8/10/2019 REC 670 Measurements
1/37
1
AB
B
PowerTechnologiesAB,
2005
2006-03-30 Substation Automation Products Training
Substation
Automation Products
Training
Control IED
REC 670
Measurements
8/10/2019 REC 670 Measurements
2/37
2
AB
B
PowerTechnologiesAB,
2005
2006-03-30 Substation Automation Products Training
Contents
Hardware Measuring Function Blocks
Application Configuration
Signal Matrix
Monitoring and supervision
Signal Monitoring
Local HMI
Exercise
8/10/2019 REC 670 Measurements
3/37
3
ABB
PowerTechnologiesAB,
2005
2006-03-30 Substation Automation Products Training
Hardware - IED670 IEDs
8/10/2019 REC 670 Measurements
4/37
4
ABB
PowerTechnologiesAB,
2005
2006-03-30 Substation Automation Products Training
Hardware Structure - IED670 IEDs
Transformer Input Module6I + 6U, 9I+3U, 6I or 12I TRM1(TRM2)
Analog Digital Conversionmodule ADM1 (ADM2)
Central Processing Unit NUM GPS time synchronization
module GSM (option)
Binary Input / Output modulesBIM, BOM, IOM and MIM
Power supply module PSM
19 rack, 6U high
NUM
IOM
BOM
PSM
TRM1
GSM
AD1
BIM
MIM
BIM
8/10/2019 REC 670 Measurements
5/37
5
ABB
PowerTechnologiesAB,
2005
2006-03-30 Substation Automation Products Training
Transformer input module (TRM)
Isolation barrier preventing
disturbances to enter intoIED670
Adapt measured values to
static circuitry
Up to 12 analog inputs can beconnected
0 - 6 U, 110-220V rated
range 50/60 Hz
6 -12 I, 1A or 5A rated current
Max 2 TRM in each IED
8/10/2019 REC 670 Measurements
6/37
6
ABB
PowerTechnologiesAB,
2005
2006-03-30 Substation Automation Products Training
Analog / Digital conversion Module (ADM)
Mounting position for OEMmodule (only on AD1)
Analog inputs (from TRM)
8/10/2019 REC 670 Measurements
7/377
ABB
PowerTechnologiesAB,
2005
2006-03-30 Substation Automation Products Training
mA input module (MIM)
6 independent input channels
Software selected input ranges
0-5, 0-10, 0-20, mA
1-5, 2-10, 4-20, mA
5, 10, 20 mA
Resolution: 16 bit
Accuracy: 0,1%
Independent settable digital
filters
8/10/2019 REC 670 Measurements
8/378
ABB
PowerTechnologiesAB,
2005
2006-03-30 Substation Automation Products Training
Measuring Function blocks
Power system measurement (in primary values)
Apparent, active and reactive power
Voltage and current
Frequency
Power factor Phase currents
Phase-phase voltages
Sequence quantities (in primary values)
Positive, negative and zero sequence voltages
Positive, negative and zero sequence currents
DC measurement
8/10/2019 REC 670 Measurements
9/379
ABB
PowerTechnologiesAB,
2005
2006-03-30 Substation Automation Products Training
Measuring Function blocksGeneral
Measured information via
Local HMI Service values
Single one-line diagram
Monitoring tool within PCM600 (local or remote)
IEC 61850-8-1 (direct or via MVGGIO)
IEC 60870-103 (via special 103 function blocks)
LON (via Event function blocks (EVxx))
Disturbance function block (DRA4)
Zero point clamping
Input: Group signals (voltage or current)
Measurement supervision
Three Reporting modes
Level supervision output (4 levels)
8/10/2019 REC 670 Measurements
10/3710
A
BB
PowerTechnologiesAB,
2005
2006-03-30 Substation Automation Products Training
Measuring Function blocksService Values (SVRx)
Logical Node: CVMMXU
Max 3 instances 9 measuring modes
use one, two or three voltages,
use pos. seq. voltage
etc
Calibration of analog inputs
Amplitude and angle compensation
Three points (5, 30 and 100 %)
Class 0.5 accuracy Low pass filtering
Compensation facility
Level supervision (xRANG)
8/10/2019 REC 670 Measurements
11/3711
A
BB
PowerTechnologiesAB,
2005
2006-03-30 Substation Automation Products Training
Measuring Function blocksService Values (SVRx)
8/10/2019 REC 670 Measurements
12/3714
A
BB
PowerTechnologiesAB,
2005
2006-03-30 Substation Automation Products Training
Measuring Function blocksVoltage and Current (VPx, CPx)
Logical Node: VMMXU
Max 3 instances
Output: Phase to phase voltages
Calibration of analog inputs
Amplitude and angle compensation
Three points (5, 30 and 100 %) Class 0.5 accuracy
Level supervision (ULxRANG)
Logical Node: CMMXU
Max 10 instances
Output: Phase currents
Calibration of analog inputs
Level supervision (ILxRANG)
8/10/2019 REC 670 Measurements
13/3715
A
BB
PowerTechnologiesAB,
2005
2006-03-30 Substation Automation Products Training
Logical Node: VMSQI
Max 3 instances Output: Positive, negative and zero
sequence voltages
Level supervision (UxRANG)
Measuring Function blocksSequence (VSQx and CSQx)
Logical Node: CMSQI
Max 3 instances
Output: Positive, negative and zero
sequence currents
Level supervision (IxRANG)
8/10/2019 REC 670 Measurements
14/3716
A
BB
PowerTechnologiesAB,
2005
2006-03-30 Substation Automation Products Training
Logical Node: MVGGIO
Max 16 instances Input:
SMMI function block (mA currents)
etc
Level supervision (RANGE)
Measuring Function blocksDC measurement (MVxx)
8/10/2019 REC 670 Measurements
15/3717
A
BB
PowerTechnologiesAB,
2005
2006-03-30 Substation Automation Products Training
Application configuration (CAP531)Pre-processor blocks
SMAI Function Block(Virtual Analog Input Block)
for VOLTAGE measurements
#1
U
8/10/2019 REC 670 Measurements
16/3718
A
BB
PowerTechnologiesAB,
2005
2006-03-30 Substation Automation Products Training
Application configuration (CAP531)Pre-processor blocks
SMAI Function Block
(Virtual Analog Input Block)
for CURRENT measurements
Sum3Ph Function Block
for SUMMATION
Group signals
#2
I
8/10/2019 REC 670 Measurements
17/3719
A
BB
PowerTechnologiesAB,
2005
2006-03-30 Substation Automation Products Training
Application configuration (CAP531)Pre-processor blocks
SMMI Function Block
(Virtual Analog Input Block)for mA measurements
8/10/2019 REC 670 Measurements
18/3720
A
BB
PowerTechnologiesAB,
2005
2006-03-30 Substation Automation Products Training
Configuration of Analog Inputs in CAP531
Function blocks using
analog signals is configured in
CAP531
-Group signals
-Sampled signals
8/10/2019 REC 670 Measurements
19/3721
A
BB
PowerTechnologiesAB,
2005
2006-03-30 Substation Automation Products Training
PCM600, Signal Matrix Tool and Application configuration
Inputs/Outputs in CAP531 are hardware independent
8/10/2019 REC 670 Measurements
20/3722
A
BB
PowerTechnologiesAB,
2005
2006-03-30 Substation Automation Products Training
PCM600 and Signal Matrix Tool (SMT)
SMT is the tool to define relationship
between VIRTUAL INPUT/OUTPUT signals
(Analog and or Digital) and REAL
INPUT/OUTPUT signals (Analog or Digital).
8/10/2019 REC 670 Measurements
21/3723
A
BB
PowerTechnologiesAB,
2005
2006-03-30 Substation Automation Products Training
SMT: Virtual and Real Analog Inputs
CAP531 view:
Virtual analog input
Hardware:
TRM
8/10/2019 REC 670 Measurements
22/3724
A
BB
PowerTechnologiesAB,
2005
2006-03-30 Substation Automation Products Training
SMT: Virtual and Real mAmpere Inputs
CAP531 view:
Virtual mA input
Hardware:
MIM
8/10/2019 REC 670 Measurements
23/3725
A
BB
PowerTechnologiesAB,
2005
2006-03-30 Substation Automation Products Training
Monitoring
Measurement supervision applies to different measuringfunction blocks
Service values xMMXU
S, P, Q, U, I, ILx and ULxy-ULyz
Sequence Components xMSQI
Positive, Negative and Zero sequence quantities
Generic measured values MVGGIO For instance mA-input signals
Reporting modes:
Cyclic reporting
Amplitude dead-band supervision
Integrated dead-band supervision
8/10/2019 REC 670 Measurements
24/3726
A
BB
PowerTechnologiesAB,
2005
2006-03-30 Substation Automation Products Training
MonitoringCyclic reporting
8/10/2019 REC 670 Measurements
25/37
27
A
BB
PowerTechnologiesAB,
2005
2006-03-30 Substation Automation Products Training
MonitoringAmplitude dead-band supervision
8/10/2019 REC 670 Measurements
26/37
28
A
BB
PowerTechnologiesAB,
2005
2006-03-30 Substation Automation Products Training
MonitoringIntegrating dead-band supervision
8/10/2019 REC 670 Measurements
27/37
29
A
BB
PowerTechnologiesAB,
2005
2006-03-30 Substation Automation Products Training
MonitoringReporting, Settings
8/10/2019 REC 670 Measurements
28/37
30
ABB
PowerTechnologiesAB,
2005
2006-03-30 Substation Automation Products Training
MonitoringSupervision levels
8/10/2019 REC 670 Measurements
29/37
31
ABB
PowerTechnologiesAB,
2005
2006-03-30 Substation Automation Products Training
MonitoringSupervision levels AC-signals, Settings
8/10/2019 REC 670 Measurements
30/37
32
ABB
PowerTechnologiesAB,
2005
2006-03-30 Substation Automation Products Training
MonitoringSupervision levels mA-signals, Settings
8/10/2019 REC 670 Measurements
31/37
33
ABB
PowerTechnologiesAB,
2005
2006-03-30 Substation Automation Products Training
MonitoringExpander block (XPxx)
Logical Node: --
Max 66 instances Input: xRANGE, Integer
Output: Binary signal
8/10/2019 REC 670 Measurements
32/37
34
ABB
PowerTechnologiesAB,
2005
2006-03-30 Substation Automation Products Training
PCM600 and Signal Monitoring
8/10/2019 REC 670 Measurements
33/37
35
ABB
PowerTechnologiesAB,
2005
2006-03-30 Substation Automation Products Training
Signal Monitoring
Presentation in primary values of
measured/calculated quantities delivered byMeasuring Function blocks
Service Values xMMXU
Sequence components xMSQI
(Binary I/O BIM, BOM and IOM)
Online monitoring Automatic or Manual refresh
8/10/2019 REC 670 Measurements
34/37
36
ABB
PowerTechnologiesAB,
2005
2006-03-30 Substation Automation Products Training
Signal Monitoring
Service ValuesS, P, Q, I, U, Pf and f
Phase values
IL13, UL1231
Sequential values
I1, I2, 3I0, U1, U2 and 3U0
8/10/2019 REC 670 Measurements
35/37
37
ABB
PowerTechnologiesAB,
2005
2006-03-30 Substation Automation Products Training
Local HMI
Measured values may be presented: on the Single Line Diagram
(Control Screen) on medium
sized LCD
in the HMI-tree sub menu
C on t o l cS
N o r t C o n nh e c t i o n2 0 0 4 - 1 2 1- 7 0 8 : 3 7
r r e e n
hu t P oS tio n 4 0 0 kV OHL
BB1
BB2
QB 1 QB2
QC1
QC2
QA1
QB9
L a D i us r b ant c e
Re c 6# 2 0 0 4 - 1 2 1- 6 1 2 : 4 30 : 5 7 . 3 4 9
s t
F a l aot t i o ncu l : 2 4 0 . 5 km
011 TOC1 - TR I P
012 TR I P - TR I P
0 2 5 Z M1 - S T L 1
4 2 1 k V
kV0
kV0
A0
C9Q
o f f - >on
o f f - >on
o f f - >on
0
Do you want to
close QC1?
Measurement
Monitoring
Service Values
Current Phasors
Voltage Phasors
Current Sequence Components
Voltage Sequence Components
8/10/2019 REC 670 Measurements
36/37
38
ABB
PowerTechnologiesAB,
2005
2006-03-30 Substation Automation Products Training
Exercise time
Exercise 6-8
Measurements engineering
8/10/2019 REC 670 Measurements