ROYAL SERVICESUPPLIES (U.S.A.)
Constant Air Flow RegulatorsVariable Air Flow Regulators
Non- Electric / Electric
RSCAVC-AIR SIDE SOLUTION
Constant Air flow
Designed to control the flow of air without power.
Maintain set point in a pressure independent
operation.
Building-Designed Air Side Solutions
The model RSV-CAVC / can be operated at a
constant or variable- flow rate to maintain the
designed air flow. In an occupied or unoccupied
demand with, a low pressure drop damper
automatically maintains design air-flows in a supply
or exhaust systems. Controlled without electrical or
pneumatic in a pressure independent system.
Building designs cannot compensate for pressure
changes that commonly occur because of duct-work
installation, stack effect, poorly completed air
balancing, transfer duct-work sizing poorly, fans
operating over time and could be running over
designed static pressures and aging damper
adjustments off over time.
RS-CAVC fit the designs, the solutions and your
toughest requirements.
Balancing time is shortened and cost are
decreased because the RS-CAVC is pressure
independent with accessible settings. Final air fan
RPM is decreased adding to additional and some
time over looked energy savings in the total
building design. A complete air side ventilation
solution.
Manufactured air-side soultions are for most air
side systems, including cooling, heating and
RS-CAVC-R
RS-CAVC-Q
RS-CAVC-R
RS-CAVC-IRP
Non- Electric
Electric
1
Office and hotelOver 1000 RS-CAVC
ROYAL SERVICE SUPPLIES
AIR SIDE SOLUTION
Operation
Simple clock work function, the control arm
connects to the damper. It’s armature stainless
steel feeler spring control (ASC). When the
pressure modulates, the ASC control assembly
maintains flow at a constant rate. By using the
static pressure effect the flow setting is maintained.
Air flow temperature range is (38-155 F) (10-50C)
Model R Round or Q rectangle units: Once installed
in to the duct-work, operates pressure
independently. You can field-set the flow against
the required flow. The valve maintains the flow with
a mechanical balance of a UL-94-V2 -compliant
bellows and its armature stainless steal feeler
spring control (ASC). When the pressure
modulates the ASC controls the flow at constant
rate. In variable flow mode, the flow setting is
changed with an actuator. A standard control signal
operates the actuator for a floating or modulating
control point operation. The ASC controls the flow
throughout the range of the signal.
Both round or rectangle units operate and maintain
as close as 5 % in the middle range and 10 % on the
outside range.
Lower air flow rates are adjustable.
Pressure ranges are 0.2 inch Wg to 4.0 Wg, (50-800
PA) ( high-, medium, low -pressure systems). Units
are pre-factory calibrated as required. No
additional inserts for pressures or flow is required.
IR available in plastic or metal.
UL 181 compliant.
Installation
Installs into Round or rectangle duct-work.
RS-CAVC-IR Insert type installs into a 4 inch round
duct-work.
The CAVC-R metal units construction and lip can be
installed with metal or flexible duct.
RS-CAVC type flows are designed for air flows of
(30 CFM to 2650 CFM(45 m3hr to 4510 m3hr)
RS-CAV-Q type flows are designed for air flows of
(80 CFM to 7050 CFM(135m3hr to 1250m3hr).
ERV/PAU UNITS
Hotel Rooms
Rest Rooms
Confrence Rooms
Lobbies
2
ROYAL SERVICE SUPPLIES
PA 50 75 125 249 498 747 995
Inwg 0.20 0.30 0.50 1.00 2.00 3.00 4.00
ALLModel
HIGH
Med
Low
FL
OW
Selection
RS-Royal Service CAVC - constant air volume control DR- Round with 24 volt damper actuator in front of the cavc for on-off / open and shut off control
Q- Rectangle inlet and out let models showing only width dimensions here.
Selection
RS-Royal Service
CAVC - Constant Air Volume control
DR- Round with 24 volt damper actuator in front of the CAVC for
on-off / open- shut off control
Q- Rectangle inlet and outlet models showing only width
dimensions here.
R- Round inlet, round outlet
IR- Galvanized Steel Round insert type, Insert into the duct-work.
IRP- Plastic Round insert type, Insert into the duct-work.
Range for air flow. Use the product catalogue for extra models
Diffuser
CAVC
Diffuser
CAVC
Diffuser
Ceiling
Fig. Z7
Apartment fresh air and exhaust, Single air fans,E.R.V, and PAU units.
Operation-range
3
Apartment buildings fresh air and exhaust
CFM MCHR CFM MCHR CFM MCHR
4 100 26 45 34 58 68 115
4 100 26 45 34 58 68 115
4 TO 8 100-200 50 85 305 518 609 1035
4 TO16 100-400 50 85 1327 2255 2654 4510
6 TO 30 160-800 79 135 1142 1940 2284 3880
RS-CAVC-DR100-200
RS-CAVC-R100-400
RSCAVC-Q160-800
SIZE
LOW Med High
AIR FLOW
RS-CAVC-IR100
RS-CAVC-IRP100
ModelsINCH MM
Ĭ ÑÕÑŃPÒŎŌĪ Ĭ ǼĪ ŎŘMÕ Ĭ ÑǾQÒŃÑ
FĖIJF ǼŃŎŌŒPMŌP MÒǾ QŎÕÞÖ Ñ ŃŎŌPǾŎÕ GĪ ǼĪ ŎÞŌŇ R ÒPO ČÇ QŎÕP ŇMÖŐÑǾ MŃPÞMPŎǾ ÒŌ ŅǾŎŌP ŎŅ POÑ ŃMQŃ ŅŎǾ ŎŌǼŎŅŅ C ŎŐÑŌ MŌŇ ŒOÞP ŎŅŅ ŃŎŌPǾŎÕ
Ï ǼĪ ÑŃPMŌŊÕÑ ÒŌÕÑP MŌŇ ŎÞP ÕÑP Ö ŎŇÑÕŒ ŒOŎRÒŌŊ ŎŌÕŘ R ÒŇPO ŇÒÖ ÑŌŒÒŎŌŒ OÑǾÑB
ERV/PAU UNITS
ROYAL SERVICE SUPPLIES
Operation
Warranty
Guaranteed two years from the date of shipment
against defects in material or workmanship when
the units are install correctly and under normal
standard clean air flow conditions. Limited
warranty to the repair or replacement of the
materials.
Maintenance
Under normal standard conditions, no maintenance
is required.
Non-standard is not recommended. Consult the
factory.
Supply Air
Return Air
AHUPAU
CAVC-DRCAVC-R or -Q
CAVC FilterOSA
Fresh Air
Economizer control
CO2
4
AHUPAU
Diffuser
CAVC
Diffuser
CAVC
Control flow to each zone Fig. 03
Filter bankAir flow maintained over filter life
Air flow constantFB
RSCAVC
Fig. 01
AHUPAU
CAVC Mall Areas
High/Medium pressure duct
CAVC
High pressure Required flow
Fig. 04High/Medium air pressure duct-work systems
RS-CAVC-Q
RS-CAVC-R
RS-CAVC-IRP
ROYAL SERVICE SUPPLIES
Applications
Correct Airflow
Correct Airflow
Before RS CAVC installation
After RS CAVC installation
Installation changes
During operation, air dynamics change pressure
and flow from air filters to system dampers. The
CAVC will automatically change and maintain the
setting when there is a decrease or increase in the
static building pressures the damper modulates
and adjusts it self.
If the design was not correct, then the field can
adjust the damper to increase or decrease the flow
in the range of the damper.
Dirty filters will decrease the flow. With CAVC R-Q
it automatically adjusts.
Design of duct work changes during installation
Co2 changes set minimum and maximum air-flow
using a actuator connected to a Co2 sensor via
Indoor Air Quality
Specified outside / exhaust air is maintained.
Controllable outside / exhaust air is maintained.
You can set required code air flow.
Install with energy recovery ventilation (ERV).
Hotels complies with title 24 section 120.2.
Lab control of supply air.
Supply Air
Return Air
ERV
CAVC-R CAVC-R
5
RS-CAVC-Q
RS-CAVC-R
RS-CAVC-IRP
ROYAL SERVICE SUPPLIES
Applications- For Fan Control
Installation changes
Supply or exhaust units
Supply fans can now be adjusted without a fan-
motor variable speed drive (VSD), or SCR.
It is installed after the fan and the fan does not load
more then the air flow required therefore the motor
operates with the fan laws.
No fan speed control
6
AHUPAUFC
PCAVC
Lower CFM or increase CFM.(DX system adjust only to min allowable flow)
Modulating control
Air flow control
Fig. 02
ROYAL SERVICE SUPPLIES
Applications Large or small Individual zoning
Zone Applications
Supply a single zone for multiple diffusers.
Single diffuser for individual zone
No room sensor constant air flow.
Automatic control with a 24 volt damper motor
actuator and a room sensor installed, min and max
flows are adjustable. BA systems can operate
different flows for occupied or unoccupied times
and demands.
Heating flows and cooling flows are adjustable.
Manual control at the unit or install a cord adjustor.
7
Fig. Z1
Diffuser
CAVC
Diffuser
Ceiling
Fig. Z2
Diffuser
CAVC
Exhaust, room, restrooms, lobbies, and floor corridors.
Supply air zones for Rooms, Laboratories, and general areas
ROYAL SERVICE SUPPLIES
Apply with all Hard Ceiling Zones with manual ceiling adjustors
HSZ
Hard ceilings require damper
adjustments at the ceiling. Installing a
metal cable attached to the RS-RS-CAVC.
With the RS-CAVC air-flow adjustment are
made in the zones. Air Flow adjustments
not damper adjustment you’re in control
not the damper !
Installing a RS-CAVC inside a closed ceiling with a
cable regulator a perfect air adjustment is possible.
TAB is completed without a 2nd change in air
balance in other zones.
The difference is adjusting the air flow not adjusting
the damper.
Make VSD automatically resets and keep the air
flow without further adjustments to CAVC’s.
Once set, the air flow is regulated by pressure
independently a constant flow
Install with metal cable damper adjustors.
Save energy in all applications!
8
CAVC
(Set once or make a readjustment . All others CAVCdo not need readjustment)
Manual cable key
Hard ceiling
You control air flowNot the damper
Fig. Z4
ROYAL SERVICE SUPPLIES
Title 24 Section 120.1
Zone
Mechanical Ventilation of each space (MVS)
Must be capable of providing a rate no less than the
largest air-flow design.
Meeting area with predetermined occupied and
unoccupied space.
The minimum rate shall be supplied to each space
in time of occupancy
(MVS) from the Fresh Air Handler, a constant flow
is controlled into the space the RS-CAVC can
control at no less then design
Demand Control Min and Max flow without
expensive controls
Constant flowCAVC
Min to Max (variable) air flowCAVCDamper
ActuatorDemand control(CAVC with damper)
Maintain no less than design
Title 24 Section 120.1 © Demand control CO2 sensors
Zone
CO2 sensors installed to control demand ventilation
CAVC can change flow. Simple floating actuator
can adjust flow to the required rate.
Connections to CO2 directly in small zones and
linked connections for larger zones
9
Fig. Z5
Electric
Non-electric
CAVCActuator
CNT
Co2 sensors(Min & Max air flow)
occupied sensor or DDC control demand./
Electric
Fig. Z6
CO2
ROYAL SERVICE SUPPLIES
Hotel Title 24 Section 120.2 (f)
Zone
120.2 (f) requires dampers supply and exhaust
must close upon fan shut down.
RS-CAVC-DR with an open / close damper
operates a damper to open and close on demand.
ActuatorDamper CAVC Hotel room
120.2(F)
10
Fig. Z3
ROYAL SERVICE SUPPLIES
ROYAL SERVICE SUPPLIES
1712 New Ave., San Gabriel, Los Angeles County, California 91776, U.S.A.