+ All Categories
Transcript

LEK

INSTALLATION AND MAINTENANCE INSTRUCTIONS

FIGHTER 1120230 V, 3 X 230 V, 3 X 400 V

MOS GB 0642-2FIGHTER 1120031053

LEK LEK

LEK LEK

LE

K

LE

K

LE

K

LE

K

Contents 1

FIGHTER 1120

GeneralConcise product description ................................ 2Setting table ........................................................ 2

System descriptionPrinciple of operation .......................................... 3

Front panelLayout .................................................................. 4Explanation .......................................................... 4

SettingsGeneral ................................................................ 6Default setting ...................................................... 6Changing the room temperature .......................... 6Basic values for the automatic heating control .... 7Setting using diagrams .............................................. 8Heating curve offset -2 .............................................. 8Heating curve offset 0 ................................................ 8Heating curve offset +2 .............................................. 8Heat production .................................................... 9Hot water production ............................................ 9Additional heat only (electric boiler mode) ............ 9Brine pump .......................................................... 9Fixed condensing ................................................ 9Standby mode “ ” ............................................ 9

General points for the installation engineerTransport and storage ................................................ 10Installation .................................................................. 10Floating condensing .................................................. 10Fixed condensing ...................................................... 10Guideline values for collectors .................................. 10Inspection of the installation ...................................... 10

Pipe connectionsGeneral ...................................................................... 11Heating medium pump .............................................. 11Pipe connections (collector) ...................................... 11Pipe connections (heating medium) .......................... 11Ventilation recovery .................................................... 11Free cooling ................................................................ 11Pump capacity diagrams, heating medium side ........ 12Pump capacity diagrams, collector side .................... 13

Electrical connectionConnection ................................................................ 14Connection on delivery 230 V -5 ................................ 15Connection on delivery 230 V -8, -12 ........................ 15Connection on delivery 3 x 230 V .............................. 16Connection on delivery 3 x 400 V .............................. 17Tariff connection 3 x 400 V ........................................ 17Outside temperature sensor ...................................... 18Temperature sensor for hot tap water ...................... 18Temperature sensor with fixed condensing .............. 18External compensation .............................................. 18Max hot water temperature ........................................ 19Max. electrical addition .............................................. 19Max phase current including electrical addition,

binary 3 steps .......................................................... 19Centralised load control and load monitor ................ 20External contacts ........................................................ 21Alarm/alarm outputs .................................................. 22Soft-start relay ............................................................ 22

DockingGeneral ...................................................................... 23Abbreviations .............................................................. 23Option 1 immersion heater and water heater .......... 25Option 2 gas boiler .................................................... 26Option 3 oil-fired boiler .............................................. 28Option 4 another heat source .................................. 30

Commissioning and adjustingPreparations .............................................................. 32Filling and venting the collector system .................... 32Filling the heating medium system ............................ 32Internal air vent valve, brine ...................................... 32Starting and checking ................................................ 33Rotation check ............................................................34Readjusting, heating medium side ............................ 35Readjusting, collector side ........................................ 35

ControlGeneral........................................................................ 36Key lock ...................................................................... 36Quick movement ........................................................ 36Changing parameters ................................................ 37Menu tree .................................................................... 38Main menus ................................................................ 42Hot water temperature ................................................ 43Flow temperature ........................................................ 44Flow temperature system 2 ........................................ 46Outdoor temperature .................................................. 48Brine in/out temperature ............................................ 48Room temperature/Settings ...................................... 49Clock .......................................................................... 49Other settings ............................................................ 51

Service menusSettings additional heat .............................................. 53Operating settings ...................................................... 53Quick start .................................................................. 56TEST Force driven operation...................................... 56Alarm log .................................................................... 57

Dealing with malfunctionsAlarm indications on the display .............................. 58Low room temperature .............................................. 61High room temperature ............................................ 61Low hot water temperature or no hot water ............ 61Draining, heat medium side .................................... 62Draining, collector side .............................................. 62Helping the circulation pump to start ........................ 62

Component positionsComponent positions 230 V -5 .................................. 63Component positions 230 V -8, -12 ............................ 63Component positions 3 x 230 V ................................ 64Component positions 3 x 400 V ................................ 64Component positions ................................................ 65

List of componentsList of components .................................................... 66

DimensionsDimensions and setting-out coordinates .................. 65

Enclosed kitEnclosed kit ................................................................ 68

AccessoriesAccessories ................................................................ 69

Technical specificationsTechnical specifications 230 V .................................. 70Technical specifications 3 x 230 V ............................ 71Technical specifications 3 x 400 V ............................ 72

General

FIGHTER 1120

2In order to get the ultimate benefit from your heat pumpFIGHTER 1120 you should read through this Installationand Maintenance Instruction.

FIGHTER 1120 is a base heat pump for heating smallhouses, apartment blocks and industrial premises. Soil,rock or lakes can be used as the heat source.

FIGHTER 1120 is a Swedish made quality product offer-ing a long life span and safe operation.

Installation date

Accessories:Electrical addition ............ ■■Hot water control ............ ■■

Room control .................. ■■Other .............................. ■■

The serial number (95), should always be stated with allcorrespondence with NIBE._ _ _ _ _ _ _ _ _ _ _ _ _ _FIGHTER 1120- _ _

Installation engineers

Completed by the installation engineer when the heat pumpis installed

The type of brine - Mixing proportion/freezing point

Active drilling depth/collector length

Commissioning checksBrine temperature (in/out)____ / ____ Pump setting ___

(Nominal temperature diff 2 - 5 °C)

Temperature heat medium (supply/return)____ / ____ Pump setting ___(Nominal temperature diff 5 - 10 °C)

Settings

* Accessories

Date ________ Signed ____________________________

Menu Factorysetting

1.4 Start time.HW* ............ 47

1.5 Stop temp.HW* ............ 54

1.6 Stop Temp. XHW*............ 60

1.8 Interval XHW* .............. 14

2.1 Curve coefficient .......... 9

2.2 Heating curve offset. .... 0

2.3 Flow temp./MIN .............. 15

2.4 Flow temp./MAX.............. 55

2.7 Return temp./MAX .......... 53

Position Factorysetting

100 “Fuse” .............. 20

101 “Max electrical output”...... C

102 “Max boiler temp” ............ 65

FIGHTER 1120 consists of a heat pump, circulationpumps and a control system for the heat pump andany additional heat (an immersion heater is not includ-ed in the basic design). FIGHTER 1120 has built-in circulation pumps, makingit easy to connect to the heating medium and collectorcircuits.The absorption of heat from the heat source (rock,ground or lake) is through a closed collector systemcontaining water mixed with antifreeze.

Ground water can also be used as a heat source. Thisrequires an intermediate heat exchanger.The brine emits its heat to the refrigerant in the heatpump's evaporator. It then vaporises and is com-pressed in the compressor. The refrigerant, with itsincreased temperature, is led into the where it emitsits energy to the heat medium circuit.

System description 3

FIGHTER 1120

Principle of operation

Brine out

Compressor

Horizontal loop collector Vertical loop collector

Heating water pump

Condenser

Expansion valve

Brine in

Evaporator

Brine pump

Heating water flow

Heating water return

The installation must be fittedwith the necessary safetyequipment in accordance withthe applicable regulations.

Front panel4

A BI II III I II

5 0 . 0 CH o t w a t e r t e m p e r a t u r e

13.431.0

A

Display

Switch

Left keypad

Heating curve offset

Layout

A

B

C

D

Right keypad

E

Explanation

Switchwith three positions 1 - 0 - :1 Normal mode. All control functions connect-

ed. 0 The boilers is completely switched off.

Standby Only the circulation pump and pos-sibly the electrical addition. Not connectedat the factory

The switch must not be turned to “1” or “ ”before filling the boiler with water.

A

Display First row:

Compressor symbolIndicates when the compressor is opera-tional.

Addition symbolIndicates when the immersion heater isconnected. The line indicates which powerstep/steps are currently connected.

I Step 1 is connected.II Step 2 is connected.III Step 3 is connected.I II Steps 1+2 are connected.II III Steps 2+3 are connected.I III Steps 1+3 are connected.I II III Steps 1+2+3 are connected.

B

I II III

A

Hot water symbol.Tap is shown when the heat pump chargesthe hot water.A is shown when a temperature increase isin progress.B is shown when a time based temperatureincrease is in progress, for example, peri-odic.

Circulation pump symbol.I Shown when the circulation pump isoperational.II Shown when circulation pump 2 is oper-ational (the accessory ESV 20 is required).

Heating system symbolsShown when house heating is in progress.

A B

I II

FIGHTER 1120

Front panel 5

FIGHTER 1120

Left keypadC

Operating modeThis button is used to set the required op-erating mode with regard to permitting/blocking the circulation pump and addi-tional energy. The change does not needto be confirmed with the enter button.

The different operating modes are:Auto mode: FIGHTER 1120 automatically selects the operatingmode by taking the outdoor temperature into account.The circulation pump and the immersion heater arepermitted to run as needed.

Summer mode:Only production of hot water using FIGHTER 1120.The circulation pump and immersion heater areblocked. However, when “Extra hot water” is activatedthe immersion heater is connected.

Spring/Autumn mode:Production of heating and hot water using FIGHTER1120. The circulation pump is operational. The immer-sion heater is disabled. However, when “Extra hotwater” is activated the immersion heater is connected.

The current operating mode is shown on the displaywhen the button is pressed and the mode changeswhen you continue to press the button. The displayreturns to the normal display mode once the enter but-ton is pressed.

In alarm mode the operating mode changes to wintermode and additional heat engages.

Display (continued)Second row: Value of the current parameter.Third row: Description of current display para-

meter. “Hot water temp” is normal-ly shown.

Fourth row: Shows menu numbers, key lock,clock symbol and time

B

A key lock can be activated in the mainmenus by simultaneously pressing theplus and the minus buttons. The keysymbol will then be shown on the dis-play. The same procedure is used todeactivate the key lock.

The symbol becomes visible when atimer function is selected, for example,periodic lowering of the supply or timesetting for extra hot water.

Right keypad

Heating curve offsetD

E

Extra hot water (accessory)The “Extra hot water” function is activat-ed using this button. The change doesnot need to be confirmed with the enterbutton.

A: Means that the hot water temperature is increasedto 60 °C (adjustable). The temperature then returns tothe normal value.When A comes on the function is activated.When A goes out the function is deactivated.Press once to give extra hot water for 3 hours.Press twice to give extra hot water for 6 hours.Press three times to give extra hot water for 12 hours.Press four times to give extra hot water for 24 hours.Press five times to deactivate the function.

Plus buttonThis button is used to scroll through themenu system (forwards) or increase the value of the selected parameter.

See the section “Control - General”.

Minus buttonThis button is used to scroll through themenu system (backwards) or lower the value of the selected parameter.

See the section “Control - General”.

Enter buttonThis button is used to select a lowermenu in the menu system, to activate aparameter change as well as confirm aparameter change.

See the section “Control - General”.

This knob is used to change the heatingcurve's parallel offset and in doing sothe room temperature. Turning clock-wise increases the room temperature.When the knob is turned menu 2.0 isshown on the display and the value forthe calculated flow temperaturechanges.

No function.

Settings

FIGHTER 1120

6

GeneralThe indoor temperature depends on several factors.Sunlight and heat emissions from people and house-hold machines are normally sufficient to keep thehouse warm during the warmer parts of the year.When it gets colder outside, the heating system mustbe started. The colder it is outside, the warmer radia-tors and floor heating system must be. The heat pump is controlled by built-in sensors forflow and return brine temperatures (collector). Brinereturn temperatures can, if so required, be limited to aminimum (e.g. for ground water systems).Heat production is usually controlled on the “floatingcondensing” principle. This means that the tempera-ture level needed for heating at a given outside tem-perature is produced on the basis of values taken fromsensors for outside temperature and flow temperature(see docking options 1 - 3). This adjustment is madeautomatically, however the basic settings must first bemade on the boiler, see the section “Settings” -“Default setting”. Room sensors can also be used as an option to com-pensate for variations in room temperature, see menu6.1 “Room compensation”.

The basic heating is set using menu 2.1 and with the“Heating curve offset” knob.

If the required room temperature is not obtained, read-justment may be necessary.

NOTE! Wait one day between settings so that the tem-peratures have time to stabilise.

Readjustment of basic settings.

Cold weather conditionsWhen the room temperature is too low, the “Heatingcurve” value is increased in menu 2.1 by one incre-ment.

When the room temperature is too high, the “Heat-ing curve” value is decreased in menu 2.1 by oneincrement.

Warm weather conditionsIf the room temperature is low, increase the “Heat-ing curve offset” setting by one step.

If the room temperature is high, reduce the “Heatingcurve offset” setting by one step.

Default setting

Heating curve offset

Menu 2.1 Curve coefficient

9C u r v e c o e f f i c i e n t 2 . 1

Settings 7

FIGHTER 1120

Changing the room temperature manually.

If you want to temporarily or permanently lower orraise the indoor temperature relative to the previouslyset temperature, turn the “Heating curve offset” knobanticlockwise or clockwise. One scale marking corre-sponds to a change of about one degree in the roomtemperature.

NOTE! An increase in the room temperature may be“inhibited” by the radiator or floor heating thermostats,if so these must be turned up.

Changing the room temperature

A BI II III I II

5 0 . 0 CH o t w a t e r t e m p e r a t u r e

13.431.0

A

Heating curve offset

Settings8

FIGHTER 1120

The heating control system on the FIGHTER 1120 iscontrolled by the outside temperature. This means theflow temperature is regulated in relation to the currentoutdoor temperature.The relationship between the outside temperature andthe flow temperature is set using the control system,also see section “Heating control system - Basic set-ting”.The diagram is based on the dimensioned outdoortemperature in the area and the dimensioned supplytemperature of the heating system. When these twovalues “meet”, the heating control's curve slope canbe read. This is set on menu 2.1 “Curve coefficient”.

Heating curve offset 0

Heating curve offset -2Setting using diagrams

Heating curve offset +2

15 14 13 12 11 10

9

8

7

6

5

4

3

2

1

- 40 °C

UTETEMPERATUR

- 10010

- 5

+ 5

30

40

50

60

70°C

FR

AM

LED

NIN

GS

TE

MP

ER

AT

UR

- 20 - 30

FÖRSKJUTNINGVÄRMEKURVA (-2)

VÄRMEKURVA

30

40

50

60

70°C

FR

AM

LED

NIN

GS

TE

MP

ER

AT

UR

- 40 °C

UTETEMPERATUR

- 10010 - 20 - 30

15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

VÄRMEKURVA

- 5

+ 5

FÖRSKJUTNINGVÄRMEKURVA (0)

1514 13 12 11 108

7

6

5

4

3

2

1

- 40 °C

UTETEMPERATUR

- 10010

- 5

+ 5

30

40

50

60

70°C

FR

AM

LED

NIN

GS

TE

MP

ER

AT

UR

- 20 - 30

FÖRSKJUTNINGVÄRMEKURVA (+2)

9

VÄRMEKURVA

A BI II III I II

5 0 . 0 CH o t w a t e r t e m p e r a t u r e

13.431.0

A

Heating curve offset

Menu 2.1 Curve coefficient

9C u r v e c o e f f i c i e n t2 . 1

The “Heating curve offset” knob is then set. A suitablevalue for floor heating is -1 and for radiator systems -2.

HEATING CURVE

HEATING CURVEOFFSET

SUPP

LY T

EMPE

RA

TUR

E

OUTSIDE TEMPERATURE

HEATING CURVE

HEATING CURVEOFFSET

SUPP

LY T

EMPE

RA

TUR

E

OUTSIDE TEMPERATURE

HEATING CURVE

HEATING CURVEOFFSET

SUPP

LY T

EMPE

RA

TUR

E

OUTSIDE TEMPERATURE

Settings 9

FIGHTER 1120

If the FIGHTER 1120 is fitted with the accessory ETS12 / ETS 121 the unit can be used solely as additionalheat (electric boiler) to produce heat and hot water.This is especially useful, for example, before the col-lector installation is finished. Changing the “Electric boiler” is done in menu 9.2.4.NOTE! Select “Off” to deactivate only additionalheat and select the required operating mode usingthe operating mode button.

The brine pump normally follows the operation of theheat pump. There is a special operating mode for con-tinuous operation for 10 days, followed by return tonormal mode (used before stable circulation has beenestablished).The setting is made on menu 9.2.12 “Brinepump 10days”.

If required FIGHTER 1120 can be docked to an exter-nal unit with its own heating controls. FIGHTER 1120then delivers heat up to a fixed temperature level. Thisis known as “fixed condensing”. To regulate the room temperature, see the instructions for the externalunits.

Not connected from the factory, requires the accesso-ry ETS 12 / ETS 121.

FIGHTER 1120 can be complemented with “Domestichot water operation” and, for example, our VPA hotwater accumulator to produce domestic hot water.

The supply of heat to the building is controlled by thecontrol system settings (curve slope and offset). Afteradjustment the correct amount of heat for the currentoutdoor temperature is supplied. The flow line temper-ature of the heat pump (heating medium flow) will huntaround the theoretically required value (the value inbrackets on the display). For subnormal temperaturesthe control system calculates a heating deficit in theform of “degree-minutes”, which means that heatingproduction is accelerated. The larger the subnormaltemperature, the greater the heat production.The heat pump's control system can control an immer-sion heater in a maximum of seven output steps if fit-ted, or an external oil-fired boiler and shunt valve.

Heat production Hot water production

Additional heat only (electricboiler mode)

Brine pump

Fixed condensing

Standby mode

General information for the installer10

FIGHTER 1120

Current regulations require the heating installation tobe inspected before it is commissioned. The inspec-tion must be carried out by a suitably qualified personand should be documented. The above applies toclosed heating systems. If the heat pump is replaced,the installation must be inspected again.

FIGHTER 1120 is placed on a firm base, preferably aconcrete floor or foundation. FIGHTER 1120 shouldbe setup with its rear against an outer wall in ascullery or similar type of room to eliminate noiseproblems. If this is not possible, avoid placing itagainst a wall behind a bedroom or other room wherenoise may be a problem. Wherever the unit is located,any wall that backs on to a bedroom should be fittedwith sound insulation. Route pipes so they are notfixed to an internal wall that backs on to a bedroom orliving room.

The FIGHTER 1120 must be transported and storedupright and dry.

Transport and storage

Installation

Guideline values for collectors

Inspection of the installation

For use with 40 x 2.4 PN 6.3 PEM hose.

The length of the collector hose varies dependingon the rock /soil conditions and on the heating sys-tem, i.e. radiators or floor heating.Max length per collector should not exceed 400 m.

Where there is more than one collector, they must beconnected in parallel, with a means of adjusting theflow.

The hose should be buried at a depth of about1 metre and the distance between the hoses shouldbe at least 1 metres for surface soil heat.

For several bore holes, the distance between theholes must be at least 15m.

If required FIGHTER 1120 can be docked to an exter-nal unit with its own heating controls. FIGHTER 1120then delivers heat up to a fixed temperature level. Thisis called “fixed condensing”. See docking option 4. Toset the correct parameters for fixed condensing see“Docking - option 4”. The heat medium pump does notneed to be changed.See the instructions for the external units for how toregulate the room temperature.The outside temperature sensor has no function withthis option, but it should be connected to prevent errormessages appearing on the display. There is no needto install the sensor outside.

Heat production is usually controlled on the “floatingcondensing” principle. This means that the tempera-ture level needed for heating at a given outside tem-perature is produced on the basis of values taken fromsensors for outside temperature and flow temperature(see docking options 1 - 3).

Fixed condensing

Floating condensing

NOTE! Enter the selected values on page 2 in this Installation instruction. The

details are important for service work.

+ 20-2

1

R

0

H M flo w4 9 (5 0 ) °CH o t w a te r 5 1 °C

+20

-2

1 R0

HM

flow 4

9 (5

0)

°CH

ot w

ater

51 °C

Type Soil heat Rock heat,recommended recommendedcollector length active drilling depth

6 250 - 400 m 90 - 110 m

10 400 - 2 x 300 m 140 - 170 m

15 2 x 300 - 2 x 400 m 2 x 100 - 2 x 120 m

8 325 - 2 x 250 m 120 - 140 m

17 2 x 350 - 3 x 300 m 2 x 110 - 2 x 140 m

12 2 x 250 - 2 x 350 m 160 - 190 m

5 200 - 300 m 70 - 90 m

When dimensioning the collector, consideration mustbe given to the geographical location, type of rock andground and the degree of coverage provided by theheat pump. When installing the collector hose ensure it rises con-stantly towards the heat pump to avoid air pockets. Ifthis is not possible, install high points to vent the air.All brine pipes in heated rooms must be insulatedagainst condensation. The level vessel (NK) must beinstalled as the highest point in the collector system andon the incoming pipe before the brine pump. Note thatcondensation may drip from the level vessel. Positionthe vessel so that this does not harm other equipment.As the temperature of the collector system can fallbelow 0 °C it must be protected against freezing downto -15 °C. One litre of ready mixed brine per meter ofcollector hose (applies when using PEM-hose 40 x 2.4PN 6.3) is used as a guide value when making the vol-ume calculation. The level vessel must be marked to show the type ofantifreeze used.Shut-off valves should be installed as close to the heatpump as possible. Fit a particle filter to the incoming pipe.In the case of connection to an open groundwater sys-tem, an intermediate frost-protected circuit must beprovided, because of the risk of dirt and freezing in theevaporator. This requires an extra heat exchanger.

Pipe connections 11

FIGHTER 1120

Pipe installation must be carried out in accordancewith current norms and directives. FIGHTER 1120 canoperate up to a return temperature of about 58* °Cand an outgoing temperature from the heat pump ofabout 70* °C. The compressor produces up to 65* °C,the rest is obtained using additional heating.* Applies to 5 kW 1-phase, 6 kW 3-phase 3 x 400 V, 8

kW 3-phase 3 x 400 V and 10 kW 3-phase 3 x 400 V.The other heat pumps has a max return temperatureof approximately 50 °C and an outgoing max tempera-ture from the heat pump of approximately 60 °C.Since FIGHTER 1120 is not fitted with shut-off valves,these must be fitted outside of the heat pump to facili-tate servicing.

General

Pipe connections (collector)

The heating medium pump (VBP) runs at the sametime as the brine pump (KBP) with fixed condensing(docking option 4) in auto mode.

Heating medium pump

NOTE!The pipe system needs to be flushed

out before the heat pump is connectedso that debris cannot damage

component parts.

Pipe connections for the heat medium side are madeat the top. All required safety devices, shut-off valves(as close to the heat pump as possible), and particlefilter (supplied) are fitted.You should fit either an overflow valve or removesome of the thermostats when connecting to systemswith thermostats on all the radiators (coils).

Pipe connections (heating medium)

FIGHTER 1120

SF

Köldb in

Köldb ut

SÄV

FLM 30

EXP

BV

RV P

A BI II III I II I II

5 0 . 0 CVa r m v a t t e n t e m p . 1 . 0

A B A B

The equipment can be supplemented with a fan coilunit to make the connection of free cooling possible.Toavoid condensation, all pipes and other cold surfacesmust be isolated with diffusion-proof material.Wherethe cooling demand is high, fan convectors with driptrays and drain connection are needed. The collectorcircuit should be fitted with a pressure expansion ves-sel. If there is a level vessel, this should be replaced.

Free cooling

P

A BI II III I II I II

5 0 . 0 CVa r m v a t t e n t e m p . 1 . 0

A B A B

Fläktkonvektor

Köldb inKöldb ut

Brine in

Brine out

Brine inBrine out

Fan convectors

The installation can be supplemented with the exhaustair module FLM to provide ventilation recovery. Toavoid condensation, all pipes and other cold surfacesmust be isolated with diffusion-proof material. The col-lector circuit should be fitted with a pressure expan-sion vessel. If there is a level vessel, this should bereplaced.

Ventilation recovery

Extract airØ 160

Exhaust airØ 160

0,2 0,4 0,6 0,8 1,0 1,20

Flöde

l/s0

10

20

30

40

50

60

70

80

90

1 2 3

kPaTillgängligt tryck

0,2 0,4 0,6 0,8 1,0 1,20

Flöde

l/s0

10

20

30

40

50

60

70

80

90

1 2 3

kPaTillgängligt tryck

Pipe connections

FIGHTER 1120

12

Pump capacity diagrams, heating medium side

LE

K

GR

UN

DF

OS

Typ

eU

PS

25

- 6

013

0P

/N:5

952

64

47

23

0V

-

HE

JS

AN

PC

;001

7N

IBD

K50

Hz

IP 44

TF

1

10

Cla

ss

HM

ax. 1

0ba

r

2.5

uF

45

0.2

06

50

.30

90

0.4

0

1m(A

)P,

(W)

The pump isadjustable to adjustthe flow: 1, 2, or 3 .

kPa

0

20

80

40

Tillgängligt tryck

Flöde

60

kPa

0

20

80

40

Tillgängligt tryck

Flöde

60

kPa

0

20

80

40

Tillgängligt tryck

Flöde

60

kPa

0

20

80

40

Tillgängligt tryck

Flöde

60

FIGHTER 1115 4

FIGHTER 1115 7 FIGHTER 1115 8,5

FIGHTER 1115 5

0 0,07 0,13 0,21 l/s 0,27 0,35 0,42 0,48 0,69 0,62 0,55 0 0,07 0,13 0,21 l/s 0,27 0,35 0,42 0,48 0,69 0,62 0,55

0 0,07 0,13 0,21 l/s 0,27 0,35 0,42 0,48 0,69 0,62 0,55 0 0,07 0,13 0,21 l/s 0,27 0,35 0,42 0,48 0,69 0,62 0,55

1 2 3 1 2 3

1 2 3 1 2 3

FIGHTER 1120 12

FIGHTER 1120 6FIGHTER 1120 5

FIGHTER 1120 8 FIGHTER 1120 10

FIGHTER 1120 15/17

Availablepressure

Availablepressure

Availablepressure

Availablepressure

Availablepressure

Flow Flow

Flow

Availablepressure

Flow

Flow Flow

Flöde0 0,1 0,2 0,3 l/s0,4 0,5 0,6 0,7 10,90,8

kPa

30

40

110

70

Tillgängligt tryck

90

50

60

80

100

12

34

Pipe connections 13

FIGHTER 1120

Pump capacity diagrams, collector side

FIGHTER 1215 7 kPa

0

10

80

40

Tillgängligt tryck

Flöde

60

0 0,1 0,2 0,3 l/s 0,4 0,5 0,6 0,7 1 0,9 0,8

1 2 3 20

30

50

70

FIGHTER 1215 4 kPa

0

10

80

40

Tillgängligt tryck

Flöde

60

0 0,1 0,2 0,3 l/s 0,4 0,5 0,6 0,7 1 0,9 0,8

1 2 3

20

30

50

70

FIGHTER 1215 8,5 kPa

0

10

80

40

Tillgängligt tryck

Flöde

60

0 0,1 0,2 0,3 l/s 0,4 0,5 0,6 0,7 1 0,9 0,8

1 2 3 20

30

50

70

FIGHTER 1120 6FIGHTER 1120 5

FIGHTER 1120 8 FIGHTER 1130/1230 10 kPa

0

10

80

40

Tillgängligt tryck

Flöde

60

0 0,1 0,2 0,3 l/s 0,4 0,5 0,6 0,7 1 0,9 0,8

1 2 3

20

30

50

70

FIGHTER 1120 10

FIGHTER 1120 12/15/17

LE

K

GR

UN

DF

OS

Typ

eU

PS

25

- 6

013

0P

/N:5

952

64

47

23

0V

-

HE

JS

AN

PC

;001

7N

IBD

K50

Hz

IP 44

TF

1

10

Cla

ss

HM

ax. 1

0ba

r

2.5

uF

45

0.2

06

50

.30

90

0.4

0

1m(A

)P,

(W)

The pump is adjust-able to adjust theflow: 1, 2, or 3 (4).

Availablepressure

Availablepressure

Availablepressure

Availablepressure

Availablepressure

FlowFlow

FlowFlow

Flow

NOTE! Electrical installation and service

must be carried out under thesupervision of a qualified electrician.

Electrical installation and wiring mustbe carried out in accordance with the

stipulations in force.

Electrical connection14

FIGHTER 1120

Cable glands forthe supply.

Cable glands forsensors.

FIGHTER 1120 must not be connected without thepermission of the electricity supplier and must be con-nected under the supervision of a qualified electrician.

FIGHTER 1120 must be installed via an isolatorswitch with a minimum breaking gap of 3 mm. Otherelectrical equipment, except the outdoor temperaturesensor and the current transformers are ready con-nected at the factory.

Disconnect the heat pump before insulation testingthe house wiring.

The heat pump is not reconnectable between 1-phaseand 3-phase; neither can it be reconnected between 3x 230 V and 3 x 400 V.

If a miniature circuit breaker is used this should havemotor characteristic “D” (compressor operation). Forfuse ratings, see technical data, “Fuse” protection.

When the building is equipped with an earth-faultbreaker the heat pump should be equipped with aseparate one.

Check that motor protection (26) is set to “auto-mode”and that the operating current has been set correctly,see technical specifications, “Max. operating current,compressor”.

The automatic heating control system, circulationpumps and their wiring, are internally fuse protectedwith a miniature circuit breaker (1).

Connection

-X9

26

Electrical connection 15

FIGHTER 1120

L N PE

L

L

N

N

PE

PE

Connection on delivery 230 V -5

-X9

230 V: The heat pump is connected on terminal block-X9 to 230 V + PE via the junction box with fuses.

When a separate supply to the compressor and immer-sion heater is required, to give them separate tariff con-trol, the following should be done: ■ Remove the cable (the dotted line) between the

terminal block -X9 and the compressor contactor(69). Connect the supply directly to the contactoraccording to the picture.

Tariff connection 230 V -5

69 compressor immersionheater

-X9

Electrical connection

FIGHTER 1120

16

PEL1 L2 L3

Connection on delivery 3 x 230 V (only applies to Norway)

-X9

3 x 230 V: The heat pump is connected on terminalblock -X9 to 3 x 230 V + PE via the junction box withfuses.

L N PE

Connection on delivery 230 V -8, -12

-X9230 V: The heat pump is connected on terminal block-X9 to 230 V + PE via the junction box with fuses.

L

L

N

N

PE

PE

When a separate supply to the compressor and immer-sion heater is required, to give them separate tariff con-trol, the following should be done: ■ Remove the cable (the dotted line) between the

terminal block -X9 and the compressor contactor(69). Connect the supply directly to the contactoraccording to the picture.

Tariff connection 230 V -8, -12

69

-X9

compressorimmersion

heater

L1 L2 L3

60Line

Load

L

L1 L2 L3

N O

-X9

PENL1 L2 L3

PEL1 L2 L3

Electrical connection 17

FIGHTER 1120

PENL1 L2 L3

When a separate supply to the compressor, immersionheater and the control system is required, to give themseparate tariff control, the following should be done: ■ Remove the 3 cables between terminal block -X9

and the EMC filter (60). Connect the supply directlyto the EMC filter.

■ Remove the 2 orange straps on terminal block -X9and connect the control voltage to the outermostterminals marked L and N on the wiring diagram.

Tariff connection 3 x 400 V + N + PE

Separate supplyadditional heat

Separate supplycontrol system

Separate supplycompressor

-X9

-X9

Connection on delivery 3 x 400 V + N + PEThe heat pump is connected on terminal block -X9 to3 x 400 V + N + PE via the junction box with fuses.

compressor

immersionheater

60

Separate supplycontrol system

Phase sequence monitor FIGHTER 1120- 15, 17 3x400V■ Orange LED is lit at correct phase

sequence.■ Green LED is lit when there is power.

164

Electrical connection

FIGHTER 1120

18

In this connection option the edge board connector forthe flow line sensor (FG) and return sensor (RG)should be disconnected.The flow temperature sensor (FG) is placed in thesubmerged tube on the accumulator tank and con-nected to the screw terminals X4:15—16.The existing return sensor (RG) is disconnected fromthe edge board connector and is connected toX4:13–14. See docking options 4.

Temperature sensor withfixed condensing

The supplied sensor is connected using a two-wirecable to terminal positions X4:11 and X4:12 on theEBV card (2). The sensor is placed in a submergedtube on the accumulator tank, e.g. VPA.

Temperature sensor for hot tap water

The outside temperature sensor (15) must be installedin a shaded location on a wall facing north or north-west, where it will not be affected by any morning sun.The sensor is connected to terminals X1:1 and X1:2on the EBV-card (2). Use a two-wire cable of at least0.5 mm2.If the outside temperature sensor cable runs close topower cables, screened cable should be used. Allconduits should be sealed to avoid condensation inthe outdoor temperature sensor capsule.

Outside temperature sensor

Connecting an external contact, for example, a roomthermostat (accessory) or a timer allows you to tem-porarily or periodically raise or lower the flow tempera-ture and with that the room temperature. Connected toterminals X1:3 and X1:4 on the EBV-card (2). SeeMenu 2.5 for settings.

External compensation

X1

X4

X4

2

X4

Flow line sensor (FG)

Hot water, jacket

Outside temperature sensor

External compensation 1

Return sensor (RG)

Electrical connection 19

FIGHTER 1120

The setting of the different maximum hot water tem-peratures is done using the knob (102) on the loadmonitor card (2). The setting can be checked in themenu 9.2.1.

The setting of the different max outputs is done usingthe knob (101) on the load monitor card (2). The set-ting can be checked in the menu 8.3.5.

The immersion heater is set in the menu 9.2.13.2.Possible settings are: “Binary 3 steps”, “Linear 3steps”, “Binary 7 steps” and “Off”.

“Binary 3 steps” should be selected when ETS12/ETS 121 is connected.

65 C*

75 E

50 A

Boiler temperature Knob position

55 B

70 D

80 F

101

102

2

Max. electrical addition

2 C

5 E

0 A

No. of steps Knob position

1 B

3 D

7 F

Max phase current including electrical addition, binary 3 steps

Max hot water temperature

*Factory setting.

9 6 C* 13,6 15,5 16,7 18,6 21,7 23,4

9 0 A 4,9 6,8 8,0 10 13,1 14,8

Max electrical Immersion heater, Knob Max phase (A) Max phase (A) Max phase (A) Max phase (A) Max phase (A) Max phase (A)

output output (kW) position Type 6 Type 8 Type 10 Type 12 Type 15 Type 17

9 3 B 9,2 11,1 12,3 14,3 17,4 19,1

9 9 D 17,9 19,8 21,0 22,9 26,0 27,7

6 4 C* 26,7 34,0 40,9

6 0 A 9,0 16,3 23,5

Max electrical Immersion heater, Knob position Max. phase (A) Max phase (A) Max phase (A)output output (kW) Type 5 Type 8 Type 12

6 2 B 18,0 25,3 32,2

6 6 D 35,4 42,7 49,6

3 x 230 V for FIGHTER 1120 with ETS 12

3 x 400 V for FIGHTER 1120 with ETS 12

6 4 C* 27,3 29,3 31,3 34,9 37,9 41,9

6 0 A 12,3 14,3 16,3 19,9 22,9 26,9

Max electrical Immersion heater, Knob Max phase (A) Max phase (A) Max phase (A) Max phase (A) Max phase (A) Max phase (A)output output (kW) position Type 6 Type 8 Type 10 Type 12 Type 15 Type 17

6 2 B 19,8 21,8 23,8 27,4 30,4 34,4

6 6 D 31,3 33,3 35,3 38,9 41,9 45,9

230 V for FIGHTER 1120 with ETS 121

LPEN 1 L2 L3

Electrical connection

FIGHTER 1120

20

Centralised load control/TariffIn those cases centralised load control or tariff controlis used this can be connected to the terminal block X1on the load monitor card (2), which is positionedbehind the upper service cover.

Tariff A, the whole electrical output is disconnected.Connect a potential free contact function to terminalsX1:5 and X1:7.

Tariff B, the compressor is disconnected. Connect apotential free contact function to terminals X1:6 andX1:7.

Tariff A and Tariff B can be combined.

A made contact results in the electrical output beingdisconnected.

Load monitorNOTE! No function in a 1-phase installation.When many power consumers are connected in theproperty at the same time as the immersion heater isoperating, there is a risk of the property's main fusetripping. The heat pump is equipped with an integrat-ed load monitor that controls the electrical steps onthe immersion heater.

When the phase current is so high that there is a riskof the main fuses tripping, the load monitor reducesthe immersion heater output until the risk of the mainfuses tripping has passed. When the general powerconsumption drops, the immersion heater will be con-nected again.

A current transformer should be installed on eachincoming phase conductor in to the distribution box tomeasure the current. The distribution box is an appro-priate installation point.

Connect the current transformers to a multi-corecable in an enclosure next to the distribution box. Useunscreened multi-core cable of at least 0.50 mm2,from the enclosure to the heat pump.

The cable is connected in the heat pump to the EBV-card on terminals X1:8 - X1:11. X1:11 is the commonterminal block for the three current transformers.

The size of the property's main fuse is set using theknob (100) on the EBV-card. The setting can bechecked in the menu 8.3.4.

Centralised load control and load monitor

2

100

X1

Electricaldistribution unit

To heat pump

Incoming electricity

Pressure/level sw

itchbrine

External com

pensation 2

Pool tem

perature

Current transform

er L3

Current transform

er L2

Current transform

er L1

External com

pensation 1

Outdoor tem

perature sensor

Tariff B

Tariff A

Electrical connection 21

FIGHTER 1120

RG 10, sensor for changing the room temp.An external sensor can be connected to FIGHTER 1120to change the flow temperature and with that set theroom temperature, for example, a room sensor (RG 10,accessory). The sensor is connected on terminals X1:3,X1:4 and X1:14 on the load monitor card (2).The difference between the room temperature and theset room temperature affects the flow temperature.The required room temperature is set using the knobon RG 10 and is shown in menu 6.0.

Contact for changing the room temperatureAn external contact function can be connected toFIGHTER 1120 to change the flow temperature and indoing so change the room temperature, for example, aroom thermostat (accessory) or a timer. The contactorshould be potential free and momentary and is con-nected to terminals X1:3 and X1:4 on the load monitorcard (2).When the contact is made, the heating curve offset ischanged by the number of steps shown here. Thevalue is adjustable between -10 and +10. The value forthe change is set on menu 2.5, “Compensation exter-nal”.

Contact for activation of “Extra hot water”An external contact function can be connected to FIGHT-ER 1120 for activation of the “Temporary extra hot water”function. The contactor should be potential free andmomentary and is connected to terminals X4:3 and X4:4on the load monitor card (2).When the contact makes for at least one second, the“Temporary Extra hot water” function is activated. Anautomatic return to the previously set function occursafter 24 hours.

NV 10, Pressure/level monitor brine When a level monitor NV 10 (accessory) is required forthe brine installation, this can be connected to termi-nals X1:16 and X1:17. In order for this to be active youmust change menu 9.2.11, brine pressostat, to “On”.The contact shall be made during normal operating conditions.

External contacts

2

X1

X4

Pressure/level sw

itchbrine

External com

pensation 2

Pool tem

perature

Current transform

er L3

Current transform

er L2

Current transform

er L1

External com

pensation 1

Outdoor tem

perature sensor

Tariff B

Tariff A

Extra H

ot Water

Boiler sensor

Return sensor 1

Flow

sensor 1

Flow

sensor 2

Return sensor 2

Hot w

ater, jacket

Electrical connection

FIGHTER 1120

22

AlarmA common alarm is given in the following instances:High pressure switch (HP) has tripped. Indicated asHP-alarm. LP pressure switch (LP) has tripped. Indicated as anLP alarm. The motor cut-out (MP) has tripped, indicated by anMP-alarm. Pressure/level monitor brine (accessory) indicated aspressure/level brine. Brine temp. low, indicates a low brine temperature. Notindicated when menu 5.2 is set to automatic return“On”. Flow sensor fault is indicated by a Sensor alarm. Hot water sensor fault is indicated by a Sensor alarm.External indication of common alarms is possiblethrough the relay function on the load monitor card (2), terminals X2:1—3. The picture shows the relay in the alarm position.

When switch (8) is in the “0” or “ ” position therelay is in the alarm position.

Alarm/alarm outputs

X2

X2

2

Alarm output,common alarm

FIGHTER 1120 is equipped with a soft-start relay (97),which limits the inrush current, see section “Technicalspecifications”.The compressor must not be forced to start with peri-ods shorter that 1 start per 15 minutes.

Soft-start relay*

* Applies to 3 x 400 V and 1 x 230 V 8 and 12

Docking 23

FIGHTER 1120

AV Shut-off valveBK/JK Rock collector/Soil collector

BV Non-return valveELK Immersion heater Included with the accessory ETS 12/ETS 121

El VVB Electrical hot water heaterNK Level vessel Included with FIGHTER 1120SF Particle filter Included with FIGHTER 1120

SÄV Safety valvePG Boiler temperature sensor Included with FIGHTER 1120FG Flow sensor Included with FIGHTER 1120

VVG Hot water temperature sensor (88) Included with FIGHTER 1120UG Outdoor temperature sensor Included with FIGHTER 1120RG Return temperature sensor Included with FIGHTER 1120

VVB/ACK Accumulator with water heater e.g. VPAVXV Shuttle valve Accessory in VST 11

SV Shunt valve Motor shunt (230V)

Abbreviations

FIGHTER 1120 can be installed in several differentways, some of which are described below.Accessories such as equipment for controlling hotwater VST 11 and additional heat ETS 12/ETS 121,etc. are ordered separately. The safety equipmentmust be installed in accordance with current regula-tions for all docking options.

General

Option 1 - FIGHTER 1120 docked with immersion heater and hot water heater (floating condensing)

Principle of operationFIGHTER 1120 prioritises hot water charging via ashuttle valve (VXV). When the water heater/accumula-tor tank (VVB/ACK) is fully charged the shuttle valve(VXV) switches over to the heating circuit. The heatpump is then controlled by the outside temperaturesensor (UG) in combination with the built-in flow sen-sor (FG). The immersion heater (ELK) is connectedautomatically when the energy requirement exceedsthe capacity of the heat pump. This option requires the accessories ETS 12/ETS 121and VST 11.

Menu optionThis option requires the following selections to bemade in:■ Select “Service” in menu 8.1.1.■ Menu 9.2.13.1 “Docking type”, select alt “1”.■ Menu 9.2.13.3 “Hot water”, select “On”.■ Menu 9.2.13.2 “Immersion heat” type, select the

type of immersion heater installation here.Binary 3 step: Selected when the accessory ETS12/ETS 121 is connectedOff: PreselectedNOTE! These selections are confirmed by switchingthe heat pump off and on.

■ Check the max. output setting on knob (101), seesection “Electrical connection - Max electrical addi-tion”.

The “Auto” operating mode should beselected in order for the electrical addi-tion to be permitted to start.

Docking

FIGHTER 1120

24

SÄV

SF AV

AV

VXV

VVGVVB / ACK UG

ELVVB

SÄV

NK

AV

AV

SF

EXP

AV

AV

AV

BK / JK

ELK

FG

T

AB

AB

Docking 25

FIGHTER 1120

Option 1 - FIGHTER 1120 docked with immersion heater and hot water heater (floating condensing)

* Accessories. The figures show how the connectionshould appear when completed. For full informationabout the connections see respective “Installationinstructions”.

X4

X4 X1 -X6

Connection ETS 12/ETS 121*See the assembly instructions for ETS 12/ETS 121.

Connection of the outside temperaturesensor

Connection of hot water sensor

Connection VST 11*

Outside temperaturesensor (UG)

Shuttle valve

Hot water, jacket (VVG)

Docking

FIGHTER 1120

26

Principle of operationFIGHTER 1120 prioritises charging the hot waterheater (VVB/ACK). When the preset hot water tem-perature is reached, the shuttle valve switches toheating. If the heat pump cannot maintain the rightflow temperature the gas boiler starts. The flow linesensor (FG) should be placed on the main pipe to theradiators.This alternative requires the accessory VST 11.The “Auto” operating mode should be selected inorder for the gas addition to be permitted to startThe immersion heater in the water heater is connect-ed when “Extra Hot Water” is activated.When standby mode is activated, the heating mediumpump will be on and the gas burner receives the sig-nal. The thermostat on the gas boiler limits the tem-perature.

Menu optionThis option requires the following selections to bemade in:■ Select “Service” in menu 8.1.1.■ Menu 9.2.13.1 “Selected docking option” select opt.

”2”.■ Menu 9.2.13.2 “Immersion heater type” select “Off”When there is also a hot water heater the follow selec-tions should also be made:■ Menu 9.2.13.3 “Hot water production”, select “On”.

NOTE! These selections are confirmed by switchingthe heat pump off and on.

Sensor connectionIn this connection option the edge board connector forthe flow line sensor (FG) and return sensor (RG)should be disconnected.The flow line sensor (FG) should be placed on themain pipe and connected to the screw terminalsX4:15–16.The existing return sensor (RG) is disconnected fromthe edge board connector and is connected toX4:13–14.

Option 2 - FIGHTER 1120 docked to a gas boiler (floating condensing)

NK

VVG

BK / JK

SF

AV

SÄV

SÄV

EXP

VXV

AV

AV

AV

AV SF AV

FG

AV

Gaspanna

UG

VVB / ACK

SÄV

SÄV

EXP

AB

B A

NOTE! The gas boiler must be fitted with athermostat to limit the temperature.

Gas boiler

Connection VST 11*

Immersion heater connection for XHW

Gas boiler connection

Docking 27

FIGHTER 1120

Option 2 - FIGHTER 1120 docked to a gas boiler (floating condensing)

* Accessories. The figures show how the connectionshould appear when completed. For full informationabout the connections see respective “Installationinstructions”

X4

Gaspanna

Elpatron för XVV

Hot water, jacket (VVG)

Return sensor 1 (RG)

Flow line sensor 1 (FG)

Sensor connection

X4 X1 -X6

Connection of the outside temperaturesensor

Outside temperaturesensor (UG)

Gas boiler

Immersion heater for XXV

Shuttle valve

Docking28

FIGHTER 1120

Principle of operationFIGHTER 1120 prioritises charging the hot waterheater (VVB/ACK). When the preset hot water tem-perature is reached, the shuttle valve switches toheating. If the heat pump cannot manage to keep thecorrect flow temperature, the oil-fired boiler starts andthe shunt valve (SV) begins to open from the boiler.The flow line sensor (FG) should be placed on themain pipe to the radiators.This alternative requires the accessory VST 11.

Menu optionThis option requires the following selections to bemade in:■ Select “Service” in menu 8.1.1.■ Menu 9.2.13.1 “Docking type” select alt. ”3”.■ Menu 9.2.13.4 “Boiler temp/act mixv”. The tempera-

ture when the shunt shall start to work (open) isselected here.

When there is also a hot water heater the follow selec-tions should also be made:■ Menu 9.2.13.3 “Hot water”, is set to “On”.

NOTE! These selections are confirmed by switchingthe heat pump off and on.

Sensor connectionIn this connection option the edge board connector forthe flow line sensor (FG) and return sensor (RG)should be disconnected.The flow line sensor (FG) should be placed on themain pipe and connected to the screw terminalsX4:15–16.The existing return sensor (RG) is disconnected fromthe edge board connector and is connected toX4:13–14.

Option 3 - FIGHTER 1120 docked to an oil-fired boiler (floating condensing)

NK

VVG

BK / JK

SF

AV

SÄV

SÄV

EXP

VXV

AV

AV

AV

AV SF AV

FG

AV

Oljepanna

UG

PG SV

VVB / ACK

AB

B AOil boiler

Immersion heater connection for XHW

Docking 29

FIGHTER 1120

Option 3 - FIGHTER 1120 docked to an oil-fired boiler (floating condensing)

Connection of shunt valve*-X6:20 closes the shunt valve.-X6:21 opens the shunt valve.-X6:22 zero conductor.

* Accessories. The figures show how the connectionshould appear when completed. For full informationabout the connections see respective “Installationinstructions”

X4

-X6

Boiler sensor (PG)

Elpatron för XVV

Connection VST 11*

Sensor connection

Connection of oil boiler via an externalauxiliary relay

X4 X1 -X6

Connection of the outside temperaturesensor

Outside temperaturesensor (UG)

Hot water, jacket (VVG)

Return sensor 1 (RG)

Flow line sensor 1 (FG)

Oil burner

Immersion heater for XXV

Shuttle valve

Shunt valve

Docking

FIGHTER 1120

30

Principle of operationFIGHTER 1120 charges the hot water heater/accumu-lator tank (VVB/ACK). When the wood-fired boiler isused, the heat pump and immersion heater are dis-connected with a rising temperature on the flow sen-sor (FG) and start again when the temperature startsto drop. Self-circulation through the heat pump is pre-vented by the check valve (BV). The flow temperaturesensor (FG) is placed in the submerged tube on theaccumulator tank. For fixed condensing, 50°C is suit-able for both min and max levels. (sensor placementand pump flow observed).The flow temperature can be controlled from the heatpump using the accessory ESV 20.

Menu optionThis option requires the following selections to bemade in:■ Select “Service” in menu 8.1.1.■ Menu 9.2.13.1 “Docking type” should be set to “4”.■ Menu 9.2.13.2 “Linear 3 steps” should be selected.■ Menu 9.2.13.3 “Hot water” should be set to “Off”.NOTE! These settings must be confirmed by switchingthe heat pump off and on.■ Menu 2.3 “Flow temp./MIN” the value is set to e. g.

“50” °C.■ Menu 2.4 “Flow temp./MAX” the value is set to e. g.

“50” °C.■ Menu 9.2.2 “Flow diff HP”, “3” should be selected.■ Menu 9.2.3 “Diff HP Add”, “2” should be selected.

Sensor connectionIn this connection option the edge board connector forthe flow line sensor (FG) and return sensor (RG)should be disconnected.The flow line sensor (FG) should be placed on thesubmerged tube in the accumulator tank and connect-ed to the screw terminals X4:15–16.The existing return sensor (RG) is disconnected fromthe edge board connector and is connected toX4:13–14.

Option 4 - FIGHTER 1120 docked to another heat source (fixed condensing)

NK

UG

FG

BK / JK

RC

SF

AV AV

AV

BV

SÄV

SÄV

AV

AV

AV

AV SF

Vedpanna

Tillbehör altbefintlig regler-utrustning.

VVB / ACK

UG

Accessory orexisting controlequipment

Wood-fired boiler

Docking 31

FIGHTER 1120

Option 4 - FIGHTER 1120 docked to another heat source (fixed condensing)

Connection of the outside temperaturesensor

Connection of the flow sensor

Connection of the external electricaladdition

* Accessories. The figures show how the connectionshould appear when completed. For full informationabout the connections see respective “Installationinstructions”.

X4 X1 -X6

X4

Ste

p 3

Ste

p 1

Ste

p 2

Hot water, jacket (VVG)

Immersion heater 1

Ele

ctric

alst

ep 1

Ele

ctric

alst

ep 2

Ele

ctric

alst

ep 3

Immersion heater 2

Immersion heater 3

Return sensor 1 (RG)

Flow line sensor 1 (FG)

Outside temperaturesensor (UG)

Commissioning and adjusting

FIGHTER 1120

32

AV Shut-offSÄV Safety valvePF Particle filter

BK Rock collectorJK Ground collectorNK Level vessel

Stängs

BK / JK

Cirk.pump

Värmepump

Varmvatten

Tillsatsvärme

Larm

Kontrollera att vatten finns i pan-nan innan den in-kopplas.

1

R

0

SF

AV

AV

AV

AV

NK

SÄV

AV

Before starting up the system, check that the heating,collector and hot water circuits are full and thoroughlyvented. Check the pipe system for leakage.

Preparations

Fill the heating medium system with water to therequired pressure and vent the system.

Filling the heating medium system

When filling the collector system mix the water withantifreeze in an open container. The mixture shouldbe protected against freezing down to about -15 °C.The brine is filled by connecting a filling pump.

1. Check the collector system for leakage.

2. Connect the filling pump and return line on the col-lector system's service connections as shown infigure.

3. Close the valve under the level vessel.

4. Close the valve between the service connections.

5. Open the valves on the service connections.

6. Start the filling pump, and fill until there is fluid inthe return pipe.

7. Turn the heat pump's switch (8) to 1.

8. Select “Service” in menu 8.1.1.

9. Select “On” in menu 9.2.4.

10. Select “On” in menu 9.2.12. The filling pump andthe heat pump's brine pump are now operational.The fluid should circulate via the mixing containeruntil it emerges from the return hose without beingmixed with air.

11. Select “Off” in menu 9.2.12.

12. Stop the filling pump and clean the particle filter.

13. Start the filling pump, open the valve between theservice connections.

14. Close the valve on the service connection's returnline. Now pressurise the system (to max 3 bar)with the filling pump.

15. Close the valve on the service connection closestto the level vessel.

16. Stop the filling pump.

17. Fill the level vessel with liquid up to around 2/3.

18. Open the valve below the level vessel.

19. Select “Off” in menu 9.2.4.

20. Select the auto operating mode using theoperating mode button.

Filling and venting the collector system

Internal air vent valve, brine

77

Closes

Commissioning and adjusting 33

FIGHTER 1120

1. Set the switch (8) to 1.

2. Adjust the heating curve offset knob so there is noheating requirement.

3. Select “Service” in menu 8.1.1.

4. Select “On” in menu 9.2.4.

5. Select “On” in menu 9.2.12. The brine pump runscontinuously for 10 days, and then returns to nor-mal operations.

6. Check that the brine and heat medium systemsare vented.

7. Check that brine and heat medium pumps areoperational. If necessary help the pumps to start.

8. Check that the brine temperatures in menu 5.0correspond with the ground/rock temperature,which indicate brine flow.

9. Select “Off” in menu 9.2.4.

10. Select the spring/autumn operating modewith the operating mode button.

11. Adjust the heating curve offset knob so there is aheating requirement. The compressor will start.

12. If the heat pump is a FIGHTER 1120-12, 15, 17,check the direction of rotation at start-up ofthe compressor. See section rotation check FIGHTER.

13. Read the brine temperatures in menu 5.0. The dif-ference between these two temperatures shouldbe 2—5 °C when the system has come into bal-ance. Adjust the flow with the knob on the brinepump (35). A high difference indicates a low brineflow. A low difference indicates a high brine flow.

LE

K

GR

UN

DF

OS

Typ

eU

PS

25

- 6

013

0P

/N:5

952

64

47

23

0V

-

HE

JS

AN

PC

;001

7N

IBD

K50

Hz

IP 44

TF

1

10

Cla

ss

HM

ax. 1

0ba

r

2.5

uF

45

0.2

06

50

.30

90

0.4

0

1m(A

)P,

(W)

The pump isadjustable to adjustbrine flow.

LE

K

GR

UN

DF

OS

Typ

eU

PS

25

- 6

013

0P

/N:5

952

64

47

23

0V

-

HE

JS

AN

PC

;001

7N

IBD

K50

Hz

IP 44

TF

1

10

Cla

ss

HM

ax. 1

0ba

r

2.5

uF

45

0.2

06

50

.30

90

0.4

0

1m(A

)P,

(W)

The pump isadjustable to adjustheat medium flow.

15. Set the date and time in menu 7.1 and 7.2.

16. Fill in the commissioning report on page 2.

17. Select the auto operating mode using theoperating mode button.

18. Set the control system according to the needs ofthe property. See section “Settings - Heating con-trol system”.

14. Check the flow temperature on menu 2.0 andreturn temperature on menu 2.7. The differencebetween these two temperatures, with floatingcondensing, should be 5 - 10 °C when the houseis being heated without additional heat. Adjust theflow with the knob on the heating medium pump(16). A high difference could depend on a low heatmedium flow. A low difference indicates a highheat medium flow.

Starting and checking

NOTE! The compressor must not be forced tostart with periods shorter that 1 start

per 15 minutes.

Commissioning and adjusting

FIGHTER 1120

34

Rotation check Fighter 1120-15, 17 kW 3x400 V

Rotation check Fighter 1120-12 kW 3x400 V

The compressor in FIGHTER 1120-12 kW 3 x400 V isof the scroll type. It can only operate in one directionof rotation. Operating in the wrong direction candamage the compressor.

The direction of rotation is checked as follows:■ Set the switch to 1.

■ Check the hot gas temperature in menu 5.11. Thetemperature should increase by 10 °C within 30seconds from compressor start.

■ If the temperature remains the same, the directionof rotation is incorrect. The noise produced is alsodifferent when rotating in the incorrect direction.

- Set the switch to 0 and cut the mainpower supply.

- Swap the two incoming phases on theterminal block for incoming electricity, -X9.

- Set the switch to 1 and check the rotationagain.

The compressor in FIGHTER 1120-15, 17 kW 3 x400 V is of the scroll type. It can only operate inone direction of rotation. Operating in the wrongdirection can damage the compressor.

The direction of rotation is checked as follows:■ Set the switch to 1.

■ Wait until the symbol for the compres-sor lights up in the display.

■ Check that the compressor is operating.

■ If the compressor is not operating and the symbolfor the compressor is lit, there is a phase sequenceerror. The phase sequence monitor (164) also indi-cates this; see section “Electrical connection”.

- Set the switch to 0 and cut the mainpower supply.

- Swap the two incoming phases on theterminal block for incoming electricity, -X9.

- Set the switch to 1 and check the rotationagain.

PENL1 L2 L3

-X9

Commissioning and adjusting 35

FIGHTER 1120

Air is initially released from the hot water and ventingmay be necessary. If bubbling sounds can be heardfrom the heat pump, the entire system requires furtherventing. When the system has stabilised (correctpressure and all the air removed) the heating controlscan be set at the required values.

Check the fluid level in the level vessel (85). If thelevel has dropped, close the valve under the vessel.You can then fill through the connection at the top ofthe vessel. After filling, open the valve again. To raise the pressure, close the valve on the incomingmain pipe when the brine pump (KBP) is running andthe level vessel (NK) is open, so that water is drawn infrom the vessel.

Readjusting, collector side

Readjusting, heating medium side

2/3

LE

K

Control36

FIGHTER 1120

NOTE! Ensure the operating mode is notchanged during quick movement

A key lock can be activated in the mainmenus by simultaneously pressing theplus and the minus buttons. The key sym-bol will then be shown on the display. Thesame procedure is used to deactivate thekey lock.

Key lock

A BI II III I II

5 0 . 0 CH o t w a t e r t e m p e r a t u r e

13.431.0

A

The menu tree shows all the menus. Three differentmenu types can be chosen.

Normal, covers the normal user's needs.

Extended, shows all menus except the servicemenus.

Service, shows all menus, returns to the previ-ous menu type 30 minutes after the last buttonwas pressed.

Changing of menu type is done from menu 8.1.1

Information is presented on the display about the statusof the heat pump and the electric boiler. Menu 1.0 is nor-mally shown on the display screen. The plus and minusbuttons and the enter button are used to scroll throughthe menu system as well as to change the set value insome menus.

The Plus button is used to move forward tothe next menu on the current menu leveland to increase the value of the parameterin menus where this is possible.

The minus button is used to move back tothe previous menu on the current menulevel and to decrease value of the parame-ter in menus where this is possible.

The enter button is used to select sub-menus of the current menu, to permit para-meters to be changed and confirm anychanges to parameters. When the menunumber ends with a zero this indicatesthere is a sub-menus.

N

U

S

General

Menu name

Menu number Key lockClock

Symbols Value of thecurrent parameter

To quickly return to the main menu from sub-menuspress the following:

1. Operating mode button

2. Enter button

Quick movement

Control 37

FIGHTER 1120

Changing a parameter (value):

■ Access the required menu.

■ Press the enter button, the numerical value starts toflash.

■ Increase or decrease the value with the Plus/Minusbuttons.

■ Confirm by pressing the enter button.

■ Menu 1.0 is automatically displayed again 30 min-utes after pressing the last button.

ExampleChanging the Menu type/Service mode menu 8.1.1.■ The starting point is menu 1.0.

■ Press the plus button to move to menu 8.0.

■ Press the enter button to move to menu 8.1.0

■ Press the enter button to move to menu 8.1.1

■ Press the enter button to allow the value to bechanged.

■ Change the value using the plus or minus button.

■ Confirm the chosen value by pressing the enter but-ton.

■ Press the minus button to move to menu 8.1.5

■ Press the enter button to move to menu 8.1.0

■ Press the minus button to move to menu 8.4

■ Press the enter button to move to menu 8.0

■ Press the plus button to move to menu 1.0

Changing parameters

Normal menus Expanded menus Service menusSUN

8.1.1Operation mode types

8.1.2Language

8.1.3Contrast

8.1.4Light intensity

8.1.5Return to 8.1.0

8.2.1Summer mode temp.

8.2.2Winter mode temp.

8.2.3Return to 8.2.0

Other settings8.0

8.3.1Current Phase 1

8.3.2Current phase 2

8.3.3Current Phase 3

8.3.4Fuse size

8.3.5Max. add heat

8.3.6EBV value

8.3.7Return to 8.3.0

8.1.0Display settings

8.2.0Operating mode

8.3.0Current limiter

8.4Return to 8.0

↵↵

↵↵

↵↵

↵↵

↵↵

↵↵

↵↵

↵↵

U

U

U

U

U

U

U

U

U

U

U

U

U

U

N

N

N

N

N

N

Control

FIGHTER 1120

38

* Only shown when “On” is selected in menu 9.2.13.3.

A BI II III I II

5 0 . 0 CH o t w a t e r t e m p e r a t u r e

13.431.0

A

Normal menus Expanded menus Service menusSUN

2.6.1Flow temp.at +20°C

2.6.2Flow temp.at -20°C

2.6.3Set temperature

2.6.4Flow temp at set

2.6.5Return to 2.6.0

1.1Periodtime HW/TotalTime Heating/Set.Time HW/Set.

1.2Time period

1.3MAX-time HW-period

1.4HW-temp/Starttemp.HW

1.5HW-temp/Stoptemp.HW

1.6Stop Temp. XHW

1.7Stop compressor XHW

1.8Interval XHW

1.9Next XHW action

1.10HW running time

1.11.0Pool adjustments

1.12Return to 1.0

1.11.1Pooltemp./Setting

1.11.2Diff. Pool

1.11.3Pool Time

1.11.4Return to 1.11.0

Hotwatertemperature1.0*

2.1Curve coefficient

2.2Heating curve offset

2.3Flow Temp./MIN

2.4Flow Temp./MAX

2.5External adjustment

2.6.0Own curve definition

2.7Return temp./MAX

2.8Degree minutes

2.9.0Cooling settings

2.10Return to 2.0

Flow temperature2.0

2.9.1Cooling curve

2.9.2Offset cold curve

2.9.3Starttemp. cooling

2.9.4Diff Passive/Active

2.9.5Return to 2.9.0

↵↵

↵↵

↵↵

↵↵

↵↵

↵↵

↵↵

↵↵

↵↵↵↵

U

U

U

U

U

U

U

U

U

U

U

U

U

U

U

U

U

UU

U

U

U

U

U

U

U

U

N

N

N

N

N

N

N

N

N

N

N

Control 39

FIGHTER 1120

* Only shown when “On” is selected in menu 9.2.5.for shunt group 2 (accessory ESV 20 required).

** Shown when the accessory RG 10 is installed.

A BI II III I II

5 0 . 0 CH o t w a t e r t e m p e r a t u r e

13.431.0

A

Normal menus Expanded menus Service menusSUN

4.1Outdoor avg. temp.

4.2Return to 4.0

Outdoor temperature4.0

5.1Autoreset brinealarm

5.2Auto restart. Brine alarm

5.3Time between starts

5.4Compr. starts at

5.5Time to startStatus

5.6Number of starts

5.9Comp. acc. run time

5.11Hot gas temp.

5.12Liquide line temp.

5.13Bulb temperature

5.14Condensor out temp.

5.15Compressor type

5.22Return to 5.0

Brine in-/out- temp.5.0

3.6.1Flow temp.at +20°C

3.6.2Flow temp.at -20°C

3.6.3Set temperature 2

3.6.4Flow at set 2

3.6.5Return to 3.6.0

3.1Curve coefficient 2

3.2Offs.heating curve 2

3.3Flow temp2./MIN

3.4Flow temp2./MAX

3.5External adjustment 2

3.6.0Own curve def. 2

3.7Return temp.2 / MAX

3.8Return to 3.0

Flow temp. system 23.0*

6.1Room compensation

6.2Heating system

6.3Return to 6.0

Room temp./Settings6.0** ↵↵

↵↵

↵↵↵↵

↵↵

↵↵

↵↵

↵↵

↵↵

↵↵

U

U

U

U

U

U

U

U

U

U

U

U

U

U

U

U

U

U

U

U

U

U

U

U

N

N

N N N

N

N

N

N

N

N

Control

FIGHTER 1120

40

A BI II III I II

5 0 . 0 CH o t w a t e r t e m p e r a t u r e

13.431.0

A

Normal menus Expanded menus Service menusSUN

8.1.0Display settings

8.2.0Operating mode

8.3.0Current limiter

8.4Return to 8.0

7.1Date

7.2Time

7.3.0Temp set back time 1

7.4.0Temp set back time 2

7.5.0Timer XHW

7.7Reset timers

7.8Return to 7.0

7.3.1Heating sys per. 1

7.3.2Set back temp. +/-

7.3.3 - 7.3.9Set time Mon Sun

7.3.10Return to 7.3.0

8.1.1Operation mode types

8.1.2Language

8.1.3Contrast

8.1.4Light intensity

8.1.5Return to 8.1.0

8.2.1Summer mode temp.

8.2.2Winter mode temp.

8.2.3Return to 8.2.0

7.4.1Heating sys per. 2

7.4.2Set back temp. +/-

7.4.3 - 7.4.9Set time Mon Sun

7.4.10Return to 7.4.0

7.5.1Timer Extra HW

7.5.2 Extra HW Mon Sun

7.5.3Return to 7.5.0

Clock7.0

Other settings8.0

8.3.1Current Phase 1

8.3.2Current phase 2

8.3.3Current Phase 3

8.3.4Fuse size

8.3.5Max. add heat

8.3.6EBV value

8.3.7Return to 8.3.0

↵↵

↵↵

↵↵

↵↵

U

U

↵↵

↵↵

↵↵

UU

U

U

U

U

U

U

U

U

U

U

U

N

N

N

N

↵↵N

NN

N

↵↵

↵↵

↵↵

↵↵

↵↵

U

U

U

U

↵↵

U

U

↵↵U

U

U

U

U

U

U

UN

N

Control 41

A BI II III I II

5 0 . 0 CH o t w a t e r t e m p e r a t u r e

13.431.0

A

9.1.0Add. heat settings

9.2.0Operating mode set

9.3Quick start

9.4.0TEST/Forced operat.

9.5.0 - 9.8.0Log 1—4

9.9Reset alarm

9.10Return to 9.0

9.1.1Start BIN 3 stepStart LIN 3 stepStart BIN 7 step

9.1.2Diff. BIN 3 stepDiff. LIN 3 stepDiff. BIN 7 step

9.1.3Add heat run time

9.1.4Return to 9.1.0

Service menus9.0

9.2.1Max HW temp

9.2.2Flow diff HP

9.2.3Diff HP Add

9.2.4Add heat only

9.2.5System 2 Present

9.2.6Room disp Present

9.2.7Circ. pump 1

9.2.8Circ. pump 2

9.2.9.0Floor drying set

9.2.10Pool control

9.2.11Brine pressostat

9.2.12Brinepump 10 days

9.2.13.0Docking

9.2.14Factory setting

9.2.15RCU Present

9.2.16Cooling system

9.2.17Return to 9.2.0

9.2.9.1Floor drying

9.2.9.2Numb. of days per. 1

9.2.9.3Temp. period 1

9.2.9.4Numb. of days per. 2

9.2.9.5Temp. period 2

9.2.9.6Return to 9.2.9.0

FIGHTER 1120

↵↵

↵↵

↵↵

S

S

S

S

S

↵↵

S

S

S

S

S

S

S

S

S

S

↵↵S

↵↵

S

S

S

S

S

↵↵

S

S

S

S

S

S

S

↵↵

S

S

S

S

S

9.2.13.1Docking type

9.2.13.2Immersion heat type

9.2.13.3Hot water

9.2.13.4Boiler temp/act mixv

9.2.13.5Start value OilPower

9.2.13.6Oil burner on

9.2.13.7Return to 9.2.13.0 ↵↵

S

S

S

S

S

S

S

↵↵S

Normal menus Expanded menus Service menusSUN

Control

FIGHTER 1120

42

Main menus

Menu 1.0 HotwatertemperatureThe current water temperature (88) in the upper partof the hot water cylinder is shown here.

Menu 2.0 Flow temperatureThe current supply temperature (89) for the heatingsystem is shown here with the calculated supply tem-perature in brackets.

Shown alternately with hot water charging, “HWcharging”.

Menu 4.0 Outdoor temperatureThe current outdoor temperature is shown here.

Menu 5.0 Brine in-/out- temp.Readings regarding the temperatures and compressorare made from the sub-menus to this menu.

Menu 8.0 Other settingsSettings regarding the menu type, language, operat-ing mode settings and load monitor reading are madein the sub-menus to this menu.

Menu 9.0 Service menusThis menu and its sub-menus are only shown on the display screen when access has been selected in menu 8.1.1.

Values can be read and various settings can be madefrom these sub-menus. NOTE! These settings shouldonly be made by persons with the necessary exper-tise.

5 7 . 1 ° CH o t w a t e r t e m p e r a t u r e1 . 0

3 1 . 7 ( 2 8 . 0 ) ° CF l o w t e m p e r a t u r e2 . 0

1 0 . 3 ° CO u t d o o r t e m p e r a t u r e4 . 0

Menu 7.0 ClockSettings regarding the date and time are made in thesub-menus of this menu. Different temperature reduc-tions and increases at selected times are also set fromthis menu.

C l o c k7 . 0

O t h e r s e t t i n g s8 . 0

S e r v i c e m e n u s9 . 0

N

N

N

N

N

N N

N

N

U

S

S

Normal, covers the normal user's needs.

Extended, shows all menus except theservice menus.

Service, shows all menus, returns to theprevious menu level 30 minutes after thelast button was pressed.

1 . 0 - 2 . 0 ° CB r i n e i n - / o u t - t e m p .5 . 0

Menu 3.0 Flow temp. system 2*The current supply temperature (FG2) for the heatingsystem is shown here with the calculated supply tem-perature in brackets.

Activated in menu 9.2.5.

2 7 . 7 ( 2 4 . 0 ) ° CF l o w t e m p . s y s t e m 23 . 0

* Accessories

Menu 6.0 Room temp./Settings*The room temperature is shown here and the setroom temperature in brackets. Settings concerning thefactor for the room sensor or room unit and which sys-tem the sensor should control are made on the sub-menus to this menu. The accessory RG 10 is activat-ed in menu 6.0.

2 1 . 3 ( 2 1 . 0 ) ° CR o o m t e m p . / S e t t i n g s6 . 0

Control 43

FIGHTER 1120

Hot water temperature

Menu 1.1 Periodtime HW/TotalThe time of the hot water period and the time for thewhole period are shown here. Shown for both hotwater charging and heat when necessary:

Time HW-charge/Max when hot water charging is inprogress. Time heating/Max when heating is inprogress.

Menu 1.3 MAX-time HW-periodHere you select how much time of the period time(menu 1.1) is to be used to heat the hot water whenthere is a need of both heating and hot water. Thevalue is adjustable between 5 and 60 minutes.

Menu 1.4 HW-temp/Starttemp.HWThe temperature when the heat pump starts to workwith the hot water heater is set here. When bracketswith a minus are shown, this means the high pressurepressostat has tripped during hot water charging andFIGHTER 1120 has automatically lowered the settemperature with the value in brackets. The reductionis removed when the value is changed. The value isadjustable between 25 and 55 °C.

Menu 1.5 HW-temp/Stoptemp.HWThe temperature when the heat pump/immersionheater should stop heating the water is set here.When brackets with a minus are shown, this meansthe high pressure pressostat has tripped during hotwater charging and FIGHTER 1120 has automaticallylowered the set temperature with the value in brackets.The reduction is removed when the value is changed.The value is adjustable between 30 and 60 °C.

Menu 1.8 Interval XHWHow often the hot water temperature is increased fromthe normal level to the “Extra hot water” level is shownhere. The time is adjustable between 0 and 90 days.Extra hot water is shut-off when 0 is set. Extra hotwater starts when the value has been confirmed.

Menu 1.9 Next XHW actionFuture increases to the “Extra hot water” level areshown here.

Menu 1.10 HW running timeHow long hot water heating has been in progress isshown here (accumulated).

2 0 ( 6 0 ) m i nP e r i o d t i m e H W / T o t a l1 . 1

1 4 d a y sI n t e r v a l X H W1 . 8

9 0 h 1 0 m i nH W r u n n i n g t i m e1 . 1 0

2 0 m i nM A X - t i m e H W - p e r i o d1 . 3

5 0 . 0 ( 4 7 ) ° CH W - t e m p / S t a r t t e m p . H W1 . 4

5 0 . 0 ( 5 4 ) ° CH W - t e m p / S t o p t e m p . H W1 . 5

Menu 1.6 Stop Temp. XHWThe desired stop temperature for extra hot water is sethere. The value is adjustable between 40 and 70 °C.

5 0 . 0 ( 6 0 ) ° CS t o p T e m p . X H W1 . 6

1 0 - 2 6 1 0 : 3 1N e x t X H W a c t i o n1 . 9

N

N

N

N

Menu 1.2 Time period The length of time is set here. The value is adjustablebetween 5 and 60 minutes.

6 0 m i nT i m e p e r i o d 1 . 2

N

U

U

Menu 1.7 Stop compressor XHWThe temperature to stop the compressor for extra hotwater is set here. The value is adjustable between 50and 60 °C.

5 0 . 0 ( 5 5 ) ° CS t o p c o m p r e s s o r X H W1 . 7

U

U

U

Menu 1.11.0 Pool adjustmentsPool settings are made on the sub-menus to thismenu.

P o o l a d j u s t m e n t s1 . 1 1 . 0U

Control

FIGHTER 1120

44

Hot water temperature

Menu 1.12 ReturnPressing the enter button returns you to menu 1.0

R e t u r n1 . 1 2

Menu 1.11.4 ReturnPressing the enter button returns you to menu 1.11.0

R e t u r n1 . 1 1 . 4

Menu 1.11.2 Diff. PoolThe difference from the value in menu 1.11.1 whenpool heating starts is stated here.

The value is adjustable between 0.5 and 9.5°C.

1 . 5 ° CD i f f . P o o l1 . 1 1 . 2

Menu 1.11.3 Pool TimeThe maximum time that pool heating can run is statedhere. The value is adjustable between 5 and 60 min-utes.

2 0 m i nP o o l T i m e1 . 1 1 . 3

U

U

Menu 2.4 Flow Temp./MAXThe set maximum level for the supply temperature tothe heating system is shown here. The value isadjustable between 10 and 80 °C

The calculated flow temperature never exceeds theset level irrespective of the outdoor temperature,curve slope or heating curve offset.

Menu 2.1 Curve coefficientThe selected curve slope (heating curve) is shownhere. The “Own curve” function is activated at value 0,see menu 2.6.0. The value can be set between curve0 and 15.

Menu 2.2 Heating curve offset The selected heating curve offset is shown here. Thevalue is adjustable between -10 and +10.

Menu 2.3 Flow Temp./MINThe set minimum level for the supply temperature tothe heating system is shown here. The value isadjustable between 10 and 80 °C.

The calculated flow temperature never drops belowthe set level irrespective of the outdoor temperature,curve slope or heating curve offset.

3 5 . 5 ( 5 5 ) ° CF l o w T e m p . / M A X2 . 4

9C u r v e c o e f f i c i e n t2 . 1

- 1H e a t i n g c u r v e o f f s e t2 . 2

3 5 . 5 ( 1 5 ) ° CF l o w T e m p . / M I N2 . 3

U

U

N

N

Flow temperature

Menu 1.11.1 Pooltemp./SettingThe temperature when pool heating is stopped is stat-ed here.

The value is adjustable between 15 and 55 °C.

1 9 . 0 ( 2 0 ) ° CP o o l t e m p . / S e t t i n g1 . 1 1 . 1

U

Control 45

FIGHTER 1120

Flow temperature

Menu 2.5 External adjustmentConnecting an external contact, see “Electrical con-nections - External contacts”, for example, a roomthermostat (accessory) or a timer allows you to tem-porarily or periodically raise or lower the room temper-ature. When the external contact is made, the heatingcurve offset is changed by the number of steps shownhere. The value is adjustable between -10 and +10.

Menu 2.6.0 Own curve definitionYour own curve definition is chosen here. This is anindividual linear curve with one break point. You selecta break point and the associated temperatures.NOTE! The “Curve slope” in menu 2.1 must be set to0 to activate this function.

Menu 2.6.1 Flow temp.at +20°CThe flow temperature at an outside temperature of+20 is chosen here. The value is adjustable between0 and 60 °C.

Menu 2.6.2 Flow temp.at -20°CThe flow temperature at an outside temperature of -20 °C is chosen here. The value is adjustablebetween 0 and 60 °C.

Menu 2.6.3 Set temperatureHere you select at what outside temperature the breakpoint shall occur. The value is adjustable between -15and +15 °C.

1E x t e r n a l a d j u s t m e n t2 . 5

1 5 ° CF l o w t e m p . a t + 2 0 ° C2 . 6 . 1

3 5 ° CF l o w t e m p . a t - 2 0 ° C2 . 6 . 2

0 ° CS e t t e m p e r a t u r e2 . 6 . 3

O w n c u r v e d e f i n i t i o n2 . 6 . 0

U

U

U

U

U

Menu 2.7 Return temp./MAXHere the maximum return flow temperature is set forcompressor operation.

The value is adjustable between 40 and 58 °C.

Menu 2.6.5 ReturnPressing the enter button returns you to menu 2.6.

Menu 2.6.4 Flow temp at setYou set the required flow temperature for the breakpoint here. The value is adjustable between 0 and60 °C.

2 0 ° CF l o w t e m p a t s e t2 . 6 . 4

Menu 2.8 Degree-minutesCurrent value for number of degree-minutes. Forexample, this value can be changed to accelerate thestart of heating production. The value can be setbetween 100 and -800.

0D e g r e e m i n u t e s2 . 8

R e t u r n2 . 6 . 5

3 3 . 0 ( 5 3 ) ° CR e t u r n t e m p . / M A X2 . 7

U

U

U

Menu 2.9.0 Cooling settingsThe cooling system settings are made here. Onlyshown when HPAC or PKM is selected in menu9.2.16. Lower the value on menu 2.3 for the coolingfunction to work.

C o o l i n g s e t t i n g s2 . 9 . 0

U

Control

FIGHTER 1120

46

Flow temperature system 2

Menu 3.4 Flow temp2./MAXThe set maximum level for the supply temperature tothe heating system is shown here. The value isadjustable between 10 and 80 °C.

The calculated flow temperature never exceeds the set level irrespective of the outdoor temperature,curve slope or heating curve offset.

Menu 3.1 Curve coefficient 2The selected curve slope (heating curve) is shownhere. The “Own curve” function is activated at value 0,see menu 3.6.0. The value can be set between curve0 and 15.

Menu 3.2 Offs.heating curve 2The selected heating curve offset is shown here. Thevalue is adjustable between -10 and +10. NOTE! Thevalue is changed using the “Heating curve offset”knob.

Menu 3.3 Flow temp2./MINThe set minimum level for the supply temperature tothe heating system is shown here. The value isadjustable between 10 and 80 °C.

The calculated flow temperature never drops belowthe set level irrespective of the outdoor temperature,curve slope or heating curve offset.

3 5 . 5 ( 4 5 ) ° CF l o w t e m p 2 . / M A X3 . 4

9C u r v e c o e f f i c i e n t 23 . 1

- 1O f f s . h e a t i n g c u r v e 23 . 2

3 5 . 5 ( 1 5 ) ° CF l o w t e m p 2 . / M I N3 . 3

U

U

N

N

Flow temperature

Menu 2.10 ReturnPressing the enter button returns you to menu 2.0.

R e t u r n2 . 1 0

Menu 2.9.1 Cooling curve The selected cooling curve (curve slope) is shownhere. The value can be set between curve 1 and 3.

2C o o l i n g c u r v e2 . 9 . 1

U

Menu 2.9.5 ReturnPressing the enter button returns you to menu 2.9.0

R e t u r n2 . 9 . 5

Menu 2.9.2 Offset cold curve The selected cooling curve offset is shown here. Thevalue is adjustable between -10 and +10.

0O f f s e t c o l d c u r v e 2 . 9 . 2

U

Menu 2.9.3 Start temp. coolingThe outdoor temperature when cooling is activated isshown here. The value is adjustable between -20 and35 °C.

2 5S t a r t t e m p . c o o l i n g2 . 9 . 3

U

Menu 2.9.4 Diff Passive/Active If the flow temperature exceeds the calculated flowtemperature + this value the system switches to activecooling. The value can be set between curve 1 and 9.

4D i f f P a s s i v e / A c t i v e2 . 9 . 4

U

Control 47

FIGHTER 1120

Menu 3.5 External adjustment 2Connecting an external contact, see “Electrical con-nections - External contacts”, for example, a roomthermostat (accessory) or a timer allows you to tem-porarily or periodically raise or lower the room temper-ature. When the external contact is made, the heatingcurve offset is changed by the number of steps shownhere. The value is adjustable between -10 and +10.

Menu 3.6.0 Own curve def. 2Here you can select your own curve definition. This isan individual linear curve with one break point. Youselect a break point and the associated temperatures.NOTE! The “Curve slope” in menu 3.1 must be set to0 to activate this function.

Menu 3.6.1 Flow temp.at +20°CThe flow temperature at an outside temperature of+20°C is chosen here. The value is adjustablebetween 0 and 60°C.

Menu 3.6.2 Flow temp.at -20°CThe flow temperature at an outside temperature of -20 °C is chosen here. The value is adjustablebetween 0 and 60°C.

Menu 3.6.3 Set temperature 2Here you select at what outside temperature the breakpoint shall occur. The value is adjustable between -15and +15 °C.

1E x t e r n a l a d j u s t m e n t 23 . 5

1 5 ° CF l o w t e m p . a t + 2 0 ° C3 . 6 . 1

3 5 ° CF l o w t e m p . a t - 2 0 ° C3 . 6 . 2

0 ° CS e t t e m p e r a t u r e 23 . 6 . 3

O w n c u r v e d e f . 23 . 6 . 0

U

U

U

U

U

Flow temperature system 2

Menu 3.7 Return temp.2 / MAXThe return temperature for shunt group 2 is shownhere.

Menu 3.6.5 ReturnPressing the enter button returns you to menu 3.6.

Menu 3.6.4 Flow at set 2You set the required flow temperature for the breakpoint here. The value is adjustable between 0 and60 °C.

2 0 ° CF l o w a t s e t 23 . 6 . 4

Menu 3.8 ReturnPressing the enter button returns you to menu 3.0.

R e t u r n3 . 8

R e t u r n3 . 6 . 5

3 3 . 0 ° CR e t u r n t e m p . 2 / M A X3 . 7

U

U

Control48

FIGHTER 1120

Outdoor temperature

Menu 4.2 ReturnPressing the enter button returns you to menu 4.0.

Menu 4.1 Outdoor avg. temp.Average outdoor temperature during the last 24 hours.

R e t u r n4 . 2

O u t d o o r a v g . t e m p .4 . 1

U

Brine in/out temperature

Brine in/out temperature

Menu 5.5 Status compressorShows the compressor status for the heat pump.

“Start in XX minutes”, means the compressor will startas soon as the time condition permits.

“Compr. OFF” means that the compressor is not oper-ational.

“Compr. ON” means that the compressor is opera-tional.

“Brine pump on” means the brine pump is running.

S t a r t i n 5 m i nS t a t u s5 . 5

Menu 5.3 Time between startsTime between compressor starts is set here. Thevalue is adjustable between 10 and 60 minutes.

2 0 m i nT i m e b e t w e e n s t a r t s5 . 3

N

N

Menu 5.4 Compr. starts atHow low the degree-minutes may drop before thecompressor start can take place is set here. The valueis adjustable between -5 and -250.

- 6 0C o m p r . s t a r t s a t5 . 4

N

Menu 5.1 Brine ret. temp/MINThe lowest brine temperature is set here. The value isadjustable between 12 and -11 °C. OFF is shownwhen a lower temperature is selected, this means theheat pump never gives an alarm for a low brine tem-perature.

- 4 . 0 ( - 8 ) ° CB r i n e r e t . t e m p / M I N5 . 1

N

Menu 5.2 Autoreset brinealarmAutomatic restart after an BR alarm, when the temper-ature rises 3 °C above the selected alarm level (menu5.1) for the brine return is selected here. The value isadjustable On or Off.

O f fA u t o r e s e t b r i n e a l a r m5 . 2

N

Menu 5.6 Number of startsThe accumulated number of starts with the compres-sor is shown here.

8 2N u m b e r o f s t a r t s 5 . 6

U

Menu 5.9 Comp. acc. run timeThe accumulated time that the compressor has beenin operation is shown here.

1 1 2 hC o m p . a c c . r u n t i m e5 . 9

U

Menu 5.11 Hot gas temp.The hot gas temperature is shown in this menu.

1 0 4 ° CH o t g a s t e m p .5 . 1 1

U

Menu 5.12 Liquide line temp.The fluid line temperature is shown in this menu.

4 8 . 2 ° CL i q u i d e l i n e t e m p .5 . 1 2

U

Control 49

FIGHTER 1120

Brine in/out temperature

Menu 5.13 Bulb temperatureThe suction gas temperature is shown in this menu.

5 . 0 ° CB u l b t e m p e r a t u r e5 . 1 3

U

Menu 5.15 Compressor typeNo function.

N o r m a lC o m p r e s s o r t y p e5 . 1 5

U

Menu 5.22 ReturnPressing the enter button returns you to menu 5.0.

R e t u r n5 . 2 2

Menu 6.3 ReturnPressing the enter button returns you to menu 6.0.

R e t u r n6 . 3

Menu 6.1 Room compensationA factor is selected here that determines how muchthe flow temperature is affected by the differencebetween the room temperature and the set room tem-perature. A higher value gives a greater change. Thevalue is adjustable between 0.2 and 3.0.

1 , 0R o o m c o m p e n s a t i o n6 . 1

Menu 6.2 Heating systemYou select here whether the room sensor should acti-vate system 1 (menu 2.0) or system 2 (menu 3.0).

S h u n t 1H e a t i n g s y s t e m6 . 2

Menu 7.1 DateThe current date is set.

Menu 7.3.0 Temp set back time 1Settings, e.g. for night reduction can be selected in thesub-menus to this menu.

2 0 0 3 - 0 9 - 2 4D a t e7 . 1

T e m p s e t b a c k t i m e 17 . 3 . 0

Menu 7.3.1 Heating sys per. 1The shunt system to be affected by day change period1 is selected here. When shunt group 2 is installedboth Shunt 1 and 2 can be selected.

O f f H e a t i n g s y s p e r . 17 . 3 . 1

Menu 7.3.2 Set back temp. +/-Changes to the room temperature with a day change,e.g. the night reduction is set here. The value isadjustable between -10 and 10.

0S e t b a c k t e m p . + / -7 . 3 . 2

Menu 7.2 TimeHere the current time is set.

1 3 : 3 9T i m e7 . 2

Clock

Room temp./Settings

U

U

Menu 7.3.3 - 7.3.9 Set Time Monday - SundayThe time for the day change, e.g. night reduction ischosen here.

S e t T i m e M o n d a y7 . 3 . 3

U

N

N

U

Menu 5.14 Condensor out temp.The heat medium temperature after the condensor isshown here.

C o n d e n s o r o u t t e m p . 5 . 1 4

U

U

U

Control

FIGHTER 1120

50

Menu 7.3.10 ReturnPressing the enter button returns you to menu 7.3.0

R e t u r n7 . 3 . 1 0

Clock

Menu 7.4.0 Temp set back time 2Settings, e.g. for night reduction can be selected in thesub-menus to this menu.

T e m p s e t b a c k t i m e 27 . 4 . 0

Menu 7.4.1 Heating sys per. 2The shunt system to be affected by day change period2 is selected here. When shunt group 2 is installed,both Shunt 1 and 2 can be selected.

H e a t i n g s y s p e r . 27 . 4 . 1

Menu 7.4.2 Set back temp. +/-Changes to the room temperature with a day change,e.g. the night reduction is set here. The value isadjustable between -10 and +10.

0S e t b a c k t e m p . + / -7 . 4 . 2

Menu 7.4.10 ReturnPressing the enter button returns you to menu 7.4.0

R e t u r n7 . 4 . 1 0

U

U

Menu 7.4.3 - 7.4.9 Set Time Monday - SundayThe time for the day change, e.g. night reduction ischosen here.

S e t T i m e M o n d a y7 . 4 . 3

U

U

Menu 7.5.0 Timer XHWSettings are made in the sub-menus of this menuwhen extra hot water is required on a specific day.

T i m e r X H W7 . 5 . 0

Menu 7.5.2 - 7.5.8 Extra HW Monday - SundayHere you select the period for respective days whenextra hot water should be activated. Hours and min-utes for both start and stop are shown. Equal valuesor the stop time before the start time mean that extrahot water is not activated.

0 3 : 3 0 – 0 6 : 1 5E x t r a H W M o n d a y7 . 5 . 2

Menu 7.5.9 ReturnPressing the enter button returns you to menu 7.4.0

R e t u r n7 . 5 . 9

Menu 7.8 ReturnPressing the enter button returns you to menu 7.0.

R e t u r n7 . 8

U

U

Menu 7.5.1 Timer Extra HWYou choose here whether the time setting should beOn or Off.

O f fT i m e r E x t r a H W7 . 5 . 1

U

Menu 7.7 Reset time settingsYou can choose here to reset the time settings. Auto-matic return to “Off” after one minute.

O f fR e s e t t i m e r s7 . 7

U

Control 51

Other settings

Menu 8.2.0 Operating modeSettings regarding auto mode can be made in the sub-menus to this menu.

O p e r a t i n g m o d e8 . 2 . 0

Menu 8.2.2 Winter mode temp.Here you select the average temperature when theheat pump, in auto mode, shall switch to winter mode.The circulation pump and immersion heater are acti-vated. The value is adjustable between 0 and 30 °C.

2 0 ° CW i n t e r m o d e t e m p .8 . 2 . 2

Menu 8.2.1 Summer mode temp.Here you select the average temperature when theheat pump, in auto mode, shall switch to summermode. In summer mode the circulation pump andimmersion heater are blocked, only hot water is pro-duced. The value is adjustable between 0 and 30 °C.

2 5 ° CS u m m e r m o d e t e m p .8 . 2 . 1

U

U

U

Menu 8.1.0 Display settingsSettings concerning language and menu type are seton the sub-menus to this menu.

D i s p l a y s e t t i n g s8 . 1 . 0

Menu 8.1.1 Operation mode typesThe menu type is chosen here: Normal, extended orservice.

Normal, covers the normal user's needs.

Extended, shows all menus except the servicemenus.

Service, shows all menus, returns to the previ-ous menu level 30 minutes after the last buttonwas pressed.

N o r m a lOperat ion mode types8 . 1 . 1

Menu 8.1.2 LanguageLanguage settings are made here.

E n g l i s hL a n g u a g e8 . 1 . 2

Menu 8.1.4 Light intensityThe light intensity in idle mode is set here. The valueis adjustable between 0 and 2. Idle mode occurs 30minutes after the last button was pressed.

0=shut-off, 1=low, 2=average.

2L i g h t i n t e n s i t y8 . 1 . 4

Menu 8.1.3 ContrastThe display's contrast is set here. The value isadjustable between 0 and 31.

1 5C o n t r a s t8 . 1 . 3

N

U

N

N

U

N

U

S

Menu 8.2.3 ReturnPressing the enter button returns you to menu 8.2.0

R e t u r n8 . 2 . 3

FIGHTER 1120

Menu 8.1.5 ReturnPressing the enter button returns you to menu 8.1.0

R e t u r n8 . 1 . 5

Control

FIGHTER 1120

52

Menu 8.3.0 Current limiterSettings and readings regarding the load monitor areset on the sub-menus to this menu. NOTE! No func-tion in a 1-phase installation.

C u r r e n t l i m i t e r8 . 3 . 0

Menu 8.3.5 Max elec. stepThe setting selected on the EBV card (2) knob (101) isshown here.

2M a x e l e c . s t e p8 . 3 . 5

Menu 8.3.7 ReturnPressing the enter button returns you to menu 8.3.0.

R e t u r n8 . 3 . 7

Menu 8.4 ReturnPressing the enter button returns you to menu 8.0.

R e t u r n8 . 4

Menu 8.3.4 Fuse sizeThe setting selected on the EBV card (2) knob (100) isshown here.

1 6 AF u s e s i z e8 . 3 . 4

Menu 8.3.1 Current phase 1Shows the measured current from phase 1. If thevalue falls below 2.0 A “low” is shown.

3 . 5 AC u r r e n t P h a s e 18 . 3 . 1

Menu 8.3.2 Current phase 2Shows the measured current from phase 2. If thevalue falls below 2.0 A “low” is shown.

3 . 3 AC u r r e n t p h a s e 28 . 3 . 2

Menu 8.3.3 Current phase 3Shows the measured current from phase 3. If thevalue falls below 2.0 A “low” is shown.

3 . 3 AC u r r e n t p h a s e 38 . 3 . 3

Menu 8.3.6 EBV valueThe transfer value must be defined depending on thecurrent transformers used for the EBV card. The valueis adjustable between 100 and 900 in increments of10. The setting 300 applies for the supplied currenttransformers.

3 0 0E B V v a l u e8 . 3 . 6

U

U

U

U

U

U

U

Other settings

Service menus 53

FIGHTER 1120

Menu 9.1.4 ReturnPressing the enter button returns you to menu 9.1.0.

R e t u r n9 . 1 . 4

Settings additional heat Operating settings

Menu 9.1.1 Start BIN 3 step Degree-minute deficiency before additional heat isengaged. When the power step has reduced thedegree-minutes deficiency by 100 in relation to the setstart value it is disengaged. The value is adjustablebetween -30 and -500.

- 4 0 0S t a r t B I N 3 s t e p9 . 1 . 1

Menu 9.1.3 Add heat run timeThe accumulated running time for the immersionheater since the first start is shown.

1 8A d d h e a t r u n t i m e9 . 1 . 3

S

S

Menu 9.1.2 Diff. BIN 3 step Difference between engaging and disengaging theelectric steps. The value is adjustable between 0 and -100.

- 1 0 0D i f f . B I N 3 s t e p 9 . 1 . 2

S

Menu 9.1.0 Add. heat settingsSettings regarding additional heat in the heat pumpare made from the sub-menus to this menu. Applies todocking options 1, 2 and 4.

A d d . h e a t s e t t i n g s9 . 1 . 0

S

Menu 9.2.0 Operating mode setSettings regarding additional heat, floor drying and areturn to the factory settings can be made on the sub-menus in this menu.

O p e r a t i n g m o d e s e t9 . 2 . 0

Menu 9.2.1 Max HW tempHere the maximum boiler temperature is shown. Thevalue is selected on the load monitor card using knob(102).

6 5 ° CM a x H W t e m p9 . 2 . 1

S

S

Menu 9.2.2 Maximal deviation from the calculatedflow heat pump

When the current flow temperature deviates from theset value compared to that calculated, the heat pumpis forced to stop/start irrespective of the degree-minute figure.

When the current flow temperature exceeds the cal-culated flow by the set value, the degree-minute figureis set to 1. The compressor stops when there is only aheating requirement.

When current flow temperature falls below the calcu-lated flow by the set value the degree-minute figure isset to -60. This means the compressor will start. Whenthe value also falls below menu 9.2.3, the degree-minute figure can be set to -400. The value isadjustable between 3 and 25 °C.

1 3 ° CF l o w d i f f H P9 . 2 . 2

S

Menu 9.2.3 Maximal deviation from the calculatedflow addition

When the current flow temperature drops below that cal-culated by the set value, plus the value from menu 9.2.2,the degree-minute value is set to -400. This means thatthe additional heat can be engaged directly. The value isadjustable between 1 and 8 °C.

3 ° CD i f f H P A d d9 . 2 . 3

S

Service menus

FIGHTER 1120

54

Operating settings

Menu 9.2.5 System 2 PresentThis menu is used to select “On” or “Off” depending onwhether you have shunt group 2 (accessory ESV 20needed).

O f fS y s t e m 2 P r e s e n t 9 . 2 . 5

Menu 9.2.6 Room disp PresentNo function

O f fR o o m d i s p P r e s e n t9 . 2 . 6

S

S

Menu 9.2.7 Circ. pump 1Here you set whether heat medium pump should runconstantly in “Summer mode”. The value is adjustable“On” or “Off”. Changes to “Off” with a restart.

O f fC i r c . p u m p 1 9 . 2 . 7

S

Menu 9.2.8 Circ. pump 2Here you set whether heat medium pump 2 should runconstantly in “Summer mode”. The value is adjustable“On” or “Off”. Changes to “Off” with a restart.

O f fC i r c . p u m p 29 . 2 . 8

S

Menu 9.2.9.0 Floor drying setSettings for the floor drying program are made in thesub-menus to this menu.

F l o o r d r y i n g s e t9 . 2 . 9 . 0

S

Menu 9.2.9.1 Floor dryingThe floor drying program is chosen from this sub-menu. The options are “Prog 1 On”, “Prog 2 On” or“Off”. The heat pump must be in “Winter mode”,selected with the operating mode button. Electric boil-er mode, Menu 9.2.4 can be used together with floordrying, for example, when the heat source is notinstalled.

In “Prog 1 On”, menus 9.2.9.2 - 9.2.9.5 are shown.After time period 1 a switch is made to time period 2followed by a return to the normal settings.

In “Prog 2 On”, a fixed program over 11 days is fol-lowed. The flow temperature is increased from 20 to45 °C for 4 days, it then remains constant for 3 days.The temperature then steps down to 25 °C for 4 days,and then returns to the normal settings.

O f fF l o o r d r y i n g9 . 2 . 9 . 1

Menu 9.2.9.2 Numb. of days per. 1Selection of the number of days in period 1.

The value is adjustable between 1 and 5.

3 N u m b . o f d a y s p e r . 19 . 2 . 9 . 2

Menu 9.2.9.3 Temp. period 1Selection of the flow temperature in period 1.

The value is adjustable between 15 and 50 °C.

2 5 ° CT e m p . p e r i o d 19 . 2 . 9 . 3

S

S

S

Menu 9.2.9.4 Numb. of days per. 2Selection of the number of days in period 2.

The value is adjustable between 1 and 5.

1 N u m b . o f d a y s p e r . 29 . 2 . 9 . 4

Menu 9.2.9.5 Temp. period 2Selection of the flow temperature in period 2.

The value is adjustable between 15 and 50 °C.

4 0 ° CT e m p . p e r i o d 29 . 2 . 9 . 5

S

S

Menu 9.2.4 Add heat only (el. boiler)Only additional heat is activated when “On” is shownon the display, otherwise “Off” is shown. When onlyadditional heat is activated, the immersion heaterrespective circulation pump cannot be blocked withthe operating mode button. NOTE! Select “Off” todeactivate only additional heat and select therequired operating mode using the operatingmode button.

O f fA d d h e a t o n l y9 . 2 . 4

S

Service menus 55

FIGHTER 1120

Menu 9.2.10 Pool control On/OffSettings whether pool control should be “On” or “Off”.Basic setting is Off.

O f fP o o l c o n t r o l9 . 2 . 1 0

S

Operating settings

Menu 9.2.9.6 ReturnPressing the enter button returns you to menu 9.2.9.0

R e t u r n9 . 2 . 9 . 6

S

Menu 9.2.11 Brine pressostatYou set here whether an external brinepressostat/load monitor is connected to the load moni-tor card.

O f fB r i n e p r e s s o s t a t9 . 2 . 1 1

S

Menu 9.2.12 Brinepump 10 daysThe brine pump can be active for 10 days when theinstallation is started. The basic setting is “Off”.

O f fB r i n e p u m p 1 0 d a y s9 . 2 . 1 2

S

Menu 9.2.13.0 DockingSettings regarding external docking can be made inthe sub-menus to this menu. NOTE! These settingsmust be confirmed by switching the heat pump offand on within 30 minutes.

D o c k i n g9 . 2 . 1 3 . 0

S

Menu 9.2.13.1 Docking typeThis menu is used to select the docking option:

Select 1 for docking to an electric boiler.

Select 2 for docking to a gas boiler.

Select 3 for docking to an oil boiler.

Select 4 for fixed condensing

The value is adjustable between -1 and 5.

1D o c k i n g t y p e9 . 2 . 1 3 . 1

S

Menu 9.2.13.2 Immersion heat typeBinary 3 step: Selected when ETS-12/ETS 121 is con-nected.

Linear 3 step: Selected with an external electric boiler.

Binary 7 step: Selected with an external electric boiler.

Off: Preselected

O f fI m m e r s i o n h e a t t y p e9 . 2 . 1 3 . 2

S

Menu 9.2.13.3 Hot waterThis menu is used to select whether there is a hotwater heater or not. When “On” is selected Menu 1.0and its sub-menus become visible.

The value is adjustable “On” or “Off”.

O f fH o t w a t e r9 . 2 . 1 3 . 3

S

Menu 9.2.13.4 Boiler Temp/act mixvThis menu shows the boiler temperature and here youselect at which temperature the oil shunt starts to work(open).

4 0 ( 5 5 ) ° CB o i l e r t e m p / a c t m i x v9 . 2 . 1 3 . 4

S

Service menus

FIGHTER 1120

56

Operating settings

Menu 9.2.13.7 ReturnPressing the enter button returns you to menu 9.2.13

R e t u r n9 . 2 . 1 3 . 7

Menu 9.2.13.5 Start value OilPowerIn this menu you can set the number of degree min-utes when the oil addition should start to work. Appliesto docking option 3.

The value is adjustable between -30 and -500

- 4 0 0S t a r t v a l u e O i l P o w e r9 . 2 . 1 3 . 5

S

Menu 9.2.13.6 Oil burner onIn this menu you set the running time for the oil burn-er.

The value can be set between 0 and 12 hours.

1 2 hO i l b u r n e r o n9 . 2 . 1 3 . 6

S

Quick start

Menu 9.4.1.26 ReturnPressing the enter button returns you to menu 9.4.0.

R e t u r n9 . 4 . 1 . 2 6

Menu 9.3 Quick startWhen “Yes” is selected, the heat pump starts within 5minutes. Returns automatically to “No”, which indi-cates that quick start is activated.

N oQ u i c k s t a r t9 . 3

S

TEST Force driven operation

Menu 9.4.0 TEST/Forced operat.Test of outputs, automatic return after 30 minutes.Only for service personnel.

T E S T / F o r c e d o p e r a t .9 . 4 . 0S

Menu 9.4.1.0 Forced operationSelectable between “On” or “Off”.

O f fF o r c e d o p e r a t i o n9 . 4 . 1 . 0

S

Menu 9.4.1.1 - 9.4.1.25 Manual test of relays, opto and AD.

R E 19 . 4 . 1 . 1

S

Menu 9.2.15 RCU PresentNo function.

O f fR C U P r e s e n t9 . 2 . 1 5

S

Menu 9.2.17 ReturnPressing the enter button returns you to menu 9.2.0

R e t u r n9 . 2 . 1 7

Menu 9.2.14 Factory settingReturn to the factory settings in FIGHTER 1120, “Yes”or “No”. When returning to the factory settings the lan-guage switches to English.

N oF a c t o r y s e t t i n g9 . 2 . 1 4

S

Menu 9.2.16 Cooling systemHere you select whether HPAC or PKM is installed.

O f fC o o l i n g s y s t e m9 . 2 . 1 6

S

Service menus 57

FIGHTER 1120

Alarm log

Menu 9.5.0 - 9.8.0 Log 1 - Log 4The alarm logs are shown in the sub-menus of thismenu. Log 1 is the last alarm, log 2 the next last, etc.

L o g 1 .9 . 5 . 0

Menu 9.10 ReturnPressing the enter button returns you to menu 9.0.

R e t u r n9 . 5 . 1 7

Menu 9.5.17 ReturnPressing the enter button returns you to menu 9.5.

R e t u r n9 . 1 0

S

Menu 9.5.1 Time

Menu 9.5.2 Alarm type

Alarm type Cause

1 High pressure pressostat

2 Low pressure pressostat

3 Motor protection

6 Temperature limiter

7 Low Brine temperature

8 BR level switch/pressostat

9 Flow sensor

10 Flow sensor 2

12 Hot water sensor

14 High return temperature

15 Boiler sensor

16 Pool sensor

19 Outside sensor

20 Return sensor

21 Alarm cond VB

22 Maxtemp cond VB

Menu 9.5.3 Charging type

Menu 9.5.4 Brine in

Menu 9.5.5 Brine out

Menu 9.5.6 Outdoor temp.

Menu 9.5.7 Flow temp.

Menu 9.5.8 Return temp.

Menu 9.5.9 Hot water temp.

Menu 9.5.10 Hot gas temp.

Menu 9.5.11 Compr. time

Menu 9.5.12 Electric b. time

Menu 9.5.13 Relay register 1

Menu 9.5.14 Relay register 2

Menu 9.5.15 External input

Menu 9.5.16 Reset log

Menu 9.9 Reset alarmAlarms are reset in this menu.

R e s e t a l a r m9 . 9

Dealing with malfunctions

FIGHTER 1120

58

Alarm LPThis information is shown when the low pressureswitch in FIGHTER 1120 has tripped. The compressoris blocked and FIGHTER 1120 switches to wintermode, only additional heat without hot water.

This may be due to: ■ Bad circulation in collector system due to inferior

venting/low pressure or ice (if ice has formed thebrine pump (35) will be warm).

■ Brine pump (35) malfunction.■ Iced evaporator due to too low antifreeze concen-

tration.■ Leakage in the collector circuit.

The background lighting on the display flashes with analarm and the following information is shown depend-ing on the fault. An alarm log is created with eachalarm containing a number of temperatures, times andthe status of outputs. The four alarms are saved onmenu 9.5.0 - 9.8.0. The following alarms block hot water charging to drawattention to the alarm. The operating mode switches towinter mode and additional heat engages.Alarm HP Alarm LPAlarm MP Alarm BRAlarm Flow 2 Alarm HWBrine levelWhen the alarm can not be reset using the mainswitch, the operating mode “Add heat only” can beactivated in menu 9.2.4 to give hot water again.

- - A L A R M L P - -1 . 0

Alarm HPThis information is shown when the high pressureswitch in FIGHTER 1120 has tripped. The compressoris blocked and FIGHTER 1120 switches to wintermode, only additional heat without hot water.

This may be due to:■ No or low flow on the brine pump (16).■ Closed thermostat valves.■ Too high value in menu 1.5 and/or menu 1.7 for the

stop temperature. The alarm temperature varieswith the heat pump's operating conditions.

- - A L A R M H P - -1 . 0

Brine level (accessory)Shows that the level or pressure in the collector circuitis low. The compressor is blocked and FIGHTER1120 switches to winter mode, only additional heatwithout hot water.

This may be due to:■ Leakage in the collector circuit.

- B R I N E L E V E L -1 . 0

Alarm MP Shows when the motor cut-out on the compressor hastripped. The compressor is blocked and FIGHTER1120 switches to winter mode, only additional heatwithout hot water.

This may be due to: ■ Dropped phase due to tripped fuses. ■ Incorrect setting on the motor cut-out.

- - A L A R M M P - -1 . 0

- - A L A R M B R - -1 . 0

Alarm BRShows when the brine's return temperature is lowerthan the set value in menu 5.1. Factory setting “-8”.Not indicated when menu 5.2 is set to automaticreturn “YES”. The compressor is blocked and FIGHT-ER 1120 switches to winter mode, only additional heatwithout hot water.This may be due to: ■ Too low flow on the brine.■ Temperature sensor damaged/missing.

If the operating disturbance cannot be rectified by means of the above, an installation engineer should be called.

Alarm indications on the display

The following alarms stop the compressor and brinepump. The alarms can only be acknowledged byswitching off the heat pump for a few seconds andthen starting it again. This is done using switch (8).

Dealing with malfunctions 59

FIGHTER 1120

Alarm indications on the display

A L A R M H WThis information is shown when a fault on the hotwater temperature sensor has been registered.FIGHTER 1120 is force-run solely for hot watercharging and automatic mode is engaged. The alarmmay be due to:■ Defective sensor or broken sensor cable.

- - A L A R M H W - -1 . 0

Alarm condThis information is shown when the measured valueon the fluid line sensor is missing.■ Broken cable to the fluid line sensor.

- - A L A R M C O N D - -1 . 0

Alarm FlowThis information is shown when the measured valueon the flow line sensor is missing.■ Broken cable to the flow line sensor.

- A L A R M F L O W -1 . 0

Alarm Flow 2This information is shown when the measured valueon the flow line sensor 2 is missing.■ Broken cable to the flow line sensor 2 (shunt group

2).

- A L A R M F L O W 2 -1 . 0

Boiler sensorThis information is shown when docking option 3 isselected and:■ Boiler sensor is defective/not connected or the

cable to the boiler sensor is broken.

B O I L E R S E N S O R1 . 0

If the operating disturbance cannot be rectified by means of the above, an installation engineer should be called.

Condensor Out Sensor This information is shown when there is a fault on thesensor (141) between the condensor and immersionheater.

CONDOUTSENSOR1 . 0

The following sensor alarms remove their control func-tion. Rectify the fault and acknowledged the alarm byswitching off the heat pump for a few seconds andthen starting it again.

Outdoor sensor This information is shown when the outside sensor isnot connected.■ Broken cable, no connected or defective sensor.

O U T D O O R S E N S O R1 . 0

Return sensor This information is shown when the Return sensor isnot connected.■ Broken cable, no connected or defective sensor.

R E T U R N S E N S O R 1 . 0

Pool sensor This information is shown when Pool control in menu9.2.10 is set to “On” and no sensor is connected.■ Broken cable, no connected or defective sensor.

- P O O L S E N S O R -1 . 0

Dealing with malfunctions

FIGHTER 1120

60

If the operating disturbance cannot be rectified by means of the above, an installation engineer should be called.

Alarm indications on the display

H I G H R E T U R N T E M P .1 . 0

High return temp.This information is shown when the return sensor onthe heating medium measures a higher value thanthat set in menu 2.7. or higher than 58 °C on thereturn pipe when hot water charging.

The following alarms are automatically reset when thetemperature has increased/reduced by 2 °C

Max condensor flow tempThis information is displayed when the flow tempera-ture between the condensor and immersion heaterreaches 65 °C or more.

M A X C O N D F L T E M P 1 . 0

Dealing with malfunctions 61

FIGHTER 1120

Cause: Incorrect setting of “Curve slope” and/or“Heating curve offset”.

Action: Adjust the setting.

Cause: Large amount of hot water drawn off.Action: Wait until the water heater reheats.

Cause: Compressor and/or immersion heater doesnot heat up.

Action: Check and replace any blown circuit andmain fuses.

Cause: Too low start temperature setting on thecontrol system.

Action: Adjust the start temperature setting in menu1.4.

Cause: Possible earth circuit-breaker tripped.Action: Reset the earth circuit-breaker, if the earth

circuit-breaker trips repeatedly, call an elec-trician.

Cause: Compressor and immersion heater do notheat up.

Action: Check and replace any blown circuit andmain fuses.

Cause: The compressor does not start because of atoo low value set on the heating curve.

Action Check and possibly raise the “Heating curveoffset” (knob on the front panel) or “Curveslope”.

Cause: The compressor standstills due to the inter-nal overheating protection tripping.

Action: Automatic resetting after cooling for a fewhours.

Cause: Possible earth circuit-breaker tripped.Action: Reset the earth circuit-breaker, if the earth

circuit-breaker trips repeatedly, call an electri-cian.

Low hot water temperature orno hot water

Low room temperature

In the event of malfunction or operating disturbances first check the points below:

NOTE! As FIGHTER 1120 can be connectedto a large number of external units

even these should be checked.

High room temperature

If the operating disturbance cannot be rectified by means of the above, an installation engineer should be called.

Dealing with malfunctions

FIGHTER 1120

62

Ifthe operating disturbance cannot be rectified by means of the above,an installation engineer should be called.

Close the shut-off valves in heating medium system.Now open the drain valve (76). A small amount ofwater runs out, however, to fully empty the heatingmedium side requires the connector that joins theheating medium side and the connection on the heatpump “VB-flow” to be loosened a little to allow air toenter so the remaining water can run out. When theheating medium is empty the requisite service can becarried out.

When replacing the brine pump or drive side or whencleaning the pump, the shut-off valves in the collectorsystem should be closed. The hose between the topof the evaporator and the brine pump is loosened onthe evaporator. The loose hose end can now be bentdown and emptied in a small bowl. Now loosen theconnection on “Brine-in” a little to allow air to enter sothe heat pump's collector side is emptied completely.When the circuit is empty the requisite service can becarried out.

Draining, collector sideDraining, heat medium side

■ Shut down FIGHTER 1120 by turning the switch(8) to “0”.

■ Open the service cover.

■ Loosen the venting screw with a screwdriver. Holda cloth around the screwdriver blade as a certainamount of water may run out.

■ Insert a screwdriver and turn the pump rotor.

■ Screw in the venting screw.

■ Start FIGHTER 1120 and check whether the circu-lation pump runs.

It is usually easier to start the circulation pump withFIGHTER 1120 running, switch (8) set to “1”. If help-ing the circulation pump to start is performed withFIGHTER 1120 running, be prepared for the screw-driver to jerk when the pump starts.

Helping the circulation pump to start

NOTE! The product's serial number

should always be stated with allcorrespondence with NIBE._ _ _ _ _ _ _ _ _ _ _ _ _ _

Luftningsskruv

16

LE

K

GR

UN

DFO

SType

UP

S25 -

60

130

P/N

:59526447

230V

-

HE

JS

AN

PC

;0017N

IBD

K50H

z

IP 44

TF

110

Cla

ss H

Max. 1

0bar

2.5

uF

45

0.2

065

0.3

090

0.4

0

1m(A

)P,

(W)

Venting screw

Component positions 63

FIGHTER 1120

230 V -5

230 V -8, -12

101

100

102

14

34

2

6

26

9

10

67

25

8

3

3229 1

61

97

69

101

100

102

34

2

14

6 12

9

26

61

11

10

67

25

8

3

3229 1

68 69

Component positions64

FIGHTER 1120

3 x 230 V

3 x 400 V

101

100

102

34

2

6

9

61

26

69

10

67

25

8

3

3229

68

1

LE

K

29 1 32

2

102

100

101

6 60

9

26

61

97

10

67

25

83

69

164165

1) 15,17 kW

1)

Component positions 65

FIGHTER 1120

The figure shows the heat pumpwith accessories.

LE

K

95

8

1

KE

L

4 86 71 70 895

94

35

77

76

16

96

24

87

141

LE

K

4118

17

111

110

27

65

7

48

112

42

33

153

LE

K

41

18 110

33

17

27

42

7

48

65

153

112

111

41

18

LE

K

111

112

33

17

27

42

7

48

65

153

110

FIGHTER 1120-15, 17 kW 3x400 V

FIGHTER 1120-12 kW 3x400 V

FIGHTER 1120- 5, 6, 8, 10 kW 3x400 VFIGHTER 1120- 6, 8, 10, 12, 15, 17 kW 3x230 VFIGHTER 1120- 5, 8, 12 kW 1x230 V

List of components

FIGHTER 1120

66

1 Miniature circuit breaker

2 EBV-card, Load monitor card

3 * Thermostat

4 Brine connection, in (f)

5 Brine connection, out (r)

6 Terminal block, -X6

7 Service connection, high pressure

8 Switch, 1 – 0 –

9 Terminal block, incoming electricity, -X9

10 * Contactor, immersion heater step 1

11 Starting capacitor, compressor

12 Start relay

14 Operating condensor, compressor

15 ** Outside temperature sensor

16 Heating medium pump

17 Evaporator

18 Condenser

19 * Shuttle valve

24 * Immersion heater

25 * Temperature limiter

26 Motor protection

27 Compressor

29 Relay card with power supply unit

32 Display unit

33 High pressure pressostat

34 CPU-unit, control system

35 Brine pump

41 Low pressure pressostat

42 Service connection, low pressure

48 Expansion valve

52 ** Safety valve, collector side

60 EMC-filter

61 Suppression capacitor

63 ** Particle filter

65 Drying filter

67 * Contactor, immersion heater step 2

69 Contactor

70 Connection, heating flow

71 Connection, heating return

76 Drainage for heating system

77 Venting valve, collector system

85 ** Level vessel

86 Temperature sensor, “BR-f”, brine in

87 Temperature sensor, “BR-r”, brine out

88 Temperature sensor, hot water jacket

89 Temperature sensor, “VB-Flow”, flow

94 Temperature sensor, “VB-r”, return

95 Type plate

96 Type plate, cooling section

97 Soft-start relay

100 Knob, setting “Fuse”

101 Knob, setting “Max electrical output”

102 Knob, “Max boiler temperature setting”

110 Temperature sensor, hot gas

111 Temperature sensor, fluid pipe

112 Temperature sensor, suction gas

141 Temperature sensor, condensor heat medium

153*** Compressorheater

164 Phase sequence monitor

165*** Terminal block X221, compressorheater

* Accessories** Enclosed*** 10, 12, 15, 17 kW 3x400 V

The component list refers to all the different types of heat pump. See each component position picture.

Dimensions 67

5 4 71 70

598

525 525

625

A BI II III I II

5 0 . 0 CVa rm va t t e n t e m p.

13.431.0

A

A BI II III I II

5 0 . 0 CVa rm va t t e n t e m p.

13.431.0

A

30 –

50

1000

75

198100100 100

30

100

67

130

An area of 800 mm isrequired in front ofthe heat pump forservice work.

Leave space free tothe right of the heatpump for servicing.

Dimensions and setting-out coordinates

FIGHTER 1120

Enclosed kit

FIGHTER 1120

68

LE

K

Insulation tapePart no 025 910

Aluminium tapePart no 025 179

Tubes forsensors

Part no 408 017

LE

K

LEK

LEK

NIBE AB

Utetemperatur givare

Outdoor temperature sensor

Aussentemperatur fühler

Artikel 018764

Level vessel with safetyvalve

Part no. (85) 024 413Part no. (52) 024 684

Temperature sensors withprobes

Part no 418 027

Particle filter F1120 4-8.5 kW2 (R25) F1120 10-15 (kW)1 (R25)1 R32)

Outside temperaturesensor

Part no 018 764

63

85 52

15

LEK

LEK

LEK

Current transformerPart no 018 569

Conex connectorsF1120 4-8.5 kW4 x (ø28 x R25 int.) Part no 024 035F1120 10-15 (kW)2 x (ø28 x R25 int.) Part no 024 0352 x (ø35 x R32 int.) Part no 424 283

Accessories 69

FIGHTER 1120

Electrical addition ETS 12 (3-phase)Part no 089 399

Electrical addition ETS 121 (1-phase)Part no 089 419

LEK

Hot water control VST 11Part no 089 152

LEK

Shuttle valveLEK

Exhaust air module FLM 30Part no 089 268

3 25

10 67

24

19

Filling set KB R25/R32

including insulationPart no 089 368 (max 10 kW)Part no 089 971 (max 30 kW)

LEK

LE

K

213

4

5678 9

Room sensor RG 10Part no 018 433

Extra shunt ESV 20Part no 089 317

LEK

LE

K

GR

UN

DF

OS

Typ

eU

PS

25 -

60

130

P/N

:59

526447

230V

-

HE

JS

AN

PC

;0017N

IBD

K50H

z

IP 44

TF

110

Cla

ss H

Max. 1

0bar

2.5

uF

45

0.2

065

0.3

090

0.4

0

1m(A

)P,

(W)

Pool 11Part no 089 435

Communication unitRCU 10

Part no 418 925

LE

K

Auxiliary relay HR 10Part no 089 423

LEK

10

15 20

2530°C

Room thermostat RT 10Part no 418 366

Level monitor NV 10Part no 089 315

LEK

PKMPassive cooling module

PKM 10 (intended for 5 - 8 kW)Part no 089 397

PKM 20 (intended for 10 - 17 kW)Part no 089 398

Bracket pack FLM 30Part no 089 304

Technical specifications

FIGHTER 1120

70

Weight (kg) 170 190 200

Type 5 8 12

Difference pressostat LP (bar) +1,5

Starting current, compressor (A) 39 24 33

Max oper. current incl. immersion heater 4 kW ***(A) 26,7 34,0 40,9

Output, heat medium pump (W) 75 75 170

Refrigerant quantity (R407C) (kg) 1,4 2,2 2,4

Pressure drop, evaporator (kPa) 22 19 19

Heating medium flow (l/s) 0,10 0,19 0,31

Max temperature (flow- /return pipe) (°C) 70****/58 60/50 60/50

Difference pressostat HP (bar) -7

Connection brine o.d. Ø (mm) 28 28 35

Max pressure, collector system (bar) 3

Operating voltage (V) 1 x 230 V + PE 50 Hz

Max operating current, compressor (A) 9,0 15,0 21,5

Max oper. current incl. immersion heater 6 kW ***(A) 35,4 42,7 49,6

Output, brine pump (W) 130 170 250

Connection, heating medium ext (mm) 28

Brine flow (l/s) 0,25 0,53 0,65

Available pressure, collector system (kPa) 45 59 70

Pressure drop, condensor (kPa) 2,7 2,4 3,1

Enclosure class IP 21

Part No 689 400 689 893 689 894

Cut-out value pressostat HP (bar) 29 27 27

Operating temperature collector system (°C) -5 – +20

Cut-out value pressostat LP (bar) 1,5

Delivered/supplied power* at 0/35 °C ** (kW) 4,8/1,05 8,3/1,8 11,5/2,5

IP 21

* Compressor output only.** Regards brine in temperature / heat medium flow temperature in accordance with EN 255.*** Accessory ETS 121.**** The compressor produces up to 65 °C, the rest is obtained using additional heating.

Delivered/supplied power* at 0/50 °C ** (kW) 3,8/1,2 7,8/2,5 10,7/3,6

Technical specifications 230 V

Technical specifications 71

FIGHTER 1120

Technical specifications 3 x 230 V (only applies to Norway)

Weight (kg) 175 195 200 215 225 230

Type 6 8 10 12 15 17

Difference pressostat LP (bar) +1,5

Starting current, compressor (A) 60 115 138 145 157 165

Max oper. current incl. immersion heater 4 kW *** (A) 27,3 29,3 31,3 34,9 37,9 41,9

Output, HC pump (W) 75 75 75 170 170 170

Refrigerant quantity (R407C) (kg) 1,7 2,2 2,4 2,4 2,5 2,6

Pressure drop, evaporator (kPa) 21 23 23 19 25 22

Heating medium flow (l/s) 0,13 0,18 0,22 0,26 0,31 0,36

Max temperature (flow- /return pipe) (°C) 60/50

Difference pressostat HP (bar) -7

Connection Brine male Ø (mm) 28 28 28 35 35 35

Max pressure, collector system (bar) 3

Max operating current, compressor (A) 11 13 15 18 21 25

Max oper. current incl. immersion heater 6 kW *** (A) 31,3 33,3 35,3 38,9 41,9 45,9

Output, Brine pump (W) 130 170 170 250 250 250

Connection heating medium male Ø (mm) 28

Brine flow (l/s) 0,35 0,48 0,58 0,65 0,75 0,86

Available pressure, collector system (kPa) 40 58 53 70 65 60

Pressure drop, condensor (kPa) 2,6 3,4 3,2 4,4 3,1 4,1

Enclosure class IP 21

Part No 689 791 689 792 689 793 689 794 689 795 689 796

Cut-out value pressostat HP (bar) 27

Operating temperature collector system (°C) -5 – +20

Cut-out value pressostat LP (bar) 1,5

Delivered/supplied power* at 0/35 °C ** (kW) 6.0/1.3 8.8/1.9 10.3/2.2 11.7/2.5 14.6/3.1 17.0/3.7

IP 21

* Compressor output only.** Regards brine in temperature / heat medium flow temperature in accordance with EN 255.*** Accessory ETS 12.

Delivered/supplied power* at 0/50 °C ** (kW) 4.8/1.5 7,1/2,2 8,5/2,5 9,9/2,9 12,6/3,6 14,8/4,3

Operating voltage (V) 3 x 230 V + PE 50 Hz

Technical specifications72

Technical specifications 3 x 400 V

Enclosure class IP 21

Type 6 8 10 12 15 17

Cut-out value pressostat LP (bar) 1,5

Max operating current, compressor (A) 4,5 5,5 7 10 13,1 14,8

Max oper. current incl. immersion heater 9 kW 4) (A) 17,9 19,8 21,0 22,9 26,0 27,7

Brine flow (l/s) 0,35 0,48 0,58 0,69 0,79 0,85

Pressure drop, condensor (kPa) 2,6 3,4 3,2 2,4 2,8 3,4

Cut-out value pressostat HP (bar) 29

Output, Brine pump (W) 130 170 170 250 250 250

Starting current, compressor (A) 21 23 30 22 37 46

Max oper. current incl. immersion heater 6 kW 4) (A) 13,6 15,5 16,7 18,6 27,7 23,4

Output, HC pump (W) 75 75 75 170 170 170

Connection Brine male Ø (mm) 28 28 28 35 35 35

Refrigerant quantity (R407C) (kg) 1,8 2,2 2,4 2,1 2,3 2,3

Pressure drop, evaporator (kPa) 6,8 7,9 8,1 15 18 20

Heating medium flow (l/s) 0,13 0,18 0,22 0,27 0,36 0,40

Difference pressostat LP (bar) +1,5

Weight (kg) 175 195 200 208 221 229

Max pressure, collector system (bar) 3

Difference pressostat HP (bar) -7

Delivered/supplied power1) at 0/35 °C 2) (kW) 6,43/1,30 8,22/1,66 9,98/1,98 11,6/2,4 15,4/3,4 16,8/3,84

IP 21

1) Compressor output only.2) Regards brine in temperature / heat medium flow temperature in accordance with EN 255.3) Regards brine in temperature / heat medium flow temperature in accordance with EN 14511.4) Accessory ETS 12.5) The compressor produces up to 65 °C, the rest is obtained using additional heating.

Delivered/supplied power1) at 0/50 °C 2) (kW) 5,22/1,49 6,97/1,93 8,66/2,37 10,8/3,1 14,8/4,4 16,2/4,9Delivered/supplied power1) at 0/45 °C 3) (kW) 10,5/3,0 14,4/4,3 15,7/4,8

Part no. 689 401 689 402 689 403 689 694 689 695 689 696

Connection heating medium male Ø (mm) 28

Operating temperature collector system (°C) -5 – +20

Available pressure, collector system (kPa) 40 58 53 62 53 48

Operating voltage (V) 3 x 400 V + N + PE 50 Hz

FIGHTER 1120

Max temperature (flow- /return pipe) 5) (°C) 70/58

PL

NO

NL

FI

DK

DE

CZ

NIBE – Haato, Valimotie 27, 01510 VantaaPuh: 09-274 697 0 Fax: 09-274 697 40 E-mail: [email protected] www.haato.fi

NIBE-BIAWAR Sp. z o. o. Aleja Jana Pawła II 57, 15-703 BIAŁYSTOKTel: 085 662 84 90 Fax: 085 662 84 14 E-mail: [email protected] www.biawar.com.pl

NIBE AB, Jerikoveien 20, 1067 OsloTel: 22 90 66 00 Fax: 22 90 66 09 E-mail: [email protected] www.nibe-villavarme.no

NIBE Energietechniek B.V. Postbus 2 4797 ZG WILLEMSTAD NBTel: 0168 477722 Fax: 0168 476998 E-mail: [email protected] www.nibeboilers.nl

Vølund Varmeteknik, Filial af NIBE AB, Brogårdsvej 7, 6920 VidebækTel: 97 17 20 33 Fax: 97 17 29 33 E-mail: [email protected] www.volundvt.dk

NIBE Systemtechnik GmbH, Am Reiherpfahl 3, D-29223 CelleTel: 05141/7546-0 Fax: 05141/7546-99 E-mail: [email protected] www.nibe.de

NIBE CZ, V Zavetri 1478/6, CZ-170 00 Prague 7Tel: 0266 791 796 Fax: 0266 791 796 E-mail: [email protected] www.nibe.com

NIBE AB Sweden, Box 14, Järnvägsgatan 40, SE-285 21 MarkarydTel: +46-(0)433-73 000 Fax: +46-(0)433-73 190 E-mail: [email protected] www.nibe.com

GBNIBE Energy Systems LtdTel: 0845 095 1200 Fax: 0845 095 1201 E-mail: [email protected] www.nibe.co.uk


Top Related