UPFLOW/HORIZONTAL2-STAGE, VARIABLE SPEEDGAS-FIRED FURNACE
PUB. NO. 22-1650-13
XV80MODELS TUD2B060A9V3VB, TUD2B080A9V3VB TUD2C080A9V4VB, TUD2C080B9V4VBTUD2B100A9V3VB, TUD2C100A9V5VBTUD2C100B9V5VB, TUD2D120A9V5VBTUD2D120B9V5VB, TUD2D140A9V5VB
© 2011 Trane
Two-Stage FanAssisted CombustionSystem
2 22-1650-13
GeneralFeatures
© 2011 Trane
NATURAL GAS MODELSCentral Heating furnace designs are cer-tified by the American Gas Association for both natural and L.P. gas. Limit setting and rating data were established and approved under standart rating condi-tions using American National Standards Instirute standards.
SAFE OPERATIONThe Integrated System Control has solid state devices, which continuously monitor for presence of flame, when the system is in the heaating mode of operation. Dual solenoid combination gas valve and regulator provide extra safety.
QUICK HEATINGDurable, cycle tested, heavy gauge aluminized steel heat exchanger quickly transfers heat to provide warm condi-tioned air to the structure. Low energy power vent blower, to increase efficiency and provide a positive discharge of gas fumes to the outside.
BURNERSMultiport In-shot burners will give years of quiet and efficient service. All models can be converted to L.P. gas.
INTEGRATED SYSTEM CONTROLExclusively designed operational program provides total control of furnace limit sensors, blowers, gas valve, flame control and includes self diagnostics for ease of service. Also contains connection points for E.A.C./humidifier.
AIR DELIVERYThe variable speed, direct drive blower motor, has sufficient airflow for most heating and cooling requirements, will switch from heating to cooling speeds on demand from room thermostat. The blower door safety switch will prevent or terminate furnace operation when the blower door is removed. Some models are available with high efficiency blowers.
STYLINGHeavy gauge steel and “wrap-around” cabinet construction is used in the cabinet with baked-on enamel finish for strength and beauty. The heat exchanger section of the cabinet is completely lined with foil faced fiberglass insulation. This results in quiet and efficient opera-tion due to the excellent acoustical and insulating qualities of fiberglass. Built-in bottom pan and alternate bottom, left or right side return air connection provision.
FEATURES AND GENERAL OPERA-TIONThe XV80 High Efficiency Gas Furnaces employ a Hot Surface Ignition system, which eliminates the waste of a constant burning pilot. The integrated system control lights the main burners upon a de-mand for heat from the room thermostat. Complete front service access. a. Low energy power venter b. Vent proving pressure switch.
322-1650-13
Feature Summary
Features and Benefits Standard Equipment Optional Equipment
General Data TUD2B060A9V3VB TUD2B080A9V3VB TUD2C080A9V4VB TUD2C080B9V4VB TUD2B100A9V3VB TUD2C100A9V5VB TUD2C100B9V5VB TUD2D120A9V5VB TUD2D120B9V5VB TUD2D140A9V5VB
Performance Data
Electric Data
Field Wiring Diagrams
Dimensions
Contents
2
4 4 5
6
9
19
19
24
4 22-1650-13
XV80 STANDARD EQUIPMENT•Upflow/Horizontaland•Powersupply115/1/60•2-stagegasvalve•2-speedventer•Variablespeedblowermotor•SiliconNitridehotsurfaceigniterwith
adaptive heat up•Integratedsolidstatecontrol•Attractivecoloraccents•Heavygaugealuminizedsteelheat
exchanger•Multi-portIn-shotburners•Completefrontserviceaccess•Alternatebottom/left/rightreturnair•Slideoutblowerassembly•Hingedblowerdoor•Perfectfitdoorcatches
•Insulatedblowerdoor•Gasketedblowerdoor•Internalfilterrack•Standardfiltersizes•Two-tonecolor•Directdrive,variablespeedmotor•Integratedsolidstatecontrolwith self-diagnostics•Commonventcapability•Cleanableframedfilters•OptionalL.P.conversionkit•Left/rightgasconnection•Accessoryhook-upcapability•Selectablecoolingfanoffdelay
eliminates need for BAY24X045 time delay kit
•Enhancedcoolingcontrol
Featuresand Benefits
522-1650-13
XV80 OPTIONAL EQUIPMENTThermostat, Mechanical 2-Stage Heating/1-Stage Cooling ........................................................................................ TAYSTAT241 [ ]Thermostat, Mechanical Heating Only With Fan Switch ............................................................................................. BAYSTAT303 [ ]Thermostat, Mechanical Heating Only ....................................................................................................................... BAYSTAT388 [ ]Thermostat, Heating/Cooling Single Stage (Mounts Horizontally) .................................................................................AY28X092 [ ]Thermostat, Electronic Non-programmable 1-Stage Heating/1-Stage Cooling .......................................................... BAYSTAT370 [ ]Thermostat, Electronic Programmable (5-2) 1-Stage Heating/1-Stage Cooling ......................................................... BAYSTAT340 [ ]Thermostat, Heating/Cooling Single Stage (Mounts Vertically) .................................................................................. BAYSTAT305 [ ]Thermostat, Electronic Programmable 2-Stage Heating/2-Stage Cooling ............................................................... TAYSTAT302C [ ]Thermostat, Electronic Programmable 1-Stage Heating/1-Stage Cooling ............................................................... TAYSTAT300C [ ]Propane Conversion Kit ........................................................................................................................................... BAYLPKT210A [ ]Electronic Air Filter, “Perfect Fit” High Efficiency (17-1/2" Wide Gas Furnace) ........................................................TFM175A9FR0 [ ]Electronic Air Filter, “Perfect Fit” High Efficiency (21" Wide Gas Furnace) ..............................................................TFM210A9FR0 [ ]Electronic Air Filter, “Perfect Fit” High Efficiency (24-1/2" Wide Gas Furnace) ........................................................TFM245A9FR0 [ ] Electronic Air Filter, “Perfect Fit” Standard Efficiency (17-1/2" Wide Gas Furnace)..................................................TFP175A9FR0 [ ]Electronic Air Filter, “Perfect Fit” Standard Efficiency (21" Wide Gas Furnace) ........................................................TFP210A9FR0 [ ]Electronic Air Filter, “Perfect Fit” Standard Efficiency (24-1/2" Wide Gas Furnace)..................................................TFP245A9FR0 [ ] Coil Enclosure (17-1/2" Wide Cabinets) ............................................................................................................BAYCLE17A1722A [ ]Coil Enclosure (21" Wide Cabinets) ..................................................................................................................BAYCLE21A2130A [ ]Coil Enclosure (24-1/2" Wide Cabinets) ............................................................................................................BAYCLE24A2430A [ ]Side Filter Rack .......................................................................................................................................................... BAYFLTR200 [ ]High Altitude Switch ....................................................................................................................................................BAYHALT249 [ ]Masonry Chimney Vent Kit (Upflow models only) ....................................................................................................BAYVENT800B [ ] Filter Rack Kit 1 .................................................................................................................................................... BAYRACK960A [ ]1 Available for models with 1800 CFM or greater which require an additional side return.
Featuresand Benefits
6 DATA SUBJECT TO CHANGE WITHOUT NOTICE 22-1650-13
MODEL
TYPE
RATINGS 21st Stage Input BTUH 1st Stage Capacity BTUH (ICS) 32nd Stage Input BTUH 2nd Stage Capacity BTUH (ICS) 3Temp. rise (Min.-Max.) °F.
BLOWER DRIVEDiameter - Width (In.)No. UsedSpeeds (No.)CFM vs. in. w.g.Motor HPR.P.M.Volts / Ph / Hz
COMBUSTION FAN - TypeDrive - No. SpeedsMotor HP - RPMVolts / Ph / HzFLA
FILTER — Furnished?Type RecommendedHi Vel. (No.-Size-Thk.)
VENT — Size (In.)
HEAT EXCHANGERType -Fired -UnfiredGauge (Fired)
ORIFICES — MainNat. Gas. Qty. — Drill SizeL.P. Gas Qty. — Drill Size
GAS VALVE
PILOT SAFETY DEVICEType
BURNERS — TypeNumber
POWER CONN. — V / Ph / Hz 4Ampacity (In Amps)Max. Overcurrent Protection (Amps)
PIPE CONN. SIZE (In.)
DIMENSIONSCrated (In.)
WEIGHTShipping (Lbs.) / Net (Lbs.)
TUD-R9V PRODUCT SPECIFICATIONS1
1 Central Furnace heating designs are certified to ANSI Z21.47 / CSA 2.32 For U.S. applications, above input ratings (BTUH) are up to 2,000 feet, derate 4% per 1,000 feet for elevations above 2,000 feet above sea level. For Canadian applications,
above input ratings (BTUH) are up to 4,500 feet, derate 4% per 1,000 feet for elevations above 4,500 feet above sea level.3 Based on U.S. government standard tests.4 The above wiring specifications are in accordance with National Electrical Code; however, installations must comply with local codes.
GENERAL DATA
TUD2B080A9V3VB
Upflow / Horizontal
52,00041,60080,00064,00030 - 60
Direct10 x 7
1Variable
See Airflow Table1/2
Variable115/1/60
CentrifugalDirect - 2
1/50 - 3000115/1/60
0.7
YesHigh Velocity
1 - 17x25 - 1in.
4 Round
Alum. Steel - Type 1
20
4 — 454 — 56
Redundant - Two Stage
Hot Surface Ignition
Multi-port In-shot4
115/1/6010.515
1/2
H x W x D41-3/4 x 19-1/2 x 30-1/2
142 / 132
TUD2B060A9V3VB
Upflow / Horizontal
39,00031,20060,00048,00030 - 60
Direct10 x 7
1Variable
See Airflow Table1/2
Variable115/1/60
CentrifugalDirect - 2
1/50 - 3000115/1/60
0.7
YesHigh Velocity
1 - 17x25 - 1in.
4 Round
Alum. Steel - Type 1
20
3 — 453 — 56
Redundant - Two Stage
Hot Surface Ignition
Multi-port In-shot3
115/1/6010.515
1/2
H x W x D41-3/4 x 19-1/2 x 30-1/2
136 / 126
TUD2C080A9V4VB
Upflow / Horizontal
52,00041,60080,00064,00030 - 60
Direct10 x 10
1Variable
See Airflow Table3/4
Variable115/1/60
CentrifugalDirect - 2
1/50 - 3000115/1/60
0.7
YesHigh Velocity
1 - 20x25 - 1in.
4 Round
Alum. Steel - Type 1
20
4 — 454 — 56
Redundant - Two Stage
Hot Surface Ignition
Multi-port In-shot4
115/1/6012.920
1/2
H x W x D41-3/4 x 23 x 30-1/2
166 / 155
22-1650-13 DATA SUBJECT TO CHANGE WITHOUT NOTICE 7
MODEL
TYPE
RATINGS 21st Stage Input BTUH 1st Stage Capacity BTUH (ICS) 32nd Stage Input BTUH 2nd Stage Capacity BTUH (ICS) 3Temp. rise (Min.-Max.) °F.
BLOWER DRIVEDiameter - Width (In.)No. UsedSpeeds (No.)CFM vs. in. w.g.Motor HPR.P.M.Volts / Ph / Hz
COMBUSTION FAN - TypeDrive - No. SpeedsMotor HP - RPMVolts / Ph / HzFLA
FILTER — Furnished?Type RecommendedHi Vel. (No.-Size-Thk.)
VENT — Size (In.)
HEAT EXCHANGERType -Fired -UnfiredGauge (Fired)
ORIFICES — MainNat. Gas. Qty. — Drill SizeL.P. Gas Qty. — Drill Size
GAS VALVE
PILOT SAFETY DEVICEType
BURNERS — TypeNumber
POWER CONN. — V / Ph / Hz 4Ampacity (In Amps)Max. Overcurrent Protection (Amps)
PIPE CONN. SIZE (In.)
DIMENSIONSCrated (In.)
WEIGHTShipping (Lbs.) / Net (Lbs.)
TUD2C100A9V5VB
Upflow / Horizontal
65,00052,000100,00079,00035 - 65
Direct10 x 10
1Variable
See Airflow Table1
Variable115/1/60
CentrifugalDirect - 2
1/50 - 3000115/1/60
0.87
YesHigh Velocity
1 - 20x25 - 1in.
4 Round
Alum. Steel - Type 1
20
5 — 455 — 56
Redundant - Two Stage
Hot Surface Ignition
Multi-port In-shot5
115/1/6014.920
1/2
H x W x D41-3/4 x 23 x 30-1/2
166 / 155
TUD2B100A9V3VB
Upflow / Horizontal
65,00052,000100,00080,00040 - 70
Direct10 x 7
1Variable
See Airflow Table1/2
Variable115/1/60
CentrifugalDirect - 2
1/50 - 3000115/1/60
0.87
YesHigh Velocity
1 - 17x25 - 1in.
4 Round
Alum. Steel - Type 1
20
5 — 455 — 56
Redundant - Two Stage
Hot Surface Ignition
Multi-port In-shot5
115/1/6010.815
1/2
H x W x D41-3/4 x 19-1/2 x 30-1/2
142 / 132
TUD-R9V PRODUCT SPECIFICATIONS1
1 Central Furnace heating designs are certified to ANSI Z21.47 / CSA 2.32 For U.S. applications, above input ratings (BTUH) are up to 2,000 feet, derate 4% per 1,000 feet for elevations above 2,000 feet above sea level. For Canadian applications,
above input ratings (BTUH) are up to 4,500 feet, derate 4% per 1,000 feet for elevations above 4,500 feet above sea level.3 Based on U.S. government standard tests.4 The above wiring specifications are in accordance with National Electrical Code; however, installations must comply with local codes.5 Model uses high efficiency blower.
TUD2C080B9V4VB 5
Upflow / Horizontal
52,00041,60080,00064,00030 - 60
Direct 10 x 10
1Variable
See Airflow Table3/4
Variable115/1/60
CentrifugalDirect - 2
1/50 - 3000115/1/60
0.7
YesHigh Velocity
1 - 20x25 - 1in.
4 Round
Alum. Steel - Type 1
20
4 — 454 — 56
Redundant - Two Stage
Hot Surface Ignition
Multi-port In-shot4
115/1/6012.920
1/2
H x W x D41-3/4 x 23 x 30-1/2
166 / 155
8 DATA SUBJECT TO CHANGE WITHOUT NOTICE 22-1650-13
MODEL
TYPE
RATINGS 21st Stage Input BTUH 1st Stage Capacity BTUH (ICS) 32nd Stage Input BTUH 2nd Stage Capacity BTUH (ICS) 3Temp. rise (Min.-Max.) °F.
BLOWER DRIVEDiameter - Width (In.)No. UsedSpeeds (No.)CFM vs. in. w.g.Motor HPR.P.M.Volts / Ph / Hz
COMBUSTION FAN - TypeDrive - No. SpeedsMotor HP - RPMVolts / Ph / HzFLA
FILTER — Furnished?Type RecommendedHi Vel. (No.-Size-Thk.)
VENT — Size (In.)
HEAT EXCHANGERType -Fired -UnfiredGauge (Fired)
ORIFICES — MainNat. Gas. Qty. — Drill SizeL.P. Gas Qty. — Drill Size
GAS VALVE
PILOT SAFETY DEVICEType
BURNERS — TypeNumber
POWER CONN. — V / Ph / Hz 4Ampacity (In Amps)Max. Overcurrent Protection (Amps)
PIPE CONN. SIZE (In.)
DIMENSIONSCrated (In.)
WEIGHTShipping (Lbs.) / Net (Lbs.)
TUD-R9V PRODUCT SPECIFICATIONS1
1 Central Furnace heating designs are certified to ANSI Z21.47 / CSA 2.32 For U.S. applications, above input ratings (BTUH) are up to 2,000 feet, derate 4% per 1,000 feet for elevations above 2,000 feet above sea level. For Canadian applications,
above input ratings (BTUH) are up to 4,500 feet, derate 4% per 1,000 feet for elevations above 4,500 feet above sea level.3 Based on U.S. government standard tests.4 The above wiring specifications are in accordance with National Electrical Code; however, installations must comply with local codes.5 Model uses high efficiency blower.
TUD2D120A9V5VB
Upflow / Horizontal
78,00062,400120,00097,00035 - 65
Direct10 x 10
1Variable
See Airflow Table1
Variable115/1/60
CentrifugalDirect - 2
1/50 - 3000115/1/60
1.14
YesHigh Velocity
1 - 24x25 - 1in.
4 Round
Alum. Steel - Type 1
20
6 — 456 — 56
Redundant - Two Stage
Hot Surface Ignition
Multi-port In-shot6
115/1/6015.320
1/2
H x W x D41-3/4 x 26-1/2 x 30-1/2
193 / 181
TUD2D140A9V5VB
Upflow / Horizontal
91,00072,800140,000111,00040 - 70
Direct10 x 10
1Variable
See Airflow Table1
Variable115/1/60
CentrifugalDirect - 2
1/50 - 3000115/1/60
1.16
YesHigh Velocity
1 - 24x25 - 1in.
4 Round
Alum. Steel - Type 1
20
7 — 457 — 56
Redundant - Two Stage
Hot Surface Ignition
Multi-port In-shot7
115/1/6015.320
1/2
H x W x D41-3/4 x 26-1/2 x 30-1/2
197 / 185
TUD2D120B9V5VB 5
Upflow / Horizontal
78,00062,400120,00097,00035 - 65
Direct10 x 10
1Variable
See Airflow Table1
Variable115/1/60
CentrifugalDirect - 2
1/50 - 3000115/1/60
1.14
YesHigh Velocity
1 - 24x25 - 1in.
4 Round
Alum. Steel - Type 1
20
6 — 456 — 56
Redundant - Two Stage
Hot Surface Ignition
Multi-port In-shot6
115/1/6015.320
1/2
H x W x D41-3/4 x 26-1/2 x 30-1/2
193 / 181
TUD2C100B9V5VB 5
Upflow / Horizontal
65,00052,000100,00079,00035 - 65
Direct10 x 10
1Variable
See Airflow Table1
Variable115/1/60
CentrifugalDirect - 2
1/50 - 3000115/1/60
0.87
YesHigh Velocity
1 - 20x25 - 1in.
4 Round
Alum. Steel - Type 1
20
5 — 455 — 56
Redundant - Two Stage
Hot Surface Ignition
Multi-port In-shot5
115/1/6014.920
1/2
H x W x D41-3/4 x 23 x 30-1/2
166 / 155
22-1650-13 DATA SUBJECT TO CHANGE WITHOUT NOTICE 9
*UD2B060A9V3VB FURNACE COOLING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER
OUTDOOR UNIT SIZE
(TONS)
AIRFLOWSETTING
DIP SWITCH SETTING EXTERNAL STATIC PRESSURE
SW1 SW2 SW3 SW4 0.1 0.3 0.5 0.7 0.9
1.5
LOW(350 CFM/ TON) ON ON OFF ON CFM
WATTS49950
53780
520110
520145
500175
NORMAL(400 CFM/ TON) ON ON OFF OFF CFM
WATTS60560
61080
610120
597155
593180
HIGH(450 CFM/ TON) ON ON ON OFF CFM
WATTS64975
681110
665145
665180
672220
2
LOW(350 CFM/ TON) OFF ON OFF ON CFM
WATTS68080
722125
680150
696190
696225
NORMAL(400 CFM/ TON) OFF ON OFF OFF CFM
WATTS798105
804145
809170
823235
818280
HIGH(450 CFM/ TON) OFF ON ON OFF CFM
WATTS884145
896180
924240
931280
931330
2.5
LOW(350 CFM/ TON) ON OFF OFF ON CFM
WATTS858125
863175
882220
894275
895320
NORMAL(400 CFM/ TON) ON OFF OFF OFF CFM
WATTS984170
1017225
1038295
1017330
1017375
HIGH(450 CFM/ TON) ON OFF ON OFF CFM
WATTS1125245
1138315
1150370
1161435
1161475
3 **
LOW(350 CFM/ TON) OFF OFF OFF ON CFM
WATTS1035205
1056265
1076330
1076370
1076430
NORMAL **(400 CFM/ TON) OFF OFF OFF OFF CFM
WATTS1208300
1247360
1268440
1278485
1200490
HIGH(450 CFM/ TON) OFF OFF ON OFF CFM
WATTS1380440
1410500
1402550
1350550
1235525
NOTES:1. *FIRST LETTER MAY BE "A" OR "T" 2. **FACTORY SETTING.3. CONTINUOUS FAN SETTING: HEATING OR COOLING AIRFLOW IS APPROXIMATELY 50% OF SELECTED COOLING VALUE.4. LOW 350 CFM/TON IS RECOMMENDED FOR VARIABLE SPEED APPLICATION FOR COMFORT & HUMID CLIMATE SETTING: NORMAL IS 400 CFM/TON: HIGH 450 CFM/TON IS FOR DRY CLIMATE SETTING.
*UD2B060A9V3VB FURNACE HEATING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER
AIRFLOWSETTING
DIP SWITCH SETTING EXTERNAL STATIC PRESSURE
SW7 SW8 0.1 0.3 0.5 0.7 0.9
HEATING1ST
STAGE
LOW ON ONCFM
TEMP. RISEWATTS
5894965
6044895
61947125
60448160
60748200
MEDIUM ** ON OFFCFM
TEMP. RISEWATTS
6634475
69442120
68442145
68142185
68642220
HIGH OFF OFFCFM
TEMP. RISEWATTS
77537105
78137145
77637180
80536230
81136270
HEATING2ND
STAGE
LOW ON ONCFM
TEMP. RISEWATTS
81355110
81854150
81854185
83753240
84253280
MEDIUM ** ON OFFCFM
TEMP. RISEWATTS
90749140
91948200
94247240
95846300
95946330
HIGH OFF OFFCFM
TEMP. RISEWATTS
103843190
106642260
108641325
108941365
107941415
10 DATA SUBJECT TO CHANGE WITHOUT NOTICE 22-1650-13
*UD2B080A9V3VB FURNACE COOLING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER
OUTDOORUNIT SIZE
(TONS)
AIRFLOWSETTING
DIP SWITCH SETTING EXTERNAL STATIC PRESSURE
SW 1 SW 2 SW 3 SW 4 0.1 0.3 0.5 0.7 0.9
2.5
LOW(350 CFM/TON) OFF ON OFF ON CFM
WATTS880120
875155
860190
845225
840245
NORMAL (400 CFM/TON) OFF ON OFF OFF CFM
WATTS1020170
1000205
990240
980280
960320
HIGH(450 CFM/TON) OFF ON ON OFF CFM
WATTS1110210
110260
1110320
1100350
1100385
3.0
LOW(350 CFM/TON) ON OFF OFF ON CFM
WATTS1040190
1010220
1000260
1000310
990340
NORMAL (400 CFM/TON) ON OFF OFF OFF CFM
WATTS1200250
1200320
1190370
1190415
1175450
HIGH(450 CFM/TON) ON OFF ON OFF CFM
WATTS1340355
1340425
1330475
1320530
1300570
3.5 **
LOW(350 CFM/TON) OFF OFF OFF ON CFM
WATTS1215265
1210330
1210375
1200430
1185465
NORMAL **(400 CFM/TON) OFF OFF OFF OFF CFM
WATTS1430415
1415457
1410520
1385575
1330580
HIGH(450 CFM/TON) OFF OFF ON OFF CFM
WATTS1430415
1415475
1410520
1385575
1330580
NOTES:1. * First Letter may be "A" or "T"2. ** Factory setting3. Continuous Fan Setting: Heating or Cooling airflow is approximately 50% of selected Cooling value.4. LOW 350 cfm/ton is recommended for Variable Speed application for COMFORT & HUMID CLIMATE setting; NORMAL is 400 cfm/ton; HIGH 450 cfm/ton is for DRY CLIMATE setting
*UD2B080A9V3VB FURNACE HEATING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER
AIRFLOWSETTING
DIP SWITCH SETTING EXTERNAL STATIC PRESSURE
SW 7 SW 8 0.1 0.3 0.5 0.7 0.9
HEATING1ST
STAGE
LOW ON ONCFM
TEMP. RISEWATTS
80048100
79049135
76550155
75052200
73053230
MEDIUM ** ON OFFCFM
TEMP. RISEWATTS
91043130
89044170
87544210
86045240
82047280
HIGH OFF OFFCFM
TEMP. RISEWATTS
106037188
102038220
101039265
101039310
100039350
HEATING2ND
STAGE
LOW ON ONCFM
TEMP. RISEWATTS
111054210
109055260
109055310
108055350
106556400
MEDIUM ** ON OFFCFM
TEMP. RISEWATTS
124548300
124048355
124048410
123048460
121549500
HIGH OFF OFFCFM
TEMP. RISEWATTS
141542410
140042470
140042530
137543580
132045590
22-1650-13 DATA SUBJECT TO CHANGE WITHOUT NOTICE 11
*UD2C080A9V4VB FURNACE HEATING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER
AIRFLOWSETTING
DIP SWITCH SETTING EXTERNAL STATIC PRESSURE
SW 7 SW 8 0.1 0.3 0.5 0.7 0.9
HEATING1ST
STAGE
LOW ON ONCFM
TEMP. RISEWATTS
7824975
76251110
75151145
74851185
73752225
MEDIUM ** ON OFFCFM
TEMP. RISEWATTS
8704490
86545125
86145175
84845215
83146255
HIGH OFF OFFCFM
TEMP. RISEWATTS
96240110
97440155
96340200
93841245
91442290
HEATING2ND
STAGE
LOW ON ONCFM
TEMP. RISEWATTS
109154145
109254190
108755245
109254305
107755355
MEDIUM ** ON OFFCFM
TEMP. RISEWATTS
121149190
124348255
124348310
124448370
123548430
HIGH OFF OFFCFM
TEMP. RISEWATTS
137143255
138843325
139243395
138543455
137743515
*UD2C080A9V4VB FURNACE COOLING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER
OUTDOORUNIT SIZE
(TONS)
AIRFLOWSETTING
DIP SWITCH SETTING EXTERNAL STATIC PRESSURE
SW 1 SW 2 SW 3 SW 4 0.1 0.3 0.5 0.7 0.9
2.5
LOW(350 CFM/TON) ON ON OFF ON CFM
WATTS86390
865130
858175
843220
831255
NORMAL (400 CFM/TON) ON ON OFF OFF CFM
WATTS995115
1005170
989210
973260
956305
HIGH(450 CFM/TON) ON ON ON OFF CFM
WATTS1101150
1112200
1111255
1107305
1101360
3.0
LOW(350 CFM/TON) OFF ON OFF ON CFM
WATTS1031125
1031175
1026215
1013270
1003320
NORMAL (400 CFM/TON) OFF ON OFF OFF CFM
WATTS1163170
1178230
1188285
1183345
1178405
HIGH(450 CFM/TON) OFF ON ON OFF CFM
WATTS1319240
1337305
1344365
1340420
1336485
3.5 LOW
(350 CFM/TON) ON OFF OFF ON CFMWATTS
1182200
1206240
1211295
1211350
1211420
NORMAL(400 CFM/TON) ON OFF OFF OFF CFM
WATTS1380255
1401325
1402390
1402460
1399515
HIGH(450 CFM/TON) ON OFF ON OFF CFM
WATTS1553350
1566425
1557500
1558560
1559645
4 **
LOW(350 CFM/TON) OFF OFF OFF ON CFM
WATTS1386255
1401330
1408395
1402460
1390520
NORMAL **(400 CFM/TON) OFF OFF OFF OFF CFM
WATTS1590360
1593440
1591515
1588575
1576650
HIGH(450 CFM/TON) OFF OFF ON OFF CFM
WATTS1791360
1808615
1810615
1808775
1726800
NOTES:1. * First Letter may be "A" or "T"2. ** Factory setting3. Continuous Fan Setting: Heating or Cooling airflow is approximately 50% of selected Cooling value.4. LOW 350 cfm/ton is recommended for Variable Speed application for COMFORT & HUMID CLIMATE setting; NORMAL is 400 cfm/ton; HIGH 450 cfm/ton is for DRY CLIMATE setting
12 DATA SUBJECT TO CHANGE WITHOUT NOTICE 22-1650-13
*UD2C080B9V4VB FURNACE HEATING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER
AIRFLOWSETTING
DIP SWITCH SETTING EXTERNAL STATIC PRESSURE
SW 7 SW 8 0.1 0.3 0.5 0.7 0.9
HEATING1ST
STAGE
LOW ON ONCFM
TEMP. RISEWATTS
97449133
96849285
94950202
92551254
90652304
MEDIUM ** ON OFFCFM
TEMP. RISEWATTS
11024393
111243144
110343201
108344255
106645305
HIGH OFF OFFCFM
TEMP. RISEWATTS
119440119
121739180
121539243
120040304
118240362
HEATING2ND
STAGE
LOW ON ONCFM
TEMP. RISEWATTS
118958142
121057209
120957276
119358341
117558404
MEDIUM ** ON OFFCFM
TEMP. RISEWATTS
134651141
138849207
139849274
139049339
137250401
HIGH OFF OFFCFM
TEMP. RISEWATTS
146047186
151645263
153645335
153345407
151545477
*UD2C080B9V4VB FURNACE COOLING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER
OUTDOORUNIT SIZE
(TONS)
AIRFLOWSETTING
DIP SWITCH SETTING EXTERNAL STATIC PRESSURE
SW 1 SW 2 SW 3 SW 4 0.1 0.3 0.5 0.7 0.9
2.5
LOW(350 CFM/TON) ON ON OFF ON CFM
WATTS84271
819114
789163
756207
740249
NORMAL (400 CFM/TON) ON ON OFF OFF CFM
WATTS95690
948140
928196
901248
884298
HIGH(450 CFM/TON) ON ON ON OFF CFM
WATTS1071113
1078171
1067233
1045292
1028348
3.0
LOW(350 CFM/TON) OFF ON OFF ON CFM
WATTS100299
1000152
983210
958265
942318
NORMAL (400 CFM/TON) OFF ON OFF OFF CFM
WATTS1140128
1155191
1150256
1132319
1114379
HIGH(450 CFM/TON) OFF ON ON OFF CFM
WATTS1278165
1311238
1316308
1305377
1287444
3.5 LOW
(350 CFM/TON) ON OFF OFF ON CFMWATTS
1163134
1181199
1177265
1161328
1143389
NORMAL(400 CFM/TON) ON OFF OFF OFF CFM
WATTS1324179
1363255
1372326
1363397
1345466
HIGH(450 CFM/TON) ON OFF ON OFF CFM
WATTS1485234
1544319
1566396
1565472
1546550
4 **
LOW(350 CFM/TON) OFF OFF OFF ON CFM
WATTS1324179
1363255
1372326
1363397
1345466
NORMAL **(400 CFM/TON) OFF OFF OFF OFF CFM
WATTS1508243
1570329
1594407
1593483
1575562
HIGH(450 CFM/TON) OFF OFF ON OFF CFM
WATTS1691322
1777416
1816499
1824579
1805669
NOTES:1. * First Letter may be "A" or "T"2. ** Factory setting3. Continuous Fan Setting: Heating or Cooling airflow is approximately 50% of selected Cooling value.4. LOW 350 cfm/ton is recommended for Variable Speed application for COMFORT & HUMID CLIMATE setting; NORMAL is 400 cfm/ton; HIGH 450 cfm/ton is for DRY CLIMATE setting
22-1650-13 DATA SUBJECT TO CHANGE WITHOUT NOTICE 13
*UD2B100A9V3VB FURNACE HEATING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER
AIRFLOWSETTING
DIP SWITCH SETTING EXTERNAL STATIC PRESSURE
SW 7 SW 8 0.1 0.3 0.5 0.7 0.9
HEATING1ST
STAGE
LOW ON ONCFM
TEMP. RISEWATTS
7516486
79661132
81759175
83258218
83857263
MEDIUM ** ON OFFCFM
TEMP. RISEWATTS
86256121
92152185
95351233
96750285
95450322
HIGH OFF OFFCFM
TEMP. RISEWATTS
95950148
100248210
103646280
103646325
100348355
HEATING2ND
STAGE
LOW ON ONCFM
TEMP. RISEWATTS
109967227
112466287
114964355
115764415
105570395
MEDIUM ** ON OFFCFM
TEMP. RISEWATTS
128658365
132156450
131356455
121561475
111966450
HIGH OFF OFFCFM
TEMP. RISEWATTS
139953465
141952570
134755545
126559520
116364485
*UD2B100A9V3VB FURNACE COOLING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER
OUTDOORUNIT SIZE
(TONS)
AIRFLOWSETTING
DIP SWITCH SETTING EXTERNAL STATIC PRESSURE
SW 1 SW 2 SW 3 SW 4 0.1 0.3 0.5 0.7 0.9
1.5
LOW(350 CFM/TON) ON ON OFF ON CFM
WATTS51650
53675
551105
547135
530165
NORMAL(400 CFM/TON) ON ON OFF OFF CFM
WATTS58359
61592
633127
621157
61818
HIGH(450 CFM/TON) ON ON ON OFF CFM
WATTS68170
697110
701140
709180
712215
2.0
LOW(350 CFM/TON) OFF ON OFF ON CFM
WATTS68075
726120
735150
741190
745230
NORMAL(400 CFM/TON) OFF ON OFF OFF CFM
WATTS769103
819145
843190
858235
865286
HIGH(450 CFM/TON) OFF ON ON OFF CFM
WATTS882130
938190
961245
975300
970345
2.5
LOW(350 CFM/TON) ON OFF OFF ON CFM
WATTS831180
903180
928230
935275
935320
NORMAL(400 CFM/TON) ON OFF OFF OFF CFM
WATTS979167
1036240
1053295
1053345
1015368
HIGH(450 CFM/TON) ON OFF ON OFF CFM
WATTS1121245
1147310
1176383
1167442
1055396
3.0**
LOW(350 CFM/TON) OFF OFF OFF ON CFM
WATTS1061210
1081265
1095320
1101382
1032380
NORMAL **(400 CFM/TON) OFF OFF OFF OFF CFM
WATTS1185278
1223364
1251435
1205455
1101426
HIGH(450 CFM/TON) OFF OFF ON OFF CFM
WATTS1351425
1372503
1343535
1248505
1168480
NOTES:1. * First Letter may be "A" or "T"2. ** Factory setting3. Continuous Fan Setting: Heating or Cooling airflow is approximately 50% of selected Cooling value.4. LOW 350 cfm/ton is recommended for Variable Speed application for COMFORT & HUMID CLIMATE setting; NORMAL is 400 cfm/ton; HIGH 450 cfm/ton is for DRY CLIMATE setting
14 DATA SUBJECT TO CHANGE WITHOUT NOTICE 22-1650-13
*UD2C100A9V5VB FURNACE HEATING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER
AIRFLOWSETTING
DIP SWITCH SETTING EXTERNAL STATIC PRESSURE
SW 7 SW 8 0.1 0.3 0.5 0.7 0.9
HEATING1ST
STAGE
LOW ON ONCFM
TEMP. RISEWATTS
90053100
89054130
87055175
85057220
83558270
MEDIUM ** ON OFFCFM
TEMP. RISEWATTS
112543150
109044200
106046235
107045300
107045340
HIGH OFF OFFCFM
TEMP. RISEWATTS
130037220
130037290
132036365
135036430
134036490
HEATING2ND
STAGE
LOW ON ONCFM
TEMP. RISEWATTS
127059200
129058260
129058335
129058400
128058460
MEDIUM ** ON OFFCFM
TEMP. RISEWATTS
157547355
160046445
161046520
160046575
158047650
HIGH OFF OFFCFM
TEMP. RISEWATTS
187040560
189039665
186040710
187040830
173043760
*UD2C100A9V5VB FURNACE COOLING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER
OUTDOORUNIT SIZE
(TONS)
AIRFLOWSETTING
DIP SWITCH SETTING EXTERNAL STATIC PRESSURE
SW 1 SW 2 SW 3 SW 4 0.1 0.3 0.5 0.7 0.9
3.0
LOW(350 CFM/TON) ON ON OFF ON CFM
WATTS1075135
1055185
1015220
1000265
990325
NORMAL(400 CFM/TON) ON ON OFF OFF CFM
WATTS1220185
1200240
1210295
1210350
1210410
HIGH(450 CFM/TON) ON ON ON OFF CFM
WATTS1390245
1390320
1410391
1410470
1400510
3.5
LOW(350 CFM/TON) OFF ON OFF ON CFM
WATTS1214185
1210240
1215295
1210350
1210415
NORMAL(400 CFM/TON) OFF ON OFF OFF CFM
WATTS1430310
1460355
1470430
1460500
1440555
HIGH(450 CFM/TON) OFF ON ON OFF CFM
WATTS1640370
1665460
1650540
1640615
1610660
4.0
LOW(350 CFM/TON) ON OFF OFF ON CFM
WATTS1405270
1430310
1440375
1440480
1420550
NORMAL(400 CFM/TON) ON OFF OFF OFF CFM
WATTS1670395
1675490
1670550
1655630
1630700
HIGH(450 CFM/TON) ON OFF ON OFF CFM
WATTS1870540
1880635
1880730
1845800
1670640
5.0 **
LOW(350 CFM/TON) OFF OFF OFF ON CFM
WATTS1775480
1800580
1820680
1800750
1680740
NORMAL **(400 CFM/TON) OFF OFF OFF OFF CFM
WATTS2065755
2020840
1945900
1805880
1623800
HIGH(450 CFM/TON) OFF OFF ON OFF CFM
WATTS23101000
21001000
2100950
1965890
1800825
NOTES:1. * First letter may be "A" or "T"2. ** Factory setting3. Continuous Fan Setting: Heating or Cooling airflow is approximately 50% of selected Cooling value.4. LOW 350 cfm/ton is recommended for Variable Speed application for COMFORT & HUMID CLIMATE setting; NORMAL is 400 cfm/ton; HIGH 450 cfm/ton is for DRY CLIMATE setting
22-1650-13 DATA SUBJECT TO CHANGE WITHOUT NOTICE 15
*UD2C100B9V5VB FURNACE HEATING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER
AIRFLOWSETTING
DIP SWITCH SETTING EXTERNAL STATIC PRESSURE
SW 7 SW 8 0.1 0.3 0.5 0.7 0.9
HEATING1ST
STAGE
LOW ON ONCFM
TEMP. RISEWATTS
9535093
94450146
93651193
90852243
88754292
MEDIUM ** ON OFFCFM
TEMP. RISEWATTS
114242135
114142200
113542255
111243322
109843377
HIGH OFF OFFCFM
TEMP. RISEWATTS
125838169
126038240
125638302
123638378
122739437
HEATING2ND
STAGE
LOW ON ONCFM
TEMP. RISEWATTS
131252188
131752261
131452326
129453406
128753468
MEDIUM ** ON OFFCFM
TEMP. RISEWATTS
157744301
159243387
159243468
159743563
158243644
HIGH OFF OFFCFM
TEMP. RISEWATTS
173939392
176139486
176239575
175339675
176239774
*UD2C100B9V5VB FURNACE COOLING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER
OUTDOORUNIT SIZE
(TONS)
AIRFLOWSETTING
DIP SWITCH SETTING EXTERNAL STATIC PRESSURE
SW 1 SW 2 SW 3 SW 4 0.1 0.3 0.5 0.7 0.9
3.0
LOW(350 CFM/TON) ON ON OFF ON CFM
WATTS1056114
1050173
1044225
1019284
1002336
NORMAL(400 CFM/TON) ON ON OFF OFF CFM
WATTS1199151
1199219
1194277
1172349
1161405
HIGH(450 CFM/TON) ON ON ON OFF CFM
WATTS1342198
1348273
1345340
1326422
1320486
3.5
LOW(350 CFM/TON) OFF ON OFF ON CFM
WATTS1223158
1224227
1219287
1198361
1187418
NORMAL(400 CFM/TON) OFF ON OFF OFF CFM
WATTS1389217
1397294
1395363
1377449
1373515
HIGH(450 CFM/TON) OFF ON ON OFF CFM
WATTS1556291
1570376
1570455
1556549
1559629
4.0
LOW(350 CFM/TON) ON OFF OFF ON CFM
WATTS1389217
1397294
1395363
1377449
1373515
NORMAL(400 CFM/TON) ON OFF OFF OFF CFM
WATTS1580303
1595389
1595469
1582565
1585647
HIGH(450 CFM/TON) ON OFF ON OFF CFM
WATTS1770411
1793507
1795598
1787698
1797801
5.0 **
LOW(350 CFM/TON) OFF OFF OFF ON CFM
WATTS1723382
1744475
1754564
1735663
1744760
NORMAL **(400 CFM/TON) OFF OFF OFF OFF CFM
WATTS1961546
1991652
1996751
1991850
2010981
HIGH(450 CFM/TON) OFF OFF ON OFF CFM
WATTS2199754
2217875
2217983
21971067
1987943
NOTES:1. * First letter may be "A" or "T"2. ** Factory setting3. Continuous Fan Setting: Heating or Cooling airflow is approximately 50% of selected Cooling value.4. LOW 350 cfm/ton is recommended for Variable Speed application for COMFORT & HUMID CLIMATE setting; NORMAL is 400 cfm/ton; HIGH 450 cfm/ton is for DRY CLIMATE setting
16 DATA SUBJECT TO CHANGE WITHOUT NOTICE 22-1650-13
*UD2D120A9V5VB FURNACE HEATING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER
AIRFLOWSETTING
DIP SWITCH SETTING EXTERNAL STATIC PRESSURE
SW7 SW8 0.1 0.3 0.5 0.7 0.9
HEATING1ST
STAGE
LOW ON ONCFM
TEMP. RISEWATTS
100757114
106254177
108453285
106354303
106354350
MEDIUM ** ON OFFCFM
TEMP. RISEWATTS
115450167
121148230
121148277
122147344
121248417
HIGH OFF OFFCFM
TEMP. RISEWATTS
128845208
131944273
131044330
134943410
135843460
HEATING2ND
STAGE
LOW ON ONCFM
TEMP. RISEWATTS
138764250
142163320
145561400
148860460
149559540
MEDIUM ** ON OFFCFM
TEMP. RISEWATTS
158956350
163754440
166653535
167853600
154158575
HIGH OFF OFFCFM
TEMP. RISEWATTS
177150475
178850560
180449650
175151675
155457590
*UD2D120A9V5VB FURNACE COOLING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER
OUTDOOR UNIT SIZE
(TONS)
AIRFLOWSETTING
(See Notes)
DIP SWITCH SETTING EXTERNAL STATIC PRESSURE
SW1 SW2 SW3 SW4 0.1 0.3 0.5 0.7 0.9
3.5
LOW(350 CFM/ TON) OFF ON OFF ON CFM
WATTS1195150
1243225
1235275
1251325
1251410
NORMAL(400 CFM/ TON) OFF ON OFF OFF CFM
WATTS1353210
1403290
1417370
1437425
1458485
HIGH(450 CFM/ TON) OFF ON ON OFF CFM
WATTS1554315
1572410
1615480
1634570
1567575
4
LOW(350 CFM/ TON) ON OFF OFF ON CFM
WATTS1356200
1391280
1399370
1433420
1454510
NORMAL(400 CFM/ TON) ON OFF OFF OFF CFM
WATTS1565320
1584410
1633475
1639560
1554575
HIGH(450 CFM/ TON) ON OFF ON OFF CFM
WATTS1766450
1799550
1810650
1784685
1590600
5 **
LOW(350 CFM/ TON) OFF OFF OFF ON CFM
WATTS1708420
1758530
1759585
1775675
1575585
NORMAL **(400 CFM/ TON) OFF OFF OFF OFF CFM
WATTS1994665
2018775
1971785
1814725
1618625
HIGH(450 CFM/ TON) OFF OFF ON OFF CFM
WATTS2247975
2152925
2019860
1861765
1693680
NOTES: "CONTINUOUS FAN SETTING" IS THERMOSTAT FAN SWITCH "ON" AND DIP SWITCHS 5 AND 6 "ON".1. *FIRST LETTER MAY BE "A" OR "T"2. **FACTORY SETTING.3. CONTINUOUS FAN SETTING: HEATING OR COOLING AIRFLOW IS APPROXIMATELY 50% OF SELECTED COOLING VALUE.4. LOW 350 CFM/TON IS RECOMMENDED FOR VARIABLE SPEED APPLICATION FOR COMFORT & HUMID CLIMATE SETTING: NORMAL IS 400 CFM/TON: HIGH 450 CFM/TON IS FOR DRY CLIMATE SETTING.
22-1650-13 DATA SUBJECT TO CHANGE WITHOUT NOTICE 17
*UD2D120B9V5VB FURNACE HEATING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER
AIRFLOWSETTING
DIP SWITCH SETTING EXTERNAL STATIC PRESSURE
S4-3 S4-4 0.1 0.3 0.5 0.7 0.9
HEATING1ST
STAGE
LOW ON ONCFM
TEMP. RISEWATTS
10504599
104446146
103546208
100547252
98048310
MEDIUM ** ON OFFCFM
TEMP. RISEWATTS
121439129
121639188
121739262
119240252
116941310
HIGH OFF OFFCFM
TEMP. RISEWATTS
128837147
129337212
129837293
127537309
125438373
HEATING2ND
STAGE
LOW ON ONCFM
TEMP. RISEWATTS
142948191
144048267
145347363
143548340
141648406
MEDIUM ** ON OFFCFM
TEMP. RISEWATTS
167241310
169540402
172240528
171140409
169740480
HIGH OFF OFFCFM
TEMP. RISEWATTS
178239385
180938480
189036623
183537565
187137644
*UD2D120B9V5VB FURNACE COOLING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER
OUTDOOR UNIT SIZE
(TONS)
AIRFLOWSETTING
(See Notes)
DIP SWITCH SETTING EXTERNAL STATIC PRESSURE
S3-1 S3-2 S3-3 S3-4 0.1 0.3 0.5 0.7 0.9
3.5
LOW(350 CFM/ TON) OFF ON OFF ON CFM
WATTS1208128
1209186
1210260
1185306
1162370
NORMAL(400 CFM/ TON) OFF ON OFF OFF CFM
WATTS1343162
1350232
1358318
1337365
1317433
HIGH(450 CFM/ TON) OFF ON ON OFF CFM
WATTS1477210
1491290
1507391
1490436
1472508
4.0
LOW(350 CFM/ TON) ON OFF OFF ON CFM
WATTS1343162
1350232
1358318
1337365
1317433
NORMAL(400 CFM/ TON) ON OFF OFF OFF CFM
WATTS1496218
1511300
1528403
1511447
1494520
HIGH(450 CFM/ TON) ON OFF ON OFF CFM
WATTS1650296
1671387
1698511
1686548
1671626
5.0 **
LOW(350 CFM/ TON) OFF OFF OFF ON CFM
WATTS1612274
1631363
1655482
1642521
1627598
NORMAL **(400 CFM/ TON) OFF OFF OFF OFF CFM
WATTS1858403
1902533
1907624
1906714
1871755
HIGH(450 CFM/ TON) OFF OFF ON OFF CFM
WATTS1871585
2126711
2110797
2098888
2001953
NOTES: "CONTINUOUS FAN SETTING" IS THERMOSTAT FAN SWITCH "ON" AND DIP SWITCHS 5 AND 6 "ON".1. *FIRST LETTER MAY BE "A" OR "T"2. **FACTORY SETTING.3. CONTINUOUS FAN SETTING: HEATING OR COOLING AIRFLOW IS APPROXIMATELY 50% OF SELECTED COOLING VALUE.4. LOW 350 CFM/TON IS RECOMMENDED FOR VARIABLE SPEED APPLICATION FOR COMFORT & HUMID CLIMATE SETTING: NORMAL IS 400 CFM/TON: HIGH 450 CFM/TON IS FOR DRY CLIMATE SETTING.
18 DATA SUBJECT TO CHANGE WITHOUT NOTICE 22-1650-13
*UD2D140A9V5VB FURNACE HEATING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER
AIRFLOWSETTING
DIP SWITCH SETTING EXTERNAL STATIC PRESSURE
SW 7 SW 8 0.1 0.3 0.5 0.7 0.9
HEATING1ST
STAGE
LOW ON ONCFM
TEMP. RISEWATTS
109062130
110061175
107063215
108062255
106063290
MEDIUM ** ON OFFCFM
TEMP. RISEWATTS
123055180
126553235
128053315
130052380
130052455
HIGH OFF OFFCFM
TEMP. RISEWATTS
138049235
140548290
142547375
143047415
145047520
HEATING2ND
STAGE
LOW ON ONCFM
TEMP. RISEWATTS
154567320
155067385
156067475
156067540
157566605
MEDIUM ** ON OFFCFM
TEMP. RISEWATTS
176059435
179058545
181058620
180058695
172560725
HIGH OFF OFFCFM
TEMP. RISEWATTS
200052615
201052715
200052790
195054820
180058775
*UD2D140A9V5VB FURNACE COOLING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER
OUTDOORUNIT SIZE
(TONS)
AIRFLOWSETTING
DIP SWITCH SETTING EXTERNAL STATIC PRESSURE
SW 1 SW 2 SW 3 SW 4 0.1 0.3 0.5 0.7 0.9
3.5
LOW(350 CFM/TON) OFF ON OFF ON CFM
WATTS1175165
1165200
1180265
1170320
1150400
NORMAL(400 CFM/TON) OFF ON OFF OFF CFM
WATTS1345225
1370285
1400360
1405440
1380490
HIGH(450 CFM/TON) OFF ON ON OFF CFM
WATTS1525295
1565390
1585470
1575515
1530585
4.0
LOW(350 CFM/TON) ON OFF OFF ON CFM
WATTS1320220
1330275
1335355
1300435
1240490
NORMAL(400 CFM/TON) ON OFF OFF OFF CFM
WATTS1550310
1580400
1590475
1555540
1460610
HIGH(450 CFM/TON) ON OFF ON OFF CFM
WATTS1735430
1735510
1710600
1670675
1590710
5.0 **
LOW(350 CFM/TON) OFF OFF OFF ON CFM
WATTS1700415
1725470
1730560
1725640
1690700
NORMAL **(400 CFM/TON) OFF OFF OFF OFF CFM
WATTS1980616
1980710
1950770
1885780
1735735
HIGH(450 CFM/TON) OFF OFF ON OFF CFM
WATTS2190835
2150870
2075890
1905800
1735735
NOTES:1. * First Letter may be "A" or "T"2. ** Factory setting3. Continuous Fan Setting: Heating or Cooling airflow is approximately 50% of selected Cooling value.4. LOW 350 cfm/ton is recommended for Variable Speed application for COMFORT & HUMID CLIMATE setting; NORMAL is 400 cfm/ton; HIGH 450 cfm/ton is for DRY CLIMATE setting
22-1650-13 DATA SUBJECT TO CHANGE WITHOUT NOTICE 19
PRODUCT DATA
WIRING DIAGRAM
From Dwg. D344249P02
20 DATA SUBJECT TO CHANGE WITHOUT NOTICE 22-1650-13
PRODUCT DATASCHEMATIC DIAGRAMS
From Dwg. D344249P02
22-1650-13 DATA SUBJECT TO CHANGE WITHOUT NOTICE 21
PRODUCT DATA
FIELD WIRING DIAGRAM FOR SINGLE STAGE HEATING ONLY
From Dwg. 21B341127 Rev. 0
From Dwg. 21B341126 Rev. 0
FIELD WIRING DIAGRAM FOR TWO STAGE HEATING
TO 115 V 1 PH.,60 HZ., POWERSUPPLY PERLOCAL CODESMMMMMM SSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEE
HUM SEENOTE 5
EASSSSSSSSSSSSSSSSS
C SEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEENOSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSEEEEESSSSSSSSSSSSSSSSSSSEEEEEETE 5EEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEE
TO 115 V 1 PH.,60 HZ., POMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMM SSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEWEREEEEEEEEEEEEEEEEEEEEEEEESUPPLMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMM SSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSY PERSSSSSSSSSSSSEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEELOCAL CODESTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEE 55555555555555555555555555555
HUM SEENOTE 5
EACCCCCCCCCCCCCCC SSSSSSSSSSSSC SEESSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEENO
TTTTTTEEEEEEEEEETE 5
EEE 555
22 DATA SUBJECT TO CHANGE WITHOUT NOTICE 22-1650-13
PRODUCT DATA
FIELD WIRING DIAGRAM FOR SINGLE STAGE HEATING WITH SINGLE STAGE COOLING (OUTDOOR SECTION WITHOUT TRANSFORMER)
From Dwg. 21B341125 Rev. 1
From Dwg. 21B341124 Rev. 1
FIELD WIRING DIAGRAM FOR TWO STAGE HEATING WITH SINGLE STAGE COOLING(OUTDOOR SECTION WITHOUT TRANSFORMER)
22-1650-13 DATA SUBJECT TO CHANGE WITHOUT NOTICE 23
PRODUCT DATA
FIELD WIRING DIAGRAM FOR TWO STAGE HEATING WITH TWO STAGE COOLING (OUTDOOR SECTION WITHOUT TRANSFORMER)
From Dwg. 21B341128 Rev. 0
TO 115 V 1 PH.,60 HZ., POESSSSSSSEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEE WERSUPPLEEEEEEEEEEEEEEEEEESSEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEY PERLOCAL CODES555555555555555555555555555
HUM SEEWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEERRRRRRREEEEEEERRRRRRRRREEEEERRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRR6RRRR6666R6RRRR6666R6RRRR6666NOWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWTE 5EEEEEEEEEEEEEEEERRRRRRRRR
EADDDDDDDDDDDDDEEEEEEEEEEC SEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEESSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSS LLLLLLLNOTE 5
24 DATA SUBJECT TO CHANGE WITHOUT NOTICE 22-1650-13
PRODUCT DATA
TU
D-9
V O
UT
LIN
E D
RA
WIN
G(A
LL D
IME
NS
ION
S A
RE
IN IN
CH
ES
)
From
Dw
g. C
3416
99
MO
DE
LA
BC
D
*UD
2B06
0A9V
3V**
*UD
2B08
0A9V
3V**
*UD
2B10
0A9V
3V**
17-1
/2"
9-5/
8"16
-1/4
"16
"
*UD
2C08
0A9V
4V**
*UD
2C10
0A9V
5V**
*UD
2C08
0B9V
4V**
*UD
2C10
0B9V
5V**
21"
13-1
/16"
19-3
/4"
19-1
/2"
*UD
2D12
0A9V
5V**
*UD
2D14
0A9V
5V**
*UD
2D12
0B9V
5V**
24-1
/2"
15-5
/16"
23-1
/4"
23"
*
- F
irst L
ette
r M
ay B
e "A
" or
"T
"
** -
Suf
fix L
ette
rs M
ay B
e "K
" (0
Thr
ough
9)
22-1650-13 DATA SUBJECT TO CHANGE WITHOUT NOTICE 25
Since the manufacturer has a policy of continuous product and product data improvement, it reserves the right to change the design and specifications without notice.
Technical Literature - Printed in U.S.A.
Trane6200 Troup HighwayTyler, TX 75707
PRODUCT DATA