To Whom It May Concern, Achilles performed water sterilization at O.V.H. Physical Therapy 1521 N. Tangerine Rd Oro Valley Az. All new water piping was isolated and injected with chlorine at a rate of 50 ppm. We then purged all water outlets until full of chlorinated water and left to stand for 24 hours. All water was then purged until chlorine was no longer present. At that time a sample was provided to Turner Labs for testing. Any questions or concerns please contact Jake Leonard Plumbing Department Manager 520-358-8217
May 14, 2020
Jake Leonard
Achilles Air Conditioning
1490 S. Cherrybell Stravenue
Tucson, AZ 85713
TEL (520) 882-4518
FAX
RE: Drinking Water
Dear Jake Leonard,
Turner Laboratories, Inc. received 1 sample(s) on 05/13/2020 for the analyses presented in the
following report.
All results are intended to be considered in their entirety, and Turner Laboratories, Inc. is not
responsible for use of less than the complete report. Results apply only to the samples analyzed.
Samples will be disposed of 30 days after issue of our report unless special arrangements are
made.
The pages that follow may contain sensitive, privileged or confidential information intended
solely for the addressee named above. If you receive this message and are not the agent or
employee of the addressee, this communication has been sent in error. Please do not disseminate
or copy any of the attached and notify the sender immediately by telephone. Please also return the
attached sheet(s) to the sender by mail.
Please call if you have any questions.
Respectfully submitted,
Turner Laboratories, Inc.
ADHS License AZ0066
Kevin Brim
Project Manager
Work Order No.: 20E0303
Order Name: O.V.H. G.I.
2445 NORTH COYOTE DRIVE n SUITE #104 n TUCSON, ARIZONA 85745 n 520 882-5880 n FAX# 520 882-9788
Page 1 of 5
Lab Sample ID Client Sample ID Collection Date/Time
Project:
Turner Laboratories, Inc.
Client:
Work Order:Work Order Sample SummaryDate Received:
Date: 05/14/2020
Matrix
Order: O.V.H. G.I.Achilles Air Conditioning
Drinking Water
20E0303
05/13/2020
20E0303-01 1521 N. Tangerine Drinking Water 05/13/2020 0800
Page 2 of 5
Project:
Turner Laboratories, Inc.
Client:
Work Order:Case NarrativeDate Received:
Date: 05/14/2020
20E0303
Achilles Air Conditioning
Drinking Water
05/13/2020
Not Detected at or above the PQLND
Practical Quantitation LimitPQL
DF Dilution Factor
All soil, sludge, and solid matrix determinations are reported on a wet weight basis unless otherwise noted.
Page 3 of 5
Client Sample ID: 1521 N. Tangerine
Result Units DF Analysis DatePQLAnalyses
Collection Date/Time:
Matrix:
Qual
Turner Laboratories, Inc.
Achilles Air Conditioning
Drinking Water
20E0303
20E0303-01Lab Sample ID:
Work Order:
Project:
Client:
05/13/2020 0800
Analyst
Date: 05/14/2020
Drinking Water
Prep Date
Order Name: O.V.H. G.I.
Coliform by Colilert-SM9223B
CWB05/14/2020 1546E.Coli Absent 05/13/2020 1545
CWB05/14/2020 1546Total Coliform Absent 05/13/2020 1545
Page 4 of 5
Page 5 of 5
SECTION 610
DISINFECTION OF POTABLE WATER SYSTEM
610.1 General. New potable water systems shall be purged of deleterious matter and disinfected prior to utilization. The method to be followed shall be that prescribed by the health authority or water purveyor having jurisdiction or, in the absence of a prescribed method, the procedure described in either AWWA C651 or AWWA C652, or as described in this section. This requirement shall apply to “on-site” or “in-plant” fabrication of a system or to a modular portion of a system.
1. The pipe system shall be flushed with clean, potable water until dirty water does not appear at the points of outlet. 2. The system or part thereof shall be filled with a water/chlorine solution containing not less than 50 parts per million (50 mg/L) of chlorine, and the system or part thereof shall be valved off and allowed to stand for 24 hours; or the system or part thereof shall be filled with a water/chlorine solution containing not less than 200 parts per million (200 mg/L) of chlorine and allowed to stand for 3 hours. 3. Following the required standing time, the system shall be flushed with clean potable water until the chlorine is purged from the system. 4. The procedure shall be repeated where shown by a bacteriological examination that contamination remains present in the system.