLASHING,BITUTHENE MASTIC, OR BITUTHENELIQUID MEMBRANE - 1-INCHTROWELED BEAD
GENERAL NOTES
LEGEND
1. Detail not suitable for all climates. Avoiding excessive moisture accumulation in exterior walls is dependent on many factors including properplacement of insulation and water, air, and vapor control layers in the wall. Confirm membranes are suitable for project specific servicetemperatures. For assistance with exterior wall design, consult with a building science professional.
2. Install all GCP products in accordance with GCP Product Data Sheets and GCP recommendations.3. GCP products are indicated in the detail legend in BOLDFACE font. Detail components by others are indicated in GRAY FONT. Install
components per manufacturer and project specific requirements.
*Refer to air barrier system product data sheet for acceptable SELF-ADHERED FLASHING* products.
EXTE
RIO
R
INTE
RIO
R
SEE DETAIL OPTION(RIGHT)
OPTION 1
OPTION 2
3" M
IN.
3" M
IN.
6
3" M
IN.
3" M
IN.
6
5
2
5
3
4
1
7
4
1
3" = 1'
CURTAINWALL HEAD DETAIL DRAWING: PWM-021
SCALE:
EFFECTIVE DATE: 2020.05.21
SUPERCEDES:
PERM-A-BARRIER® WALLMEMBRANE
NEW
1. PERM-A-BARRIER® WALL MEMBRANE2. CLADDING ATTACHMENT -
CONFIRM DETAILING REQUIREMENTSWITH THE GCPAT REPRESENTATIVE
3. PERM-A-BARRIER® SELF-ADHEREDFLASHING*
4. SHEET METAL FLASHING PER ARCH5. INTERIOR AIR SEALANT OVER
BACKER ROD
3" MIN.
5
GENERAL NOTES
LEGEND
1. Detail not suitable for all climates. Avoiding excessive moisture accumulation in exterior walls is dependent on many factors including properplacement of insulation and water, air, and vapor control layers in the wall. Confirm membranes are suitable for project specific servicetemperatures. For assistance with exterior wall design, consult with a building science professional.
2. Install all GCP products in accordance with GCP Product Data Sheets and GCP recommendations.3. GCP products are indicated in the detail legend in BOLDFACE font. Detail components by others are indicated in GRAY FONT. Install
components per manufacturer and project specific requirements.
*Refer to air barrier system product data sheet for acceptable SELF-ADHERED FLASHING* products.
SEE DETAIL OPTIONS(RIGHT)
OPTION 1
OPTION 2
EXTERIOR
INTERIOR
24 413 3 1
3" MIN.
3" = 1'
CURTAINWALL JAMB DETAIL DRAWING: PWM-022
SCALE:
EFFECTIVE DATE: 2020.05.21
SUPERCEDES:
PERM-A-BARRIER® WALLMEMBRANE
NEW
3" M
IN.
1. CURTAINWALL SILL OVERMANUFACTURER'S STARTER TRACK
2. INTERIOR AIR SEALANT OVERBACKER ROD
3. PERM-A-BARRIER® S100,PERM-A-BARRIER® LIQUID FLASHING,BITUTHENE MASTIC, OR BITUTHENELIQUID MEMBRANE - 1-INCHTROWELED BEAD
4. PERM-A-BARRIER® SELF-ADHEREDFLASHING*
5. PERM-A-BARRIER® WALL MEMBRANE6. CLADDING ATTACHMENT -
CONFIRM DETAILING REQUIREMENTSWITH THE GCPAT REPRESENTATIVE
2
GENERAL NOTES
LEGEND
1. Detail not suitable for all climates. Avoiding excessive moisture accumulation in exterior walls is dependent on many factors including properplacement of insulation and water, air, and vapor control layers in the wall. Confirm membranes are suitable for project specific servicetemperatures. For assistance with exterior wall design, consult with a building science professional.
2. Install all GCP products in accordance with GCP Product Data Sheets and GCP recommendations.3. GCP products are indicated in the detail legend in BOLDFACE font. Detail components by others are indicated in GRAY FONT. Install
components per manufacturer and project specific requirements.
*Refer to air barrier system product data sheet for acceptable SELF-ADHERED FLASHING* products.
EXTE
RIO
R
INTE
RIO
ROPTION 1
OPTION 2
SEE DETAIL OPTIONS(RIGHT)
3" M
IN.
6
1
5
4
3
4
5
3" = 1'
CURTAINWALL SILL DETAIL DRAWING: PWM-023
SCALE:
EFFECTIVE DATE: 2020.05.21
SUPERCEDES:
PERM-A-BARRIER® WALLMEMBRANE
NEW
1. PERM-A-BARRIER® WALLMEMBRANE
2. PERM-A-BARRIER® SELF-ADHEREDFLASHING*
3. MINIMUM 3/4" BACKER ROD4. PERM-A-BARRIER DETAIL
MEMBRANE INVERTED STRIPSUFFICIENT IN SIZE TO COVERBACKER ROD
5. CLADDING ATTACHMENT,CONFIRM DETAILINGREQUIREMENTS WITH THE GCPATREPRESENTATIVE
3" M
IN.
3" M
IN.
GENERAL NOTES
LEGEND
1. Detail not suitable for all climates. Avoiding excessive moisture accumulation in exterior walls is dependent on many factors including properplacement of insulation and water, air, and vapor control layers in the wall. Confirm membranes are suitable for project specific servicetemperatures. For assistance with exterior wall design, consult with a building science professional.
2. Install all GCP products in accordance with GCP Product Data Sheets and GCP recommendations.3. GCP products are indicated in the detail legend in BOLDFACE font. Detail components by others are indicated in GRAY FONT. Install
components per manufacturer and project specific requirements.
*Refer to air barrier system product data sheet for acceptable SELF-ADHERED FLASHING* products.
3
1
2
4
OPTION 2
OPTION 3
1
2
3
4
1
5
2
3
4
5
5
3" = 1'
DEFLECTION JOINT DRAWING: PWM-024
SCALE:
EFFECTIVE DATE: 2020.05.21
SUPERCEDES:
PERM-A-BARRIER® WALLMEMBRANE
NEW