8/10/2019 Motor Diesel San Luis
1/16
POWER PRODUCTS
PR60e/US-2005/1
60Hz0 kWe -2000 kWeENGLISH
8/10/2019 Motor Diesel San Luis
2/16
Since its creation in 1966, SDMO
Industries has chosento specialize exclusively in generating sets, so as to
concentrate on the competitiveness and quality of its
services. From this specialization, SDMO has acquired
skills recognized by all of its customers.
SDMO is now one of the worlds leading companies in
the generating set market and is committed to supplying
you with impeccable products.
Specializing in the manufacture of generating sets,
SDMO offers you a wide range of standard sets,
from 1 to 2000 kWe. Its teams, spread over
3 production sites, have skills at the leading edge
of the new technologies and of manufacturing
processes. Each team works on a common data
base, and specializes in a range of standard
products, thus increasing its efficiency.
SDMO undertakes to supply you with a reliable,
innovative and quality electrical energy source,
to accompany you in each of your projects.
SDMO
60HZPOWER PRODUCTS
8/10/2019 Motor Diesel San Luis
3/16
Now SDMO is represented in over 150
countries, thought a network of agents,
distributors, 8 subsidiaries all established in
Great Britain, Spain, Belgium, Singapore,
Argentina, the United States, Brazil, Nigeria
and a liaison office in Algeria. SDMO
devotes its energy to accompanying you
in the successful completion of each
of your projects all over the world.
SDMO
is committed to supplying you with the energy sourcwhich suits you, where you need it
In order to provide you with proof of
reliability, SDMO has introduced a quality
procedure. Its careful compliance with this
commitment has made it possible to obtain
ISO 9001 certification. For you this is the guarantee
that delivery will take place on time, with the best possible
monitoring of your order. The reputation for service qualityacquired by SDMO all over the world is the result of this continuous
search for improvement.
he generating set specialist
8/10/2019 Motor Diesel San Luis
4/16
60HZPOWER PRODUCTS
SDMO Power Products from 650 kWe to 2000
X 910 UC
X 650 UC
(1) Available voltages, page 7 (2) Standby Power (ESP) (3) The dimensions and weights are given for a defined generator according to the price list excluding options. Soundproof version, p8-9 (4) Dimensions arewithout cooling system (5) PRP : Prime Power is available for an unlimited number of annual operating hours in variable load applications, in accordance with ISO 8528-1. A 10% overload capability is available for a pe1 hour within 12-hour period of operation, in accordance with ISO 3046-1 (6) ESP : The standby power rating is applicable for supplying emergency power in variable load applications in accordance with ISO 8528-1. not allowed.
Standard.
THREE PHASE GENSETS
PRP(5) ESP(6) kWm Engine type Cyl. Bore Stroke Cyl. EPA CARB Brand Type Dimensions(4)
net(2) (in) (in) (Ci) LxWxH(in)
Genset
Type
Genset specifications Engine specifications Alternator Compact ve480/277 V(1)
kWe Engine
G E N E R A L S P E C I F I C A T I O N S
Range
EXEL 1
EXEL 2
Consump.75% load
(US Gal/h)
X 650 UC 591 650 735 34,5 12V2000G43 12V 5,1 5,9 1457 Tier I LS 491 M5 153x64x77
X 750 UC 682 750 835 32,2 12V2000G83 12V 5,1 5,9 1457 Tier I LS 491 L9A 153x64x77X 910 UC 828 910 1000 47,3 16V2000G43 16V 5,1 5,9 1945 Tier I LS 491 L10 172x70x86
X 1000 UC 909 1000 1115 43 16V2000G83 16V 5,1 5,9 1945 Tier I LS 501 S4 172x70x86
X 1145 UC 954 1145 1250 48,9 18V2000G83 18V 5,1 5,9 2183 Tier I LS 501 M6 180x80x87
X 1250 UC - 1250 1490 66,5 12V4000G41 12V 6,5 7,5 2976 Tier I LS 501 M7 148x72x87
X 1500 UC 1364 1500 1640 73,2 12V4000G81 12V 6,5 7,5 2976 Tier I LS 501 VL10 156x72x87
X 1750 UC - 1750 1990 88,7 16V4000G41 16V 6,5 7,5 3963 Tier I LS 512 S55 170x72x87
X 2000 UC 1818 2000 2190 96,7 16V4000G81 16V 6,5 7,5 3963 Tier I LS 512 M60 174x72x87
8/10/2019 Motor Diesel San Luis
5/16
60HPOWER PROD
X 1500 UC
X 1145 UC
THREE PHASE GENSETS
X 650 UC 12V2000G43 491 M5 591 650 591 650 591 650 591 650
X 750 UC 12V2000G83 491 L9A 682 750 682 750 682 750 682 750
X 910 UC 16V2000G43 491 L10 828 910 796 875 - - - -
X 1000 UC 16V2000G83 501 S4 909 1000 909 1000 - - - -
X 1145 UC 18V2000G83 501 M6 954 1145 954 1145 - - - -
X 1250 UC 12V4000G41 501 M7 1137 1250 - 1250 - - - -
X 1500 UC 12V4000G81 501 VL10 1364 1500 1364 1500 - - - -
X 1750 UC 16V4000G41 512 S55 1591 1750 - 1750 - - - -
X 2000 UC 16V4000G81 512 M60 1818 2000 1818 2000 - - - -
480/277 V 440/254 V 220/127 V 208/120 V
Genset type Engine Alternator T61A1 (kWe) T61 A3 (kWe) T61 B2 (kWe) T61B3 (kWe)
PRP ESP PRP ESP PRP ESP PRP ESP
G E N E R A L S P E C I F I C A T I O N S
Range
EXEL 1
EXEL 2
8/10/2019 Motor Diesel San Luis
6/16
automatic oil top-up
264 US Gal daily tank
with auto pump
batteries mounted
centrifuge filter
(doubles the interva
between oil changes
radiator with mechani
fan for XS 650 to
XS 1145 UC
documentation level
1
2
3
4
5
6
optional equipmentE Q U I P M E N T S
Standard & Options
Motor
Alternator
Genset
Oil
Cooling
Exhaust
Starting
Fuel
Miscellaneous
EXEL 1MTU 2000
Series
EXEL 2MTU 4000
Series4-stroke liquid-cooled diesel engine
Electronic governor
Standard air-filter
Air filter with replacable cartridge EN 02 EN 02
Coolant heater 220/240 V (without relay) EN 20 EN 20
Double starter Air/Elec (1) SO 005 SO 005
Double starter Elec/Elec (1) SO 007 SO 007
IP 23 single bearing alternator, class T=H
Anti condensation heater AL 01 AL 01
Tropical impregnation AL 05(2)
Isolation and finishing work reinforced AL 06 AL 06
CTP stator pick up AL 07 AL 07
CTO bering pick up AL 08 AL 08
PT 100 stator pick up AL 09 AL 09
PT 100 bearing pick up AL 10 AL 10
Droop kit + 3 function regulator O(3) O(3)
Alternator oversizing AO 001B AO 001BElectric panel CE compliance
Fabricated all welded baseplate with anti-vibration mountings
Standard colour RAL9005/5007 (black/blue)delivered in shrinkwrap
Supplied with oil and coolant (-86F)
Automatic filling up oil system with oil tank EN 18 EN 18
Oil centrifuge filter X EN 19
Lub oil drain pump
Radiator for "air on" temperature 122F maxi air cooler (4) (9) X
Mounted radiator for "air on" temperature 122F maxi with drain cock (4) X
Electrical louvres X CS 003
Delivered without coolant FD 11 FD 11
Protection maeh for fan and revolving parts
Front rad protection EN 14 X
Stainless steel bellows
Silencer 9 dB(A) supplied separately EN 07 EN 07
Silencer 29 dB(A) supplied separately EN 08 EN 08
Silencer 40 dB(A) supplied separately EN 09 EN 09
Heat and protection CEL 02 X
Starter and charge alternator 24 V 24 V
Non-supply charge alternator X EN 17
Battery with cables and battery tray SO 001 SO 001
Non-supply of batteries and tray
Battery isolator EN 16 EN 16
Generator without tank
Tank with retent. Bund 132 US Gal FD 06 FD 06
Tank with retent. Bund 264 US Gal FD 07 FD 07
Retention bund alarm FD 14 FD 14
Auto. Fuel fill kit (1 pump 35Ft3/H) FD 08 FD 08
Auto. Fuel fill kit (2 pump 35Ft3/H) FD 09 FD 09Auto. Fuel fill kit (2 pump 141Ft3/H) FD 10 FD 10
W separator fuel prefilter
Fuel cooling radiator X EO 006
Technical documentation language to choice(5) level A (6) (1 copy)
Technical documentation language to choice(5) level A (6) (extra copy) AD 23 AD 23
Technical documentation english version level B(7) AD 31 AD 31
Technical documentation english version level C(8) AD 41 AD 41
GENSERVICE spare parts O O
Standard X Impossible O Different options available EN 01 Option code EN 01 Free option
(1) No control panel available for this option (2) Standard for XS 1145 (3) Coupling IT. Unecessary with the Mics KERYS (4) Outdoor ambient temperature, reduce of 45F approximately (5) French or English(6) Level A documentation including : Maintenance manual and diagrams, Genset user manual and description of switchboard, Genset installation guide (7) Level B including : level A + list of engines and alternator parts(English only) (8) Level C including : level B + workshop manual (English only) (9) 115F for X1145UC
1
2
3
4
5
6
8/10/2019 Motor Diesel San Luis
7/16
Contenergy
International standards-compliant trailers are also available, thus
enabling you to transform your generator set into a mobile unit
(contact us for further details).
The CONTENERGY containers
can be installed on a concrete slab
(fitted with ducts for the cabling
and piping) or simply on a hardsurface. This CONTENERGY
concept is very simple and
economical, thanks to its integrated
cooling system, silencer and sound
traps.
Through the years, SDMO has dealt with many installation
requirements, which is why our current containers are designed to
withstand difficult climatic conditions. Whether your installation
needs to withstand extreme cold or tropical conditions, our designs
are flexible enough to accommodate your each and every need.
Whether your installation needs to withstand extreme cold
conditions or has to operate in a tropical climate, tell us what you
need, we probably have the solution to your problem.
8/10/2019 Motor Diesel San Luis
8/16
60HZPOWER PRODUCTS Contenergy
The ISO Contenergy are designed in
accordance with dimensions defined by the
ISO/TC104(1) standards. This design enables
during transport to endure without damage
high pressures and big loads and to travel by
boat without specific constraints.
Two sizes are available : 20 and 40 feet
High Cube.
The CIR version is built on an ISO 20Contenergy base. This very compact model
is more specifically suited for rental and
mobile applications thanks to its high
capacity and its low sound level.
Compliance with the ISO/TC104(1) standard
upon request.
Dedicated to generator sets fitted with MTU-DDC Series 4000 motor, the EUR Contenergy offers, for a single
base, two noise level variations : Silent and Super Silent.
This soundproofed version also offers features such as side doors or a daily tank.
CIR 20
(1) The ISO / TC 104 standard includes the ISO 668, ISO 1496-1, ISO 830, ISO 1161, ISO 3874, ISO 6346 standards and ensures the CSC cer tification.
EUR 40
8/10/2019 Motor Diesel San Luis
9/16
Standard containers
SDMO now offers a sound-proof hood for your EXEL generator set fitted with anMTU 12V2000 or 16V2000 motor.
You thus optimise your installations footprint and can even fit the assembly into a 40 High Cube container in order to facilitate transport.
Genset type Canopy Tank Dimensions Weight(1) Noise level - 60 Hz
(US Gal) (feet) (Ibs) dB(A)@23 feetX 650 UC 427 264 21x7.1x18.9 17364 79X 750 UC 427 264 21x7.1x18.9 18103 79X 910 UC 427 264 21x7.1x18.9 18969 77
X 1000 UC 427 264 21x7.1x18.9 19641 77(1) Dry weight, without fuel
Genset type Engine SILENT SILENT SUPER SILENT SUPER SILENT
79-82 DB (A)@23 feet 78-81 DB (A)@23 feet 73-75 DB (A)@23 feet 77-79 DB (A)@23 feet
X 650 - X 750 12V2000 ISO 20 Si X CIR 20 SSi XX 910 - X 1000 16V2000 ISO 20 Si X CIR 20 SSi X
X 1145 18V2000 ISO 20 Si X CIR 20 SSi X
X 1250 - X 1500 12V4000 ISO 40 Si X EUR 40 SSi CIR 20 SSiX 1750 - X 2000 16V4000 X EUR 40 Si EUR 40 SSi X
Range
EXEL
C H A R A C T E R I S T I C S
P R E S E N T A T I O N
E Q U I P M E N T S
M O D E L S
Standard X Impossible EN 01 Option code CT 011 Free option
Standard & Options
Base
Specifications
Carburant
Panels
Dimensions
SILENT SUPER S ILENT
ISO 20 SI ISO 40 SI EUR 40 SI CIR 20 SSI EUR 40 SSI
Baseplate
Starter, charging alternator 24 V
Batteries with electrolyte SO001 SO001 SO001 SO001 SO001
Standard air-filter Lub oil drain pump
Sound-proofing type Si Si Si SSi SSi
Highly efficient silencer built in - attenuation 30dB (A)
Floor wooden wooden wooden Waterlight steel wooden
Number of doors 1 2 2 2 2
Air outlet galvanized steel rain guard grid CT 005 CT 005 X
Emergency light and emergency fuel valve CT 007 CT 007 CT 007 CT 007 CT 007
Exhaust exit on flanges CT 011 CT 011 CT 011 CT 011 CT 011
White paint finishing (RAL 9010)
Retention bund under the whole container CT 014 CT 014 CT 014 CT 014 CT 014
Tank without retent. Bund 132 US Gal X X X
Tank with retent. Bund 132 US Gal X X
Tank with retent. Bund 600 US Gal + external renting connection terminal box X X X CT 003 X
Auto. Fuel fill kit (1 pump 35ft3/h) CT 008 CT 008 CT 008 CT 008 CT 008
Auto. Fuel fill kit (2 pump 35ft3/h) X CT 009 CT 009 X CT 009Auto. Fuel fill kit (2 pump 14ft3/h) X CT 010 CT 010 X CT 010
Electric panel EC compliance
Mics TELYS Control panel CM 40 CM 40 CM40 CM 40 CM 40
Mics KERYS Control Panel CA 600 CA 600 CA600 CA 600 CA 600
Length (feet) 20 40 20 40 40
Width (feet) 8 8 8 8 8
Height (feet) 9.5 9,5 9.5 9.5 9.5
M 427
8/10/2019 Motor Diesel San Luis
10/16
electrical panels
0
POWER PRODUCTS
60HZ
The M80 cabinet is a direct display control panel. Its various dials provide a global overview of our generator sets basic
parameters.
Three control cabinets are available in our 650 to 2000 kWe range : the M80, the Mics TELYS and the
Mics KERYS. In order to guarantee a high degree of modularity and standardisation, each optional peripheral
device (aero, RJ, oil top-up) possesses its own protection.
For plants, an auxiliary cabinet containing the mains detection and preheating controls can be fitted, along with
separate cabinets.
S P E C I F I C A T I O N S
P R E S E N T A T I O N
M 80
Instruments
Emergency stop
CE Compliance
Client connection terminal strip
Tachometer (54 mm)
Timer
Oil pressure gauge
Water temperature display O
Oil pressure display O
Operation
Miscellaneous
Engineparameters
Oilpressure
Timer
Emergencystop button
Tachometer
Watertemperature
M 80
Standard O Option code
8/10/2019 Motor Diesel San Luis
11/16
A major component of our range of control units, the Mics TELYS is a standard addition to our generator sets from 300 kWe
upwards its user-friendly interface and range of features allow careful monitoring of your installation.
MICS TELYS
(1) Control and automatisms installed, but necessity to have the option "External AMF predisposition" and the possible configuration of one parameter on the MICS
Telys (2) The choice Alarm or Fault is programmed through the keyboard (3) The earth fault protection is ensured by one external module connected to the CB12card and through connecting of one tiny relay on the CB12 card. A local configuration is also needed (4) MICS DS mains detection is proposed as a base in thesource inverter. In the case whereby the source inverter is not chosen, the MICS DS module can be moulded in the panel (5) Choice is revised through programming- The alternator's voltage reference connecting wire modification is necessary (6) Not available on Mics KERYS
Measurements
Operationan
d/orsa
fetylights
Safety
devices
Automation
Misce
llaneous
Line voltages in Volts
Single voltages in Volts
Phase currents in Amps
Neutral current in Amps
Frequency in Hertz
All generating set states, all starter phases
Analogical indicator
Ammeter battery
Indication of engine speed
Indication of battery voltage
Elapsed hour meter
Powering up
Fuel solenoid-operated valve controlStarter control
Plug preheating control
Water preheating control
Mains contactor control
Generating set contactor control
Oil pressure fault
Water temperature fault
Fail to start fault
Overspeed fault
Set ready for load
Charging alternator fault
General alarm
General fault
Panel lamp, 22 dia.
STOP/MANU/AUTO/TEST mode
Generating set side contactor closed
Mains side contactor closed
Any faults or any alarms messages
Oil pressure fault
Water temperature fault
Emergency stop fault
Overload or short-circuit alarm or fault
Min/max battery voltage alarm or fault
Min/max alternator voltage alarm or fault
Min/max alternator frequency alarm or fault
Overspeed fault
Differential relay present fault
Differential triggering alarm or fault
Automatic standby
Automatic extinction
4 modesEngine stopping for cooling
Voltage and speed stabilization
Plug preheating
ATS changeover presence choice
Mains contactor position return
Generating set and mains contactor position return
Generating set contactor manual closing
Generating set contactor manual opening
Starting on clock
External starting order
Mains sensing 3-ph
Test LEDs
Fault reset
External AMF predisposition
3-phase with or without neutral, 2-phase or single-phase use
12V battery charger
NFPA 110 level 1 modul (6)
Differential protection with time and sensitivity adjustment
Alarm hooter
LCD
LCD
LCD
LCD
LCD
LCD
O
O
LCD
LCD
LCD
O
O
O (1)
O (1)
O (1)
O (1)
LCD
(2)
(2)
(2)
(2)
O (3)
O (2+3)
O
O (1)
O (1)
O (1)
O (1)
O (1)
O (1)
O (1)
O (4)
O
(5)
O
O
O (2)
O
S P E C I F I C A T I O N S
This software developed by SDMO enables the user to set up the dialog between the Mics TELYS panel fitted
on our gensets and the PC type computer on which it is installed in order to control from a distance the operating
system. Depending on the configuration of your installation, you can select from 4 types of connection, the one
that best suits your needs : local mode supervision, Switched Telephone Network remote management, Ethernetremote management or maintenance or SGM electronic surveillance. For further information concerning Wintelys,
please contact an SDMO reseller.
Engine
Parameters
Operation
P R E S E N T A T I O N
1 - Oil pressure fault (R)
2 - Water temperature fault (R)
3 - Failure to start fault (R)
4 - Overspeed fault (R)
5 - Set ready to output (G)
6 - Charging alternator fault (R)
7 - General alarm (Y)
8 - General fault (R)
(R = red, G = Green, Y = Yellow)
8 DISPLAYLEDS
alarms, faults, statuses
LCD SCREENincorpored back-lighting,featuring 8 lines x 21 characters
1 ON KEYwith integrated LED
(after automatic extinction)
2 generating SET REGULATION
OUTPUT KEYS (+/-)
2 ERROR RESETAND LED TEST KEYS
4 OPERATING MODESELECTION KEYS
with integrated selection LEDs
15 PROGRAMMINGKEYS
NUMBER KEY PAD
(0 TO 9)
4 electrical QUANTITIESAND ENGINEPARAMETERS KEYS
Standard O Option code
LCD Standard with LCD message
8/10/2019 Motor Diesel San Luis
12/162
60HZOWER PRODUCTS
MICS KERYSP R E S E N T A T I O N
The Mics KERYS is available in two versions. The basic GUI (Graphical User Interface) is made up of a monochrome
LCD screen and a function keypad. The top of the range Mics KERYS Tactil version possesses a TFT colour touch screen.
Both of these versions provides a user-friendly configuration, operation or diagnostic interface.
The Mics KERYS possesses all of the features of the Mics TELYS (cf. table page 13)
For further information, check the Mics KERYS documentation
or contact your SDMO sales representative.
MeasurementsPowers (active, reactive)Power factor in the various dialsActive and reactive energiesSynchronism (phase, voltage and frequencydeviation)
Voltage and current harmonics
Protective measuresOverload, short-circuitLine current directiveNeutral currentReverse component
Voltage hold-backThermal image
Voltage max. and min.Presence and absence of voltage
Frequency max. and Min.Active poxer maximumActive and reactive reverse powerHomopolar current and homopolar currentdirectiveHomopolar voltage and restricted earth
Vector jump, mini Z and dF/dt
SynchronisationManual and automaticFrequency and voltage equalisation
ControlSpeed and voltageFrequency and voltage setpoint switchingFrequency and voltage setpoint adjusmentActive and reactive power setpoint adjustmentActive and reactive power ramp-upActive and reactive power distributionActive and reactive power lock-outManual speed and voltage control
CommunicationLocal or remote modeOn board Web siteRS485 linkEthernet (local mode) and Internet(remote mode)
Standard added benefitsFailure troubleshooting assistanceMaintenance assistance (logs, automatic Email,etc.)Electrical and mechanical parameter graphs andlogsLoad impact managementAddition of extra logics with no external tools
SynchronisingA612 : Generator set without gridA622 : Generator set with ATS and grid,no synchronising
A633 : Production plant without gridA634 : Production plant with grid and ATS (nogrid synchronising)
A641 : Generator set with permanent gridsynchronising, no ATS - grid synchronising + resale
A642 : Generator set with permanent gridsynchronising, no ATS - Grid synchronising + 0 kWpower cap on grid
A651 : Generator set with fading grid synchronisingand INS
A661 : Generator set with permanent gridsynchronising and ATS
S P E C I F I C A T I O N S
A D D I T I O N A L S P E C I F I C A T I O N S
The Mics KERYS is a user-friendly and intuitive tool that possesses a very broad range of features. It is fitted asstandard on all generator sets intended for synchronising applications and can be fitted as an option on all ofour other applications. In order to meet all of the requirements of low or high voltage power plants, the MicsKERYS can be fitted into a control desk, directly onto the generator set, or in aseparate cabinet. It complies with EC, UL and CSA standards.
Display screen
TFT LCD 7,4 in
Colour graphical display
Touch screen
Dimensions 6,10 x 3,40 in
Configuration keypad
For configuration, navigation
and direct access to screens
Control keypad
with display LEDs
Directional keypad
with activity LED
WEB SITE
The Mics KERYS and KERYS Tactil are providstandard with an on-board web site. This site andresident screens enables you to completely checinstallation (operation andsetup), whatever thedistance.
Electrical variabledisplay screen
Manu mode selectionStop mode selection
Auto mode selection
Open/Close GE circuit breaker
Activate/Deactivate test
Open/Close network circuit breaker
LED test
Stop horn
Erase anomalies
8/10/2019 Motor Diesel San Luis
13/16
Each genset can be delivered with a protection panel.This panel is fitted on the generating set frame with the connecting cables on to the alternator. Depending on the type and power ofthe engine, the panel AIPR can be positioned whether on the right or left hand side of the generating set.
POWER MODULES
C H A R A C T E R I S T I C S
AIPR Rating800A
1000A
1250A
1600A
2000A
2500A
3200A
3 poles power circuit breaker
Compact type
3 poles power circuit breaker
Open type
4 poles power circuit breaker O O O O
Compact type
4 poles power circuit breaker O O O
Open type
OPTION MOTORIZED CONTROL *
With 3 or 4 poles circuit breaker O O O O O O OOnly open type
Voltage 208-440V
Option power auxiliaries panel (**) O O O O O O O
Bus bars
Remote control terminal box
Protection index IP207 IP207 IP207 IP207 IP207 IP207 IP207
Dimensions : height (Feet) 4,13 4,13 4,13 4,13 4,13 4,13 4,13
(without optional panel) width (Feet) 2,18 2,18 2,18 2,18 2,18 2,18 2,18
depth (Feet) 1,18 1,18 1,18 1,18 1,18 1,18 1,18
Dimensions : height (Feet) 5,50 5,50 5,50 5,50 5,50 5,50 5,50
(with optional panel) width (Feet) 2,18 2,18 2,18 2,18 2,18 2,18 2,18
depth (Feet) 1,18 1,18 1,18 1,18 1,18 1,18 1,18
Standard O Option X Impossible (1) Protection of auxiliaries : mains power detection, panel relay, water heater, battery charger
(*) The motorized remote control includes : one XF coil, one MX coil, and one AC engine.(**) The optional panel "power auxiliary" is fitted above the main panel. It is used for the genset auxiliaries power connection, i.e :- air cooler supply- fuel pump supply
AIPR
WITH A FRONT MANUAL COMMAND
OPTION MOTORIZED CONTROL *
8/10/2019 Motor Diesel San Luis
14/164
PRESENTATIONBoth innovative and original in its design, it is perfectly adapted to applications in which transfer of the main source to the replacement source is central to thecorrect operation of your facilities.Intuitive and easy to use, this module is remarkable in that it is automatically configured in the presence of network-side voltage. By simply pressing the AUTOkey, the following parameters are configured: network voltage, min. and max. voltage threshold, type of use, min. and max. frequency threshold.Electronic power source switching allows it to permanently self-power itself.
NBIsP R E S E N T A T I O N
SCREENintegrated backlight, with two16-character rows
ROTOPHASE LEDIndicates the direction ofrotation of inverted phases.
Source Status LEDThree-colour LED symbolising
the source's status :Off : No voltageGreen :Voltage presentOrange : AlarmRed : Fault
NAVIGATION AND SELECTION keysused for browsing through the differentelectrical variable screens, or forcomplete module configurationto customer specifications.
Validation key
Testused to simulate generator set start-up,
with possible complete switch-oversequence.
User-defined key
Auto key: automatic module configurationautomatic operation on mains power cut or voltKey1 : Forced source 1 operation.Key2 : Forced source 2 operation.Lock-out key: complete inverter lock-ouand hence total isolation of the backed up sour(no downstream alternating voltage)
Padlock key: used to lock inverter operaPressing this key prohibits the operation of eitheof the instruments
Position LEDindicating the contactor's closedposition
60HZPOWER PRODUCTS
SDMO presents a complete range of separate NBIs (Normal Backup Inverters). Our technical solution presents a large number of advantages, boin terms of cost and of ease of installation.The design of our boxes and cabinets allows extremely easy connection, even to high cable cross-sections. The box's front panel no longer opens only one side, like a conventional box, but on three sides, thus providing full access to power equipment and terminal strip jumpers. All of our boxare either three-pole or four-pole.The TSI module (Transfer Switch Intelligence) is fitted as standard to our whole range of Normal/Backup Inverters, whatever the rating of the inverselement (from 25 to 3200 A).
T H E T S I M O D U L E
PROPERTIES2 screen lines for simultaneous network-side and generator-side voltage display. The same applies to the frequency.
The 6 LEDs provide instantaneous information concerning the position status of one or other of the 2 sources, along with any possible alarms or faultsADDITIONAL PROPERTIESCommunicationIn addition to a wired link for remote dry contact start-up on all SDMO monitoring / control modules (Nexys, Telys, Kerys), the TSI module possesseCAN bus allowing it to communicate with the Kerys MICS.This link allows the TSI to send to the Kerys all of the data concerning the network and the start-up order following a voltage variation.
Short Term SynchronisingAn additional board, available as an option*, allows: Short Term Synchronising on network substitution request Short Term Synchronising on return to mains.
Vo
ltage
Dimensions
Switc
h-over
208-440 V
By contactors X X X X X X X X X
By selector switches X X X X X X X
Height (mm) 500 500 500 500 500 500 600 800 800 800 1000 1000 1000 1800* 1800* 1800*
Width (mm) 430 430 430 430 430 430 600 600 600 600 800 800 800 1000 1000 1000
Depth (mm) 200 200 200 200 200 200 250 400 400 400 500 500 500 800 800 800
NBI2
5A
NBI3
2A
NBI4
5A
NBI6
3A
NBI1
10A
NBI1
40A
NBI2
00A
NBI2
50A
NBI4
00A
NBI6
30A
NBI8
00A
NBI1
000A
NBI1
600A
NBI2
000A
(1)
NBI2
500A
(1)
NBI3
150A
(1)
(*) On a base, height = 200 mm, i.e. a cabinet height of 1600 + 200 (1) Integrated into a cabinet on the ground
*As from June 2005
8/10/2019 Motor Diesel San Luis
15/16
C A R A C T E R I S T I C S
SERVICES
In order to provide you with faultless products, SDMO has created a Service department with three major objectives:
Technical assistance
Technician and agent training
Spare Parts
T E C H N I C A L A S S I S T A N C E
SDMOs technical assistance department is committed to providing an efficient and
effective after-sales service program.
Through our mass network of distributor and agents, users are guided and supported towards the best answer to their
questions.
Whether a user is directed towards a regional agent or if on-site maintenance is required, all situations are taken
intoaccount in order to provide the best possible service in the shortest time frame.
T R A I N I N G
In order to optimise the performance levels of the SDMO generator sets, the Services
Department possesses a training centre in Brest, near to our production plant, and designed for
our customers' and agents' technicians who service our products.
Syllabus: "Generator set operation and maintenance", "Mechanical engineering", "Electricity", topped up with
specific one-off courses performed on-site and on request.Each year, 2200 man-days of training, dispensed by specialists, are dedicated to the acquisition and updating of
SDMO product knowledge.
S P A R E P A R T S
The Spare Parts Department represents 25,000 references, of which 9,200 in stock, on 4.5 km of shelving.
In charge of managing stocks and procurements, the SPD is also responsible for service traceability and ensures the
ongoing improvement of quality. It is with these points in mind that the Spare Parts Department created GENPARTS,
an SDMO spare parts brand. The SPD also provides our customers with interactive computer assisted spare parts
selection tools.
8/10/2019 Motor Diesel San Luis
16/16
SUBSIDIARIES
SDMO GENERATING SETS IncUSATel. +1 305 863 00 12 Fax +1 305 863 97 81
SDMO DO BRASIL LtdaBrazil
Tel. +55 (11) 4053-2700 Fax +55 (11) 4053-2718
SDMO ARGENTINAArgentina
Tel./Fax +54 114 205 3005
SDMO ASIA PACIFIC PTE LtdSingapore
Tel. +65 6419 3788 Fax +65 6419 3798
SDMO ENERGY Ltd
UKTel. +44 (0) 1932 345 777 Fax +44 (0) 1932 350 033
SDMO INDUSTRIES IBERICASpain
Tel. +34 93 586 34 00 Fax +34 93 580 31 36
SDMO LAGOSNigeria
Tl. +234 (0) 1 776 95 95 Fax +234 (0) 1 461 34 75
OFFICES
SDMO ALGERAlgeria
Tel. +213 21 92 55 84 Fax +213 21 92 47 76
SDMO Industries 12 bis rue de la Villeneuve CS 92848 29228 BREST Cedex 2 France
ISO 9001
SDMO IndustriesSites in France