Diesel Generator Set mtu 16V4000 DS2250

Post on 05-Apr-2022

31 views 0 download

transcript

Optionalequipmentandfinishingshown.Standardmayvary.Optionalequipmentandfinishingshown.Standardmayvary.

mtu 16V4000 DS2250DieselGeneratorSet

Producthighlights

380V–11kV/50Hz/standbypower/NEA(ORDE)optimized16V4000G74F/waterchargeaircooling

Bene� ts— Lowfuelconsumption— Optimizedsystemintegrationability— Highreliability— Highavailabilityofpower— Longmaintenanceintervals

Support— Globalproductsupportoffered

Standards— Engine-generatorsetisdesignedandmanufacturedinfacilitiescertifiedtostandardsISO2008:9001andISO2004:14001

— GeneratorsetcompliestoISO8528— GeneratormeetsNEMAMG1,BS5000,ISO,DINENandIECstandards

— NFPA110

Power rating— Systemratings:2230kVA-2350kVA— AcceptsratedloadinonestepperNFPA110*— GeneratorsetcompliestoG3accordingtoISO8528-5— GeneratorsetexceedsloadstepsaccordingtoISO8528-5*

Performance assurance certi� cation (PAC)— Engine-generatorsettestedtoISO8528-5fortransientresponse— 85%loadfactor— Verifiedproductdesign,qualityandperformanceintegrity— Allenginesystemsareprototypeandfactorytested

Complete range of accessories available— Controlpanel— Powerpanel— Circuitbreaker/powerdistribution— Fuelsystem— Fuelconnectionswithshut-offvalvemountedtobaseframe— Starting/chargingsystem— Exhaustsystem— Mechanicalandelectricaldrivenradiators— Mediumandoversizedvoltagealternators

Emissions— NEA(ORDE)optimized

Certi� cations— CEcertificationoption— Unitcertificateacc.toVDE-AR-N4110

* Changestothestandardparametersets(alternator-regulatorand

genset-controller)arenecessary

Application data 1)

EngineManufacturer mtuModel 16V4000G74FType 4-cycleArrangement 16VDisplacement:l 76.3Bore:mm 170Stroke:mm 210Compressionratio 16.4Ratedspeed:rpm 1500Enginegovernor ECU9Maxpower:kWm 1965Aircleaner dry

Fuel systemMaximumfuellift:m 5Totalfuelflow:l/min 20

Fuel consumption 2) l/hr g/kwhAt100%ofpowerrating: 471.1 199At75%ofpowerrating: 358.7 202At50%ofpowerrating: 247.4 209

Liquid capacity (lubrication)Totaloilsystemcapacity:l 300Enginejacketwatercapacity:l 175Intercoolercoolantcapacity:l 50

Combustion air requirementsCombustionairvolume:m3/s 2.5Max.airintakerestriction:mbar 50

Cooling/radiator systemCoolantflowrate(HTcircuit):m3/hr 68.5Coolantflowrate(LTcircuit):m3/hr 30Heatrejectiontocoolant:kW 660Heatradiatedtochargeaircooling:kW 430Heatradiatedtoambient:kW 90Fanpowerforelectr.radiator(40°C):kW 70

Exhaust systemExhaustgastemp.(afterturbocharger):°C 480Exhaustgasvolume:m3/s 6.6Maximumallowablebackpressure:mbar 85Minimumallowablebackpressure:mbar 30

Standardandoptionalfeatures

System ratings (kW/kVA)

Generator model Voltage NEA (ORDE) optimized

without radiator with mechanical radiator

kWel kVA* AMPS kWel kVA* AMPS

LeroySomerLSA52.3S7(LowvoltageLeroySomerstandard)

380V 1864 2330 3540 1808 2260 3434

400V 1864 2330 3363 1808 2260 3262

415V 1864 2330 3242 1808 2260 3144

LeroySomerLSA52.3L12(LowvoltageLeroySomeroversized)

380V 1864 2330 3540 1808 2260 3434

400V 1864 2330 3363 1808 2260 3262

415V 1864 2330 3242 1808 2260 3144

Marathon744RSL7092(LowvoltageMarathon)

380V 1848 2310 3510 1784 2230 3388

400V 1848 2310 3334 1784 2230 3219

415V 1808 2260 3144 1784 2230 3102

Marathon1020FDL7093(LowvoltageMarathonoversized)

380V 1848 2310 3510 1784 2230 3388

400V 1848 2310 3334 1784 2230 3219

415V 1808 2260 3144 1784 2230 3102

Marathon1020FDH7097(Mediumvolt.marathon)

11kV 1864 2330 122 1800 2250 118

LeroySomerLSA53.2XL9(Mediumvolt.LeroySomer)

11kV 1880 2350 123 1808 2260 119

*cosphi=0.8

1 AlldatarefersonlytotheengineandisbasedonISOstandardconditions(25°Cand100mabovesealevel).

2 ValuesreferencedareinaccordancewithISO3046-1.Conversioncalculatedwithfueldensityof0.83g/ml.Allfuelconsumptionvaluesrefertoratedenginepower.

Standard and optional features

Representsstandardfeatures

Representsoptionalfeatures

Cooling system

Jacketwaterpump Thermostat(s) Waterchargeaircooling

Mechanicalradiator Electricaldrivenfront-endcooler Jacketwaterheater

Control panel

Unitcablingwithcodedplugsforeasyconnectionofcustomer-specificcontrols(V0) Pre-wiredcontrolcabinetforeasyapplicationofcustomizedcontroller(V1+) Islandoperation(V2) AutomaticmainsfailureoperationwithATS(V3a) Automaticmainsfailureoperationincl.controlofgeneratorandmainsbreaker(V3b) Islandparalleloperationofmultiplegensets(V4) Automaticmainsfailureoperationwithshort(<10s)mainsparalleloverlapsynchronization(V5)

Mainsparalleloperationofasinglegenset(V6) Mainsparalleloperationofmultiplegensets(V7) Baslercontroller Deifcontroller Completesystemmetering Digitalmetering Engineparameters Generatorprotectionfunctions Engineprotection SAEJ1939engineECUcommunications Parametrizationsoftware Multilingualcapability Multipleprogrammablecontactinputs Multiplecontactoutputs

Eventrecording IP54frontpanelratingwithintegratedgasket Differentexpansionmodules Remoteannunciator Daytankcontrol Generatorwindingtemperaturemonitoring Generatorbearingtemperaturemonitoring ModbusTCP-IP

Generator

4polethree-phasesynchronousgenerator Brushless,self-excited,self-regulating,self-ventilated Digitalvoltageregulator Anticondensationheater StatorwindingY-connected,accessibleneutral(broughtout) ProtectionIP23

InsulationclassH,utilizationacc.toH RadiosuppressionEN55011,group1,cl.B Shortcircuitcapability3xInfor10sec WindingandbearingRTDs(withoutmonitoring) ExcitationbyAREP MountingofCT´s:2coreCT´s Windingpitch:2/3winding Voltagesetpointadjustment±10%

MeetsNEMAMG-1,BS5000,IEC60034-1,VDE0530,DINEN12601,AS1359andISO8528-3requirements LeroySomerlowvoltagegenerator Marathonlowvoltagegenerator Oversizedgenerator Mediumvoltagegenerator

Engine

4-cycle Standardsinglestageairfilter Oildrainextension&shut-offvalve

Closedcrankcaseventilation Governor-electronicisochronous Commonrailfuelinjection

NEA(ORDE)optimizedengine

Connectivity

Theenginesystemautomaticallycollectsandtransfersenginedatatothemanufacturerfromtimetotime.Thedataisusedbythemanufacturerforthepurposesofproduct

developmentandimprovementaswellasserviceoptimization.Userscanloginorregisterviahttps://mtu-go.comandalsogaininsightintothedata.

Standard and optional features

Representsstandardfeatures

Representsoptionalfeatures

Circuit breaker/power distribution

3-polecircuitbreaker 4-polecircuitbreaker

Electrical-actuatedcircuitbreaker BaseframemountedGCB,pre-wiredwithgenerator,readyforcommissioning

Fuel system

Flexiblefuelconnectorsmountedtobaseframe Fuelfilterwithwaterseparator Fuelfilterwithwaterseparatorheavy-duty

Switchablefuelfilterwithwaterseparator Switchablefuelfilterwithwaterseparatorheavy-duty Seperatefuelcooler

Fuelcoolerintegratedintocoolingequipment

Starting/charging system

24Vstarter Redundantstartingsystem

Starterbatteries,cables,rack,disconnectswitch(lockable)

Batterycharger Alternator

Mounting system

Weldedbaseframe Resilientengineandgeneratormounting Modularbaseframedesign

Baseframemountingonfoundation/baseplatewithusingclampingbrackets

Exhaust system

Exhaustbellowswithconnectionflange Exhaustsilencerwith10dB(A)soundattenuation

Exhaustsilencerwith30dB(A)soundattenuation

Exhaustsilencerwith40dB(A)soundattenuation Y-connection-pipe

Power panel

Supplyelectricaldrivenradiatorfrom45kW–75kW

Rolls-Royce Groupwww.mtu-solutions.com/powergen

Weights and dimensions

Drawing above for illustration purposes only, based on a standard open power 400 Volt engine-generator set. Lengths may vary with other voltages. Do not use for installation design. See website for unit specific template drawings.

Emissionsdata

— Consultyourlocalmtu distributorforemissionsdata.

Sounddata

— Consultyourlocalmtudistributorforsounddata.

Weightsanddimensionsarebasedonopenpowerunitsandareestimatesonly.Consultthefactoryforaccurateweightsanddimensionsforyourspecificengine-generatorset.

System Dimensions (LxWxH) Weight (dry/less tank)

Openpowerunit(OPU) 4766x1810x2330mm 12428kg

Ratingdefinitionsandconditions

— Standbyratingsapplytoinstallationsservedbyareliableutilitysource.Thestandbyratingisapplicabletovaryingloadsforthedurationofapoweroutage.Nooverloadcapabilityforthisrating.RatingsareinaccordancewithISO8528-1,ISO-3046-1,BS5514andAS2789.Averageloadfactor:≤85%.Operatinghours/year:max.500.— Consultyourlocalmtudistributorforderatinginformation.

Subjecttochange.|3237831|Edition01/22|BMC2021-12.