Post on 08-Nov-2014
description
transcript
System Architecture
INTEGRATED BUILDING MANAGEMENT SYSTEM
BUILDING MANAGEMENT SYSTEM
SECURITY SYSTEM
NURSE CALL SYSTEM
SAFETY SYSTEM
Building Management systemHVAC system managementExhaust & Ventilation system managementElectrical Management System & DG MonitoringWater Management/ Pumping SystemLighting Management System in common areasTime based sprinkler controlLift Monitoring
HVAC system management PLANT ROOM SIDEChiller, pumps, cooling tower – on/off as per requirement
& its status , Trip , Auto ManualValves – ON/OFF as per requirement & its StatusSupply/ return temperature of header pipesMODBUS integration of chiller & Secondary pump VFD
& monitoring the working parameters.
AC PLANT SCHEMATIC
AHU, TFA, HRW
On/off as per requirementControlling of inside temperature. VFD Integration through MODBUS & controlling.Fire Damper feedback monitoring.
EXHAUST & VENTILATION SYSTEM
On/off as per requirement, monitoring the Status
AHU SCHEMATIC
Electrical Management System & DG MonitoringMODBUS integration of DG & monitoring
the working parameters.Diesel Tank Monitoring &
Transfer pump ON/OFFMODBUS integration of
Multi Function Energy Meters .
HT Line Incomer Breaker, ACB Status, monitoringLT Panel ON/OFF, Status, Trip, Voltage Measurement ,
Power factor measurement Lighting DB ON/OFF, StatusAmbient Lux Sensing & Controlling the light.
LT Panel
Lux Sensor
Water Management/ Pumping System Tank Level Monitoring Switching on/off of pumps to maintain required tank level
& its statusSensing the line pressure of pressurized lines.
Tank Level Sensor
Pressure Sensor
Lift Monitoring
Lift Monitoring through Modbus including
floor status, alarm status, under
maintenance status, fireman switch
status etc.
Lift MODBUS connectivity
BMS PC
Time based sprinkler controlSprinkler irrigation system
can be automated using a
Time schedule facility
available in the BMS.
Sprinkler Pumps/valves Controller with MODBUS
connectivity BMS PC
THIRD PARTY INTEGRATIONChiller SystemSecondary Pumping SystemDG SystemDG Synchronization panelLift / Elevator SystemFire Alarm SystemCar Park ventilation systemVariable Frequency Drives for AHU’sMulti Function Energy MetersWater MetersSprinkler Control Panel
BMS SCREEN SHOTS
Plant Viewer Time scheduler
Trend Viewer Alarm Viewer
TENANT BILLING SYSTEMAC Billing
AC billing is based on the BTU Consumption
and arriving the monthly electricity consumption based on various energy meters readings including other common service charges like maintenance cost, operation
charges, water consumption, estate management etc.
BTU Meter
Electrical Energy Billing
The electrical energy consumption can be monitored using Multi Function Energy Meters with MODBUS connectivity. [KWH,PF,THDI etc]
Water Billing
Water consumption can be monitored for each client using flow meters that are compatible to BMS system.