SISTEMA FLATPACK 2
José Rodas Utani
Jefe de Servicios & Soporte Técnico
Perú, Ecuador y Bolivia
Slide 2 of 23 08.04.23
Slide 3 of 23 08.04.23
Generation 4Generation 4
Slide 4 of 23 08.04.23
Generation 1
Generation 3
Generation 4
1. Highest Power Density1. Highest Power Density
5W/in3
1995
2000
2005
SMPS 60/20
SMPS 1000
Flatpack 1800
2010
FP2 1800
10W/in3
15W/in3
20W/in3
25W/in3
FP2 2000
Flatpack 1500
Saves the customer money by :- More space for customer equipment and/or batteries- Thus less cabinets and less footprint in the location
33W/in3FP2 3000
Slide 5 of 23 08.04.23
1. Highest Power Density – FP2 2KW SHELF1. Highest Power Density – FP2 2KW SHELF
Modular Configuration 48 VDCModular Configuration 48 VDC
167A Maximum Per Shelf
125A Redundant
With four rectifiers installed
DimensionsDimensions
17.5” Wide –
brackets mount 19”, 21” or 23”
14.5” Deep
1U – 1.75” Height
Slide 6 of 23 08.04.23
1. Highest Power Density – FP2 3KW SHELF1. Highest Power Density – FP2 3KW SHELF
Modular Configuration 48 VDCModular Configuration 48 VDC
250A Maximum Per Shelf
187,5A Redundant
With four rectifiers installed
DimensionsDimensions
17.5” Wide –
brackets mount 19”, 21” or 23”
17” Deep
1U – 1.75” Height
Slide 7 of 23 08.04.23
2. Pequeño y ligero 2. Pequeño y ligero
< 1.9 Kg
- Personal de mantenimiento - especialmente como repuestos - Logística - un peso más ligero, significa menos costos de envío
41.5mm
109 mm
327 mm
Más fácil para dirigir :
Slide 8 of 23 08.04.23
3. Operación de los ventiladores3. Operación de los ventiladores
2 Fans – Front to back airflow - will work with only one
(Back to front version in design stage)
• Evitar las salidas de llamadas de prioridad (fuera de horas normales) - Da una alta eficacia del rectificador
Ahorros por costos de mantenimiento y operación por :
Slide 9 of 23 08.04.23
4. Controles digitales4. Controles digitales
2 controlador digital : Dan mas supervisión y control.
- Dando al operadores una información más en tiempo real del sistema
- El personal de mantenimiento sabe exactamente qué necesita hacer con las ayudas.
Ahorro de tiempo y dinero por :
Slide 10 of 23 08.04.23
5. Edge connectors5. Edge connectors
Edge-connector technology
- Módulos intercambiables en caliente.- Reduce fallas de interconexión.
Ahorra tiempo (y dinero) :
AC Input
Communications
DC Output
Slide 11 of 23 08.04.23
6. Amplio Rango de entrada CA 6. Amplio Rango de entrada CA
85V 185 290
650W
0W
NominalInput
Red LED Yellow LED Red LEDGreen LED
1800W2000W
850W
300
Output Power vs. Input voltage
Slide 12 of 23 08.04.23
6. Large AC input range6. Large AC input range
Mains derating
0
20
40
60
80
100
120
0 50 100 150 200 250 300 350
Voltage (Vac)
Ou
tpu
t P
ow
er (
%)
FP2 48/2000 FP2 48/3000
> Derating below 176Vac (185Vac on 2kW module)
> 1382W (46%) at 85Vac
Slide 13 of 23 08.04.23
7. Temperatura De-rating7. Temperatura De-rating
+45o
2000W
1400W
0W+75o
Yellow LED Red LEDGreen LED
1800W
1200W
Temperatura ambiente (max full carga de salida)
LinearDe-rating Zone
Slide 14 of 23 08.04.23
7. Temperature De-rating7. Temperature De-rating
> Derating above 45 oC
> 2100W (67%) at 75 oC
> Delivers 50A at 65 oC
> Operating down to -40 oC
Temperature derating
0
20
40
60
80
100
120
0 10 20 30 40 50 60 70 80
Ambient temperature
Ou
tpu
t P
ow
er (
%)
FP2 48/2000 FP248/3000
Slide 15 of 23 08.04.23
8. Excelente protección en AC/DC8. Excelente protección en AC/DC
Mains fuse: 2x15 A (fast) in Live and Neutral
Varistor across the lines for transient
protection
Hi -ohmic disconnect above 290V / 300V AC
(with auto reconnect when in range)
DC Output· Short circuit proof
(constant current)
· Single or double fan blockage/failureDC output : Blocking Diode
Slide 16 of 23 08.04.23
9. Highly Efficient – 2 KW9. Highly Efficient – 2 KW
MaxEfficiency
Zone
2000W rectifier : Efficiency at 230Vac input
90
90,5
91
91,5
92
92,5
93
0 200 400 600 800 1000 1200 1400 1600 1800 2000
Pout(W)
Eff.
(%)
Slide 17 of 23 08.04.23
9. Highly Efficient – 3 KW9. Highly Efficient – 3 KW
> Efficiency above 93% at 40-80% load, 92.4% at 100% load
> 10% loss reduction on system level
> Low load efficiency also improved
86
87
88
89
90
91
92
93
94
0 10 20 30 40 50 60 70 80 90 100
Load (%)
Eff
icie
ncy
(%)
3000W
2000W
Slide 18 of 23 08.04.23
9. Highly Efficient – 2 KW HE9. Highly Efficient – 2 KW HE
Slide 19 of 23 08.04.23
Technical Data – 24V 2000 WTechnical Data – 24V 2000 W
Slide 20 of 23 08.04.23
Technical Data – 48 V 1800 WTechnical Data – 48 V 1800 W
Slide 21 of 23 08.04.23
Technical Data – 48 V 2000 WTechnical Data – 48 V 2000 W
Slide 22 of 23 08.04.23
Technical Data – 48 V 3000 WTechnical Data – 48 V 3000 W
Slide 23 of 23 08.04.23
Technical Data – 48 V 2000 W HETechnical Data – 48 V 2000 W HE
Slide 24 of 23 08.04.23
Procedimiento de instalaciónProcedimiento de instalación
Handle in locked
positionHole to release
the handle’s spring
mechanism
Handle in unlocked position
Slide 25 of 23 08.04.23
Panel FrontalPanel Frontal
Dual Fan Cooling RED Alarm LED
YELLOWYELLOW Warning LEDGREENGREEN Power LED
Slide 26 of 23 08.04.23
Panel FrontalPanel Frontal
Power (green) ON Rectifier is powered
Flashing
Smartpack controller accessing information on the rectifier
OFF Mains are unavailable
Slide 27 of 23 08.04.23
Panel FrontalPanel Frontal
Warning (yellow)
ON
Rectifier is in Derating Mode (reduced output power) high internal temperature (+65 to 70 C) orlow input voltage (lower than 176VAC) or
single fan failure The remote Battery Current Limit is activated
AC input voltage is out of range Rectifier in stand-alone mode (or loss of
communication with the Smartpack controller
Flashing Rectifier is in Over-voltage Protection Mode
OFF No abnormal situation is present
Slide 28 of 23 08.04.23
Panel FrontalPanel Frontal
Alarm (red)
ON
Rectifier is in Shut-down Mode due to low mains (0 – 85VAC) or
high internal temperature (+75 C or higher) orhigh output voltage (higher than 59.5 VDC)
Internal rectifier failure (malfunction) Fan failure (double fan malfunction) Low output voltage (0 to 43.5VDC)
CAN bus failure
OFF No alarm situation is present
Slide 29 of 23 08.04.23
Unidad de ControlUnidad de Control
> Scaleable y modular, control flexible para la gama entera de productos Eltek
Slide 30 of 23 08.04.23
Unidad de ControlUnidad de Control> Front panel backlit LCD (2x16) and key pad
> USB for PC connection and easy FW uploading
> CAN bus para comunicacion con modulos Eltek
> 6 entradas digitales programables
> 6 relay de salidas configurables
> Latched contactor control
> Monitoreo y test de baterias
> Compensacion de carga por temperatura
> 8 symmetry measurements
> log de eventos(10000) con hora y fecha.
> Windows-based PC communication software
Slide 31 of 23 08.04.23
Pequeño pero de gran alcance Pequeño pero de gran alcance
44mm
109 mm
144 mm
< 300g
Slide 32 of 23 08.04.23
Smartpack Vista Frontal
> ”Top-level alarms” scrolls on display when active• Battery, Load, Rectifier, Control System & Mains
> Alarm LED (red) = Major Alarm active
> Warning LED (yellow) = Minor Alarm active
> Power LED (green) = Normal status active
Slide 33 of 23 08.04.23
Panel TraseroCAN BusPanel TraseroCAN Bus
CAN bus
Part No : 242100.110(RoHS compliant)
•ID based serial bus communications
•Max 8 Smartpack
•Max 50 Rectifiers
Slide 34 of 23 08.04.23
Panel TraseroMonitoreo de BateríasPanel TraseroMonitoreo de Baterías
Monitoreo de Baterías
Part No : 242100.110(RoHS compliant)
Con 4 : StandardCon 3 : Extended
• Symmetry measurement
• 8 strings mid point or2 strings 12V block
• Sensor de Temp.
Slide 35 of 23 08.04.23
ConectividadBateríaConectividadBatería
> CON3 & CON4 – Conexiones de baterías
Cable Sensor de Temperatura
Pin Function
1 Symmetry I/P 1
2 Symmetry I/P 2
3 Symmetry I/P 3
4 Symmetry I/P 4
5 Symmetry I/P 5
6 Symmetry I/P 6
7 Symmetry I/P 7
8 Symmetry I/P 8
9-10 Con 3 : Temp sense 2
Con 4 : Temp sense 1
11 - 14 Con 3 – 2nd batt current, batt fuse
Con 4 : Not used
Slide 36 of 23 08.04.23
Conectividad - Batería> CON3 & CON4 – Conexión de batería
Slide 37 of 23 08.04.23
> Symmetry measurement options
ConectividadSymmetryConectividadSymmetry
Slide 38 of 23 08.04.23
Panel TraseroSistema internoPanel TraseroSistema interno
Sistema Interno
Part No : 242100.110(RoHS compliant)
System measurements
Unit Power
2xLVD control (Latched)
Battery fuse fail
Slide 39 of 23 08.04.23
Conectividad SistemaConectividad Sistema
> CON5 – Conexión del sistemaPin Function
1 Positive Input
2 Negative Input
3 Batt Current +ve
4 Batt Current -ve
5 Batt Fuse +ve
6 Batt Fuse -ve
7 Load Fuse Fail
8 LVD1 Active
9 LVD1 Common
10 LVD2 Active
11 LVD2 Common
System Connection Card. Art 200625
Slide 40 of 23 08.04.23
ConectividadSistemaConectividadSistema
> Sistema de Configuración de la tarjeta
JP1-48v system = 1-2 +24v system = 2-3
JP2-48v system = ‘Neg’+24v system = ‘Pos’
Slide 41 of 23 08.04.23
Panel TraseroAlarmas I/OPanel TraseroAlarmas I/O
Alarma I/O
Part No : 242100.110(RoHS compliant)
Con 1 (standard):-
2 + 2 relay input / output
Con 2 (extended):-
4 + 4 relay input / output
Slide 42 of 23 08.04.23
ConectividadExterna y Alarm I/OConectividadExterna y Alarm I/O
> CON1 & CON2 – I/O Conexiones Pin Function
1 - 2 Alarm input 1 ( + / -)
3 – 4 Alarm input 2 ( + / -)
5 - 7 Alarm output 1 ( NO /C / NC)
8 - 10 Alarm output 2 ( NO /C / NC)
1 - 2 Alarm input 3 ( + / -)
3 - 4 Alarm input 4 ( + / -)
5 - 6 Alarm input 5 ( + / -)
7 - 8 Alarm input 6 ( + / -)
9 - 11 Alarm output 3 ( NO /C / NC)
12 - 14 Alarm output 4 ( NO /C / NC)
15 - 17 Alarm output 5 ( NO /C / NC)
18 - 20 Alarm output 6 ( NO /C / NC)
Alarm Output & Input CardArt 105954
Slide 43 of 23 08.04.23
RS-232 OpcionesRS-232 Opciones
RS-232 mounted
Part No : 242100.111(RoHS compliant)
•Enables connection of Standalone Webpower or modem
•Rear position : Replaces extended Battery symmetry card
Part No : 242100.112(RoHS compliant)
Slide 44 of 23 08.04.23
Smartpack
Smartpack Extended RS232
Slide 45 of 23 08.04.23
Panel TraseroWebpower incluidoPanel TraseroWebpower incluido
Embedded
WebPower
Part No : 242100.113(RoHS compliant)
Ethernet interface of remote monitoring of SmartpackIs possible to “tunnel” Powersuite remotely also.
Slide 46 of 23 08.04.23
Smartpack
Smartpack SNMP/Webpower
Slide 47 of 23 08.04.23
EscalabilidadEscalabilidad
Smartpack MasterSmartpack Slave n
System functionalityVoltage input 1
Symmetry inputs 8 (2x4x12V)
Current inputs 2
Temperature inputs 2
General purpose inputs 6
Load fuse input 1
Batt fuse input 2
Relay outputs 6
Contactor control 2+
System functionalityVoltage inputs 2
Symmetry inputs 16 (4x4x12V)
Current inputs 4
Temperature inputs 4
General purpose inputs 12
Load fuse input 2
Batt fuse input 4
Relay outputs 12
Contactor control 4+
System functionality with 8 modulesVoltage inputs 8
Symmetry inputs 64 (16x4x12V)
Current inputs 2x8
Temperature inputs 2x8
General purpose inputs 6x8
Load fuse input 1x8
Batt fuse input 2x8
Relay outputs 6x8
Contactor control 2+x8
Smartpack Slave 1
CAN/Power bus
Slide 48 of 23 08.04.23
ConectividadLatched ContactorsConectividadLatched Contactors
A latching contactor changes state only when a reversed pulse voltage is applied to the coil.
Protection Diode
Slide 49 of 23 08.04.23
> Explorer oriented easy to use PC SW
> USB gives simple access.
> Wide functionality with clear graphic presentation.
PowerSuitePowerSuite
Slide 50 of 23 08.04.23
Smartpack Front / Power SuiteContent
> Front menu
> Password levels
> Alarm ”monitor”
> AlarmGroups and output (relay) mapping
> ”Programmable” inputs
> Event log
> Operational mode and ”Critical” conditions
> Low Voltage Disconnect (LVD)
> Battery functions• Battery discharge test• Test results• Battery tables• Temp. comp & Charge curr. limitation• Test results• Special monitors• Boost• Symmetry
> Calibration & shunt Scaling
> Rectifier ID’s
> Mains measurement
> PowerSuite installation and basic introduction
Slide 51 of 23 08.04.23
Niveles de acceso
> Smartpack/PowerSuite password• 4 digit pin-code
> Nivel de usuario• No password
> Novel de Servicio• Password: ”0003” (default)
> Nivel de Fabrica • Password:
> Si perdió la contraseña de servicio, envíe el numero de serie a fabrica, para poder enviar ”PUK-code” de retorno.
Slide 52 of 23 08.04.23
Smartpack menu frontal
Option Description
NomVolt Nominal output voltage
BoostVolt Battery boost-charging voltage
LowBatt1 Voltage limit for MinorLow Battery Alarm
LowBatt2 Voltage limit for MajorLow Battery Alarm
HighBatt1 Voltage limit for MinorHigh Battery Alarm
HighBatt2 Voltage limit for MajorHigh Battery Alarm
LVBD Voltage limit for Low Voltage Battery Disconnect (LVBD)
LVLD 1.1 Voltage limit for Low Voltage Load Disconnect (LVLD)
> VoltageInfo - details
Slide 53 of 23 08.04.23
Smartpack menu frontal
> RectifierInfo - details
Option Description
NoOfRects. Number of rectifiers installed in the system.
RectCurrent Rectifier current
RectSerialNumber Rectifier ID and serial number
Rect.PrimaryVolt Rectifier input mains voltage
Rectifier Status Rectifier status
Rectifier Temp Rectifier temperature
Slide 54 of 23 08.04.23
Alarm ”monitor” cont’
Slide 55 of 23 08.04.23
Entradas programables
> 6 entradas digitales programables.
Slide 56 of 23 08.04.23
Entradas programables> Input ”Monitor”
• Event is selectable in ”drop-down-list”- Not all activates a function (yet...)
• Description may be changed
> Description and Event text listed in Event log
Slide 57 of 23 08.04.23
Log de Eventos
> Smartpack front: ”DisplayMessages”
> PowerSuite: “Event Log”
> El Smartpack controlador puede almacenar hasta 1000 eventos cronológicos. Cuando el registro esta lleno, se sobre escribe el más viejo evento.
> El registro se almacena en EEPROME
Ejemplo• 27-09-2005 (Date ”dd-mm-yyyy”)
• 17:15 (Time ”hh:mm”)
• Battery Voltage (Monitor name/Description)
• MinorLow: ON (Event status in monitor)
Slide 58 of 23 08.04.23
Desconexión por bajo voltaje (LVD)
> Se toma la acción de desconexión cuando el sistema está en “crítico” y:
- El voltaje de la batería esta debajo del limite.
- Delay time ha expirado, si es activo.
> Volver a conectar se toma cuando el sistema “NO es crítico” y:
- El voltaje de la batería está sobre límite.
> Default hysteresis entre reconexión y desconexión es de 4V
Slide 59 of 23 08.04.23
Funciones de Batería Test de Descarga
> Smartpack Tiene dos tipos de test batería.• Normal – usa la tabla de batería
• Simplificado – usa el voltaje final y el tiempo a criterio- Si se alcanza el tiempo de la prueba las baterías son buenas- Si se alcanza el voltaje final de las baterías primero son malas
> Tres diferentes modos de test son posibles (para ambos tipos)• Manual: Empiezo y parada por una entrada manual
• Periódico/Intervalo: Programado por tiempo, fecha y el intervalo de periodos.
Slide 60 of 23 08.04.23
Funciones de BateríaResultado del Test
> Hasta 10 diferentes resultados de la prueba de descarga almacenados en la EEPROM• Empiezo Fecha [mm/dd/yyyy]• Tiempo Final [hh:mm]• Tipo de Test [Manual/Periodic/Automatic]• Tabla de batería• Duración del Test [m]• Corriente de descarga [Ah]• Voltaje final [V]• Calidad Calculada [%]• Resultado del Test
> Datos Registardos• Corriente de bateria(1 & 2)• Voltaje de bateria• Temperatura(1 & 2)• Voltaje de simetria (8)
> Los Resulatados pueden ser vistos haciendo click en el icono de batería en la columna del resultado de la prueba• First 10 min and last 10 min logging are done every minute• In between every
- 10 min (test duration < 300 min) - 20 min (300 min < test duration < 600 min)- 40 min (600 min < test duration < 1200 min)
Slide 61 of 23 08.04.23
Funciones de Batería Tabla de Batería
> Smartpack puede almacenar dos tablas de batería definida por el usuario con:• Tiempo [min]• Corriente de Bateria 1.9V/cell Voltaje final alto [A]• Corriente de Bateria 1.75V/cell Voltaje final bajo [A]
> NOTE. Muchas tablas de batería pueden ser almacenadas en la PC y facil de uploaded al Smartpack con PowerSuite
> What is Eltek Std?• Es el promedio de valores no cambiables de los diferentes tipos de
fabricantes de baterías.
Slide 62 of 23 08.04.23
Funciones de Batería Tabla de Batería
> Configuración de la tabla de baterías por Powersuite
Slide 63 of 23 08.04.23
Funciones de Batería Tabla de Batería
Slide 64 of 23 08.04.23
Funciones de Batería Temp. Comp. & Curr. Lim.
> Compensacion por temperatura• Slope
• Ref. temp
• Min comp. volt
• Max comp. volt
> Limitación corriente de batería• Dos limitación configurables (v1.02)
• Planta generadora, indicando con una entrada digital.
Slide 65 of 23 08.04.23
Funciones de Batería Temp. Comp. & Curr. Lim.
52,5
53
53,5
54
54,5
55
55,5
Temperature T [oC]
Ou
tpu
t V
olt
age
[Vd
c]
Min Comp, volt Max Comp, Volt
Slope
Slide 66 of 23 08.04.23
Funciones de Batería Temp. Comp. & Curr. Lim.
Mains
Ba
tte
ry C
urr
en
t (A
)
Float current
Battery current limit [A] = 0.3*C10
Mains OK Mains OK, RechargeMains failure Mains OK
Load current
Slide 68 of 23 08.04.23
Rectifier ID’s cont’
> Reset number of rectifiers
>
Soluciones de SistemasSoluciones de Sistemas
Cuanta potencia usted necesita ?
Slide 70 of 23 08.04.23
4 across a 19” rack
1U
Mas densidad de potenciaMas densidad de potencia
Up to 8000W per 1PR shelf
370mm deep
Slide 71 of 23 08.04.23
Montaje FlexibleMontaje Flexible
Smartpack mounting options
Smartpack in PR Smartpack in Distribtuion
Slide 72 of 23 08.04.23
Incluye (up to) :
Soluciones IntegradasSoluciones Integradas
1U Distribucion + 1 PR
8000W (166A@48V)
Smartpack
2 x 100A Breakers de Bateria
6 x 2–32A Breakers de Carga
2 x LVD (150A)
Soluciones Integradas 2U
5 kg (exc rectifiers)
Slide 73 of 23 08.04.23
Incluye (up to) :
Soluciones IntegradasSoluciones Integradas
4U Distribucion + 1-4 PR
32000W (660A@48V)
Smartpack
6 x 100A Breakers de Bateria*
18 x 2–63A Breakers de carga*
2 x LVD (up to 600A)* Verficar en datasheet por otra for otra
configuracion disponible
Solucion Integrada 5 - 8U
8 kg (exc rectifiers)
Slide 74 of 23 08.04.23
Soluciones IntegradasSoluciones Integradas
FP2NX-48-9U power system block
Battery Tray #4
Battery Tray #3
Battery Tray #2
Battery Tray #1Battery Disconnect #1
Battery Disconnect #2
Battery Disconnect #3
Battery Disconnect #4
23” EIA Seismic Equipment Rack
7U available equipment space
Slide 75 of 23 08.04.23
GabinetesGabinetes
> 8 - 96 kW en un solo Gabinete
> Max 2000A@48V = 96kW
(CAN bus limitation)
> Típicamente hasta 4PR por sistema con baterías.
> Variedad de gabientes disponibles
Example 32 kW
Slide 76 of 23 08.04.23
Solución Gabinete 96kW Solución Gabinete 96kW
• Input 230V/400V 3-phase
• FP2 2kW rectifiers
• Max Output 48V 2000A
• Cabinet dimensions: 600x2000x600mm
• 2 SmartPacks (Master-Slave)
Slide 77 of 23 08.04.23
Gracias!!