MODULERA Modular UPS Systems 60 / 100 / 200kVA 3Phase in / 3Phase out

Post on 23-Feb-2016

73 views 5 download

Tags:

description

MODULERA Modular UPS Systems 60 / 100 / 200kVA 3Phase in / 3Phase out . Main Features. Hot Swappable Modularized Parallel Architecture Decentralized parallel structure DSP ( Digital Signal Processor ) Controlled Technology Modular N+X Parallel Redundancy - PowerPoint PPT Presentation

transcript

MODULERA Modular UPS Systems

60 / 100 / 200kVA3Phase in / 3Phase out

Main Features Hot Swappable Modularized Parallel ArchitectureDecentralized parallel structure DSP ( Digital Signal Processor ) Controlled Technology Modular N+X Parallel Redundancy Parallel Operation up to 10 Power Modules High Power Capacity up to 200kVA on per single Rack Invest as You Grow , Easy to Upgrade Common Battery Operation Cold Start Function Parallel connection availability of UPS Frames up to 4pcs

25% 50% 75% 100%0.0

1.0

2.0

3.0

4.0

5.0

6.0

7.0

8.0

9.0

10.0

R

S

T

LOAD(%)

THD

I(%)

Low Input Current Distortion (THDi <3% )

Main Features

25% 50% 75% 100%0.975

0.980

0.985

0.990

0.995

1.000

R

S

T

LOAD(%)

PF

High Input Power Factor ( p.f. = 0.99 )

Main Features

25% 50% 75% 100%89.0

90.0

91.0

92.0

93.0

94.0

95.0

96.0

Efficiency η

η

LOAD(%)

Effi

cien

cyη

(%

High Efficiency ( up to 94% )

Main Features

Main Features High Output Power Factor ( p.f.= 0.9) Wide input voltage 208V~478VacWide input frequency range ( 40Hz – 70Hz )Plug & Play Type Hot Swappable Power Modules Each Power module with individual LCD display Touch-screen Graphical LCD Display Panel Centralized module monitoring is also availableSmart Fan Speed Control Fan spins according to load percentage ; 50%: Spin slowly / over 50%: Spin at full Speed

Main FeaturesHigh MTBF ( 250.000 hours ) and Low MTTRBattery Temperature CompensationPowerful Charger Built in Module ( Max. 6Amp ) Equip with Maintenance Bypass Switch for easy maintenanceRS232 & 485 Ports as standard communication Remote EPO FunctionMegatec/Mod Bus Protocol Optional Communication Interfaces (SNMP or DRY contact)

MODULERA FRAME TYPES

MDL 3300-60KMDL 3300-100K

MDL 3300-200K

200kVA 60kVA & 100kVA

MODULERA FRAME TYPES

MDL 3300-60K = 3+1 Modules ( 3modules for power upgrade + 1module for redundancy

MDL 3300-100K = 5Modules

MDL 3300-200K = 10Modules

Max. 4Frames can be connected in parallel

MODULERA POWER MODULE

MDL3320-RM 3/3 Power Module20KVA/18KW Module

Compact Size Only 3U Height

3U O

nly

Plug-and-Play Hot Swappable Module

Safe Swappable Modular Concept Reduce SPOF(Single Points of Failure) Power Availability Increase High Power Capacity Reduced Footprint Flexibility/Scalability Less Service Cost Lowest Installation Cost

Battery Temperature Compensation Set from LCD Display

Compensate from 20 C: Reduce 0.001V*6 of floating voltage per 1°C.

0.002~0.006V * 6 per 1°C settable

Battery Voltage Configurable 384/408/432/456/480Vdc

Configurable Decrease Initial Investment Increase Competition

Derating OperationDerating as per Temperature : Normal operation Temperature 0~40 C Max. operation Temperature 50 C De-rating operation: 10% per 5 C

Derating as per Altitude : Max. Altitude for normal operation : 1500m The load capacity should be reduced as shown in the below table when the UPS is installed in a place where altitude is higher than 1500 m;

Altitude( m) 1500 2000 2500 3000 3500 4000 4500 5000

Loadcoefficient

100% 95% 90% 85% 80% 75% 70% 65%

Powerful Charger Each Power Module: 6Amp 60K: Max. 18A 100K: Max. 30A 200K: Max. 60ACharging Current adjustable from LCD3-Stage Intelligent Charging Modes Constant Current Constant Voltage Floating (Boost Charge 2.30V to 2.35V per cell & Float Charge 2.20V to 2.29V per cell)

Power Module LCD Display

Input Voltage/Frequency Output Voltage/Frequency Load Capacity, Battery Voltage/Current Charge Modes/Charger Status Internal/Ambient Temperature Module ID/Status Alarm Codes

Touch-Screen Graphical LCD Display Panel

Touch-Screen Graphical LCD Display Panel

ONLINE 30KVA 22-12-2008ID:01 08:30

◄ Output Module Input Batt State ►

APhase Voltage(v) 220Phase Current(A) 1Frequency(HZ) 50Active Power(kw) 0.0Apparent Power(KVA) 0.0Load percent(%) 0Load crest factor 0.0   

  

ONLINE 30KVA 22-12-2008ID:01 08:30

◄ Output Module Input Batt State ►

Module01 A B C Invert Voltage(V) 380 380 380 Invert Current(A) 220 220 220 Frequency(HZ) 50 Positive Bus Voltage(V) 400 Negative Bus Voltage(V) 400 Code 8000-8000 D800-8000 0000-0000 0000-0000  Back

 

ONLINE 30KVA 22-12-2008ID:01 08:30

◄ Output Module Input Batt State ►

Mains A B C Phase Voltage(V) 380 380 380 Phase Current(A) 220 220 220 Frequency(HZ) 50 Power Factor 0.97 0.97 0.97 Bypass Phase Voltage(V) 220 220 220 Frequency(HZ) 50

  ONLINE 30KVA 22-12-2008ID:01 08:30

◄ Output Module Input Batt State ►

 Positive Battery Voltage (V) 240.0Negative Battery Voltage (V) 240.0Positive Battery Current (A) 10.0Negative Battery Current (A) 10.0Battery State ChargeBattery Temperature (℃) 28Lasting(min) 90

 

Complete status information about ;Input / Output / Battery /Modules

Touch-Screen Graphical LCD Display Panel

UPS Management Commands;Battery TestBuzzer Set Default Set

ONLINE   

30KVA 22-12-2008 ID:01 08:30

◄  Command Setting Record Version ►

Battery TestBuzzer Set MuteDefault Set

 

ONLINE 30KVA 22-12-2008 ID:01 08:30

◄ Command  Setting Record Version ►

 

Language Change Password Date Setting Back-light Delay Contrast Self-Test Date Back Next 

ONLINE 30KVA 22-12-2008 ID:01

08:30 ◄  Comman

d Setting Record Version ►

Work Mode Single

LBS Group Setting Ma System Voltage Level 220 System Frequence Level 50 Auto Turn-on En Bypass Frequence Range 2 Bypass Volt. Upper Limit 1

Back Bypass Volt. Lower Limit -30 Output crest factor 0%

Next 

Self-Test Date Mode: Weekly ▲ Week: SAT Time: 18:36 ▼ Lasting: 60min

Ensure Cancel

LBS Group Setting

▼Master▲Ensure Cancel

Touch-Screen Graphical LCD Display PanelSettings; Language System Parameters Working Modes Parallel ID Battery Voltage/Capacity

ONLINE  

  30KVA 22-12-2008 ID:01 08:30

◄ Command  Setting Record Version ► Language Change Password Date Setting 2008-12-22 08:30:00 Back-Light Delay 10Min Contrast 20 Self-Test Date STA 18:36 FOR:60min Back Timing of ON/OFF ON:MON 08:48 OFF:SUN 17:25 Next

 

ONLINE   30KVA 22-12-2008 ID:01 08:30

◄  Command Setting Record Version ►

Parallel ID 01M/S hot standby Cyc. 6 MonUPS Output EnablePre-Alarm Time 14 MinFloat Volt Revise 0.001Parallel Amount 04Parallel Redundancy 01 Back  Next

 

ONLINE 30KVA 22-12-2008 

ID:01 08:30

◄ Command  Setting Record Version ► Single Battery Volt. 12VBattery Number 20Battery Group 1Single Battery Capa. 100AHBoost Upper Limit Volt. 2.31Float Base Volt. 2.25Battery Protect Volt. 1.70Boost Charge Enable BackBoost Last Time 231 MinMax Charge Current 25A Next

 

  ONLINE 30KVA 22-12-2008ID:01 08:30

◄  Command Setting Record Version ►

Work Mode Single LBS Group Setting Master System Voltage Level 220V System Frequency Level 50HZ Auto Turn-on Enable Bypass Frequency Range 2% Bypass Volt. Upper Limit 10% Back Bypass Volt. Lower Limit -30% O/P Volt Micro tuning 0% Next

 

Touch-Screen Graphical LCD Display PanelRecord All Events/Alarm Message;Display Up to 49 events 50 alarm messages

  ONLINE 30KVA 22-12-2008ID:01 08:30

◄  Command Setting Record Version ► 0001 12-21 15:00:26 On Line0002 12-21 15:00:25 Rectifier Active..0003 12-21 15:00:10 Int.Input Switc..0004 12-21 15:00:08 Int.Bypass Swit..0005 12-21 15:00:05 Int.Output Swit..0006 12-21 15:00:00 Ext. Output Swit..

Back  Next

 

ONLINE 30KVA 22-12-2008 ID:01 08:30

◄ Command  Setting Record Version ►

 

ID:00 Record:0001 ▲2008-12-21 15:00:25 Status:On Line ▼Event: On LineAlarm:CODE: CC00-0000 DF00-0000 0000 0000-0000 0000-0000 Quit

ONLINE 30KVA 22-12-2008ID:01 08:30

◄ Command  Setting Record Version ► 

Single Battery Volt. 12VBattery Number 20Battery Group 1Single Battery Capa. 100AHBoost Upper Limit Volt. 2.31Float Base Volt. 2.25Battery Protect Volt. 1.70Boost Charge Enable BackBoost Last Time 231 MinMax Charge Current 25A Next

 

Max Charge Current

▼ 25 ▲Ensure Cancel

Touch-Screen Graphical LCD Display PanelCharge Current Setting :

ONLINE 30KVA 22-12-2008 ID:01 08:30

◄  Command Setting Record Version ► Single Battery Volt. 12V

Battery Number 20Battery Group 1Single Battery Capa. 100AHBoost Upper Limit Volt. 2.31Float Base Volt. 2.25Battery Protect Volt. 1.70Boost Charge Enable BackBoost Last Time 231 MinMax Charge Current 25A Next

 

ONLINE 30KVA 22-12-2008 ID:01 08:30

◄  Command Setting Record Version ► 

Single Battery Volt. 12VBattery Number 20Battery Group 1Single Battery Capa. 100AHBoost Upper Limit Volt. 2.31Float Base Volt. 2.25Battery Protect Volt. 1.70Boost Charge Enable BackBoost Last Time 231 MinMax Charge Current 25A Next

 

Battery Number

▼ 20 ▲Ensure Cancel

Battery Group

▼ 1 ▲Ensure Cancel

ONLINE30KVA 22-12-2008 ID:01 08:30

◄  Command Setting Record Version ►  

 

Single Battery Capa.1000

7 8 9 Cancel

4 5 6 ←1 2 3 →

. 0 Ensure

Touch-Screen Graphical LCD Display PanelBattery Qty & Capacity Setting :

Single Line Diagram

Multi-Communication Interfaces

2 x RS485 Ports 1 x RS232 Port 1 x Mod Bus Port 2 x Communication

Slots

Communication Interface Options SNMP Card Megatec Protocol Supported

Communication Interface Options Dry Contact Board Pin Function

1

O/P

Utility Failure

2 /

3 Battery Low

4 On bypass

5 UPS Fault

6 Inverter On

7 UPS Alarm

8 Common

9

I/P

+12V

10 0V

Fuses & Breakers  

MDL 3300-60K MDL3300-100K MDL3300-200K

Input Breaker ( present on each power module

as built in )

3P 40Amp 230/400VAC

3P 40Amp 230/400VAC

3P 40Amp 230/400VAC

Output Breaker ( present on the frame )

3P 125Amp380/400/415VAC

3P 250Amp380/400/415VAC

3P 400Amp380/400/415VAC

By-Pass Breaker ( present on the frame )

4P 125Amp380/400/415VAC

4P 225Amp380/400/415VAC

4P 400Amp380/400/415VAC

Batteries Breaker ( present on the frame )

3P 175Amp 250VDC/415VAC

3P 250Amp 250VDC/415VAC

3P 600Amp 250VDC/415VAC

Mission critical & industrial applications Operator Centres, Servers, Computer rooms, Telecom Switchgear & Infrastructures, Processing Control Equipments, Security Systems, Emergency Lighting, Fire Protection, Airport Infrastructure, Bank, Hospital, Healthcare Equipment …