SIRCO MC PV UL 508ILoad break switches for photovoltaic applicationsfrom 25 to 45 A, up to 1000 VDC
Load
bre
ak
swit
ches
sirc
o-m
c_00
2_a_
1_ca
t
sirc
o-m
c_02
8_a
SIRCO MC PV 25 A - 1000 VDCDIN-rail mounting
SIRCO MC PVDIN-rail mounting
FunctionSIRCO MC PV are DC non-fusible disconnect switches. They make and break under load conditions and provide optimum safe isolation for any PV circuit.
AdvantagesCompactThanks to its compact design, the space needed within the combiner box or the solar inverter is greatly reduced.
High breaking capacity up to 1000 VDC • Making and breaking capacity under load conditions up to 1000 VDC.
• Specific photovoltaic test beyond requirements of UL 508I and IEC 60947-3 standard.
Safety • Bridging bars are factory fitted for easier, quicker and safer connection.
• Direct access to connection terminals for adequate tightening.
> Compact > High breaking capacity up to 1000 VDC
> Safety
Strong points
> Residential > Buildings > Solar parks
The solution for
> UL 508I Guide NMSJ,file E365404
> IEC 60947-3
Conformity to standards
Approvals and certifications(1)
(1) Product reference on request.
SIRCO MC PV UL 508ILoad break switches for photovoltaic applications
from 25 to 45 A, up to 1000 VDC
SIRCO MC PV UL 508ILoad break switches for photovoltaic applicationsfrom 25 to 45 A, up to 1000 VDC
Multi-circuit switching
Completely isolate the inverter within one operation
• The SIRCO MC PV for dual circuits (2 MPPT: Maximum Power Point Tracking) enables connection of two independent photovoltaic circuits to a single switch in order to reduce the costs of the global solution.
• The SIRCO MC PV with two additional AC poles can be integrated into the inverter to provide complete and simultaneous isolation of the PV and AC circuits. This improves safety and reduces the overall product size.
For grounded or ungrounded networks:It is possible to use the SIRCO MC PV in both network systems, either switching one or both polarities.
sirco-mc_016_a
sirc
o-m
c_04
5_a_
1_gb
_cat
sirco-mc_013_b_1_gb_cat
sirc
o-m
c_02
0_a
sirco-mc_026_a_1_x_cat
sirco-mc_027_a_1_x_cat
sirc
o-m
c_02
4_a_
1_x_
cat
sirc
o-m
c_02
5_a_
1_x_
cat
-+
1 5
2
7
8
7
86
-+Inverter 1
-+Inverter 2
Panel 1-+
Panel 2
-
1 3 5
2 4 6
+
- +
AC AC
Inverter
Panel
What you need to know
174 General Catalogue 2017-2018
SIRCO MC PV UL 508ILoad break switches for photovoltaic applicationsfrom 25 to 45 A, up to 1000 VDC
Load
bre
ak
swit
ches
sirc
o-m
c_00
2_a_
1_ca
t
sirc
o-m
c_02
8_a
SIRCO MC PV 25 A - 1000 VDCDIN-rail mounting
SIRCO MC PVDIN-rail mounting
FunctionSIRCO MC PV are DC non-fusible disconnect switches. They make and break under load conditions and provide optimum safe isolation for any PV circuit.
AdvantagesCompactThanks to its compact design, the space needed within the combiner box or the solar inverter is greatly reduced.
High breaking capacity up to 1000 VDC • Making and breaking capacity under load conditions up to 1000 VDC.
• Specific photovoltaic test beyond requirements of UL 508I and IEC 60947-3 standard.
Safety • Bridging bars are factory fitted for easier, quicker and safer connection.
• Direct access to connection terminals for adequate tightening.
> Compact > High breaking capacity up to 1000 VDC
> Safety
Strong points
> Residential > Buildings > Solar parks
The solution for
> UL 508I Guide NMSJ,file E365404
> IEC 60947-3
Conformity to standards
Approvals and certifications(1)
(1) Product reference on request.
SIRCO MC PV UL 508ILoad break switches for photovoltaic applications
from 25 to 45 A, up to 1000 VDC
SIRCO MC PV UL 508ILoad break switches for photovoltaic applicationsfrom 25 to 45 A, up to 1000 VDC
Multi-circuit switching
Completely isolate the inverter within one operation
• The SIRCO MC PV for dual circuits (2 MPPT: Maximum Power Point Tracking) enables connection of two independent photovoltaic circuits to a single switch in order to reduce the costs of the global solution.
• The SIRCO MC PV with two additional AC poles can be integrated into the inverter to provide complete and simultaneous isolation of the PV and AC circuits. This improves safety and reduces the overall product size.
For grounded or ungrounded networks:It is possible to use the SIRCO MC PV in both network systems, either switching one or both polarities.
sirco-mc_016_a
sirc
o-m
c_04
5_a_
1_gb
_cat
sirco-mc_013_b_1_gb_cat
sirc
o-m
c_02
0_a
sirco-mc_026_a_1_x_cat
sirco-mc_027_a_1_x_cat
sirc
o-m
c_02
4_a_
1_x_
cat
sirc
o-m
c_02
5_a_
1_x_
cat
-+
1 5
2
7
8
7
86
-+Inverter 1
-+Inverter 2
Panel 1-+
Panel 2
-
1 3 5
2 4 6
+
- +
AC AC
Inverter
Panel
What you need to know
175General Catalogue 2017-2018
SIRCO MC PV UL 508ILoad break switches for photovoltaic applicationsfrom 25 to 45 A, up to 1000 VDC
References600 VDC
1000 VDC
Rating (A) Circuit type No. of poles Switch body Direct handle External handleShaft for external
handle Auxiliary contact
25 A
Single PV circuit 2 P 21PV 2102-UL
MC01 typeBlue
2119 1012
S00 type
Black4.4X
147D 0111(1)
Red4.4X
147R 0111(1)
S00 type
265 mm10.43 in
2107 0517
1 contact NC+NO
2119 0001
Dual PV circuit 4 P 21PV 5102-UL
45 A
Single PV circuit 4 P 21PV 4144
Dual PV circuit 8 P 21PV 8144MC01 type
Blue2119 1412
Rating (A) Circuit type No. of poles Switch body Direct handle External handleShaft for external
handle Auxiliary contact
32 A
Single PV circuit 4 P 21PV 4144MC01 type
Black2119 1012
S00 type
Black4.4X
147D 0111(1)
Red4.4X
147R 0111(1)
S00 type
265 mm10.43 in
2107 0517
1 contact NC+NO
2119 0001
Dual PV circuit 8 P 21PV 8144MC01 type
Black2119 1412
(1) Door interlocking.
(1) Door interlocking.
AccessoriesDirect operation handle
acce
s_30
5_a_
1_ca
t
MC0 handle
acce
s_29
3_a_
1_ca
t
MC01 handle
Rating (A) Handle color Type of locking Handle type45 mm modular DIN front plate Reference
25 … 45 Blue - MC0 yes 2119 0012(1)
25 … 45 Blue 1 padlock Ø 5 mm / 0.20 in MC01 yes 2119 1012
2 MPPT 600 V
Rating (A) Handle color Type of locking Handle type45 mm modular DIN front plate Reference
25 Blue - MC0 yes 2119 001225 Blue 1 padlock Ø 5 mm / 0.20 in MC01 yes 2119 101245 Blue 1 padlock Ø 5 mm / 0.20 in MC01 yes 2119 1412
(1) Standard handle.
UseThe direct operation conversion kit requires an additional 4 mm distance on each side of the 2 and 3 pole device.
SIRCO MC PV UL 508ILoad break switches for photovoltaic applications
from 25 to 45 A, up to 1000 VDC
External operation handle
acce
s_30
2_a_
1_ca
tac
ces_
341_
a_1_
cat
UseThe external control will allow the operator to safely disconnect and isolate the solar strings prior to any intervention.
External controls are user-friendly and adapted to meet requirements of residential installations, large roofs and ground-based generators.
DIN-rail or back plate mounting
Rating (A)Handle
type Handle color Type of lockingProtection degree(1) Reference
25 … 45 MC1 Black 3 padlocks Ø 8 mm / 0.35 in 4.4X 2119 331225 … 45 MC1 Red/Yellow 3 padlocks Ø 8 mm / 0.35 in 4.4X 2119 331325 … 45 S00 Black 3 padlocks Ø 8 mm / 0.31 in 4.4X 147D 011125 … 45 S00 Red/Yellow 3 padlocks Ø 8 mm / 0.31 in 4.4X 147R 0111
(1) Nema/UL protection degree.
MC1 handle
S00 handle
Shaft for external handle
acce
s_29
7_a_
1_ca
t
UseThe shaft can be adjusted and cut depending on the need.
Shaft lengthDevice + shaft:- 265 mm
DIN-rail or back plate mounting
Rating (A)Device + shaft
Length Reference
25 … 45 265 mm / 10.43 in 2107 0517(1)
(1) Shaft for door interlocking.
Terminal shrouds
UseTop or bottom protection against direct contact with the terminals or connection parts. 1 and 3 poles are available.The SIRCO MC PV load break switch is pre-bridged. Terminal covers are mounted on the top or bottom free space of the device.Possibility to assemble a terminal shroud on the bridge side by removing the insulating material of the series connection bar (irreversible step).
Rating (A) Type of mounting No. of poles Position Reference
25 … 45 DIN-rail 1 P top or bottom 2194 100425 … 45 DIN-rail 3 P top or bottom 2194 3004
acce
s_29
9_a_
1_ca
tac
ces_
300_
a_1_
cat
+
+
-
-
-
- ++
+
+
-
-
+
+
-
-
-
- ++
-
-++
-
- ++
-
-++
+
+
+
+
sirc
o-m
c_01
1_e_
1_ca
t
Terminal shrouds 1 pole
Terminal shrouds 3 pole
176 General Catalogue 2017-2018
SIRCO MC PV UL 508ILoad break switches for photovoltaic applicationsfrom 25 to 45 A, up to 1000 VDC
References600 VDC
1000 VDC
Rating (A) Circuit type No. of poles Switch body Direct handle External handleShaft for external
handle Auxiliary contact
25 A
Single PV circuit 2 P 21PV 2102-UL
MC01 typeBlue
2119 1012
S00 type
Black4.4X
147D 0111(1)
Red4.4X
147R 0111(1)
S00 type
265 mm10.43 in
2107 0517
1 contact NC+NO
2119 0001
Dual PV circuit 4 P 21PV 5102-UL
45 A
Single PV circuit 4 P 21PV 4144
Dual PV circuit 8 P 21PV 8144MC01 type
Blue2119 1412
Rating (A) Circuit type No. of poles Switch body Direct handle External handleShaft for external
handle Auxiliary contact
32 A
Single PV circuit 4 P 21PV 4144MC01 type
Black2119 1012
S00 type
Black4.4X
147D 0111(1)
Red4.4X
147R 0111(1)
S00 type
265 mm10.43 in
2107 0517
1 contact NC+NO
2119 0001
Dual PV circuit 8 P 21PV 8144MC01 type
Black2119 1412
(1) Door interlocking.
(1) Door interlocking.
AccessoriesDirect operation handle
acce
s_30
5_a_
1_ca
t
MC0 handle
acce
s_29
3_a_
1_ca
t
MC01 handle
Rating (A) Handle color Type of locking Handle type45 mm modular DIN front plate Reference
25 … 45 Blue - MC0 yes 2119 0012(1)
25 … 45 Blue 1 padlock Ø 5 mm / 0.20 in MC01 yes 2119 1012
2 MPPT 600 V
Rating (A) Handle color Type of locking Handle type45 mm modular DIN front plate Reference
25 Blue - MC0 yes 2119 001225 Blue 1 padlock Ø 5 mm / 0.20 in MC01 yes 2119 101245 Blue 1 padlock Ø 5 mm / 0.20 in MC01 yes 2119 1412
(1) Standard handle.
UseThe direct operation conversion kit requires an additional 4 mm distance on each side of the 2 and 3 pole device.
SIRCO MC PV UL 508ILoad break switches for photovoltaic applications
from 25 to 45 A, up to 1000 VDC
External operation handle
acce
s_30
2_a_
1_ca
tac
ces_
341_
a_1_
cat
UseThe external control will allow the operator to safely disconnect and isolate the solar strings prior to any intervention.
External controls are user-friendly and adapted to meet requirements of residential installations, large roofs and ground-based generators.
DIN-rail or back plate mounting
Rating (A)Handle
type Handle color Type of lockingProtection degree(1) Reference
25 … 45 MC1 Black 3 padlocks Ø 8 mm / 0.35 in 4.4X 2119 331225 … 45 MC1 Red/Yellow 3 padlocks Ø 8 mm / 0.35 in 4.4X 2119 331325 … 45 S00 Black 3 padlocks Ø 8 mm / 0.31 in 4.4X 147D 011125 … 45 S00 Red/Yellow 3 padlocks Ø 8 mm / 0.31 in 4.4X 147R 0111
(1) Nema/UL protection degree.
MC1 handle
S00 handle
Shaft for external handle
acce
s_29
7_a_
1_ca
t
UseThe shaft can be adjusted and cut depending on the need.
Shaft lengthDevice + shaft:- 265 mm
DIN-rail or back plate mounting
Rating (A)Device + shaft
Length Reference
25 … 45 265 mm / 10.43 in 2107 0517(1)
(1) Shaft for door interlocking.
Terminal shrouds
UseTop or bottom protection against direct contact with the terminals or connection parts. 1 and 3 poles are available.The SIRCO MC PV load break switch is pre-bridged. Terminal covers are mounted on the top or bottom free space of the device.Possibility to assemble a terminal shroud on the bridge side by removing the insulating material of the series connection bar (irreversible step).
Rating (A) Type of mounting No. of poles Position Reference
25 … 45 DIN-rail 1 P top or bottom 2194 100425 … 45 DIN-rail 3 P top or bottom 2194 3004
acce
s_29
9_a_
1_ca
tac
ces_
300_
a_1_
cat
+
+
-
-
-
- ++
+
+
-
-
+
+
-
-
-
- ++
-
-++
-
- ++
-
-++
+
+
+
+
sirc
o-m
c_01
1_e_
1_ca
t
Terminal shrouds 1 pole
Terminal shrouds 3 pole
177General Catalogue 2017-2018
SIRCO MC PV UL 508ILoad break switches for photovoltaic applicationsfrom 25 to 45 A, up to 1000 VDC
Characteristics
25 A 45 A
General use rating with 200% overload extra test
Rated voltage Number of poles of the device Number of PV circuits (A) (A)
600 VDC 2 P 1 25 -
600 VDC 4 P 1 - 45
600 VDC 2 x 2 P 2 25 -
600 VDC 2 x 4 P 2 - 45
1000 VDC 4 P 1 - 32
1000 VDC 2 x 4 P 2 - 32
Short-circuit capacity at 600 VDCProspective short-circuit current (kA rms) 5 5
Type of fuse gPV gPV
Associated fuse rating (A) 25 80
Short-circuit capacity at 1000 VDCProspective short-circuit current (kA rms) 5 5
Connection terminalsMin. connection wire range / AWG (solid or stranded) 14 / 7 14 / 3
Mechanical characteristicsDurability (number of operating cycles) 30 000 30 000
Tightening torque (Nm) 2 2
Rated current 25 A 45 A
Thermal current Ith at 40°C (A) 25 45
Thermal current at 50°C (A) 25 45
Thermal current at 60°C (A) 25 45
Rated insulation voltage Ui (V) 1000 1000
Rated impulse withstand voltage Uimp (kV) 8 8
Rated operational currents Ie (A)Rated voltage Number of poles of the device Number of PV circuits (A) (A)
600 VDC 2 P 1 30 -
600 VDC 4 P 1 - 40
600 VDC 2 x 2 P 2 30 -
600 VDC 2 x 4 P 2 - 40
1000 VDC 2 P 1 10 -
1000 VDC 4 P 1 - 40
1000 VDC 2 x 2 P 2 10 -
1000 VDC 2 x 4 P 2 - 40
according to UL 508I
according to IEC 60947-3
SIRCO MC PV UL 508ILoad break switches for photovoltaic applications
from 25 to 45 A, up to 1000 VDC
2 MPPT - 45 A - 600 VDC and 32 A - 1000 VDC - DIN-rail mounting - Direct operation
1. Terminal shrouds 3P.2. Auxiliary contact.
3. PV power pole. A. MC01 handle.
3.8297
3.07 78
2.76
/ 7
0
0.9825
0.5714.5
2.36
/ 6
0
2.56
/ 6
5
0.15
3.8
3.74951.65
420.205
1.8948
Ø 0.18Ø 4.65
2,8071
A
3 22 3
1 1
sirc
o-m
c_03
9_a_
1_us
_cat
Dimensions (in/mm)DIN-rail mounting - Direct operation
1. Terminal shrouds 1P.2. Terminal shrouds 3P.3. Auxiliary contact.
4. AC power pole.5. AC or PV power pole.
A. MC0 handleB. MC01 handle
3.6091.5
1.6542
1.9148.5
Ø 0.18Ø 4.65
2.6667.5
3 3
12
4 5
2.8973.52.0552
3.07 78
2.76
/ 7
0
0.9825
2.36
/ 6
0
2.56
/ 6
5
0.15
3.8
3.6091.5
1.65420.20
50.20
5
1.9448.5
2.6667.5
A B
sirc
o-m
c_00
4_b_
1_us
_cat
DIN-rail mounting - External operation
2.8773.5
1.7544.5
3.07 78
2.76
/ 7
0
0.9825
2.36
/ 6
0
2.56
/ 6
5
3.8
0.15
Min. 3.46 - 3.86 / Max. 9.96 - 10.83Min. 88 - 98 / Max. 253 - 275
1.65420.20
5
2.1755
Max. 0.20Max. 5
66
1.2632
A
3 3
12
4 5
sirc
o-m
c_00
5_b_
1_xu
s_ca
t
1. Terminal shrouds 1P.2. Terminal shrouds 3P.
3. Auxiliary contact.4. AC power pole.
5. AC or PV power pole.A. MC1 handle
Max. 5
178 General Catalogue 2017-2018
SIRCO MC PV UL 508ILoad break switches for photovoltaic applicationsfrom 25 to 45 A, up to 1000 VDC
Characteristics
25 A 45 A
General use rating with 200% overload extra test
Rated voltage Number of poles of the device Number of PV circuits (A) (A)
600 VDC 2 P 1 25 -
600 VDC 4 P 1 - 45
600 VDC 2 x 2 P 2 25 -
600 VDC 2 x 4 P 2 - 45
1000 VDC 4 P 1 - 32
1000 VDC 2 x 4 P 2 - 32
Short-circuit capacity at 600 VDCProspective short-circuit current (kA rms) 5 5
Type of fuse gPV gPV
Associated fuse rating (A) 25 80
Short-circuit capacity at 1000 VDCProspective short-circuit current (kA rms) 5 5
Connection terminalsMin. connection wire range / AWG (solid or stranded) 14 / 7 14 / 3
Mechanical characteristicsDurability (number of operating cycles) 30 000 30 000
Tightening torque (Nm) 2 2
Rated current 25 A 45 A
Thermal current Ith at 40°C (A) 25 45
Thermal current at 50°C (A) 25 45
Thermal current at 60°C (A) 25 45
Rated insulation voltage Ui (V) 1000 1000
Rated impulse withstand voltage Uimp (kV) 8 8
Rated operational currents Ie (A)Rated voltage Number of poles of the device Number of PV circuits (A) (A)
600 VDC 2 P 1 30 -
600 VDC 4 P 1 - 40
600 VDC 2 x 2 P 2 30 -
600 VDC 2 x 4 P 2 - 40
1000 VDC 2 P 1 10 -
1000 VDC 4 P 1 - 40
1000 VDC 2 x 2 P 2 10 -
1000 VDC 2 x 4 P 2 - 40
according to UL 508I
according to IEC 60947-3
SIRCO MC PV UL 508ILoad break switches for photovoltaic applications
from 25 to 45 A, up to 1000 VDC
2 MPPT - 45 A - 600 VDC and 32 A - 1000 VDC - DIN-rail mounting - Direct operation
1. Terminal shrouds 3P.2. Auxiliary contact.
3. PV power pole. A. MC01 handle.
3.8297
3.07 78
2.76
/ 7
0
0.9825
0.5714.5
2.36
/ 6
0
2.56
/ 6
5
0.15
3.8
3.74951.65
420.205
1.8948
Ø 0.18Ø 4.65
2,8071
A
3 22 3
1 1
sirc
o-m
c_03
9_a_
1_us
_cat
Dimensions (in/mm)DIN-rail mounting - Direct operation
1. Terminal shrouds 1P.2. Terminal shrouds 3P.3. Auxiliary contact.
4. AC power pole.5. AC or PV power pole.
A. MC0 handleB. MC01 handle
3.6091.5
1.6542
1.9148.5
Ø 0.18Ø 4.65
2.6667.5
3 3
12
4 5
2.8973.52.0552
3.07 78
2.76
/ 7
0
0.9825
2.36
/ 6
0
2.56
/ 6
5
0.15
3.8
3.6091.5
1.65420.20
50.20
5
1.9448.5
2.6667.5
A B
sirc
o-m
c_00
4_b_
1_us
_cat
DIN-rail mounting - External operation
2.8773.5
1.7544.5
3.07 78
2.76
/ 7
0
0.9825
2.36
/ 6
0
2.56
/ 6
5
3.8
0.15
Min. 3.46 - 3.86 / Max. 9.96 - 10.83Min. 88 - 98 / Max. 253 - 275
1.65420.20
5
2.1755
Max. 0.20Max. 5
66
1.2632
A
3 3
12
4 5
sirc
o-m
c_00
5_b_
1_xu
s_ca
t1. Terminal shrouds 1P.2. Terminal shrouds 3P.
3. Auxiliary contact.4. AC power pole.
5. AC or PV power pole.A. MC1 handle
Max. 5
179General Catalogue 2017-2018
SIRCO MC PV UL 508ILoad break switches for photovoltaic applicationsfrom 25 to 45 A, up to 1000 VDC
Dimensions for external handles (in/mm)
DIN-rail or back plate mounting
poig
n_00
1_a_
1_us
_cat
poig
n_05
6_a_
1_us
_cat
1.5740
4 Ø 0.284 Ø 7
Ø 1.22 Ø 31
1.10 28
S00 type
0
I
90°
13.5
Ø 0.89Ø 22.5
0.123Ø 3.07
Ø 78
1.4236
2.80 71
With fixing nutWith 4 fixing screws
Direction of operation Door drillingHandle type
Front operation
0
OFF
0
OFF
1.30 33
1.2632
2.6066
2.60 66
Ø 0.55Ø 14
Ø 0,13Ø 3.4
1.4236
1.42 360
I
90°
Direction of operation Door drillingHandle type
Front operation
MC1 type
DIN-rail mounting - External operation
1. Terminal shrouds 3P. 2. Auxiliary contact. A. MC1 handle.
Min. 3.74 - 3.86 / Max. 10.24 - 10.83Min. 95 - 98 / Max. 260 - 275
1.65420.20
5
2.6266.5
Max. 0.20Max. 5
2.60 66
1.2632
A3.5089
3.07 78
0.9825
0.5714.5
0.15 3.8
3 22 3
1 1
2.76
/ 7
0
2.36
/ 6
0
2.56
/ 6
5
sirc
o-m
c_04
0_b_
1_us
_cat
Dimensions (continued)
SIRCO MC PV UL 508ILoad break switches for photovoltaic applications
from 25 to 45 A, up to 1000 VDC
Rating Single PV circuit Dual PV circuit
25 A - 600 VDC 21PV 2102-UL 21PV 5102-UL
45 A - 600 VDC32 A - 1000 VDC
21PV 4144 21PV 8144
Poles connections
-
1 5
2 6
+
- +Inverter
Panel
+
1 3 5
2 4 6
7
8
-
+ -Inverter
Panel Panel
-+
1 5
2
7
8
7
86
-+Inverter 1
-+Inverter 2
Panel 1-+
Panel 2
+
1 3 5
2 4 6
Pan
el 1
Pan
el 1
+
1 3 5
2 4 6
Inverter 2
Pan
el 2
Pan
el 2
-
7
8
- + +
-
7
8
-Inverter 1 Inverter 1
sirc
o-m
c_04
4_a_
1_gb
_cat
sirc
o-m
c_08
3_a_
1_gb
_cat
sirc
o-m
c_04
5_a_
1_gb
_cat
sirc
o-m
c_06
5_a_
1_gb
_cat
Switching of polarities + and - (1)
Single PV circuit Dual PV circuit
sirc
o-m
c_02
6_a_
1_x_
cat
sirc
o-m
c_02
4_a_
1_x_
cat
(1) For grounded systems, single polarity switching, a bridge shall be added. For spare bridging bars, please consult use.
180 General Catalogue 2017-2018
SIRCO MC PV UL 508ILoad break switches for photovoltaic applicationsfrom 25 to 45 A, up to 1000 VDC
Dimensions for external handles (in/mm)
DIN-rail or back plate mounting
poig
n_00
1_a_
1_us
_cat
poig
n_05
6_a_
1_us
_cat
1.5740
4 Ø 0.284 Ø 7
Ø 1.22 Ø 31
1.10 28
S00 type
0
I
90°
13.5
Ø 0.89Ø 22.5
0.123Ø 3.07
Ø 78
1.4236
2.80 71
With fixing nutWith 4 fixing screws
Direction of operation Door drillingHandle type
Front operation
0
OFF
0
OFF
1.30 33
1.2632
2.6066
2.60 66
Ø 0.55Ø 14
Ø 0,13Ø 3.4
1.4236
1.42 360
I
90°
Direction of operation Door drillingHandle type
Front operation
MC1 type
DIN-rail mounting - External operation
1. Terminal shrouds 3P. 2. Auxiliary contact. A. MC1 handle.
Min. 3.74 - 3.86 / Max. 10.24 - 10.83Min. 95 - 98 / Max. 260 - 275
1.65420.20
5
2.6266.5
Max. 0.20Max. 5
2.60 66
1.2632
A3.5089
3.07 78
0.9825
0.5714.5
0.15 3.8
3 22 3
1 1
2.76
/ 7
0
2.36
/ 6
0
2.56
/ 6
5
sirc
o-m
c_04
0_b_
1_us
_cat
Dimensions (continued)
SIRCO MC PV UL 508ILoad break switches for photovoltaic applications
from 25 to 45 A, up to 1000 VDC
Rating Single PV circuit Dual PV circuit
25 A - 600 VDC 21PV 2102-UL 21PV 5102-UL
45 A - 600 VDC32 A - 1000 VDC
21PV 4144 21PV 8144
Poles connections
-
1 5
2 6
+
- +Inverter
Panel
+
1 3 5
2 4 6
7
8
-
+ -Inverter
Panel Panel
-+
1 5
2
7
8
7
86
-+Inverter 1
-+Inverter 2
Panel 1-+
Panel 2
+
1 3 5
2 4 6
Pan
el 1
Pan
el 1
+
1 3 5
2 4 6
Inverter 2
Pan
el 2
Pan
el 2
-
7
8
- + +
-
7
8
-Inverter 1 Inverter 1
sirc
o-m
c_04
4_a_
1_gb
_cat
sirc
o-m
c_08
3_a_
1_gb
_cat
sirc
o-m
c_04
5_a_
1_gb
_cat
sirc
o-m
c_06
5_a_
1_gb
_cat
Switching of polarities + and - (1)
Single PV circuit Dual PV circuit
sirc
o-m
c_02
6_a_
1_x_
cat
sirc
o-m
c_02
4_a_
1_x_
cat
(1) For grounded systems, single polarity switching, a bridge shall be added. For spare bridging bars, please consult use.
181General Catalogue 2017-2018