cdvigroup.com 1
STAR1M - Mullion Mifare® standalone controller and card reader
Security to Accesswww.cdvigroup.com
English EN
STAR1M
Mullion Mifare® Standalone Controller and Card Reader
cdvigroup.com2
STAR1M - Mullion Mifare® standalone controller and card reader
1] PRODUCT PRESENTATION - 2-in-1 Mifare Reader : - Standalone Access control system - Wiegand Mifare® reader mode- Resin-coated electronics- Audible and visual feedback- 3 metre cable (10 wire cable - AWG28)- Up to 150 cards (shadow mode)- Up to 300 cards (standard mode)- 1 Relay output (1A 12V dc)- 1 Request to exit input
-25°C à +70°C
STAR1M
IP54
Dimensions (L x W x D): 130 x 41 x 28 mmTechnology: 13.56 MHzProtocol: Mifare® classic, ultralight CInput voltage: 12VdcConsumption: 120mAWiegand 26/30/44-bit (Mifare® reader)
2] REMINDERS AND RECOMMENDATIONSRecommended cable10 wire cable (AWG28)
Recommended power suppliesADC335 and BS60 (in case the reader is powered by neither the controller nor the reader controller [INTBUSW]).The power supply must be designed to be a limited power supply as defined by EN 60950-1.
EnvironmentWhen in a humid area or close to the sea, we recommend applying varnish to the terminals to avoid oxidation.
Installation recommendationsTo protect the device from back EMF, do not forget to install the varistor across the lock terminals (in parallel).
This product is shipped with a varistor.The varistor must be connected directly to the locking system terminals (electric strikes, electromagnet, or lock) operated by the device. If the device functions with several locking systems, each one must be fitted with a varistor. The varistor limits overload produced by the strike coil, known as self-effect or back EMF. If you are using a shearlock, electromagnet or other type of electric lock, we recommend the use of dedicated power supply for the lock.
For optimum lighting, be
careful to not fold the cable
inside the product.
3] MOUNTING KIT
Leaktight seal
TF 3x30 Screws
S5 Plastic anchor
TORX® Screwdriver tip
TORX® 3x8 Screws
Varistor METALR tag
STAR1M 1 2 2 1 1 1 1
R76,7
R35,
4
7
60
30
Ce document est la propritété exclusive de CDVI, il ne peut être communiqué à des tiers sans son autorisation.This document is the exclusive property of CDVI and it may not be disclosed to others without permission.
31, av du Gal Leclerc93691 PANTIN CEDEXF R A N C ETel : 33(0)148910102Fax : 33(0)148912121www.cdvi.com
Plan M1806-VdE
Edition 00
Date 01/10/2009
ECHELLE 1:1
A4V
DES.: A. Broustal
Matière : ... Tolérance gale : 0.1 Etat de surface : Ra 3,2
A0228015Badge PP New
plan coté pour dépôt "dessin&modèle" C.A.: ...
Vol. (mm3) : Poids (g) :
IK09
Frequency band: 13,553 - 13,567 MHzMaximum power emitted: 42 dBμA/m
We, CDVI, declare that the STAR1M complies with the 2014/53/UE European directive. The full UE declaration is avaiblable on our website www.cdvi.com.
INSTALLATION MANUAL EN
Thank you for buying our products and for the trust placed in our company
cdvigroup.com 3
STAR1M - Mullion Mifare® standalone controller and card readerINSTALLATION MANUAL EN
4] OPERATION MODES
Dipswitch Standalone mode (page 13)Wiegand mode
(page 18)
1 OFF ON
2OFF ON OFF ON
Change the Master card
NORMAL operation
Dipswitch 3 option 44-bit
3OFF ON OFF ON
Shadow mode (page 15)
Standard mode (page 16) 26-bit 30-bit
4 Not assigned
The different dipswitch positions are used to switch the STAR1M to a standalone system or to a Mifare® access reader.
5] WIRING DIAGRAM
C56
C58
C61
1
MM10
4
3
2
1 ON
ON
ON
ON
L7
Q6
Q7
Q8
R77
R78
R79
P1
1P3
BZ3
C6
C24
C59
-+
MM1
MM14
CR3
+
-
CR10
CR25
CR26
CR24
MM3
MM15
CR12
CR13
CR15
I1
+
-
+
-
MM16
CR22
P2
-
+
CR19
CR21
CR20
CR28
CR27
CR29
CR11R70R67
R68R64
R69R65
C68
CR30
Wire colors
Wiring tableStandalone mode Wiegand mode
Red 12Vdc 12Vdc
Black 0V 0V
Green / Data 0
White / Data 1
Blue Normally open /
Grey Common /
Purple Normally closed /
Brown Request to exit input Buzzer input
Yellow / Green LED input
Orange / Red LED input
LEDs on start-up:- Green (1s)- Red (1s)- Blue + BEEP (1s)
LEDs during routine operation:- Standby: Blue- When a tag is read: Green or red
To switch operation mode, please reboot the STAR1M.
cdvigroup.com4
STAR1M - Mullion Mifare® standalone controller and card reader
6] SETTING READER MODE
1
ON
2
ON
3
ON
ON ON ON
1 2 3
ON
OFF
ON
OFF
Before powering on, select the operating mode (Wiegand Mifare® reader or standalone mode).
1] Wiegand Mifare® reader (DIP1 ON)- green- red- blue + buzzer (starting sequence)
2] Standalone mode (DIP1 OFF) = factory default setting- green- red- blue + buzzer (starting sequence)- yellow/green: waiting for the Master card to be programmed (when powering on for the 1st time)
7] STANDALONE MODE- Mifare® compliant - ISO 14443A (Mifare® classic)- Programming using the Master card directly on the reader- Capacity: 1 Master card + 300 or 150 user cards (according to mode)- 1 door controller: 1 relay output N.O/N.C contact (1A 12Vdc)- 1 request to exit input- Compatible with METAL, PVP (Mifare®) badges, BV cards (ISO Mifare® credit card format) and ERV, ERNV remote transmitters
INSTALLATION MANUAL EN
ON
4
ON
4
Electric strike wiring example (Fail secure)
12V DCADC335
Push button
Strike fail secure
All our locks are fitted with a varistor.
cdvigroup.com 5
STAR1M - Mullion Mifare® standalone controller and card readerINSTALLATION MANUAL EN
Electromagnetic lock wiring example (Fail safe)
12V DCADC335
Push button
MagnetStrike fail safe
Normal operation
1
ON
2
ON
3
ON
4
ON ON
OFF
Swipe user cardAccess granted Beep + green LED + relay activated
Access denied Beep + red LED
Blue LEDPosition DIP2 to ON
The factory setting of the STAR1M is shadow mode.For first use, please program a master badge (see process page 8).
cdvigroup.com6
STAR1M - Mullion Mifare® standalone controller and card readerINSTALLATION MANUAL EN
Enter programming mode
Yellow led
Present user card Beep + green LED then yellow LED
Blue LEDPresent the master badge
Swipe the master badge or wait 10 seconds
Exit programming mode
To add more cards, repeat step user card and step shadow card.
Present the shadow card2 beeps + green LED flashing
Add user cards (max. 150)
Delete user cards
Enter programming mode
Yellow LED
Present the user card or its shadow cardBeep + LED OFF then back to yellow LEDPresent again the same cardBeep + red LED then back to yellow LEDBoth cards are deleted
Blue LED Present the master badge
Swipe the master badge or wait 10 seconds
Exit programming mode
7.1 Shadow mode
In Shadow mode, two different badges are programmed for the same user. The user gets one of the two badges and the second badge is stored in a secure place by the system supervisor as a shadow badge. These 2 badges can both grant access. In the event that the user badge is lost or stolen, the shadow badge can be used to delete the user badge from the STAR1M.
1
ON
2
ON
3
ON
4
ON ON
OFF
Dipswitch setting
cdvigroup.com 7
STAR1M - Mullion Mifare® standalone controller and card reader
Blue LED
INSTALLATION MANUAL EN
Add user cards (max. 300)
Enter programming mode
Yellow LED
Present the user card one after the otherBeep + green LED then yellow LED If the card is already programmedBeep + LED OFF then back to yellow LED
Blue LEDPresent the master badge
Swipe the master badge or wait 10 seconds
Exit programming mode
Enter programming mode
Yellow LED
Present the user cardBeep + LED OFF then back to yellow LED Present again the same card Beep + red LED then back to yellow LED.
Blue LED
Delete user cards
Present the master badge
Swipe the master card or wait 10 seconds
Exit programming mode
7.2 Standard mode
In Standard Mode only one user badge is programmed for each user. To delete a user from the STAR1M, enter the programming mode and present the user badge.
1
ON
2
ON
3
ON
4
ON ON
OFF
Dipswitch setting
cdvigroup.com8
STAR1M - Mullion Mifare® standalone controller and card readerINSTALLATION MANUAL EN
7.3 Common operation
Program or replace a Master badge
1
ON
2
ON
3
ON
4
ON ON
OFF
Set DIP2 to OFF
Yellow LED + Beep
Present the new master badge (the old one will be erased)
Beep + LED OFF
1
ON
2
ON
3
ON
4
ON ON
OFF
Set DIP2 to ON
Beep
Blue LED
After 10 seconds
White and Red LED flashing + Beep
1 flash : 1 second
Program the unlock time
Enter programming mode
Yellow LED
Press the push button Each push button press: 1 second Blue LEDPresent the master badge
Default value : 5 seconds, programmable from 01 to 99 seconds
1
ON
2
ON
3
ON
4
ON ON
OFF
Switch on power supply
White/Red LED flashing while the memory is deleted. Followed by start-up sequence
Delete all cards (reset the reader to the factory default values)
Switch off power supply Set DIP1 to ON
Switch off power supply
1
ON
2
ON
3
ON
4
ON ON
OFF
Set DIP1 and DIP2 to OFF Standalone Mode is activated Switch on power supply
To delete all cards switch to Wiegand mode Switch to standalone mode
cdvigroup.com 9
STAR1M - Mullion Mifare® standalone controller and card readerINSTALLATION MANUAL EN
8.1 Wiegand 26, 30 and 44 bit output format
8] MIFARE® READER WIEGAND MODE
OFF1
ON
2
ON
3
ON
4
ON ON
OFF1
ON
2
ON
3
ON
4
ON ON
OFF1
ON
2
ON
3
ON
4
ON ON
30-bit Wiegand Output
44-bit Wiegand Output
26-bit Wiegand Output
Important : - Switching « shadow mode » to « independent mode »: all cards are saved
but become independant- Switching « independent mode » to « shadow mode »: all cards are erased
cdvigroup.com10
STAR1M - Mullion Mifare® standalone controller and card readerINSTALLATION MANUAL EN
8.3 LEDs management in CENTAUR
8.2 LEDs management in ATRIUM
GREEN ACCESS GRANTEDRED ACCESS DENIEDBLUE STANDBY
LED STATUS
GREEN ACCESS GRANTEDRED ACCESS DENIEDBLUE STANDBY
LED STATUS
GREEN LEDCONFIGURATION
RED LEDCONFIGURATION
GREEN LED CONFIGURATION
RED LEDCONFIGURATION
Reference : G0301FR1031V04Extranet : CDVI_IM_STAR1M_A5_EN-01
cdvigroup.com 11
STAR1M - Mullion Mifare® standalone controller and card reader
Security to Accesswww.cdvigroup.com
Reference : G0301FR1031V04Extranet : CDVI_IM_STAR1M_A5_EN-01
*G0301FR1031V04*
CDVI GroupFRANCE (Headquarters)
Phone: +33 (0)1 48 91 01 02
CDVI FRANCE + EXPORT31, av. du Général Leclerc93500 PANTIN - FrancePhone: +33 (0)1 48 91 01 02www.cdvi.com
CDVI AMERICAS[CANADA - USA]Phone: +1 (450) 682 7945www.cdvi.ca
CDVI BENELUX[BELGIUM - NETHERLANDS - LUXEMBOURG]Phone: +32 (0) 56 73 93 00www.cdvibenelux.com
CDVI TAIWANPhone: +886 (0)42471 2188www.cdvichina.cn
CDVI SUISSEPhone: +41 (0)21 882 18 41www.cdvi.ch
CDVI CHINA Phone: +86 (0)10 84606132/82www.cdvichina.cn
CDVI IBÉRICA[SPAIN - PORTUGAL]Phone: +34 (0)935 390 966www.cdviberica.com
CDVI ITALIAPhone: +39 0321 90 573 www.cdvi.it
CDVI MAROCPhone: +212 (0)5 22 48 09 40www.cdvi.ma
CDVI NORDICS [SWEDEN - DENMARK - NORWAY - FINLAND]Phone: +46 (0)31 760 19 30www.cdvi.se CDVI UK [UNITED KINGDOM - IRELAND]Phone: +44 (0)1628 531300 www.cdvi.co.uk
CDVI POLSKAPhone +48 12 659 23 44 www.cdvi.com.pl
All t
he in
form
atio
n co
ntai
ned
with
in t
his
docu
men
t (p
ictu
res,
dra
win
gs,
feat
ures
, sp
ecifi
catio
ns a
nd d
imen
sion
s)co
uld
be p
erce
ptib
ly d
iffer
ent
and
can
be c
hang
ed w
ithou
t pr
ior
notic
e.