RF-RXS-B
SonNet Wireless Receiver BACnet IP Issue Number: 7.0
Date of Issue: 13/03/2017
Four Elms Road Edenbridge
Kent TN8 6AB UK
Features & Benefits
Sensing and controlling without the need of structural cabling
Minimal downtime and costs for installation
Seamless integration into BACnet IP over Ethernet
DIN-rail mounted
Easy to install and commission
Technical Overview
The RF-RXS-B SonNet Wireless receiver allows quick and seamless integration of SonNet devices into building management systems. It automatically
maps data from SonNet end devices into BACnet objects which are transmitted via the vendor independent BACnet IP communication protocol,
using a simple web browser interface. Depending on the layout of the SonNet network it can connect up to 40 nodes. Please see the System User
manual for more information.
The receiver collects data from all other devices on the wireless network, including measurements from sensors, link quality, battery levels for all
battery powered devices, hours run for all devices and the current status of all devices.
Specification
Radio Output 2.4 GHz, 16 channels automatically
selected
Direct-sequence spread spectrum
Compliance IEEE802.15.4-2006
Aerial Characteristics Gain 3.0dBi
VSWR <2:1
Data encryption AES 128
Power supply 24Vdc ±15%
24Vac ±15%, 50/60Hz
Communication: USB 2.0
RJ45 Ethernet (for BACnet IP protocol)
configured with Auto-MDI-X for 10/100
Mb/s
BIBBs supported:
DS-RP-B
DS-WP-B
DM-DDB-B
DM-DOB-B
DM-DCC-B
DS-RPM-B
DM-RD-B
Environmental:
Operating Temp. -10 to +50˚C
Operating RH 0-90%, non-condensing
Storage Temp -10 to +80˚C
Storage RH 0-90%, non-condensing
Dimensions 100 x 95 x 65mm
Weight 150g
Country of origin UK
The RF-RXS-B referred to in this data sheet meet the requirements of
EU Directive 2014/30/EU
Product Codes
RF-RXS-B SonNet Wireless Receiver BACnet IP
Accessories
RF-AERIAL-PM2 Coaxial extension cable for externally mounted
aerial – 2m length
RF-AERIAL-PM5 Coaxial extension cable for externally mounted
aerial – 5m length
WEEE Directive:
At the end of the products useful life please dispose
as per the local regulations.
Do not dispose of with normal household waste.
Do not burn.
Tel: +44 (0)1732 861200 - E-mail: [email protected] - Web: www.sontay.com
© 2017 Sontay Limited. All rights reserved
Page 2 of 26
RF-RXS-B
SonNet Wireless Receiver BACnet IP Issue Number: 7.0
Date of Issue: 13/03/2017
Four Elms Road Edenbridge
Kent TN8 6AB UK
How it works
These receivers are used in conjunction with the Sontay RF-IOM, RF-RR and RF-RS radio sensors and IO modules.
Routers are used to route signals from battery powered nodes and other routers to the receiver module, where the signal strength
of a direct path is not sufficient for reliable communications. Note that RF-IOMs also have full router functionality.
Data is transmitted back to the receiver at configurable time intervals, or on a configurable change in measured value. Each sensor
retains these configurations if the battery becomes discharged or requires replacement.
The receiver automatically selects which of the 16 transmission channels available gives the best radio network performance, taking
into account both signal strength and interference levels from adjacent channels and equipment (such as Wi-Fi etc.)
The sensors and routers automatically find the best path back to the receiver, which may be directly to the receiver or via “parent”
routers or RF-IOM modules.
NB The receiver can support a maximum of 16 directly connected “children”, a maximum of 12 of which can be battery powered
“end devices”. Each router or RF-IOM module can support a maximum of 16 directly connected “children”, a maximum of 8 of
which can be battery powered “end devices”. Consideration should be given on network planning for redundancy in case of router
failure or damage. A maximum of 40 devices (excl. the receiver) can be mapped into BACnet IP.
Installation
1. Remove all packaging from the network receiver and note the MAC address printed on the affixed label.
2. Mount the network receiver in the required position (this will have been determined by the site survey tool, (see the quick
start guide and manual for further details), taking care not to site the receiver, and more importantly the aerial, behind
any obstruction likely to impede the radio signal.
3. Fix the receiver to the DIN rail.
NB If the receiver is to be mounted in a metal enclosure, it is essential that the aerial is mounted externally. A 2 or 5m
coaxial extension cable assembly is available for this option.
4. Ensure the antenna is positioned in a vertical alignment.
5. Observe correct polarity if using a 24Vdc power supply.
6. Commissioning of the SonNet wireless network is accomplished using CMS (Configuration and Monitoring Software).
7. Mapping of all BACnet devices and points is accomplished via the receiver’s built-in web browser interface. The default IP
address is 192.168.1.227.
Note
If the USB port is connected (for commissioning with CMS), the Ethernet port is disabled. Ensure the USB port is disconnected
before attempting to communicate via the Ethernet port.
A full user guide is supplied with each new network receiver and is also available at www.sontay.com
Tel: +44 (0)1732 861200 - E-mail: [email protected] - Web: www.sontay.com
© 2017 Sontay Limited. All rights reserved
Page 3 of 26
RF-RXS-B
SonNet Wireless Receiver BACnet IP Issue Number: 7.0
Date of Issue: 13/03/2017
Four Elms Road Edenbridge
Kent TN8 6AB UK
Electrical connections
Note: The Ethernet is configured to use Auto-MDI-X for 10/100 Mb/s. It should be able to connect to any 10/100 10base-T device,
either through a switch or directly to the device without the need for a crossover cable. The Ethernet standard specifies that the
maximum 10base-T cable distance is 100 meters.
Default home screen for the RF-RXS-B
RF-RXS-B®
So
nN
et
Sta
tus
Data
Reset
0V 24V
Sta
tus
BA
Cn
et
Devic
eR
ein
itia
lize
Aerial LED indication
Power supply
LED indication Button
Button USB Connector RJ45 Ethernet
LED indication
- SonNet Status: ON if there is at least one
child node connected on the wireless
network, flashes once per second if there are
no child nodes present.
- Data: Blinking up each time data on the
wireless network is received or sent.
- BACnet Status: Blinking each time data on the
BACnet network is received or sent.
Push buttons
- Reinitialize Device: Resets the Ethernet IP
address to the factory default of 192.168.1.227.
Note it does not affect the Ethernet MAC
address or the device BACnet instance
- Reset: Resets the wireless network at the
receiver. For a short time, until nodes re-join
the network, LED D100 will flash once per
second.
Tel: +44 (0)1732 861200 - E-mail: [email protected] - Web: www.sontay.com
© 2017 Sontay Limited. All rights reserved
Page 4 of 26
RF-RXS-B
SonNet Wireless Receiver BACnet IP Issue Number: 7.0
Date of Issue: 13/03/2017
Four Elms Road Edenbridge
Kent TN8 6AB UK
Changing IP settings
1. From the Home page, click on the BACnet/IP Settings link
2. Change the IP address, the IP subnet mask and the IP gateway, if required. Click the appropriate “Update” button.
3. Change the Device Instance if required. Note that the last 3 digits of the device instance form the BACnet device address
(005 in the example above). Click the appropriate “Update” button.
4. Change the Device Location if required. Click the appropriate “Update” button.
5. Change the BACnet/IP UDP port number if required. Click the appropriate “Update” button.
6. Note – changing the settings values may require the RF-RXS-B to be rebooted.
Mapping SonNet Points to BACnet Objects:
1. From the Home page, click on the BACnet/IP Settings link
A list of SonNet devices, including the receiver, will appear. Note that only the last 8 characters of the SonNet device
MAC addresses are displayed.
2. Click the “Map Device” button to add the BACnet points for each required SonNet device.
Tel: +44 (0)1732 861200 - E-mail: [email protected] - Web: www.sontay.com
© 2017 Sontay Limited. All rights reserved
Page 5 of 26
RF-RXS-B
SonNet Wireless Receiver BACnet IP Issue Number: 7.0
Date of Issue: 13/03/2017
Four Elms Road Edenbridge
Kent TN8 6AB UK
BACnet PICS
This document contains the BACnet Protocol Implementation Conformance Statement (PICS) and BACnet®
Interoperability Building Blocks (BIBBs) for the SonNet BACnet/IP Receiver as required by the American National
Standards Institute/ American Society of Heating, Refrigerating, and Air-Conditioning Engineers (ANSI/ASHRAE)
Standard 135-2012, BACnet protocol. BACnet interoperability building blocks are collections of one or more BACnet
services. This document includes a listing of the BIBBs currently supported by this device.
The SonNet BACnet/IP Receiver is a native BACnet-Application Specific Controller (B-ASC) with BACnet/IP
capabilities.
Product Description
The SonNet devices (wireless) communicate to this Receiver, where the data is received and is modeled by various
BACnet objects. The BACnet application, running on the Receiver, will automatically model the SonNet device data to
BACnet objects, and will update the Present_Value of each object with data from the SonNet.
BACnet Requirements:
BACnet Standardized Device Profile (Annex L)
BACnet Operator Workstation (B-OWS)
BACnet Building Controller (B-BC)
BACnet Advanced Application Controller (B-AAC)
X BACnet Application Specific Controller (B-ASC)
BACnet Smart Sensor (B-SS)
BACnet Smart Actuator (B-SA)
BACnet Interoperability Building Blocks (BIBBs) (Annex K)
The table below lists all the BIBBs that are required for the BACnet Application Specific Controller (B-ASC) profile. The
BIBBS that are not required for B-ASC Profile but supported in this product are also listed.
Application Services (B-ASC) BIBB
Data Sharing - Read Property - B DS-RP-B
Data Sharing - Write Property - B DS-WP-B
Device Management - Dynamic Device Binding - B DM-DDB-B
Device Management - Dynamic Object Binding - B DM-DOB-B
Device Management - Device Communication Control - B DM-DCC-B
Data Sharing - Read Property Multiple - B DS-RPM-B
Device Management - Reinitialize Device - B DM-RD-B
Tel: +44 (0)1732 861200 - E-mail: [email protected] - Web: www.sontay.com
© 2017 Sontay Limited. All rights reserved
Page 6 of 26
RF-RXS-B
SonNet Wireless Receiver BACnet IP Issue Number: 7.0
Date of Issue: 13/03/2017
Four Elms Road Edenbridge
Kent TN8 6AB UK
Standard Device Binding Methods Supported
The table below lists all the standard Device Binding methods supported by this device.
Send Who-Is, receive I-Am (BIBB DM-DDB-A)
X Receive Who-Is, send I-Am (BIBB DM-DDB-B)
Send Who-Has, receive I-Have (BIBB DM-DOB-A)
X Receive Who-Has, send I-Have (BIBB DM-DOB-B)
Manual configuration of recipient device's network number and MAC address
None of the above
Standard Object Types Supported
The following is a list of the standard object types, as defined by ASHRAE, that are currently supported by this
product. This section includes object type details.
Analog Input Object Type
Dynamically creatable using BACnet's CreateObject service? No
Dynamically deletable using BACnet's DeleteObject service? No
Property Identifier Writable Required Optional Property Data
Object_Identifier No X ANALOG INPUT #
Object_Name Yes X "Temperature"
Object_Type No X ANALOG INPUT
Present_Value No X Temperature in Degrees Celsius
Status_Flags No X {FALSE,FALSE,FALSE,FALSE}
Event_State No X {NORMAL}
Out_Of_Service No X FALSE
Units No X Degrees Celsius
Reliability No X no-fault-detected
Property Identifier Writable Required Optional Property Data
Object_Identifier No X ANALOG INPUT #
Object_Name Yes X "Humidity"
Tel: +44 (0)1732 861200 - E-mail: [email protected] - Web: www.sontay.com
© 2017 Sontay Limited. All rights reserved
Page 7 of 26
RF-RXS-B
SonNet Wireless Receiver BACnet IP Issue Number: 7.0
Date of Issue: 13/03/2017
Four Elms Road Edenbridge
Kent TN8 6AB UK
Object_Type No X ANALOG INPUT
Present_Value No X Relative Humidity in Percent
Status_Flags No X {FALSE,FALSE,FALSE,FALSE}
Event_State No X {NORMAL}
Out_Of_Service No X FALSE
Units No X Percent Relative Humidity
Reliability No X no-fault-detected
Property Identifier Writable Required Optional Property Data
Object_Identifier No X ANALOG INPUT #
Object_Name Yes X "CO2"
Object_Type No X ANALOG INPUT
Present_Value No X CO2 in Parts Per Million
Status_Flags No X {FALSE,FALSE,FALSE,FALSE}
Event_State No X {NORMAL}
Out_Of_Service No X FALSE
Units No X Parts Per Million
Reliability No X no-fault-detected
Property Identifier Writable Required Optional Property Data
Object_Identifier No X ANALOG INPUT #
Object_Name Yes X "Setpoint"
Object_Type No X ANALOG INPUT
Present_Value No X Setpoint in Percent
Status_Flags No X {FALSE,FALSE,FALSE,FALSE}
Event_State No X {NORMAL}
Out_Of_Service No X FALSE
Units No X Percent
Reliability No X no-fault-detected
Tel: +44 (0)1732 861200 - E-mail: [email protected] - Web: www.sontay.com
© 2017 Sontay Limited. All rights reserved
Page 8 of 26
RF-RXS-B
SonNet Wireless Receiver BACnet IP Issue Number: 7.0
Date of Issue: 13/03/2017
Four Elms Road Edenbridge
Kent TN8 6AB UK
Property Identifier Writable Required Optional Property Data
Object_Identifier No X ANALOG INPUT #
Object_Name Yes X "Ch.x Measurement"
Object_Type No X ANALOG INPUT
Present_Value No X Measurement in Milliamperes, Volts,
Ohms, or VFC count
Status_Flags No X {FALSE,FALSE,FALSE,FALSE}
Event_State No X {NORMAL}
Out_Of_Service No X FALSE
Units No X Milliamperes, Volts, Ohms, or no units.
Reliability No X no-fault-detected
Analog Value Object Type
Dynamically creatable using BACnet's CreateObject service? No
Dynamically deletable using BACnet's DeleteObject service? No
Property Identifier Writable Required Optional Property Data
Object_Identifier No X ANALOG VALUE #
Object_Name Yes X “RF Channel”
Object_Type No X ANALOG VALUE
Present_Value No X RF Channel number
Status_Flags No X {FALSE,FALSE,FALSE,FALSE}
Event_State No X {NORMAL}
Out_Of_Service No X FALSE
Units No X No units
Reliability No X no-fault-detected
Property Identifier Writable Required Optional Property Data
Object_Identifier No X ANALOG VALUE #
Object_Name Yes X “Runtime”
Object_Type No X ANALOG VALUE
Tel: +44 (0)1732 861200 - E-mail: [email protected] - Web: www.sontay.com
© 2017 Sontay Limited. All rights reserved
Page 9 of 26
RF-RXS-B
SonNet Wireless Receiver BACnet IP Issue Number: 7.0
Date of Issue: 13/03/2017
Four Elms Road Edenbridge
Kent TN8 6AB UK
Present_Value No X Runtime in hours
Status_Flags No X {FALSE,FALSE,FALSE,FALSE}
Event_State No X {NORMAL}
Out_Of_Service No X FALSE
Units No X Hours
Reliability No X no-fault-detected
Property Identifier Writable Required Optional Property Data
Object_Identifier No X ANALOG VALUE #
Object_Name Yes X “Battery Runtime”
Object_Type No X ANALOG VALUE
Present_Value No X Runtime in hours
Status_Flags No X {FALSE,FALSE,FALSE,FALSE}
Event_State No X {NORMAL}
Out_Of_Service No X FALSE
Units No X Hours
Reliability No X no-fault-detected
Property Identifier Writable Required Optional Property Data
Object_Identifier No X ANALOG VALUE #
Object_Name Yes X "Parent LQI"
Object_Type No X ANALOG VALUE
Present_Value No X Link Quality in Percent
Status_Flags No X {FALSE,FALSE,FALSE,FALSE}
Event_State No X {NORMAL}
Out_Of_Service No X FALSE
Units No X Percent
Reliability No X no-fault-detected
Property Identifier Writable Required Optional Property Data
Object_Identifier No X ANALOG VALUE #
Tel: +44 (0)1732 861200 - E-mail: [email protected] - Web: www.sontay.com
© 2017 Sontay Limited. All rights reserved
Page 10 of 26
RF-RXS-B
SonNet Wireless Receiver BACnet IP Issue Number: 7.0
Date of Issue: 13/03/2017
Four Elms Road Edenbridge
Kent TN8 6AB UK
Object_Name Yes X "Sensor Measurement Interval"
Object_Type No X ANALOG VALUE
Present_Value No X Interval in Seconds
Status_Flags No X {FALSE,FALSE,FALSE,FALSE}
Event_State No X {NORMAL}
Out_Of_Service No X FALSE
Units No X Seconds
Reliability No X no-fault-detected
Property Identifier Writable Required Optional Property Data
Object_Identifier No X ANALOG VALUE #
Object_Name Yes X "Temperature COV"
Object_Type No X ANALOG VALUE
Present_Value No X Temperature in Degrees Celsius
Status_Flags No X {FALSE,FALSE,FALSE,FALSE}
Event_State No X {NORMAL}
Out_Of_Service No X FALSE
Units No X Degrees Celsius
Reliability No X no-fault-detected
Property Identifier Writable Required Optional Property Data
Object_Identifier No X ANALOG VALUE #
Object_Name Yes X "Humidity COV"
Object_Type No X ANALOG VALUE
Present_Value No X Relative Humidity in Percent
Status_Flags No X {FALSE,FALSE,FALSE,FALSE}
Event_State No X {NORMAL}
Out_Of_Service No X FALSE
Units No X Percent Relative Humidity
Reliability No X no-fault-detected
Tel: +44 (0)1732 861200 - E-mail: [email protected] - Web: www.sontay.com
© 2017 Sontay Limited. All rights reserved
Page 11 of 26
RF-RXS-B
SonNet Wireless Receiver BACnet IP Issue Number: 7.0
Date of Issue: 13/03/2017
Four Elms Road Edenbridge
Kent TN8 6AB UK
Property Identifier Writable Required Optional Property Data
Object_Identifier No X ANALOG VALUE #
Object_Name Yes X "CO2 COV"
Object_Type No X ANALOG VALUE
Present_Value No X CO2 in Parts Per Million
Status_Flags No X {FALSE,FALSE,FALSE,FALSE}
Event_State No X {NORMAL}
Out_Of_Service No X FALSE
Units No X Parts Per Million
Reliability No X no-fault-detected
Property Identifier Writable Required Optional Property Data
Object_Identifier No X ANALOG VALUE #
Object_Name Yes X "Setpoint COV"
Object_Type No X ANALOG VALUE
Present_Value No X Setpoint in Percent
Status_Flags No X {FALSE,FALSE,FALSE,FALSE}
Event_State No X {NORMAL}
Out_Of_Service No X FALSE
Units No X Percent
Reliability No X no-fault-detected
Property Identifier Writable Required Optional Property Data
Object_Identifier No X ANALOG VALUE #
Object_Name Yes X "PIR Off Delay"
Object_Type No X ANALOG VALUE
Present_Value No X Off-Delay in Seconds
Status_Flags No X {FALSE,FALSE,FALSE,FALSE}
Event_State No X {NORMAL}
Tel: +44 (0)1732 861200 - E-mail: [email protected] - Web: www.sontay.com
© 2017 Sontay Limited. All rights reserved
Page 12 of 26
RF-RXS-B
SonNet Wireless Receiver BACnet IP Issue Number: 7.0
Date of Issue: 13/03/2017
Four Elms Road Edenbridge
Kent TN8 6AB UK
Out_Of_Service No X FALSE
Units No X Seconds
Reliability No X no-fault-detected
Property Identifier Writable Required Optional Property Data
Object_Identifier No X ANALOG VALUE #
Object_Name Yes X "VFC Count"
Object_Type No X ANALOG VALUE
Present_Value No X VFC Count
Status_Flags No X {FALSE,FALSE,FALSE,FALSE}
Event_State No X {NORMAL}
Out_Of_Service No X FALSE
Units No X No units
Reliability No X no-fault-detected
Property Identifier Writable Required Optional Property Data
Object_Identifier No X ANALOG VALUE #
Object_Name Yes X "Ch.x Output"
Object_Type No X ANALOG VALUE
Present_Value Yes X 0-10 Volts
Status_Flags No X {FALSE,FALSE,FALSE,FALSE}
Event_State No X {NORMAL}
Out_Of_Service No X FALSE
Units No X Volts
Reliability No X no-fault-detected
Property Identifier Writable Required Optional Property Data
Object_Identifier No X ANALOG VALUE #
Object_Name Yes X "Measurement Interval"
Object_Type No X ANALOG VALUE
Tel: +44 (0)1732 861200 - E-mail: [email protected] - Web: www.sontay.com
© 2017 Sontay Limited. All rights reserved
Page 13 of 26
RF-RXS-B
SonNet Wireless Receiver BACnet IP Issue Number: 7.0
Date of Issue: 13/03/2017
Four Elms Road Edenbridge
Kent TN8 6AB UK
Present_Value No X Interval in Seconds
Status_Flags No X {FALSE,FALSE,FALSE,FALSE}
Event_State No X {NORMAL}
Out_Of_Service No X FALSE
Units No X Seconds
Reliability No X no-fault-detected
Property Identifier Writable Required Optional Property Data
Object_Identifier No X ANALOG VALUE #
Object_Name Yes X "Ch.x Input COV"
Object_Type No X ANALOG VALUE
Present_Value No X 0-10 Volts
Status_Flags No X {FALSE,FALSE,FALSE,FALSE}
Event_State No X {NORMAL}
Out_Of_Service No X FALSE
Units No X Volts
Reliability No X no-fault-detected
Property Identifier Writable Required Optional Property Data
Object_Identifier No X ANALOG VALUE #
Object_Name Yes X "Ch.x Upper Alarm"
Object_Type No X ANALOG VALUE
Present_Value No X 0-10 Volts
Status_Flags No X {FALSE,FALSE,FALSE,FALSE}
Event_State No X {NORMAL}
Out_Of_Service No X FALSE
Units No X Volts
Reliability No X no-fault-detected
Property Identifier Writable Required Optional Property Data
Tel: +44 (0)1732 861200 - E-mail: [email protected] - Web: www.sontay.com
© 2017 Sontay Limited. All rights reserved
Page 14 of 26
RF-RXS-B
SonNet Wireless Receiver BACnet IP Issue Number: 7.0
Date of Issue: 13/03/2017
Four Elms Road Edenbridge
Kent TN8 6AB UK
Object_Identifier No X ANALOG VALUE #
Object_Name Yes X "Ch.x Lower Alarm"
Object_Type No X ANALOG VALUE
Present_Value No X 0-10 Volts
Status_Flags No X {FALSE,FALSE,FALSE,FALSE}
Event_State No X {NORMAL}
Out_Of_Service No X FALSE
Units No X Volts
Reliability No X no-fault-detected
Property Identifier Writable Required Optional Property Data
Object_Identifier No X ANALOG VALUE #
Object_Name Yes X "Ch.x Output COV"
Object_Type No X ANALOG VALUE
Present_Value No X 0-10 Volts
Status_Flags No X {FALSE,FALSE,FALSE,FALSE}
Event_State No X {NORMAL}
Out_Of_Service No X FALSE
Units No X Volts
Reliability No X no-fault-detected
Property Identifier Writable Required Optional Property Data
Object_Identifier No X ANALOG VALUE #
Object_Name Yes X "Ch.x Output Fallback
Object_Type No X ANALOG VALUE
Present_Value Yes X 0-10 Volts
Status_Flags No X {FALSE,FALSE,FALSE,FALSE}
Event_State No X {NORMAL}
Out_Of_Service No X FALSE
Units No X Volts
Tel: +44 (0)1732 861200 - E-mail: [email protected] - Web: www.sontay.com
© 2017 Sontay Limited. All rights reserved
Page 15 of 26
RF-RXS-B
SonNet Wireless Receiver BACnet IP Issue Number: 7.0
Date of Issue: 13/03/2017
Four Elms Road Edenbridge
Kent TN8 6AB UK
Reliability No X no-fault-detected
Binary Input Object Type
Dynamically creatable using BACnet's CreateObject service? No
Dynamically deletable using BACnet's DeleteObject service? No
Property Identifier Writable Required Optional Property Data
Object_Identifier No X BINARY INPUT #
Object_Name No X "Online Status"
Object_Type No X BINARY INPUT
Present_Value No X Active=Online, or Inactive=Offline
Status_Flags No X {FALSE,FALSE,FALSE,FALSE}
Event_State No X {NORMAL}
Out_Of_Service No X FALSE
Polarity No X Normal Polarity
Reliability No X no-fault-detected
Property Identifier Writable Required Optional Property Data
Object_Identifier No X BINARY INPUT #
Object_Name No X "Momentary Switch"
Object_Type No X BINARY INPUT
Present_Value No X Active=Closed, or Inactive=Open
Status_Flags No X {FALSE,FALSE,FALSE,FALSE}
Event_State No X {NORMAL}
Out_Of_Service No X FALSE
Polarity No X Normal Polarity
Reliability No X no-fault-detected
Property Identifier Writable Required Optional Property Data
Object_Identifier No X BINARY INPUT #
Tel: +44 (0)1732 861200 - E-mail: [email protected] - Web: www.sontay.com
© 2017 Sontay Limited. All rights reserved
Page 16 of 26
RF-RXS-B
SonNet Wireless Receiver BACnet IP Issue Number: 7.0
Date of Issue: 13/03/2017
Four Elms Road Edenbridge
Kent TN8 6AB UK
Object_Name No X "VFC Input"
Object_Type No X BINARY INPUT
Present_Value No X Active=Enabled, or Inactive=Disabled
Status_Flags No X {FALSE,FALSE,FALSE,FALSE}
Event_State No X {NORMAL}
Out_Of_Service No X FALSE
Polarity No X Normal Polarity
Reliability No X no-fault-detected
Property Identifier Writable Required Optional Property Data
Object_Identifier No X BINARY INPUT #
Object_Name No X "PIR"
Object_Type No X BINARY INPUT
Present_Value No X Active=detection, or Inactive=no
detection
Status_Flags No X {FALSE,FALSE,FALSE,FALSE}
Event_State No X {NORMAL}
Out_Of_Service No X FALSE
Polarity No X Normal Polarity
Reliability No X no-fault-detected
Property Identifier Writable Required Optional Property Data
Object_Identifier No X BINARY INPUT #
Object_Name No X "VFC Count Reset"
Object_Type No X BINARY INPUT
Present_Value Yes X Active=reset requested, or Inactive=no
reset requested
Status_Flags No X {FALSE,FALSE,FALSE,FALSE}
Event_State No X {NORMAL}
Out_Of_Service No X FALSE
Polarity No X Normal Polarity
Tel: +44 (0)1732 861200 - E-mail: [email protected] - Web: www.sontay.com
© 2017 Sontay Limited. All rights reserved
Page 17 of 26
RF-RXS-B
SonNet Wireless Receiver BACnet IP Issue Number: 7.0
Date of Issue: 13/03/2017
Four Elms Road Edenbridge
Kent TN8 6AB UK
Reliability No X no-fault-detected
Property Identifier Writable Required Optional Property Data
Object_Identifier No X BINARY INPUT #
Object_Name No X "CO2 Auto Calibration"
Object_Type No X BINARY INPUT
Present_Value No X Active=auto calibration enabled, or
Inactive=auto calibration disabled
Status_Flags No X {FALSE,FALSE,FALSE,FALSE}
Event_State No X {NORMAL}
Out_Of_Service No X FALSE
Polarity No X Normal Polarity
Reliability No X no-fault-detected
Property Identifier Writable Required Optional Property Data
Object_Identifier No X BINARY INPUT #
Object_Name No X "Ch.x Input Alarm"
Object_Type No X BINARY INPUT
Present_Value No X Active=input alarm, or Inactive=no input
alarm
Status_Flags No X {FALSE,FALSE,FALSE,FALSE}
Event_State No X {NORMAL}
Out_Of_Service No X FALSE
Polarity No X Normal Polarity
Reliability No X no-fault-detected
Property Identifier Writable Required Optional Property Data
Object_Identifier No X BINARY INPUT #
Object_Name No X "Ch.x COV Status"
Object_Type No X BINARY INPUT
Present_Value No X Active=significant change, or Inactive=no
significant change
Tel: +44 (0)1732 861200 - E-mail: [email protected] - Web: www.sontay.com
© 2017 Sontay Limited. All rights reserved
Page 18 of 26
RF-RXS-B
SonNet Wireless Receiver BACnet IP Issue Number: 7.0
Date of Issue: 13/03/2017
Four Elms Road Edenbridge
Kent TN8 6AB UK
Status_Flags No X {FALSE,FALSE,FALSE,FALSE}
Event_State No X {NORMAL}
Out_Of_Service No X FALSE
Polarity No X Normal Polarity
Reliability No X no-fault-detected
Property Identifier Writable Required Optional Property Data
Object_Identifier No X BINARY INPUT #
Object_Name No X "Ch.x COV Status"
Object_Type No X BINARY INPUT
Present_Value No X Active=significant change, or Inactive=no
significant change
Status_Flags No X {FALSE,FALSE,FALSE,FALSE}
Event_State No X {NORMAL}
Out_Of_Service No X FALSE
Polarity No X Normal Polarity
Reliability No X no-fault-detected
Binary Value Object Type
Dynamically creatable using BACnet's CreateObject service? No
Dynamically deletable using BACnet's DeleteObject service? No
Property Identifier Writable Required Optional Property Data
Object_Identifier No X BINARY VALUE #
Object_Name No X "Low Battery"
Object_Type No X BINARY VALUE
Present_Value No X Active=Low Battery, or Inactive=Battery
Okay
Status_Flags No X {FALSE,FALSE,FALSE,FALSE}
Event_State No X {NORMAL}
Out_Of_Service No X FALSE
Tel: +44 (0)1732 861200 - E-mail: [email protected] - Web: www.sontay.com
© 2017 Sontay Limited. All rights reserved
Page 19 of 26
RF-RXS-B
SonNet Wireless Receiver BACnet IP Issue Number: 7.0
Date of Issue: 13/03/2017
Four Elms Road Edenbridge
Kent TN8 6AB UK
Polarity No X Normal Polarity
Reliability No X no-fault-detected
Property Identifier Writable Required Optional Property Data
Object_Identifier No X BINARY VALUE #
Object_Name No X "Online Status"
Object_Type No X BINARY VALUE
Present_Value No X Active=Online, or Inactive=Offline
Status_Flags No X {FALSE,FALSE,FALSE,FALSE}
Event_State No X {NORMAL}
Out_Of_Service No X FALSE
Polarity No X Normal Polarity
Reliability No X no-fault-detected
Property Identifier Writable Required Optional Property Data
Object_Identifier No X BINARY VALUE #
Object_Name No X "Sensor Fault"
Object_Type No X BINARY VALUE
Present_Value No X Active=Fault, or Inactive=No Fault
Status_Flags No X {FALSE,FALSE,FALSE,FALSE}
Event_State No X {NORMAL}
Out_Of_Service No X FALSE
Polarity No X Normal Polarity
Reliability No X no-fault-detected
Property Identifier Writable Required Optional Property Data
Object_Identifier No X BINARY VALUE #
Object_Name No X "Temperature COV Status"
Object_Type No X BINARY VALUE
Present_Value No X Active=Significant Change, or
Inactive=No Significant Change
Tel: +44 (0)1732 861200 - E-mail: [email protected] - Web: www.sontay.com
© 2017 Sontay Limited. All rights reserved
Page 20 of 26
RF-RXS-B
SonNet Wireless Receiver BACnet IP Issue Number: 7.0
Date of Issue: 13/03/2017
Four Elms Road Edenbridge
Kent TN8 6AB UK
Status_Flags No X {FALSE,FALSE,FALSE,FALSE}
Event_State No X {NORMAL}
Out_Of_Service No X FALSE
Polarity No X Normal Polarity
Reliability No X no-fault-detected
Property Identifier Writable Required Optional Property Data
Object_Identifier No X BINARY VALUE #
Object_Name No X "Humidity COV Status"
Object_Type No X BINARY VALUE
Present_Value No X Active=Significant Change, or
Inactive=No Significant Change
Status_Flags No X {FALSE,FALSE,FALSE,FALSE}
Event_State No X {NORMAL}
Out_Of_Service No X FALSE
Polarity No X Normal Polarity
Reliability No X no-fault-detected
Property Identifier Writable Required Optional Property Data
Object_Identifier No X BINARY VALUE #
Object_Name No X "CO2 COV Status"
Object_Type No X BINARY VALUE
Present_Value No X Active=Significant Change, or
Inactive=No Significant Change
Status_Flags No X {FALSE,FALSE,FALSE,FALSE}
Event_State No X {NORMAL}
Out_Of_Service No X FALSE
Polarity No X Normal Polarity
Reliability No X no-fault-detected
Property Identifier Writable Required Optional Property Data
Tel: +44 (0)1732 861200 - E-mail: [email protected] - Web: www.sontay.com
© 2017 Sontay Limited. All rights reserved
Page 21 of 26
RF-RXS-B
SonNet Wireless Receiver BACnet IP Issue Number: 7.0
Date of Issue: 13/03/2017
Four Elms Road Edenbridge
Kent TN8 6AB UK
Object_Identifier No X BINARY VALUE #
Object_Name No X "Setpoint COV Status"
Object_Type No X BINARY VALUE
Present_Value No X Active=Significant Change, or
Inactive=No Significant Change
Status_Flags No X {FALSE,FALSE,FALSE,FALSE}
Event_State No X {NORMAL}
Out_Of_Service No X FALSE
Polarity No X Normal Polarity
Reliability No X no-fault-detected
Multi-State Input Object Type
Dynamically creatable using BACnet's CreateObject service? No
Dynamically deletable using BACnet's DeleteObject service? No
Property Identifier Writable Required Optional Property Data
Object_Identifier No X MULTI-STATE INPUT #
Object_Name No X "Fan Speed Switch"
Object_Type No X MULTI-STATE INPUT
Present_Value No X 1="Off", 2="Low", 3="Medium", 4="High",
5="Auto"
Status_Flags No X {FALSE,FALSE,FALSE,FALSE}
Event_State No X {NORMAL}
Out_Of_Service No X FALSE
Number_Of_States No X 5
Reliability No X no-fault-detected
State_Text No X 1="Off", 2="Low", 3="Medium", 4="High",
5="Auto"
Multi-State Value Object Type
Dynamically creatable using BACnet's CreateObject service? No
Tel: +44 (0)1732 861200 - E-mail: [email protected] - Web: www.sontay.com
© 2017 Sontay Limited. All rights reserved
Page 22 of 26
RF-RXS-B
SonNet Wireless Receiver BACnet IP Issue Number: 7.0
Date of Issue: 13/03/2017
Four Elms Road Edenbridge
Kent TN8 6AB UK
Dynamically deletable using BACnet's DeleteObject service? No
Property Identifier Writable Required Optional Property Data
Object_Identifier No X MULTI-STATE VALUE #
Object_Name No X "Battery Level"
Object_Type No X MULTI-STATE VALUE
Present_Value No X 1="Poor", 2="Okay", 3="Good"
Status_Flags No X {FALSE,FALSE,FALSE,FALSE}
Event_State No X {NORMAL}
Out_Of_Service No X FALSE
Number_Of_States No X 5
Reliability No X no-fault-detected
State_Text No X 1="Poor", 2="Okay", 3="Good"
Property Identifier Writable Required Optional Property Data
Object_Identifier No X MULTI-STATE VALUE #
Object_Name No X "Parent Link Quality"
Object_Type No X MULTI-STATE VALUE
Present_Value No X 1="Marginal", 2="Okay", 3="Good"
Status_Flags No X {FALSE,FALSE,FALSE,FALSE}
Event_State No X {NORMAL}
Out_Of_Service No X FALSE
Number_Of_States No X 5
Reliability No X no-fault-detected
State_Text No X 1="Marginal", 2="Okay", 3="Good"
Property Identifier Writable Required Optional Property Data
Object_Identifier No X MULTI-STATE VALUE #
Object_Name No X "Ch.x Input Type"
Object_Type No X MULTI-STATE VALUE
Tel: +44 (0)1732 861200 - E-mail: [email protected] - Web: www.sontay.com
© 2017 Sontay Limited. All rights reserved
Page 23 of 26
RF-RXS-B
SonNet Wireless Receiver BACnet IP Issue Number: 7.0
Date of Issue: 13/03/2017
Four Elms Road Edenbridge
Kent TN8 6AB UK
Present_Value No X 1="Current", 2="Voltage", 3="Resistance",
4="VFC", 4="Error"
Status_Flags No X {FALSE,FALSE,FALSE,FALSE}
Event_State No X {NORMAL}
Out_Of_Service No X FALSE
Number_Of_States No X 5
Reliability No X no-fault-detected
State_Text No X 1="Current", 2="Voltage", 3="Resistance",
4="VFC", 4="Error"
Octet-String Value Object Type
Dynamically creatable using BACnet's CreateObject service? No
Dynamically deletable using BACnet's DeleteObject service? No
Property Identifier Writable Required Optional Property Data
Object_Identifier No X OCTETSTRING VALUE #
Object_Name No X “MAC Address"
Object_Type No X OCTETSTRING VALUE
Present_Value No X 00158D00001194AE
Status_Flags No X {FALSE,FALSE,FALSE,FALSE}
Event_State No X {NORMAL}
Out_Of_Service No X FALSE
Reliability No X no-fault-detected
Property Identifier Writable Required Optional Property Data
Object_Identifier No X OCTETSTRING VALUE #
Object_Name No X "Parent"
Object_Type No X OCTETSTRING VALUE
Present_Value No X 00158D00010A780C
Status_Flags No X {FALSE,FALSE,FALSE,FALSE}
Event_State No X {NORMAL}
Tel: +44 (0)1732 861200 - E-mail: [email protected] - Web: www.sontay.com
© 2017 Sontay Limited. All rights reserved
Page 24 of 26
RF-RXS-B
SonNet Wireless Receiver BACnet IP Issue Number: 7.0
Date of Issue: 13/03/2017
Four Elms Road Edenbridge
Kent TN8 6AB UK
Out_Of_Service No X FALSE
Reliability No X no-fault-detected
Device Object Type
Dynamically creatable using BACnet's CreateObject service? No
Dynamically deletable using BACnet's DeleteObject service? No
Property Identifier Writable Required Optional Property Data
Object_Identifier Yes X DEVICE #
Object_Name Yes X "SonNet-BACnet-Gateway"
Object_Type No X DEVICE
System_Status No X Operational
Vendor_Name No X "Sontay Limited"
Vendor_Identifier No X 662
Model_Name No X "SBIP"
Firmware_Revision No X "0.9.1"
Application_Software_
Version No X "1.1.8"
Location Yes X "Building 1"
Description Yes X "SonNet devices"
Protocol_Version No X 1
Protocol_Revision No X 12
Protocol_Services_ Supported No X stack library filled
Protocol_Object_Types_
Supported No X stack library filled
Object_List No X stack library filled
Max_APDU_Length_
Accepted No X 1476 bytes
Segmentation_Supported No X None
APDU_Timeout No X 3000ms
Number_Of_APDU_Retries No X 3
Tel: +44 (0)1732 861200 - E-mail: [email protected] - Web: www.sontay.com
© 2017 Sontay Limited. All rights reserved
Page 25 of 26
RF-RXS-B
SonNet Wireless Receiver BACnet IP Issue Number: 7.0
Date of Issue: 13/03/2017
Four Elms Road Edenbridge
Kent TN8 6AB UK
Device_Address_Binding No X {}
Database_Revision No X counter
Data Link Layer Options
X BACnet IP, (Annex J)
BACnet IP, (Annex J), Foreign Device
ISO 8802-3, Ethernet (Clause 7)
ANSI/ATA 878.1, 2.5 Mb. ARCNET (Clause 8)
ANSI/ATA 878.1, RS-485 ARCNET (Clause 8), baud rate(s):
MS/TP master (Clause 9), baud rate(s): 9600, 19200, 38400, 57600, 76800,
115200
MS/TP slave (Clause 9), baud rate(s):
MS/TP (Clause 9), transceiver unit load and isolation 1/4 unit load, isolated
Point-To-Point, EIA 232 (Clause 10), baud rate(s):
Point-To-Point, modem, (Clause 10), baud rate(s):
LonTalk, (Clause 11), medium:
Other:
Network Options
Router, Clause 6 - List all routing configurations (e.g. ARCNET-Ethernet, Ethernet-MS/TP, etc.):
Annex H.3, BACnet Tunnelling Router over UDP/IP
BACnet/IP Broadcast Management Device (BBMD)
BBMD supports registrations by Foreign Devices
Segmentation Capability
Window Size
Segmented requests supported
Segmented responses supported
Device Address Binding
Static device binding supported for MS/TP Slaves and other devices
Tel: +44 (0)1732 861200 - E-mail: [email protected] - Web: www.sontay.com
© 2017 Sontay Limited. All rights reserved
Page 26 of 26
RF-RXS-B
SonNet Wireless Receiver BACnet IP Issue Number: 7.0
Date of Issue: 13/03/2017
Four Elms Road Edenbridge
Kent TN8 6AB UK
Character Sets Supported
X ANSI X3.4 / UTF-8
IBMÔ/MicrosoftÔ DBCS
ISO 8859-1
ISO 10646 (UCS-2)
ISO 10646 (ICS-4)
JIS C 6226