Post on 04-Jun-2020
transcript
Flue Gas NOx Removal Equipment (SCR and SNCR)
SCR (selective catalytic NOx removal equipment): A NOx removal system that can effectively remove toxic nitrogen oxides. SNCR (selective non-catalytic NOx removal equip-ment): The simplest removal system based on sound operational achievement. SNCR: The simple structure allows easy and low-cost installation in both existing and new facilities.
Ammonia solution and urea solution are injected as reducing agents to remove NOx in the exhaust gas, while nitrogen oxides are decomposed into non-toxic nitrogen (N2) and water (H2O).
Number of SNCR and SCR shipments・Japan: More than 100 locations・Overseas: Several locations
SCR (selective catalytic NOx removal) delivers a high NOx removal effect of more than 90% and allows stable operations with dirty gases containing SOx and dust.
SNCR (selective non-catalytic NOx removal) is rela-tively easy to install and delivers NOx removal rates of 30% to 50%. It is suitable as a NOx removal system for existing systems.
[Decomposition of urea solution to ammonia] CO(NH2)2 + H2O ⇒ 2NH3 + CO2 [Decomposition of NOx by ammonia] 4NO + 4NH3 + O2 ⇒ 4N2 + 6H2O
The amount of reducing agent injected can be adjusted based on the combus-tion load and NOx concentration.
SCR (selective catalytic NOx removal) delivers high efficiency removal rate of 90% or higher due to the function of the catalyst in the reactor vessel.
SNCR (selective non-catalytic NOx removal) delivers a 30% to 50% NOx removal rate depending on the installation conditions by supplying reduc-ing agents to the high-temperature zone of an incinerator.
SNCR denitration equipment
SCR
SNCR Flow for a large-scale boiler
Compressed air
Power, Operation shutdown signal, Current NOx value
Usual SNCR flow
Warnings, Pump operation signal
BoilerPump unit
Urea solution strage tank
Urea solution spray nozzle
Dilution water
Tanker
Pure water
Steam
Boiler No. 2
Boiler No. 3
Compressed air
Power, Operation shutdown signal, Current NOx value
Warnings, Pump operation signal
BoilerPump unit
Urea solution strage tank
Urea solution spray nozzle
Dilution water
Boiler No. 2
Boiler No. 3
Urea dilution tank
P
MM
SNCR denitration equipment(Urea solution system) (SCR Reactor)
Main reaction formulas
Catalyst (SCR)
1-6-7 Minami-Honmachi, Chuo-ku, Osaka 541-8587 Japan
k.kajita@teijin.co.jp
Environmental Department Teijin Engineering Ltd.