Kentrox Modules
Version 2.91
Release Notes Rev A May 2016
© Westell Technologies
Part # 030-300762 Rev A
WESTELL.COM
RELEASE N
OTES
Modules Version 2.91 Release Notes
Copyright © 2016 by Westell Inc. All Rights Reserved. Westell, Kentrox® and Optima Management System® are registered trademarks of Westell. All other names are trademarks of their respective owners.
Information is correct at time of publication and is subject to change without notice. Contact Westell in Aurora, Illinois to verify current product information. Westell, Inc. is an Equal Opportunity/Affirmative Action employer.
Westell, Inc.750 North Commons Drive
Aurora, IL 60504 USAToll Free: (800) 377-8766
International: +1 (630) 375-4950 Fax: +1 (630) 375-4931
TABLE OF CONTENTSAffected Types Pages 2-3
New Supported Devices Pages 4-21
74996 -- Alpha AMPS24 UPS Page 475652 -- ZTE new SNMP MIB Page 1175773 -- Corning Core v7.2 Page 1776107 -- Huawei Rectifier Page 1776117 -- Commscope ION-E v1.6 Page 1976274 -- Commscope ION-M/B v7.20 Page 2176275 -- Commscope ION-U v1.7 Page 21
New Features Pages 22-24
76174 -- Module Eltek Smartpack monitoring enhanced to process traps Page 22SNMP Configuration Enhancements Page 2276304 -- Shared Discrete Description Configuration Page 2275939, 75938, 75937-- SPX NeType names updated Page 2276004 -- BatteryDAQ rectifier integration Page 2376074 -- UDiT Updates (components, fix actions) Page 24
Fixes Pages 25-26
Issue List Pages 26-27
Modules Version 2.91 Device Compatibility Information Pages 28-31
WESTELL.COM
Page 1
1-800-377-8766
Modules Version 2.91 Release Notes
Kentrox ModulesRelease Notes
Version 2.91May 2016
Affected Types
Vendor Models Configured Types Issue(s)
Alpha Technologies FXM AlphaAMPS24 74996
APC Galaxy 5000 APCBatteryString 76004
Basler DGC-2020 BaslerDGC20202Generator 75911
Battery DAQ 2402W2/M6 BatteryDAQBatteryMonitor 76004
Commscope
ION-E AndrewIONDAS 76117
ION M AndrewIONDAS 76274, 76071
ION-B AndrewIONDAS 76274, 76071
ION-U AndrewIONDAS 76275
Corning SC450 MobileAccessSC450DAS 75773
CSI UDiT CSIUDiTDASPanel 76074
Deep Sea Electronics
5210 DeepSea5210Generator 75911
5220 DeepSea5220Generator 75911
7320 DeepSea7320Generator 75911
Eltek SmartpackEltekSmartPackRectifier 75911
EltekBatteryString 76004
Emerson Rectifier Battery String EmersonBatteryString 76004
WESTELL.COM
1-800-377-8766
Page 2
Modules Version 2.91 Release Notes
Generac
EPanel GeneracEPanelGenerator 75911
EPanel with Annunciator GeneracEPanelGeneratorWithAnnunciator
75911
H100 GeneracH100GeneratorGeneracH100HTSGenerator
75911
HTS GeneracH100HTS 75911
Huawei 5210 Rectifier HuaweiSMURectifier 76107
Intelilite AMF25 InteliliteAMF25Generator 75911
Kentrox
Virtual Battery String VirtualBatteryString 76004
Analog Battery Sensor BatteryStringVoltageSensor 76004
Discrete Test ATS DiscreteControlledATS 76304
Discrete Power Detection DiscretePowerDetection 76304
Discrete Fule Quality DiscreteFuelQuality 76304
Discrete Generator DiscreteGenerator 76304
Shared Discrete Generator SharedDiscreteGenerator 76304
Discrete Controller Generator
DiscreteControlledGenerator 76304
Discrete IP Camera DiscreteIPCamera 76304
Lovato RGK60 LovatoRKG60Generator 75911
Marvair CommStat4 MarvairCS4HVACSystem 75948
Mobile Access SC450 (Corning Core) MobileAcccessSC450DAS 75960
SPX
Vanguard SPXVanguard 75939, 76179
36305 (LED) SPX36305 75938
903803 (Xenon/Eagle) SPX903803 75937
ZTE ZXDU68ZTEZxduRectifier 75652
ZTEBatteryString 76004
Vendor Models Configured Types Issue(s)
WESTELL.COM
Page 3
1-800-377-8766
Modules Version 2.91 Release Notes
New Supported Devices
74996 -- Alpha AMPS24 UPS
The AMPS24 is a typical UPS system comprised of inverter modules, a battery, and rectifier modules. This system is monitored using SNMP polling. The application collects measurements on a regular poll cycle (default 60 seconds). The application also listens for trap notifications from the AMPS24 and reports alarms accordingly. Furthermore, the application will perform SNMP polls to determine alarm status at start-up, at a user's request (using "sync" control-action), and on a configurable regular cycle (default 24 hours).
Configuration Example
config site module tower
application UPSmonitoring
application Rectifiermonitoring
config site network-element-set UPS
instance ups1
display-name UPS1
exit
config site newtork-element ups1
type AlphaAMPS24
param deviceIP 10.48.154.12
Inventory Example
UPS
|-- Battery
|-- Inverters
| |-- Inverter 01
| |-- Inverter 02
WESTELL.COM
1-800-377-8766
Page 4
Modules Version 2.91 Release Notes
| |-- Inverter 03
| |-- Inverter 04
| |-- Inverter 05
| |-- Inverter 06
| |-- Inverter 07
| |-- Inverter 08
| |-- Inverter 09
| |-- Inverter 10
| |-- Inverter 11
| |-- Inverter 12
\-- Rectifiers
Detailed Table of Information Provided by the AMPS24
Type Attribute Sample Content
Element: ups
Alarm Communication Communication Warning (Poll: Timeout)
Alarm Compatibility Minimum Supported Version “3.13” Received Version “3.12”
Alarm BatteryBreakerAlarm Battery Breaker Alarm
Alarm BypassmodeOn Bypass mode On
Alarm Digital4 Digital 4
Alarm InputBreakeroff Input Breaker off
Alarm TVSS TVSS
Alarm Digital7 Digital 7
Alarm Digital8 Digital 8
Alarm BatteryCurrentHigh Battery Current High
Alarm LoadCurrentHigh Load Current High
WESTELL.COM
Page 5
1-800-377-8766
Modules Version 2.91 Release Notes
Alarm ACMainsHigh AC Mains High
Alarm AC MainsLow AC Mains Low
Alarm HighVoltage1 High Voltage1
Alarm HighVoltage2 High Voltage 2
Alarm LowVoltage Low Voltage
Alarm LowBatteryVoltage Low Battery Voltage
Alarm MidpointMonitor1 Midpoint Monitor 1
Alarm MidpointMonitor2 Midpoint Monitor 2
Alarm MidpointMonitor3 Midpoint Monitor 3
Alarm MidpointMonitor4 Midpoint Monitor 4
Alarm MidpointMonitor5 Midpoint Monitor 5
Alarm TempSensor1Fail Temp Sensor 1 Fail
Alarm TempSensor2Fail Temp Sensor 2 Fail
Alarm TempSensor3Fail Temp Sensor 3 Fail
Alarm TempSensor4Fail Temp Sensor 4 Fail
Alarm TCSensorFail TC Sensor Fail
Alarm Custom1 Custom 1
Alarms Custom2 > Custom20 Custom 2 > Custom 20
Alarm RealTimeClockError Real Time Clock Error
Alarm InvalidDeviceFirmware Invalid Device Firmware
Alarm GroundFaultDetected Ground Fault Detected
Alarm ImproperControllerShutdown Improper Controller Shutdown
Alarm InvalidBatteryVoltage Invalid Battery Voltage
Alarm SystemMajor System Major
Alarm SystemMinor System Minor
Alarm LVD1 LVD1
Type Attribute Sample Content
WESTELL.COM
1-800-377-8766
Page 6
Modules Version 2.91 Release Notes
Alarms LVD2 > LVD10 LVD 2 > LVD 10
Alarm CEMFControl CEMF Control
Alarm HVSDControl HVSD Control
Alarm LVDInhibit LVD Inhibit
Alarm* CellDeviation Cell Deviation
Alarm* CurrentAlarm Current Alarm
Alarm* VoltageAlarm Voltage Alarm
Alarm* TemperatureAlarm Temperature Alarm
Alarm* CommsAlarm Comms Alarm
*NOTE: There are 16 sets of the above five Adio Alarms.
Alarm ConverterFail Converter Fail
Alarm ConverterMinor Converter Minor
Alarm ConvMajorFailCount Conv. Major Fail Count
Alarm ConvMinorFailCount Conv. Minor Fail Count
Alarm ConvOutOfTolerance Conv. Out Of Tolerance
Alarm ConvCommsLost Conv. Comms Lost
Alarm ConvInputVoltageFail Conv. Input Voltage Fail
Alarm InnvFanFail Conv. Fan Fail
Alarm ConvLoadCurrentHigh Conv. Load Current High
Alarm ConvLowOutputVoltage Conv. Low Output Voltage
Alarm ConvHighOutputVoltage Conv. High Output Voltage
Attribute softwareVersion 3.13
Element: upsBattery
Alarm BatteryRuntimeLow Battery Runtime Low
Alarm BatteryCapacityLow Battery Capacity Low
Alarm BatteryOvertemp Battery Overtemp
Type Attribute Sample Content
WESTELL.COM
Page 7
1-800-377-8766
Modules Version 2.91 Release Notes
Alarm BatteryOnDischarge Battery On Discharge
Alarm BatteryTestAlarm Battery test Alarm
Alarm BoostModeAlarm Boost Mode Alarm
Element: upsInverters
Alarm InverterMajorFailCount Inverter Major Fail Count
Alarm InverterMinorFailCount Inverter Minor Fail Count
Alarm InverterCommsLost Inverter Comms Lost
Alarm InverterACInputFail IUnverter AC Input Fail
Alarm InverterAlarm Inverter Alarm
Measurement ACInputApparentPower 5.40 kVA
Measurement ACInputCurrent 44.70 A
Measurement ACInputFrequency 60.00 Hz
Measurement ACInputPower 5.28 kW
Measurement ACInputPowerFactor 0.98
Measurement ACInputVoltage 120.00 V
Measurement ACOutputApparentPower 5.30 kVA
Measurement ACOutputCurrent 43.50 A
Measurement ACOutputPower 5.00 kW
Measurement AcOutputPowerFactor 0.94
Measurement ACOUtputVoltage 120.05 V
Measurement DCInputCurrent 0.00 A
Measurement DCInputPower 0.00 kW
Measurement DCInputVoltage 54.12 V
Element: upsInverter_01
Measurement ACInputApparentPower 0.42 kVA
Measurement ACInputCurrent 3.50 A
Type Attribute Sample Content
WESTELL.COM
1-800-377-8766
Page 8
Modules Version 2.91 Release Notes
Measurement ACInputFrequency 60.00 Hz
Measurement ACInputPower 0.42 kW
Measurement ACInputPowerFactor 1.00
Measurement ACInputVoltage 120.10 V
Measurement ACOutputApparentPower 0.43 kVA
Measurement ACOutputCurrent 3.50 A
Measurement ACOutputPower 0.40 kW
Measurement AcOutputPowerFactor 0.94
Measurement ACOUtputVoltage 120.10 V
Measurement DCInputCurrent 0.00 A
Measurement DCInputPower 0.00 kW
Measurement DCInputVoltage 53.80 V
Attribute serialNumber 6093
Attribute softwareVersion 196
*NOTE: There will be additional upsInverter_* components for each inverter module. The table index will match the inverter module number..
Element: upsRectifiers
Alarm RectifierFail Rectifier Fail
Alarm RectifierMinor Rectifier Minor
Alarm RectMajorFailCount Rect. Major Fail Count
Alarm RectMinorFailCount Rect. Minor Fail Count
Alarm RectifierLockout RectifierLockout
Alarm OutOfTolerance Out Of Tolerance
Alarm RectCommsLost Rect. Comms Lost
Alarms RectEqualizeActivated Rect. Equalize Activated
Alarm RectACMainsFail Rect. AC Mains Fail
Type Attribute Sample Content
WESTELL.COM
Page 9
1-800-377-8766
Modules Version 2.91 Release Notes
75652 -- ZTE new SNMP MIB
Inventory Example
rectifier
|-- rectifierBatteryString
|-- rectifierInputPower
|-- rectifierOutput1Power
|-- rectifierOutput2Power
|-- rectifierOutput3Power
|-- rectifierTenant1Power
|-- rectifierTenant2Power
|-- rectifierTenant3Power
|-- rectifierTenant4Power
Configuration Example
config site network-element rectifier
type ZTEZXDUNewRectifier
param deviceIP <ipaddress>
Alarm MaxRectifiersExceeded Max Rectifiers Exceeded
Alarm FanFailAlarm Fan Fail Alarm
Alarm PowerSave Power Save
Alarm UrgentRectACMainsFail Urgent Rect. AC Mains Fail
Measurement Current 1.28 A
Measurement Power 68.92 W
Measurement Voltage 53.84 V
Type Attribute Sample Content
WESTELL.COM
1-800-377-8766
Page 10
Modules Version 2.91 Release Notes
param totalTheoreticalMaxCurrent <total max current in amps of all modules>
Alarms
2.7.X and higher offers Device Alarms, so the batched alarms on the ZTE have been refactored into individual Device Alarms:
Type Attribute Sample Content
Element: rectifier
Alarm Communication Communication Error
Alarm Compatibility Minimum Supported Version “1.0G” Received Version “1.0F”
Alarm ACInSwitchOFF AC In Switch OFF
Alarm ACPowerOFF AC Power OFF
Alarm ACSPD AC SPD
Alarm BLVDLoopEBroken BLVD Loop E Broken
Alarm BatteryTestFail Battery Test Fails
Alarm CAN CAN
Alarm Common Common
Alarm DCSPD DC SPD
Alarm DCHVoltageHigh DC Voltage High
Alarm DCVoltageLow DC Voltage Low
Alarm DoorMagnet Door Magnet
Alarm EnvironmentHumidityHigh Environment Humidity High
Alarm EnvironmentHumidityInvalid Environment Humidity Invalid
Alarm EnvironmentHumidityLow Environment Humidity Low
Alarm EnvironmentTemperatureHigh Environment Temperature High
Alarm EnvironmentTemperatureInvalid
Environment Temperature Invalid
Alarm EnvironmentTemperatureLow Environment Temperature Low
WESTELL.COM
Page 11
1-800-377-8766
Modules Version 2.91 Release Notes
Alarm Extend Extend
Alarm Flood Flood
Alarm GlassBroken Glass Broken
Alarm HighTemperatureDownload High Temperature Download
Alarm Intrusion Intrusion
Alarm LLVD1LoopEBroken LLVD1 Loop E Broken
Alarm LLVD2LoopEBroken LLVD2 Loop E Broken
Alarm LLVD3LoopEBroken LLVD3 Loop E Broken
Alarm LowTemperatureDownload Low Temperature Download
Alarm LowVoltageDownload1 Low Voltage Download 1
Alarm PhaseVoltageImbalance Phase Voltage Imbalance
Alarm Radiator Radiator
Alarm Smoke Smoke
Alarm System Current System Current
Alarm TotalAlarmDisabled Total Alarm Disabled
Element: rectifierPower
Alarm <major> Communication Communication Error
Elements: AlphaDCPower, BetaDCPower, GammaDCPower
Alarm <major> Communication Error communicating with the meter
Alarm <critical> Failure Power failure detected (<20.0 VDC)
Element: TenantXDCPower
Alarm <major> Communication Error communicating with the meter
Element: batteryString
Alarm Communication Communication Alarm
Alarm BatteryBreaker Battery Breaker
Type Attribute Sample Content
WESTELL.COM
1-800-377-8766
Page 12
Modules Version 2.91 Release Notes
Measurements and Status Points
Alarm BatteryLowVoltageDownload Battery Low Voltage Download
Alarm Battery Battery
Type Attribute Sample Content New Reference Oid
Element: rectifier
Measurement CapacityUtilization 33.60% (totalDCCurrent (calculated) / totalTheoreticalMaxCurrent (parameter)) * 100
Measurement Efficiency 89.10% (totalDCPower (calculated) / totalACPower (calculated)) * 100
Measurement Source_ACPowerHours 0 hours
Measurement Source_ACPowerMinutes 5 minutes
Measurement Source_ACPowerSeconds 328 seconds
Measurement Source_BatteryHours 0 hours
Measurement Source_BatteryMinutes 0 minutes
Measurement Source_BatterySeconds 0 seconds
Measurement Source_BatteryTestHours
0 hours
Measurement Source_BatteryTestMinutes
0 minutes
Measurement Source_BatteryTestSeconds
0 seconds
Measurement Source_OfflineHours 0 hours
Measurement Source_OfflineMinutes 0 minutes
Measurement Source_OfflineSeconds 0 seconds
Status Point Source ACPower or BatteryTest or Offline
Type Attribute Sample Content
WESTELL.COM
Page 13
1-800-377-8766
Modules Version 2.91 Release Notes
Element: rectifierPower
Measurement CommunicationCount 0
Measurement CommunicationDurationMinutes
0 minutes
Measurement CommunicationDurationSeconds
0 seconds
Measurement L1N_Voltage 228 V .1.3.6.1.4.1.3902.2800.1.2.3.2.15.1.2.1.1 * 1.0
Measurement L1_Current 2 A .1.3.6.1.4.1.3902.2800.1.2.3.2.16.1.2.1.1 * 1.0
Measurement L2N_Voltage 229 V .1.3.6.1.4.1.3902.2800.1.2.3.2.15.1.2.1.2 * 1.0
Measurement L2_Current 2 A .1.3.6.1.4.1.3902.2800.1.2.3.2.16.1.2.1.2 * 1.0
Measurement L3N_Voltage 229 V .1.3.6.1.4.1.3902.2800.1.2.3.2.15.1.2.1.3 * 1.0
Measurement L3_Current 2 A .1.3.6.1.4.1.3902.2800.1.2.3.2.16.1.2.1.3 * 1.0
Measurement TotalRealPower 1.37 kW (L1N_Voltage * L1_Current * 0.001) + (L2N_Voltage * L2_Current * 0.001) + (L3N_Voltage * L3_Current * 0.001)
Element: AlphaDCPower
Measurement CommunicationCount 0
Measurement CommunicationDurationHours
0 hours
Measurement CommunicationDurationMinutes
0 minutes
Measurement CommunicationDurationSeconds
0 seconds
Type Attribute Sample Content New Reference Oid
WESTELL.COM
1-800-377-8766
Page 14
Modules Version 2.91 Release Notes
Measurement Current 8.9 A .1.3.6.1.4.1.3902.2800.1.2.3.3.2.1.2.1.1 * 0.1
Measurement FailureCount 0
Measurement FailureDurationHours 0 hours
Measurement FailureDurationMinutes 0 minutes
Measurement FailureDurationSeconds 0 seconds
Measurement Power 0.48 kW Voltage * Current * 0.001
Measurement Voltage 53.8 V .1.3.6.1.4.1.3902.2800.1.2.3.3.1.1.2.1.1 * 0.1
Element: BetaDCPower
Measurement CommunicationCount 0
Measurement CommunicationDurationSeconds
0 seconds
Measurement Current 8.7 A .1.3.6.1.4.1.3902.2800.1.2.3.3.2.1.2.1.2 * 0.1
Measurement FailureCount 0
Measurement FailureDurationHours 0 hours
Measurement FailureDurationMinutes 0 minutes
Measurement FailureDurationSeconds 0 seconds
Measurement Power 0.48 kW Voltage * Current * 0.001
Measurement Voltage 53.8 V .1.3.6.1.4.1.3902.2800.1.2.3.3.1.1.2.1.2 * 0.1
Element: GammaDCPower
Measurement CommunicationCount 0
Measurement CommunicationDurationSeconds
0 seconds
Measurement Current 8.4 A .1.3.6.1.4.1.3902.2800.1.2.3.3.2.1.2.1.3 * 0.1
Type Attribute Sample Content New Reference Oid
WESTELL.COM
Page 15
1-800-377-8766
Modules Version 2.91 Release Notes
Measurement FailureCount 0
Measurement FailureDurationHours 0 hours
Measurement FailureDurationMinutes 0 minutes
Measurement FailureDurationSeconds 0 seconds
Measurement Power 0.45 kW Voltage * Current * 0.001
Measurement Voltage 53.6 V .1.3.6.1.4.1.3902.2800.1.2.3.3.1.1.2.1.3 * 0.1
Element: TenantXDCPower
Measurement CommunicationCount 0
Measurement CommunicationDurationSeconds
0 seconds
Measurement Current -0.30 A .1.3.6.1.4.1.3902.2800.1.2.3.4.29.1.2 * 0.1
Measurement TotalExportEnergy 69.19 kWh .1.3.6.1.4.1.3902.2800.1.2.3.4.41.1.2 * 0.01
Measurement IntervalExportEnergy 0.00 kWh NOTE: Only provided in Optima
Element: batteryString
Measurement ChargeLevel 100% .1.3.6.1.4.1.3902.2800.1.2.3.4.14.1.2.1.1 * 1.0
Measurement Current 21.3 A .1.3.6.1.4.1.3902.2800.1.2.3.4.29.1.2.1.1 * 0.1
Measurement Temperature 31 C .1.3.6.1.4.1.3902.2800.1.2.3.4.6.1.2.1.1 * 1.0
Measurement TimeUntilDischarged ? .1.3.6.1.4.1.3902.2800.1.2.3.4.12.1.2.1.1 * 1.0
Measurement Voltage ‘54.0 V .1.3.6.1.4.1.3902.2800.1.2.3.4.4.1.2 * 0.1
Type Attribute Sample Content New Reference Oid
WESTELL.COM
1-800-377-8766
Page 16
Modules Version 2.91 Release Notes
75773 -- Corning Core v7.2
Updated the alarm mapping to match what is currently implements in the Corning Core.
76107 -- Huawei Rectifier
The Huawei SMU is a newly supported rectifier.
Configuration Example
config site module Tower
application RectifierMonitoring enable
config site network-element rectifier
type HuaweiSMURectifier
param deviceIp 10.48.154.12
The following is a detailed table of the information provided by the Huawei SMU network-element:
Trap OID Trap Name
48 btscSyncAlarmSet
49 btscSuyncAlarmClear
1051 hxnGeneralServiceSet
1052 hxnGeneralServiceClear
Type Attribute Sample Content
Element: rectifier
Alarm <major> Communication Communication Error
Measurement CapacityUtilization 5.00%
Measurement TotalOutputPower 0.60 kW
WESTELL.COM
Page 17
1-800-377-8766
Modules Version 2.91 Release Notes
Element: rectifierPower
Alarm <major> Communication Communication Error
Measurement CommunicationCount 0
Measurement CommunicationDurationSeconds
0 seconds
Measurement L1N_Voltage 215.00 V
Measurement L2N_Voltage 0.00 V
Measurement L3N_Voltage 0.00 V
Measurement L1_Current 1.0 A
Measurement L2_Current 1.0 A
Measurement L3_Current 1.0 A
Element: rectifierDCPowerX
Alarm <major> Communication Error communicating with the meter
Alarm <critical> Failure Power failure detected (<20.0 VDC)
Measurement CommunicationCount 0
Measurement CommunicationDurationSeconds
0 seconds
Measurement Current 6.30 A
Measurement FailureCount 0
Measurement FailureDurationSeconds 0 seconds
Measurement Power 0.32 kW
Measurement Voltage 51.50 V
Element: batteryStringX
Alarm <major> Communication Communication Alarm
Measurement ChargeLegel 100.00%
Measurement Current 1.70 A
Type Attribute Sample Content
WESTELL.COM
1-800-377-8766
Page 18
Modules Version 2.91 Release Notes
76117 -- Commscope ION-E v1.6
This system is monitored using SNMP polling. The application also listens for trap notifications from the ION-E and reports alarms accordingly. Furthermore, the application will perform SNMP polls to determine alarm status at start-up, at a user's request (using "sync" control-action), and on a configurable regular cycle (default 24 hours).
Configuration Example
config site module Tower
application DASMonitoring enable
config site network-element DAS
type AndrewIONDAS
param deviceIp 10.11.12.13
Inventory Example
das_01
|-- das_01_00
| |-- das_01_00_BKP
| |-- das_01_00_CAT
| | \-- das_01_00_CAT_L1
| | |-- das_01_00_CAT_L1_01
| | |-- das_01_00_CAT_L1_02
| | |-- das_01_00_CAT_L1_03
| | \-- das_01_00_CAT_L1_04
Measurement Temperature 19.00 C
Measurement TimeUntilDischarged 2192.00 minutes
Type Attribute Sample Content
WESTELL.COM
Page 19
1-800-377-8766
Modules Version 2.91 Release Notes
| |-- das_01_00_EPOI
| | |-- das_01_00_EPOI_00
| | \-- das_01_00_EPOI_01
| |-- das_01_00_OPT
| | \-- das_01_00_OPT_L5
| | |-- das_01_00_OPT_L5_01
| | |-- das_01_00_OPT_L5_02
| | |-- das_01_00_OPT_L5_03
| | \-- das_01_00_OPT_L5_04
| |-- das_01_00_PSU
| | |-- das_01_00_PSU_00
| | |-- das_01_00_PSU_01
| | \-- das_01_00_PSU_03
| |-- das_01_00_RFD
| | \-- das_01_00_RFD_R1
| | |-- das_01_00_RFD_R1_01
| | |-- das_01_00_RFD_R1_02
| | |-- das_01_00_RFD_R1_03
| | \-- das_01_00_RFD_R1_04
| |-- das_01_00_SUI
| | \-- das_01_00_SUI_M3
| \-- das_01_00_WCS
\-- das_01_17
|-- das_01_17_BKP
|-- das_01_17_CAT
| \-- das_01_17_CAT_L1
WESTELL.COM
1-800-377-8766
Page 20
Modules Version 2.91 Release Notes
| \-- das_01_17_CAT_L1_02
|-- das_01_17_OPT
| \-- das_01_17_OPT_R1
| |-- das_01_17_OPT_R1_01
| |-- das_01_17_OPT_R1_02
| |-- das_01_17_OPT_R1_03
| \-- das_01_17_OPT_R1_04
|-- das_01_17_PSU
| |-- das_01_17_PSU_00
| |-- das_01_17_PSU_01
| \-- das_01_17_PSU_03
\-- das_01_17_WCS
76274 -- Commscope ION-M/B v7.20
Internal performance improvements.
76275 -- Commscope ION-U v1.7
Internal performance improvements.
WESTELL.COM
Page 21
1-800-377-8766
Modules Version 2.91 Release Notes
New Features
76174 -- Module Eltek Smartpack monitoring enhanced to process traps
Version 2.91 enhances Eltek Smartpack monitoring to support and process traps received from SNMP host entries added in the Eltek Web User Interface instead of polling alarms.
SNMP Configuration Enhancements
Removing snmpManagerIp from all SNMP devices
Removing snmpManagerPort from all SNMP devices
Added deviceSnmpTrapPort (defaults to 162)
76304 -- Shared Discrete Description Configuration
Version 2.91 adds a new optional parameter, “discreteDescription,” providing a way to describe a shared discrete input which generates multiple alarms and/or measurements. This can be used to describe, for example, a shared discrete input providing alarms, measurements and/or messages including powerDistribution, mainsPowerDetection, and generatorRunning.
If the discreteDescription parameter is filled in, it will be applied to the discrete. If multiple NEs share a discrete, only one should fill in that value. It will exist until all NEs sharing the discrete are deconfigured.
75939, 75938, 75937-- SPX NeType names updated
All SPX Flash Technology tower light type names have been updated in Version 2.91 for consistency and clarity:
The words “TowerLight” have been removed from each type.
Flash Vanguard types are now called SPXVanguard.
Flash LED tower light types are now called SPX36305.
Flash Eagle tower light types are now called SPX903803
WESTELL.COM
1-800-377-8766
Page 22
Modules Version 2.91 Release Notes
Refer to the following table:
76004 -- BatteryDAQ rectifier integration
Version 2.91 fulfills a new feature on the BatteryDAQ M6 that will take battery current (as pulled from a rectifier or meter) as a Modbus set. It then uses that for additional calculation. The
Old Type NameStill valid but deprecated; will be removed in a future release
New Type Name
DialightHighIntensityDiscreteTowerLightDialightHighIntensity
DialightHighIntensityTowerLight
DialightMediumIntensityDiscreteTowerLightDialightMediumIntensity
DialightHighIntensityTowerLight
DialightRedOnlyDiscreteTowerLightDialightA2_A6Style
DialightRedOnlyTowerLight
DialightRedOnlySmallDiscreteTowerLightDialightA2_A6Style
DialightRedOnlySmallTowerLight
FlashEagle11DiscreteTowerLight
SPX9038XXFlashEagle11TowerLight
FlashEagle11EthernetDiscreteTowerLight
FlashEagle11EthernetTowerLight
FlashLEDTowerLightSPX36503
FlashLEDDiscreteTowerLight
FlashVanguardSerialDiscreteTowerLight
SPXVanguardFlashVanguardSerialTowerLight
FlashVanguardEthernetDiscreteTowerLight
FlashVanguardEthernetTowerLight
No longer valid; will no longer work:
FlashVanguardTowerLight N/A
WESTELL.COM
Page 23
1-800-377-8766
Modules Version 2.91 Release Notes
application will make the M6 soft dependent on rectifiers and supply that value if applicable. The module will now write the battery current value from a rectifier into the appropriate register on the BatteryDAQ every five seconds..
76074 -- UDiT Updates (components, fix actions)
DAS type UDiT has been updated in Version 2.91 to make use of device alarms and provide fix actions.
Configuration Example
config site module Tower
application DASMonitoring enable
config site network-element DAS
instance das1
display-name DAS1
exit
config site network-element das1
type CSIUDiTDASPanel
param deviceIp 10.48.154.12
Inventory Example
DAS1
|--SubRack01
| |-- Slot01 POI_1
| \-- Slot02 POI_2
\--SubRack02
|-- Slot01 L7ABC
|-- Slot02 AWS
\-- Slot03 SMR
WESTELL.COM
1-800-377-8766
Page 24
Modules Version 2.91 Release Notes
Fixes
76071 - TSUN Alarms on Node 0 aren’t shown
Alarms that come in with a CTA of 0 can now be set and cleared on the top level DAS element.
76112 - cabinetBattery Alarm Typo
A misspelling in a cabinetBattery alarm message has been corrected: “Battery fully discharged.”
76179 - Flash Vanguard Tower Light Type Issue
Eagle systems can now update their lighting type to white only. They should identify the correct tower light style D1 when white only instead of E1.
75948 - When configEnforcementDelay is set to 0, module should never set Marvair coolingSetpoint and emergencyShutoffTemperature
Module will no longer incorrectly enforce Marvair config on startup when the configEnforcementDelay is 0.
75911 - Generac H100 generator status continues to show running if serial communication to generator is lost during run
Now every serial-based generator will set the State status point to Offline when there is a communication alarm currently active.
WESTELL.COM
Page 25
1-800-377-8766
Modules Version 2.91 Release Notes
76358 - Direct Connect sites with alarms not syncing
In certain cases, components would not function correctly after changing a parameter on the top-level network element. This has been resolved so that alarms and status points will continue to function after making config changes..
Issue List
Issue ID Version Description
76304 2.9.0 Allow setting discrete description for shared discrete inputs
76275 2.9.0 Support Commscope ION-U firmware 1.7
76274 2.9.0 Support Commscope ION-M/B firmware 7.20
76174 2.9.0 Module Eltek Smartpack monitoring -- currently an snmp polling solution -- request to enhance to process traps
76171 2.9.0 SNMP simulator should work on multiple sub interfaces
76117 2.9.0 Application support for Commscope ION-E v1.6
76107 2.9.0 Application support of Huawei rectifier
76074 2.9.0 Update UDiT to function as other DAS types
76005 2.9.0 Report firmware version as an attribute
76004 2.9.0 Provide rectifier battery current to BatteryDAQ M6 if that combo is being used
75773 2.9.0 Support Corning Core v7.2
74996 2.9.0 Support AlphaTechnologies AMP24 UPS
76347 2.9.0 The single trap listener needs to be able to handle multiple trap community strings
76361 2.9.0 CAS-13954//ATC//ATC DAS SC450 alarms not showing up in Optima or the RMM - Site 332224 Park Meadows Mall
76358 2.9.0 344199 Southcenter_DC alarms not syncing
76332 2.9.0 Module 2.8.4 issue: making param changes to an NE does not actually make changes until module restart
76328 2.9.0 ValueError? when parsing snmp parameters - Emerson Netsure
WESTELL.COM
1-800-377-8766
Page 26
Modules Version 2.91 Release Notes
76322 2.9.0 v2.9.0 Module Validation - snmpMangerPort param no longer required?
76314 2.9.0 Support ION-E device management table
76302 2.9.0 Top level DAS alarms not clearing on syncAlarms control action
76256 2.9.0 Generac E-panel Annunciator communication - short duration (1-9 second) comm alarm events
76215 2.9.0 deviceSnmpTrapCommunity is actually used
76200 2.9.0 MissingAlias? alarms will not clear in Optima
76179 2.9.0 Case # 13480 // ATC US // 88468 Sanderson - Tower Type Issue on Flash Vanguard
76087 2.9.0 Battery DAQ writing to wrong register to update battery sting current
76048 2.9.0 Writing to BatteryDAQ Current register won’t recover after One Failure
76015 2.9.0 Directconnection doesn't measure every 15 minutes uptime data on the capacity server
75996 2.9.0 RunMode Status Point not Added to all Generator Types
75948 2.9.0 When configEnforcementDelay is set fo 0, module should never set marvair coolingSetpoint and emergencyShutoffTemperature
75911 2.9.0 Generator status continues to show running if serial communication to generator is lost during run. Generac H100 generator.
76382 2.9.0 SC-450 not reading firmware version until syncInventory
76380 2.9.0 Unnecessary component updates after first syncInventory event
76365 2.9.0 No logger property for controls
76339 2.9.0 Remove excess logging
76293 2.9.0 Measurement precision is not working correctly
76170 2.9.0 Clean up the RemoteConfigurations that apply to ip tables
76112 2.9.0 The word discharged is misspelled on the “Battery fully dicharged”
76093 2.9.0 unnecessary Communication alarms on monitor ne
76011 2.9.0 Only supply battery current to M6 if optional parameter is specified
76008 2.9.0 Updating NE display name only is ignored by module
Issue ID Version Description
WESTELL.COM
Page 27
1-800-377-8766
Modules Version 2.91 Release Notes
76385 2.9.1 Allow optional trap community string configuration
Issue ID Version Description
WESTELL.COM
1-800-377-8766
Page 28
Modules Version 2.91 Release Notes
Modules Version 2.91 Device Compatibility Information
Vendor Model / Variant Version(s)APC Galaxy 500 GDENA9S300IC303
Acrel PZ Series
Airsys ASLLC.2 13B64
AlphaAMPS24 3.13
FXM 2.00.01
Basler DCG-2020 3.17.02
BatteryDAQ 2402W2/M6
CCS WattNode
CSI UDiT 01.03.01
Commscope
ION MMC Plus Linux ION-M 6.50.0, 7.20.0
MMC Plus Windows ION-M 5.30.0
RMC1600 Linux ION-M 6.50.0, 7.0.1, 7.10.0, 7.20.0
RMC1600 Linux ION-U 1.64.1, 1.70.0
TSUN1/2 ION-B 5.1.1, 5.1.2
TSUN4 Linux ION-M 6.50.0, 7.20.0
TSUN4 Windows ION-M 5.30.0
Corning SC-450 7.0, 7.2
Deep Sea Electronics
5210 6.2a
5220 6.2a
5220/7320
7320 9.x.x
WESTELL.COM
Page 29
1-800-377-8766
Modules Version 2.91 Release Notes
Dialight
A0-A1 Style A.1
High Intensity A.31
Medium Intensity B.6
Medium Intensity Red A.6
Medium Intensity Small Red A.1
Red Only A2-A6 Style A.6
Eaton 9130 4.30, 4.32, 4.34, 4.36, 4.38
ElkorWattsOn Split Phase
WattsOn Three Phase
Eltek SmartPack 4.6, 4.7, 4.8, 4.9, 4.10
EmersonEmerson Rectifier
NetSure 4.00, 4.02, 4.04, 4.10, 4.21
FenceHawk RG-7781
Flash
Eagle 4747/9038
Eagle Ethernet 4747/9038
LED JUN 26 2012 10:47:38
Vanguard 2.7, 2.8, 2.9, 3.0,, 3.1, 3.2
Vanguard Ethernet 2.7, 2.8, 2.9, 3.0,, 3.1, 3.2
ForlongDRT-301C
DRT-301C2
Generac
EPanel
EPanel with Annunciator
H100 3.4-4.0
HTS 4.0
HTS Ethernet 4.0
GreystoneRH310A02C2E6
RH310A03C2A6
Huawei SMU V500R001C20SPC901T
Intelilite AMF25 1.4
WESTELL.COM
1-800-377-8766
Page 30
Modules Version 2.91 Release Notes
iSnail
VC
VC10
VC25
LovatoEXM10
RGK60 42
Marvair CommStat4 v62
Measurlogic DTS DC
Microwave Photonics OFW3478
SOLiD DMS-1200 4.2.0, 6.1.0
SPX
36305 JUN 26, 2012 10:47:38
9038XX 4747/9038
Vanguard 2.7, 2.8, 2.9, 3.0, 3.1, 3.2
Standardel DPS520
TE Prism 8.1.0, 8.1.7
ZTE
ZXDU
ZXDU68 W301 V.5.0 1.0G
ZXDU68 W301 V.5.0R06M04 1.12.01.01
Kentrox
Access Manager
Analog Battery Sensor
Analog Fuel Sensor
Discrete ATS
Discrete Asset Monitor
Discrete Controlled Generator
Discrete Door Sensor 18-130-101
Discrete Fuel Quality
Discrete Generator
Discrete Monitor
Discrete Power Detection
WESTELL.COM
Page 31
1-800-377-8766
Modules Version 2.91 Release Notes
Kentrox (continued)
Discrete Rectifier
Discrete Siren
Discrete Smoke Detector
Discrete Test ATS
Dual Discrete ATS
HPM
MeasTable
Module Monitor
RMB
RMC Power Detection
SBTEMP-RJ45
SBTEMPHUMIDITY-RJ45
SMS Backhaul Sender
Shared Discrete Generator
Tenant-Based Site Power Detection
Three Phase Voltage Teansducer
Virtual ATS
Virtual Battery String
Virtual Equipment Power Meter
Virtual Generator
Virtual HVAC System Energy Meter
Virtual HVAC Unit Energy Meter
Virtual Power Detection
Virtual Power Distribution
Virtual Power Management
Virtual Split Phase
Virtual Split Phase Power Detection
Virtual Three Phase
Virtual Three Phase Power Detection
WESTELL.COM
1-800-377-8766
Page 32