+ All Categories
Transcript
Page 1: RankineCycle Operator Manual

“main” — 2005/9/16 — 13:21 — page i — #1i

i

i

i

i

i

i

i

RankineCycler

Steam Turbine Power System Operator’s ManualTurbine Technologies, LTD

REVISION 9.05

THIS MANUAL MUST BE KEPT WITHTHE SYSTEM AND AVAILABLE AT ALL TIMES

Model RC-101

Page 2: RankineCycle Operator Manual

“main” — 2005/9/16 — 13:21 — page ii — #2i

i

i

i

i

i

i

i

Copyright c©2005 Turbine Technologies, LTD

Service Publications410 Phillip StreetChetek, WI 54728

All rights reserved. No part of this manual may be reproduced, stored in a retrieval system or transmitted by anymeans, electronic, mechanical, photocopying, recording or otherwise–without written permission from TurbineTechnologies, LTD, except for the explicit use and inclusion in a course of academic study utilizing the TurbineTechnologies, LTD RankineCycler Steam Turbine Power System

Many of the designations used by manufacturers to distinguish their products are claimed as trademarks or servicemarks. Every attempt has been made to supply trademark information about manufacturers and their productsmentioned in this manual. A list of the trademark or service mark designations and their owners appears on pageiii.

Every effort has been made to make this manual as complete and accurate as possible. The purchaser shall besolely responsible for determining the suitability of the information contained herein. See page v.

Page 3: RankineCycle Operator Manual

“main” — 2005/9/16 — 13:21 — page iii — #3i

i

i

i

i

i

i

i

iii

TRADEMARK NOTICES

RankineCyclerTM and DigiDAQTM are trademarks of Turbine Technologies, LTD.

Microsoft r©, Windows r©, Visual Basic r© and C++ for Windows r© are registered trademarks of Microsoft

Corporation.

Personal DaqsTM , Personal DaqViewTM , Personal DaqView PlusTM , eZ-PostViewTM , Personal DaqViewXLTM ,

DASYLabTM and Out-of-the-Box TM are registered trademarks of IOtech, Incorporated.

LabVIEWTM is a registered trademark of National Instruments, Incorporated

Page 4: RankineCycle Operator Manual

“main” — 2005/9/16 — 13:21 — page iv — #4i

i

i

i

i

i

i

i

iv

Page 5: RankineCycle Operator Manual

“main” — 2005/9/16 — 13:21 — page v — #5i

i

i

i

i

i

i

i

v

SUITABILITY

The Turbine Technologies, LTD RankineCycler is not offered as and shall not be construed bythe purchaser to be “Consumer Products” within the common definition of the United States FederalTrade Commission. All Turbine Technologies, LTD products are represented to be, and offered as,EXPERIMENTAL TECHNOLOGY, subject to the limitations in safety and performance inherent toequipment so classified. PURCHASER SHALL BE SOLELY RESPONSIBLE for determining, priorto purchase, at acceptance and for all subsequent usage, the suitability for any purpose(s) intendedof equipment, instructions, procedures or materials offered or supplied by Turbine Technologies, LTDfor use in any educational, laboratory or industrial setting.

Page 6: RankineCycle Operator Manual

“main” — 2005/9/16 — 13:21 — page vi — #6i

i

i

i

i

i

i

i

vi

Page 7: RankineCycle Operator Manual

“main” — 2005/9/16 — 13:21 — page vii — #7i

i

i

i

i

i

i

i

Preface

The RankineCycler is the best tool on the market for laboratory teaching of thermodynamicprinciples and power generation, and it comes with the lowest price tag. In fact, as far as I can tell,

it is the only available educational equipment of its kind.- Dr. Andy Gerhart

Assistant Professor Mechanical EngineeringCollege of Engineering, Lawrence Technological University

Southfield, MI

Since the first century AD and the invention of the aeolipile by Heron of Alexandria, man hasendeavored to harness the power of steam. Refined by Denis Papin and improved throughout theIndustrial Revolution by the likes of Thomas Savery, Thomas Newcomen and James Watt, the steamengine became an important source of mechanical power. The steam turbine, made practical byCharles Parson and improved commercially by George Westinghouse, furthered the use of steampower and helped accelerate the electrification of the modern world.

William Rankine, a Scottish physicist and early pioneer in the study of thermodynamics, compiledthe first comprehensive study of steam power in his 1859 Manual of the Steam Engine and OtherPrime Movers. Describing the production of power with a vapor power plant, the Rankine Cyclebecame the basis for all future thermodynamic power system and cycle study.

Challenging generations of engineering students ever since, the Rankine Cycle has been usedto theoretically model and teach the physical processes taking place in power-generating systems.The Turbine Technologies, LTD RankineCycler takes this abstract modeling to a new level, al-lowing students to not only measure the various variables that go into the Rankine Cycle, but tosee, hear and even feel the generation of steam power first hand. By making text book academicscome alive, the RankineCycler will help today’s students become the real world engineers of tomorrow.

vii

Page 8: RankineCycle Operator Manual

“main” — 2005/9/16 — 13:21 — page viii — #8i

i

i

i

i

i

i

i

viii

Manual Structure

Section 1 - General Information Background information to help the new user become familiarwith the RankineCycler unit prior to operation.

Section 2 - Limitations Important limitations for the safe operation of the RankineCycler.

Section 3 - Abnormal Procedures Checklist Procedures for operations that exceed or are outsidethe scope of the RankineCycler Limitations or Normal Procedures.

Section 4 - Normal Procedures Checklist Procedures for Normal Operation of the Rank-ineCycler.

Section 5 - Systems Description of all unique RankineCycler systems and their operation.

Section 6 - Service and Maintenance Information to maintain the RankineCycler in proper op-erating condition.

Appendix A - Warranty Information

Comments/Questions

Please address comments and questions concerning this Operator’s Manual to the publisher:

Turbine Technologies, LTD.Service Publications410 Phillip StreetChetek, WI 54728(715) 924-4876(715) 924-2436 (fax)

A RankineCycler web page featuring an image gallery, press releases, video, product specificationsand operator produced technical papers is available at:

http://www.turbinetechnologies.com/steam.html

Specific questions regarding the operation or servicing of the RankineCycler should be addressed to:

[email protected]

For more information about Turbine Technologies, LTD and its products for engineering education,please see the Turbine Technologies web site at:

http://www.turbinetechnologies.com

Or email:

[email protected]

Page 9: RankineCycle Operator Manual

“main” — 2005/9/16 — 13:21 — page ix — #9i

i

i

i

i

i

i

i

Contents

Preface vii

Section 1 - General Information 1

1.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

1.2 SAFETY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

1.3 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

1.4 Uncrating and Set-Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

Section 2 - LIMITATIONS 7

Section 3 - ABNORMAL PROCEDURES 9

3.1 ABBREVIATED ABNORMAL PROCEDURES . . . . . . . . . . . . . . . . . . . . . 11

3.1.1 Boiler Overpressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

3.1.2 Fire . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

3.1.3 Electrical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

3.2 EXPANDED ABNORMAL PROCEDURES . . . . . . . . . . . . . . . . . . . . . . . . 13

3.2.1 Boiler Overpressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

3.2.2 Fire . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

3.2.3 Electrical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

Section 4 - Normal Procedures 15

4.1 Abbreviated Normal Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

4.1.1 Pre-Start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

4.1.2 Start and Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

4.1.3 Data Collection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23

4.1.4 Shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

4.1.5 Measurements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27

4.1.6 Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29

4.2 Expanded Normal Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31

4.2.1 Pre-Start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33

4.2.2 Start and Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35

4.2.3 Data Collection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37

4.2.4 Shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38

4.2.5 Measurements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39

4.2.6 Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40

4.3 General Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42

ix

Page 10: RankineCycle Operator Manual

“main” — 2005/9/16 — 13:21 — page x — #10i

i

i

i

i

i

i

i

x CONTENTS

Section 5 - Systems 435.1 Steam Turbine System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43

5.1.1 Burner . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 435.1.2 Boiler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 445.1.3 Sight Glass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 455.1.4 Boiler Pressure Gauge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 455.1.5 Steam Admission Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 455.1.6 Steam Turbine . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 455.1.7 Generator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 465.1.8 Condenser Tower . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 465.1.9 Operator Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46

5.2 Fill/Drain System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 475.3 Data Acquisition System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47

5.3.1 Computer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 475.3.2 DAQ Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 475.3.3 Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 485.3.4 Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51

5.4 Cabinetry . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 515.4.1 Chassis . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 515.4.2 Electrical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 515.4.3 Fuel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 515.4.4 Miscellaneous . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51

Section 6 - Service and Maintenance 536.1 General Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53

6.1.1 Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 536.1.2 Condition Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 536.1.3 Service Schedule . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54

6.2 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 556.3 Factory Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58

Appendix A - WARRANTY INFORMATION 59

Page 11: RankineCycle Operator Manual

“main” — 2005/9/16 — 13:21 — page xi — #11i

i

i

i

i

i

i

i

List of Tables

1.1 Shipping Container Inventory List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55.2 DAQ Channel Assignments and Sensor Details . . . . . . . . . . . . . . . . . . . . . . 495.3 Channel Configuration - Analog Input . . . . . . . . . . . . . . . . . . . . . . . . . . . 50

xi

Page 12: RankineCycle Operator Manual

“main” — 2005/9/16 — 13:21 — page xii — #12i

i

i

i

i

i

i

i

xii LIST OF TABLES

Page 13: RankineCycle Operator Manual

“main” — 2005/9/16 — 13:21 — page 1 — #13i

i

i

i

i

i

i

i

Section 1General Information

1.1 Introduction

The Turbine Technologies, LTD RankineCycler Steam Turbine Power System is a complete steamelectric power plant in miniature purposely designed for engineering education and research. Thesystem accurately represents a typical fossil-fueled vapor power plant in which water is the workingfluid.

Turning heat energy into useful work is the purpose of any vapor power system. With the Rank-ineCycler, steam is generated by heating water in a multi-pass, flame-through tube type boiler witha super heat dome. This high-pressure steam is expanded through an axial flow turbine wheel thatdrives an AC/DC generator to produce electricity. Leaving the turbine at low pressure, the vaporthen enters a condenser tower, returning to its original liquid state. In a full scale power plant, thisliquid water would then be returned to the boiler.

Initial thermodynamic calculations can be made using the classic Ideal Rankine Cycle model. Nu-merical predictions based on the temperature-entropy process flows of the cycle can then be measureddirectly on the RankineCycler with the integrated data acquisition system. Sensors located at variouspoints along the vapor path allow accurate measurements to be made of the operating conditions atthose points.

Explaining the differences and accounting for the real world results presents limitless educationalopportunities.∗ For safety and convenience, the RankineCycler is not equipped with a feedwaterreturn pump. Because actual pump work is significantly less than that in the turbine, neglecting thepump contribution will have negligible effect on the net work of the cycle and the cycle calculationsoverall.

Additional opportunities in the study of Environmental and Pollution engineering are possiblethrough both qualitative and quantitative analysis of other parameters outside the scope of the stockRankineCycler.

∗Reasonable expectations regarding experimental results must be made when operating the RankineCycler or anysimilar equipment where scale effects are present. By size and design, the system can only model full-size steam andpower generation. Efficiency, power output and overall system performance will naturally be much different thanthat for the same process on a larger scale. Additionally, temperatures and pressures are necessarily kept low forsafety considerations. In whole, the RankineCycler provides an excellent foundation for exploring the shortcomings(and pitfalls) of applying textbook formulas and ideal data to a problem without considering all aspects of the overallsystem. The challenge to the student is in the analysis of experimental run-time data and determining why the resultsmay differ from analytical expectations. This is the true benefit of hands-on, laboratory and experimental engineering.Rest assured, no Laws of Thermodynamics are broken during the operation of the RankineCycler.

1

Page 14: RankineCycle Operator Manual

“main” — 2005/9/16 — 13:21 — page 2 — #14i

i

i

i

i

i

i

i

2 SECTION 1

1.2 SAFETY

As with any piece of laboratory equipment, basic safety precautions must be followedat all times. Protective eyewear must be worn whenever the equipment is in operationor receiving service. Complete familiarization with all aspects of the RankineCycler

system and its operation must be made prior to usage.

During normal operation, various surfaces of the RankineCycler obtain temperaturesthat can cause severe burns. ALL surfaces of the system should be considered HOTduring operation. Under no circumstances should the boiler doors be opened duringoperation.

The RankineCycler boiler has been low cycle fatigue pressure tested to 150% of normaloperating pressure. The boiler is NOT ASME rated, nor is it approved by any othertesting facility or regulatory body.

DO NOT ATTEMPT TO MAKE ANY ADJUSTMENTS TO OR BYPASS SAFETYDEVICES AND/OR CONTROLS TO FORCE OPERATIONS OUTSIDE OF PUB-LISHED LIMITATIONS. DO NOT EXCEED, UNDER ANY CIRCUMSTANCES,THE PUBLISHED MAXIMUM OPERATING PRESSURE.

If any limitation is exceeded, operation of the system should be suspended until adetermination is made of the cause of the out of limit condition and suitability forcontinued operation.

The RankineCycler is considered to be in “operation” WHENEVER the burneris ignited, there is positive boiler pressure or any surface is warmer than ambienttemperature.

FAILURE TO FOLLOW THE LIMITATIONS AND USAGE AS SET

FORTH IN THIS OPERATOR’S MANUAL MAY CAUSE SERIOUS

INJURY OR DEATH.

1.3 Specifications

• DIMENSIONS - Steam Turbine Power System

– LENGTH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30.0 inches (77 cm)– WIDTH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .48.0 inches (122 cm)– HEIGHT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58.0 inches (148 cm)– HEIGHT with FILL BEAKER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82.0 inches (209 cm)– WEIGHT operational . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .175 lbs (80 kg)

• OPERATIONAL REQUIREMENTS - Steam Turbine Power System

– ELECTRICAL SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120 VAC Breaker Protected– FUEL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Liquid Propane (LP) Only– ADEQUATE VENTILATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Steam and Combustion Gasses– ADEQUATE CLEARANCE to allow operator access to all four sides, RECOMMEND 48 inches(122 cm) on the RIGHT and REAR SIDES. RECOMMEND 72 inches (183 cm) on the LEFTand FRONT SIDES. Existing Fire and Safety Codes may prevail.

Page 15: RankineCycle Operator Manual

“main” — 2005/9/16 — 13:21 — page 3 — #15i

i

i

i

i

i

i

i

GENERAL INFORMATION 3

1.4 Uncrating and Set-Up

The RankineCycler is shipped in a custom built container for maximum protection against damageduring delivery. It is recommended that a thorough inspection of the container’s exterior be madeprior to acceptance from the shipper. If any damage or discrepancy is noted, it should be brought tothe attention of the shipping agent immediately and prior to any further disassembly of the shippingcontainer.†

When unloading or moving the shipping container,DO NOT apply pressure or force to the container sides.

Doing so may puncture the container and damage the contents inside.

The steps necessary to uncrate the RankineCycler and prepare it for initial use are outlined asfollows. NOTE: DO NOT discard ANY material within the shipping container until a completeinventory has been made of the included contents.

1. Remove Shipping Container Front Door DO NOT pry the container open! Locate thefront door of the container as indicated by the “DOOR - OPEN THIS SIDE ONLY” stencil.Approximately 21 screws, indicated by 1.0 inch (2.5 cm) red squares and located around thedoor perimeter, need to be removed to open the container front door. Only remove those screwsdelineated by the red squares. With all the screws removed, the door may be opened and setaside.

2. Remove Packaged Contents Boxes Various items are separately boxed and/or located underthe RankineCycler cabinet. The following items are typically included:

(a) Important Documents and System Keys A box marked Important Documentscontains all documents essential to the operation of the RankineCycler (including backupsoftware disks and sensor calibration data). Included are two copies of theRankineCycler

Steam Turbine Power System Operator’s Manual. One copy should be removed atthis time and used for the remainder of the SET-UP process and all subsequent operation.The other copy should be set aside for safe keeping. A set of QuickCheck operator checklistsare included for convenient reference and efficient operation of the RankineCycler. The keysfor the RankineCycler Master Switch are located within the manual binder, attached tothe top binder ring. It is recommended that one key be left in the binder for safe keepingand the other placed into the Master Switch until a specific key storage location and usagepolicy is determined.

(b) Boiler Fill/Drain Beaker The fill/drain beaker is located in a box and wrapped inprotective plastic.

(c) Computer Equipment Any computer equipment and accessories ordered with the systemwill be found in a box. All software required to operate the data acquisition system ispreloaded on this computer.

3. Remove Hold Down Clips Three hold down clips secure the RankineCycler to the shippingcontainer. These clips are indicated by 2.0 inch (5.0 cm) red squares, one each on the left, rightand rear exterior sides of the shipping container. By removing the items in Step 2 above, accessis gained to the clips and the corresponding fasteners on the interior of the box. Remove thesethree clips and corresponding fasteners.

†Turbine Technologies, LTD is not responsible for damage due to shipping. It is the recipient’s responsibility toinspect the shipping container for obvious external damage and to make the appropriate claims with the shipping agentprior to accepting the contents or opening the shipping container.

Page 16: RankineCycle Operator Manual

“main” — 2005/9/16 — 13:21 — page 4 — #16i

i

i

i

i

i

i

i

4 SECTION 1

4. Remove Perimeter Base Screws At the base of the left, right and rear exterior sides ofthe shipping container are the perimeter base screws holding the upright sides of the shippingcontainer to the pallet base. Approximately 12 screws, indicated by 1.0 inch (2.5 cm) red squares,need to be removed around the container base. No other screws need be removed.

5. Remove Shipping Container Side/Top AssemblyWith the perimeter base screws removedin Step 4 above, the three container sides (with the top still attached) can be removed. Thisis accomplished by tilting the container assembly “back,” away from the open door. Take carethat the sides continue to clear the RankineCycler as the entire assembly is tilted back. Onceit is clear of the RankineCycler, the container side assembly can be set aside.

6. Lift RankineCycler Clear of PalletWith adequate assistance, the RankineCycler may nowbe lifted clear of the container pallet and set on the floor. To avoid damage to the system, onlylift on the area adjacent to the cabinet legs. DO NOT lift by grasping any of the componentson the top side of the system cabinet.

7. Unlock Caster Wheels All four caster wheels under the system cabinet are lockable and willbe locked for shipping. Lifting the locking tab releases the lock mechanism. Release all fourcaster wheel locks as necessary.

8. Remove Protective Packing Material A large piece of plastic will be draped over the entireRankineCycler. Bubble-wrap type material will be wrapped around the entire system. The twoboiler doors will be secured with a length of plastic wrap. Remove all of this material from theRankineCycler.

9. Inventory / General Condition Assessment / Cleaning Using Table 1.1 as a guide, in-ventory all received contents and verify their general condition. Separate Packing and Inventorylists will be found within the shipping container to further assist in this process. If any item isfound to be missing or damaged, contact Turbine Technologies, LTD immediately. With a softcloth, wipe any dust or dirt from the system cabinetry and accessories.

10. Retain Shipping Container / MaterialsWith all RankineCycler components accounted forin Step 9, the shipping container may be removed for storage. All packing material should beplaced within the container and the container side assembly and front door reattached with theoriginal screws previously removed. While the container may be disposed of at this time, it isrecommended that the container and packing material be retained for future use should the needarise to move the RankineCycler over any appreciable distance, store for an extended period oftime or to return the RankineCycler to the factory for service or upgrade.

11. Connect Suitable Fuel Supply An appropriate liquid propane tank with an adequate supplyof fuel is required to operate the RankineCycler. Tanks of the 20, 30 and 40 “pound” varietycommon to gas cooking appliances and portable heating equipment are acceptable. The 20pound size is ideal for classroom use, allowing portable operation with several hours of run-time.The fuel source gas regulator and hose assembly is tie-wrapped to the front, right cabinet leg.Cut the tie-wrap loose and connect the provided fuel source gas regulator to the selected fuelsource. This regulator is factory adjusted to work with liquid propane fuel. Please consult thefactory prior to using other fuel types.

The RankineCycler is now ready for operation. See Section 4 - Normal Procedures for furtherinstructions.

Page 17: RankineCycle Operator Manual

“main” — 2005/9/16 — 13:21 — page 5 — #17i

i

i

i

i

i

i

i

GENERAL INFORMATION 5

Table 1.1: Shipping Container Inventory List

ITEM DESCRIPTIONNUMBER 1 2 3 4 Level QTY LOCATION

1 SHIPPING CONTAINER 12 . RankineCycler 1 SHIPPING CONTAINER3 . . Fuel Source Gas Regulator/Hose Assembly 1 RankineCycler Front, Right Leg4 . Important Documents 1 SHIPPING CONTAINER5 . . Master Keys 2 Important Documents6 . . Operator’s Manual 2 Important Documents7 . . Computer Software various Important Documents8 . Box 1 1 SHIPPING CONTAINER9 . . Fill/Drain Beaker 1 Box 110 . Box 2 1 SHIPPING CONTAINER11 . . Computer/Power Cable/Power Adapter 1 each Box 212 . . USB Cable 1 Box 2

Page 18: RankineCycle Operator Manual

“main” — 2005/9/16 — 13:21 — page 6 — #18i

i

i

i

i

i

i

i

6 SECTION 1

Page 19: RankineCycle Operator Manual

“main” — 2005/9/16 — 13:21 — page 7 — #19i

i

i

i

i

i

i

i

Section 2LIMITATIONS

The RankineCycler is designed to be operated within the following limitations. Under no circum-stances should these limitations be exceeded by any margin. Operator safety and efficient operationof the RankineCycler is contingent upon these limitations being followed.

• BOILER

– MAXIMUM OPERATIONAL BOILER PRESSURE . . . . . . . . . . . . . . . 120 psi (827 kPa)– MAXIMUM OPERATIONAL BOILER STEAM TEMPERATURE . . . 608 F (320 C)– MAXIMUM OPERATIONAL BOILER VOLUME . . . . . . . . . . . . . . . . . 203 oz (6,000 ml)– OPERATING FLUID . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .WATER

• BURNER

– FUEL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .LIQUID PROPANE (LP) ONLY

• GENERATOR

– MAXIMUM GENERATOR OUTPUT, Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . .15.0 Volts– MAXIMUM GENERATOR OUTPUT, Current . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.0 Amps– MAXIMUM GENERATOR OUTPUT, Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 Watts– MAXIMUM GENERATOR SPEED, RPM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4500 RPM

7

Page 20: RankineCycle Operator Manual

“main” — 2005/9/16 — 13:21 — page 8 — #20i

i

i

i

i

i

i

i

8 SECTION 2

Page 21: RankineCycle Operator Manual

“main” — 2005/9/16 — 13:21 — page 9 — #21i

i

i

i

i

i

i

i

Section 3ABNORMAL PROCEDURES

The RankineCycler is designed with the highest regard to operator safety. It is very unlikely duringthe normal course of operation and within the limitations set forth in this manual, that any conditionswill be encountered requiring the use of ABNORMAL PROCEDURES as set forth herein. Theseprocedures are provided in the event of a “worst case” scenario resulting from multiple system failures.

The procedures in this section outline the minimum steps necessary to achieve a safe system state.When the system is secured and there is no further potential for personal harm, normal shutdownprocedures should be completed. All further operation of the system should be suspended until adetermination is made of the cause of the abnormal event and the suitability for continued operationis determined by qualified personnel.

Summary operating checklists are provided in the ABBREVIATED PROCEDURES sections(3.1.X). Detailed procedures for the same steps are described in the EXPANDED PROCEDURESsections (3.2.X).

In general, remembering “OFF - OPEN - OFF,” will be all that is necessary to deal with anyabnormal condition encountered with the RankineCycler.

1. OFF - Shut OFF the Master Switch.

2. OPEN - OPEN the Steam Admission Valve, relieving system pressure.

3. OFF - Shut OFF the supply of gas to the burner.

“OFF - OPEN - OFF”

9

Page 22: RankineCycle Operator Manual

“main” — 2005/9/16 — 13:21 — page 10 — #22i

i

i

i

i

i

i

i

10 SECTION 3

Page 23: RankineCycle Operator Manual

“main” — 2005/9/16 — 13:21 — page 11 — #23i

i

i

i

i

i

i

i

ABNORMAL PROCEDURES 11

3.1 ABBREVIATED ABNORMAL PROCEDURES

3.1.1 BOILER OVERPRESSURE

1. MASTER SWITCH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .OFF

2. STEAM ADMISSION VALVE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . OPEN

3. OPERATOR PANEL GAS VALVE (or FUEL SOURCE) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .OFF

4. IF SAFETY IS NOT COMPROMISED

a. LOAD SWITCH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .ONb. LOAD RHEOSTAT CONTROL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .TURN FULLY CLOCKWISE

3.1.2 FIRE

1. MASTER SWITCH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .OFF

2. FIRE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .EXTINGUISH WITH FIRE EXTINGUISHER

3. IF SAFETY IS NOT COMPROMISED

a. STEAM ADMISSION VALVE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .OPENb. OPERATOR PANEL GAS VALVE (or FUEL SOURCE) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .OFF

3.1.3 ELECTRICAL

1. MASTER SWITCH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .OFF

2. STEAM ADMISSION VALVE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . OPEN

3. OPERATOR PANEL GAS VALVE (or FUEL SOURCE) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .OFF

4. LOAD SWITCH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .OFF

“OFF - OPEN - OFF”

Page 24: RankineCycle Operator Manual

“main” — 2005/9/16 — 13:21 — page 12 — #24i

i

i

i

i

i

i

i

12 SECTION 3

Page 25: RankineCycle Operator Manual

“main” — 2005/9/16 — 13:21 — page 13 — #25i

i

i

i

i

i

i

i

ABNORMAL PROCEDURES 13

3.2 EXPANDED ABNORMAL PROCEDURES

3.2.1 BOILER OVERPRESSURE

BOILER OVERPRESSURE occurs anytime the boiler pressure exceeds 130 psi (896 kPa) as indicatedon the analog boiler pressure gauge. Multiple safety devices make the likelihood of an overpressurecondition unlikely. An independent boiler pressure transducer continually measures the boiler oper-ating pressure and regulates the burner accordingly. Flame control is provided for and monitored bya microprocessor based gas ignition and regulation module. Finally, a manual overpressure poppetvalve, located on top of the boiler, is designed to automatically relieve boiler pressure should theinternal pressure exceed 130 psi (896 kPa).In the event a failure of these three safety devices occurs, the operator should immediately eliminate

the potential for any further pressure rise.

1. The console MASTER SWITCH should be placed in the OFF position. Doing so removesall electrical power to the system. By removing electrical power, both the gas regulator andthe combustion blower will shut off. Both are needed to support combustion in the boiler.By eliminating the heat source, no additional energy transfer to the boiler is possible therebyeliminating the potential for further pressure rise.

2. The STEAM ADMISSION VALVE should be turned counter-clockwise to the fully OPENposition. This vents boiler pressure through the normal steam path across the turbine and intothe condenser tower. With no heat and an open steam admission valve, the boiler pressureshould begin decreasing immediately.

3. Turn the OPERATOR PANEL GAS VALVE (or FUEL SOURCE) to the OFF position.

Items 1 through 3 should sufficiently eliminate the potential for further pressure rise. If operatorsafety is in question, all personnel should leave the area until such time that the boiler has cooled.

4. IF SAFETY IS NOT COMPROMISED in any way, the following additional steps should beconsidered:

a. Select the LOAD SWITCH to the ON position.

b. Rotate the LOAD RHEOSTAT CONTROL to the FULLY CLOCKWISE position.

Engaging the LOAD SWITCH helps to quickly dissipate the steam pressure by placing a load onthe steam turbine (through the generator). This also prevents damage to the turbine, generatorand associated bearings caused by overspeeding the turbine with the higher than normal steampressure.

3.2.2 FIRE

The likelihood of a FIRE is virtually non-existent with the RankineCycler. Although a flame ispresent within the boiler, only a failure at the operator panel gas valve, the fuel source regulator orthe connecting hose would produce a flame or persistent fire requiring the use of abnormal procedures.It should be noted that the burner may occasionally “burp” – producing an audible popping noise

with a small blue flame present at the blower inlet. This behavior is normal and should NOT beconsidered a fire requiring the execution of the fire abnormal procedures.

1. The console MASTER SWITCH should be placed in the OFF position. Doing so removes allelectrical power to the system. By removing electrical power, both the gas regulator and thecombustion blower will shut off.

Page 26: RankineCycle Operator Manual

“main” — 2005/9/16 — 13:21 — page 14 — #26i

i

i

i

i

i

i

i

14 SECTION 3

2. Using an available and appropriate FIRE EXTINGUISHER (ABC Type), extinguish the flames.

If operator safety is in question, all personnel should leave the area, activate the appropriate firealarm and follow the required emergency plan.

3. IF SAFETY IS NOT COMPROMISED in any way, the following additional steps should beconsidered:

a. Because of the elevated heat around the system, the potential exists for a boiler overpressurecondition. The STEAM ADMISSION VALVE should be turned counter-clockwise to thefully OPEN position.

b. Turn the OPERATOR PANEL GAS VALVE (or FUEL SOURCE) to the OFF position,positively removing the fuel source and eliminating the potential for re-ignition.

3.2.3 ELECTRICAL

There are two distinct electrical systems within the RankineCycler, the main bus that powers theindicator lights, boiler combustion blower and the gas regulator system and a separate steam generatorbus allowing the measurement of electrical generating capability of the steam turbine and generator.The main bus is further divided into a “high” and “low” system, each equipped with its own resettablecircuit breaker (8 and 3 amps respectively). The main bus and the steam generator bus are electricallyisolated preventing any interaction between the two systems. Problems of an electrical nature wouldmost likely be caused through a short condition in either bus or between the two busses. Any electricalmalfunction of a short or overload nature will trip the on board circuit breaker, the facility circuitbreaker or both.If an electrical fault is suspected, either through an unexpected shut-down of the RankineCycler or

through more obvious signs such as audible or visible arcing or electrical type smoke caused by meltinginsulation, the following steps should be followed. Once the system is secure, a close examination ofthe cause of the malfunction should be made prior to resetting any circuit breaker.

1. The console MASTER SWITCH should be placed in the OFF position. Doing so removes allelectrical power to the system.

2. As standard procedure and to maintain consistency with other abnormal procedures, theSTEAM ADMISSION VALVE should be turned counter-clockwise to the fully OPEN posi-tion.

3. As with Item 2, turn the OPERATOR PANEL GAS VALVE (or FUEL SOURCE) to the OFFposition.

4. The LOAD SWITCH should now be selected OFF to remove any resistance from the steamgenerator bus.

“OFF - OPEN - OFF”

Page 27: RankineCycle Operator Manual

“main” — 2005/9/16 — 13:21 — page 15 — #27i

i

i

i

i

i

i

i

Section 4Normal Procedures

The RankineCycler is designed with simplicity and operator convenience in mind. Inexperiencedoperators will quickly gain familiarity and confidence with the system permitting the collec-tion of meaningful data from the very first run. No special knowledge or skills are required to usethe RankineCycler thereby allowing its usage in even the most basic of science and engineering courses.

This section provides a set of standard procedures to follow while operating the RankineCycler.The steps and the order in which they appear represent the most efficient procedure to initiateoperation of the RankineCycler and to collect run-time data for use in a typical academic setting.Aside from the necessary cool down time, a complete operational run can be accomplished within aone-hour lab session.

Summary operating checklists are provided in the ABBREVIATED PROCEDURES sections(4.1.X). Detailed procedures for the same steps are described in the EXPANDED PROCEDURESsections (4.2.X).

Familiarity with these procedures must be made prior to operating the RankineCycler for thefirst time. Experienced operators should continue to use the checklist for each operational run toeliminate the possibility of overlooking or inadvertently eliminating a necessary step. With powerremoved from the system (electrical service removed), the various switches, valves and controls maybe manipulated without harm to the system. This permits the ability to use the checklists in a “dryrun” or rehearsal fashion prior to operating the RankineCycler under power.

The RankineCycler represents a dynamic system. Operation should not be initiated without apurpose or plan such as a lab procedure. Each participant needs to be familiar with their role andwhat to do in case of an emergency (see Section 3 - ABNORMAL PROCEDURES).

WARNINGDo Not Permit Unattended Operation of the RankineCycler

15

Page 28: RankineCycle Operator Manual

“main” — 2005/9/16 — 13:21 — page 16 — #28i

i

i

i

i

i

i

i

16 SECTION 4

Page 29: RankineCycle Operator Manual

“main” — 2005/9/16 — 13:21 — page 17 — #29i

i

i

i

i

i

i

i

NORMAL PROCEDURES 17

4.1 Abbreviated Normal Procedures

Abbreviated Normal Procedures consist of a series of easy to follow summary operating checklists forthe safe and efficient operation of the RankineCycler.

These checklists are presented in order of usage. Each item should be completed before proceedingto the next item. Each section must be completed before proceeding to the next section. It isrecommended that one operator read the checklist while another performs the task.

Six separate Checklist are provided as follows:

1. Section 4.1.1 PRE-START - Prepares the RankineCycler for operation.

2. Section 4.1.2 START and OPERATION - Starts the RankineCycler and establishes a steadystate system.

3. Section 4.1.3 DATA COLLECTION - Uses the data acquisition system to display and recordsystem operational parameters.

4. Section 4.1.4 SHUTDOWN - Stops operation of the RankineCycler.

5. Section 4.1.5MEASUREMENTS - Steps necessary to measure the quantity of boiler water usedand condensate collected.

6. Section 4.1.6 STORAGE - Prepares the RankineCycler for extended storage.

Page 30: RankineCycle Operator Manual

“main” — 2005/9/16 — 13:21 — page 18 — #30i

i

i

i

i

i

i

i

18 SECTION 4

Page 31: RankineCycle Operator Manual

“main” — 2005/9/16 — 13:21 — page 19 — #31i

i

i

i

i

i

i

i

NORMAL PROCEDURES 19

4.1.1 PRE-START

1. AREA CHECK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .VERIFY SUITABILITY FOR OPERATION

2. CASTER WHEELS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . LOCKED

3. KEYED MASTER SWITCH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .OFF

4. BURNER SWITCH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .OFF

5. LOAD SWITCH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .OFF

6. LOAD RHEOSTAT . . . . . . . . . . . . . . . . . .MINIMUM LOAD, FULL COUNTER-CLOCKWISE POSITION

7. OPERATOR PANEL GAS VALVE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . OFF

8. VISUAL INSPECTION

a. FUEL TANK/SOURCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . CHECKEDb. BURNER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . CHECKEDc. BOILER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . CHECKEDd. BOILER PRESSURE GAUGE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . CHECKEDe. SIGHT GLASS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . CHECKEDf. STEAM ADMISSION VALVE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . CHECKEDg. STEAM LINES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .CHECKEDh. OPERATOR PANEL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .CHECKEDi. CONDENSER TOWER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .CHECKED

9. CONDENSER TOWER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .DRAIN

10. FRONT and REAR BOILER DOORS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . CLOSED and LATCHED

11. STEAM ADMISSION VALVE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . OPEN

12. BOILER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .DRAIN, COMPLETELY

13. BOILER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . FILL, 203 oz (6,000 ml) maximum - use provided beaker

Allow approximately 5 minutes for complete fill.

14. FILL EQUIPMENT . . . . . . . . . . . . . . . . . . . . . . . . . . . STOWED - DO NOT leave beaker in condenser tower

15. STEAM ADMISSION VALVE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .CLOSED

16. COMPUTER DAQ SYSTEM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .CONNECT USB CABLE

17. RANKINECYCLER ELECTRICAL SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . CONNECT

18. FUEL SOURCE . . . . . . . . . . . . . CONNECT to barbed fitting, only use provided regulator on fuel source

19. FINAL CHECK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .COMPLETE

Page 32: RankineCycle Operator Manual

“main” — 2005/9/16 — 13:21 — page 20 — #32i

i

i

i

i

i

i

i

20 SECTION 4

Page 33: RankineCycle Operator Manual

“main” — 2005/9/16 — 13:21 — page 21 — #33i

i

i

i

i

i

i

i

NORMAL PROCEDURES 21

4.1.2 START and OPERATION

1. COMPUTER DAQ SYSTEM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .COMPUTER ON

2. FUEL SOURCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ON

3. FUEL LEAK CHECK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . COMPLETED

4. OPERATOR PANEL GAS VALVE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .ON

5. MASTER SWITCH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .ON - GREEN LIGHT

6. BURNER SWITCH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .ON - RED LIGHT

7. COMBUSTION BLOWER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . VERIFY ON

8. PURGE FUEL LINES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . IF NECESSARY

9. BURNER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . VERIFY LIT within 45 SECONDS

10. BOILER PRESSURE . . . . . . . . . . . . . . . . . . . . . . . . . . . .VERIFY POSITIVE PRESSURE within 3 MINUTES

11. PREHEATAllow approximately 7 minutes to complete the following preheat steps:

a. BOILER PRESSURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .≈ 110 psi (758 kPa)b. STEAM ADMISSION VALVE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .OPENc. BOILER PRESSURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .≈ 40 psi (276 kPa)d. STEAM ADMISSION VALVE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .CLOSEe. BOILER PRESSURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .≈ 110 psi (758 kPa)f. STEAM ADMISSION VALVE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .OPENg. BOILER PRESSURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .≈ 40 psi (276 kPa)h. STEAM ADMISSION VALVE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .CLOSEi. BOILER PRESSURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .≈ 110 psi (758 kPa)

12. STEAM ADMISSION VALVE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .OPEN slowly

13. VOLT METER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .FULL SCALE DEFLECTION ≈ 15.0 Volts

14. LOAD SWITCH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .ON

15. ADJUST LOAD RHEOSTAT to MAINTAIN:

16. BOILER PRESSURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ≈ 110 psi (758 kPa)

17. ADJUST STEAM ADMISSION VALVE / LOAD RHEOSTAT TO ACHIEVE STEADY STATE CONDITION.

a. AMP METER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .≈ 0.2 Ampsb. VOLT METER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .≈ 6.0 Voltsc. BOILER PRESSURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .≈ 110 psi (758 kPa)d. WHEN STEADY STATE ACHIEVED, RESUME CHECKLIST

18. TIME . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .NOTED

19. SIGHT GLASS UPPER BEZEL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .SET TO WATER LEVEL

20. STEAM ADMISSION VALVE . . . . . . . . . . . . . . . . . . . . . . . . . .PERIODIC ADJUSTMENT, STEADY STATE

21. CONDUCT EXPERIMENT AS REQUIRED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .MONITOR WATER LEVEL

(NOT LESS THAN 1 inch (2.5 cm) FROM BOTTOM OF SIGHT GLASS)

Page 34: RankineCycle Operator Manual

“main” — 2005/9/16 — 13:21 — page 22 — #34i

i

i

i

i

i

i

i

22 SECTION 4

Page 35: RankineCycle Operator Manual

“main” — 2005/9/16 — 13:21 — page 23 — #35i

i

i

i

i

i

i

i

NORMAL PROCEDURES 23

4.1.3 DATA COLLECTION

NOTE: The following steps assume the use of the standard PersonalDaqView and default settingsas supplied with the RankineCycler. Use of non-default settings or other software may necessitatealternative methods or procedures for data collection. Consult the PersonalDaqView or softwarespecific manuals as required.

1. OPEN DAQ SOFTWARE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pDaqView

2. RECORD DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . SELECT Arm Trigger for Disk Recording

3. DISPLAY DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . SELECT Enable Readings Column

4. CONFIGURE CHARTS, GRAPHS or METERS . . . . .Select the appropriate button on the Main Control

Window

5. Make Changes as Necessary

6. SAVE RECORDED DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . .DE-SELECT Arm Trigger for Disk Recording

Consult the PersonalDaq UsersManual.pdf and the PostAcquisition Analysis.pdf manu-als for more information on the capabilities and usage of the included data acquisition software. Thesemanuals are found in the C:\Program Files\pDaqView\Applications\Users Manuals directory.

Page 36: RankineCycle Operator Manual

“main” — 2005/9/16 — 13:21 — page 24 — #36i

i

i

i

i

i

i

i

24 SECTION 4

Page 37: RankineCycle Operator Manual

“main” — 2005/9/16 — 13:21 — page 25 — #37i

i

i

i

i

i

i

i

NORMAL PROCEDURES 25

4.1.4 SHUTDOWN

1. TIME . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .NOTED

2. STEAM ADMISSION VALVE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .CLOSED

3. SIGHT GLASS LOWER BEZEL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . SET TO WATER LEVEL

4. BURNER SWITCH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .OFF, RED LIGHT EXTINGUISHED

5. OPERATOR PANEL GAS VALVE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . OFF

6. LOAD RHEOSTAT . . . . . . . . . . . . . . . . . .MINIMUM LOAD, FULL COUNTER-CLOCKWISE POSITION

7. LOAD SWITCH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .OFF

8. MASTER SWITCH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .OFF, GREEN LIGHT EXTINGUISHED

9. STEAM ADMISSION VALVE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . OPEN

10. FUEL SOURCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . OFF

Page 38: RankineCycle Operator Manual

“main” — 2005/9/16 — 13:21 — page 26 — #38i

i

i

i

i

i

i

i

26 SECTION 4

Page 39: RankineCycle Operator Manual

“main” — 2005/9/16 — 13:21 — page 27 — #39i

i

i

i

i

i

i

i

NORMAL PROCEDURES 27

4.1.5 MEASUREMENTS

1. To Measure Condensate Collected

a. INSURE EQUIPMENT HAS SUITABLY COOLED FOR HANDLING and THERE IS NO BOILER

PRESSUREb. CONDENSER TOWER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .DRAIN FULLYc. CONDENSATE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . RECORD VOLUMEd. DISCARD CONDENSATE - DO NOT REUSE

2. To Measure Boiler Water Consumed

a. INSURE EQUIPMENT HAS SUITABLY COOLED FOR HANDLING and THERE IS NO BOILER

PRESSUREb. STEAM ADMISSION VALVE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .OPENc. BOILER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . FILL TO SIGHT GLASS UPPER BEZELd. BOILER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .DRAIN TO SIGHT GLASS LOWER BEZELe. BOILER WATER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .RECORD VOLUMEf. STOW MEASUREMENT EQUIPMENT

Page 40: RankineCycle Operator Manual

“main” — 2005/9/16 — 13:21 — page 28 — #40i

i

i

i

i

i

i

i

28 SECTION 4

Page 41: RankineCycle Operator Manual

“main” — 2005/9/16 — 13:21 — page 29 — #41i

i

i

i

i

i

i

i

NORMAL PROCEDURES 29

4.1.6 STORAGE

1. COMPUTER DAQ SYSTEM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .OFF, DISCONNECT, STOW USB CABLE

2. LOAD RHEOSTAT . . . . . . . . . . . . . . . . . .MINIMUM LOAD, FULL COUNTER-CLOCKWISE POSITION

3. LOAD SWITCH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .OFF

4. BURNER SWITCH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .OFF

5. KEYED MASTER SWITCH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .OFF

6. OPERATOR PANEL GAS VALVE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . OFF

7. FUEL SOURCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . OFF

8. FUEL SOURCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .DISCONNECT, SUPPLY LINES STOWED

9. RANKINECYCLER ELECTRICAL SERVICE . . . . . . . . . . . . . . . . . . . . . . . . DISCONNECT, CORD STOWED

10. STEAM ADMISSION VALVE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . OPEN

11. INSURE EQUIPMENT HAS SUITABLY COOLED FOR HANDLING and THERE IS NO BOILER PRESSURE

12. BOILER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .DRAIN

13. FRONT and REAR BOILER DOORS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . CLOSED and LATCHED

14. CONDENSER TOWER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .DRAIN

15. FINAL CHECK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .COMPLETE

16. RANKINECYCLER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .SECURED

Page 42: RankineCycle Operator Manual

“main” — 2005/9/16 — 13:21 — page 30 — #42i

i

i

i

i

i

i

i

30 SECTION 4

Page 43: RankineCycle Operator Manual

“main” — 2005/9/16 — 13:21 — page 31 — #43i

i

i

i

i

i

i

i

NORMAL PROCEDURES 31

4.2 Expanded Normal Procedures

Expanded Normal Procedures consist of a series of descriptive steps detailing each summary operatingchecklist item necessary for the safe and efficient operation of the RankineCycler.

These steps are presented in order of usage. Each item should be completed before proceedingto the next item. Each section must be completed before proceeding to the next section. It isrecommended that one operator read the steps aloud while another performs the task.

Six separate sections are provided as follows:

1. Section 4.2.1 PRE-START - Prepares the RankineCycler for operation.

2. Section 4.2.2 START and OPERATION - Starts the RankineCycler and establishes a steadystate system.

3. Section 4.2.3 DATA COLLECTION - Uses the data acquisition system to display and recordsystem operational parameters.

4. Section 4.2.4 SHUTDOWN - Stops operation of the RankineCycler.

5. Section 4.2.5MEASUREMENTS - Steps necessary to measure the quantity of boiler water usedand condensate collected.

6. Section 4.2.6 STORAGE - Prepares the RankineCycler for extended storage.

Page 44: RankineCycle Operator Manual

“main” — 2005/9/16 — 13:21 — page 32 — #44i

i

i

i

i

i

i

i

32 SECTION 4

Page 45: RankineCycle Operator Manual

“main” — 2005/9/16 — 13:21 — page 33 — #45i

i

i

i

i

i

i

i

NORMAL PROCEDURES 33

4.2.1 PRE-START

The PRE-START checklist must be completed prior to operating the RankineCycler. The checklistestablishes that all systems are ready for operation and that heat can be safely applied to the boiler.

1. The AREA CHECK is a general assessment to VERIFY SUITABILITY FOR OPERATION. Thisincludes a suitability determination of safety and facilities factors, additional equipment require-ments and the presence of trained, knowledgeable operators. All operators and personnel in theimmediate area should know the location of fire extinguisher equipment, circuit breakers and fuelsupply valves, as well as being familiar with existing safety policies and procedures, emergencyescape routes, and emergency services telephone numbers/points of contact. The facility mustprovide adequate ventilation sufficient to vent the anticipated amounts of steam and combustiongas production. In addition to safety glasses, all operators should have access to face shields,gloves, lab coats or other items of personal protection as deemed necessary. All operators mustbe thoroughly familiar with the contents of this manual prior to operating the RankineCycler.It is strongly encouraged that two or more individuals operate the RankineCycler as a team toenhance safety and insure that all checklist items are completed.

2. CASTER WHEELS must be in the LOCKED position prior to operation, preventing movementthat may either pose a safety hazard or disrupt critical operations such as boiler filling.

3. KEYEDMASTER SWITCH to theOFF position puts the system into a known, safe condition fromwhich it can be properly started. The MASTER SWITCH controls electrical power distributionto the entire system. With the MASTER SWITCH OFF, no electricity can flow to the burner,thereby preventing any chance for ignition prior to the system being ready.

4. BURNER SWITCH to the OFF position puts the system into a known, safe condition from whichit can be properly started.

5. LOAD SWITCH to the OFF position puts the system into a known, safe condition from whichit can be properly started.

6. LOAD RHEOSTAT to the MINIMUM LOAD, FULL COUNTER-CLOCKWISE POSITIONputs the system into a known, safe condition from which it can be properly started.

7. OPERATOR PANEL GAS VALVE to theOFF position puts the system into a known, safe conditionfrom which it can be properly started.

8. At this point, a thorough VISUAL INSPECTION of each major component or system is performed.This will verify that the component or system is in a safe condition for proper operation. Thisimportant step verifies that no components were damaged, tampered with or removed sincethe last run. If any component is in doubt, qualified personnel should be consulted prior tooperation.

a. The FUEL TANK/SOURCEmust be CHECKED for general condition. Liquid Propane (LP)bottles and corresponding regulators should be free from rust or corrosion, not damagedin any way and intact with all standard safety features in place. Fuel lines should be freefrom cuts and abrasion. All fittings and open lines must be clean and free from dirt andmoisture. Any liquid propane fuel source may be used providing it can accept the TurbineTechnologies, LTD provided fuel source gas regulator and hose assembly.

b. The BURNER must be CHECKED for general condition. All external surfaces should befree from damage such as dents or cracks. All external fasteners should be in place. Thealuminum fins inside the blower fan should be straight and free from contamination. Thevortex disk, visible through the open boiler doors should appear clean and straight.

Page 46: RankineCycle Operator Manual

“main” — 2005/9/16 — 13:21 — page 34 — #46i

i

i

i

i

i

i

i

34 SECTION 4

c. The BOILER must be CHECKED for general condition. The boiler mantle should be cleanwith no obvious signs of leakage. The front and rear boiler doors must fit tight when closed,with no binding, and latch securely.

d. The BOILER PRESSURE GAUGE must be CHECKED for general condition. There shouldbe no obvious signs of leakage around the base fittings or the pressure gauge head. Thepressure gauge steam line must be free from kinks or non-original bends. The gauge itselfmust be undamaged with no cracks permitted in the clear faceplate.

e. The SIGHT GLASS must be CHECKED for general condition. All fittings should be tightwith no obvious signs of leakage. All external fasteners should be in place. The SIGHTGLASS should be intact with no cracks.

f. The STEAM ADMISSION VALVE must be CHECKED for general condition. There shouldbe no obvious signs of leakage around the valve. The valve should move from fully closedto fully open with no binding.

g. The STEAM LINES must be CHECKED for general condition. There should be no obvioussigns of leakage around any STEAM LINE fittings. The lines must be free from kinks ornon-original bends. The orange insulating tape should be secure at all locations.

h. The OPERATOR PANEL must be CHECKED for general condition. All switches, controlsand meters should be secure in the console. The clear meter face plates must be in placeand not cracked or otherwise damaged.

i. The CONDENSER TOWER must be CHECKED for general condition. The CONDENSERTOWER should be free from dents or other damage. The outlet must be free from obstruc-tion.

9. The CONDENSER TOWER should be DRAINED. This provides a known starting condition forthe next experimental run. CONDENSER TOWER condensate will usually contain some amountof minerals depending upon water quality. Drain the CONDENSER TOWER using the attachedclear tubing and pinch-clamp. Discard any condensate collected from the CONDENSER TOWER.

10. The FRONT and REAR BOILER DOORS must be CLOSED and LATCHED.

11. The STEAM ADMISSION VALVE must be OPEN to allow air to vent out of the boiler duringthe fill operation. Water will not enter the boiler with the STEAM ADMISSION VALVE closed.

12. The BOILER should be DRAINED completely. This provides a known starting condition forthe next experimental run. The BOILER can be quickly drained using the fill/drain valve andbeaker assembly. Place the beaker on a firm support lower than the boiler fill/drain valve atthe rear of the boiler. Insert the aluminum coupler at the end of the beaker hose assembly intothe fill/drain valve coupling hole. Firmly pressing the coupler into the fill/drain valve will openthe internal valve and allow water to flow out of the boiler. Open the beaker ball valve to allowwater to drain into the beaker. When it appears that no more water is draining from the boiler,close the beaker ball valve and remove the aluminum coupler from the fill/drain valve. Thewater collected from this draining operation may be discarded.

13. Fill the BOILER with 203 oz (6,000 ml) of clean, distilled water (tap water is acceptable, although,depending on dissolved mineral content, boiler fouling may eventually result). This amount willfill the boiler to the recommended level allowing for the most efficient operation. Any quantityover this recommended amount will likely degrade boiler performance and may prevent theboiler from producing any pressure. With the beaker ball valve closed, fill the beaker to thedesired boiler level. Place the beaker on a firm support higher than the boiler fill/drain valveat the rear of the boiler. If this is the first run of the day or adequate time has passed that thecondenser tower is sufficiently cool, the base of the beaker may be placed into the top opening ofthe condenser tower for convenience. Insert the aluminum coupler at the end of the beaker hose

Page 47: RankineCycle Operator Manual

“main” — 2005/9/16 — 13:21 — page 35 — #47i

i

i

i

i

i

i

i

NORMAL PROCEDURES 35

assembly into the fill/drain valve coupling hole. Firmly pressing the coupler into the fill/drainvalve will open the internal valve and allow water to flow into the boiler. Open the beakerball valve to allow water to fill the boiler. When all the water has emptied from the beaker,close the beaker ball valve and remove the aluminum coupler from the fill/drain valve. Allowapproximately five minutes to completely fill the boiler using the beaker.

14. The FILL EQUIPMENT should be STOWED, keeping it out of the way during operation and ina safe location. If the beaker assembly was placed into the top opening of the condenser towerwhile filling the boiler, remove it before proceeding to the next step.

15. The STEAM ADMISSION VALUE to the CLOSED position puts the system into a known, safecondition from which it can be properly started. Starting with a closed valve allows boilerpressure to properly build.

16. The COMPUTER DAQ SYSTEM USB cable should now be CONNECTED to the DigiDAQsystem receptacle on the left side panel of the RankineCycler. A computer with the appropriatedata acquisition software should be connected to the opposite end of the cable. Make sure thecomputer is OFF prior to connecting the cable or the DAQ Module hardware/software may notproperly initialize.

17. The RANKINECYCLER ELECTRICAL SERVICE should be CONNECTED to the electrical outlet.

18. The FUEL SOURCE line should be CONNECTED to the barbed gas inlet underneath the Rank-ineCycler cabinet. Verify that the Turbine Technologies, LTD gas source regulator and hoseassembly are used for this purpose. Use of any other regulator or hose combination may resultin poor RankineCycler performance. If any other regulator or hose combination is to be used,please consult the factory for assistance.

19. Insure that a FINAL CHECK of all items is COMPLETE. Verify that each checklist item hasbeen covered.

4.2.2 START and OPERATION

The START and OPERATION checklists details the steps necessary to take the RankineCycler fromthe shutdown, cold condition through preheating and run-time data collection at steady state. Thevarious values are recommendations and should provide satisfactory results under most conditions.As skill is gained and operational technique refined, the ability to establish a steady state conditionwill come more readily.

1. The COMPUTER DAQ SYSTEM (data acquisition computer) should be turned ON. This allowsthe computer adequate time to initialize prior to data collection. Make sure the computer isconnected via USB cable to the DigiDAQ system receptacle on the left side panel of the Rank-ineCycler prior to turning the computer ON or the DAQ Module hardware/software may notproperly initialize.

2. The FUEL SOURCE regulator can be turned ON.

3. A FUEL LEAK CHECK must be COMPLETED prior to proceeding further. A “hissing” gassound and/or gaseous odor (characterized as “rotten eggs”) will indicate that there is a problemwith the fuel supply connection to the RankineCycler. IMMEDIATELY shut the FUEL SOURCEOFF. DO NOT proceed further until the source of the gas leak can be determined and rectified.

4. Turn the RankineCycle OPERATOR PANEL GAS VALVE to ON. This permits the flow of fuelto the fuel control system.

Page 48: RankineCycle Operator Manual

“main” — 2005/9/16 — 13:21 — page 36 — #48i

i

i

i

i

i

i

i

36 SECTION 4

5. Select the MASTER SWITCH to the ON position. Verify illumination of the GREEN panel light.Electrical power is now available to the system and the controls.

6. Select the BURNER SWITCH to the ON position. Verify illumination of the RED panel light.Electrical power is now available to the combustion blower.

7. Observe the COMBUSTION BLOWER and VERIFY ON. The COMBUSTION BLOWER motorwill begin to rotate, drawing air into the burner and forcing it through the boiler.

8. PURGE FUEL LINES IF NECESSARY. This is accomplished by allowing the COMBUSTIONBLOWER to operate for approximately 45 seconds, selecting the BURNER SWITCH to OFFthen immediately selecting the BURNER SWITCH back to ON. This assures that the fuel linesare purged by reseting the starting cycle of the fuel control system. After approximately 45seconds, the automatic gas valve will open and the BURNER will light.

9. VERIFY that the BURNER has LIT within 45 SECONDS of selecting the BURNER switch to theON position. It should be noted that the burner may occasionally “burp” - producing an audiblepopping noise with a small blue flame present at the blower inlet. This behavior is normal andshould NOT be considered a fire requiring the execution of the fire abnormal procedures.

10. Monitor BOILER PRESSURE. VERIFY POSITIVE PRESSURE within 3 MINUTES fromBURNER start. If there is no positive indication of boiler pressure within three minutes ofstarting the BURNER, select the BURNER switch to OFF and investigate. Verify that theproper amount of water is in the boiler and the STEAM ADMISSION VALVE is fully CLOSED.When ready to proceed, start with Step 9 above.

11. The system should now be PREHEATED. This allows the steam lines, valves and turbine to comeup to the proper operating temperature. The turbine bearings are also lubricated at this time.During the preheating period, small vapor leaks and condensation droplets may be seen aroundthe turbine and related fittings. This is normal and should subside once the turbine bearingclearances close due to thermal expansion. The preheating process outlined below should takeapproximately 7 to 10 minutes to complete. This preheating process is essential to supplyingthe highest quality steam available to the turbine. If preheating is omitted, condensation willform in the steam lines degrading system performance overall.

a. Allow the indicated BOILER PRESSURE to rise to approximately 110 psi (758 kPa).

b. The STEAM ADMISSION VALVE should be turned counter-clockwise to OPEN. This willallow steam to flow throughout the system. The turbine/generator may or may not rotateat this point.

c. Monitor BOILER PRESSURE until it falls to approximately 40 psi (276 kPa).

d. The STEAM ADMISSION VALVE should be turned clockwise to CLOSE. This will stop theflow of steam throughout the system and allow the boiler pressure to build again.

e. Allow the indicated BOILER PRESSURE to rise to approximately 110 psi (758 kPa).

f. The STEAM ADMISSION VALVE should be turned counter-clockwise to OPEN. This willallow steam to flow throughout the system. The turbine/generator may or may not rotateat this point.

g. Monitor BOILER PRESSURE until it falls to approximately 40 psi (276 kPa).

h. The STEAM ADMISSION VALVE should be turned clockwise to CLOSE. This will stop theflow of steam throughout the system and allow the boiler pressure to build again.

i. Allow the indicated BOILER PRESSURE to rise to approximately 110 psi (758 kPa).

Page 49: RankineCycle Operator Manual

“main” — 2005/9/16 — 13:21 — page 37 — #49i

i

i

i

i

i

i

i

NORMAL PROCEDURES 37

12. While maintaining approximately 110 psi (758 kPa) of BOILER PRESSURE, the STEAM ADMIS-SION VALVE should be OPENED slowly. The rate at which the STEAM ADMISSION VALVEis OPENED should be just enough to maintain 110 psi (758 kPa) of BOILER PRESSURE andto counter any tendency for the BOILER PRESSURE to increase beyond this value. Once theturbine begins to rotate, the generator will produce electricity. Generator output will be directlyindicated on the VOLT METER.

13. Continue opening the STEAM ADMISSION VALVE until the VOLT METER shows an approximateFULL SCALE DEFLECTION or an indicated 15.0 Volts.

14. The LOAD SWITCH should be selected to ON.

15. The LOAD RHEOSTAT should be ADJUSTED to MAINTAIN:

16. A BOILER PRESSURE of approximately 110 psi (758 kPa). This is nothing more than astarting point and the operator should not spend a great deal of time trying to achieve thesevalues exactly.

17. In preparation of an experimental data run, the STEAM ADMISSION VALVE and the LOADRHEOSTAT may now be adjusted to achieve a STEADY STATE CONDITION. Satisfactory run-time results can be achieved with the following STEADY STATE values:

a. An AMP METER indication of approximately 0.2 Amps.

b. A VOLT METER indication of approximately 6.0 Volts.

c. A BOILER PRESSURE indication of approximately 110 psi (758 kPa).

d. These values need not be matched exactly. When a reasonable STEADY STATE isACHIEVED, RESUME CHECKLIST.

18. To begin an experimental run, the TIME should be NOTED. This allows a steam rate calculationto be made at the conclusion of the experimental run.

19. SET the SIGHT GLASS UPPER BEZEL to the current, indicated WATER LEVEL. This allowsmeasurement of the boiler water consumed during the experimental run.

20. Use the STEAM ADMISSION VALVE to make PERIODIC ADJUSTMENT maintaining theSTEADY STATE established in Step 17.

21. Allow time to CONDUCT THE EXPERIMENT AS REQUIRED. Once the STEADY STATE hasbeen achieved, this is usually nothing more than collecting an appropriate amount of datawith the DAQ system for later analysis. While CONDUCTING THE EXPERIMENT, MONITORWATER LEVEL in the BOILER using the SIGHT GLASS. The WATER LEVEL must NOT fallto LESS THAN 1.0 in (2.5 cm) FROM BOTTOM OF SIGHT GLASS. Serious BOILER orBURNER damage may result if the BOILER is allowed to run out of water. At the conclusion ofthe experiment, or should the WATER LEVEL fall below the lower limit, proceed immediatelyto the SHUTDOWN checklist, Section 4.1.4.

4.2.3 DATA COLLECTION

NOTE: The following steps assume the use of the standard PersonalDaqView and default settingsas supplied with the RankineCycler. Use of non-default settings or other software may necessitatealternative methods or procedures for data collection. Consult the PersonalDaqView or softwarespecific manuals as required.

Momentarily moving the mouse pointer over a button will reveal the name of that button.

Page 50: RankineCycle Operator Manual

“main” — 2005/9/16 — 13:21 — page 38 — #50i

i

i

i

i

i

i

i

38 SECTION 4

1. From Windows, Open the PersonalDaqView software by double-clicking on the pDaqView short-cut icon in the RankineCycler folder located on the Windows Desktop. PersonalDaqView willstart with the Main Control Window and Channel Configuration Window displayed.

NOTE: The computer must be connected to the RankineCycler USB port prior to openingthe PersonalDaqView software. The RankineCycler configuration software is dependent uponthe specific DAQ Module serial number as installed in the RankineCycler and will not functionproperly if the DAQ Module cannot be found. Exit the program, attach the USB cable and startover with Step 1 above. To verify that the software is communicating with the DAQ Module,select View from the Main Control Window and select Active Devices... on the drop downmenu. Verify that a check appears in the check box next to the appropriate device name.Generally, two device names will be present. A name specific to the DAQ Module installed(with a corresponding serial number) and a generic name such as PD1 representing a SimulatedDAQ Module.

2. To record data to disk, select the Arm Trigger for Disk Recording button. This but-ton appears as a play button with a red record indicator on it. Data acquisition be-gins and data is stored to a disk file as indicated in the Data Destination Window.The default destination, including the default file name of PDAQ.BIN is C:\ProgramFiles\pDaqView\Applications\DATA\PDAQ.BIN. A different location and/or file name may beselected in the Data Destination Window. Step 2 may be skipped if recorded data is notnecessary.

3. Start sampling real time data by pushing the play button - Enable Readings Column, withinthe Channel Configuration Window. Measured values are then displayed in the Reading column.

4. With the system sampling and displaying measured data, scrolling charts, bar graph, analog ordigital meters may be displayed for any of the various channels as deemed appropriate for thetype of data being collected. Select the appropriate button on the Main Control Window forthe type of chart, graph or meter desired.

5. To change any setting within the Channel Configuration Window, it is first necessary to push thestop button - Disable Readings Column, within the Channel Configuration Window. Make thechanges as necessary, then repeat Step 3. Chart, graph and meter formatting may be changedby left, right or double clicking in the chart, graph or meter area. In some cases, it may benecessary to push the stop button - Disable Readings Column, to make changes to the chart,graph or meter. Repeating Step 3 resumes the display of measured values. It may also benecessary to push the play button on individual charts, graphs or meters if changes were madeto those independently.

6. At the conclusion of the data run, deselect the Arm Trigger for Disk Recording button. Thespecific file saved during the data run must immediately be copied out of the present directoryand/or renamed. Attempting to take additionally data will overwrite the current file resultingin the loss of that data. Read all dialog boxes that appear on the screen and understand theresult of any action selected.

Consult the PersonalDaq UsersManual.pdf and the PostAcquisition Analysis.pdf manu-als for more information on the capabilities and usage of the included data acquisition software. Thesemanuals are found in the C:\Program Files\pDaqView\Applications\Users Manuals directory ofthe default DAQ software installation.

4.2.4 SHUTDOWN

The SHUTDOWN checklists ceases RankineCycler operation and places the system into a known,safe condition.

Page 51: RankineCycle Operator Manual

“main” — 2005/9/16 — 13:21 — page 39 — #51i

i

i

i

i

i

i

i

NORMAL PROCEDURES 39

1. At the conclusion of the experimental run, the TIME should be NOTED for a steam rate calcu-lation.

2. Turn the STEAM ADMISSION VALVE to the CLOSED position.

3. SET the SIGHT GLASS LOWER BEZEL to the current, indicated WATER LEVEL. This allowsmeasurement of the boiler water consumed during the experimental run.

4. Select the BURNER SWITCH to OFF. Verify that the RED light is extinguished indicating thatno electrical power is available at the burner or the blower. The blower should immediately stoprotating.

5. The OPERATOR PANEL GAS VALVE should be selected OFF.

6. The LOAD RHEOSTAT should be turned FULL COUNTER-CLOCKWISE, resulting in MINI-MAL LOAD.

7. The LOAD SWITCH should be selected OFF.

8. The MASTER SWITCH should be selected OFF. Verify that the GREEN light is extinguished.

9. The STEAM ADMISSION VALVE should be turned to the fully OPEN position. This relieves allremaining boiler pressure.

10. The FUEL SOURCE valve should now be turned OFF.

4.2.5 MEASUREMENTS

1. To Measure Condensate Collected

a. INSURE EQUIPMENT HAS SUITABLY COOLED FOR HANDLING and THERE IS NOBOILER PRESSURE.

b. Locate a suitable measuring vessel for collecting the condensate. As the condensate willcontain suspended turbine oil, it is suggested that a disposable or condensate specific vesselbe used. Remove the pinch-clamp from the clear hose allowing the CONDENSER TOWERcondensate to FULLY DRAIN into the vessel.

c. With all the CONDENSATE drained from the CONDENSER TOWER, replace the pinch-clamp on the clear hose. RECORD VOLUME of CONDENSATE drained.

d. Because of the potential for concentrated mineral amounts, appropriately DISCARD CON-DENSATE - DO NOT REUSE in the boiler or for any other purpose.

2. To Measure Boiler Water Consumed

a. INSURE EQUIPMENT HAS SUITABLY COOLED FOR HANDLING and THERE IS NOBOILER PRESSURE.

b. OPEN the STEAM ADMISSION VALVE to vent the boiler.

c. Using the fill beaker assembly, FILL the BOILER TO SIGHT GLASS UPPER BEZELlevel. This represents the volume of water in the boiler when the steady state conditionwas achieved and the experimental run time noted. With the beaker ball valve closed, fillthe beaker. Place the beaker on a firm support higher than the boiler fill/drain valve atthe rear of the boiler. If adequate time has passed that the condenser tower is sufficientlycool, the base of the beaker may be placed into the top opening of the condenser tower forconvenience. Insert the aluminum coupler at the end of the beaker hose assembly into thefill/drain valve coupling hole. Firmly pressing the coupler into the fill/drain valve will open

Page 52: RankineCycle Operator Manual

“main” — 2005/9/16 — 13:21 — page 40 — #52i

i

i

i

i

i

i

i

40 SECTION 4

the internal valve and allow water to flow into the boiler. Open the beaker ball valve toallow water to fill the boiler. When the SIGHT GLASS water level reaches that marked bythe SIGHT GLASS UPPER BEZEL, close the beaker ball valve and remove the aluminumcoupler from the fill/drain valve.

d. Empty the fill beaker assembly of any water remaining from Item (c) above. Using thefill beaker assembly, DRAIN the BOILER TO SIGHT GLASS LOWER BEZEL level. Thetotal volume of water drained into the fill beaker assembly represent the volume of waterconverted into steam and consumed during the experimental run. Place the beaker ona firm support lower than the boiler fill/drain valve at the rear of the boiler. Insert thealuminum coupler at the end of the beaker hose assembly into the fill/drain valve couplinghole. Firmly pressing the coupler into the fill/drain valve will open the internal valve andallow water to flow out of the boiler. Open the beaker ball valve to allow water to draininto the beaker. When the SIGHT GLASS water level reaches that marked by the SIGHTGLASS LOWER BEZEL, close the beaker ball valve and remove the aluminum couplerfrom the fill/drain valve.

e. The total amount of water now in the beaker represents the total amount of BOILERWATER used during the steady state portion of the run. RECORD VOLUME.

f. STOW MEASUREMENT EQUIPMENT.

4.2.6 STORAGE

The STORAGE checklist prepares the system for an extended period of non-use. This can be anywherefrom overnight to several months. In general, the system needs to be cool, clean and fully drainedbefore being placed into storage. If the system is it be used within the same day, the STORAGEchecklist may be omitted. Resume operation with the PRE-START checklists.

1. The COMPUTER DAQ SYSTEM (data acquisition computer) should be turned OFF, the USBCABLE DISCONNECTED from the DigiDAQ system receptacle on the side panel of the Rank-ineCycler and all COMPUTER DAQ SYSTEM components STOWED for safe keeping.

2. LOAD RHEOSTAT to the FULL COUNTER-CLOCKWISE POSITION for MINIMUM LOAD.

3. LOAD SWITCH to the OFF position.

4. BURNER SWITCH to the OFF position.

5. KEYED MASTER SWITCH to the OFF position. The MASTER SWITCH KEYS should be re-moved and stored in a secure location.

6. OPERATOR PANEL GAS VALVE to the OFF position.

7. FUEL SOURCE REGULATOR to the OFF position.

8. FUEL SOURCE should be DISCONNECTED from the barbed fitting underneath the system.The hose assembly should be STOWED.

9. ELECTRICAL SERVICE to the system should be DISCONNECTED and the CORD STOWED.

10. STEAM ADMISSION VALVE to the fully OPEN position. This vents the system and allows theboiler to be completely drained.

11. For safety and before proceeding further, INSURE EQUIPMENT HAS SUITABLY COOLED FORHANDLING and THERE IS NO BOILER PRESSURE.

Page 53: RankineCycle Operator Manual

“main” — 2005/9/16 — 13:21 — page 41 — #53i

i

i

i

i

i

i

i

NORMAL PROCEDURES 41

12. The BOILER should be DRAINED completely. The BOILER can be quickly drained using thefill/drain valve and beaker assembly. Place the beaker on a firm support lower than the boilerfill/drain valve at the rear of the boiler. Insert the aluminum coupler at the end of the beaker hoseassembly into the fill/drain valve coupling hole. Firmly pressing the coupler into the fill/drainvalve will open the internal valve and allow water to flow out of the boiler. Open the beaker ballvalve to allow water to drain into the beaker. When it appears that no more water is drainingfrom the boiler, close the beaker ball valve and remove the aluminum coupler from the fill/drainvalve. The water collected from this draining operation may be discarded.

13. For protection, the FRONT and REAR BOILER DOORS should be CLOSED and LATCHED.

14. The CONDENSER TOWER should be DRAINED completely.

15. COMPLETE a FINAL CHECK of the system. Clean any accumulated dirt, oil or water fromthe top surfaces as well as the individual components and operator panel. If the system is tobe stored for an extended period of time, breathable covering material such as a cotton sheetshould be placed over the system to prevent the accumulation of dust or dirt in the condensertower and boiler chimney.

16. The RankineCycler should be stored in a SECURED place. For long-term storage, the originalshipping container should be used for security and protection.

Page 54: RankineCycle Operator Manual

“main” — 2005/9/16 — 13:21 — page 42 — #54i

i

i

i

i

i

i

i

42 SECTION 4

4.3 General Guidelines

The following General Guidelines are offered as quick reminders of those items requiring particularattention.

• Read and become familiar with the RankineCycler Operator’s Manual.• Use the provided checklists during every operation.• Mandate the appropriate personal safety equipment for all operators and observers.• Know the facility safety policies, emergency contact numbers and location of fire extinguishers.• Consider all surfaces to be HOT during and for a significant time after operation.• Lock all four caster wheels during operation.• Use only in a well ventilated area.• Continually monitor all system parameters and be attentive for out of limit readings. Immedi-ately stop operation if anything is questionable.

• Remember, the working fluid is high temperature, pressurized steam.

• DO NOT operate the RankineCycler without first becoming familiar with the Operator’sManual.

• DO NOT operate the system unattended.• DO NOT touch any surface during operation.• DO NOT move the system while operating or when the boiler is pressurized.• DO NOT allow the boiler water level to become less than 1.0 in (2.5 cm) as indicated on thesight glass.

• DO NOT attempt to fill the boiler while the system is pressurized.• DO NOT open the boiler doors while hot, doing so may cause permanent warp-age of the boilercradle.

• DO NOT exceed scale readings/limitations on any instrument or gauge.• DO NOT tighten or adjust fittings while system is under pressure.• DO NOT tap on or scratch boiler sight glass.

Page 55: RankineCycle Operator Manual

“main” — 2005/9/16 — 13:21 — page 43 — #55i

i

i

i

i

i

i

i

Section 5Systems

5.1 Steam Turbine System

The RankineCycler Steam Turbine Power System is representative of an actual steam power plantrendered in miniature. Each component faithfully models the full size component in purpose andfunction.

5.1.1 Burner

A forced air gas burner provides the necessary energy to vaporize the liquid working fluid as it passesthrough the boiler. The burner converts chemical energy in the form of gaseous fuel into heat energythat the boiler can use.

An electrically driven centrifugal blower provides combustion air to the burner through a blowerduct. A fuel line is routed through this duct, delivering fuel to a gas mixing nozzle. The fuel and airare further mixed by a vortex disk that introduces turbulence to the flow. Factory calibration of theblower fan optimizes the mass flow rate of air for clean, efficient gas combustion.

Ignition and subsequent combustion of the fuel and air mixture takes place downstream of thevortex dis within the primary flame tube of the boiler. A “hot surface” igniter located in the rearboiler door and at the end of the primary flame tube provides the ignition source. The igniter is aresistance element that glows when current is applied to it. The fuel and air mixture combusts whenit comes in contact with this glowing element producing a flame confined within the primary flametube. Once combustion commences, the flame is self sustaining and the igniter will shut off.

A flame sensor located within the blower duct and adjacent to the vortex disk monitors thepresence of the flame and provides feedback to the microprocessor based gas and ignition controlmodule. Operationally, the control module is designed to energize the gas valve and igniter throughthe feedback loop. The system is a positive shut off design that locks out the gas valve if the burnerdoes not light within a four second ignition period.

Blower operation commences when the BURNER switch is selected ON. A red panel light illumi-nates indicating that the switch is on and that power is available to the blower and the gas controlmodule. The blower starts and begins providing combustion air. The gas control module commandsthe gas valve into a purge condition and then energizes the igniter for a period of 45 seconds. If theburner lights as detected through the flame sensor, the control module will continue energizing the gasvalve as needed to maintain heat for the boiler. If the boiler does not light, it will repeat the processin a second attempt to light the burner. If this second attempt fails, the gas valve will be deenergizedto prevent any further flow of gas. The system will then lock itself out as a safety precaution. Thesystem can only be reset by cycling the BURNER switch.

A boiler pressure transducer regulates a preset boiler pressure by cycling the burner on and off(through the gas control module).

43

Page 56: RankineCycle Operator Manual

“main” — 2005/9/16 — 13:21 — page 44 — #56i

i

i

i

i

i

i

i

44 SECTION 5

A bi-metallic, self resetting switch on the boiler prevents the occurrence of high-temperature boilover by opening the burner circuit should a preset temperature be exceeded.

The burner is attached to the forward boiler door via a flanged fitting on the blower duct. Theblower duct extends an additional length into the boiler and mates with the primary flame tube. Apositive seal between the blower duct and the primary flame tube is achieved through the flame sealring.

5.1.2 Boiler

The boiler facilitates the vaporization of the system working fluid, making it available to the turbinefor power extraction. All boilers provide for some manner of heat transfer between the heat sourceand the system working fluid. The RankineCycler utilizes a firetube or shell type boiler arrangementwhich is representative of over 80% of all boiler systems in use today.

The shell of the boiler is an 8 in (20.3 cm) diameter by 11.5 in (29.2 cm) long stainless steelcylinder. The cylinder holds both the working fluid of the system as well as the high-pressure vaporprior to it exiting to the turbine.

To allow heat transfer, 17 0.5 in diameter (1.3 cm) tubes pass through the cylinder allowing hotcombustion gasses from the burner to “flow through” the boiler. Five of these boiler tubes lie abovethe full water line. A primary flame tube 2 in (5.1 cm) in diameter also passes through the boilerand holds the flame produced by the burner. The walls of the 17 tubes and the primary flame tubeprovide nearly 380 in2 (2,451.6 cm2) of surface area for heat transfer.

Positive pressure provided by both the blower and the expansion of the combustion gasses movesthe hot air through and out of the primary flame tube. The rear boiler door then ducts this airto the 17 through tubes. The combined volume of the 17 through tubes is just under that of theprimary flame tube, insuring an even air flow with maximum surface area contact. The hot air exitsthe through tubes and is ducted by the front boiler door through a vertical stack, exhausting thecombustion gasses up and away from the boiler.

Both the front and rear boiler doors are hinged. Latches secure the doors in the closed positionwhile the system is operating. When the system is not operating and sufficiently cool, the doors maybe unlatched and opened for viewing. The general arrangement of the through tubes and the primaryflame tube can be seen. The rear door holds the hot surface gas igniter while the front door holdsthe blower unit and the exhaust stack. All of these components are plainly visible while the doorsare open. In addition, each door is insulated and contains a refractory material to aid in the properand efficient transfer of heat. For optimum performance, the hot surface gas igniter should not betouched.

Integral to the boiler’s construction are five threaded bosses. These bosses provide a way “in” or“out” of the boiler. They are as follows:

1. Steam Dome Discharge Fitting This fitting allows the vaporized working fluid to exit theboiler and ultimately be used for useful work. This fitting discharges to the boiler pressure gaugeand then the turbine through the steam admission valve.

2. Boiler Vapor Temperature Thermocouple Fitting A thermocouple enters this fitting toprovide the measurement of working fluid vapor temperature.

3. Sight Glass Supply Fitting This fitting supplies the sight glass to indicate the relative levelof water in the boiler.

4. Sight Glass Vent Line / Overpressure Poppet Valve Fitting The sight glass is ventedthrough this fitting back into the boiler. An overpressure safety valve is also located at thisfitting. Should the boiler pressure exceed 130 psi (896 kPa), this valve will open, relieving boilerpressure.

Page 57: RankineCycle Operator Manual

“main” — 2005/9/16 — 13:21 — page 45 — #57i

i

i

i

i

i

i

i

SYSTEMS 45

5. Fill/Drain Valve Fitting This fitting, located on the bottom of the boiler is attached to afill/drain valve that allows the filling and draining of the system working fluid.

The entire boiler shell is insulated with a ceramic blanket to stem heat loss through the boilerwall. An external mantle protects this insulation from damage.

5.1.3 Sight Glass

The sight glass provides an indication of the relative level of working fluid within the boiler. An upperand lower adjustable bezel allow the extents of working fluid to be marked. These markings make iteasy to measure the amount of working fluid consumed during operation of the system.Attached to the bottom of the sight glass is the fill fitting, connecting the sight glass to the boiler

and permitting the boiler working fluid level to show in the sight glass. At the top of the sight glassis a vent fitting that also connects back to the boiler to equalize pressure.The sight glass is not calibrated and only provides an indication of the boiler fluid level. Because

of the curvature of the boiler cylinder and the presence of the through tubes, the level in the sightglass is non-linear over the volume of the boiler.

5.1.4 Boiler Pressure Gauge

An analog pressure gauge is installed providing a direct read out of available boiler pressure. Thegauge indicates the normal range of operation with a white background. The red area of the gaugeindicates pressure conditions that exceed normal operating limitations.

5.1.5 Steam Admission Valve

The steam admission valve is a needle type valve that regulates the flow of steam vapor to the turbine.In the fully clockwise position, the valve is CLOSED preventing the flow of steam. In the fullycounter-clockwise position, the valve is OPEN and the full flow of steam is available to the turbine.Intermediary positions regulate accordingly. In addition to the steam admission valve setting, steamflow is dependent on boiler pressure and temperature.

5.1.6 Steam Turbine

The steam turbine provides useful work through the extraction of energy from the vaporized workingfluid provided by the boiler. High pressure steam is directed through a nozzle, forcing the steam toimpinge directly on the blades of the turbine wheel causing it to rotate. This rotation is then used toderive useful work.The single stage turbine unit is made up of a front and rear housing, each precision machined

and fitted with a carbon bearing requiring no additional oil or lubrication. The front housing holdsa stationary slotted vane guide ring and turbine shroud. The rear housing is ”empty” and serves asa diffuser to the expanding steam upon exiting the turbine. The rotating turbine is centered in thefront housing turbine shroud and rides on a stainless steel shaft supported by the carbon bearings.High pressure steam, as regulated by the steam admission valve, enters the front housing through

a fitting. Directed through the vane guide ring’s six radially spaced nozzles, the steam causes theturbine to rotate by the steam’s momentum reaction on the turbine blades. The steam now expandsand diffuses in the rear housing, exiting through an exhaust fitting directing the steam to the condensertower.In addition to the inlet and outlet fittings in the front and rear housing, respectively, two other

fittings provide transducer access to turbine inlet temperature and pressure as well as turbine outlettemperature and pressure. These values are measured by the data acquisition system and availableat the computer.

Page 58: RankineCycle Operator Manual

“main” — 2005/9/16 — 13:21 — page 46 — #58i

i

i

i

i

i

i

i

46 SECTION 5

5.1.7 Generator

The generator utilizes the rotational motion of the turbine to produce electrical energy. A four-pole,permanent magnet, brushless design, the generator is directly coupled to the output shaft of theturbine and supported on its own set of preloaded ball bearings.Both alternating current (AC) and direct current (DC) are available at the generator outputs.

The AC is as generated, while the DC is produced after having passed through a diode rectifier. Nofiltering, ripple suppression or voltage regulation is provided following rectification.

5.1.8 Condenser Tower

The condenser tower facilitates heat transfer between the hot vapor exiting the turbine and therelatively cool ambient air surrounding the tower. The tower mantle, manufactured from aluminum,provides the heat transfer interface and a condensation surface.Steam enters the condenser tower through a distribution manifold that disperses the steam within

the tower to maximize contact with the mantle. Four internal stainless steel baffles further direct thesteam along the mantle, while allowing condensate to run back to a catchment basin at the bottomof the condenser tower. This basin can be drained, using the attached hose and pinch-clamp, toaccurately measure the amount of condensation collected. Approximately 625 in2 (4,032 cm2) of areais available for heat transfer and condensation formation.

5.1.9 Operator Panel

Various controls and indicators are provided to assist the operator in using the RankineCycler.

1. Keyed Master Switch The key lockable system master switch controls the supply of electricalpower to the main bus that powers the indicator lights, boiler combustion boiler and the gascontrol module. When selected ON, power is available to this main bus. A GREEN indicatorlight will illuminate when this switch is selected ON and power is available to the main bus.The separate steam generator bus is not controlled by this switch.

2. Burner Switch The burner switch enables the gas control module and powers the burnerblower. A RED indicator light will illuminate when this switch is selected ON and power isavailable to the burner circuits. The burner switch only works if the keyed master switch isselected on.

3. Load Switch The load switch enables the load bank. The load bank presents a true load tothe generator, allowing the operator to simulate conditions at a full scale power station whenconsumer demand fluctuates.

4. Load Rheostat Control The load rheostat control varies the amount of load presented to thegenerator. The generator sees this as a true electrical load quantified in terms of resistance,measured in Ohms - Ω. The full counter-clockwise position of the control represents NO LOAD.The full clockwise position of the control represents FULL LOAD. The range of control is linearlyvariable, with NO LOAD equal to 0 Ω and FULL LOAD equal to 100 Ω.

5. Operator Panel Gas Valve The operator panel gas valve regulates the flow of gas to the onboard gas regulator. The burner controller modulates this gas valve internally to provide gaseousfuel to the burner. Rotating the black gas valve knob counter-clockwise to the 3 o’clock positionOPENS the valve. Rotating the valve knob clockwise to the 6 o’clock position CLOSES thevalve and prevents any flow of gas through the regulator. The two valve positions are markedon the face of the regulator near the black gas valve knob. The valve has spring locking detentsthat indicate when the valve is properly positioned in either the open or closed positions.

Page 59: RankineCycle Operator Manual

“main” — 2005/9/16 — 13:21 — page 47 — #59i

i

i

i

i

i

i

i

SYSTEMS 47

6. Amp Meter The amp meter indicates the amount of current the load is drawing based uponthe load (as set by the Load Rheostat Control) and the available voltage (as provided by thegenerator - a function of generator speed/RPM).

7. Volt Meter The volt meter indicate the amount of voltage the generator is providing (a functionof generator speed/RPM).

5.2 Fill/Drain System

The RankineCycler Fill/Drain System allows the convenient, hands free filling of the boiler with anaccurate and repeatable amount of water. A 203 oz (6,000 ml) graduated beaker connects with thefill/drain valve at the rear of the boiler through an attached fill hose, flow valve and aluminum fill/draincoupler. The aluminum coupler is required to open the specially designed fill/drain valve. Thiseliminates the potential of inadvertent boiler opening during positive pressure operation providing thefill/drain system is properly used and the beaker assembly stowed when the system is under pressure.The fill/drain system operates on gravity. Filling or draining the boiler is a matter of locating the

beaker in respect to the level of the boiler fill/drain valve. For filling, and providing the RankineCycleris cool, the beaker can be set in the condenser tower opening.

5.3 Data Acquisition System

The RankineCycler comes equipped with the DigiDAQ precision data acquisition system permittinga full range of system parameter measurement. This system, comprising a suite of sensors, excitationpower sources, signal conditioners, data acquisition hardware and user interface software, when used inconjunction with an appropriate computer, allows actual run-time data to be displayed and recordedfor later analysis. Off the shelf hardware, industry standard software and factory setup and calibrationof the data acquisition system makes data collection a trivial event allowing the educational emphasisto be placed on system operation and analysis.Additional information can be obtained from the respective manufacturer’s equipment and software

manuals contained in the three-ring binder included with the RankineCycler. In the unlikely eventthat data acquisition system software settings or sensor calibration is lost, all factory settings areprovided on CD-ROM for quick data restoration. Additional information regarding default systemsettings can be found in subsequent sections of this chapter.

5.3.1 Computer

The RankineCycler is typically provided with a Microsoft Windows XP Professional based laptopcomputer for portability and system security. Final factory sensor settings are saved to this computeras well as a standard user interface display for initial system familiarization and data collection runs.The computer is equipped with a writable CD-ROM and Ethernet interface to facilitate run-time datadissemination.For maximum flexibility, the system is designed to work with any Windows XP Professional com-

puter equipped with a standard Universal Serial Bus (USB).

5.3.2 DAQ Module

The RankineCycler DigiDAQ System utilizes an IOtech Personal Daq/56 USB Data AcquisitionModule. Featuring 22-bit analog to digital conversion, multiple channels of voltage, thermocouples,pulse, frequency and digital I/O can be measured and controlled. This is accomplished through 20single-ended or 10 differential analog (up to ±20V full scale) or thermocouple input channels, 16programmable ranges, 500V optical isolation, 16 digital I/O lines and four frequency/pulse channels.

Page 60: RankineCycle Operator Manual

“main” — 2005/9/16 — 13:21 — page 48 — #60i

i

i

i

i

i

i

i

48 SECTION 5

The integrated USB connection allows a single cable interface of up to 16 feet (5 meters) betweenthe RankineCycler and the data acquisition computer. This distance is easily increased up to 98 feet(30 meters) through the use of powered USB hubs (serving as data repeaters). The USB’s high-speeddata transfer rate (up to 12Mbits/s) allows for a real-time display of acquired data, while eliminatingthe need for buffer memory in the data acquisition system itself.Unused data channels are available for operator use. With sensors or transducers appropriate to

the variables of interests, interface to the DAQ Module is accomplished through convenient, removablescrew-terminal input connections. Optionally available snap-on expansion DAQ Modules increase thetotal channel capacity to 60 analog or thermocouple channels, 32 digital I/O lines and four frequencyinput channels. USB hubs used in conjunction with multiple DAQ Modules can further increase theavailable channel count to over 8,000 - enough for any conceivable data acquisition need.

5.3.3 Sensors

Ten (10) system parameters are sensor measured with the stock RankineCycler configuration.The basic sensor package includes pressure, temperature and flow sensors measuring parameters

common to Rankine Cycle type analysis. The following list details the measured system parametersand their corresponding physical DAQ Module channel. Table 5.2 provides more detailed informationconcerning channel assignments, installed sensor or transducer type and a listing of all open andavailable DAQ Module channels.

1. Boiler Pressure (physical analog channel PD1 A01) - Boiler vapor pressure.

2. Steam Turbine Inlet Pressure (physical analog input channel PD1 A02) - Turbine vaporpressure immediately prior to the turbine.

3. Steam Turbine Outlet Pressure (physical analog input channel PD1 A03) - Turbine vaporpressure immediately after the turbine.

4. Boiler Pressure (physical analog input channel PD1 A04) - Boiler vapor pressure.

5. Steam Turbine Inlet Temperature (physical analog input channel PD1 A05) - Turbine vaportemperature immediately prior to the turbine.

6. Steam Turbine Outlet Pressure (physical analog input channel PD1 A06) - Turbine vaporpressure immediately after the turbine.

7. Generator Current (Amperage) Output (physical analog input channel PD1 A07) - Gen-erator current output, should correspond to operator panel meter readout.

8. Generator Voltage Output (physical analog input channel PD1 A08) - Generator voltageoutput, should correspond to operator panel meter readout.

9. Fuel Flow (physical analog input channel PD1 A09) - Turbine-based gas flow meter measuresthe volume of gaseous fuel flowing per unit time.

10. Turbine/Generator RPM (physical analog input channel PD1 A10) - Turbine/Generatorrotational speed (in revolutions per minute, RPM) derived from measuring the voltage of thedirect current output voltage as provided by the rotating generator. Generated DC voltage is adirect function of generator speed/RPM.

Page 61: RankineCycle Operator Manual

“main” — 2005/9/16 — 13:21 — page 49 — #61i

i

i

i

i

i

i

i

SYSTEMS 49

Table 5.2: DAQ Channel Assignments and Sensor Details

PHYSICAL SYSTEM SENSOR PHYSICAL SENSORCHANNEL PARAMETER TYPE RANGE OUTPUT

Analog PD1 A01 Boiler Pressure Setra Model 209 0 - 200 (psig) 0.5 - 5.5 VoltsAnalog PD1 A02 Steam Turbine Inlet Pressure Setra Model 209 0 - 25 (psig) 0.5 - 5.5 VoltsAnalog PD1 A03 Steam Turbine Outlet Pressure Setra Model 209 0 - 25 (psig) 0.5 - 5.5 VoltsAnalog PD1 A04 Boiler Temperature K-type thermocouple max 1375 CAnalog PD1 A05 Steam Turbine Inlet Temperature K-type thermocouple max 1375 CAnalog PD1 A06 Steam Turbine Outlet Temperature K-type thermocouple max 1375 CAnalog PD1 A07 Generator Amperage On board voltage 0 - 1.0 Amps 0.0 - 0.05 VoltsAnalog PD1 A08 Generator Voltage On board voltage 0 - 15.0 Volts 0.0 - 15.0 VoltsAnalog PD1 A09 Fuel Flow Dwyer TF2110 0 - 10 ltrs / min 0.0 - 5.0 VoltsAnalog PD1 A10 RPM On board voltage 0 ≈ 5,250 RPM 0.0 - 15.0 Volts

Frequency PD1 F1 OPENFrequency PD1 F2 OPENFrequency PD1 F3 OPENFrequency PD1 F4 OPENDigital PD1 D01 OPENDigital PD1 D02 OPENDigital PD1 D03 OPENDigital PD1 D04 OPENDigital PD1 D05 OPENDigital PD1 D06 OPENDigital PD1 D07 OPENDigital PD1 D08 OPENDigital PD1 D09 OPENDigital PD1 D10 OPENDigital PD1 D11 OPENDigital PD1 D12 OPENDigital PD1 D13 OPENDigital PD1 D14 OPENDigital PD1 D15 OPENDigital PD1 D16 OPEN

Page 62: RankineCycle Operator Manual

“main

”—

2005/9/16—

13:21—

page50—

#62

i

i

i

i

i

i

i

i

50SE

CT

ION

5Table 5.3: Channel Configuration - Analog Input

Physical User Single-ended/ MeasurementChannel Label On Range Units Differential Duration Scale Offset

PD1 A01 B P On -220.0 to 180.0 PSIG Differential 110 ms 40.0 -20.0PD1 A02 T IN P On -220.0 to 180.0 PSIG Differential 110 ms 5.0 -2.5PD1 A03 T OUT P On -55.0 to 45.0 PSIG Differential 110 ms 5.0 -2.5PD1 A04 B T On Type K C Differential 110 ms 1.0 0.0PD1 A05 T IN T On Type K C Differential 110 ms 1.0 0.0PD1 A06 T OUT T On Type K C Differential 110 ms 1.0 0.0PD1 A07 DC - A On -200.0 to 200.0 AMPS Differential 110 ms 20.0 0.0PD1 A08 DC - V On -20.0 to 20.0 VOLTS Differential 110 ms 1.0 0.0PD1 A09 Fuel Flow On -20.0 to 20.0 LTRS/MIN Differential 110 ms 1.6 0.0PD1 A10 RPM On -20.0 to 20.0 RPM Differential 110 ms 350.0 0.0

NOTE: These values represent the default Channel Configuration as set by the factory and should provide satisfactory performance under normalconditions. Scale and Offset values may be changed if recalibration or other engineering units are required. Entering a Scale value of 1.0 andan Offset value of 0.0 on any channel results in the display of raw voltage in the Reading column for that channel. Scale and Offset values arederived from the linear mx+ b transfer function for each sensor relative to the appropriate physical range and voltage output as provided in Table 5.2(PhysicalValue = Scale · Voltage + Offset). The Reading column will only be populated when the data acquisition system is sampling data. It hasbeen omitted from this table for clarity. Chapter 4 of the PersonalDaq UsersManual .pdf contains further information on the Channel ConfigurationWindow.

Page 63: RankineCycle Operator Manual

“main” — 2005/9/16 — 13:21 — page 51 — #63i

i

i

i

i

i

i

i

SYSTEMS 51

5.3.4 Software

The DigiDAQ System utilizes IOtech’s Personal DaqView software for Out-of-the-Box graphical dataacquisition. This software provides an easy-to-use yet powerful data acquisition application that allowsinexperienced users to test, display and record data within minutes of power-up while requiring noprogramming. The software works seamlessly with the IOtech Personal Daq/56 USB Data AcquisitionModule installed in the RankineCycler. Individual channel configuration is accomplished through aspreadsheet type interface. Each channel can be enabled, configured and labeled independently ofall other channels. Sensor output is converted into physical, engineering terms by applying Scaleand Offset values in an mX + b operation. The software allows the creation of customized real-timedisplays using built-in display options including charts, graphs and meters. Each display option canbe independently configured by channel to show instantaneous values, peak hold and trends. Alldisplayed data is easily recorded for later play-back and follow-on analysis. Post-acquisition softwareis also included to facilitate time-domain data viewing of multiple channels. Additional software toenable real-time data acquisition from within Microsoft Excel is also available.The DigiDAQ System is designed to work with other popular software packages including IOtech’s

DASYLab and National Instrument’s LabVIEW. With the appropriate software, advanced data ac-quisition, control and virtual instruments (VI) may be utilized with the installed DigiDAQ System inthe RankineCycler. Application Programming Interface (API) code, documentation and drivers forVisual Basic and C++ for Windows are freely available at the IOtech website.

5.4 Cabinetry

5.4.1 Chassis

The RankineCycler cabinetry is purpose built. Laser cut for precision and powder coated for longlasting durability.

5.4.2 Electrical

Standard outlet service of 120 VAC, 60 Hz (220 VAC, 50 Hz) is the only electrical service necessary tooperate the RankineCycler. Gas regulation and control and the DigiDAQ system electrical require-ments are served internally. No additional external electrical service is required. Computer equipmentor additional operator provided sensors, meters or instrumentation will necessarily require their ownelectrical service as appropriate to the specific equipment used.

5.4.3 Fuel

Fuel is supplied to the RankineCycler through an external source, usually a standard Liquid Propane(LP) bottle typical of the type used for gas grills and portable heating equipment. A fuel source gasregulator and hose assembly is provided with the RankineCycler to make the connection between thefuel source and the on board gas regulator. The provided fuel source gas regulator and hose assemblyare specially calibrated and adjusted to work with each RankineCycler. Any adjustment to thisregulator or deviation from the recommended fuel may result in poor system performance. TurbineTechnologies, LTD should be consulted if any changes are necessary due to local fuel availability.A barbed fitting on the bottom of the RankineCycler provides a convenient and quick method ofattaching the fuel source gas regulator and hose assembly to the on board gas regulator.

5.4.4 Miscellaneous

The RankineCycler cabinetry is fitted with lockable caster wheels to facilitate movement of the systemfor use and storage.

Page 64: RankineCycle Operator Manual

“main” — 2005/9/16 — 13:21 — page 52 — #64i

i

i

i

i

i

i

i

52 SECTION 5

Page 65: RankineCycle Operator Manual

“main” — 2005/9/16 — 13:21 — page 53 — #65i

i

i

i

i

i

i

i

Section 6Service and Maintenance

6.1 General Maintenance

The RankineCycler is designed for continuous educational and research use requiring only a minimalamount of service or maintenance. This section provides information regarding operator conductedroutine service procedures. When any component requires service other than that outlined in thissection, contact Turbine Technologies, LTD for additional assistance.

6.1.1 Cleaning

Keeping the RankineCycler clean and free from dirt, oil and water accumulation is the best way tomaximize the usefulness and efficiency of the system. Typical household, non-flammable and non-abrasive cleaners may be used where appropriate. Non-toxic, biodegradable, “green” or “citrus” typeconcentrated cleaners are particularly well suited for cleaning the RankineCycler where mineral ordirt buildup may occur.

Boiler Periodically flushing with clean, distilled water (fill and empty per normal procedures withoutheating the boiler) will help prevent mineral build up and accumulation. Pay particular attentionto the fill/drain valve area. As this is the lowest point in the system, sediment may collect inand around the fill/drain valve. Rapid opening and closing of the fill/drain valve by insertingand removing the aluminum coupler will help dislodge sediment and insure the fill/drain valveremains clean. DO NOT use any type of cleaner, soap or solvent when flushing the boiler.

Condenser Tower The condenser tower, over time, may acquire a thin film of mineral buildup onthe internal mantle and baffle surfaces depending upon local water conditions. A mild cleanerdilution works well to remove this buildup.

Cabinetry All cabinet surfaces are electrostatically powder coated for maximum surface durability.Mild soap and water should be sufficient for most cleaning needs.

Other Components All system components are manufactured of materials that provide sufficientresistance to corrosion under normal usage. Mild soap and water should be sufficient for mostcleaning needs. Care should be taken to minimize any water or cleaning solution contact withthe generator assembly, particularly the coupling area between the turbine and the generator.Water or cleaning solution usage should be the minimal amount necessary to prevent contactwith the wiring or electrical equipment within the system cabinetry.

6.1.2 Condition Inspection

The prudent operator will make a cursory condition check prior to each and every start up, operationand shutdown cycle of the RankineCycler. At regular intervals, particularly after long term storage

53

Page 66: RankineCycle Operator Manual

“main” — 2005/9/16 — 13:21 — page 54 — #66i

i

i

i

i

i

i

i

54 SECTION 6

or after extended running periods, it is advisable to conduct a more thorough inspection of the entiresystem to insure safety and reliability.

The following points provide a minimal checklist for a periodic Condition Inspection:

1. Cleanliness Keeping the system clean and free from dust and dirt, mineral buildup and waterwill help in readily identifying problems. A regular cleaning helps the operator become morefamiliar with the general arrangement of components and aware when things aren’t as theyshould be.

2. Security of Fittings Ensuring all nuts, bolts, couplings and other areas where two componentsare physically attached are tight and secure will prevent future problems stemming from leakageor wear.

3. Proper Operation Simply monitoring the RankineCycler for operation consistent with themanual will assist in determining if greater problems are imminent.

4. Boiler Door Gaskets The boiler doors are sealed with a fiberglass gasket material. Over time,the material will degrade and begin to pull apart. This is normal. When the condition of thedoor gaskets is such that it no longer appears to be sealing or appears to be rapidly deteriorating,it should be replaced. The material is commonly available at fireplace or plumbing dealers aswell as most industrial supply companies. New gasket material should be positively attached tothe boiler door using high temperature stove and gasket cement or similar material.

5. General Condition Always be observant of the RankineCycler ’s general condition. Lightdamage such as paint chips, scratches or dents may appear minor, but could be hiding moreextensive damage resulting in poor or improper operation of the RankineCycler as a whole.

Exercising common sense is the best action to follow. If something doesn’t “look” or “act” right,there may be a problem. Usage should be delayed until the potential problem can be investigatedand rectified. Always err on the side of caution. This protects the user as well as the machine. TheRankineCycler should be afforded the same respect in operation, maintenance and overall care givento any piece of laboratory grade equipment.

6.1.3 Service Schedule

The design of the RankineCycler eliminates all periodic or reoccurring maintenance outside of thatspecifically listed in Section 6.

Page 67: RankineCycle Operator Manual

“main” — 2005/9/16 — 13:21 — page 55 — #67i

i

i

i

i

i

i

i

SERVICE and MAINTENANCE 55

6.2 Troubleshooting

Troubleshooting information is provided to identify and provide solutions to common operator prob-lems. These problems usually arise from not following the Normal Procedures in their proper order.Use of the included checklists will eliminate the possibility that a necessary step is overlooked orexecuted out of sequence (see Section 4 - Normal Procedures). Review the checklist steps priorto consulting the Troubleshooting tables.

Problems that relate directly to RankineCycler hardware, such as a failed or damaged component,should be directed to the factory for immediate attention. Readily diagnosed problems arising fromloose or broken electrical wires, loose fluid fittings and no or low fuel pressure are generally deferredto the operator for troubleshooting and repair.

Data acquisition hardware and software usage and troubleshooting is covered in greater detailwithin the provided users manuals. See PersonalDaq UsersManual.pdf and PostAcquisition-

Analysis.pdf within the C:\Program Files\pDaqView\Applications\Users Manuals directory ofthe default DAQ software installation.

Operator modifications may adversely effect the overall operation of the system and may preventthe following troubleshooting steps from being effective.

BOILER FILL/DRAINTROUBLE PROBABLE CAUSE REMEDY

Boiler will not drain. Fill/drain valve is not open or sys-tem is under vacuum.

Insert the aluminum fill/drain cou-pler fully into the boiler fill/drainvalve. Turn the steam admis-sion valve fully counter-clockwiseto open the valve and vent the sys-tem.

Boiler will not fill. System is under pressure or thefill/drain valve is not open.

Turn the steam admission valvefully counter-clockwise to open thevalve and vent the system. In-sert the aluminum fill/drain cou-pler fully into the boiler fill/drainvalve.

Boiler will not accept a full 203 oz(6,000 ml) of water.

Boiler was not previously drained. Insure that the boiler was properlydrained prior to filling.

Fill/drain valve does not open.Cannot insert aluminum fill/draincoupler.

Boiler under pressure. Relieve boiler pressure. Allow sys-tem to cool before attempting tofill.

Page 68: RankineCycle Operator Manual

“main” — 2005/9/16 — 13:21 — page 56 — #68i

i

i

i

i

i

i

i

56 SECTION 6

BURNER OPERATIONTROUBLE PROBABLE CAUSE REMEDY

System does not indicate power upwhen MASTER SWITCH is se-lected ON.

No electrical service to system. Verify that electrical service isavailable to the system. Check linepower cord is plugged into wall.Check that all applicable circuitbreakers and other protection de-vices have not been tripped.

Burner does not light whenBURNER SWITCH is selected toON.

Inadequate fuel supply or air in thefuel lines.

Verify that the fuel source is prop-erly attached to the unit. Prop-erly purge the fuel lines per theExpanded Normal Procedures sec-tion.

Burner lights but operates rough,rapidly extinguishing and relight-ing.

Improper fuel to air mixture. If fuel source gas bottle was storedoutside, allow it to warm to roomtemperature and try again. Verifythat there are no leaks in the gasline. Consult factory for instruc-tions on adjusting the blower fanspeed.

GENERAL OPERATIONTROUBLE PROBABLE CAUSE REMEDY

Boiler does not come up to pres-sure.

Steam admission valve not fullyclosed.

Verify that the steam admissionvalve is fully closed and that thereare no leaks in the steam tubing toor from the turbine.

Cannot achieve steady state. Improper preheat. Load rheostatset too high.

The system must be properly pre-heated before a steady state canbe achieved. Steady state will bedifficult to achieve if there is toomuch initial load on the generator.Turn down the load rheostat.

Turbine squeals during operation. Turbine speed is too high. Reduce turbine speed by closingsteam admission valve and/or in-creasing generator load throughthe load rheostat.

Page 69: RankineCycle Operator Manual

“main” — 2005/9/16 — 13:21 — page 57 — #69i

i

i

i

i

i

i

i

SERVICE and MAINTENANCE 57

DATA COLLECTIONTROUBLE PROBABLE CAUSE REMEDY

Computer wont recognize DAQModule.

USB cable not plugged in. Specificdevice not selected.

Make sure USB cable is con-nected between the computer andthe DigiDAQ USB port on theleft side panel before the softwareis started. To select the spe-cific device, select View from theMain Control Window and selectActive Devices... on the dropdown menu. Check the box nextto the serial numbered device.

Channel Configuration Window

appears blank. All sensor settingare gone.

Factory configuration file has beenerased or overwritten.

The required configurationfile is RankineCycler.cfg.A backup copy is located inthe RankineCycler folderon the desktop. COPY

this file to the DAQ Sys-tem directory: C:\ProgramFiles\pDaqView\Applications.Prior to doing this, make surethe PersonalDAQ software isshutdown and the USB cableis connected. If the backupRankineCycler.cfg file cannotbe found, a new configuration filecan be created by manually en-tering the settings from Table 5.3and Table ??. Charts, graphs andmeters will have to be re-created.

Run-time data doesn’t appear tobe saving.

Run-time data is getting over-written.

All run-time data is saved asPDAQ.BIN. Immediately after col-lecting data, copy and renamePDAQ.BIN to another location. Itwill be necessary to first convertthis binary data file to a usable fileformat such as text which is thenreadable by Microsoft Excel andother programs. To do so, fromwithin the Main Control Window,select Tools and then Convert

Binary Data... from the dropdown menu.

Page 70: RankineCycle Operator Manual

“main” — 2005/9/16 — 13:21 — page 58 — #70i

i

i

i

i

i

i

i

58 SECTION 6

6.3 Factory Service

Turbine Technologies, LTD Factory Service Department is available to perform any service requiredon the RankineCycler. Factory trained technicians using only approved parts and the latest productinformation will clean, service and test your system. Our full parts inventory, production toolingand engineering department are available to insure that your RankineCycler is returned in the samecondition as originally delivered.Before sending any Turbine Technologies, LTD product to the factory for service, first email Prod-

uct Technical Support ([email protected]) to verify that there is a true problemwith the system requiring factory service. In many cases, service issues can be handled by the operatorthrough factory direction, eliminating the downtime associated with a factory return.If it is determined that factory service is required, a service information form will be sent for

completion by the operator. Please include this service information form with the system when it isreturned to the factory. Any information that may be beneficial in servicing the system should beincluded on the service information form.To facilitate safe transportation of the system to the factory, ship it in its original factory shipping

container. If the original container is no longer available, other crating may be used provided thesystem is securely packed. Damage caused by poor or inappropriate crating will not be coveredunder warranty. Do not send product documentation, cables, computers, support equipment (beakers,hoses, funnels, etc.) or any user add ons not specifically part of the service concern. Under certaincircumstances, only the actual part or system requiring service needs to be returned.

Page 71: RankineCycle Operator Manual

“main” — 2005/9/16 — 13:21 — page 59 — #71i

i

i

i

i

i

i

i

WARRANTY INFORMATION

RANKINECYCLER WARRANTY

Two Year Warranty

Turbine Technologies, LTD warrants each RankineCycler, of its manufacture, to be free of defects inmaterials and workmanship at time of shipment and to remain in serviceable condition for a periodof two years (24 calendar months) following date of shipment.

In the event of malfunction or failure, purchaser may, at its expense, return the RankineCyclerto Turbine Technologies, LTD for inspection. If, in the sole discretion of Turbine Technologies, LTD,the malfunction or failure resulted from a defect in materials or workmanship, Turbine Technologies,LTD will repair or replace any defective component or assembly.

Specific Exceptions

Specific exceptions to the above section include:

1. This warranty will become void if any person has made an attempt, regardless of extent, to repairor modify the RankineCycler without express written authorization by Turbine Technologies,LTD.

2. This warranty does not apply to any damage resulting from operation outside the publishedoperating limitations found in the Operator’s Manual.

3. The RankineCycler is not offered as and shall not be construed by purchaser, or any agentthereof, as a “Consumer Product” (within the common definition or definitions of the UnitedStates Federal Trade Commission).

4. The RankineCycler is represented to be, and is offered as, experimental technology, subject tothe limitations in performance and safety risks inherent to equipment so classified.

5. The Purchaser and agents thereof shall be solely responsible for determining, prior to purchase,the suitability for any purpose or purposes intended of equipment, services or information offeredor supplied by Turbine Technologies, LTD.

6. This Limited Warranty, as written, constitutes the entire warranty offered or intended, expressedor implied, and is offered in lieu of all other warranties.

7. The Limited Warranty does not apply to “on-board” hardware or software items that are coveredby other OEM warranties.

59

Page 72: RankineCycle Operator Manual

“main” — 2005/9/16 — 13:21 — page 60 — #72i

i

i

i

i

i

i

i

60 APPENDIX A


Top Related