SEVO Systems offers you and your customers the most SAFE, environmentally sustainable choice in fire suppression, by offering the NEW! Novec™ 1230 Fire Protection Fluid!

SEVO Systems provides choices to meet your needs.  This will give you the ability to utilize your existing installation program or allow you to create new and updated systems.

Our Mission

BackgroundSEVO Systems was developed by

Modular Protection Corporation as the “Safe Environmental Choice” for halon replacement.

Modular Protection Corp. -Established 40 years ago

-Modular pre-engineered units-Long term relationship with 3M-Developed CEA-410

World Wide Distribution

• Asia• Canada• Europe• Middle East• South America• United States

Distribution in over 30 countries

Init ial Testing Novec™ 1230 Fire Protection Fluid

• Finding the Characteristics– Two-Phase Flow

• Liquid to vapor– Extinguishing Concentration– Nozzle Distribution

3M Fire Test Facility, Mendota Heights, MN

Benefits of a Liquid

• Available for Air Shipping• It can be stored on site• Allows for on site refilling• Fills can be increased or decreased to

meet changes in size or room density• Storage pressure can vary to meet

application

Tote Fil l ing

• Remove valve from cylinder

• Fill cylinder with agent to desired weight

• Insert diptube into cylinder

• Charge cylinder through valve outlet to correct nitrogen weight

• Agitate cylinder until pressure gauge indicates 360 psi

On Site Refi l l ing

Transport Liquid, Nonpressurized to site

Required Materials• Nitrogen, Regulator, and

Tape MeasureProcedure• Disconnect• Fill to required amount• Charge with nitrogen

Variable Temperature Ranges

• 0°F - 130°F (-17.78°C – 54.44°C)-North Slope (Prudue Bay)

• Alaska Pipeline -Unmanned Pump Stations

Life Safety• With a NOAEL of 10% and using a design

concentration of 4.2%

67-150% Safety Margin

Naturally occurring compounds

HFCs

PFCs

HFEs

Novec 1230 fluid

Compound GWP (100 Yr ITH)

CO2 1

N2O 296

CH4 23

CF3CH2F (HFC-134a) 1,300

CF3CFHCF3 (HFC-227ea) 3,500

CF3H (HFC-23) 12,000

C2F6 11,900

C3F8, C4F10, C6F14 8,600 - 9,000

SF6 22,200

C4F9OCH3 (HFE-7100) 320

C4F9OC2H5 (HFE-7200) 55

C2F5C(O)CF(CF3)2 1

Environmental Benefits

• Zero Ozone Depletion• Global Warming Potential of 1• Atmospheric Lifetime of 3-5 days

Environmental Need

Phase-out of Ozone Depleting AgentsHalon

-EU (European Union)-Canada-Asia-Australia

Environmental Need

Phase-out of HGWMs (High Global Warming Materials)

HFCs-EU (European Union)

-Austria – Banned by 2008-Denmark - Banned by 2007-Germany – Initial proposal underway-Norway – Enacted tax ($72 USD) per kg-Switzerland – Banned on January 1, 2003

Emissions Trading

Trade in “your” HGWMs/Halon 1301 for 3M™Novec™1230 Fire Protection Fluid To assist in the reduction of greenhouse gases, SEVO® Systems is willing to propose a trade for existing HGWMs (High Global Warming Materials).

-Up to a 50% discount off the cost of Novec™ 1230 fluid, for HGWMs/Halon 1301.

The following agents are available for credit with purchase of Novec 1230 fluid:

Formula Trade Name PFC-3-1-10 CEA-410™ HFC-227ea FM-200® &FE-227™ HFC-236fa FE-36™ HFC-23 FE-13™ HFC-125 FE-25™ CBrF3 Halon 1301

Replacing today and the future With the commercialization of 3M™ Novec™ 1230 Fire Protection Fluid (C6-flouroketone), there is now a reason to phase-out first generation Halon alternatives. SEVO Systems offers a long-term sustainable choice. With the regulatory status of today and tomorrow, Novec 1230 fluid is the Safe Environmental Choice that meets the acceptance worldwide. HFCs have been identified in the Kyoto Protocol as greenhouse gases targeted for emission reduction because of their high global warming potential. Due to the environmental impact of HFCs, countries around the world have already taken action on its use.

Countries that have taken action towards HFCs include: Norw a y – enacted a tax on imports of HFCs/PFCs of 180 NKr per ton (0.18 NKR per kg CO2), for HFC-227ea tax would be 552 NKr ($72 USD) per kg. G e rm a ny – Environment Ministry issued a paper in October 2002 with initial proposals for HFC controls, options include use restrictions or bans.

Replacing today and the future With the commercialization of 3M™ Novec™ 1230 Fire Protection Fluid (C6-flouroketone), there is now a reason to phase-out first generation Halon alternatives. SEVO Systems offers a long-term sustainable choice. With the regulatory status of today and tomorrow, Novec 1230 fluid is the Safe Environmental Choice that meets the acceptance worldwide. HFCs have been identified in the Kyoto Protocol as greenhouse gases targeted for emission reduction because of their high global warming potential. Due to the environmental impact of HFCs, countries around the world have already taken action on its use.

Countries that have taken action towards HFCs include: Norw a y – enacted a tax on imports of HFCs/PFCs of 180 NKr per ton (0.18 NKR per kg CO2), for HFC-227ea tax would be 552 NKr ($72 USD) per kg. G e rm a ny – Environment Ministry issued a paper in October 2002 with initial proposals for HFC controls, options include use restrictions or bans. German industry is generally opposed. A proposal was expected in June, but may be delayed indefinitely. De nm a rk – first comprehensive national law banning HFCs enacted on July 1, most uses banned by 2007. Aus tria – bans HFCs for fire protection in 2003, many uses banned by 2008 with a procedure for review in 2005 to determine whether the phase-out dates are feasible. Sw itze rla nd – HFC extinguishing agents were banned on January 1, 2003.

Along with countries that have begun the phase-out of HGWMs, a number of global companies have begun the phase-out in order to make their company a more sustainable business.

Environmental Properties of Halon 1301 and Alternatives

Properties Halon 1301

HFC- 23

CEA-410

HFC-227ea

HFC-125

Novec 1230

Ozone Depletion Potential (ODP)

12 0 0 0 0 0

Global Warming Potential-IPCC 20011 6900 12000 8,600 3500 3400 1

Atmospheric Lifetime (Years) 65 260 2,600 33 29 0.014

Environmental Properties of Halon 1301 and Alternatives

Properties Halon 1301

HFC- 23

CEA-410

HFC-227ea

HFC-125

Novec 1230

Ozone Depletion Potential (ODP) 12 0 0 0 0 0

Global Warming Potential-IPCC 20011

6900 12000 8,600 3500 3400 1

Atmospheric Lifetime (Years) 65 260 2,600 33 29 0.014

SNAP (Yes/No) No Yes Yes Yes Yes Yes

1Intergovermental Panel on Climate Change Novec 1230 fluid has a Global Warming Potential (GWP) of one, that of CO2, not to mention a 99.97% reduction in greenhouse from HFC-227ea. In addition, Novec 1230 fluid has a safety margin of 67-150%, making it the Clean Agent of Safe Environmental Choice around the World.

Please contact your local SEVO Systems distributor for further details :

SEVO® Systems 14824 West 107th Street Lenexa, KS 66215 USA

Tel 913.677.1112 Fax 913.384.5935

info@sevosystems.com

Approvals

LISTED (Clean Agent Extinguishing System Unit)

7CA2

UL File# EX 6174

LISTED (Clean Agent Extinguishing System Unit)

7CA2

ULC File# CEX 1411www.ul.com

GAQF.EX6174Clean Agent Extinguishing System Units

SEVO ® SYSTEMS INC EX617414824 W 107TH STLENEXA, KS 66215 USA

PRE-ENGINEERED UNITS 3M™ Novec™ 1230 Fire Protection Fluid (dodecafluoro-2-methylpentan-3-one) Extinguishing System Units, stored pressure type, having nominal charging capacities of 40, 76, 164, 322 and 601 lb (18.1, 34.5, 74.4, 146.1 and 272.6 kg) Novec™ 1230 Fluid, respectively. The units are super-pressurized to 25 bar (363 psig) with operating temperatures of 0 F to 130 F. The units are designed for total flooding protection against Class A surface burning, Class B flammable liquid and Class C fires occurring within an enclosure.A description of these extinguishing system units, and the design and installation limitations are contained in the Listee's installation manual dated October 17, 2002 (p/n SE 1230). Copies are available from the above Listee.

GAQF.EX6174Clean Agent Extinguishing System Units

A description of these extinguishing system units, and the design and installation limitations are contained in the Listee's installation manual dated October 17, 2002 (p/n SE 1230). Copies are available from the above Listee.

AGENT STORAGE CONTAINER ASSEMBLY

Weight of Agent ( lbs) Part No.16-40 CV

1449030-76 CV

1425166-164 CV

14817129-322 CV

14325241-601 CV

14813

Approvals in Progress• NFPA 2001 – 2004 Edit ion - Approved• FM approval – (1Q - 2004)

(Pending – Subscriber #301250)• European Notif ied Body

VdS Component (Germany)CNPP Approval (France)

• Austrian Government Approved• NFA approval (Taiwan) Approved

(March 2004)• FRDM (Malaysia) – Approved

(March 2004)• Hong Kong Fire Department

(August 2004)• CCOE (Chief Control ler of Explosives) -

India

Applications Replacing Halon 1301 with 2 nd

Generation

Industry– Telecommunications

• Verizon• Alltel

– Data & Control Rooms• NBC• Coca-Cola

– Marine• Yachts• Offshore

– Mil itary• Austrian• Swedish• US Capital

–Museums•Taipei National Historical Museum

–Petroleum•Alyeska (Alaska Pipeline)•BP (British Petroleum)•Kappa Ethanol•Conoco Phillips

–Pharmaceuticals•Hoffman-LaRoche

–Power Plants•Hydro Quebec•BC Hydro

Engineered & Pre-engineered System

Cylinders D.O.T & T.C. approved / TPED final in 1Q-04

Cylinder Sizes

40

76

164

322

601

975

1240

Allowable Fil l lbs

19-40

34-76

76-164

150-322

280-601

390-975

531-1240

Catalog Numbers

CV-14490

CV- 14251

CV-14817

CV-14325

CV-14813

CV-14975

CV-11240*

* Twin valve engineered only (Pending)

Cylinder ComponentsModels: 40, 76, 164, 322, 601, 975, 1240

• Seven Sizes Filled at Factory in  One lb. Increments • High Flow Rate Valve • Electric Solenoid Operation • Fill Check Valve• Vertical Mounting

• Optional: -Manual Actuation

-Liquid Level Indicator-Pressure Switch – Low Pressure & Operational

Engineered Hydraulic Flow Calculation Software

-25 bar (360 psi)

• Allowing drop-in replacement for existing Halon/HFCs piped installations

-Pressures up to 35 bar (500 psi)

• Optional Variable Storage Pressure

Why SEVO Systems/Novec 1230

Halon drop-in replacement- 2 to 1 agent replacement- 1 to 1 cylinder replacement- Utilize existing pipe network- Variable operating pressure- Save labor & downtime

HFC drop-in replacement- 1 to 1 cylinder replacement due to fill density (75 vs. 70 lbs/ft3)

Why SEVO Systems/Novec 1230?

Life Safety - Unlike other Halon replacing systems/clean agentsNovec 1230 at Design Concentration gives customer 67-150% Safety Margin, due to a NOAEL/LOAEL 10%- Even at inerting concentrations, Novec 1230 allows for a minimum life safety margin

Vs. HFCs- Low NOAEL/LOAEL allowing for a very low to zero margin for life safety

Why SEVO Systems/Novec 1230?

Environmental - Zero Ozone Depletion- Global Warming Potential of 1- Atmospheric Lifetime of 3-5 days - Meet today and future regulations

Vs. HFCs- High Global Warming Potential- Atmospheric Lifetime measured in years- Environmental regulations will force phase-out

Novec 1230 to HalonCylinder Exchange

SEVO Replacement Cylinders (lbs)

2 to 1 Cylinder Change

Existing Halon Cylinders

(lbs)

1240 = 600

975 = 400

601 = 300

322 = 150

164 = 75

76 = 30

40 = 20

Design

Agent Requirements

Agent Class “A” Class“B” Class “C”

Novec™ 1230 4.2 % 5.85% 4.2%Design Concentration

Agent Use Conc. NOAEL* Safety Margin

Novec™ 1230 9-9.9% 10% 1 - 11%

HFC-227ea 12.8% 9% - 41%

HFC-23 20.2% 24% 19%

CO2 30 - 75% <5% lethal @ design conc.

Safety Margin for Flooding Agents - Inerting

Elevation Factors

Feet Kilometers-3000 -0.92 1.11-2000 -0.61 1.07-1000 -0.3 1.040 0 11000 0.3 0.962000 0.61 0.933000 0.92 0.894000 1.21 0.865000 1.52 0.826000 1.83 0.787000 2.13 0.758000 2.44 0.729000 2.74 0.6910000 3.05 0.66

AltitudeCorrection

Example

x 0.0379 (4.2% Class “A”)285 lbs. -Novec™ 1230

25’ x 25’ x 12’ = 7500 ft3

Nozzles

Large Area Coverage Capabil ity.

1, 11/2, and 2 Inch Sizes180° and 360° Discharge Options.

UL Listed Nozzle Coverage

32 ft (9.75 m) X 32 ft (9.75 m)

Nozzle Ceiling Height:14 feet (4.27 meters)

Center Nozzle Radius Throw

Center Nozzle (360°) 22.6 ft (6.9 m)

Sidewall Nozzle Radius Throw

Sidewall Nozzle (180°) 35.8’ (10.9 m)

Multi-Layered

Equivalent Length

Pipe Size (in.)

90 el. (ft.)

Union Cpig.

(ft.)

2 1/2 6.5 1.43 8.2 1.8

A B CCV 14813 20 54 1/2 61 8.02 2 1/2 241-601

FILL RANGE (lbs)

PART NUMBER

DIMENSIONS (in.)CUBIC FT.

VALVE SIZE (in.)

2" 2 1/2" 3"8.02 241-601 32'-8" 28'-6" 68'-5" 2" Qty 2

C B C A-B

REQUIRED NOZZLE

SIZE

CYLIN DER S IZE cu.f t.

FILL RAN GE lbs . Equivalent Pipe Length

Equivalent Pipe Length

Equivalent Pipe Length

14813 – 601 lb Cylinder

Pipe Limits

Table 3.2

1" 1 1/4" 1 1/2" 2" 2 1/2" 3"

0.53 16-40 61'10" - - - - - 1- 1"

1.02 29-76 - 50'9" - - - - 1- 1"

2.19 66-164 1'2" - 41'6" - - - 1- 1 1/2"

4.3 129-322 - - - 52' - - 1- 2"

8.02 241-601 - - - 32'8" 28'6" 68'5" 2- 2"

REQUIRED NOZZLE

S IZE

CYLINDER S IZE cu.ft.

FILL RANGE

lbs.

Equivalent Pipe Length

Pipe Size (in.)

90 el. (ft.)

45 el. (ft.)

Union Cpig.

(ft.)

Union Elbow

(ft.)

Tees (ft.)

1 2.8 1.3 0.6 3.4 n/a1 1/2 4.3 2 0.9 5.2 n/a

2 5.5 2.6 1.2 6.7 8.962 1/2 6.5 3.1 1.4 8 10.32

3 8.2 3.8 1.8 10 12.78

Table 3.3 Reference Page 21 & 22

Control Panel

•  Two Class A or Class B supervised detection zones. Programmable for single zone or cross zone detection. •  One Class A or Class B manual station input programmable. •  One Class A or Class B abort station input. to four different options. •  Two Class B supervised solenoid outputs. •  Supervisory input option. •  Two Class A or Class B alarm outputs. •  Pre-discharge timer. •  Auxiliary relay card option. •  Battery volt / ampmeter option.

Electric Solenoid

12 VDC24 VDC

Manufactured

by ASCO

Compatibil i tyQty Part # Manufacturer Rating

2 21857 12V DC Asco 1/4" NPT 9.11 watts .76 MA Total1 21858 24V DC Asco 1/4" NPT 9.11 watts .38 MA Total

UL Listed For Release

Panel Manual Reference Manufacturer Card / Term Release Circuit RatingRP 1002 Notifier (2) Style Y 1.5 amps / 2.25 totalRP-1002M Modular (2) Style Y 1.5 amps / 2.25 total

Ansul (2) Style Y 1.5 amps / 2.25 totalChemetron (2) Style Y 1.5 amps / 2.25 total

AFP-200 Notifier # 1 - 4 (4) Syle Y 2.25 amps / 5.0 totalS-500 Notifier TC - 2 (2) Style Y 3.0 amps per circuitS-5000 Notifier TCM - 2 (6) Style Y 3.0 amps per circuit

LSS4 EST RMOD (2) Style Y 1 amp totalSHP 8.3 Fike #17 & 18 (2) Style Y .1 - 2.0 ampsCheetah 5.3.2 Fike SRM (2) Style Y 2.1 ampsRhino 48, 43, 9.4.3 Fike DCM D1 output 1-3 2.0 amps

Micro One Chemetronics SOL 1-3 (3) 10 Watts per circuit

Gemini Kidde SCB (2) Style Y 2 amp Fused