Synchrophasors and the Smarter Grid - IEEE PES Boston · Apply Synchrophasors Now Disturbance...

Post on 27-Mar-2020

12 views 0 download

transcript

Copyright © SEL 2011

Synchrophasors and the Smarter GridSynchrophasors and the Smarter Grid

Copyright © SEL 2011

A synchrophasor is a phasor measurement with respect to an absolute time reference. With this

measurement we can determine the absolute phase relationship between phase quantities at different

locations on the power system.

““SynchrophasorSynchrophasor””

Copyright © SEL 2011

Absolute Time Synchronization Has Absolute Time Synchronization Has

Fundamentally Changed the WorldFundamentally Changed the World

GPS RCVR

PMU 1

A B

Satellite

GPS RCVR

PMU 2

IRIG-B IRIG-B

Mag/Ang Mag/Ang

Copyright © SEL 2011

ωt

φφ

Time WaveformTime Waveform

and Phasor Representationand Phasor Representation

Reference

A

2

Copyright © SEL 2011

A Timing Mark on a Generator ShaftA Timing Mark on a Generator Shaft

Copyright © SEL 2011

Synchrophasors Provide a Synchrophasors Provide a ““SnapshotSnapshot””

of the Power Systemof the Power System

P= |V1| |V2|sinФ / X Ф= sin-1(PX / |V1| |V2|)

V1∠0 V2 ∠ФP→

Increase Stable Power Transfer

Copyright © SEL 2011

Synchrophasor System ComponentsSynchrophasor System Components

System Components

● Clocks

● PMUs

● PDCs

● Visualization

● Secure communications

Copyright © SEL 2011

ISO

Neighbor Utility Control Center

Visualization SELVisualization SEL--50785078

Utility Control Center

GPS ClockGPS Clock

Security GatewaySecurity Gateway

Station PDCStation PDC

System PDCSystem PDC

PDCPDC

Super PDCSuper PDC

PMUPMUPMUPMU

Other Substations

SystemSystem

ArchitectureArchitecture

Copyright © SEL 2011

Timing Accuracy RequirementsTiming Accuracy Requirements

● Synchrophasors require ±500 ns

● Modern Clocks provides ±100 ns

● GPS synchronized clocks typically used

Copyright © SEL 2011

Synchrophasor System ComponentsSynchrophasor System Components

System Components

● Clocks

● PMUs

● PDCs

● Visualization

● Secure communications

Copyright © SEL 2011

Phasor Measurement Units (PMUs)Phasor Measurement Units (PMUs)

Synchronized Phasor Measurement Synchronized Phasor Measurement

and Distance Protectionand Distance Protection

Copyright © SEL 2011

Enabling PMU Capability in the RelayEnabling PMU Capability in the Relay

SCADA

Disturbance RecordHigh-Speed Control

Just Say Yes!

Copyright © SEL 2011

C37.118 Signal Processing FilterC37.118 Signal Processing Filter

Selecting the Frequency ResponseSelecting the Frequency Response

Copyright © SEL 2011

Synchrophasor System ComponentsSynchrophasor System Components

System Components

● Clocks

● PMUs

● PDCs

● Visualization

● Secure communications

Copyright © SEL 2011

Data Concentration & ArchivingData Concentration & Archiving

● Time Alignment and Superpacket Creation

● Protocol Conversion

● Data Parsing

● Data Rate Change

● Archive Maximum Data Locally

Copyright © SEL 2011

PDC ArchitecturePDC Architecture

Copyright © SEL 2011

Synchrophasor System ComponentsSynchrophasor System Components

System Components

● Clocks

● PMUs

● PDCs

● Visualization

● Secure communications

Copyright © SEL 2011

Bus Voltage

Line MVA

Frequency

Instantaneous Phase Angles

Trended Phase Angles

PMU ID

Visualizing SynchrophasorsVisualizing Synchrophasors

Copyright © SEL 2011

Synchrophasor System ComponentsSynchrophasor System Components

System Components

● Clocks

● PMUs

● PDCs

● Visualization

● Secure communications

Copyright © SEL 2011

ISO

Neighbor Utility Control Center

Visualization SELVisualization SEL--50785078

Utility Control Center

GPS ClockGPS Clock

Security GatewaySecurity Gateway

Station PDCStation PDC

System PDCSystem PDC

PDCPDC

Super PDCSuper PDC

PMUPMUPMUPMU

Other Substations

SystemSystem

ArchitectureArchitecture

Copyright © SEL 2011

Substation Security

Information SecurityInformation SecurityEndEnd--toto--End SecurityEnd Security

Copyright © SEL 2011

Securing the InformationSecuring the Information

● Establish an electronic security perimeter• Use multilayered system architecture that

includes a firewall• Encrypt communications in/out of

substation• Disable unused ports on all devices• Send C37.118 data using UDP Secure

(UDP_S)

Multi-layered Secure Architecture

Copyright © SEL 2011

SCADA Speed Sufficient for Many SCADA Speed Sufficient for Many

Special Protection SchemesSpecial Protection Schemes

System operators

need data before things start

to happen

Copyright © SEL 2011

Sometimes the Need for Speed Is Not ObviousSometimes the Need for Speed Is Not Obvious

64 Minutes

Copyright © SEL 2011

It Can Fall Apart in Three MinutesIt Can Fall Apart in Three Minutes

64 Minutes

Copyright © SEL 2011

Synchrophasors Are a Flexible ToolSynchrophasors Are a Flexible Tool

● State measurement● Disturbance recording

● Modal analysis● Dynamic response

measurement

and…

High-Speed Protection and Control

Copyright © SEL 2011

Synchrophasor ApplicationsSynchrophasor Applications

Copyright © SEL 2011

Synchrophasors Provide a Synchrophasors Provide a ““SnapshotSnapshot””

of the Power Systemof the Power System

P= |V1| |V2|sinФ / X Ф= sin-1(PX / |V1| |V2|)

V1∠0 V2 ∠ФP→

Increase Stable Power Transfer

Copyright © SEL 2011

Streaming Data Better than SCADAStreaming Data Better than SCADA

-- Imagine Driving in 5 Second BlinksImagine Driving in 5 Second Blinks

Copyright © SEL 2011

Synchrophasor Data is Critical

Copyright © SEL 2011Courtesy of Entergy Corp.Courtesy of Entergy Corp.

Copyright © SEL 2011Courtesy of Entergy Corp.Courtesy of Entergy Corp.

Copyright © SEL 2011

Synchrophasors Detect IslandSynchrophasors Detect Island

Courtesy of Entergy Corp.Courtesy of Entergy Corp.

Copyright © SEL 2011

Florida Power & Light: Distributed Florida Power & Light: Distributed

Generation AntiGeneration Anti--IslandingIslanding

Angle

Freqdf/dt

Voltage

Copyright © SEL 2011

SEGIS AntiSEGIS Anti--Islanding DemoIslanding Demo

● Advanced Energy led● ODOT solar project: 100 kW installation

● Stage 3 demo planned for August ‘11

Copyright © SEL 2011

SEGIS Field Testing Results SEGIS Field Testing Results

● Island event � Longest trip 1.1 seconds

● Utility functions � Curtailment � Ramp rate

� Power factor

Copyright © SEL 2011

Archiving SystemArchiving System

SEL-3306

••Disturbance RecordingDisturbance Recording

••Event Capture and Event Capture and

AnalysisAnalysis

Copyright © SEL 2011

Utilities Are Operating Closer to the EdgeUtilities Are Operating Closer to the Edge

MarginMargin

1.0 1.3 1.5 1.7PU Nominal Load

1.0

0.5

0.0

Operating

Point

BifurcationPoint

Copyright © SEL 2011

EskomEskom’’s Voltage Stability Assessment s Voltage Stability Assessment

SystemSystem

Copyright © SEL 2011

UT Pan Am

Austin

McDonald

Observatory

Austin 120V and

Harris 69kV

Waco

Houston (SEL)

Boerne (SEL)

Brazos Electric

PMU

Austin Energy

PMU

• Funding provided by

EPRI

Wind

country

Concentrated distant load

Blue outlines: Central ERCOT

2

The Texas Synchrophasor Network

Bus 7

WIND

Bus 7

WIND500 km

Local conventional

Pload,conv − Pgen,conv

Pexport

Thevenin Impedance

jXTH

Central ERCOT

Vangle = 0

Vangle = δ

Use the Excel Solver with angle measurements to minimize least-squared error

and obtain Xth

Estimate Thevenin Equivalent Impedances Across

the Grid with Synchrophasors

80 1 2 3 4 5 6 7 8 9 10 11 12

)sin(21 δ•≈TH

X

VVP

Copyright © SEL 2011

2 Hz

Cluster

March 18, 02:00 – 03:00

Wind Generation > 20%

March 12, 02:00 – 03:00

Wind Generation ≈ 2%

Big Wind (20%) with 2 Hz ClusterSmall Wind (2%) without 2 Hz Cluster

A 2 Hz Mode in Ambient Oscillation Forms with

High Wind Generation

9

1 hour

Copyright © SEL 2011

Only Synchrophasors Only Synchrophasors

Provide Angle Provide Angle

DifferenceDifference

FrequencyFrequency

AngleAngle

DifferenceDifference

Charts provided by University of Texas

Copyright © SEL 2011

46 46

Integration of Renewable EnergyIntegration of Renewable Energy

● With over 28GW of wind power in the SPP interconnection queue, this is a big deal!

● OG&E requiring a PMU at the point of interconnection for every wind farm

● Important to monitor power quality and dynamic response

47

Oscillations Due to Wind FarmOscillations Due to Wind Farm

� Wind farm PMU shows many undesirable components, the worst at 14Hz

Copyright © SEL 2011

Big Creek Controls Rector Big Creek Controls Rector

Static VAR CompensatorStatic VAR Compensator

Copyright © SEL 2011

C37.118 to SCADA based FACTS ControlC37.118 to SCADA based FACTS Control

SCADAMaster

DNP3

IEEE C37.118

Information

Processor

Copyright © SEL 2011

SRP SRP –– SynchroWAVe SynchroscopeSynchroWAVe Synchroscope

115 kV

Bus

230 kV

Bus

13.8 kV Bus

SEL-421

SEL-421

Copyright © SEL 2011

SRP Operator Closes Tie Based

on Synchrophasors, 2004

Copyright © SEL 2011

RelayRelay--toto--Relay Relay

Synchrophasors for Synchrophasors for

Generator SheddingGenerator Shedding

Copyright © SEL 2011

Generator Shedding Based on AngleGenerator Shedding Based on AngleChicoasen Chicoasen –– AngosturaAngostura

Copyright © SEL 2011

WideWide--Area Protection at Relay SpeedsArea Protection at Relay Speeds

Copyright © SEL 2011

Modal AnalysisModal Analysis

Shows System ResponseShows System Response

1996 Event

Copyright © SEL 2011

Slow Oscillations Facilitate ControlSlow Oscillations Facilitate Control

P= |V1| |V2|sinФ / X

RaiseVoltage

Reduce

Voltage

0.4 Hz → 2.5 sec.

Copyright © SEL 2011

A New Tool for Old ProblemsA New Tool for Old ProblemsSynchrophasorsSynchrophasors

● Are cost effective● Provide accurate time-synchronized

event information● Can be used to meet NERC PRC-002-2

requirements

● Are being used for new approaches in protection and control

Apply Synchrophasors NowApply Synchrophasors Now

� Disturbance recording

� Relay-to-relay control

� Modal analysis

� Special protection schemes

� System control

Copyright © SEL 2011

DonDon’’t Imagine It t Imagine It –– Engineer ItEngineer It

What Can You Do With What Can You Do With

Synchrophasors?Synchrophasors?

Copyright © SEL 2011

URLs for More Application InformationURLs for More Application InformationSEL website:

● Eskom Voltage Stabilty

https://www.selinc.com/WorkArea/DownloadAsset.aspx?id=6378

● Solar Generator Control – PV Powered https://www.selinc.com/WorkArea/DownloadAsset.aspx?id=8494

● Generator Black-start – SRP

https://www.selinc.com/WorkArea/DownloadAsset.aspx?id=3194

● Anti-islanding at FPL https://www.selinc.com/WorkArea/DownloadAsset.aspx?id=6375

● UT Texas with Dr. Mack Grady

https://www.selinc.com/WorkArea/DownloadAsset.aspx?id=7264

● SCE Static VAR Control https://www.selinc.com/WorkArea/DownloadAsset.aspx?id=3487

● Using Modal Analysis to Mitigate Power System Oscillations

https://www.selinc.com/WorkArea/DownloadAsset.aspx?id=5322

Another useful website - North American SynchroPhasor Initiative (NASPI) website: http://www.naspi.org/

● OGE presentation , Entergy presentation and many others