+ All Categories
Transcript
Page 1: Spectra Series™ Power Panelboards - GE Industrial · AFP5X 60 A & 100 A, 5X 44 AFP7T 100 A & 200 A T fuse, 7X 44 AFP7X2 200 A R fuse, 7X double branch 44 AFP7X 200 A R fuse, 7X

gSpectra Series™ Power Panelboards

Type AFP Filler Plates

WARNING: Danger of electrical shock or injury.Turn OFF power ahead of the panelboard orswitchboard before working inside theequipment or removing any component. Donot remove circuit protective devices or anyother component until the power is turnedOFF.

Installing the Filler PlatesUse the following procedure to install type AFP fillerplates. The catalog numbers covered by this instructionare listed in Table 1.

CatalogNumber Use with ADS Switch

BoxWidth, in.

AFP10T 400 A & 600 A J or T fuse, 10X mainor branch

36, 44

AFP10X 400 A & 600 A R fuse, 10 X main orbranch

44

AFP19X 800 A & 1200 A, 19X main or branch 44AFP4X 30 A & 60 A, 4X 44AFP5X 60 A & 100 A, 5X 44AFP7T 100 A & 200 A T fuse, 7X 44

AFP7X2 200 A R fuse, 7X double branch 44

AFP7X 200 A R fuse, 7X main or singlebranch

36, 44

Table 1. Type AFP filler plates covered by this instruction.

1. For ease of assembly, the filler plates should beinstalled after the side trim is in place.

2. Insert the flat end of the filler plate into the channelon the edge of the side trim, as shown in Figure 1.

Figure 1. Inserting the filler plate into the side trim.

3. Attach the opposite end of the filler plate to theflange on the device, using the screws furnished onthe filler plate, as shown in Figure 2. Tighten thescrews to 25–30 in-lb.

Figure 2. Attaching the filler plate to the device.

gGE Industrial Systems

General Electric Company41 Woodford Ave., Plainville, CT 06062

GEH5590 R03 0701 © 2001 General Electric Company

These instructions do not cover all details or variations in equipment nor do they provide for every possible contingency thatmay be met in connection with installation, operation, or maintenance. Should further information be desired or shouldparticular problems arise that are not covered sufficiently for the purchaser’s purposes, the matter should be referred to theGE Company.

GEH5590 Installation Instructions R03

Side Trim Filler Plate

Screw

Top Related