Post on 16-Feb-2021
transcript
Solutions For Energy StorageATEPS is based around a number of core tech-nologies that all focus on the preservation and storage of energy.
We have developed unique solutions for peak-shaving, energy storage and fuel saving for CHP’s that can be delivered quickly and starts saving your ener-gy cost energy cost almost instantly.
In many cases these installations can be offered including financing and do not need any capital investments on your side. Therefore these solution are risk-free for any user; risk free both financially and technically since any changes to your exist-ing application can be undone in a matter of minutes should you desire to do so.
Our service devision keeps an eye on all the units and service and optimization can often be done without user interference.
HSB01-UK. Rev. 4
ATEPS
ATEPS Nederland BV Advanced Technologies for Energy & Power Systems
19” Lithium batteryATEPS Netherlands BV has developed a 19” battery with a height of 2U, which can be used in many applications. Due to the universal design of the battery it can easily be integrated into existing installations such as:
• Energy Storage System• Backup in ICT systems• Emergency power supply for telecommu-
nication systems The batteries are interconnected via the back-plane so there are no voltage-carrying parts on the front of the battery, an important safety feature.
For applications where the voltage should be available to the front, this can be achieved by means of a 1U high connection-unit.
Depending on the backplanes used, the bat-teries can be connected in series or parallel or a combination of these whereby a maximum of 16 modules can be inserted in tot rack. Thereby systems with different voltages and capacities can be easily configured.
A 19” BMU is available for integration in the same cabinet that controls all batteries in this rack. The BMU communicates to external devic-es via RS485 or the ATEPS Energy Management System that also controls the converters in ESS applications.
An SD card can be inserted in the BMS to update firmware in the batteries and can be used to log battery data for later analyses of the battery parameters.
Each cell individually fused
19” batteries
Batteries in 19” racks
ESS Application
ESS Project Planning
Important at the outset of any ESS project is a clear understanding of the current opera-tional cost and the cost of ownership. Using advanced analytical tools, a prediction on obtainable cost savings are made that will form the basis for the Return on Investment calcula-tions.
The ESS system can be combined with differ-ent solar installations, wind generators or in combination with fuel cells and the creation of hydrogen.
Depeding on the size of the ESS, installation is done using an exter-nal power-house or as a single or small row of cabinets. Installation is simple and will be han-dled by qualified Ateps engineers in a mater of hours or days.
Service, updates and frequent reporting is part of the system so the ESS application will hardly be noticed other than in your monthly energy bills!
More information:
ATEPS Nederland BVPanovenweg 34 5708 HR HelmondThe Netherlands
Tel: +31 (0)492 - 792707www.ateps.cominfo@ateps.com
ATEPS
Specifications
Type AB5050
Nominal voltage 50V
Capacity 50Ah
Technologies Li-NiMnCoO2
Dimensions 19” x 2U x 550mm
Weight 23kg
BMU External - 4U
Nom. discharge current 50A
Max. discharge current 100A standard - 200A in special cabinet
Nom. Charge current 25A
Max. Charge current 50A standard - 100A in special cabinet
Integrated sensors 14 x Voltage, Current, 7 x Temperature
Communication RS485 with secure protocol
Temp. range in use 0°C to +45°C
Temp. range storage -10°C to +55°C
System Vmax 1050V (42U cabinet, batteries connected in series)
System Ah max. 1050Ah (42U cabinet, batteries connected in parallel)
Diagnostics 3-color LED
Service USB Cell voltage, temperatures, current
SafetyPacks designed for 1500V and in accordance
with, UN 3480, UN 38.3 and UL2054
BMSSmart BMS with automatic battery ID distribution
and communication to EMS