7847i Internet Communication Module

Post on 14-Jan-2016

104 views 3 download

description

7847i Internet Communication Module. Agenda. Introduction Overview of the 7847i / 7847iE Communication Path Features Summary of connections Before You Leave the Shop Network Connectivity Programming the Device Registering the Device Updating Code. Introduction. - PowerPoint PPT Presentation

transcript

7847i Internet Communication Module

Honeywell Proprietary

Honeywell.com

27847i

Agenda

• Introduction• Overview of the 7847i / 7847iE Communication Path• Features• Summary of connections• Before You Leave the Shop• Network Connectivity• Programming the Device• Registering the Device• Updating Code

Honeywell Proprietary

Honeywell.com

37847i

Introduction

The 7847i delivers highly secure, reliable, Internet communication of alarm data while the 7847i-E is suitable for enterprise private network applications using local LAN or point to point connections.

Honeywell Proprietary

Honeywell.com

47847i

Applications

• Banking Institutions• Jewelry Industry• Federal Government• Medical• Industrial• Residential

Honeywell Proprietary

Honeywell.com

57847i

Features

•Secure IP Reporting •Dialer Capture Ready •Universal Control Panel Compatibility •Full Contact ID or ADEMCO High Speed Reporting •Six Input Zones •Tamper Protected Enclosure •Remote Services Capability* •Network Friendly •Ease of installation •Upload/Download

Honeywell Proprietary

Honeywell.com

67847i

Wiring the 7847i/7847i-E

Wiring connections for ECP or 4204 modes

Wiring for ECP, 4204 and Two-4204 Modes

Connect the 7847i/7847i-E to a compatible Honeywell VISTA control panel's ECP terminals,in parallel with keypads and other peripheral devices

Honeywell Proprietary

Honeywell.com

77847i

Wiring the 7847i/7847i-E

Wiring a LynxR-I for ECP Mode

To trip the zone on the 7847i/7847i-E in V+ trigger mode, the positive triggering voltage fromthe control panel must be within 2.0V-14V.

Note:•Trigger levels above this range may cause permanent damage to the unit.•Trigger levels below this range result in unreliable operation.

To trip the zone on the 7847i/7847i-E in V- trigger mode, the negative triggering voltagemust be less than 1.0V.

Honeywell Proprietary

Honeywell.com

87847i

Wiring the 7847i/7847i-E

Wiring for Zone Trigger Mode

To trip the zone on the 7847i/7847i-E in V+ trigger mode, the positive triggering voltage from the control panel must be within 2.0V-14V.

Note:•Trigger levels above this range may cause permanent damage to the unit.•Trigger levels below this range result in unreliable operation.

To trip the zone on the 7847i/7847i-E in V- trigger mode, the negative triggering voltage must be less than 1.0V.

Honeywell Proprietary

Honeywell.com

97847i

Wiring the 7847i/7847i-E

Primary power for the 7847i/7847i-E is provided by the auxiliary power output of the control panel 9.6V –13.8V, typical, or other external power source.

Zone 1 Input to a LynxR Trigger Output

Zone 1 Input for EOL Supervised N.O./N.C. Triggers

Honeywell Proprietary

Honeywell.com

107847i

Select Programming Option

From AlarmNet Direct• If the device is already in

service go to:

• If the device is new, choose the appropriate selection:

Honeywell Proprietary

Honeywell.com

117847i

For A new account enter the following:

• Primary City ID• Primary CSID• Primary subscriber• Supervision rate• MAC ID• MAC CRC

Then select:• Enable remote services• Advanced programming

Enabling Remote Services

Remember to enable here if using Total Connect

Honeywell Proprietary

Honeywell.com

127847i

Edit Mode

• Status of the device is displayed.

• With Edit displayed in the Actions box Click GO.

Honeywell Proprietary

Honeywell.com

137847i

Select Operation ModeECP –– 4204 Emulation ––

2-4204s Emulation –– Zone

Select Options• Old Alarm Time• IP Fault Time• Fault Relay Normally On• Tamper Report• Use DHCP

– NIC IP Address– Subnet Mask– Gateway IP Address– DNS Server IP Address

• Enable Power Save

Select Mode and Options

Honeywell Proprietary

Honeywell.com

147847i

AlarmNet Direct Programming

ECP Mode• Enable Direct Wire Downloading

– Keypad Address

• Total Connect Features– Remote Access

– Keypad Address/Type

– Multimode

– Multimode Address

• Zone 6 and 7– EOLR, V+ or V-

– Invert Zone

– Zone Restore

– Zone Delay

Honeywell Proprietary

Honeywell.com

157847i

Zone Mode• Trip Inputs 1 or 2 w/Bell out

– Increases Trip Voltage to 5V for V+ mode

• Lynx Panic• Telco Zone• Open/Close Zone• Multimode

– Total Connect

• Trigger Type• Invert Zone• Zone Restore• Zone Delay• Zone Report On Arm

AlarmNet Direct Programming

Honeywell Proprietary

Honeywell.com

167847i

4204 Emulation Modes• Fault Relay Normally On• Telco Zone• Open/Close Zone• Enable Direct Wire Downloading

– Keypad Address

• Total Connect Feature– Remote Access

– Keypad Address/Type

– Set Multi Partition View

• Zone Restore• Zone Delay• Zone Report On Arm

– Zone 4 or Zone 8 Arms

AlarmNet Direct Programming

Honeywell Proprietary

Honeywell.com

177847i

If the device is powered and connected to the Internet:

• Save And Transfer Data to Device

If the device is not powered or connected to the Internet:

• Click “Save”• Click “Exit”

Return to Show Program Devices page.

AlarmNet Direct Programming

Honeywell Proprietary

Honeywell.com

187847i

7720 Programming Tool

•The device can also be programmed using a 7720P Programmer.

•This 7720P allows access to Useful Diagnostic Tools.

Honeywell Proprietary

Honeywell.com

197847i

7720P Programming

Enters programming mode.

If a password has been previously assigned, thisprompt appears.Enter a 4-digit password (0-9, A-F, N, S, T, X, Y).The next prompt appears.

NOTE: The central station can remotely block access to local device programming. If this has been done, the following prompt appears:

Strt Prog Mode?(Y/N)_

Enter Password

Program Device?(Y/N)_

Change Password?(Y/N)_

Access to ProgMode Denied

Honeywell Proprietary

Honeywell.com

207847i

Programming

In ECP mode, the 7847i/7847i-E communicates withthe panel as a Long Range Radio (LRR) device. Enterthe appropriate ECP device address. For controls, see the control panel’s Installation and Setup Guide.

Press the [space] key to scroll through the modes of operation. Press [ENTER] to select ECP mode.

• ECP• Zone Triggers• 4204 Emu• Two 4204s

Device Address(03)_

Device Mode(ECP)_

Honeywell Proprietary

Honeywell.com

217847i

Programming

Enter the 2-digit primary city ID, 01-99 (decimal).

Enter the 2-digit primary central station ID number, 01-FE (HEX).

Enter the 4-digit subscriber account number for the primary central station, 0001-9999 (decimal).

Applicable only if control supports Central Station #1and #2 Category Enable reporting for the LRR device(e.g., VISTA-128BP, FA1660C, etc.).

Enter the 2-digit secondary city ID, 01-99 (decimal).

Enter the 2-digit second central station's ID number,01-FE (HEX).

Enter the 4-digit subscriber account number for the second central station, 0001-9999.

Primary City ID?(??)_

Primary CS ID?(??)_

Primary Sub ID?(????)_

2ND City ID?(??)_

2ND CS ID?(??)_

2ND Sub ID?(????)_

2ND CS Y/N?(N)_

Honeywell Proprietary

Honeywell.com

227847i

Programming

Multi-Mode (email notification) is intended as a convenience for the user, and does not replace Central

Station reporting of critical events (alarms, troubles, etc.).

Select "4204 Sourced" to send up to four events or "2-4204 Sourced" to send eight events. Disable for normal alarm processing and go to Prompt21: "Primary City ID".

Device address must be unique fromthe normal LRR Device Address (Prompt 28), and the Keypad Address used for Remote Access or Direct Wire downloading.

Press [Y] to allow the end user to access their system via a website.

Remote Access Y/N(N)_

Multi Mode(Disabled)_

Multi Mode Addr(12)_

Honeywell Proprietary

Honeywell.com

237847i

Programming

Applies only to VISTA-128BP/250BP and FBP Series controls, and FA1600C and FA1700C Series controls.

Must be programmed if using either the Remote Access feature or Direct Wire downloading. Enter the appropriate device address.

24 Hours• 1 Hour• US UL Line (6 Min)• CN UL Line Lvl 3 (3 Min)• US UL Line (90 Sec)• CN UL Line Lvl 4 (90 Sec)• CN UL Line Lvl 5 (75 Sec)• None• 30 Day

The AlarmNet network must hear at least one supervisory message from the module during this supervision period; otherwise, AlarmNet notifies the central station that a communication failure has occurred.

Direct Wire Y/N(N)_

Keypad Address(28)_

Supervision(24 Hours)_

Honeywell Proprietary

Honeywell.com

247847i

Programming

Sets how long an undeliverable alarm is retried for delivery to the central station.

Enter the time delay (01-99) in minutes before the7847i/7847i-E notifies the control panel that there isloss of contact with the network.

The fault open collector output is normallyenergized to ground, and de-energizes (open circuit) in the event of a module fault.

Allows the Cover Tamper to be disabled/enabled.

UL NOTE: Must be 10 Minutes

Old Alarm Time(10 Minutes)_

IP Flt Time(60 mins)_

Flt Rel ON Y/N(N)_

Tamper Rpt Y/N(Y)_

Honeywell Proprietary

Honeywell.com

257847i

Programming Mode

Use DHCP Y/N(Y) _

NIC IP Address:255.255.255.255_

Gateway IP Addr:255.255.255.255_

Subnet Mask:255.255.255.255_

DNS Serv IP Addr:255.255.255.255_

If using DHCP the screens below will not be shown. It will skip to the “PWR Save Mode” question.

Honeywell Proprietary

Honeywell.com

267847i

Programming Mode

Enable Zn 6 (Y/N)(N)

Zn 6 Trigger Type(V+)

Restore Zn 6 Y/N(Y)

Invert Zn 6 (Y/N)(N)

Delay Zn 6 (secs)(00)

Repeat for zone 7 if required

V+ 2V to 13V Trips ZoneV- 0V Ground Trips ZoneEOLR Loss of 2k EOLR Trips

No - Normal Zone ActivationYes - Faulted Zone sends normal report. - Normal Zone sends alarm report.

Yes - Zone sends Restore report.No - Zone will not send Restore report.

• Zone can be Delayed from 1 to 15 seconds• Zone must remain faulted for the full extent of delay to send report.

Honeywell Proprietary

Honeywell.com

277847i

Programming Mode

Pwr Save Mode (Y/N)(Y) _

• When Power Save Mode is enabled, the Network Interface Card (NIC) powers up, Pings a Redir, and turn back off.

• This process takes about 3 seconds and the process repeats every 20 seconds.

• Some Routers may see this as being “under attack” and shut down the Port on the router.

Devices connected to routers that shut down the port may try using Static IP Addressing, before disabling the Power Save Mode feature. Power cycle the Router to reset the port, and determine if this was the problem.

NOTE: If this feature is disabled, the device will not meet the UL Requirement for Battery Backup. It will reduce the backup time to 18 hours.

Honeywell Proprietary

Honeywell.com

287847i

Updating RootFile \

DONEResetting………

Programming Mode

Create Password?Y/N

Exit Prog Mode?Y/N

Review? Y/N

Press Enter to Continue and Exit

Press Enter to Continue and Exit

Press Shift Y then Enter to Continue and Exit

Zone Mode Setup

Honeywell Proprietary

Honeywell.com

307847i

Programming Zone Mode

Lynx Panic Y/N(N)

With a LynxR/R-EN Panel, enable Lynx Panic • Temporal Pulse = Zone 1 Report

–FIRE

• Constant or Steady = Zone 2 Report–BURG

• Single 3 second Pulse = Zone 3 Report–Silent Panic, Medical, Duress

Always program Zone 1/2 as a negative trip (V-) and install a 2k EOLR across the zone input and ground.

Honeywell Proprietary

Honeywell.com

317847i

Programming Zone Mode

Enabling this option will change the required trip voltage on zones 1, 2 and 3, as described below.

• Positive Trip – Always enable for Positive Trip.– Disabled – 2V– Enabled – 5V

• Negative Trip– Disabled – 0V ground potential– Enabled – 0V to 5V will trip. Must be greater than 5V to be normal.

This field also affects the zone 3 input.

Trip Inputs 1 or 2 w/Bell Out (N)

Honeywell Proprietary

Honeywell.com

327847i

Programming Zone Mode

Enabling this option will cause the specified zone input to send the High Speed Telco Report to Central Station.

• Available for zones 3 through 7.• Telco Fault 5555 5155 6• Telco Restore 5555 5355 6

Telco Zone (0)

Honeywell Proprietary

Honeywell.com

337847i

Enabling this option will cause the specified zone to send a High Speed Open or Close report to central station, in the zone that was indicated.

Example uses zone 3 to indicate Open/Close

• Available for zones 3 through 7.• Arming 5545 5555 7 – Restore Report• Disarming 5525 5555 7 – Alarm Report

Note: If your trigger activates for Arming, you will need to enable INVERT for the zone. (Invert option will be discussed later.)

Programming Zone Mode

Open/Close Zone (0)

Honeywell Proprietary

Honeywell.com

347847i

Programming Zone Mode

• Enabling this option will cause the specified zone ONLY attempt to generate an email message via Total Connect Remote Services.

• When enabled, only device Supervisory Messages will be sent to Central Station, i.e. Low Batt, AC Loss, Swinger Suppression, etc. (Not Tamper)

NOTE: This option should only be enabled when using Remote Services and Alarm Reports are not desired to be received by Central Station.

Multi-mode (N)

Honeywell Proprietary

Honeywell.com

357847i

Programming Zone Mode

Zn x Trigger Type(V+)

Restore Zn x Y/N(Y)

Invert Zn x (Y/N)(N)

Delay Zn x (secs)(00)

V+ 2V to 13V Trips ZoneV- 0V Ground Trips ZoneEOLR Loss of 2k EOLR Trips

No - Normal Zone ActivationYes - Faulted Zone sends normal report. - Normal Zone sends alarm report.

Yes - Zone sends Restore report.No - Zone will not send Restore report.

• Zone can be Delayed from 1 to 15 seconds• Zone must remain faulted for the full extent of delay to send report.

Honeywell Proprietary

Honeywell.com

367847i

Exiting Program Mode Correctly

• NEVER disconnect the programmer while in program mode.• ALWAYS exit program mode AND leave the programmer

connected until the screen displays “DONE”.

If you didn’t exit correctly…

Plug the programmer back in and…• Press enter then exit as normal.

- or -• Power cycle the 7845GSM radio.

Honeywell Proprietary

Honeywell.com

377847i

Registering…

Shift

Registering…

RegistrationSuccessful

Honeywell Proprietary

Honeywell.com

387847i

Registering…PIN Replacement• When registering the GSM radio press

– Enter PIN

– Wait for acknowledgement

Registering…

PIN: _

RegistrationSUCCESS

Honeywell Proprietary

Honeywell.com

397847i

Status Codes

STATUS CODE DESCRIPTION

0000 Control Panel lost communication with panel

0880 7847i tamper detected (cover removed)

0005 7847i has lost contact with AlarmNet

000F 7847i is not registered; radio account not activated

0400 7847i Power On Reset

0C80 7847i Power On Reset & Tamper detected

0C8F 7847i Power On Reset, Tamper detected & Not Registered

The 7847i sends status messages to the control panel for tamper and network communication failures. When using Honeywell’s VISTA-10P, VISTA-15P, Vista 20P series control panels, the status is displayed on the control panel’s keypad as “Check 103 LRR” followed by a 4-digit code).

Honeywell Proprietary

Honeywell.com

407847i

Status Display LEDs

Honeywell Proprietary

Honeywell.com

417847i

Mode & Status LEDs

Press and hold the Mode & Status button to view.

The two Yellow LEDs indicate which mode the device is programmed in.

The first Green LED indicates the status of the Internet or Web connection.

Honeywell Proprietary

Honeywell.com

427847i

Network Connectivity LEDs

Honeywell Proprietary

Honeywell.com

437847i

Central Station Messages

7720P ProgrammerDiagnostic Commands

Honeywell Proprietary

Honeywell.com

457847i

Programmer Keyboard Commands

INTERNAL IP/GSMx.x.xx mm/dd/yy

MAC xxxxxxxxxxxxMAC CRC yyyy

[ A ]

[ B ]

Software Revision

MAC Address

Mon 01 Jan 200105:48:39 am

[ C ] GMT Time and Date

The 7720P Programmer is an invaluable tool for troubleshooting the device and network connection. Section 5 of the Installation

Instructions provides details of each command.

Honeywell Proprietary

Honeywell.com

467847i

Programmer Keyboard Commands

Physical LinkGood

NIC IP Addressxxx.xxx.xxx.xxx

Subnet Maskxxx.xxx.xxx.xxx

[ D ] Network Diagnostics Display

If using DHCP, this information is assigned by the Gateway/Router.

If not using DHCP, this information must match the information provided by the site Network Administrator.

[ * ] to go to Subnet Mask

[ * ] to go to NIC IP Address

[ * ] to go to Gateway IP Address

For more information on Network Diagnostics, see Section 6 of the Installation Instructions.

Gateway IP Addrxxx.xxx.xxx.xxx

[ * ] to go to DNS Server IP

Honeywell Proprietary

Honeywell.com

477847i

Programmer Keyboard Commands

Encryption TestAES Passed!

DHCPOK

DNS Serv IPxxx.xxx.xxx.xxx

[ * ] to go to DHCP Status

[ * ] to go to encryption test

If using DHCP, this information is assigned by the Gateway/Router.

If not using DHCP, this information must match the information provided by the site Network Administrator.

If using DHCP

Run Network Diagnostic Tests

Network Diagnostics Display Continued

[ F ] Testing GatewayRedir 1

Honeywell Proprietary

Honeywell.com

487847i

Programmer Keyboard CommandsECP 67 TmPB Flt xx 5 ++ OK

1234 67 TmPB Flt5555 xx 5 ++ OK

12345678 TmPB Flt5555555x 5 ++ OK

[ S ]Status Display for ECP Mode

Status Display for 4204 Emulation Mode

Status Display for 2-4204 Emulation Mode

[ * ] = next field, [BS] = previous field

[ * ] = next field, [BS] = previous field

Bat NLd: x.xxVBat Ld: x.xxV

Status Display for Zone Trigger Mode1234567 TmPB Flt5555555 5 ++ OK

Battery Voltage Status Display

[ * ] = next field, [BS] = previous field

[ * ] = next field, [BS] = previous field

[ * ] = next field, [BS] = previous field

Honeywell Proprietary

Honeywell.com

497847i

Programmer Keyboard CommandsECP 67 TmPB Flt xx 5 ++ OK

1234 67 TmPB Flt5555 xx 5 ++ OK

12345678 TmPB Flt5555555x 5 ++ OK

[ S ]Status Display for ECP Mode

Status Display for 4204 Emulation Mode

Status Display for 2-4204 Emulation Mode

[ * ] = next field, [BS] = previous field

[ * ] = next field, [BS] = previous field

Bat NLd: x.xxVBat Ld: x.xxV

Status Display for Zone Trigger Mode1234567 TmPB Flt5555555 5 ++ OK

Battery Voltage Status Display[ * ] = next field, [BS] = previous field

[ * ] = next field, [BS] = previous field

[ * ] = next field, [BS] = previous field

Honeywell Proprietary

Honeywell.com

507847i

Programmer Keyboard Commands

[ * ] = next field, [BS] = previous field

Reset CPU Y/N

[ T ]

[ X ] Reset the 7847i

Test Msg Sent Send Test Alarm

[ * ] = next field, [BS] = previous field

[ * ] = next field, [BS] = previous field

Battery ChargerOK

Line Voltagexx.xxV

Battery Charger Status Display

Line Voltage Status Display

[ S ] Continued

Honeywell Proprietary

Honeywell.com

517847i

Programmer Keyboard Commands

Force Server Update?Y/N

Cannot UploadTry Later!_

Force Upload of Configuration File[ 0 ]

Path for Data Transmission Not Available.

Note: If the Internet is not available or if the module cannot communicate with AlarmNet, the following screen will be displayed after entering this command.

http://www.security.honeywell.com/hsc/

and click on MyWebTech

User name: honeywell

Password: support99

Honeywell Security support email: MyWebTech@Honeywell.com

AlarmNet Support (800) 222-6525