Date post: | 07-Sep-2015 |
Category: |
Documents |
Upload: | thusiyanthan-ponnampalam |
View: | 182 times |
Download: | 34 times |
EUROCODE 7 AND ITS IMPACT ON EXISTING DESIGN AND TESTING OF PILESBCA-GeoSS EC7 Seminar24 April 2015
Dr Darren Chian Siau ChenNational University of Singapore
1
ObjectivesWorries of a Geotechnical Engineer in Singapore How do I design according to EC7? How do I know if I have designed correctly? How can I take advantage of EC7 to my favour?
IntroductionChange in Design Approach Working state design:
Analyse expected working condition, then apply factor of safety
Limit state design Analyse various unexpected conditions, where loadings
are increase and resistances are reduced using partial factors.
3
4Prior to Eurocode 7 =
+
Working Load Fwl
Permanent + Variation Loads
Fd = G Gk + Q QkEurocode 7
Rs
, = + &, = / + /
, ,, ,
Rb
Rs
Rb
Site Investigation for Piles Recommended minimum depth of
investigation below the base of the deepest pile, za, as shown in figure on right:
where bg is the smaller width of the pile group on plan and DF is the base diameter of the largest pile.
The depth za may be reduced to 2m if the foundation is built on competent strata with distinct (i.e. known) geology. With indistinct geology, at least one borehole should go to at least 5m. If bedrock is encountered, it becomes the reference level for za.
Greater depths of investigation may be needed for very large or highly complex projects or where unfavourable geological conditions are encountered.
5
6Eurocode 7 Geotechnical Framework
Design Methods/ConsiderationsDesign of piles shall be based on either: Empirical or analytical calculations Static load tests/dynamic load tests Ground tests
7
Design of Piles in CompressionPile Groups: Bearing resistance failure of the piles failing individually
and acting as a block shall both be checked. Generally a pile block can be analysed as a single large
diameter pile. The lower of these two to be taken as the design bearing
resistance (Rd).
8
General Procedure to Design for EC79
Calculate design action
Compute resistance from soil parameters
Derive resistance from load test / ground test
Convert resistance to characteristic values using model factor or correlation factors
Compute characteristic shaft and base resistance
Determine required penetration depth of pile where total characteristic resistance design action
General Procedure to Design for EC710
Calculate design action
Compute resistance from soil parameters
Derive resistance from load test / ground test
Convert resistance to characteristic values using model factor or correlation factors
Compute characteristic shaft and base resistance
Determine required penetration depth of pile where total characteristic resistance design action
Permanent actions, Gk Fixed, doesnt change much.
Variable actions, Qk Change at different times.
Favourable Action that will make fdn less susceptible to ULS condition.
Unfavourable Action that will make fdn more susceptible to ULS condition
Design values of actions, FdFd = G Gk + Q Qk
where G and Q are partial factor
11
ULS Design Value of Actions
12
Action Partial Factors
Action SymbolSet
A1 A2
PermanentUnfavourable
G1.35 1.0
Favourable 1.0 1.0
VariableUnfavourable
Q1.5 1.3
Favourable 0 0
Which Sets to Use? Two combinations to be checked:
Combination 1: Increase loading Combination 2: Reducing resistance
In Combination 2, set M1 is used for calculating resistances of piles or anchors and set M2 for calculating unfavourable actions on piles owing e.g. to negative skin friction or transverse loading.
13
Combination 1:A1 + M1 + R1
Combination 2:A2 + (M1 or M2) + R4
where + implies: to be combined with.
Design of Piles in CompressionDesign Axial Compression Load (Vd): Determined, using the load partial factors for Combination
1 and 2, from the characteristic applied loads and the self weight of the pile and includes any downdrag, heave or transverse loading on the pile, as appropriate.
Common practice to assume that the weight of the pile cancels the weight of the overburden at the foundation base. This is permitted by EC7, provided the two cancel approximately.
The implication of this is to reduce the effect of the pile weight in the design or omitting the weight of pile completely.
14
Design of Piles in CompressionPile weight may not cancel the weight of the overburden if: downdrag is significant (as it reduces the effective stress
at the base of a pile); the soil is light, such as a pile through peat; or the pile extends above the surface of the ground.
15
16
Example:Action from superstructure: - Permanent unfavourable action = 1000 kN- Variable unfavourable action = 500 kNSelf-weight of pile = 200 kN
Total permanent unfavourable action = 1000 + 200 = 1200 kN
Total variable unfavourable load = 500 kN
Set A1:Design Action, Vd = 1.35Gk + 1.5Qk
= 1.35 (1200) + 1.5 (500) = 2370 kN
Set A2:Design Action, Vd = 1.0Gk + 1.3Qk
= 1.0 (1200) + 1.3 (500) = 1850 kN
General Procedure to Design for EC717
Calculate design action
Compute resistance from soil parameters
Derive resistance from load test / ground test
Convert resistance to characteristic values using model factor or correlation factors
Compute characteristic shaft and base resistance
Determine required penetration depth of pile where total characteristic resistance design action
General Procedure to Design for EC718
Calculate design action
Compute resistance from soil parameters
Derive resistance from load test / ground test
Convert resistance to characteristic values using model factor or correlation factors
Compute characteristic shaft and base resistance
Determine required penetration depth of pile where total characteristic resistance design action
19
Characteristic Values of Ground Properties A cautious estimate of the value affecting the occurrence
of the limit state
Orr and Farrell, 1999
20
Characteristic Value (Xk) Statistical methods:
Students method (author is actually Gossett)
where t = Student valuen = no. of test resultsV = coefficient of variation [std deviation() / mean value(Xm)]
21
Characteristic Value (Xk) Statistical methods:
Schneiders method
where kn = factor (=0.5 for one half a std deviation below mean)
22
Characteristic Value (Xk)Example: The characteristic value of the undrained shear strength, cu
is to be determined from 10 triaxial tests: 20 kPa, 25 kPa, 23 kPa, 27 kPa, 35 kPa, 15 kPa, 18 kPa, 32 kPa, 25 kPaand 26 kPa.
23
Characteristic Value (Xk)Students method:
cu,ave = 24.6 kPa, = 6.059 kPa, V = 0.246
t with 10 test results, 95% confidence = 2.228
cuk = 24.6 - 6.059 x 2.228 / sqrt(10) = 24.1 kPa
Scheniders method:
cuk = 24.6 - 0.5 x 6.059 = 21.6 kPa
24
Characteristic Value (Xk)Say, lets take
cu = 1.0 (Set M1) cu = 1.4 (Set M2)
Therefore,
For M1: cu,d = 21.6 / 1.0 = 21.6 kPa
For M2: cu,d = 21.6 / 1.4 = 15.4 kPa
Characteristic Value (Xk)25
Characteristic Value (Xk)26
Characteristic Value (Xk)27
Compute Resistance from Soil ParametersShaft Resistance Per Unit Area: Undrained: qs,cal = cuk Drained: qs,cal = Ks 'v0 tan = 'v0
Base Resistance Per Unit Area: Undrained: qb,cal = Nc cuk , where Nc = 9 Drained: qb,cal = q Nq
28
Note: qb 10 MPa (bored pile)
18 MPa (driven pile)
General Procedure to Design for EC729
Calculate design action
Compute resistance from soil parameters
Derive resistance from load test / ground test
Convert resistance to characteristic values using model factor or correlation factors
Compute characteristic shaft and base resistance
Determine required penetration depth of pile where total characteristic resistance design action
Derive Resistance from TestsPile Load Test: Select pile type, design load tests, carry out load tests
Determine the measured pile resistance, Rcmfrom the load tests
Ground Tests: Select pile type, design load tests, carry out insitutests (e.g. CPT, SPT, etc)
Determine the pile shaft and base resistances, Rsand Rb from correlations
30
General Procedure to Design for EC731
Calculate design action
Compute resistance from soil parameters
Derive resistance from load test / ground test
Convert resistance to characteristic values using model factor or correlation factors
Compute characteristic shaft and base resistance
Determine required penetration depth of pile where total characteristic resistance design action
Convert Resistance to Characteristic ValueModel Factor: Obtain characteristic base resistance per unit area, qbk
and shaft resistance per unit area, qsk by dividing the calculated values by a model factor (MF):
qbk = qb,cal/MF and qsk = qs,cal/MFwhere:MF = 1.4 (without pile load test), or
= 1.2 (with pile load test)
32
Convert Resistance to Characteristic ValueCorrelation Factor:Pile Load Test Obtain characteristic resistance, Rcm by dividing the
measured values by correlation factors ():Rck = min(Rcm,mean/1, Rcm,min/2)
Ground Test Obtain characteristic base resistance per unit area, qbk
and shaft resistance per unit area, qsk by dividing the derived values by correlation factors ():
qbk = min(qb,mean/3, qb,min/4)qsk = min(qs,mean/3, qs,min/4)
33
Convert Resistance to Characteristic Value The factor used to determine Rck from the Rcm values,
accounts for the uncertainty in determining bearing resistance for the working piles from the results of a limited number of load tests on similar piles installed in similar ground at a finite number of locations on the site.
The uncertainty depends on the number of test results available, so reduces as the number of test results increases.
Rck is the minimum value obtained applying the values to the mean and average of the load test results.
Ultimate load test and working load test generally 2.5 to 3 times and 1.5 to 2 times working load respectively, subject to structural capacity of the pile not being exceeded.
34
Convert Resistance to Characteristic Value35
Number of pile load tests 1 2 3 4 5Factor 1 on mean Rcm 1.55 1.47 1.42 1.38 1.35Factor 2 on lowest Rcm 1.55 1.35 1.23 1.15 1.08
Static Pile Load Test
Number of tested piles 2 5 10 15 20Factor 5 on mean Rcm 1.94
(1.65)1.85 (1.57)
1.83 (1.56)
1.82 (1.55)
1.81 (1.54)
Factor 6 on lowest Rcm 1.90 (1.62)
1.76 (1.50)
1.70 (1.45)
1.67 (1.42)
1.66 (1.41)
Dynamic Impact Test
Note: For structures having sufficient stiffness and strength to transfer loads from
weak to strong piles, the above factors may be divided by 1.1.
Note: Bracket values are values when using dynamic impact tests with signal
matching. Other notes available in NA to SS EN 1997-1:2010.
Convert Resistance to Characteristic Value
36
Number of profiles of tests 1 2 3 4 5 7 10Factor 3 on mean value 1.55 1.47 1.42 1.38 1.36 1.33 1.30Factor 4 on lowest value 1.55 1.39 1.33 1.29 1.26 1.20 1.15
Ground Test
Note: For structures having sufficient stiffness and strength to transfer loads from
weak to strong piles, the above factors may be divided by 1.1.
General Procedure to Design for EC737
Calculate design action
Compute resistance from soil parameters
Derive resistance from load test / ground test
Convert resistance to characteristic values using model factor or correlation factors
Compute characteristic shaft and base resistance
Determine required penetration depth of pile where total characteristic resistance design action
Compute Characteristic Resistances For pile load test, separate Rck into base and shaft
components, Rbk and Rsk, where possible.
Calculate the characteristic shaft and base resistances from:
Rbk = Ab qbk and Rsk = qsk Aswhere:Ab = the nominal plan area of the base of the pileAs = the nominal surface area of the pile
Obtain the design resistances for each resistance set:Set R1: Rd = Rbk + Rsk or Rd = RckSet R4: Rd = Rbk/b + Rsk/s or Rd = Rck/t
38
39
Resistance Partial Factors
Resistance Symbol
Set
R1
R4 without explicit
verification of SLS
R4 with explicit
verification of SLS
Base b 1.0 1.7 1.5Shaft (compression) s 1.0 1.5 1.3Total/combined (compression) t 1.0 1.7 1.5
Shaft in tension s,t 1.0 2.0 1.7
Driven Piles
40
Resistance Partial Factors
Resistance Symbol
Set
R1
R4 without explicit
verification of SLS
R4 with explicit
verification of SLS
Base b 1.0 2.0 1.7Shaft (compression) s 1.0 1.6 1.4Total/combined (compression) t 1.0 2.0 1.7
Shaft in tension s,t 1.0 2.0 1.7
Bored Piles
41
Resistance Partial Factors
Resistance Symbol
Set
R1
R4 without explicit
verification of SLS
R4 with explicit
verification of SLS
Base b 1.0 2.0 1.7Shaft (compression) s 1.0 1.6 1.4Total/combined (compression) t 1.0 2.0 1.7
Shaft in tension s,t 1.0 2.0 1.7
Continuous Flight Auger (CFA) Piles
Design Methods/ConsiderationsR4 with or without explicit verification of SLS? If serviceability is verified by load tests carried out on
more than 1% of the constructed piles to loads not less than 1.5 times the representative load or if settlement at serviceability limit state is of no concern.
Resistance is verified by a maintained load test taken to the calculated, unfactored ultimate resistance. Use the lower factors from R4 with explicit verification of
SLS.
42
General Procedure to Design for EC743
Calculate design action
Compute resistance from soil parameters
Derive resistance from load test / ground test
Convert resistance to characteristic values using model factor or correlation factors
Compute characteristic shaft and base resistance
Determine required penetration depth of pile where total characteristic resistance design action
Example 1: Compression
1. Calculate design action: Assume: ignore self weight of pile
Set A1: G = 1.35, Q = 1.5 Design action = 1.35x1000+1.5x300
= 1800kN
Set A2: G = 1.0, Q = 1.3 Design action = 1.0x1000+1.3x300
= 1390kN
44
0m
4m
Sandk = 32k = 19kN/m3
Gk = 1000kNQk = 300 kN
ClayShaft: cuk = 80kPaBase: cuk = 100kPa
Pile base level?
0.6m diameter bored pile
Example 1
2. Compute resistance: Assume: Pile load test carried out
with verification of SLS
Apply model factor, MF=1.2. Set R1: s = 1.0, b = 1.0
For sand layer,Design shaft resistance, Rs,d1= [K
tan x As,1] / MF / s
= [0.7tan x (DL1)] / 1.2 / 1.0
= [0.7x(18x4/2)x(tan32)x(x0.6x4)] / 1.2= 98.94kN
45
0m
4m
Sandk = 32k = 19kN/m3
Gk = 1000kNQk = 300 kN
ClayShaft: cuk = 80kPaBase: cuk = 100kPa
Pile base level?
0.6m diameter bored pile
Example 12. Compute resistance: For clay layer,
Design shaft resistance, Rs,d2= [ cu x As,2] / MF / s= [0.49x80x(x0.6xL2)] / 1.2 / 1.0= 61.58 L2 kN
Design base resistance, Rb,d= [9 cu x Ab] / MF / b= [9x100x(x0.62/4)] / 1.2 / 1.0= 212.06 kN
Set R1: Total resistance= 98.94 + 61.58 L2 + 212.06= 311 + 61.58 L2 kN
46
0m
4m
Sandk = 32k = 18kN/m3
Gk = 1000kNQk = 300 kN
ClayShaft: cuk = 80kPaBase: cuk = 100kPa
Pile base level?
0.6m diameter bored pile
Example 1
2. Compute resistance: Assume: Pile load test carried out
with verification of SLS
Apply model factor, MF=1.2. Set R4: s = 1.4, b = 1.7
For sand layer,Design shaft resistance, Rs,d1= [K
tan x As,1] / MF / s
= [0.7tan x (DL1)] / 1.2 / 1.4
= [0.7x(18x4/2)x(tan32)x(x0.6x4)] / 1.68= 70.67kN
47
0m
4m
Sandk = 32k = 19kN/m3
Gk = 1000kNQk = 300 kN
ClayShaft: cuk = 80kPaBase: cuk = 100kPa
Pile base level?
0.6m diameter bored pile
Example 12. Compute resistance: For clay layer,
Design shaft resistance, Rs,d2= [ cu x As,2] / MF / s= [0.49x80x(x0.6xL2)] / 1.2 / 1.4= 43.99 L2 kN
Design base resistance, Rb,d= [9 cu x Ab] / MF / b= [9x100x(x0.62/4)] / 1.2 / 1.7= 124.74 kN
Set R4: Total resistance= 70.67 + 43.99 L2 + 124.74= 195.41 + 43.99 L2 kN
48
0m
4m
Sandk = 32k = 18kN/m3
Gk = 1000kNQk = 300 kN
ClayShaft: cuk = 80kPaBase: cuk = 100kPa
Pile base level?
0.6m diameter bored pile
Example 1
3. Determine penetration depth:
Set A1 vs Set R1:1800kN = 311 + 61.58 L2 kN1800 311 = 61.58 L2L2 = 24.18m
Set A2 vs Set R4:1390kN = 195.41 + 43.99 L2 kN1390 195.41 = 43.99 L2L2 = 27.16m
Hence, total penetration depth = 27.16 + 4 = 31.16m
49
0m
4m
Sandk = 32k = 19kN/m3
Gk = 1000kNQk = 300 kN
ClayShaft: cuk = 80kPaBase: cuk = 100kPa
Pile base level?
0.6m diameter bored pile
Which Sets to Use? Two combinations to be checked:
Combination 1: Increase loading Combination 2: Reducing resistance
In Combination 2, set M1 is used for calculating resistances of piles or anchors and set M2 for calculating unfavourable actions on piles owing e.g. to negative skin friction or transverse loading.
50
Combination 1:A1 + M1 + R1
Combination 2:A2 + (M1 or M2) + R4
where + implies: to be combined with.
Which Sets to Use? Two combinations to be checked:
Combination 1: Increase loading Combination 2: Reducing resistance
In Combination 2, set M1 is used for calculating resistances of piles or anchors and set M2 for calculating unfavourable actions on piles owing e.g. to negative skin friction or transverse loading.
51
Combination 1:A1 + M1 + R1
Combination 2:A2 + (M1 or M2) + R4
where + implies: to be combined with. Question:
Wouldnt the use of M2 in Combination 2 reduce the negative skin friction? Unconservative approach??
52
Material Partial Factors
Soil Parameter SymbolSet
M1 M2
Angle of shearing resistance1 ' 1.0 1.25
Effective cohesion c' 1.0 1.25
Undrained shear strength cu 1.0 1.4
Unconfined strength qu 1.0 1.4
1 Factor is applied to tan '
Example 2: Downdrag
53
Soft claycuk = 20 kPa
Stiff claycuk = 50 kPa
Cuk.neg = 20 kPa
Gk = 300 kN
Simpson and Driscoll, 1998
Surcharge placed at ground level which is sufficient to mobilise limiting negative skin friction between the pile and the soft clay.
Characteristic applied load, = V#= 300kN.
Characteristic downdrag force, = D#=DL*q,-= 0.3 5 20
= 94.2 kN.
Characteristic shaft resistance, = R#= 0.3 50 L2= 47.1L2 kN.
54
Example 2: Downdrag
Combination 1(F) - downdrag force taken as action Partial factors for actions :
Vertical load, V: 3
= 1.35 Downdrag, D:
3= 1.35
Partial factors for resistances:Shaft resistance, R:
= 1.0
Total design vertical load = F = V + D= V#
3+ D#
3
= 3001.35 + 94.21.35= 532.2 kN.
55
Example 2: Downdrag
Note: Downdrag is classified as a 'permanent' action because its variation is always in the same direction (monotonic) until the action attains a certain limit value (EC1, 1.5.3.3).
Combination 1(F) - downdrag force taken as action Design shaft resistance = R
= R#/
= 47.1 L2 / 1.0. Require R F.
Hence 47.1 L2 / 1.0 532.2 kN.L2 11.29 m.
Design force for concrete shaft = F = 532.2 kN.
56
Example 2: Downdrag
Combination 1(S) - settlement taken as action Partial factors for actions:
Vertical load, V: 3
= 1.35 Any partial factor applied to settlement would have no
effect in this case.
Partial factors for resistances:Shaft resistance, R:
= 1.0
Partial factor for unfavourable soil strength transmitting effect of settlement to pile = 1.0.
Hence design downdrag force = 94.2 kN.
57
Example 2: Downdrag
Combination 1(S) - settlement taken as action Total design vertical load = F = V + D
= V# 3
+ 94.2
= 3001.35 + 94.2= 499.2 kN.
Design shaft resistance = R= R#/
= 47.1 L2 / 1.0.
58
Example 2: Downdrag
Combination 1(S) - settlement taken as action Require R F.
Hence 47.1 L2 / 1.0 499.2 kN.L2 10.6 m.
Design force for concrete shaft = F = 499.2 kN.
It is necessary to satisfy both Combinations 1 and 2, but the choice of force or displacement as the action is open to the designer.
59
Example 2: Downdrag
Combination 2(F) - downdrag force taken as action Partial factors for actions:
Vertical load, V: 3
= 1.0 Downdrag, D:
3= 1.0
Partial factors tor resistances:Shaft resistance, R:
= 1.3 (R4 with explicit verification of SLS)
Total design vertical load = F = V + D= V#
3+ D#
3
= 3001.0 + 94.21.0= 394.2 kN.
60
Example 2: Downdrag
Combination 2(F) - downdrag force taken as action Design shaft resistance = R
= R#/
= 47.1 L2 / 1.3. Require R F.
Hence 47.1 L2 / 1.3 394.2 kN.L2 10.88 m.
Design force for concrete shaft = F = 394.2 kN.
61
Example 2: Downdrag
Combination 2(S) - settlement taken as action Partial factors for actions :
Vertical load, V: 3
= 1.0 Settlement:
3= 1.0
Partial factors for resistances:Shaft resistance, R:
= 1.3
When settlement is taken to be the action, downdrag effect is transferred to the pile using the soil strength, which therefore acts in an unfavourable manner.
62
Example 2: Downdrag
Combination 2(S) - settlement taken as action EC7, 2.4.2 (11) says that a partial factor less than 1.0 must
be applied in such cases. It could be taken to be 1 / 89
from Material Table (or 1 /
from Resistance Table). This would give 1 / 1.4 = 0.714 (or 1 / 1.3 = 0.769).
Assumption that the displacement would mobilise all the available shaft adhesion in the soft clay. The characteristic value of this (D#) is 94.2 kN, as shown earlier.
63
Example 2: Downdrag
Combination 2(S) - settlement taken as actionD = 94.2 /
,
= 94.2 / 0.714= 131.9 kN
Total design vertical load = F = V + D= V#
3+ D#
3
= 3001.0 + 131.9= 431.9 kN.
64
Example 2: Downdrag
Combination 2(S) - settlement taken as action Design shaft resistance = R
= R#/
= 47.1 L2 / 1.3. Require R F.
Hence 47.1 L2 / 1.3 431.9 kN.L2 11.92 m.
Design force for concrete shaft = F = 431.9 kN.
65
Example 2: Downdrag
66
Calculation :;(m)
Which Sets to Use? Two combinations to be checked:
Combination 1: Increase loading Combination 2: Reducing resistance
In Combination 2, set M1 is used for calculating resistances of piles or anchors and set M2 for calculating unfavourable actions on piles owing e.g. to negative skin friction or transverse loading.
67
Combination 1:A1 + M1 + R1
Combination 2:A2 + (M1 or M2) + R4
where + implies: to be combined with.
Answer:Partial factor M2 is applied onto the soil parameter (e.g. cu) when downdrag effect is transferred to the pile using the soil strength, Downdrag is multiplied
with the M2 partial factor. Caution: Engineer should not double factor for the
same resistance.
Design of Piles in Compression
68
Number of pile load tests 1 2 3 4 5Factor 1 on mean Rcm 1.55 1.47 1.42 1.38 1.35Factor 2 on lowest Rcm 1.55 1.35 1.23 1.15 1.08
Static Pile Load Test
Number of tested piles 2 5 10 15 20Factor 5 on mean Rcm 1.94 1.85 1.83 1.82 1.81Factor 6 on lowest Rcm 1.90 1.76 1.70 1.67 1.66
Dynamic Impact Test
Number of profiles of tests 1 2 3 4 5 7 10Factor 3 on mean value 1.55 1.47 1.42 1.38 1.36 1.33 1.30Factor 4 on lowest value 1.55 1.39 1.33 1.29 1.26 1.20 1.15
Ground Test
Design of Piles in Compression
69
Number of pile load tests 1 2 3 4 5Factor 1 on mean Rcm 1.55 1.47 1.42 1.38 1.35Factor 2 on lowest Rcm 1.55 1.35 1.23 1.15 1.08
Static Pile Load Test
Number of tested piles 2 5 10 15 20Factor 5 on mean Rcm 1.94 1.85 1.83 1.82 1.81Factor 6 on lowest Rcm 1.90 1.76 1.70 1.67 1.66
Dynamic Impact Test
Number of profiles of tests 1 2 3 4 5 7 10Factor 3 on mean value 1.55 1.47 1.42 1.38 1.36 1.33 1.30Factor 4 on lowest value 1.55 1.39 1.33 1.29 1.26 1.20 1.15
Ground Test Question: Is it worthwhile to do more static pile load tests?
Design of Piles in Compression
70
Number of pile load tests 1 2 3 4 5Factor 1 on mean Rcm 1.55 1.47 1.42 1.38 1.35Factor 2 on lowest Rcm 1.55 1.35 1.23 1.15 1.08
Static Pile Load Test
Number of tested piles 2 5 10 15 20Factor 5 on mean Rcm 1.94 1.85 1.83 1.82 1.81Factor 6 on lowest Rcm 1.90 1.76 1.70 1.67 1.66
Dynamic Impact Test
Number of profiles of tests 1 2 3 4 5 7 10Factor 3 on mean value 1.55 1.47 1.42 1.38 1.36 1.33 1.30Factor 4 on lowest value 1.55 1.39 1.33 1.29 1.26 1.20 1.15
Ground Test
Design of Piles in Compression
71
Number of pile load tests 1 2 3 4 5Factor 1 on mean Rcm 1.55 1.47 1.42 1.38 1.35Factor 2 on lowest Rcm 1.55 1.35 1.23 1.15 1.08
Static Pile Load Test
Number of tested piles 2 5 10 15 20Factor 5 on mean Rcm 1.94 1.85 1.83 1.82 1.81Factor 6 on lowest Rcm 1.90 1.76 1.70 1.67 1.66
Dynamic Impact Test
Number of profiles of tests 1 2 3 4 5 7 10Factor 3 on mean value 1.55 1.47 1.42 1.38 1.36 1.33 1.30Factor 4 on lowest value 1.55 1.39 1.33 1.29 1.26 1.20 1.15
Ground TestAnswer:
Reduction of factor from 1.55 to 1.35 Increase in characteristic bearing resistance by
15%.Beneficial when you have many piles to install
within the zone of similar soil profile.
Design of Piles in Compression
72
Number of pile load tests 1 2 3 4 5Factor 1 on mean Rcm 1.55 1.47 1.42 1.38 1.35Factor 2 on lowest Rcm 1.55 1.35 1.23 1.15 1.08
Static Pile Load Test
Number of tested piles 2 5 10 15 20Factor 5 on mean Rcm 1.94
(1.65)1.85 (1.57)
1.83 (1.56)
1.82 (1.55)
1.81 (1.54)
Factor 6 on lowest Rcm 1.90 (1.62)
1.76 (1.50)
1.70 (1.45)
1.67 (1.42)
1.66 (1.41)
Dynamic Impact Test
Question: Is it worthwhile to do more dynamic impact
tests?
Note: Bracket values are values when using dynamic impact tests with signal
matching. Other notes available in NA to SS EN 1997-1:2010.
Design of Piles in Compression
73
Number of pile load tests 1 2 3 4 5Factor 1 on mean Rcm 1.55 1.47 1.42 1.38 1.35Factor 2 on lowest Rcm 1.55 1.35 1.23 1.15 1.08
Static Pile Load Test
Number of tested piles 2 5 10 15 20Factor 5 on mean Rcm 1.94
(1.65)1.85 (1.57)
1.83 (1.56)
1.82 (1.55)
1.81 (1.54)
Factor 6 on lowest Rcm 1.90 (1.62)
1.76 (1.50)
1.70 (1.45)
1.67 (1.42)
1.66 (1.41)
Dynamic Impact Test
Note: Bracket values are values when using dynamic impact tests with signal
matching. Other notes available in NA to SS EN 1997-1:2010.
Design of Piles in Compression
74
Number of pile load tests 1 2 3 4 5Factor 1 on mean Rcm 1.55 1.47 1.42 1.38 1.35Factor 2 on lowest Rcm 1.55 1.35 1.23 1.15 1.08
Static Pile Load Test
Number of tested piles 2 5 10 15 20Factor 5 on mean Rcm 1.94
(1.65)1.85 (1.57)
1.83 (1.56)
1.82 (1.55)
1.81 (1.54)
Factor 6 on lowest Rcm 1.90 (1.62)
1.76 (1.50)
1.70 (1.45)
1.67 (1.42)
1.66 (1.41)
Dynamic Impact Test
Note: Bracket values are values when using dynamic impact tests with signal
matching. Other notes available in NA to SS EN 1997-1:2010.
Answer:Requires a fair number of dynamic test with signal
matching analysis in order to reduce value of correlation factor.
Note: Take lower of the two categories of factors.Beneficial when you have many piles to install
within the zone of similar soil profile.
Design of Piles in CompressionModel Factor vs Correlation Factor
Model Factor, MF = 1.4 (without pile load test), or = 1.2 (with pile load test)
Correlation Factor,
75
Number of pile load tests 1 2 3 4 5Factor 1 on mean Rcm 1.55 1.47 1.42 1.38 1.35Factor 2 on lowest Rcm 1.55 1.35 1.23 1.15 1.08
Static Pile Load Test
Design of Piles in CompressionModel Factor vs Correlation Factor
Model Factor, MF = 1.4 (without pile load test), or = 1.2 (with pile load test)
Correlation Factor,
76
Number of pile load tests 1 2 3 4 5Factor 1 on mean Rcm 1.55 1.47 1.42 1.38 1.35Factor 2 on lowest Rcm 1.55 1.35 1.23 1.15 1.08
Static Pile Load Test
Question: Which gives a more aggressive design?
Design of Piles in CompressionModel Factor vs Correlation Factor
Model Factor, MF = 1.4 (without pile load test), or = 1.2 (with pile load test)
Correlation Factor,
77
Number of pile load tests 1 2 3 4 5Factor 1 on mean Rcm 1.55 1.47 1.42 1.38 1.35Factor 2 on lowest Rcm 1.55 1.35 1.23 1.15 1.08
Static Pile Load Test
Design of Piles in CompressionModel Factor vs Correlation Factor
Model Factor, MF = 1.4 (without pile load test), or = 1.2 (with pile load test)
Correlation Factor,
78
Number of pile load tests 1 2 3 4 5Factor 1 on mean Rcm 1.55 1.47 1.42 1.38 1.35Factor 2 on lowest Rcm 1.55 1.35 1.23 1.15 1.08
Static Pile Load Test
Answer: Model factor is often more aggressive as the factor is
generally lower.
79
Design of Piles in Compression
80
Design of Piles in Compression
Answer: Implied FoS from EC7 lower than BS. Shorter piles are
expected? Not necessary. Application of characteristic value onto soil parameters (i.e. cautious estimate) may bring the design of pile using EC7
closer to BS.
Structural CapacityEurocode 2:
Partial factors for concrete and steel for ULS:
The recommended values of c and s in the serviceability limit state (SLS) is 1.0.
The partial factor for concrete c given above should be multiplied by a factor, kf, for calculation of design resistance of cast in place piles without permanent casing. The recommended value is 1.1.
81
Design Situations c for concrete s for reinforcing steelPersistent & Transient 1.5 1.15Accidential 1.2 1.0
Structural CapacityEurocode 2:Bored piles Arrangement of reinforcements to allow free flow of concrete. Min. diameter for longitudinal bars not be less than 16 mm. At least 6 longitudinal bars. Clear distance between bars should not exceed 200 mm
measured along the periphery of the pile. Permit ease of flow of concrete.
82
Structural CapacityEurocode 2:Bored piles
83
Cast-in-place bored pile cross-section, Ac
Min area of longitudinal reinforcement, As,bpmin
Ac 0.5 m2 As 0.5% Ac0.5 m2 < Ac 1.0 m2 As 25 cm2 (0.25 - 0.5% Ac) Ac > 1.0 m2 As 0.25% Ac
Note: Prior recommendation was As 0.5% Ac .
Structural CapacityEurocode 2: Concrete
fcd = fck / c= 0.85 fck / 1.5 [driven]= 0.85 fck / (1.5 x 1.1) [bored-reinforced]= 0.60 fck / (1.5 x 1.1) [bored-unreinforced)]
Steelfyd = fyk / s
= fyk / 1.15 Structural capacity of pile > Design Action/Load
Q = fcd Ac + fyd As > Fd = G Gk + Q Qk= 0.515 fck Ac + 0.87 fyk As [bored-reinforced]= 0.364 fck Ac [bored-unreinforced]
84
Note:Factor of 0.85 for flexure and axial loading (NA to EC2 3.1.6)Factor of 0.6 due to less ductile properties of plain concrete (NA to EC2 12.3.1)
Structural CapacityEurocode 2:
Concretefcd = fck / c
= 0.85 fck / 1.5 [driven]= 0.85 fck / (1.5 x 1.1) [bored-reinforced]= 0.60 fck / (1.5 x 1.1) [bored-unreinforced)]
Steelfyd = fyk / s
= fyk / 1.15 Structural capacity of pile > Design Action/Load
Q = fcd Ac + fyd As > Fd = G Gk + Q Qk= 0.515 fck Ac + 0.87 fyk As [bored-reinforced]= 0.364 fck Ac [bored-unreinforced]
85
BS 8004 and SS CP4:Q = (0.4 fcu Ac + 0.75 fy As)/FoS [bored-reinforced]
SS CP65:Q = 0.25 fcu Ac [bored-unreinforced]
Note: fcu fck & fy fyk
Structural CapacityEurocode 2: Table 3.1 Strength characteristics for concrete
86
Structural CapacityEurocode 2: Table 3.1 Strength characteristics for concrete
87
Cylinder: fcm = fck + 8 (MPa)Cylinder fck 0.8 fck,cube
Note: Strength of a cylinder is approx. 0.8 that of a cube. Research has shown that the ratio of strength of a cylinder
vs cube increases (>0.8) as the strength of concrete increases.
Structural CapacityHence, Bored - reinforced section:
Q = fcd Ac + fyd As= 0.515 fck Ac + 0.87 fyk As 0.412 fck,cube Ac + 0.87 fyk As
Bored - unreinforced section:Q = fcd Ac
= 0.364 fck Ac 0.291 fck,cube Ac
Note: In CP4 and CP65,Q = (0.4 fcu Ac + 0.75 fy As)/FoS [bored-reinforced]Q = 0.25 fcu Ac [bored-unreinforced]
88
THANK YOU
Dr Darren Chian Siau ChenNational University of [email protected]
89