SECTION 5: page �
Temaline Solutions
Section 5.�: Access Control Solutions
Honeywell’s total new concept in access control, integrated security solutions and security system communications.
Temaline re-defines the concept of access control sub-systems for the future by bringing enhanced performance and reliability
to installations. Temaline establishes a new benchmark in providing secure solutions to protect people, property and assets.
The complete modularity of the system frees the peripheral and field devices from reliance on the central supervisory system
for all access control functionality and relieves the supervisory system of card transaction processing.
Most systems today have too
many vulnerabilities. A failure of the
central supervisory system or loss of
communications causes untold problems in
any organisation.
Availability
Peer-to-peer communication allows the
system to work autonomously and completely
without degradation of performance or
security, without the supervisory system.
System availability is furthermore enhanced
by a ‘Shared Load’ concept undertaken by
smart TemaServers. When one TemaServer
fails another ‘takes over’ the management
of its TemaKeys, without suffering any
degraded operation in the system. A
removable FlashEprom cartridge guarantees
complete data recovery on any TemaServer.
Expandability
From small to large complex facilities, there
is a need for a flexible solution. System
installations are ‘living’ entities, constantly
changing and expanding to meet the facility
environment. Temaline’s design concepts
of modularity and openness address this
requirement exactly. When expansion
is required, simply add what is needed,
without having to add intermediary devices
such as terminal servers or extensive
reprogramming.
HEADQUARTERS
REGIONS
BRANCHES
SECTION 5: page �
Section 5.�: Access Control Solutions
Temaline Solutions
Peripheral Controllers: The TemaServer
is the heart of the system architecture.
l The design concept establishes a new
benchmark for features and functions of
a peripheral device
l The enhanced distributed intelligence
and peer-to-peer communication
creates an operating environment to
allow multi-application devices, including
access control, time and attendance and
intruder detection
l For a unique level of security, continuity
and performance, TemaServers feature
a Shared Load function. During normal
system operation, each TemaServer
manages its devices but, should one
of the TemaServers fail, the remaining
TemaServer takes over the management
of the orphaned devices without
any degradation or loss of system
functionality
Field Devices: The TemaKey devices
are the connection of the system with
the company’s employees, visitors and
subcontractors.
l Through a modular Plug & Play
approach, TemaKey can meet any
customer variable in a facility
l TemaKeys are composed of any
combination of readers, displays,
keyboards, digital sensors, actuators
LONWORKS
ETHERNET
EnterpriseBuildings
Integrator™(EBI)
TemaServers
TemaKeys
TemaKeys
ETHERNET
EnterpriseBuildings
Integrator™(EBI)
TemaServers
Peer-to-Peer
TemaKeys
LONWORKS
ETHERNET
EnterpriseBuildings
Integrator™(EBI)
TemaServers
TemaKeys
LONWORKS
SECTION 5: page �
Temaline Solutions
Section 5.�: Access Control Solutions
An Open Environment
Temaline meets openness at three
levels:
l Shared database functionality allows
customers to use their own company
database to manage cardholder
database information
l Ethernet networks with TCP/IP
communication protocols; there is no
longer a need for additional terminal
servers. Temaline’s communication
structure matches exactly customer IT
philosophies both now and in the future
l LONWORKS® – compatible field
devices guarantee the ability to interact
with other devices including: building
management applications (HVAC,
lighting etc.) and fire alarm systems
The same TemaServer platform manages
different applications such as access
control, time and attendance and intruder
detection. No other system provides this level
of security systems integration capability.
Temaline’s communication protocol allows
real-time event management and direct
panel to panel communication.
Shared Database Application
Database technology is a critical element
in the operations of a security system
today. Temaline is designed with a powerful
database distribution engine (DBDE) which
manages the database updating to the
TemaServers.
Save On Costs
The advent of Enterprise Resource
Management providers, such as SAP®,
Oracle, PeopleSoft and others, are also
increasing customer focus on systems
integration and the openness as they
seek ways to tie their facilities into singular
interacting systems to save on operational
costs.
This shift in influence has been felt most
strongly in the inter-relationships between
access control, time and attendance and
payroll applications.
Honeywell has been actively installing
SAP® approved solutions for over 10 years
and now a new capability is here – a SAP®
certified application meeting the validation
of SAP® for time and attendance and access
control and all are on the same hardware
platform.
l Distributed, uninterruptible and intelligent
power supply is totally independent from
the data wiring, so many power supply
modules can be located on a system to
provide the necessary power specific
field device groups
l Service and maintenance diagnostic
tools perform remote monitoring on all
Temaline devices. Diagnostic features
can be implemented as embedded
functions of the terminals or as external
tools
l Remote maintenance provides for
read/restore/edit functions to all system
configuration parameters
SAP is registered trademark of SAP® AG
The Complete Honeywell
Security Solution
As one of the world’s leading security
companies, Honeywell understands
the need to protect people, assets
and intellectual property. With an
international network of skilled people,
state of the art technology and global
experience, Honeywell can meet
individual customers needs with
complete security solutions.
l Providing help with all aspects of a
project from initial needs analysis
through designing systems and
managing installation, to providing
ongoing maintenance and systems
operation
l A comprehensive understanding of
security requirements, technologies
and innovations
l Being there to help customers,
whenever there is a need
SECTION 5: page �
10 Reasons to Specify Temaline
Section 5.�: Access Control Solutions
1System AvailabilityStandalone capabilities of the controllers ensure complete autonomy of the access control system.
2ReliabilityA product from a world leader in Advanced Access Control Solutions with a proven performance on thousands of projects.
3ExpandabilityBased on native TCP/IP Ethernet communications ensures that the system is able to expand as requirements expand.
4Multi-Site ManagementTemaline allows management of a single building, to a multi building campus or a global solution covering any number of facilities with single or multiple operator stations.
5Powerful Integration CapabilityAs a key solution from the award winning Enterprise Buildings Integrator facility management central, Temaline is able to integrate with CCTV, Fire, HVAC, Asset Management and many other building automation technologies.
6Integration of �rd Party TechnologiesTemaline can integrate with existing card readers via industry standard Wiegand interface. Multiple reader technologies on a single door can also be managed. Integration into 3rd party ERP’s systems such as PeopleSoft, SAP, Oracle and many others is available using standard tools.
7Durable System LifeWith a proven record of very low Mean Time Between Failure (MTBF) as well as flash upgradeable operating firmware, Temaline provides a lifetime of functionality and reliability.
8Multi Functional SystemTemaline has been designed not only to support advanced access control applications, but also advanced Time and Attendance applications (including HR and Payroll integration), Electronic Visitor Management and many more advanced applications.
9Multi Application DevicesTemaline’s unique range of multi function card readers and HMIs allows not only advanced access control applications but also Time and Attendance, Intruder Detection, Bulletin Board Service, Muster Station functionality and much more.
10IT Infrastructure CompatibilityNative Ethernet, Microsoft Windows and SQL and other features ensures that Temaline is able to operate with existing IT services.
HEADQUARTERS
REGIONS
BRANCHES
SECTION 5: page 5
Temaline Specification Data
Section 5.�: Access Control Solutions
KEY FEATURESl Provides a simple, three-level
architecture. The supervisory level is
managed by Honeywell’s Enterprise
Buildings Integrator™ (EBI) and provides
the Human Machine Interface
l At the peripheral level the TemaServers
(controllers) manage the peripheral
database containing all the information
essential to ensure the complete
autonomy of the devices independent of
the supervisory level
l TemaServers communicate on a
peer-to-peer basis with one another
and exchange data in order to share
information in a distributed mode
creating greater system autonomy
l The field devices – or TemaKeys
– represent the interface to the
“environment” such as employees and
visitors, doors and turnstiles. TemaKeys
represent readers, displays, keyboards
and Input/Output modules
l Controllers use industry-standard TCP/
IP networking over Ethernet leveraging
the facility’s existing Ethernet network.
Controller to field communication
is managed using an Echelon
LONWORKS® network
l Applications include integrated Access
Control, Time & Attendance, Intrusion
Detection, Reception Management
LONWORKS
ETHERNET
EnterpriseBuildings
Integrator™(EBI)
TemaServers
TemaKeys
TemaKeys
ETHERNET
EnterpriseBuildings
Integrator™(EBI)
TemaServers
Peer-to-Peer
TemaKeys
PersonalBadge
RDR
EquipmentBadge
LONWORKS
SECTION 5: page �
Temaline Specification Data
Section 5.�: Access Control Solutions
The modular design of the system frees the
controllers and field devices from reliance
on the central supervisory system for all
access control functionality and relieves the
supervisory system of the responsibility of
card transaction processing.
ACCESS MANAGEMENT
AND CONTROL
The basic goal of the Temaline Access
Control system is to ensure the security and
safety of the resources – people, assets,
documents, intellectual property – present in
a specific area, while still allowing authorised
users easy, but controlled access.
The Temaline system philosophy is as
follows:
l People Management – extend the
Access Control solution to also
include intrusion detection and Time &
Attendance
l Robust Solutions – high reliability and
availability
l Connectivity – direct Ethernet
connection to standard local or wide
area networks
TIME AND ATTENDANCE
MANAGEMENT
The Time and Attendance Manager is a fully
integrated software module within the EBI
Temaline Access Management and Control
application. As a result, database entries
need only be done once for each cardholder
and application.
In addition to the integral Time & Attendance
Manager, EBI Temaline has the ability to
interface to SAP®, Oracle and PeopleSoft
systems as well as other third-party
applications.
The same controllers and field devices
used for Access Control also manage
Time & Attendance functionality simplifying
the system architecture, design and
engineering.
INTRUSION
DETECTION
Integrated security requires interaction
between all security functions. EBI Temaline
accomplishes this via the concept of
“integration by design” using the same
core software, hardware platform,
database and the same field bus wiring.
All controllers, regardless of their specific
function communicate on a peer-to-peer
basis. The TemaServer is able to manage
a low-level intrusion detection strictly
integrated with access control. This task is
carried out using a TemaKey dedicated to
the management of digital input / output
signals. Each TemaServer is able to manage
up to 64 digital inputs and 64 digital outputs
and each I/O can be enabled/disabled/
armed/disarmed. The TemaServer device
continuously checks the status of the field
points controlled in order to detect a status
variation.
RECEPTION
MANAGEMENT
The term “reception management” refers to
all activities associated with checking in and
monitoring external persons who enter the
building. Typical activities include
l Checking in visitors on arrival
l Checking out visitors on departure
l Pre-registering visitors
l Keeping an address book of all company
contacts
l Collecting and performing historical
analysis of visitor data
l Assigning and administering the return
of temporary cards
LOSS
PREVENTION
The Asset Loss Prevention solution is
designed to control the rights of a cardholder
to exit/enter from a controlled location while
in the possession of specific, identifiable
assets.
SECTION 5: page �
Temaline Specification Data
Section 5.�: Access Control Solutions
PRIMARY SYSTEM CONCEPTS
The concept of “Integration by Design” is
the core philosophy of the EBI Temaline
architecture. Dedicated software allows
users to determine the operational
parameters for the chosen subsystems
– including Access Management &
Control, Time & Attendance, Intrusion
Detection, Reception Management and
Loss prevention. These design disciplines
create seamless inter-operability and a more
secure functioning system.
Access Management and Control
The access control platform of the EBI
Temaline subsystem guarantees one of the
highest levels of availability of any system
on the market today with multiple layers of
redundancy, peer-to-peer communication
and the highest marks for application
flexibility designed as standard in the
system.
The system controls and monitors the
peripheral hardware, stores all data received
via the same hardware devices, and makes
the data available for analysis.
The system operator can perform operations
such as:
l Check the number of users present in
each area
l Execute antipassback controls
l Execute “length of stay” checks on the
users
l Check the list of visitors that entered at a
given time
l Check the number of available parking
spaces in the parking lot
Time & Attendance
The Time & Attendance platform of EBI
Temaline allows administrative users the
ability to communicate with the company’s
employees via the field devices and
terminals.
The system manages the information
associated with the various clock-in and
clock-out operations and makes it available
to Time & Attendance applications such
as the EBI Temaline Time & Attendance
Manager or SAP®. The bi-directional
functionality also allows messaging from
administration to employees providing
broadcast or individually tailored messages.
A system user interacting directly with the
terminal display can execute the following
operations:
l Reason entry – specifies a transit reason
l Transit enquiry – interrogates the system
directly regarding past transit operations
l Generic enquiry – displays various
user-specific information requested by a
cardholder
l Spontaneous messages – display
personal information addressed either to
the cardholder or to a group, following a
card read operation
l Electronic bulletin board – displays
information addressed to all cardholders
who use the terminal
Intrusion Detection and Security
The EBI Temaline subsystem’s intrusion
detection platform ensures a high level of
security by allowing operators to monitor all
the events and alarms generated in a facility
in a single user interface.
The system immediately detects when
an intrusion sensor is activated, when a
gate is forced or when a communication
line is interrupted, and alerts the operator
concerned. The operator also receives
detailed information describing the alarm
or event as well as the required response/
action. Subsequent analysis of the events
and corrective actions taken by operators
facilitates the continued improvement of
security and control procedures and also
ensures continuous improvements to
company safety standards.
Remote access via either dial-in or Wide
Area Network (or LAN) connection or EBI’s
Alarm Pager option (providing notification via
SMS, e-mail, pager or SNMP) allows alarms
to be managed from remote workstations or
security centres, which is a great advantage
for installations that are not attended or
guarded 24 hours per day.
Asset Tracking & Loss Prevention
Asset Loss Prevention provides additional
security over a Real Time Location System
(RTLS). This option provides the ability to
not only locate assets within a facility but
also control the movement of assets in and
out of protected areas. Assets are equipped
with active, radio frequency tags that allow
them to be uniquely identified and they can
be linked to people, who are identified by
means of their access cards.
The system uses a combination of long-
range readers, transmitters and Temaline
devices connected together to form a
special Asset Portal (AP). In its simplest
form, the Asset Portal is a double technology
TemaKey, in which one reader is the radio
frequency receiver and the other a Temaline
reader.
SECTION 5: page �
Temaline Specification Data
Section 5.�: Access Control Solutions
LAN/WAN
EnterpriseBuildings
Integrator™(EBI)
TemaServers
RTLS Reader Prox Reader
Does this Person have authorisationto remove this Asset?
The diagram above illustrates a typical layout
for the entrance/exit area of a building when
creating an Asset Portal.
Reception Management
A visitor’s first impression of a company
is often the reception area. Providing an
efficient and professional reception service
is the first step in creating a positive
impression for visitors.
Temaline Reception Manager provides an
optional solution for managing visitors to a
facility and provides complete integration
Asset Loss Prevention System Concept
with the EBI Temaline access control
system. The seamless integration is critical
as it provides levels of security and visitor
control that cannot be provide by stand-
alone solutions.
In addition to capturing visitor data, the
visitor management package also permits
the issuing of visitor access cards and
temporary staff cards while the powerful
reporting capabilities help identify the
location of visitors present in the building at
any given time.
Temporary and Visitor Cards
Temporary and Visitor cards are configured
in the system and then physically stored
in an archive kept by reception staff. The
cards can then be issued and enabled
on demand – either for a new visitor or an
employee whose card has temporarily been
misplaced.
Visitor Pre-registration
Visitor pre-registration helps speed up the
visitor check in process by allowing staff to
enter details for their visitors prior to their
arrival.
The reception has access to an on-line list
of pre-registered visitors and simply have
to complete any outstanding details, issue
a card (or print a pass) if needed and start
the visit.
Visitor Check-in/Check-out
The reception desk manages all visitor
check-in/out operations including:
l Record personal and identification data
l Use the address book to identify a
contact person for the visit
l Record all data concerning the visit
and, if appropriate, assign a card and
associated access rights
l Print a visitor’s pass on paper or card
l Suspend and continue a check-in
operation to allow time to trace the
desired contact person
l Terminate the visit if it is not possible to
trace the desired contact person
l Modify data associated with the current
visit without terminating the visit itself, for
example, extend the card expiry date or
enter notes regarding the visit
Asset Loss Prevention Gate Configuration
SECTION 5: page �
Temaline Specification Data
Section 5.�: Access Control Solutions
WEB Reception Management
The WEB Reception Management
module improves the Reception Manager
functionality by providing an Internet
Explorer-based web browser connection
to the Reception Manager database. The
browser connection provides more stations,
better performance and reduces engineering
by eliminating the need for manual software
installation.
The functionality includes:
l Customised Human Machine Interface
l Check-in and check-out of visitors
l Visitor pre-registration
l Temporary card assignment and return
l Cardholder present in zone report
l User status
This option requires:
l The Reception Management option
l A Microsoft SQL Server Client
Access Licence (CAL) for each
computer using the browser based
solution.
Photo ID
EBI Temaline PhotoID is a fully integrated
function that enables the user to create
identification cards for users of the system.
The functionality includes;
l Image capture (including cardholder
photographs and signatures)
l Image storage in a variety of formats
such as bitmap, JPEG or GIF formats
l Integration of dynamic data from the EBI
Temaline database to the card layout for
printing specific cardholder details on
cards.
l Custom card graphic creation.
l Card printing
The integrated graphic design tool provides
the ability to create flexible and personalised
card layouts. Cards can be printed with
information specific to the cardholder such
as the cardholder’s first and last name,
additional personal data, a photograph and/
or a signature.
Cards can be used for visual identification
only, or as physical access cards that
are part of the electronic access control
system.
Interface to external applications
Access management systems are normally
integrated to third party or external systems
in order to exchange personnel data, either
to update cardholder details or to provide
transaction information to Human Resource
applications such as Payroll programs or
general Time & Attendance management
systems.
Temaline provides a flexible Time &
Attendance management solution allowing
the collection of entry and exit transaction
details using the employee’s standard
access card and, very often, the same
readers used for access control.
EBI Temaline supports the following
operations:
l Creation of data import/export and
conversion specifications
l Interaction with external applications
l Data export, manually or on-line
l Interaction with the HR-PDC Interface for
SAP R/3 for data import and export.
Personal data of the company’s employees
is imported from the Time & Attendance
application software. This application can
be a stand-alone application or part of a
complete Enterprise Resource Planning
solution such as SAP® or PeopleSoft.
User Access to the Web Reception Manager The Visitor Check-in/Check-out Form
SECTION 5: page �0
Temaline Specification Data
Section 5.�: Access Control Solutions
SITE A
SITE C
ETHERNET
SITE B
Enterprise Resource Management
Temaline provides the ability to interface to
common Enterprise Resource Planning
solutions such as SAP®, Oracle or
PeopleSoft.
EBI Temaline uses an SAP® Certified
Integration module for integration to the
mySAP Human Resource application
module via the HR-PDC channel. The
bi-directional HR-PDC interface allows
personnel data transfer from the SAP®
master database to EBI Temaline and the
transfer of transaction data – complete with
specific reasons and time codes for Time &
Attendance – to SAP®.
SYSTEM
ARCHITECTURE
The EBI Temaline solution can be grouped
into three distinct levels:
Supervisory Level
The Supervisory Level comprises the
Enterprise Buildings Integrator and Temaline
software and has the following primary
functions:
l System configuration
l Data collection
l Event analysis
l Reporting
l Interface to external applications
Peripheral level
The peripheral level is where most decisions
are made and it is made up of the controllers
(TemaServers) responsible for the Access
Control, Time & Attendance and Intrusion
Detection applications.
TemaServers are usually connected to the
Local Area Network via a dedicated Ethernet
port and use peer-to-peer communication
to exchange data and commands with one
another. The TemaServers can therefore
take all decisions locally, once configured,
removing dependence on the Supervisor
Level and improving system autonomy.
The TemaServer is battery backed and the
Temaline power supply modules can power
any associated devices. These modules
provide up to 4 hours of operation after
failure of the mains power supply. In the
battery backup status, the system reduces
the power consumption (e.g. backlight) but
does not suspend functionality for gate
control, communications, or other critical
management actions.
TemaServers are used to manage single
devices such as individual card readers,
displays or keypads as well as integrated
units that are built out of several single
devices (e.g. reader and display, display and
keyboard, reader and display and keyboard).
The TemaServer is able to logically assemble
simple devices to form a virtual terminal
responsible for managing a door.
Each TemaServer supports the management
of up to 12 doors, using either a single reader
for entry or a reader for entry AND a second
reader for exit. TemaServers support up
to 24 readers per controller, depending on
system configuration.
SECTION 5: page ��
Temaline Specification Data
Section 5.�: Access Control Solutions
Field level
This is the level where the system interacts
with the external world (company employees,
visitors, gates, etc.). It comprises readers,
displays, keypads, locking devices, digital
sensors, and other devices.
LON
Temaline uses the Echelon communication
bus as the field bus for TemaKeys, Tema
Power and I/O devices. Each LONWORKS®
bus can support up to 64 nodes or devices
(readers, I/O modules, etc.). As with any
LONWORKS® communication bus, in a
“daisy-chain” configuration, the total length
of the LON bus cannot exceed 2700 metres.
In a “free-topology configuration, the length of
the total LON bus cannot exceed 500 metres.
PEER-TO-PEER COMMUNICATION
In order to maintain high availability and
flexibility of the system, the TemaServers
communicate with one another on a peer-
to-peer basis.
Each TemaServer is continually updated
with system status regarding employee
presence, number of people present in each
zone, and details for anti-passback control
amongst others.
In order to avoid unnecessary information
exchange, TemaServers can be
logically grouped and the peer-to-peer
communication limited to the group. This
creates consistent high-performance
response. Communication over Ethernet is
managed via the TCP/IP protocol stack.
SHARED LOAD
The purpose of the Shared Load
architecture configuration is to enhance
system availability. The system has the
capability for it to protect itself in the event of
a TemaServer failure, as shown below.
This added level of hardware redundancy
is achieved using redundant pairs of
TemaServers. During normal system
operation, each TemaServer manages its
devices but, should one of the TemaServers
fail, the remaining TemaServer takes over
the management of the orphaned devices
without any degradation or loss of system
functionality.
LAN
EnterpriseBuildings
Integrator™(EBI)
ETHERNET
EnterpriseBuildings
Integrator™(EBI)
TemaServers
Peer-to-Peer
TemaKeys
LONWORKS
ETHERNET
EnterpriseBuildings
Integrator™(EBI)
TemaServers
TemaKeys
LONWORKS
Peer-to-Peer Communication
Shared Load
SECTION 5: page ��
Temaline Specification Data
Section 5.�: Access Control Solutions
MULTI-SITE
The multi-site functionality is a logical
concept that can be used with only one
server or over a Distributed System
Architecture (i.e. multi-servers) to manage
the TemaServers and peripheral devices
installed over a Wide-area Network (Wan).
Multi-site allows the management of up to
255 different sites per system. Each site
has its specific terminals, behaviour models,
calendar and zones. The employees,
visitors, vehicles, available cards can be
enabled to have multi-site capabilities. Using
this function information can be distributed
in the most suitable manner relating to
employees, visitors, vehicles and available
cards to the appropriate sites.
The multi-site functionality is often used in a
campus or business park type facility.
HARDWARE COMPONENTS
TemaSeRveR
The TemaServer is the heart
of the Temaline architecture.
Each TemaServer has its
own database and is able to communicate
with other TemaServers via peer-to-
peer communications. It represents the
distributed intelligence of the system
providing an operating environment that
seamlessly supports inter-operability of
Access Control, Time & Attendance and
Intruder Detection.
TemaServers connect to the EBI Temaline
Supervisory System via Ethernet. The
connection between the TemaServer and
the field devices is via Echelon bus protocol.
TemaPOWeR
The TemaPower is an active power supply device that does not only supply power, but is
also able to exchange messages with the TemaServer controllers thus providing continuous
information on the status of the main power supply and of the batteries.
In emergency situations, the devices can be configured in a redundant mode. Each device
then has the ability to manage additional TemaKeys normally managed by another Tema
Power, which is temporarily in failure.
muSTeR STaTiOnS
The Muster Station provides
the ability to electronically
manage a muster point in the event of an
emergency. Any TemaServer or TemaKey
equipped with a graphic display can be
configured as a Muster Station. Cardholders
are linked to a Muster station via the
behaviour models as for the other types of
readers in the system.
Each Muster Station supervises specific
zones of the plant displays a list of
cardholders still present in these zones
(including detail on their last recorded zone).
Proper site mustering is a critical requirement
for any facility that requires a structured,
secure and on-line evacuation plan.
TemaKeyS
The TemaKey devices are the
interface to all cardholders
(e.g. company employees, visitors and sub-
contractors). The modularity of the devices
allows each customer to select the right
TemaKey to suit their requirements.
In its smallest form, a TemaKey is a single
reader but larger TemaKeys can also include
additional readers, displays, keypads and/or
I/O modules.
Standard reader technologies supported
include:
l Magnetic stripe
l Proximity – HID, Motorola, NexWatch,
Sokymat, and others
l LCD devices – 16 characters x 2 rows
and graphic display with 16 lines x 40
columns
l Wiegand interface devices
l Digital I/O devices
l Specialist smart card technologies
including: Mifare, Legic, ST Micro and
others
TemaPower A TemaPower B
SECTION 5: page ��
Temaline Specification Data
Section 5.�: Access Control Solutions
SYSTEM FEATURES AND
FUNCTIONS
General System Configuration
System configuration engineering can be
accomplished completely from the EBI
supervisory level – on-line – using an EBI
station, without affecting the operation of
the system.
Updating is automatically initiated and is
carried out involving only the modified
details to the TemaServer. Only the essential
updated information is sent thus avoiding
unnecessary operations and network
traffic and also minimising the download
time for database changes. TemaServers
are also able to receive update versions of
the firmware and other basic tables using
standard tools like Telnet and TFTP.
Using the same tools is also possible to
download all localisation data (strings,
date formats, currency) or to download the
firmware to the TemaKeys – in this case the
download is done via the TemaServer. The
TemaServer acts only as a gateway between
the supervisory level network (TCP/IP) and
the field level network (LonWorks).
Data Collection
The supervisory level collects data as clock-
in and clock-out transactions, events such
as I/O and other “objects” status changes
coming from the peripheral level and device
failure messages. All this information is
characterised by a priority that determines
when they are sent: events are sent first
followed by transactions, based upon
priority.
“Reasoned” Transactions
Reasoned transactions allow cardholders to
associate a specific reason with a cad
transaction. This is normally used in Time
& Attendance to associated extraordinary
transactions with reasons such as leaving
for a doctor’s appointment.
In the case of Time and Attendance, the
normal behaviour of the TemaKey when a
‘reason’ is entered is:
�. The reason is chosen by the cardholder,
using a function key or selecting a
choice in a menu of reasons associated
to a function key
�. The card is presented to complete the
transaction.
Information Point
The information point functionality is available
only on a TemaKey with a reader and a
graphic display. There are different ways to
present information to the cardholder:
l Bulletin Board – the bulletin board is a
message displayed by the LCD when it
is in an idle condition (there is no other
activity in progress). Configuration is
done at the supervisory station.
A text message can also be set that
could be a “Welcome” message,
Company name or any other message
as defined. These messages are
supported by user-friendly configuration
software in order to allow easy tailoring
of the functionality.
l Inquiry – The cardholder request
information in the following way:
�. The type of information is chosen by
the cardholder using a function key
or selecting a choice in a menu of
information associated to a function key
�. Presenting a card. The inquiries are
requests of information that can stay
on the TemaServer or EBI. Inquiries are
always personal information.
Transactions Inquiry
The Transactions Inquiry functionality gives
cardholders the opportunity to view and
check their transactions.
The transactions are shown complete with
the relevant information such as the date
and time, the direction and the reason
associated to the transaction.
This functionality is managed by the EBI
Temaline Interface and the Temaline
peripherals and does not require any
maintenance activity, human intervention or
interface to other applications.
SECTION 5: page ��
Temaline Specification Data
Section 5.�: Access Control Solutions
General Inquiries
Configurable information available to the
cardholder that is contained within the
application such as time and vacation
balances.
Event Analysis
The event analysis functionality allows
the operators to display and analyse the
historical data stored in the system. The
operator can define:
l What data to display
l Which filters to apply to the data in order
to show only events that satisfy certain
defined criteria
l What information applies according to
the content of the fields
Spontaneous Messages
Spontaneous messages are alphanumeric
and displayed automatically on the terminal
following a clock-in or clock-out operation.
The operator can also define spontaneous
messages;
l Associated to a specific employee
– addressed exclusively to the person in
question
l Associated to a specific display i.e.
to the TemaKeys that use the primary
object in question. All authorised users
who transit at the TemaKey can then
view these messages
Spontaneous messages can be configured
for all displays, with the following limitations:
l Alphanumeric display: a single line of 16
characters
l Graphic display: 4 lines of 32 characters
The Spontaneous Message functionality
gives the opportunity to show a message
to the cardholder using the terminal,
simultaneously with the transaction
information. The message can be specific
for the terminal, for the cardholder, or for
a group of cardholders. Examples include
time limits for an individual to complete a
specific personnel task such as special
training or a group of individuals who might
be required for medical exams or a meeting
room is changed.
Dial Up Communications
The Temaline system architecture supports
point-to-point communication between the
TemaServer and the supervision centre
via Dial-up. This communication can be
used as an alternative to the LAN Ethernet
connection (as primary connection), or can
be used as a back-up connection (primary
connection in LAN Ethernet, secondary – or
back-up connection – in point-to-point).
The point-to-point connection can be
established in dial-up (modems) or using a
direct line connection (null modem, RS232
connection). The point-to-point connection
can be established both from the Tema
Server and from the Supervision Centre in
the following ways:
l Manual call from Supervisor centre
l Scheduled connection (both from centre
and peripheral level)
l Automatic (started by a Supervisor
centre commands or by a Peripheral
event/alarm)
The supervisor centre has the capability
to manage a group of modems; the
TemaServer can automatically select the
first non-busy line on up to 4 supervisor
centre telephone numbers.
Transits are not sent in an on-line manner, but
only on specific scheduled time periods. If
there is no connection between TemaServer
and supervision centre, the transits are
stored into the ‘transit buffer’ and sent to
EBI centre once the connection is establish.
If the ‘transit buffer’ level exceeds the 80%,
the TemaServer establishes automatically a
connection to decrease the occupancy of
the buffer.
From the point of view of events it is possible
to specify time periods (hours for day and
days of the week) in which the events are
sent using the point-to-point connection.
TRANSIT CONTROLS
Gate control
In its simplest form, Gate Control is the same
as a standard functionality of electronic door
access control. The main job of the Access
Control TemaServers is to control one or
more gates (doors, revolving doors, turnstiles,
etc.) in a single or bi-directional way.
The TemaServer monitors the gate status
and controls the door strike – both are
managed by an I/O device.
The TemaServer controls the gate both
when there is a request for transit and when
the door is closed (idle condition). In this
case the TemaServer treats the two readers
as a single door, conserving door count per
TemaServer.
l When there is a request for transit
and the cardholder is authorised, the
TemaServer opens the gate, checking
for the right transit sequence. A transit
sequence is a collection of steps related
to the gate characteristics (turnstile,
revolving doors, etc).
Gate Control
SECTION 5: page �5
Temaline Specification Data
Section 5.�: Access Control Solutions
The following are basic commands related
to the gate management;
l Open the gate for a single transit
checking for the right transit sequence
(for entrance)
l Open the gate for a single transit
checking for the right transit sequence
(for exit)
l Open the gate – the gate remains open
until a “normal condition” or a Close the
gate command is issued
l Close the gate (lock) – the gate remains
closed until a “normal condition” or an
“open the gate” command is issued,
l Normal condition – return to normal
modality
l When a “return to normal” command
is issued, if alarms are still present, the
alarm message is resent
Anti-passback
Anti-passback is used to prevent a card
being passed back to a following individual
to gain entry.
Cross-controller anti-passback is achieved
in the system through using the peer-to-
peer communication capabilities of the
TemaServers. In addition, the standard and
globally anti-passback have special “time
out” functionality that restricts re-entry by
cardholder within specified times. In other
words, even when a valid cardholder makes
a valid exit, the “anti-passback time out”
disallows re-entry before a specified time
(e.g. 10 minutes).
It is possible within the Tema system to have,
not only, global anti-passback, but also anti-
passback for a given number of zones.
To enable the anti-passback control, a
TemaKey must be configured with two
zones associated: the starting zone that is
the zone that the cardholder is leaving and
the destination zone that is the zone where
the cardholder will enter. The anti-passback
controls establish the zone in which the
card is currently located, and checks that
each subsequent card scan operation is
consistent with this information.
Escort Control
The escort transit control ensures that a
transit is granted only when two transactions
in sequence are performed with two different
cards.
This functionality can also be used to
manage vehicles associated with individual
people, or their access to specific area
based on the required “double permission”
as well as for visitor escort.
The feature is based on:
l Enabling a TemaKey to manage dual
transits
l Enabling an employee card, a vehicle
card, or a visit card to enable a coupled
transit
“One Shot” transits
In facilities visited often by supply vehicles,
there is often a requirement to enable the
vehicle for a single transit or for a single
entry and a single exit.
Number of people present in an
area (minimum and maximum)
This functionality is an important safety
feature for the Tema system. The number
of individuals present in an area can be
managed and controlled. This functionality
allows that in a defined area there cannot
be present less then a specified minimum
number of people or more then a maximum
number selected.
The Anti-passback control can also
be activated if needed in applying this
functionality. It is also possible to define
whether the gate has to be opened even if
the check fails. In this case only a warning
event is sent to the supervisory level.
Path control
Path control allows the system to grant
or deny transit at a terminal on the basis
of rules that verify the historical use of the
card requesting the transit, whether in terms
of the TemaKey utilised for the preceding
transits or in terms of the time elapsed since
those transits.
In particular, with Path Control, the operator
may set the rules that must be respected for
access through the terminal. The following
describes the three possible scenarios that
can be utilised for this type of control:
l Correlated transit among TemaKeys
l Mandatory Path
l Timing Barrier
Correlated transit among TemaKeys
In order for a transit to be granted at the
terminal, it is necessary for the user first to
have transited through one of a particular
group of terminals. In this example, path
control is enabled in such a manner that a
user will not be able to access the canteen
before having transited the required prior
TemaKeys.
SECTION 5: page ��
Temaline Specification Data
Section 5.�: Access Control Solutions
Therefore, in the example below:
l The TemaKey # 4 is associated to the
group of TemaKeys that manage an
area, for example the Canteen (Group 4)
l TemaKeys # 1 and 2 are associated to
the Group 1
l The control rule that is to be associated
to the terminal # 4 must verify the
preceding transit through the terminals
associated to the Group 1
Timing Barrier
In this instance, the terminal verifies both
the terminal group through which the user
has transited as well as the time elapsed
between transits before making the decision
to allow access.
For example, a timing barrier can be
established between a TemaKey associated
with Group 8 and a TemaKey associated with
another Group – say 7. The rule associated
with Group 8 will verify whether the user has
transited at any of the terminals associated
with Group 7 within a configurable time (less
then 24 hours or 1440 minutes).
Note: This type of control is a multi-gate
control. It relies on information from several
gate control terminals and, if communication
with one of the terminals involved is
interrupted, the control can no longer
be guaranteed. In this case, the system
automatically degrades the functionality
and disables the control until the conditions
necessary for reliable execution are
restored.
TIME AND ATTENDANCE
TRANSITS
The EBI Temaline Interface provides the
ability to define a specific use for each
TemaKey based on the specific transaction
for which the terminal/reader will be used.
These include:
l Access Control
l Time & Attendance
l Canteen
l SAP®
The Time and Attendance (T&A)
transaction is generally used to support
T&A requirements of HR departments and
payroll. EBI Temaline provides the required
transactions via ASCII file, Excel file or via a
database table.
EBI Temaline allows the user to manage
T&A transactions, not only covering the
company’s employees, but also for external
personnel such as consultants, contractors
or employees of sister companies.
Canteen Transits
EBI Temaline provides the ability to check
the number of canteen transits allowed
and executed for each cardholder per day.
TemaKeys are configured specifically for this
purpose and the information is collected by
EBI Temaline and then normally exported
to an external application for canteen
management.
Reasoned Transactions
A reasoned transaction is a transaction that
includes an associated code identifying
a specific reason in addition to the normal
information such as the card number, the
date and time of the transit, the transit
direction and the terminal identification.
Reasoned transactions are extensively
used for T&A transactions in order to allow
cardholders to identify an exceptional or
unusual transit. A reasoned transaction can
also be used to send feedback to activate/
deactivate the lights of an office or enable/
disable the intrusion detection of an area.
Length of Stay Controls
EBI Temaline has the ability to verify the
amount of time that a user remains in a
security-sensitive zone. This can be done
based on two thresholds:
l High pre-alarm threshold: indicates
that the user has remained in the zone
beyond the pre-alarm limit
l High alarm threshold: indicates that
the user has remained in the zone
beyond the time limit set for the alarm.
1
2
3
4
Mandatory Path
In the following example, a transit at
TemaKey # 8 associated with Group 8 will
only be authorised following a transit at
TemaKey # 4, associated with Group 4,
and a transit at the latter, in turn, will be
granted only after a transit at TemaKey # 1
associated with Group 1.1
3
84
SECTION 5: page ��
Temaline Specification Data
Section 5.�: Access Control Solutions
Behaviour models
This function allows the user to assign
schedules to cardholders (employees,
external personnel, visitors, companies
and vehicles) that reflect their access
requirements. Behaviour Models determine
user access rights to protected areas
of a facility, and consist of a time-based
component (time periods and day types) and
related TemaKeys (or readers) for accessing
doors or gates. Users can configure up to
512 behaviour models.
Each behaviour model can consist of up to
9 blocks (or groups) of terminals and time
periods linked to specific day types, such
as the days of the week (from Monday to
Sunday), holidays, and special days.
LOCALISATION
EBI Temaline provides a simple, user-friendly
procedure for localisation and requires no
specific tool. A database table is provided
containing all necessary character strings
in English and localisation simply requires
that the translated text be entered into the
“Customised” column as shown below.
SECTION 5: page ��
Temaline Specification Data
Section 5.�: Access Control Solutions
APPENDIX ITemaLine FieLD DeviCeS
Reader technologies
The Temaline family supports the following
standard reader technologies:
l Magnetic Stripe
l HID Proximity
l Sokemat Proximity
l ASP Motorola (only on TS_TA1x terminal)
l NexWatch (only on TS_TA1x terminal)
l Smart card ISO7816-4, only on RTU
device
In addition the system manages the following
special devices:
l Mifare (ISO14443A compliant) contact-
less reader
l Wiegand/BR450 adaptor to allow
integration of the BR450 (PCSC
magnetic stripe reader) to the Temaline
Wiegand device (TK_S014)
l Double reader technology terminal
for installations where 2 different card
reader technologies are required for
access to the same door (for example:
when migrating from one card type to
another)
l Legic Contactless Smart card
Integrated reader
The Integrated reader (mini-combo) provides
a reader (either magnetic stripe or proximity
card reader), keypad and liquid crystal
display (2 rows and 16 character columns)
in a single unit.
Keypad
The keypad is used to:
l Enter a PIN code
l Enter information for Time & Attendance
such as reasons
l Request information (inquiries)
Liquid Crystal Display (LCD)
All LCD’s are backlit and easily readable
from a range of 80cm to 100cm. There are
two LCD models:
l Alphanumeric, with 2 rows of 16
characters
l The Graphic Display module provides
a Human/Machine Interface with a
16-line/40- column display (240x128
pixels). This can be used to welcome
visitors, show an employee’s name at
clock in and out and display reports of
transactions (with associated reasons if
applicable). The Inquiry Mode accessed
by pressing function keys, allowing the
user to qualify a transit and/or to request
personal information to be displayed.
Digital I/O management devices
The TK C21 module provides 4 Supervised
Inputs and 4 Open Collector Outputs. The
same digital I/O management devices are
used for both access control and intrusion
detection purposes.
l All devices are able to monitor the
status of sensors via optically-coupled
supervised digital inputs
l All devices are able to command up
to 4 open collector outputs (100 mA
minimum at 50V). The module housing
is tamper protected for unauthorised
opening and removal.
Free I/O management
It is possible to share the I/O of an I/O
Module between different modular readers
(TemaKeys) or to use the I/O of an I/O
Module for both gate management and
intrusion detection purposes.
Wiegand Interface
The Wiegand interface module provides 2
Wiegand inputs, 2 monitored digital inputs
and 2 outputs to manage a single door. Up to
2 readers can be connected to the Wiegand
module provided they are controlling the
same door, one for entry purposes and the
other for exit.
The Wiegand interface can be customised to
match the encoding format of the proximity
card used.
Please Note:
l The 2 monitored I/O provided can only
be used to manage the inputs from
the related door. They cannot be re-
assigned to monitor detectors unrelated
to the transit sequence of the door.
l The 2 Wiegand lines can only be used
to manage two readers on same door
– 1 for entry and the other for exit. It is
not possible to manage 2 readers from
different doors using 1 Wiegand module.
SECTION 5: page ��
Temaline Specification Data
Section 5.�: Access Control Solutions
SYSTEM CAPACITY
The following tables highlight the EBI Temaline system limits for the System, the Site and for each TemaServer. Note that the maximum
number of sites managed by the EBI Temaline Interface is 256 per EBI Server.
Object System Limits Site Limits TemaServer Limits
TemaServers 512 512 N/A
TemaKeys Depending on the number of readers licensed in EBI Base Software.
Depending on the number of readers licensed in EBI Base Software.
Up to 12 doors
RTUs 512 * 32 512 * 32 32
I/O 512 * 64 512 * 64 64
Operators 1000 depending on EBI 1000 depending on EBI N/A
Operators Visibility Rights No limit No limit N/A
Operators Profiles No limit No limit N/A
Stations Depending on the number of Client licensed in EBI Base Software.
Depending on the number of Client licensed in EBI Base Software.
N/A
Encoding card formats 32 32 32
Cardholders No limit No limits See table below for TemaServers limits based on the type of memory and configurable options.
Zones 128 * sites n° 128 128
Time Periods 32 * sites n° 32 32
Behaviour Models 512 * sites n° 512 512
Feedback 150 * sites n° 150 150
Scheduled Commands 64 64 64
Reasons 245 245 245
Enquiries 30 30 30
Menu 23, each one with max 32 entries 23, each one with max 32 entries 23, each one with max 32 entries
Groups of TemaServer (for peer-to-peer communication)
255 control zone groups
�55 control zone groups N/A
TemaServer per Control Zone group
No limit No limit No limit
Primary Object 8 8 8
SECTION 5: page �0
Temaline Specification Data
Section 5.�: Access Control Solutions
LONWORKS® data cable characteristics
Type of cable Length (m) in relation to the cable capacity
AWG mm2 Ohm/Km 50nF/Km �00nF/Km �00nF/Km 500nF/Km �uF/Km
12 3.3 5.7 2676 1892 1338 846 598
14 2 8.8 2153 1523 1077 681 482
16 1.3 14 1707 1207 854 540 382
18 0.9 21 1394 986 697 441 312
20 0.6 34 1096 775 548 346 245
22 0.35 52 886 626 443 280 198
24 0.2 85 693 490 346 219 155
TemaServer Memory formatting
The following table shows the standard memory configuration of the TemaServer in the event that the controller is equipped with either the
standard memory card and with the extended memory card. This default configuration can be changed for individual TemaServers based on
individual site requirements.
Standard Memory Card Cards Transaction buffer Event buffer
Access Control 10.000 2.500 400
Enhance AC / Basic T&A (Enhanced Personal data table) 6.000 2.500 400
Interactive T&A 2.500 10.000 135
SAP 2.500 7.000 135
Extended Memory Card Cards Transaction buffer Event buffer
Access Control 60.000 40.000 5.000
Enhance AC / Basic T&A (Enhanced Personal data table) 50.000 40.000 5.000
Interactive T&A 15.000 65.000 1.000
SAP 32.000 65.000 1.000
SECTION 5: page ��
Control unit
Section 5.�: Access Control – Control Units
Control Unit
Featuresl Supports Up To 12 doors
l Supports “Open Protocol
Readers”
l Direct LAN/WAN connection
l Supports “Messaging”
l Standard Memory supports
10,000 card holders (60,000
with enhanced memory)
l Supports SAP HR s/w
connectivity
l Optional:
l “Redundant Configuration”
l “On-Line Muster Station”
l “ Time & Attendance”
Technical Specifications
Bi-processor CPU68EN302, including a Motorola 68000 (32 bit architecture) and an Ethernet communication processor.
1 MByte FLASH EPROM to Download the application firmware.
1 MByte FLASH EPROM on a removable cartridge for the download of the permanent database (tables of the access right of the users codes for the workdays, pre-holiday and holiday days) and for the ‘Transit and Events’ Buffer. Optional memory board with 8 Mbytes FLASH EPROM available.
1 MByte RAM for the current activity.
Management of up to 8 doors with TemaKeys on both directions.
Management of up to 64 I/O.
Up to 10.000 cards and 2.500 transactions stored on a removable cartridge with Flash EPROM memory in case of connection failure with the EBI_Tema host (resulting in no losses in case of a power failure). Up to 60.000 cards and 40.000 transactions with the extended memory board. See table below for details.
Management of the peer-to-peer connection with the other TemaServer and as a consequence high decision-making capability and full operative autonomy.
Autonomous clock/calendar Chip with automatic management of regular/daylight saving time with an autonomy of 1000 hours in case of power failure.
Lead battery backup, with full functionality for 4 hours in case of network failure, and signalling of the battery-charge status.
Low voltage power-supply (12 V dc/ac) for maintenance safety.
Tamper protection of the unit to prevent opening.
Watchdog protection for recovery in case of malfunctions.
Tele-diagnostic in Ethernet connection.
Electrical Specifications
Supply Voltage 12V dc/ac -15% to +20%
Energy Consumption 3.6W (4.2W max. during recharging of a fully used battery)
Interface Ethernet (10BaseT, 10Base2, AUI) for TCP/IP-UDP connection with EBI_Tema, and peer-to-peer between the TS AC01units
Physical Specifications
Protection Degree IP55
Dimensions 221mm x 304mm x 47mm (W x H x D)
Weight 3.0kg, battery included
Environmental Specifications
Working Temperature 0ºC to +50ºC
Relative Humidity Up to 95% without condensation
Electromagnetic Compatibility 89/336/CEE; 92/31/CEE; 93/68/CEE
SECTION 5: page ��
Control unit
Section 5.�: Access Control – Control Units
Standard Memory Card
Basic Configuration Cards Transactions buffer Event buffer
Access Control 10.000 2.500 400
Enhance AC / Basic T&A (Enhanced Personal data table)
6.000 2.500 400
Interactive T&A 2.500 10.000 135
SAP 2500 7.000 135
Extended Memory Card
Basic Configuration Cards Transactions buffer Event buffer
Access Control 60.000 40.000 5.000
Enhance AC / Basic T&A (Enhanced Personal data table)
50.000 40.000 5.000
Interactive T&A 15.000 65.000 1.000
SAP 32.000 65.000 1.000
ORDER CODES
Control Unit TS AC01
Memory Card Options
SECTION 5: page ��
Compact magnetic Card Reader
Section 5.�.�: Access Control – Magnetic Readers
Compact Magnetic Card Reader
Featuresl Wall or Turnstile Mounting
l Supports LCD Messaging
l PIN Support
l Internal I/O for door control
l Echelon “LON” Device
l Optional:
l Time & Attendance
ORDER CODES
Compact Magnetic Card Reader TK C01
Technical Specifications
Integrated compact reading unit complete of display, keyboard, 2 digital inputs and 2 digital outputs.
Bi-directional reader for Magnetic cards.
Alphanumeric Liquid Crystal Display (LCD), back lit, with two lines of 16 characters each, for the visualisation of time data, guide messages for the user, and service messages.
Numeric-function Keyboard with 16 keys, to enter the pin code of the user or the reason for transit.
1 double-coloured LED signal: green LED for the correct reading of each direction and red/yellow for invalid transactions and or Messages.
Variable Tones for valid/invalid transactions.
Electrical Specifications
Supply Voltage 12V dc ±15%
Energy Consumption 1.4W nominal (1.7W max.)
LonWorks cabling Interface Unshielded twisted pair cable in free topology. (Transceiver FTT10A, 78Kbps)
Digital Input 2 opto-coupled Digital Inputs
Digital Output 2 Relay Outputs (1A @ 30V)
Physical Specifications
Protection Degree IP31
Dimensions 72mm x 60mm x 75mm (W x H x D)
Weight 0.5kg
Environmental Specifications
Working Temperature 0ºC to +50ºC
Relative Humidity Up to 95% without condensation
Electromagnetic Compatibility 89/336/CEE; 92/31/CEE; 93/68/CEE
SECTION 5: page ��
magnetic Reader
Section 5.�.�: Access Control – Magnetic Readers
Featuresl Wall Mounting
l Echelon “LON” Device
l Optional:
l Time & Attendance
ORDER CODES
Magnetic Reader TK S01
Magnetic Reader
Technical Specifications
Bi-directional reader with manual swiping, for magnetic card (track 2, ISO/ABA 7811 standard).
3 LED signals: 2 green LED for the correct reading of each direction and a dual-colour LED: Red for invalid transaction, and Yellow for Echelon Service.
Variable Tones for valid/invalid transactions.
Electrical Specifications
Supply Voltage 12V dc ±15%
Energy Consumption 0.4W
LonWorks cabling Interface Unshielded twisted pair cable in free topology. (Transceiver FTT10A, 78Kbps)
Physical Specifications
Protection Degree IP31
Dimensions 160mm x 72mm x 52mm (W x H x D)
Weight 0.4kg
Mounting Horizontal or Vertical
Environmental Specifications
Working Temperature 0ºC to +50ºC
Relative Humidity Up to 95% without condensation
Electromagnetic Compatibility 89/336/CEE; 92/31/CEE; 93/68/CEE
SECTION 5: page �5
modular magnetic Reader
Section 5.�.�: Access Control – Magnetic Readers
Modular Magnetic Reader
Technical Specifications
Bi-directional reader for magnetic cards (standard ISO/ABA II track).
Alphanumeric Liquid Crystal Display (LCD), back lit, with two lines of 16 characters each, for the visualisation of time data, guide messages for the user, and service messages.
2 multicoloured LED: Green for the access granted, Red for invalid transaction, Yellow for Echelon Service function.
Keyboard composed by 10 numeric keys and 6 function keys.
Variable Tones for valid/invalid transactions.
Electrical Specifications
Supply Voltage 12V dc ±15%
Energy Consumption 2.7W (200 mA)
LonWorks cabling Interface Unshielded twisted pair cable in free topology. (Transceiver FTT10A, 78Kbps)
Physical Specifications
Protection Degree IP31 for the magnetic reader, IP55 for all the other components
Dimensions 160mm x 216mm x 52mm (W x H x D)
Weight 1.1kg
Mounting Horizontal only
Environmental Specifications
Working Temperature 0ºC to +50ºC
Relative Humidity Up to 95% without condensation
Certifications and Compliance
Electromagnetic Compatibility 89/336/CEE; 92/31/CEE; 93/68/CEE
ORDER CODES
Modular Magnetic Reader TK T01
Featuresl Wall Mounting
l Supports LCD Messaging
l Echelon “LON” Device
l Optional:
l Time & Attendance
SECTION 5: page ��
modular magnetic Reader
Section 5.�.�: Access Control – Magnetic Readers
ORDER CODES
Modular Magnetic Reader TK D01
Featuresl Wall Mounting
l Supports LCD Messaging
l Echelon “LON” Device
l Optional:
l Time & Attendance
Technical Specifications
Bi-directional reader for magnetic cards (standard ISO/ABA II track).
Alphanumeric Liquid Crystal Display (LCD), back lit, with two lines of 16 characters each, for the visualisation of time data, guide messages for the user, and service messages.
3 LED signals: 2 green LED for the correct reading of each direction and a dual-colour LED: Red for invalid transaction, and Yellow for Echelon Service function.
Variable Tones for valid/invalid transactions.
Electrical Specifications
Supply Voltage 12V dc ±15%
Energy Consumption 2.3W
LonWorks cabling Interface Unshielded twisted pair cable in free topology. (Transceiver FTT10A, 78Kbps)
Physical Specifications
Protection Degree IP31 for the magnetic reader, IP55 for all the other components
Dimensions 160mm x 144mm x 52mm (W x H x D)
Weight 0.85kg
Mounting Horizontal only
Environmental Specifications
Working Temperature 0ºC to +50ºC
Relative Humidity Up to 95% without condensation
Certifications and Compliance
Electromagnetic Compatibility 89/336/CEE; 92/31/CEE; 93/68/CEE
Modular Magnetic Reader
SECTION 5: page ��
modular magnetic Reader
Section 5.�.�: Access Control – Magnetic Readers
with Graphic Display
Modular Magnetic Reader with Graphic Display
ORDER CODES
Modular Magnetic Reader with Graphic Display TK D21
Featuresl Wall Mounting
l Supports LCD Messaging
l Echelon “LON” Device
l Optional:
l Time & Attendance
l “Mustering”
Technical Specifications
Bi-directional reader for magnetic cards (standard ISO/ABA II track).
Graphic Liquid Crystal Display (LCD) with back lit 240 x 128 pixels format, 16 lines x 40 columns, for the visualisation of time data, guide messages for the user, service messages, spontaneous messages, transaction enquiry, generic enquiry, automatic info.
14 function keys, 4 reserved for service management, and 10 configurable to manage enquiry, reasons and menu.
3 LED signals: 2 green LED for the correct reading of each direction and a dual-colour LED: Red for invalid transaction, and Yellow for Echelon Service function.
Variable Tones for valid/invalid transactions.
Electrical Specifications
Supply Voltage 12V dc ±15%
Energy Consumption 5.6W
LonWorks cabling Interface Unshielded twisted pair cable in free topology. (Transceiver FTT10A, 78Kbps)
Physical Specifications
Protection Degree IP31 for the magnetic reader, IP55 for all the other components
Dimensions 160mm x 216mm x 52mm (W x H x D)
Weight 1.2kg
Mounting Horizontal only
Environmental Specifications
Working Temperature 0ºC to +50ºC
Relative Humidity Up to 95% without condensation
Certifications and Compliance
Electromagnetic Compatibility 89/336/CEE; 92/31/CEE; 93/68/CEE
SECTION 5: page ��
mullion Style Readers
Section 5.�.�: Access Control – Proximity Readers
Featuresl Door mullion or turnstile
mounting
l Multicolour LCD messaging
l Internal l/O for door control
l Built-in audible buzzer
l Echelon “LON” device
l Optional:
l Smart card
l Proximity card
ORDER CODES
Mullion Style Reader for Smart Card TK_L12
Mullion Style Reader HID Technology TK_L19
Mullion Style Reader
Technical Specifications
Technical TK_L�� For Smartcard TK_L�� HID Technology
Compact, mono-directional reader for ISO14443A MIFARE® and ISO14443B
smart card technology (13,56MHz)
Compact, mono-directional reader for HID technology proximity cards (125kHz)
Integrated cable fly-lead for I/O wiring, LON communications and power supply connections
1 multicolour LED: Green for correct card read, Red for invalid transaction, Yellow for Echelon service function
Built-in audible buzzer with variable tones for valid/invalid transactions
Reading distance: up to 4cm with MIFARE® STD 1K card
Reading distance: up to 4cm with HID ISOprox II cards
Electrical Specifications
Supply Voltage 12V dc +/- 10%
Energy Consumption 2W
LonWorks cabling Interface
Unshielded twisted pair cable in free topology Transceiver FTT10A, 78Kbps
Digital Inputs 2 supervised inputs: normal, alarm, cut, short
Outputs 2 open collector outputs:Lock Output: Open collector 100mA max
for driving an external relayOther output (LED): Open collector 100mA for driving an external relay
2 relay outputs: See the installation manual for the details
Lock output: Normally closed/ normally open, Current 6A holding
current, peak max 10A inductive load, Voltage 30V ac/dc
Other output (LED): Normally closed/normally open, Current 1A max, Voltage
30V ac/dc
Physical Specifications
Protection Degree IP55
Dimensions H 156 x W 40 x D 27mm
Weight 300 gr
Environmental Specifications
Working Temperature -20ºC to +60ºC
Relative Humidity Up to 95% without condensation
Certification Directive EMC 89/336/EEC, 92/31/EEC Low Voltage Directive 72/23/EEC, 93/68/EEC; EN60950/EN55022-B/ETSI EN300-
339/EN55024
Directive EMC 89/336/EEC, 92/31/EEC Low Voltage Directive 72/23/EEC, 93/68/EEC; EN60950/EN55022-B/ETSI EN300-
339/EN55024
Smart Card & HiD compatible options
SECTION 5: page ��
Proximity Reader
Section 5.�.�: Access Control – Proximity Readers
Proximity Reader
ORDER CODES
Proximity Reader TK S07
Featuresl Wall Mounting
l Echelon “LON” Device
l HID Compatible
Technical Specifications
Bi-directional reader for HID Proximity cards (standard ISO/ABA 125Khz, up to 5cm of distance).
2 multicoloured LED: Green for the correct reading on each direction, Red for invalid transaction, Yellow for Echelon Service function.
Variable Tones for valid/invalid transactions.
Electrical Specifications
Supply Voltage 12V dc ±15%
Energy Consumption 0.8W
LonWorks cabling Interface Unshielded twisted pair cable in free topology. (Transceiver FTT10A, 78Kbps)
Physical Specifications
Protection Degree IP55
Dimensions 160mm x 72mm x 52mm (W x H x D)
Weight 0.45kg
Mounting Horizontal or Vertical
Environmental Specifications
Working Temperature -20ºC to +50ºC
Relative Humidity Up to 95% without condensation
Certifications and Compliance
Electromagnetic Compatibility 89/336/CEE; 92/31/CEE; 93/68/CEE
Safety CEI 111-3; CENELEC 50061
SECTION 5: page �0
Compact Proximity Reader
Section 5.�.�: Access Control – Proximity Readers
Compact Proximity Reader
ORDER CODES
Compact Proximity Reader TK C03
Featuresl Wall or Turnstile Mounting
l Supports LCD Messaging
l PIN Support
l Internal I/O for door control
l Echelon “LON” Device
l HID Compatible
l Optional:
l Time & Attendance
Technical Specifications
Integrated compact reading unit with display, keyboard, 2 digital inputs and 2 digital outputs.
Mono-directional reader for HID Proximity cards (standard ISO/ABA 125Khz, up to 5cm of distance).
Alphanumeric Liquid Crystal Display (LCD), back lit, with two lines of 16 characters each, for the visualisation of time data, guide messages for the user, and service messages.
Numeric-function Keyboard with 16 keys, to enter the pin code of the user or the reason for transit.
1 double-coloured LED signal: green LED for the correct reading of each direction and red/yellow for invalid transactions and or Messages.
Variable Tones for valid/invalid transactions.
Electrical Specifications
Supply Voltage 12V dc ±15%
Energy Consumption 1.8W nominal (2.1W max.)
LonWorks cabling Interface Unshielded twisted pair cable in free topology. (Transceiver FTT10A, 78Kbps)
Digital Input 2 opto-coupled Digital Inputs
Digital Output 2 Relay Outputs (1A @ 30V)
Physical Specifications
Protection Degree IP55
Dimensions 72mm x 160mm x 75mm (W x H x D)
Weight 0.5kg
Environmental Specifications
Working Temperature -20ºC to +50ºC
Relative Humidity Up to 95% without condensation
Electromagnetic Compatibility 89/336/CEE; 92/31/CEE; 93/68/CEE
Safety CEI 111-3; CENELEC 50061
SECTION 5: page ��
modular Proximity Reader
Section 5.�.�: Access Control – Proximity Readers
Modular Proximity Reader
ORDER CODES
Modular Proximity Reader TK D07
Featuresl Wall Mounting
l Supports LCD Messaging
l Echelon “LON” Device
l HID Compatible
l Optional:
l Time & Attendance
Technical Specifications
Bi-directional reader for HID Proximity cards (standard ISO/ABA 125Khz, up to 5cm of distance).
Alphanumeric Liquid Crystal Display (LCD), back lit, with two lines of 16 characters each, for the visualisation of time data, guide messages for the user, and service messages.
2 multicoloured LED: Green for the access granted, Red for invalid transaction, Yellow for Echelon Service function.
Variable Tones for valid/invalid transactions.
Electrical Specifications
Supply Voltage 12V dc ±15%
Energy Consumption 2.7W
LonWorks cabling Interface Unshielded twisted pair cable in free topology. (Transceiver FTT10A, 78Kbps)
Physical Specifications
Protection Degree IP55
Dimensions 160mm x 144mm x 52mm (W x H x D)
Weight 0.9kg
Mounting Horizontal only
Environmental Specifications
Working Temperature 0ºC to +50ºC
Relative Humidity Up to 95% without condensation
Certifications and Compliance
Electromagnetic Compatibility 89/336/CEE; 92/31/CEE; 93/68/CEE
Safety CEI 111-3; CENELEC 50061
SECTION 5: page ��
modular Proximity Reader
Modular Proximity Reader
Section 5.�.�: Access Control – Proximity Readers
ORDER CODES
Modular Proximity Reader TK T07
Featuresl Wall Mounting
l Supports LCD Messaging
l Echelon “LON” Device
l Personal Identification
Number
l HID Compatible
l Optional:
l Time & Attendance
Technical Specifications
One direction reader for HID cards.
Alphanumeric Liquid Crystal Display (LCD), back lit, with two lines of 16 characters each, for the visualisation of time data, guide messages for the user, and service messages.
2 multicoloured LED: Green for the access granted, Red for invalid transaction, Yellow for Echelon Service function.
Keyboard composed by 10 numeric keys and 6 function keys.
Variable Tones for valid/invalid transactions.
Electrical Specifications
Supply Voltage 12V dc ±15%
Energy Consumption 3.1W (230 mA)
LonWorks cabling Interface Unshielded twisted pair cable in free topology. (Transceiver FTT10A, 78Kbps)
Physical Specifications
Protection Degree IP55
Dimensions 160mm x 216mm x 52mm (W x H x D)
Weight 1.15kg
Mounting Horizontal only
Environmental Specifications
Working Temperature 0ºC to +50ºC
Relative Humidity Up to 95% without condensation
Certifications and Compliance
Electromagnetic Compatibility 89/336/CEE; 92/31/CEE; 93/68/CEE
Safety CEI 111-3; CENELEC 50061
SECTION 5: page ��
modular Proximity Reader
Section 5.�.�: Access Control – Proximity Readers
Modular Proximity Reader with Graphic Display
with Graphic Display
ORDER CODES
Modular Proximity Reader with Graphic Display TK D27
Featuresl Wall Mounting
l Supports LCD Messaging
l Echelon “LON” Device
l HID Compatible
l Optional:
l Time & Attendance
l “Mustering”
Technical Specifications
Bi-directional reader for HID Proximity cards (standard ISO/ABA 125Khz, up to 5cm of distance).
Graphic Liquid Crystal Display (LCD) with back lit 240 x 128 pixels format, 16 lines x 40 columns, for the visualisation of time data, guide messages for the user, service messages, spontaneous messages, transaction enquiry, generic enquiry, automatic info.
14 function keys, 4 reserved for service management, 10 configurable to manage enquiry, reasons and menu.
2 multicoloured LED: Green for the access granted, Red for invalid transaction, Yellow for Echelon Service function.
Variable Tones for valid/invalid transactions.
Electrical Specifications
Supply Voltage 12V dc ±15%
Energy Consumption 6W
LonWorks cabling Interface Unshielded twisted pair cable in free topology. (Transceiver FTT10A, 78Kbps)
Physical Specifications
Protection Degree IP55
Dimensions 160mm x 216mm x 52mm (W x H x D)
Weight 1.25kg
Mounting Horizontal only
Environmental Specifications
Working Temperature 0ºC to +50ºC
Relative Humidity Up to 95% without condensation
Certifications and Compliance
Electromagnetic Compatibility 89/336/CEE; 92/31/CEE; 93/68/CEE
Safety CEI 111-3; CENELEC 50061
SECTION 5: page ��
OmniProx™
Section 5.�.�: Access Control – Proximity Readers
OmniProx™ Proximity Card Readers
Honeywell’s OmniProx™ range is a complete line of ��5 kHz HID compatible proximity
readers that delivers consistent performance.
All OmniProx™ readers (except the OP90) include three bezels: black, charcoal grey and ivory
and are constructed with rugged polycarbonate materials potted for both indoor and outdoor
applications.
The OmniProx™ family of readers combines unique functionality, high-quality engineering and
design for a variety of applications in the electronic access control market.
OmniProx™ readers offer superb reliability and consistent read range. Installation is simple and fast
with a mounting template included in all models.
Increased security functions, including optical tamper and security screw, prevent unauthorised
users from removing the reader from the wall or attempting to compromise the system.
For vandal-proof applications the OP90 vandal resistant reader is enclosed in a zinc die-cast metal
housing.
Featuresl Variety of sizes to choose from
to fit any décor:
l Mullion style
l Single-gang style (US)
l Single-gang style (UK)
l ADA compliant, built-in audible
buzzer
l Host LED control and tamper
output
l Optical tamper detect
mechanism provides output
signal to host
l Hidden mounting screws
deter vandalism
l Potted for superior weather-
resistance
l Wiegand output
l Genuine HID™ compatible
l Includes vandal-resistant
security and installation tool
with every reader.
l Adhesive-backed mounting
template reduces installation
time and risk of mounting
errors
l Unique bezel design allows
entire face of reader to be
customised for a unique look
or with custom colour to
fulfil architectural and décor
requirements
l Three bezels included with
each reader: black, charcoal
grey and ivory
l Warranty: Limited lifetime
warranty
SECTION 5: page �5
OmniProx™
Section 5.�.�: Access Control – Proximity Readers
OP�0Mini-Mullion
OP�0Mullion
OP�0US Gang Box
OP�5UK Gang Box
OP�0Vandal Resistant
Description Smallest proximity reader for door mullions
Mini-size proximity reader for door mullions
Switch plate size, single-gang electrical box style
for US
Switch plate size, single-gang electrical box style
for UK
Vandal-resistant zinc die-cast single-gang
electrical box
Dimensions 80mm H x 40mm W x 12.8mm D
145mm H x 43mm W x 20mm D
110mm H x 75mm W x 15mm D
88.9mm H x 88.9mm W x 15mm D
114mm H x 80mm W x 15mm D
Max. Read Range1
1326 ProxCard IIClam Shell
7.6cm 10.2cm 5.1cm
1386 ISOProx® IIPVC Card
5.7cm 5.7cm 3.2cm
1336 DuoProx® IIPVC with Mag Stripe
5.7cm 5.7cm 3.2cm
1345 ProxKey™ IIKeyfob
3.2cm 3.2cm Not recommended
Environment Indoor/Outdoor weather-resistant
Operating Current@ 5 V dc)
35mA typ. / 50mA max. 35mA typ. / 100mA max. 50mA typ. / 100mA max.
Operating Voltage 5.0 – 16V dc (works down to 4.25V dc)
Power Supply Type Linear type recommended
Interface to Controller Max. cable distance to host: 150 m (Wiegand output)
Indicators ADA compliant with buzzer audio indicator, single tricolour (green-yellow-red)
Tamper Output Open collector, active low, max. sink current is 16mA
Humidity 0 – 95%, non-condensing
Temperature -31ºC to +63ºC
Colour Black, Charcoal Grey and Ivory (all three included) Silver
Regulatory Approvals USA and Canada: FCC Part15B, Industry Canada RSS-210, UL294; Europe: CE Mark Approval
Warranty2 Lifetime
ORDER CODES
OmniProx™ HID Compatible, Smallest Mullion Reader OP10HON
OmniProx™ HID Compatible, Smallest Mullion Reader without Logo (Generic) OP10GEN
OmniProx™ HID Compatible, Mullion Reader OP30HON
OmniProx™ HID Compatible, Mullion Reader without Logo (Generic) OP30GEN
OmniProx™ HID Compatible, Switch Plate, Single-Gang (US) Reader OP40HON
OmniProx™ HID Compatible, Switch Plate, Single-Gang (US) Reader without Logo (Generic) OP40GEN
OmniProx™ HID Compatible, Switch Plate, Single-Gang (UK) Reader OP45HON
OmniProx™ HID Compatible, Switch Plate, Single-Gang (UK) Reader without Logo (Generic) OP45GEN
OmniProx™ HID Compatible, Metal, Single-Gang (US) Reader OP90HON
1 Actual operating distance will vary depending upon installation environment and proximity to metal. 2 In accordance with Honeywell’s sales policy and warranty.
OmniProx™ is a trademark of Honeywell International Inc.HID is a registered trademark of HID Corporation.
SECTION 5: page ��
OmniClass™
Section 5.�.�: Access Control – Smart Card Readers
OmniClass™ Contactless Smart Card Readers
Honeywell’s latest series of affordable contactless smart card readers continue to be
optimised for access control applications. OmniClass™ readers, which build upon the
convenience and reliability of prox technology, add many valuable features including
enhanced ��-bit security, encryption options, ability to read almost any ISO contactless
smart card, multi-application support and more.
OmniClass readers offer superb reliability, consistent read range and ease of installation. They are
available in multiple sizes and read ranges. OmniClass readers are available in black with 18” pigtail
wiring. OmniClass also provides the enhanced capabilities of smart card technology allowing
support for biometric profiles and multiple applications on each card simultaneously. OmniClass
solutions can retro-fit any Wiegand output readers, including standard HID® or Honeywell proximity
readers.
Smart card technology is ideally suited for access control, logical (PC) access, storage of biometric
templates, parking, secure ID’s with embedded tamper-proof digital photos, ePurse and many
more applications requiring secure and reliable read/write cards.
PROX (��5 kHz)
SMART (��.5� MHz)
Suitable for Basic Access Applications: • Support for site and card codes • Price competitive
l l
More Open: • Support for global standards • Inter-operability between vendors & applications
l
More Secure: • Stronger security via long keys, encrypted communication and mutual authentication • Unique card serial number
l
More Storage Space: • Memory on-board to store data for other applications
l
Featuresl Supports multiple ISO
standards: Allows OmniClass
to read almost any ISO
standard smart card
l High-Security: Encrypted data
exchange available between
card and reader and between
reader and host reduces the
risk of compromised data and
duplicated cards
l Available in mullion and switch
plate sizes
l ADA compliant built-in audible
beeper
l Host LED control
(programmable)
l Control cards can be used
to manage security keys
and change the operating
characteristics of the reader
l Hidden mounting screws
deter vandalism
l Potted for superior weather
resistance
l Wiegand output
SECTION 5: page ��
OmniClass™
Section 5.�.�: Access Control – Smart Card Readers
OM�0 OM�0 OM�5 OM55
Dimensions 4.83 x 10.26 x 2.03cm 8.38 x 12.19 x 2.16cm 8.38 x 8.38 x 1.91cm 8.38 x 12.19 x 2.36cm
Max. Read Range1 7.6cm 11.4cm 7.6cm 10.1cm
Cable Distance to Host 152m max.
ISO Standard Support2 15693: Reads Infineon MyD, TI Tag-it, Philips I-Code14443A: Reads Philips MIFARE, DESFire, Ultralight, Infineon MyD
14443B: Reads PicoPass
Key Length 64 bit secret key; 32 bit challenge; 32 bit response
Data Encryption Available between card and reader and between reader and host
Regulatory Approvals UL/cUL, FCC, CE, Canada Radio, Australia
Operating Temperature -35ºC to +66ºC
Operating Humidity 5 to 95% relative humidity (non-condensing)
Operating Voltage Range 10 – 16V dc
Current (@12 V dc) 61mA avg, 178mA peak 78mA avg, 234mA peak 78mA avg, 234mA peak 80mA avg, 253mA peak
Tamper Output No Tamper magnet
Output Interfaces (all built-in) Wiegand
IP Rating IP55
Warranty3 Limited lifetime warranty
ORDER CODES
OmniClass Series Readers
OmniClass Mullion Mount Reader, Black Bezel, 18” Pigtail OM30BHON
OmniClass Switch Plate, Single-gang (US) Reader, Black Bezel, 18” Pigtail OM40BHON
OmniClass Switch Plate, Single-gang (UK/EU/Asian) Reader, Black Bezel, 18” Pigtail OM45BHON
OmniClass Reader with Keypad, Black Bezel, 18” Pigtail OM55BHON
OmniClass Series Credentials
OmniClass 2K PVC Card (26-bit) OKP0N26
OmniClass 2K PVC Card (34-bit) OKP0N34
OmniClass 16K PVC Card (26-bit) OKP2N26
OmniClass 16K PVC Card (34-bit) OKP2N34
OmniClass 16K PVC Card (26-bit) with Magnetic Stripe OKP2M26
OmniClass 16K PVC Card (34-bit) with Magnetic Stripe OKP2M34
OmniClass 16K PVC Card plus HID Prox (26-bit) OKH2N26
OmniClass 16K PVC Card plus HID Prox (34-bit) OKH2N34
OmniClass 16K PVC Card plus HID {rox (26-bit) with Magnetic Stripe OKH2M26
OmniClass 16K PVC Card plus HID prox (34-bit) with Magnetic Stripe OKH2M34
OmniClass 16K Sticker (26-bit) OKS2N26
OmniClass 16K Sticker (34-bit) OKS2N34
OmniClass 16K Keyfob (26-bit) OKK2N26
OmniClass 16K Keyfob (34-bit) OKK2N34
1 Actual operating distance will vary depending on installation environment and proximity to metal.
2 Certain ISO cards may only be able to read serial number. Please consult factory for exact compatibility.
3 In accordance with Honeywell’s sales policy and warranty.
Mifare™, DESFire™ and I-Code are registered trademarks of Philips Electronics N.V. MyD™ is a trademark of Infineon Technologies AG. OmniClass™ is a trademark of Honeywell International Inc.Tag-it™ is a trademark of Texas Instruments Incorporated. HID® is a registered trademark of HID Corporation.
SECTION 5: page ��
Omniassure™
Section 5.�.�: Access Control – Smart Card Readers
OmniAssure™ Contactless Smart Card Readers
Featuresl Flash-on-card to update
reader firmware to evolving
smart card standards
l Mullion and switch plate
mounting
l ADA compliant built-in audible
buzzer
l Two LEDs (red and green)
l Configuration cards can be
used to manage security keys
and change the operating
characteristics of the reader
l Hidden mounting screws
deter vandalism
l Potted for superior weather
resistance
l Wiegand output
Smart card technology is ideally suited for access control, logical (PC) access, storage
of biometric templates, secure IDs with embedded tamper-proof digital photos, parking,
ePurse and many other applications requiring secure and reliable read/write cards.
Honeywell’s OmniAssure™ readers combine compliance with convenience. The patent-pending
‘flash-on-card’ design makes OmniAssure readers the easiest to use. With flash-on-card, the
reader’s firmware can be easily updated to support changing government standards without
removing the readers from the wall. With other smart card readers, the configuration cards only
change parameter settings for the currently installed firmware.
OmniAssure readers can retrofit most standard Honeywell or Wiegand-output proximity systems.
The readers also feature built-in-hardware to support future RS485 protocols and both the reading/
writing of smart card credentials. This protects the OmniAssure solution for changing needs in the
future.
Reader versions include smart card reader only, smart card reader plus keypad, fingerprint smart
card reader, and a multi-technology smart card/prox reader. All wall-mount readers are sold as
mullion mounts with optional mounting kits available.
Compatible cards include:l HSPD-12/FIPS 201 PIV II cards (endpoint
and transition), low-medium assurance
l TWIC (Transportation Worker Identification
Credential) cards
l FRAC (First Responder Authentication
Cards)
l DoD CAC (Department of Defence
Common Access Credentials)
l Open standard ISO 14443 technologies
(Mifare® Classic, DESFire®, and SmartMX®)
l 125 kHz proximity technologies (including
EM4102, Hitag, and HID® Prox)
SECTION 5: page ��
Omniassure™
Section 5.�.�: Access Control – Smart Card Readers
OM�0, OT�5 Smart Card
OT��, OT�� Smart Card + ��5 kHz Prox
OT�0, OT�5 Smart Fingerprint
Dimensions Mullion: 14.2 x 4.62 x 2.5cmU.S. gangbox: 14.2 x 7.32 x 2.8cm
Mullion: 19.25 x 5.05 x 4.3cmU.S. gangbox: 21.8 x 7.6 x 0.8cm
Compatible Cards Mifare®, DESFire®, SmartMX®, PIV II, FRAC, DoD CAC, TWIC
Mifare®, DESFire®, SmartMX®,PIV II, FRAC DoD CAC, TWIC, EM4102, Hitag,
HID® Prox
Mifare®, DESFire®, SmartMX®, PIV II, FRAC, DoD CAC, TWIC4
Max. Read Range1
ISO 14443A Card (Mifare®)Up to 3cm Up to 1.1cm Up to 3cm
ISO 14443B Card (DESFire®, SmartMX®)
Up to 3cm Up to 1.1cm Up to 3cm
1326 ProxCard II Clam Shell N/A Up to 4cm N/A
1386 ISOProx® II PVC Card N/A Up to 2.5cm N/A
ISO Standard Support 14443A, 14443B
Data Encryption Available between card and reader and between reader and host
PIN 4-bit burst, 8-bit burst
BiometricsNumber of Fingerprint Templates & Size
N/A Up to 2 templates stored on smart card depending upon card type and fingerprint technology; 752 bytes for minutia; 350 bytes for user templates
and records4
Enrolment Time N/A < 3 seconds
Equal Error Rate (ERR) N/A 0.1%; Adjustable
False Acceptance/ Rejection Rates
N/A Adjustable
Verification Time N/A < 1 second
Regulatory Approvals2 UL/cUL, FCC, CE, Canada Radio* UL/cUL*, FCC, CE, Canada Radio* UL/cUL, FCC, CE, Canada Radio*
Operating Temperature -20ºC to +60ºC 0ºC to +60ºC
Operating Humidity 5 – 95% relative humidity, non-condensing 30-80%, non-condensing
IP Rating IP67 if connector is sealed IP42, Indoor use only
Operating Voltage Range 4.5 – 16V dc 8 – 24V dc
Power Consumption 1.5 Watts average; 2.0 Watts peak 2.5 Watts average, 5 Watts peak
Tamper Output Optional Tamper Switch Accessory
Output Interfaces (all built-in) Wiegand, Clock & Data, RS485/RS232/RS422
Warranty3 Limited Lifetime Limited Lifetime 2 years
ORDER CODES
Mullion-mount reader, silver bezel, terminal connection OT30HON
Mullion-mount reader plus 125kHz proximity, silver bezel, terminal connection OT31HON
Mullion-mount reader plus keypad, silver bezel, terminal connection OT35HON
Mullion-mount reader plus keypad plus 125kHz proximity, silver bezel, terminal connection OT36HON
U.S. gangbox mounting kit for OT30HON, OT31HON, OT35HON, OT36HON IEMOUNT
Mullion-mount fingerprint reader, silver bezel, terminal connection OT70HON
Mullion-mount fingerprint reader plus keypad, silver bezel, terminal connection OT75HON
U.S. gangbox mounting kit for OT70HON, OT75HON IEMOUNT2
Tamper switch accessory for all readers IETAMPER
Note: Contact factory for reader configuration cards to set up the reader per site requirements.
OmniAssure™ is a trademark of Honeywell International Inc.
Mifare®, DESFire®, and SmartMX® are trademarks of Philips. HID® and ISOProx® are trademarks of HID Global.
1 Actual operating distance will vary depending upon installation environment and proximity to metal. 2 * = submitted/pending. 3 In accordance with Honeywell’s sales policy and warranty. 4 Fingerprints supported on Mifare® and DESFire®.
SECTION 5: page �0
Bioaccess™
Section 5.�.�: Access Control – Fingerprint Readers
Contactless Mifare™ Fingerprint Readers
Precise BioAccess™ Mifare is a plug and play fingerprint reader that offers unparalleled
security for access control. Precise BioMatch™ technology provides reliable one-to-
one matching— personal proof that people are who they claim to be.
Precise BioAccess™ is convenient, fast, accurate, easy to implement and extremely cost effective.
By only storing the template on a contactless smart card instead of in a less secure database,
privacy is preserved. Precise BioAccess™ Mifare is designed to instantly replace existing readers
and requires no new wiring or software updates.
Precise BioAccess™ Enrolment Station is a standalone package for enrolling fingerprints and
writing biometric templates onto Mifare contactless cards for use with Precise BioAccess™ Mifare
readers. The Precise BioAccess™ Enrolment Station gives control over the contents of the cards
so the Precise Biometric data can coexist with other applications and data on the Mifare card.
Featuresl Increased security — identifies
people, not PIN codes
l Compatible with all major
access control systems
l Preserved privacy —
fingerprint template stored on
card
l Decreased administration cost
— no lost PIN codes
l Scalable—no local database,
no performance penalty
l Industry leading fingerprint
matching technology.
l Stores up to four fingerprint
templates on a Mifare
standard 4K card, injured
fingers are not a problem
l Each finger can be assigned
their own card number,
enabling control of alarm and
T&A systems
l Flexible storage of template
on card, enables use of cards
containing legacy data
l Unique personal keys,
protects against unauthorised
re-enrolment and cards from
unauthorised parties
l Support for MAD (Mifare
Application Directory), a
demand for multi-application
cards
SECTION 5: page ��
Section 5.�.�: Access Control – Fingerprint Readers
Bioaccess™
PRBIORDR — Mifare Compatible
Description The reader matches the fingerprint of the person seeking entry to the identity of the cardholder as stored on the Mifare card.
Dimensions 12.5cm x 6.8cm x 6.1cm (H x W x D)
Max. Read Range1 4.0cm
Cable Distance to Host (Wiegand) 152m max
Compatible Cards Mifare standard 1K and 4K, Mifare Pro and Mifare ProX
Number of Templates Unlimited
Template Size 534 bytes
Enrolment Time < 10 seconds
Equal Error Rate (EER) N/A
False Acceptance Rate Configurable
False Rejection Rate Configurable
Custom Features Mifare ROM card number, enables unique card number. Custom card number, enables use of old card number and compatibility with other card formats. RAW data, enables sending of any data required following a successful match
Verification Time < 1 second
Regulatory Approvals FCC, CE
Operating Temperature +10ºC to +50ºC
Operating Humidity Office Environment (typ. 45 to 65% relative humidity)
Operating Voltage Range 12 – 24V dc
Current (@12V dc) 100mA typ, 250mA peak
Communications No updates required to reader, templates stored on card
Output Interfaces Wiegand, Clock & Data
Warranty2 1 year
ORDER CODES
Mifare™ BioAccess Reader Fingerprint and Smart Card Reader PRBIORDR
Mifare™ BioAccess Enrolment Kit, 115V ac, USB Fingerprint Reader, and Software PRBIOENRU
Mifare™ BioAccess Enrolment Kit, 115V ac, Parallel Port Fingerprint Reader, and Software PRBIOENRP
1 Actual operating distance will vary depending upon installation environment and proximity to metal. 2 In accordance with Honeywell’s sales policy and warranty.All specifications are subject to change without notification. Precise BioAccess is a Registered Trademark of Precise Biometrics.
SECTION 5: page ��
HandKey™
Section 5.�.5: Access Control – Hand Geometry Readers
The HandKey reader by Recognition Systems, Inc. utilises field proven hand geometry
technology that maps and verifies the size and shape of a person’s hand in less than one
second.
The HandKey captures a three dimensional image of the hand using a 32,000 pixel image array. 90
measurements, including the lengths, widths, thickness and surface area of the fingers and hand
are taken. An advanced algorithm determines the unique aspects of the hand and then generates a
nine-byte hand template. This template is then stored and used for subsequent comparisons. Dirt,
cuts and abrasions on the hand have no impact on accuracy.
The HandKey CR is specifically designed to work in conjunction with card based access control
systems. This makes adding biometric security to critical access points fast, simple and seamless
for both new and existing systems. The HandKey CR without integrated card reader and the
HandKey CR with HID proximity can store up to 512 cardholder templates in the unit. The HandKey
CR with an integrated OmniClass/iCLASS reader stores cardholder templates on their cards,
protecting cardholder privacy and eliminating the need to store and update cardholder databases
in individual HandKey CR readers. The storage of the template on the card allows the reader to
support an unlimited number of cardholders.
The HandKey II provides the security and convenience at an affordable price, even when compared
to cardbased systems. Because a hand is the card, HandKey II allows access only to authorised
people without the hassles of a card or key. By eliminating cards, administrative costs are reduced
while greatly increasing the level of security. Users appreciate the convenience of never worrying
about keeping track of a card or key.
Featuresl When multiple HandKey units
are linked together via RS-485
or Ethernet, the unit’s built-in
template management system
can be used to distribute
hand imprints to other hand
readers in the network. This
allows users to enrol at one
reader and then use other
readers in the system without
re-enrolment
l Integrated wall-mount design
l Flexible storage of template
on OmniClass/iCLASS cards
eliminates need to maintain
databases in individual
readers
l Card readers support 26-bit
Wiegand with other data
formats available
l Integrates into existing
systems
l To ensure system integrity,
a tamper switch is built into
the reader. Tamper alarms
and other conditions such as
verification refused, lock out
and duress can be monitored
by the panel directly or
through one of the HandKey’s
two auxiliary outputs
HandKey™ Hand Geometry Readers
Section 5: Access Control
SECTION 5: page ��
ProductDescription
HandKey™
Section 5.�.5: Access Control – Hand Geometry Readers
HandKey CR HG-�
HandKey CR HG�-PROX
HandKey CR HG�ICLASS
HandKey II HG�-II
Description This reader stores templates for up to 512 users in the unit.
This reader stores templates for up to 512 users in the unit
and reads HID prox cards.
This reader stores templates on an OmniClass/iCLASS
smart card.
This is a standalone unit for up to 512 users with 2 auxiliary and a door egress input, 3
auxiliary outputs.
Dimensions 29.6cm x 22.3cm x 21.7cm (H x W x D)
Max. Read Range1 N/A 2” Card sits in holder N/A
Cable Distance to Host (Wiegand)
500’ (152m) max
Compatible Cards – HID proximity OmniClass / iCLASS –
Number of Templates 512 512 Unlimited 512
Template Size 9 bytes
Enrolment Time < 15 sec
Equal Error Rate (EER) 0.1%
False Acceptance Rate 0.1%
False Rejection Rate 0.1%
Custom Features FTE of 1 in 10,000
Verification Time less than 1 second
Regulatory Approvals FCC, CE, UL 294
Operating Temperature 0° to 45° C
Operating Humidity 20% – 80% relative humidity
Operating Voltage Range 12 to 24V dc
Current (@12V dc) 170mA 200mA 200mA 170mA
Tamper Built-in tamper switch
Communications RS-485, RS-422 or Ethernet
Output Interfaces Wiegand BR-100 relay
Warranty2 1 year
ORDER CODES
HandKey CR Hand Geometry Reader that stores 512 user templates HG-4
HandKey CR Hand Geometry Reader that stores 512 user templates and reads HID Prox cards HG4-PROX
HandKey CR Hand Geometry Reader that stores user templates on OmniClass/iCLASS card HG4ICLASS
HandKey II Hand Geometry Reader that stores 512 user templates for standalone use HG4-II
Ethernet Module HGEN200
RS-232 to RS-485 Interface with 120V Power Supply HGDC104
Handnet for Windows, 5 Reader Licenses HGHNR5
Handnet for Windows, 25 Reader Licenses HGHNR25
Handnet for Windows, Unlimited Reader Licenses HGHNRUNL
Memory Expansion for software key for HG-4 and HG4-II units built after 2003, supports up to 9,728 users HG4-EM801
Memory Expansion EEPROM chip for HG-4 and HG4-II, supports up to 9,728 users HG4-EM-800
Memory Expansion EEPROM chip for HG-4 and HG4-II, supports up to 32,512 users HG4-EM-803
Hurricane Outdoor Enclosure with temperature range of -20° to 120° F (-29° to 49° C) when using internal heater option Dimensions: 14” H x 12” W x 10.5” D (35.6cm H x 30.5cm W x 26.7cm D) HG4ENC1
1 Actual operating distance will vary depending upon installation environment and proximity to metal.2 In accordance with Honeywell’s sales policy and warranty.
SECTION 5: page ��
Keyboard
Section 5.�: Access Control – Peripherals
ORDER CODES
Keyboard TK S31
Featuresl Wall Mounting
l Echelon “LON” Device
l Optional:
l Combined with Reader for
higher security access or
out of hours access.
Technical Specifications
Keyboard composed by 10 numeric keys and 6 function keys. It can used as a reader allowing the cardholder to insert his card number or also as door unlocking by keying the keyboard code.
2 multicoloured LED: Green for the correct reading on each direction, Red for invalid transaction, Yellow for Echelon Service function.
Variable Tones for valid/invalid transactions.
Electrical Specifications
Supply Voltage 12V dc ±15%
Energy Consumption 0.8W
LonWorks cabling Interface Unshielded twisted pair cable in free topology. (Transceiver FTT10A, 78Kbps)
Physical Specifications
Protection Degree IP55
Dimensions 160mm x 72mm x 52mm (W x H x D)
Weight 0.4kg
Mounting Horizontal or Vertical
Environmental Specifications
Working Temperature 0ºC to +50ºC
Relative Humidity Up to 95% without condensation
Certifications and Compliance
Electromagnetic Compatibility 89/336/CEE; 92/31/CEE; 93/68/CEE
Keyboard
SECTION 5: page �5
integrated Terminal
Section 5.�: Access Control – Peripherals
ORDER CODES
Integrated Terminal TS TA1x
Featuresl Wall Mounting
l Supports LCD Messaging
l Echelon “LON” Device
l Time & Attendance
l Optional reader technology
l HID Prox
l Magnetic Stripe
l Smart Card
l Optional
l Muster Station
Technical Specifications
Bi-processor CPU68EN302, including a Motorola 68000 (32 bit architecture) and an Ethernet communication processor.
1 Mbyte FLASH EPROM to Download the application firmware.
1 Mbyte FLASH EPROM on a removable cartridge for the download of the permanent database (tables of the access right of the users codes for the workdays, pre-holiday and holiday days) and for the ‘Transit and Events’ Buffer. Optional memory board with 8 Mbytes FLASH EPROM available.
1 Mbyte RAM for the current activity.
2 Relay out (1A, 30V contacts), 2 opto-coupled digital inputs (1 / 12V range).
Up to 10.000 cards and 2.500 transactions stored on a removable cartridge with Flash EPROM memory in case of connection failure with the EBI_Tema host (resulting in no losses in case of a power failure). Up to 60.000 cards and 40.000 transactions with the extended memory board. See table below for details.
Management of the peer-to-peer connection with the other TemaServer and as a consequence high decision-making capability and full operative autonomy.
Autonomous clock/calendar Chip with automatic management of regular/daylight saving time with an autonomy of 1000 hours in case of power failure.
Lead battery backup, with full functionality for 4 hours in case of network failure, and signalling of the battery-charge status.
Low voltage power-supply (12V dc/ac) for maintenance safety.
Tamper protection of the unit to prevent opening.
Watchdog protection for recovery in case of malfunctions.
Tele-diagnostic in Ethernet connection.
Available with the following reader technologies: HID, Magnetic, Motorola, WSE, Legic, Mifare (ISO 14443A), Smart card contact (ISO 7817).
Integrated Terminal
SECTION 5: page ��
ProductDescription
Standard Memory Card
Basic Configuration Cards Transactions buffer Event buffer
Access Control 10.000 2.500 400
Enhance AC / Basic T&A (Enhanced Personal data table)
6.000 2.500 400
Interactive T&A 2.500 10.000 135
SAP 2500 7.000 135
Extended Memory Card
Basic Configuration Cards Transactions buffer Event buffer
Access Control 60.000 40.000 5.000
Enhance AC / Basic T&A (Enhanced Personal data table)
50.000 40.000 5.000
Interactive T&A 15.000 65.000 1.000
SAP 32.000 65.000 1.000
Maximum number of cards and buffers size
Technical Specification
Electrical Specifications
Supply Voltage 12V dc/ac -15% to +20%
Energy Consumption 3.6W (4.2W max. during recharging of a fully used battery)
Interface Ethernet (10BaseT, 10Base2, AUI) for TCP/IP-UDP connection with EBI_Tema, and peer-to-peer between the other TemaServer units
Physical Specifications
Protection Degree IP55. For the TS_TA11 model, the magnetic head reader has IP31 protection degree
Dimensions 221mm x 304mm x 47 mm (W x H x D)
Weight 3.5kg, (+0.5kg transformer TRN01)
Environmental Specifications
Working Temperature 0ºC to +50ºC
Relative Humidity Up to 95% without condensation
Electromagnetic Compatibility 89/336/CEE; 92/31/CEE; 93/68/CEE
ORDER CODES
Integrated Terminal TS TA1x
integrated Terminal
Section 5.�: Access Control – Peripherals
SECTION 5: page ��
Dual Wiegand interface
Section 5.�: Access Control – Peripherals
ORDER CODES
Dual Wiegand Interface TK S014
Featuresl Wall Mounting
l Supports Two “Wiegand 5
Wire connected card readers
and the I/O associated with a
single door.
l Echelon “LON” Device
Technical Specifications
Temaline Dual Wiegand Interface Module.
Electrical Specifications
Supply Voltage 12V dc ± 20%
Energy Consumption 70mA
Outputs Power Open Collector (Drain)
Number: 2 Voltage: 10V to +14V max, (internal power supply) Voltage (absolute max) 10V to +30V (from external power supply) Current: 1.2A holding current (peak max 5A inductive load)
Inputs 5 states controlled: normal/close, open, short, cut, remote tamper. Number: 2 Current: 0 to 3mA Voltage: +10V max.
LonWorks cabling Interface Unshielded twisted pair cable in free topology. (Transceiver FTT10A, 78Kbps)
Wiegand Inputs Type: Wiegand (normally high) Number: 2 Voltage: +5V nominal (TTL), +14V max.
Power supply output for the readers Voltage: 12V +/-15% (line voltage) Current: 80mA max per channel.
Output to control LEDs and buzzer Type: Open collector Number: 3 each Wiegand channel Function: Red LED, Green LED, Buzzer Voltage: +14V max Current: 80mA max
Physical Specifications
Protection Degree IP31
Dimensions 105mm x 90mm x 70mm (W x H x D)
Weight 0.2kg
Mounting Standard DIN/omega rail
Environmental Specifications
Working Temperature 0ºC to +50ºC
Relative Humidity Up to 95% without condensation
Certifications and Compliance
Electromagnetic Compatibility 89/336/CEE; 92/31/CEE; 93/68/CEE
Dual Wiegand Interface
SECTION 5: page ��
Digital i/O module
Section 5.�: Access Control – Peripherals
ORDER CODES
Digital I/O Module TK C21
Featuresl Wall Mounting
l Supports 4 x Inputs & 4 x
Outputs
l Echelon “LON” Device
Technical Specifications
Temaline I/O Module.
Provides 4 Open collector Outputs and 4 Controlled Inputs.
Must be mounted on a standard DIN rail.
Electrical Specifications
Supply Voltage 12V dc ±15%
Energy Consumption 0.7W (50mA)
Outputs Open Collector Voltage: +14V max, 0V min. Current: 0.1A max.
Inputs 5 states controlled: normal, open, short, cut, remote tamper. Current: 0 to 3mA for each input (internal reference) Voltage: +14V max.
LonWorks cabling Interface Unshielded twisted pair cable in free topology. (Transceiver FTT10A, 78Kbps)
Physical Specifications
Dimensions 105mm x 90mm x 70mm (W x H x D)
Weight 0.2kg
Mounting Standard DIN/omega rail
Environmental Specifications
Working Temperature 0ºC to +50ºC
Relative Humidity Up to 95% without condensation
Certifications and Compliance
Electromagnetic Compatibility 89/336/CEE; 92/31/CEE; 93/68/CEE
Digital I/O Module
SECTION 5: page ��
Power Supply module
Section 5.�: Access Control – Peripherals
ORDER CODES
Power Supply Module TP U01
Featuresl Intelligent Power Supply
l Monitors all features of the
Power Supply associated with
the TemaServer.
Technical Specifications
Temaline intelligent power supply.
Includes backup battery for 4 hours of autonomy in case of power failure.
Electrical Specifications
Supply Voltage 230V ac ±15% 50Hz
Energy Consumption 80 mAAC (nominal, on 10W load) 200 mAAC max. (for fast battery recharge)
Outputs Voltage 12.5V dc ±10% Current 0 to 0.8A (nominal) 1A (max.)
Battery recharge 80% of capacity in 4 hours
Battery autonomy 4 hours with an 800mA load
LonWorks cabling Interface Unshielded twisted pair cable in free topology. (Transceiver FTT10A, 78Kbps)
Physical Specifications
Protection Degree IP55
Dimensions 221mm x 305mm x 95mm (W x H x D)
Weight 5.9kg
Mounting Vertical only
Environmental Specifications
Working Temperature 0ºC to +40ºC
Relative Humidity Up to 95% without condensation
Certifications and Compliance
Electromagnetic Compatibility 89/336/CEE; 92/31/CEE; 93/68/CEE
Low Voltage Safety 72/23/CEE; 93/68/CEE
Power Supply Module
SECTION 5: page 50
Power Supply module
Section 5.�: Access Control – Peripherals
ORDER CODES
Power Supply Module TP U03
Technical Specifications
Temaline intelligent power supply.
Includes backup battery for 4 hours of autonomy in case of power failure.
Electrical Specifications
Supply Voltage 230V ac ±15% 50Hz
Energy Consumption 350 mAAC (nominal, on 60W load) 1 AAC max. (for fast battery recharge)
Outputs Voltage 12.5V dc ±10% Current 0 to 4.5A (nominal) 5A (max.)
Battery recharge 80% of capacity in 4 hours
Battery autonomy 4 hours with 4.5A load
LonWorks cabling Interface Unshielded twisted pair cable in free topology. (Transceiver FTT10A, 78Kbps)
Physical Specifications
Protection Degree IP45
Dimensions 221mm x 305mm x 233mm (W x H x D)
Weight 8.5kg + 9kg battery
Mounting Vertical only
Environmental Specifications
Working Temperature 0ºC to +40ºC
Relative Humidity Up to 95% without condensation
Certifications and Compliance
Electromagnetic Compatibility 89/336/CEE; 92/31/CEE; 93/68/CEE
Low Voltage Safety 72/23/CEE; 93/68/CEE
Power Supply Module
SECTION 5: page 5�
Power Supply Controller
Section 5.�: Access Control – Peripherals
ORDER CODES
Power Supply Controller TP U04
Featuresl Intelligent Power Supply
l Monitors all features of
3rd Party Power Supply
associated with the
TemaServer
Technical Specifications
Temaline intelligent power supply controller.
Allows user of external power supply and batteries, providing the same features that a Temaline power supply provides.
Management of tamper on case opened. Additional input for external anti-removal tamper switch.
Electrical Specifications
Power Supply 14.1V dc ±2% 10A max, depending on the configuration
Outputs Voltage 12.5V dc ±10% Current 1A, 2.5A, 5A configurable
Battery recharge time Voltage 13.8V dc ±1% Current 0.5 to 5A configurable
Battery autonomy Configurable
LonWorks cabling Interface Unshielded twisted pair cable in free topology.
Physical Specifications
Protection Degree IP31
Dimensions 160mm x 55mm x 110mm (W x H x D)
Weight 0.4kg
Mounting DIN rail
Environmental Specifications
Working Temperature 0ºC to +45ºC
Relative Humidity Up to 85% without condensation
Certifications and Compliance
Electromagnetic Compatibility 89/336/EEC; 92/31/EEC
Low Voltage Safety 72/23/EEC; 93/68/EEC
Power Supply Controller