+ All Categories
Home > Documents > 0648-LMSPowerCableHandbk_0

0648-LMSPowerCableHandbk_0

Date post: 04-Jun-2018
Category:
Upload: asawinraja
View: 223 times
Download: 0 times
Share this document with a friend

of 142

Transcript
  • 8/13/2019 0648-LMSPowerCableHandbk_0

    1/142

    PowerCableHANDBOOK

    2011 Edition

    Harmonisation of Power DistributionSystems in the Lower Mekong Subregion

  • 8/13/2019 0648-LMSPowerCableHandbk_0

    2/142

    db k f d d bl

    Copyright 2010

    International Copper Association Southeast Asia Ltd

    All rights reserved. No part of this publication may be reproduced or distributed in any form or by any means, or stored

    in a database or retrieval system, without the prior written permission of the publisher.

    Printed in Singapore

    Underground Power Cable

    HANDBOOK

  • 8/13/2019 0648-LMSPowerCableHandbk_0

    3/142

    H db k f U d d P C bl

    Foreword

    Overhead power lines, a familiar sight in many old cities, are slowly disappearing from city skylines. Anoticeable trend towards underground power cabling is gathering momentum around the world. And

    nowhere else is this more evident than in Asia. City after city, professionals involved in city planning

    and development, from planners and architects to consultants and engineers, are deciding in favour of

    underground power distribution, realising the immense benefits that it offers.

    Underground power cable systems offer far reaching benefits. Not only do these systems dramatically

    improve the skyline of a city, they also result in better environment, lower power distribution costs,higher reliability and greater protection against hazards associated with overhead power lines. This

    trend is a significant development especially for countries in the Lower Mekong Subregion (LMS)

    and for the copper industry. Copper cables, due to much higher conductivity and other properties, are

    better suited for underground applications. This means reliability and quality of power supply, critical

    factors in reducing technical losses in the electricity grids of Utilities in the LMS.

    In deciding on the choice of conductor for an underground cabling system, Utilities have to consider

    the basic properties of the conductor material - electrical resistivity, tensile strength, melting point and

    coefficient of thermal expansion. Other factors to consider include:

    Space

    Underground cabling puts pressure to keep space requirements for trenches or ducts to the minimum.

    Conductivity, resistance and losses of the conductor in relation to its diameter will therefore determine

    its space efficiency. Allowable space must also be provided for thermal expansion of the conductor.

    Current Carrying Capacity

    The higher the conductivity of the material, the higher is the current rating for the same overall

    diameter of the conductor.

    Ruggedness

    Deterioration at cable joints and risk of mechanical damage can be minimised by the hardness of the

    conductor material. Its resistance to corrosion can protect joints against water penetration. And

  • 8/13/2019 0648-LMSPowerCableHandbk_0

    4/142

    db k f d d bl

    functional problems due to heating and developing hot spots will be less prone in conductors with the

    heating ability to withstand overloads/surges.

    Studies and experiences of Utilities have shown that transformers and power cables are the two largest

    loss makers in the electricity grid. So, much can be done in these two areas to help reduce significantlosses in the LMS power distribution systems.

    I am therefore pleased to note that the development of this underground power cable handbook is a

    progression of the power and distribution transformer handbooks. The development and harmonisation

    of technical specifications for transformers as well as power cables, in relation to international

    standards and best practices, can help to narrow the differences and gaps for LMS Utilities to work

    towards further reducing losses in their electricity grids.

    Development of handbooks is only an academic exercise. Reduction will only come when the

    guidelines and recommendations are followed and implemented by all associated with the design of

    the electricity grid, specifying the standards of equipment for procurement and subsequently operating

    or maintaining them.

    Victor ZhouDirector - China & Southeast Asia

    ICA Asia

  • 8/13/2019 0648-LMSPowerCableHandbk_0

    5/142

    H db k f U d d P C bl

    Introduction

    The Lower Mekong Subregion (LMS)Harmonisation Programme

    Being developing countries, their power distribution systems, an essential infrastructure, play a

    significant role in the economic development. Energy end-users are dependent on the availability,

    reliability, and quality of electricity from the power distribution systems. The level of development

    and advancement of power distribution systems has direct impact on the developmental potential and

    economic growth, especially in urban cities.

    The power distribution systems in the urban areas of these LMS countries, however, do not have the

    same level of development. It is widely acknowledged that harmonisation in the development of power

    distribution systems can benefit these countries and accelerate their economic growth.

    In 2005, six power partners entered into a Memorandum of Understanding (MOU) to share the intent

    of working together towards harmonisation of power distribution systems in the following four LMS

    countries: Cambodia, Lao PDR, Thailand and Vietnam. The founding partners are:

    Electricit du Cambodge (EDC), Cambodia

    Electricit du Laos (EDL), Lao PDR

    Ho Chi Minh City Power Company (HCMC PC), Vietnam

    Hanoi Power Company (HNPC), Vietnam

    Metropolitan Electricity Authority (MEA), Thailand

    International Copper Association Southeast Asia (ICASEA) [formerly known as Copper

    Development Centre Southeast Asia]

    Cambodia, Lao Peoples Democratic Republic (Lao PDR), Thailand and

    Vietnam have achieved different levels of economic development. These

    countries in the Lower Mekong Subregion (LMS) have strong economic

    inter-dependence.

  • 8/13/2019 0648-LMSPowerCableHandbk_0

    6/142

    db k f d d bl

    This led to a study of power distribution systems of the power partners in Cambodia, Lao PDR and

    Vietnam; and the preparation of a regional cooperation roadmap and action plan.

    Building on the success of the first MOU, ICASEA and MEA inked a second MOU to continue their

    strategic partnership in conducting further studies and facilitating programmes as outlined in phase 2of the road map and action plan. This impetus is to enable the LMS countries to make further progress

    towards harmonisation and the realisation of the objectives as set out in the MOU with all the power

    partners.

    The study of power distribution systems in the LMS countries under the first MOU had revealed that

    there are many differences in the power distribution systems in this region. The objective of this

    second MOU was to narrow down the differences in six key areas and enable the LMS countries tomove towards greater harmonization of their power distribution systems.

    Joining this Harmonisation Programme in 2009 were:

    Danang Power Company (DNPC), Vietnam

    HaiPhong Power Company (HPPC), Vietnam

    And in 2010,

    Provincial Electricity Authority (PEA), Thailand

    Central Power Corporation (EVNCPC), Vietnam

  • 8/13/2019 0648-LMSPowerCableHandbk_0

    7/142

    H db k f U d d P C bl

    Loss in the Power Distribution System is a common and pressing concern

    expressed by Utilities in the LMS. Reducing loss is the priority given

    the energy shortage arising from rapid economic growth and high oil

    prices.

    A Regional Loss Reduction Workshop for LMS Utilities was held in Phnom Penh, Cambodia on 18 &

    19 March 2008. It concluded with a consensus to, amongst other areas of collaboration, reduce lossesin the Power Distribution Systems of EDC, EDL, HCMC PC and HNPC by harmonising technical

    specifications and developing a best practices handbook for energy efficient equipment based on

    international standards.

    The views of and input from participating Utilities were crucial in the development of technical

    specifications for the harmonisation of power equipment in the LMS. Only with acceptance and

    implementation of the technical specifications can LMS Utilities reduce losses associated with

    inefficient power equipment. Hence, a 6-member Technical Working Group (TWG) comprising a

    senior technical representative from each Utility and ICASEA was formed to participate and contribute

    in discussions and meetings.

    The objective of this TWG was to start with the development of technical specifications to harmonise

    underground power cables in the LMS. This step-by-step approach was to enable the participating

    Utilities to review and evaluate the result of this Technical Working Group before collectively moving

    to the next step of harmonising other equipment.

    This handbook was developed to help LMS Utilities implement low loss power cables. Reduction will

    only come when the minimum performance guidelines are followed and implemented by all associated

    with the design of the electricity grid, specifying the standards of equipment for procurement and

    subsequently operating or maintaining them.

    Preface

  • 8/13/2019 0648-LMSPowerCableHandbk_0

    8/142

    db k f d d bl

    Chairman

    Mr.Asawin Rajakrom

    Director, Electrical Equipment and UG CableInstallation Division

    Metropolitan Electricity Authority, Thailand

    Electricite Du Cambodge (EDC), Cambodia

    Mr. Lim Sisophuon

    Deputy Chief, Dispatching Control Centre

    Electricite Du Laos (EDL), Lao PeoplesDemocratic Republic

    Mr.Bounkheuth Vilayhak

    Deputy Chief, Technical Standards Office

    Ho Chi Minh City Power Corporation

    (HCMC PC), Vietnam

    Mr.Nguyen Huu Vinh

    Electrical Engineer, Technical Department

    Hanoi Power Corporation (HNPC), Vietnam

    Mr.Dinh Tien Dung

    Expert, Technical Department

    Metropolitan Electricity Authority (MEA),

    Thailand

    Mr. Werawat Buathong

    Director, Electrical Engineering Division

    Mr. Somchai Homklinkaew

    Asst Director, Power System Planning Division

    Mr.Preecha Tongkaewkerd

    Senior Electrical Engineer, Power System

    Planning Division

    Ms. Sasianong VacharasikornSenior Electrical Engineer, Research and

    Development Dept.

    International Copper Association Southeast

    Asia (ICASEA)

    Mr. Louis Koh

    Project Leader, Power Distribution

    Mr. Piyadith Lamaisathien

    Country Manager, Thailand

    MEA Project Support Team

    Ms. Sutida Sindhvananda, Project Director,

    International Service Business

    Ms. Kunlathida Pongchavee, Executive Project

    Assistant, International Service Business

    Mr. Prawit Chaikaew, Electrical Engineer,

    International Service Business

    Members of the Technical Working Group for Power Cable:

  • 8/13/2019 0648-LMSPowerCableHandbk_0

    9/142

    H db k f U d d P C bl

    Electricit du Cambodge, Cambodia

    Mr. Keo Rottanak,Managing Director

    Mr. Chan Sodavath,Deputy Managing Director

    Electricit du Laos, Lao Peoples Democratic

    Republic

    Mr. Khammany Inthirath,Managing Director

    Mr. Sisavath Thiravong,Deputy Managing

    Director

    Mr. Boun Oum Syvanpheng,Deputy Managing

    Director

    Ho Chi Minh City Power Corporation, Vietnam

    Mr. Le Van Phuoc,Director

    Mr. Tran Khiem Tuan,Deputy Director

    Hanoi Power Company, Vietnam

    Mr. Tran Duc Hung,Director

    Mr. Vu Quang Hung, Vice Director, Technical

    Mr. Nguyen Anh Tuan, Vice Director, Business

    Metropolitan Electricity Authority, Thailand

    Mr. Pornthape Thunyapongchai,Governor

    Mr. Danai Chitterapharb,Director, Business

    Investment Dept.

    International Copper Association Southeast

    Asia

    Mr. Steven Sim, Chief Executive Officer

    Acknowledgements

    The harmonisation of power distribution systems in the LMS will

    contribute to the expansion of the ASEAN Power Grid. However,

    harmonisation requires a robust partnership and sustained effort over

    many years.

    The harmonisation of technical specifications together with the development of this handbook is

    taking the process a step closer towards the realisation of the objectives as set out in the strategicroadmap for the harmonisation of power distribution systems in the LMS.

    Strengthening regional cooperation to build the capacity of both technical and functional staff would

    not have been possible without the endorsement and support of:

  • 8/13/2019 0648-LMSPowerCableHandbk_0

    10/142

    db k f d d bl

    Table of Contents

    Introduction 1

    Chapter 1 1

    1.1 Introduction 1

    1.2 Objective 1

    1.3 General Requirements

    1.4 Principle Specifications 5

    1.5 Existing Requirement for Electricite du Cambodge (EDC), Cambodia 10

    1.6 Existing Requirement for Electricite du Laos (EDL), Lao Peoples Democratic Republic 11

    1.7 Existing Requirement for Ho Chi Minh City Power Corporation (HCMCPC), Vietnam. 11

    1.8 Existing Requirement for Hanoi Power Corporation (HNPC) Vietnam 13

    1.9 Additional Requirement for Metropolitan Electricity Authority (MEA), Thailand 14

    1.10 Conclusion 16

    Chapter2 17

    2.1 Introduction 17

    2.2 Objective 17

    2.3 Documents required for evaluation 17

    2.4 Guideline for bid evaluation 22

    2.5 Conclusion 24

    Chapter 3 25

    3.1 Introduction 25

    3.2 Objective 25

    3.3 Inspection Committee Management 25

    3.4 Manufacturing Process Inspection 26

    3.5 Factory acceptance tests 29

    3.6 Conclusion 32

  • 8/13/2019 0648-LMSPowerCableHandbk_0

    11/142

    H db k f U d d P C bl

    Chapter 4 34

    4.1 Introduction 34

    4.2 Objective 34

    4.3 Acceptance Committee Management 34

    4.4 Acceptance Process 35

    4.5 Conclusion 39

    Chapter 5 40

    5.1 Introduction 40

    5.2 Objective 40

    5.3 Ampacity Calculation 405.4 Insulation and Sheath Thickness Calculation 55

    5.5 Calculation on Cable Pulling Tension 58

    5.6 Conclusion 71

    Chapter 6 72

    6.1 Introduction 72

    6.2 Objective 72

    6.3 Types of installation 72

    6.4 Cable Laying Procedure 79

    6.5 Installation Acceptance Process 88

    6.6 Conclusion 89

    Chapter 7 90

    7.1 Introduction 90

    7.2 Objective 90

    7.3 Maintenance and Inspection 91

    7.4 Field Tests on Cable 98

    7.5 Cable Monitoring System 106

    7.6 Conclusion 107

  • 8/13/2019 0648-LMSPowerCableHandbk_0

    12/142

    db k f d d bl

    References 108

    APPENDIX A : Specification of 8.7/15 kV & 12/20 kV XLPE COPPER CABLE A-1

    APPENDIX B : Specification of 69 & 115 kV XLPE COPPER CABLE B-1

    Figures

    Figure 1 : Cross-section of 69 & 115 kV PE Outer Sheath (Jacket) 10

    Figure 2 : Cross-section of 69 & 115 kV PE Outer Sheath (Jacket) 15

    Figure 3 : Cross-section of 69 & 115 kV Fire Retardant PVC Outer Sheath (Jacket) 16

    Figure 4 : Cable Drawing 21

    Figure 5 : Schematic diagram of Extrusion Line 28

    Figure 6 : The geometric factor (G) and the Screening Factor 50Figure 7 : Mutual Heating Effect 52

    Figure 8 : Direct Burial Installation 73

    Figure 9 : Semi-Direct Burial Installation 74

    Figure 10 : Concrete Trough Installation 74

    Figure 11 : Concrete Encased Installation 75

    Figure 12 : Concrete Trench 76

    Figure 13 : Horizontal Directional Drilling Construction Layout Crossing the River 77

    Figure 14 : Cross Section of Concrete Pipe ID 1 m 78

    Figure 15 : Pulling Eye 80

    Figure 16 : Pulling Grips 80

    Figure 17 : Direct Burial Cable Laying Procedure 82

    Figure 18 : Cable Laying for Direct Burial 82

    Figure 19 : Cable Laying Procedure for Duct Installation 83

    Figure 20 : Test Rod or Dummy 84

    Figure 21 : CCTV Camera for Checking Duct 84

    Figure 22 : Checking Duct by Using CCTV Camera 84

    Figure 23 : Method of Cable Pulling 84

    Figure 24 : Cable Laying Procedure for Tunnel Installation 86

    Figure 25 : Floor Mounting Rollers 87

    Figure 26 : Cable Installation in Tunnel by Caterpillar Method 87

    Figure 27 : Megger Test1 kV 88

  • 8/13/2019 0648-LMSPowerCableHandbk_0

    13/142

    H db k f U d d P C bl

    Figure 28 : Insulation Testing 88

    Figure 29: Murray Loop Bridge Method 95

    Figure 30: Cable Fault Waveform Reflections 96

    Figure 31 : Tan Test Results (K. Brown IEEE ICC Minutes Spring 2005) 104

    Tables

    Table 1 : Major characteristics of underground cable 5

    Table 2 : Nominal diameters of round armor wires 12

    Table 3 : Nominal thickness of armor tapes 12

    Table 4: Sample of Proposed Technical Data for High Voltage XLPE Copper Cable 20

    Table 5 : Partial Discharge Test 30Table 6: Voltage Test 30

    Table 7 : Routine and Special Tests Report 37

    Table 8 : Acceptance Tests Report 38

    Table 9 : Conductor AC Resistance 43

    Table 10 : Dielectric losses of insulation 43

    Table 11 : Sheath Resistance of each material 44

    Table 12 : Thermal Resistances of each material 49

    Table 13 : Nominal Thickness of PVC/B Insulation for Cable Rated Voltages 55

    Table 14 : Nominal Thickness of Cross-lined Polyethylene (XLPE) Insulation 55

    for Cable Rated Voltages

    Table 15 : Nominal Thickness of Ethylene Propylene Rubber (EPR) and Hard 56

    Ethylene Propylene Rubber (EPR) Insulation for Cable Rated Voltages

    from 6 kV (Um

    = 7.2 kV) to 30 kV (Um

    = 36 kV)

    Table 16 : Maximum Cable Cross-sectional Area as a Percentage of Internal 58

    Conduit or Duct Area (Refer to NEC)

    Table 17 : Minimum Recommended Bending Radii for Unarmored Power Cables 60

    for Cables Rated

    Table 18 : Cable Configurations in Conduit 61

    Table 19 : Recommended Basic Dynamic Coefficient of Friction, Straight Pulls 63

    & Bearing Pressures

    Table 20 : Recommended Maximum Pulling Tensions at Pulling Eyes 64

    Table 21: Recommended Maximum Pulling Tensions Copper and Aluminum 65

    Conductor Single

  • 8/13/2019 0648-LMSPowerCableHandbk_0

    14/142

    db k f d d bl

    Table 22 : Definition of symbols 68

    Table 23: Comparison of Different Methods of UG Cable Installation 79

    Table 24: Value of Direct Voltage for Jacket Test 88

    Table 25 : DC Test Voltage according to IEC 60502-2005 99

    Table 26 : AC Test Voltage according to IEC 60840-2004 101

    Table 27 : VLF Test Voltage according to IEEE 400.3-2006 102

    Table 28: Summary of Different Tests 106

    Table 29 : Methods for Monitoring Underground Cable System 107

  • 8/13/2019 0648-LMSPowerCableHandbk_0

    15/142

    1 | H db k f U d d P C bl

    Introduction

    This is the first ever handbook on underground cables. The objective of this handbook is to serve as

    a desk and field compendium for the utilities of Lower Mekong Sub-region (LMS) countries. These

    utilities are Electricite du Cambodge (EDC), Cambodia; Electricite du Laos (EDL), Lao Peoples

    Democratic Republic; Hanoi Power Corporation (HNPC); Ho Chi Minh City Power Corporation

    (HCMCPC), Vietnam; and the Metropolitan Electricity Authority (MEA), Thailand.

    This handbook describes all the important processes -- from procurement to final acceptance --

    involved in an underground power cable project. These processes include preparation of specifications,

    bidding evaluation, cable manufacturing inspection, contract acceptance, calculations on cable, cable

    installation, cable system operation, maintenance and testing.

    The handbook refers to the reputable reference books, the latest editions of international and national

    standards, and the current specifications of LMS utilities. Specifically, it covers underground cables

    with voltage rating from 22 kV (minimum) to 115 kV (maximum) and frequency rating of 50 Hz.

    The study of power distribution systems in the LMS countries reveals that there are many differences

    in underground cable system practice, hence, to promote the harmonization of the LMS practice, the

    common specification for underground cable of the LMS utilities shall be developed for concrete

    implementation in the future. The normative technical specification of underground power cable is

    then proposed in Appendices A and B for optional application in the LMS underground system.

  • 8/13/2019 0648-LMSPowerCableHandbk_0

    16/142

    db k f d d bl |

    Chapter 1

    Preparation of National Normative Technical Specification ofUnderground Copper Cable

    1.1 Introduction

    Underground power cables have different electrical characteristics from overhead lines. These

    differences must be taken into consideration during cable system planning, design and operation.

    This chapter describes some of the most important requirements that should be considered by utilities

    while preparing specifications of underground cables.

    1.2 Objective

    The objective is to provide general information on how to select, design, install and maintain a cable

    system effectively. And also to help cable engineers reduce cost, which tends to increase due to

    ineffective use and maintenance of underground cable. The information provided should also enable

    utilities to minimize the need for new investments, learn about loss reduction programs and minimize

    negative environmental impact.

    The secondary objectives include encouraging greater energy efficiency; developing new national

    standards; starting cost effective energy saving programs for both utilities and customers; reducing

    losses from utility-owned underground cables; and minimizing life cycle costs. Eventually,

    these programs would increase system capacity and decrease the cost of investment in constructing

    new distribution substations.

    1.3 General Requirements

    This specification is for power utility companies in the Lower Mekong Sub-region (LMS). An

    underground cable shall be installed in a cable tray or in a duct under the ground and also by direct

    burial where fault level is up to 25 kA for MV system and 40 kA for HV system.

    Site and Service Condition: LMS utilities operate in a tropical climate. The altitude ranges from 0

    meter to 1,800 meters above sea level, ambient temperature ranges from 30C to 45C and relative

  • 8/13/2019 0648-LMSPowerCableHandbk_0

    17/142

    3 | H db k f U d d P C bl

    humidity measures 84%. The cable shall be suitable for continuous use at conductor temperature of

    90C for normal operation and 250C for short-circuit condition.

    Reference Standard:The International Electrotechnical Commission (IEC) is the common

    reference standard for all LMS utilities as well as for a majority of countries around the world. ForMV underground cables, IEC 60502 series is the key reference. IEC 60840 is the reference for HV

    underground cable, and IEC 60228 serves as the reference for conductor. For fire retardant cables, IEC

    60332 and ISO 4589 shall be applied. Some utilities also refer to their own national standards, which

    are mostly equivalent to IEC except for some addition requirements due to their specific experience

    and local conditions.

    Test, Inspection and Test Report:There will be three main tests:

    Type test: The proposed cable should successfully pass all the type or design tests in accordance with

    the reference standards.

    In case the fire retardant jacket is required, the following tests shall be included:

    The oxygen index of non-metallic sheath material shall be not less than 30 according to ISO

    4589 or equivalent.

    Testing on completed cable under fire condition according to IEC 60332-3-22 or equivalent.

    The testing shall be done by a reputable independent testing agency or an agency acceptable to LMS

    utilities.

    Cable manufacturers who do not have a type test report for the proposed cable shall alternatively

    submit a type test report within the range of type approval as specified in IEC standard.

    Routine tests: Routine tests shall be made on each reel of the finished cables in accordance with the

    reference standards. At minimum, the following tests shall be included:

    a) Measurement of electrical resistance of conductors

    b) Partial discharge test

    c) High voltage test

    Special tests: The special tests shall be made on one length from each manufactured lot of the cables

    of the same type and size. But these tests shall be limited to not more than 10% of the number of cable

  • 8/13/2019 0648-LMSPowerCableHandbk_0

    18/142

    db k f d d bl |

    lengths in the contract, rounded to the upper unity. Special tests, conducted in accordance with the

    reference standards, will at least include the following items:

    a) Conductor examination

    b) Checking of dimensions including measurement of external diameter c) Electrical test

    d) Hot set test for XLPE insulation

    Special and routine tests shall be carried out to determine whether the cable complies with the

    specifications. For any additional tests required as per the mutual agreement between the purchaser

    and the manufacturer, the test method shall be proposed by the manufacturer and approved by the

    purchaser before proceeding with the testing.

    Type tests help to validate design, raw material, workmanship and quality control during the

    manufacturing process. Routine tests, as the name implies, are tests that are routinely performed on

    each drum of cable to assure that cables are good quality and made according to required specification

    before it leaves the factory. The utility reserves the right to send representatives to witness all

    the required tests at the factory.

    Routine and Special Test Report: Prior to shipment, the supplier shall submit to the utility six (6)

    complete and certified sets of all test reports. The test reports shall include all the data required for

    their complete interpretation, e.g., diagrams, methods, instruments, constants and values used in the

    tests and the results obtained.

    Drawings and Instruction: The supplier shall furnish six (6) sets of documents covering all

    the significant details of the underground cable to the utility for approval within a stipulated

    timeframe.

    To protect mutual interest in cases of delayed or late submission, compensation terms shall be

    specified in the contract. Special installation instructions and precautions, characteristic curves,

    installation instructions and instruction manuals with the contract number marked thereon -

    in the metric system - shall be machine printed or typed and delivered prior with the first

    shipment.

    Rating and Features:The major characteristics of the underground cable must be properly specified,

    such as shown in the following table:

  • 8/13/2019 0648-LMSPowerCableHandbk_0

    19/142

    5 | H db k f U d d P C bl

    Type Solid Extruded Dielectric

    System voltage level (kV)(MV) 15, 22, 24, 35 kV

    (HV) 69, 110, 115 kV

    U /U (kV)

    (MV) 12.7/22, 12/20, 21/35 kV

    (HV) 36, 64 kV

    Frequency ( Hz ) 50

    Conductor Size (sq.mm.)(MV) 70, 150, 240, 400

    (HV) 400, 800, 1000, 1200

    Insulation XLPE

    Metallic Screen COPPER WIRE

    Non Metallic Outer Sheath PVC or PE or fire retardant PVCOperating Temperature (C) 90

    Table 1 : Major characteristics of underground cable

    1.4 Principle Specifications

    The following specifications apply to underground cables for LMS utilities.

    1.4.1 Medium Voltage (MV) Cable

    The MV underground cable shall be extruded-dielectric XLPE type manufactured by dry

    curing process only. The cables shall be installed direct burial, in ducts, trays. The requirement

    of each layer shall be as follows.

    Conductor:The conductor type shall be plain annealed copper and the construction shall be

    compact round concentric lay stranded.

    Conductor Screen:The conductor screen is a conducting material by the triple extrusion

    with the insulation over the surface of the conductor. The thickness of the conductor screen

    for each utility shall be between 0.0635 and 1.0 mm. The extruded conductor screen shall have

    resistivity in accordance with the reference standards.

    Semi-conductive tape may be applied between conductor and conductor screen.

    Insulation:The insulation shall be cross-linked polyethylene (XLPE) and simultaneously

    extruded with the semi-conductive conductor screen and insulation screen layer. Electrical,

  • 8/13/2019 0648-LMSPowerCableHandbk_0

    20/142

    db k f d d bl |

    mechanical, and other properties shall comply with IEC 60502-2 or equivalent.

    The dry curing process is required. Conventional steam or hot water curing processes are

    not acceptable.

    The average thickness of insulation shall not be less than the nominal value specified in the

    reference standards. The minimum thickness shall not fall below the nominal value by more

    than 0.1 mm + 10% of the nominal value, i.e.:

    tm

    tn (0.1+0.1 t

    n)

    Where, tmis the minimum thickness

    tnis the nominal thickness

    Insulation Screen:The insulation screen shall consist of a nonmetallic covering directly over

    the insulation in combination with metallic screen. Nonmetallic covering having maximum

    volume resistivity at rated temperature shall be applied over the insulation in one or more

    layers.

    Nonmetallic screen may consist of a conducting tape or a layer of conducting compound

    having thickness between 0.0635 and 1.0 mm.

    Metallic Screen:Metallic screen shall consist of nonmagnetic metal component applied over

    the nonmetallic covering. The metallic screen shall be made of copper.

    Copper screen shall consist of plain annealed copper flat or round wires applied helically

    over the nonmetallic covering. The wires shall be electrically continuous and bonded together

    throughout the cable length with copper contact tape. The total cross-sectional area of the screen

    and minimum number of wire shall be not less than the specified value in the contract.

    Outer Sheath:The properties of outer sheath shall comply with mechanical requirements

    specified in IEC 60502-2 or equivalent. It shall also be suitable for use with the cable having

    maximum conductor temperature of 90C. The material of outer sheath shall be black PVC

    or black PE (ST7).

    If the fire retardant outer sheath is specified in the contract, the sheath shall be black flame

    retardant PVC. The oxygen index of outer sheath material shall be not less than 30 as measured

  • 8/13/2019 0648-LMSPowerCableHandbk_0

    21/142

    7 | H db k f U d d P C bl

    according to ISO 4589 or equivalent. A certified test report from the raw material manufacturer

    or an accepted reputable independent institution shall be submitted for approval. The f lame

    retardant outer sheath shall be able to stop flame propagation along vertical or horizontal cable

    ways and delay damage to cables. Test on completed cable under fire condition according to

    IEC 60332-3-22 or equivalent shall be done by reputable independent testing institution or at

    the factory test station witnessed by utilitys representative. The test report shall be submitted

    before shipment. Fire retardant is used only in confined area such as substation building or

    tunnel.

    Marking: The outer sheath shall be marked on the surface with, at minimum, cable

    description, manufacturers name or symbol, and date of manufacturing. The details of the

    marking shall be specified in the contract. Continuous marking on the sheath along the whole

    cable length shall also be provided at 1 meter interval.

    Cable End Sealing: Immediately after the factory test, the cable inner end shall be covered

    with an end cap, and the cable outer end shall be connected to a moisture-proof pulling eye of

    sufficient strength. Cable rib shall be removed before sealing. The material of cable end sealing

    shall be a metal cap or a heat shrinkable cap.

    1.4.2 High Voltage (HV) Cable

    The HV underground cable shall be extruded-dielectric XLPE type, manufactured by dry curing

    process only. The cables shall be installed by direct burial in ducts or in trays where they are

    immersed in the water all the time. The detailed requirements for each layer are as follows:

    Conductor:The conductor type shall be plain annealed copper. The construction shall be

    compact round concentric lay stranded or compact segmental stranded for cross-section area

    less than 1,000 mm. It will be compact segmental stranded for cross-section area 1,000 mm

    and above.

    Conductor Screen: The conductor screen shall be semi-conductive cross-linked polyethylene.

    The conductor screen is a conducting material by the triple extrusion with the insulation over

    the surface of the conductor. The thickness of the conductor screen for each utility shall be

    between 0.8 to 1.5 mm. The extruded conductor screen shall have resistivity in accordance

    with the reference standards.

  • 8/13/2019 0648-LMSPowerCableHandbk_0

    22/142

    db k f d d bl |

    Semi-conductive tape may be applied between conductor and conductor screen.

    Insulation:The insulation shall be cross-linked polyethylene (XLPE) simultaneously extruded

    with the semi-conductive conductor screen and insulation screen layer. Mechanical, electrical

    and other properties shall comply with IEC 60840 or equivalent.

    The dry curing process is required. Conventional steam or hot water curing processes are

    not acceptable.

    The minimum thickness of the insulation shall not be less than 90 per cent of the nominal value

    specified, and additionally it should satisfy:

    Where, maximum thickness and minimum thickness are the measured values at one and the

    same cross-section of the insulation.

    Insulation Screen: The conductor screen shall be semi-conductive cross-linked polyethylene.

    The conductor screen is a conducting material applied by triple extrusion with the insulation

    over the surface of the conductor. The thickness of the conductor screen for each utility shall

    be between 0.8 to 1.5 mm. The extruded conductor screen shall have resistivity in accordance

    with the reference standards.

    Synthetic Water Blocking Layer:A semi-conductive, non-biodegradable water blocking

    layer shall be provided under the metallic screen to provide a continuous longitudinal

    watertight barrier throughout the cable length.

    This layer shall be compatible with other cable materials and shall not corrode adjacent metal

    layers during heat aging of the cable.

    Metallic Screen (Grounding Screen): The metallic screen shall be a concentric layer of

    copper wires, which is electrically continuous and bonded together throughout the cable length

    with copper contact tape. The total cross-sectional area and minimum number of wires of the

    metallic screen shall not be less than the value specified in the contract.

    0.15

  • 8/13/2019 0648-LMSPowerCableHandbk_0

    23/142

    9 | H db k f U d d P C bl

    Synthetic Water Blocking and Cushioning Tape: A non-conductive, non-biodegradable

    water blocking tape shall be applied over the metallic screen to provide a continuous

    longitudinal watertight barrier throughout the cable length. The tape shall have sufficient

    thickness to perform well as a thermal stress relief layer and to provide for cushioning and

    bedding.

    The tape shall be compatible with other cable materials and shall not corrode adjacent metal

    layers during heat aging of the cable.

    Radial Water Barrier:As a protection against formation of water trees in the insulation, a

    traverse water barrier consisting of laminated aluminum tape coated on both sides with an

    ethylene acrylic acid adhesive co-polymer or polyethylene shall be incorporated under the non-metallic sheath. The average thickness of aluminum tape shall not be less than 0.19 mm.

    Outer Sheath: The outer sheath shall be PVC or compound black polyethylene (PE) ST7. It

    should be suitable for use with the cable having maximum conductor temperature of 90C and

    130C under normal and emergency condition respectively. The mechanical properties shall

    be in accordance with reference standard.

    If the fire retardant outer sheath is specified in the contract, the sheath shall be black flame

    retardant PVC. The oxygen index of outer sheath material shall be not less than 30 as measured

    according to ISO 4589 or equivalent. A certified test report from the raw material manufacturer

    or an accepted reputable independent institution, shall be submitted for approval. The flame

    retardant outer sheath shall be able to stop flame propagation along vertical or horizontal cable

    ways and delay damage to cables. Test on completed cable under fire condition according to

    IEC 60332-3-22 or equivalent shall be done by reputable independent testing institution or at

    the factory test station witnessed by utilitys representative, the test report shall be submitted

    before shipment. Fire retardant is used only in confined area such as substation building or

    tunnel.

    Additional requirement for 69 & 115 kV PE outer sheath for the purpose of electrical

    protection and ease of pulling, the sheath shall be ribbed type having crest width and depth of

    approximately 2.5 mm and the center to center distance between crests shall be approx. 7 mm,

    except for length marking. The crest width shall be approximately 10 mm. See Figure 1.

  • 8/13/2019 0648-LMSPowerCableHandbk_0

    24/142

    db k f d d bl |

    Marking:Manufacturers name or trade name, year of manufacturing and contract number

    shall be provided at appropriate interval throughout the cable length. This will be done on

    the outer longitudinal water blocking or on the outer sheath by inserting identification tape

    between radial water barrier layer and outer longitudinal water blocking layer.

    Cable End Sealing:Immediately after the factory test, the cable inner end shall be covered

    with an end cap, and the cable outer end shall be connected to a moisture-proof pulling eye of

    sufficient strength. Cable rib shall be removed before sealing. The material of cable end sealing

    shall be a metal cap or a heat shrinkable cap.

    1.5 Existing Requirement for Electricite` du Cambodge

    (EDC), Cambodia

    The additional specifications for MV underground cables required by Cambodias EDC utility are

    as follows:

    Metallic screen shall be copper tape. The minimum thickness shall not be less than 0.2 mm.

    For 3 cores cable only, the cables shall include an armor layer, which will be double tape type.

    Water blocking is required by using swelling material in conductor strand.

    HV underground cable specification is not currently employed.

    Figure 1 : Cross-section of 69 & 115 kV PE Outer Sheath (Jacket)

    FOR LENGTH MARKING

    10 mm (APPROX.)

    2.5 mm (APPROX.)

    7mm(APPR

    OX.)

  • 8/13/2019 0648-LMSPowerCableHandbk_0

    25/142

    11 | H db k f U d d P C bl

    1.6 Existing Requirement for Electricite` du Laos (EDL),

    Lao Peoples Democratic \ Republic

    The existing specification for MV underground cables required by EDL utility is as follows:

    Metallic screen shall be copper tape.

    HV underground cable specification is not currently employed.

    1.7 Existing Requirement for Ho Chi Minh City Power

    Corporation (HCMCPC), Vietnam.

    The existing specifications required by HCMCPC utility are as follows:

    1.7.1 MV underground cables

    The metallic screen shall be double copper tape having maximum thickness of 0.127 mm

    and minimum width of 12.5 mm.

    Inner covering and fillers are required for multi-cores cables. The cables shall have an

    inner covering over the laid-up cores. The inner coverings and fillers shall be of suitable

    materials. An open helix of suitable tape is permitted as a binder before applying an

    extruded inner covering. The material used for inner coverings and fillers shall be suitable

    for the operating temperature of the cable and compatible with the insulating material.

    The thickness of extruded inner coverings shall be specified in accordance with the

    reference standards.

    The cables shall have separation sheath. When the metal screen and armor are made

    of different metals, these shall be separated by an impervious extruded sheath. This

    may be instead of, or in addition to, an inner covering. The separation sheath shall be

    thermoplastic compound (PVC, PE or similar materials) or vulcanized elastomeric

    compound (polyethylene or similar materials). The quality of the material used for

    the separation sheath shall be suitable for the operating temperature of the cable. The

    nominal thickness of this sheath, rounded to the nearest 0.1 mm, shall be derived from

    the formula:

    Ts= 0.02D + 0.6 mm

  • 8/13/2019 0648-LMSPowerCableHandbk_0

    26/142

    db k f d d bl |

    Where: D is the fictitious diameter under the sheath. The smallest nominal thickness

    shall be 1.2 mm. The minimum thickness at any point shall not fall below 80% of the

    nominal value by more than 0.2 mm.

    For multi-cores cables, the cables shall consist of armor layer. The armor shall be flat orround wire (galvanized Fe, Pb-coated Fe, Al or Al alloy) or double tape (Fe., galvanized

    Fe, Al or Al alloy).

    Fictitious diameter under the armor [mm] Nominal diameter of armor

    wire [mm]Above Up to and including

    15 0.8

    15 25 1.625 35 2.0

    35 60 2.5

    60 3.15

    Table 2 : Nominal diameters of round armor wires

    The dimension of round armor wires shall not fall below the nominal value by more than 5%.

    Flat armor wires: For fictitious diameters under the armor greater than 15 mm, the nominal

    thickness of the flat steel wire shall be 0.8 mm. The dimension of flat armor wires shall not fall

    below the nominal value by more than 8%.

    Table 3 : Nominal thickness of armor tapes

    Fictitious diameter under the armor [mm] Nominal thickness of tape [mm]

    Above Up to and includingSteel or galvanized

    steel

    Aluminum or

    aluminum alloy

    30 0.2 0.5

    30 70 0.5 0.5

    70 - 0.8 0.8

    The dimension of armor tapes shall not fall below the nominal value by more than 10%.

  • 8/13/2019 0648-LMSPowerCableHandbk_0

    27/142

    13 | H db k f U d d P C bl

    1.7.2 HV underground cables

    The metallic screen (sheath) shall be of aluminum laminated or corrugated aluminum and

    complying with the following requirements:

    a. Laminated aluminum

    The metallic screen shall consist of laminated aluminum. This screen shall be a combination of

    a copper wire and a layer of aluminum tape.

    The cross-section of the copper screen shall have sufficient area to withstand the thermal and

    dynamic effect of a single-phase to ground short circuit current of 31.5 kA for 3 seconds. The

    bidder shall submit the calculation for determining the cross-sectional area of the copper wirescreen.

    b. Corrugated aluminum sheath

    The metal sheath shall consist of a tube of corrugated aluminum. The thickness of the corrugated

    aluminum sheath shall be sufficient to withstand the thermal and dynamic effect of a single-

    phase to ground short circuit current of 31.5 kA for 3 seconds.

    The bidder shall submit the calculations for determining the sheath thickness.

    The sheath shall be designed and manufactured as a homogeneous construction with the following

    characteristics: uniform thickness, close fitting, seamless and free from defects, porosity and

    inter-crystalline fracture. The sheath corrugation shall be of annular ring or helix construction

    designed to minimize the ingress of moisture even when the serving is damaged.

    1.8 Existing Requirement for Hanoi Power Corporation(HNPC) Vietnam

    The existing specifications of MV and HV Underground Cable required by HNPC utility

    are as follows: Metallic screen shall be copper wires. The total cross-sectional area of the

    copper wires screen shall be specified in the contract.

    For multi-cores cable, the cables shall consist of armor layer. The armor shall be steel tape

    type.

  • 8/13/2019 0648-LMSPowerCableHandbk_0

    28/142

    db k f d d bl |

    Swelling material in conductor strand, longitudinal water blocking over copper wire screen

    and radial water blocking below outer sheath are required.

    1.9 Additional Requirement for Metropolitan Electricity

    Authority (MEA), Thailand

    In addition to 1.4 Principle specifications, the following specifications should be employed to enhance

    safety, reliability, performance and maintenance:

    1.9.1 MV underground cables

    The tension necessary to remove an extruded insulation screen from cable at room

    temperature shall not be less than 13.3 N.

    Copper wire screen will consist of plain annealed copper fate or round wires applied

    helically over the nonmetallic covering. The wires shall be electrically continuous and

    bonded together throughout the cable length with copper contact tape. The total cross-

    sectional area of the screen and minimum number of wire shall be not less than the

    specified value in the contract.

    If PVC fire retardant outer sheath is specified in the contract, the sheath shall be black,

    flame retardant PVC. The oxygen index of outer sheath material shall be not less than

    30 as measured according to ISO 4589 or equivalent. A certified test report from the

    raw material manufacturer or a reputable independent institution, which is acceptable

    to MEA, shall be submitted for approval. The flame retardant outer sheath shall be able

    to stop f lame propagation along vertical or horizontal cable ways and delay damage to

    cables. Test on completed cable under fire condition according to IEC 60332-3-22 or

    equivalent shall be done by reputable independent testing institution or at the factory

    test station witnessed by MEAs representative. The test report shall be submitted before

    shipment.

    1.9.2 HV underground cables.

    If a fire retardant outer sheath is specified in the contract, the sheath shall be black, flame

    retardant, and made of PVC. The oxygen index of non-metallic sheath material shall

    be not less than 30 as measured according to ISO 4589 or equivalent. A certified test

  • 8/13/2019 0648-LMSPowerCableHandbk_0

    29/142

    15 | H db k f U d d P C bl

    report from the raw material manufacturer or a reputable independent institution, which

    is acceptable to MEA, shall be submitted for approval. The flame retardant non-metallic

    sheath shall be able to stop flame propagation along vertical or horizontal cable ways and

    delay damage to cables. Testing on the completed cable under fire condition according to

    IEC 60332-3-22 or equivalent shall be done by a reputable independent testing institution

    or at the factory (to be witnessed by MEAs representative). And the test report shall be

    submitted before shipment.

    Additional requirement for 69 & 115 kV PE outer sheath for MEA: The sheath shall be

    ribbed type having crest width and depth of approximately 2.5 mm and the center to

    center distance between crests shall be approx. 7 mm, except for length marking. The

    crest width shall be approximately 10 mm. See Figure 2.

    Figure 2 : Cross-section of 69 & 115 kV PE Outer Sheath (Jacket)

    Additional requirement for 69 & 115 kV fire retardant PVC sheathed for MEA: The

    sheath shall be ribbed type having crest width and depth of approx. 2.5 mm and the

    center to center distance between crests shall be approx. 7 mm. The crest width at the

    quarters shall be approximately 5 mm, and the crest width for length marking shall be

    approximately 10 mm. See Figure 3.

    FOR LENGTH MARKING

    10 mm (APPROX.)

    2.5 mm (APPROX.)

    7mm(A

    PPROX.)

  • 8/13/2019 0648-LMSPowerCableHandbk_0

    30/142

    db k f d d bl |

    Figure 3 : Cross-section of 69 & 115 kV Fire Retardant PVC Outer Sheath (Jacket)

    1.10 Conclusion

    From this chapter cable engineers can learn the specifications of other power utilities and compare

    them with their own specifications. This will enable them to know the advantages and disadvantages

    of different types of cable design and improve their specifications. The cable constructions for each

    power utility may be different because of its unique installation requirements. It is recommended that

    power utilities review their specifications for the cable insulation material from the point of view of

    the cost as well as the losses. However, in order to promote the harmonization of the LMS practice,

    the common specification for underground cable of the LMS utilities shall be developed for concrete

    implementation in the future. The normative technical specification of underground power cable is

    then proposed in Appendices A and B for optional application in the LMS underground system.

    FOR LENGTH MARKING

    10 mm (APPROX.)

    7mm(A

    PPROX.)

    2.5 mm (APPROX.)

    5mm

    (APPROX.)

  • 8/13/2019 0648-LMSPowerCableHandbk_0

    31/142

    17 | H db k f U d d P C bl

    Bidding Evaluation

    2.1 Introduction

    Bidding evaluation is one of the most important processes to ensure that a utility gets good quality

    cables on time. And to support bid evaluation, utilities must instruct suppliers to submit all the

    necessary documents. Inefficient documents may lead to poor quality of cables. The specification

    should clearly specify the necessary documents required to be submitted by the suppliers. Suppliers

    should fill-in all tables and forms as required in the bid documents.

    2.2 Objective

    The objective of this chapter is to guide and assist the utilities to learn about documents, data and tables

    required for evaluation. If a bidding document is complete, its evaluation will be easy and efficient. If

    not, more documents will be requested and submitted in a limited period, otherwise the bid shall not

    be considered. Only underground cables shall be discussed in this chapter.

    2.3 Documents Required for Evaluation

    Usually, there are five main documents required for evaluation: (i) type test report, (ii) proposed

    technical data, (iii) deviation form, (iv) detail drawing and (v) reference list of supply. Additional

    documents or samples may be required depending on special requirements of each utility.

    Bids should be evaluated by an Evaluation Committee whose members are selected from related

    departments. It is important not to get bids evaluated by only a single person or department.

    The requirements and instructions for evaluating each of the above-mentioned five bid documents

    are as follow.

    2.3.1 Type test report

    The proposed cables should pass all the type tests according to the reference standard specified

    in the specifications. The tests shall be conducted by a reputable independent testing agency

    Chapter 2

  • 8/13/2019 0648-LMSPowerCableHandbk_0

    32/142

    db k f d d bl |

    acceptable to the utility. All test reports shall be submitted with the offer otherwise such offer

    will not be considered.

    Cable manufacturers who do not have type test reports of the proposed cables can submit a

    type test report of the cable with the range of type approval specified in reference standard forconsideration or bigger sizes of conductor but same ratings and construction design.

    In the case of fire retardant cable, the test for vertical flame spread of vertically-mounted bunched

    cables can be carried out after the award of contract but before shipment or else the right will be

    reserved to purchase from the second lowest bidder with penalty to compensate for the balance

    in order to keep delivery schedule.

    2.3.2 Proposed technical data

    Proposed technical data is important for bid evaluation as it provides information for the

    Evaluation Committee to assess whether the proposed cables conform to the specifications.

    Normally, the standard provides guidelines for the technical data required to be filled up in the

    inquiry and order section. Any other additional requirements for technical data should also be

    provided in this section.

    Bidders are requested to fill in all the blank spaces in the technical proposal data form and return

    with the bid. Failure to submit the form or incomplete forms may render the bid invalid and

    constitute a sufficient case for bid rejection.

    The sample of technical proposal data form is shown in Table 4.

    2.3.3 Deviation form

    Bidders must clearly indicate all deviations from the specifications fill in the Deviation Form

    and attach it with the bid. If there is no deviation stated in the Deviation Form, the characteristics

    of the proposed cables shall be considered to be in complete compliance with specifications.

    However, if the delivered cable is found not in compliance with the specification, it will be

    rejected.

  • 8/13/2019 0648-LMSPowerCableHandbk_0

    33/142

    19 | H db k f U d d P C bl

    2.3.4 Drawing

    The drawing of the proposed cables is also important for bid evaluation. It should show all

    important details of the proposed cables, including cable construction, dimension, material, etc.

    All information shall be in English or the countrys official language, machine printed or typed.

    Information on drawing shall be in engineering lettering. All measurements and quantities shall

    be expressed in the units of metric system. If they are expressed in other unit systems, the metric

    equivalent shall also be indicated.

    Figure 4 shows a sample of detailed drawing of a cable.

    2.3.5 Reference list of supply and field experience

    A reference list of bidders supply and field experience shall also be taken into consideration when

    evaluating bids. Bidders should attach a reference list of supply and field experience in the same

    design of cables as proposed with the quotation.

    A reference list of previous supply projects is particularly important for evaluation in case the

    cable(s) offered are of new manufacturers. This is to ensure that the manufacturer is qualified for

    supplying cables as per the specifications and associated standards.

  • 8/13/2019 0648-LMSPowerCableHandbk_0

    34/142

    db k f d d bl |

    Material Code 204-6500

    Manufacturer ABC

    Country THAILAND

    Applied standard, publication number and year IEC 60840

    Rated voltage 115 kV

    Outline drawing number (to be attached) HVMAC-O5-155

    Conrm to attach type test reports of the cable with similar design(yes or no)

    YES

    Conrm to attach the detail of water penetration test (yes or no) YES

    Copper conductor

    Applied standard, publication number and year IEC 60228

    Volume conductivity at 20C, minimum IACS 100 %

    Number of wires 53 (minimum)

    Number of layers 4

    Wire diameter (with tolerance) 4.47 1% mm

    Conductor temper (anneal, hard-drawn, etc.) ANNEALED

    Material Code 204-6500

    Lay ratio of the outer layer 10

    Direction of lay of the outer layer LEFT- HAND

    Nominal cross-sectional area 788 mm2

    Stranding (concentric, compress or compact) COMPACT

    Overall diameter 34 mm

    Tolerance of overall diameter 1%

    Weight 14,000 kg/km

    Maximum dc resistance at 20C 0.221/km

    Conductor screen

    Material SEMI-CONDUCTIVE

    Volume resistivity, maximum

    At room temperature, .........C 1*104.cm

    At 90C 1*105.cm

    Thickness

    Average 1.5 mm

    Minimum 1.2 mm

    Table 4: Sample of Proposed Technical Data for High Voltage XLPE Copper Cable

  • 8/13/2019 0648-LMSPowerCableHandbk_0

    35/142

    21 | H db k f U d d P C bl

    Figure 4 : Cable Drawing

  • 8/13/2019 0648-LMSPowerCableHandbk_0

    36/142

    db k f d d bl |

    2.4 Guideline for Bid Evaluation

    The bid evaluation process is very important. All bids shall be scrutinized by the Evaluation Committee.

    Only those bids which are complete in terms of data and information shall be evaluated. This process

    takes a lot of time. It is recommended to make a request for more information in a limited period. sothat it will not delay the delivery schedule and the whole project. Usually, bids are evaluated based on

    the following criteria and priorities.

    2.4.1 Type Test report

    As the top priority, type test report should be assessed first. The proposed cable should pass all the

    type tests according to the reference standard as specified in the specifications. Otherwise, the bid

    shall be rejected immediately, and there is no need to review other documents.

    Manufacturers may not usually have the type test report for cables of the same size, design and

    rating as the proposed cables. There is, however, no need to do type test for all sizes and ratings

    of the cables and in such a case, the type test report of an identical cable may be acceptable on the

    following conditions.

    Once the type tests on cable(s) of specific cross-section(s), rated voltage and construction have

    been successfully performed and cleared/passed, the same type approval shall be considered

    valid for cables of other cross-sections, rated voltages and constructions as long as all of the

    following conditions are met:

    The voltage group is not higher than that of the tested cable(s).1.

    The conductor cross-section is not larger than that of the tested cable(s).2.

    The cable has the same or similar construction to that of the tested cable(s).3.

    The calculated nominal electrical stress at cable conductor screen does not exceed the4.

    electrical stress at cable conductor screen of the tested cable(s) by more than 10%.

    The calculated nominal electrical stress at cable insulation screen does not exceed the5.

    electrical stress at cable insulation screen of the tested cable(s).

    The type test on cables of different voltage ratings and conductor cross-sectional areas are required

    if these cables are of different materials and/or have been produced using different manufacturing

    processes.

  • 8/13/2019 0648-LMSPowerCableHandbk_0

    37/142

    23 | H db k f U d d P C bl

    Repetition of ageing test on pieces of a complete cable to check the compatibility of materials may

    be required in the following condition: The combination of materials applied over the screened

    core is different from that of the cable on which the type tests have been successfully carried

    out.

    2.4.2 Proposed technical data

    After the type test report has been scrutinized and found in compliance with the specifications,

    the next step is to review the proposed technical data provided by the supplier.

    This data is also important because it provides the key details of the proposed cable, that are cable

    construction, physical & electrical characteristics, materials applied and packing details.

    If the proposed technical data is not in compliance with the specifications, the bid will be rejected

    unless explanation is given in a deviation form. In case, some of proposed technical data has not

    been asked or specified clearly in the specifications, it could be accepted, provided that it does not

    have implications on the installation, rating and life time of the cable.

    2.4.3 Deviation form

    The Deviation Form clearly describes the characteristics of the proposed cable that are different

    from the specifications. If there are any major deviations, the proposed cable shall be rejected.

    In the event of minor deviations, the decision shall be made based on certain key factors, such as

    effect on installation, rating and life span of the cable.

    2.4.4 Drawings

    Drawings are required to allow the committee members understand the detailed construction and

    characteristics of the proposed cable.

    Drawings containing all information required shall be attached with the bid. Drawings and

    the proposed technical data should be evaluated together. If there are any major deviations, the

    proposed cable shall be rejected. In the event of minor deviation(s), the related departments shall

    be consulted and the decision shall be made based on the likely impact on installation, capacity

    and life span of the cable.

  • 8/13/2019 0648-LMSPowerCableHandbk_0

    38/142

    db k f d d bl |

    2.4.5 Reference list of supply and field experience

    Sometimes, one supplier offers two options of cables, one from a reputable manufacturer and

    the other from an inexperienced manufacturer whose price is lower than that of the former

    manufacturer. In this case, a reference list of supply field experience is needed. Some utilitiesmay make a trip to visit the factory of the new manufacturers to make sure they are qualified.

    If necessary, it is recommended that utilities make a special requirement for reference list of

    supply field experience of the proposed cable manufacturer in their specification; for example, a

    specific number and year of supply of the proposed cable(s) to other countries. Another solution

    to purchase from the new manufacturer is called trial contract which the utility can specify in

    the tenders condition to purchase not more than 10% of the tender quantity and to purchase the

    balanced quantity from the fully comply tenders condition bidder.

    2.5 Conclusion

    The bid evaluation process and documents required of each LMS utility may be similar. However,

    it takes a lot of time to get through the process. To complete the evaluation process in a short period

    of time, all required documents and data to be included in the bid shall be clearly specified in the

    specifications. Also, the Evaluation Committee shall be represented by qualified personnel.

    It is also recommended to perform separate evaluation if proposed cables have different construction

    characteristics and/or made of different materials.

  • 8/13/2019 0648-LMSPowerCableHandbk_0

    39/142

    25 | H db k f U d d P C bl

    Cable Manufacturing Inspection

    3.1 Introduction

    After the procurement contract for underground cables is signed, several processes need to be verified

    to ensure that cables comply with the specifications and conditions specified in the contract. Drawings

    shall be provided for approval.

    If necessary, the test method shall be, by the agreement between the purchaser and the manufacturer,

    proposed by the manufacturer and approved by the utility. Representatives from the utility, who are

    appointed based on experience in various aspects, such as specification handling, installation, testing,

    maintenance and purchasing, shall inspect the production of cables at the factory.

    3.2 Objective

    The inspection of cable manufacturing processes is required to ensure all processes run according to

    contractual requirements. If any processes are found not conforming to the reference standard and

    specifications, the Inspection Committee shall reserve the right to suspend the production and resolve

    all issues before restarting the production line.

    This chapter describes the cable manufacturing processes and testing, which includes partial discharge

    test and high voltage test. A diligent inspection of cable manufacturing processes is fundamental to

    ensuring satisfactory quality of cables and operating life of at least 25 years.

    3.3 Inspection Committee Management

    Each utility may have different practices and regulations depending on their own policies. This proven

    practice is very useful as it can prevent introduction of poor cables in the service. It also has a track record

    of success in a utility that is responsible for distributing electricity in capital and other main cities.

    After the contract is signed, an Inspection Committee should be approved by the top management. The

    committee members will be selected from the related departments, such as:

    Chapter 3

  • 8/13/2019 0648-LMSPowerCableHandbk_0

    40/142

    db k f d d bl |

    Electrical Engineering Department: The department responsible for specification or term of

    reference (TOR).

    Installation and Construction Department: The department with field experience in installation

    and construction of the cables and their accessories.

    Testing Division or Maintenance Department: The departments with experience in testing and

    preventive maintenance of cables.

    Purchasing or Contract Department: The department that controls all the related documents --

    quotation, technical and commercial condition agreement and the approval drawings.

    All engineers and technicians represented in the production Inspection Committee will be given theapproval drawings and the related correspondence for their references before they go witnessing the

    cable production line and testing.

    The supplier shall provide free access to the production facilities and shall satisfy the representatives

    that the material and equipment are in accordance with the specifications and the contract.

    In the event of a disagreement or dispute, for example, if either the contract details are not clear or the

    supplier would like an exception to be made, the issues should be discussed with the top management.

    The meeting with the top management should keep the interests of the utility as the main focal point

    while deciding on such disputed matters. This should be considered as a standard practice.

    3.4 Manufacturing Process Inspection

    This section describes manufacturing process of extruded-dielectric cables, which are used nowadays.

    Once the production of cables starts, the Manufacturing Inspection Committee will be requested to

    visit the factory and inspect the production line of cables. This is to make sure that manufacturing is

    according to the specifications in the contract.

    The manufacturing process begins by making copper wires and then stranding the conductor. Stranding

    is performed using the conventional method regardless of whether the conductor is concentric, round,

    compressed, compact, or segmental, and with or without strand blocking. The stranded conductor is

    reeled onto a drum, which is placed into its position on the extrusion line. Then the drum becomes the

    payoff reel or the first subsystem in a series of subsystems that comprise the extrusion process.

  • 8/13/2019 0648-LMSPowerCableHandbk_0

    41/142

    27 | H db k f U d d P C bl

    Other subsystems (not all required for all insulation types) are:

    Accumulator: Provides in-line conductor time for changing reels and welding the conductor for

    continuous extruder operation.

    Conductor preheating: It shortens the curing time by 20-60% depending on conductor size,

    consequently increasing the line speed and plant production.

    Compound Handling Subsystem; Stores, dries, and feeds the compound into the extruders and,

    in some cases, incorporates in-line inspection.

    Extruder: The polymer materials are supplied mixed with additives and cross-linking catalysts,

    and are heated to a plastic state. The extruder screw compresses the material and forces itthrough a fine mesh screen into the crosshead through which the conductor travels.

    Crosshead: In a true-triple extrusion process, one crosshead contains the extruder for the

    insulation and the two semiconducting layers. The three layers are formed onto the conductor

    simultaneously through their respective dies. This special process will prevent the impurity such

    as moisture, dust or any pollution particles from penetrating the insulation layer

    Vulcanizing Tube: It provides the pressure and temperature required for the cross-linking process

    used for XLPE and EPR (Ethylene Propylene Rubber) insulations.

    Cooling Tubes: It provide a carefully controlled cooling zone following the cross-linking process

    for XLPE or EPR.

    Traction Units: The capstan and caterpillar maintain the proper line tension required for catenary

    vulcanizing lines.

    Control Unit: It monitors and controls the temperature and pressure, and provides synchronized

    operation between the line speed and the extruder screw speed.

    Take-Up: This final step reels completed cable core onto a drum and hauls the drum away for

    subsequent processes in cable assembly.

  • 8/13/2019 0648-LMSPowerCableHandbk_0

    42/142

    db k f d d bl |

    Figure 5 : Schematic Diagram of Extrusion Line

    Of the three insulation types, only PE doesnt require curing tube since there is no cross-linking of the

    polymer. After the insulation and extrusion of the two semi-conducting layers onto the conductor, the

    line passes through a controlled cooling chamber (frequently a closed, pressurized tube) before being

    reeled on a take-up drum.

    Dry-Cure Systems: The radiant dry-cure system, as opposed to the steam-cure system, features

    independent control of pressure and temperature. This system uses an inert gas, such as nitrogen, as

    the pressurizing medium. Pressure prevents the premature release of the volatile curing agents. The

    temperature is maintained by an electrically heated curing tube. Heat is transferred from the tube to

    the cable by radiation.

    In the gas-cure system, both pressure and temperature are provided by a high-pressure, nitrogen

    circulating system. This system circulates nitrogen through a curing tube, then through a heat

    exchanger and finally back to the curing tube. In the long-land die-curing system, the extruder die is

    50-66 ft (15-20 m) long and the required temperature and pressure are maintained within the die, which

    serves as the curing tube. Because the die is full and under high pressure, there is little opportunity for

    gravity to pull the extruder off the center.

    Copper Wire Making Process

    Conductor Making Process

    Extrusion Line

    Cleaning

    Cleaning

    Drawing Reducing

    Stranding 1 Stranding 2 Stranding 3 Tractive

    Dio

    monitor

    Preheat Corss Head

    for 3 layer

    extrusion

    Cooling Monitor Electrotechnical

    monitor

    Compound

    Pay off

    Pay off

    Pay off

    Take up

    (Conductor)

    Take up

    (Copper wire)

    Length

    Counter

    Take up

  • 8/13/2019 0648-LMSPowerCableHandbk_0

    43/142

    29 | H db k f U d d P C bl

    Cooling:Opinions vary as to which is the best method of cooling. Some manufactures believe

    that even the driest cables have some residual moisture that cannot be reduced. They claim that the

    moisture is not from the cooling water, but rather is a by-product of the curing process. Others claim

    that water cooling shocks the insulation and sets up mechanical stresses which, in turn, intensify the

    shrink-back phenomenon. Dry-cooling methods use gas or silicone-oil circulating systems. It is in the

    cooling system that cables release volatile by-products of cross-linking, which must be carried away.

    The cable continues to de-gas for about three weeks.

    Without de-gassing, cable outer sheath may swell when subject to high temperature in tropical climate

    of LMS, then the manufacturer or contractor should take response to release all generated gas by

    pumping machine until the cable resume as standard specification requirement before installation.

    Hermetic Sealing:The industry practice is that if the cable is to be installed in a wet environment

    where moisture ingress through the jacket is probable, the cable should be hermetically sealed. This is

    to prevent moisture ingress and initiated treeing under voltage stress. The types of hermetic sealing in

    common use are lead sheath, corrugated aluminum or copper sheath, and metal laminates.

    3.5 Factory Acceptance Tests

    When the production is finished, the cable is ready to undergo routine and special tests required

    by the customer -- the utility. The routine and special tests witnessed by the Inspection Committee

    are called Factory Acceptance Tests or FAT. The Inspection Committee will witness at least the

    following tests.

    Testing Procedure

    Routine tests

    Partial discharge test:1. The partial discharge test shall be carried out in accordance with

    IEC 60885-3, except that the sensitivity as defined in IEC 60885-3 shall be 10 pC or less.

    The test voltage shall be raised gradually to hold at 1.75 Uo for 10s and then slowly reduced

    to 1.5 Uo. The magnitude of the discharge at 1.5 Uo shall not exceed 10 pC. Values of the test

    voltage for the standard rated voltages are given below.

  • 8/13/2019 0648-LMSPowerCableHandbk_0

    44/142

    db k f d d bl |

    Voltage test:2. The voltage test shall be made at ambient temperature using an alternating

    test voltage at power frequency. The test voltage -- between the conductor and metallic

    screen/sheath -- shall be raised gradually to the specified value and held there for 30

    minutes. The test voltage shall be 2.5 Uo. There will be no breakdown of the insulation.

    The voltage test values are shown below.

    Rated voltage U

    kV22 - 24 45 - 47 60 - 69 110 - 115 132 - 138 150 - 161

    Rated voltage Uo

    kV12 26 36 64 76 87

    Test voltage 2.5 Uo

    kV30 65 90 160 190 218

    Rated voltage U

    kV22 - 24 45 - 47 60 - 69 110 - 115 132 - 138 150 - 161

    Rated voltage Uo

    kV12 26 36 64 76 87

    First raised voltage 1.75

    Uo kV

    21 45.5 63 112 133 152.3

    Test voltage 1.5 Uo

    kV18 39 54 96 114 131

    Electrical test on non-metallic sheath3.

    If required in contract, the non-metallic sheath shall be subject to the routine electrical test

    as specified in IEC 60229.

    Special tests

    Special tests shall be done on the cables for about 10% of total drums.

    1. Construction and dimension check: Construction and dimension of each layer shall be

    checked. The test method shall be in accordance with clause 8 of IEC 60811-1-1.

    Table 6: Voltage Test

    Table 5 Partial Discharge Test

  • 8/13/2019 0648-LMSPowerCableHandbk_0

    45/142

    31 | H db k f U d d P C bl

    Requirement for insulation

    The lowest measured thickness at any point shall not fall below 90% of the nominal

    thickness:

    Tmin 0.9 Tn

    Additionally: (Tmax

    - Tmin

    )/ Tmax

    0.15

    Where Tmax

    : The maximum thickness (mm)

    Tmin

    : The minimum thickness (mm)

    Tn : The nominal thickness (mm)

    Note: Tmaxand Tminare measured at the same cross-section of the sample. Thickness ofthe semi-conducting screen on the conductor and over the insulation shall not be included

    in the thickness of the insulation.

    Requirement for the non-metallic sheath

    The lowest measured thickness shall not fall below 85 % of the nominal thickness by

    more than 0.1 mm.

    Tmin 0.85 Tn- 0.1

    Where Tmin

    : The minimum thickness (mm)

    Tn : The nominal thickness (mm)

    2. Conductor resistance test: The complete cable length, or a sample thereof, shall be

    placed in a test room, which shall be maintained at a reasonably constant temperature

    for at least 12 hours before the test. In case of a doubt that the conductor temperature is

    not the same as the room temperature, the resistance shall be measured after the cable

    has been in the test room for 24 hours. Alternatively, the resistance can be measured on

    a sample of conductor conditioned for at least 1 hour in a temperature-controlled liquid

    bath. The D.C. resistance of the conductor shall be corrected to a temperature of 20C and

    1 km length in accordance with the formulae and factors given in IEC 60228. The D.C.

    resistance of each conductor at 20C shall not exceed the appropriate maximum value

    specified in IEC 60228, if applicable.

  • 8/13/2019 0648-LMSPowerCableHandbk_0

    46/142

    db k f d d bl |

    For example, the maximum D.C. resistance of conductor at 20C for stranded copper

    conductor size 70, 150, 240, 400, 800, 1000 and 1200 mm 2are 0.268, 0.124, 0.0754,

    0.0470, 0.0221, 0.0176 and 0.0151 /km respectively.

    3. Hot set test of insulation: The test piece shall be suspended in an oven and weightsattached to the bottom jaws to exert a force as specified in the applicable standard. After

    15 min in the oven at the specified temperature, the distance between the marker lines

    shall be measured and the percentage elongation shall be calculated. If the oven does

    not have a window and the oven door has to be opened to make the measurement, the

    measurement shall be made not more than 30 seconds after opening the door. In case of

    a dispute, the test shall be carried out in an oven with a window and the measurement

    made without opening the door.

    The tensile force shall then be removed from the test piece (by cutting the test piece at

    the lower grip), and the cable piece shall be left to recover for 5 minutes at the specified

    temperature. The test piece shall then be removed from the oven and allowed to cool

    slowly to the ambient temperature, after which, the distance between the marker-lines

    shall be measured again.

    For the evaluation of results, the median value of the elongation -- derived after 15

    minutes at the specified temperature with the weight attached -- shall not exceed the

    value specified in the standard. And the median value of the distance between the marker

    lines -- after removing test piece from the oven and allowing it to get cool -- should not

    increase compared to the value before inserting the piece in the oven by more than the

    percentage specified in the standard.

    4. Capacitance test: The capacitance shall be measured between conductor and metallic

    screen/sheath. The measured value shall not exceed (usually by more than 8%) the

    nominal value declared by the manufacturer.

    3.6 Conclusion

    Usually, utilities have their own inspection committee teams to inspect the production line, and witness

    routine and special tests at the factory. In case the factory is located outside the country, utility may

    send a representative of the Inspection Committee to the factory or hire a third party inspector.

  • 8/13/2019 0648-LMSPowerCableHandbk_0

    47/142

    33 | H db k f U d d P C bl

    Some utilities may have their own inspection forms or special documents to process the comments

    and some corrections during the inspection, such as witness tests, material and construction check,

    discussion, etc. In case of no inspection form, it is necessary for inspection committee to investigate

    the production process and quality control before signing in every document which is usually prepared

    by the factory and make a request for a copy for their reference and every comment to the factory

    should be sent in official paper.

  • 8/13/2019 0648-LMSPowerCableHandbk_0

    48/142

    db k f d d bl |

    Contract Acceptance

    4.1 Introduction

    The purchasing contract includes all commercial conditions and technical requirements. After

    the contract is signed, contract acceptance has to be done to ensure that the quality of the cables

    complies with the contract requirements. This process is also important for utilities to ensure cables

    are delivered as per the contractual delivery period. The contract acceptance becomes a problem when

    the delivered cables do not conform to the contract requirements, such as construction, physical and

    electrical characteristics, or when the cables are damaged during transportation. All such problems

    shall be settled before cables are accepted.

    4.2 Objective

    Usually, the contract acceptance is done by an Acceptance Committee and not by one person or a

    department. The contract acceptance process and procedure may be different for each utility. The

    objective of this chapter is to share the experience in preventing and solving problems faced during

    contract acceptance process. Various scenarios have been explained as a guide to solving problem.

    4.3 Acceptance Committee Management

    This follows the same procedure as mentioned for the Production Inspection Committee in Chapter 3.

    The Acceptance Committee should be approved by the upper management after the contract is signed.

    The members will be selected from the related departments, such as: Maintenance Department which

    is responsible for cable maintenance and repair.

    Installation and Construction Department that has field experience in installation and construction

    of the cables and their accessories.

    Testing Division which is experienced in testing and preventive maintenance of cables.

    Purchasing or Contract Department that deals with all the related document like quotation,

    technical and commercial agreement, and approval drawings.

    Chapter 4

  • 8/13/2019 0648-LMSPowerCableHandbk_0

    49/142

    35 | H db k f U d d P C bl

    All engineers and technicians who are members of the Acceptance Committee will be given the

    approval drawings and the related correspondence for their reference. They will use these documents

    during sampling of the delivered cables for testing. The supplier shall submit the routine test report

    and special report of all cables to the utility before the shipment of the cables. After that the routine

    tests and special reports will be sent to the Acceptance Committee for approval.

    In the event of a disagreement or dispute, for example, if the contract details are not clear or the

    supplier would like an exception to be made, the issue should be presented at a meeting with the

    top management. During discussions on the dispute, the meeting participants should address the

    disadvantages and advantages to the utility as the main focal point. This convention should be

    considered as a standard practice.

    4.4 Acceptance Process

    Practically, the contract acceptance process comprises three steps. The first step is visual inspection.

    The second step is routine and special reports verification and the third is acceptance test or

    sampling test by utility. Routine and special reports and acceptance test report shall be reviewed

    by the Acceptance Committee. The detailed specification with approval drawings shall be used as a

    reference. Here is a practical guideline for contract acceptance process.

    The delivered cables shall be accepted provided that all three following conditions are met:

    4.4.1 Visual Inspection

    After the delivery of cables, the Acceptance Committee will conduct a visual inspection

    at the site to check the quantity of the cables (according to the invoice of the supplier)

    and any damages that may have occurred during transportation. If any damaged cable is

    found, the Committee will ask the supplier to replace it with a new one.

    During visual inspection, the Committee will also randomly select the quantity of cables

    as stated in the contract for acceptance tests by utility itself. The quantity typically does

    not exceed 3 meters per drum and not in exceed of 3 drums due to the constraints of cost,

    time and laboratory capacity.

  • 8/13/2019 0648-LMSPowerCableHandbk_0

    50/142

    db k f d d bl |

    4.4.2 Routine and Special Tests Verification

    The routine and special tests shall be carried out in order to determine whether the cable

    complies with the specification. The specification includes the required tests. The routine

    and special test reports shall be submitted to the utility before shipment. If the test resultof any cable does not comply with the specification, the cable shall be rejected. Samples

    of routine and special tests report are shown in Table 7.

    As minimum, the following acceptance tests should be done at the utilitys laboratory.

    Special tests

    a) Construction and dimension check

    b) Conductor resistance test

    c) Hot set test of insulation

    d) Capacitance test

    Routine test

    a) Partial discharge test

    b) Voltage test

    c) Electrical test on non-metallic sheath

  • 8/13/2019 0648-LMSPowerCableHandbk_0

    51/142

    37 | H db k f U d d P C bl

    Routine and Special Tests Report

    Customer: Drum No.:

    Cable Type: 115 kV XLPE Copper cable, 800 mm2 Sample Condition:

    Contract No.: Ambient Temp.:

    Reference Standard: Manufacturer:

    Test Items Unit Specification Test Results

    Routine testsPartial discharge test at 96 kV1.AC. High Voltage Test at 160 kV for 30 minutes2.Electrical test on non-metallic sheath at 15 kV3.

    pC--

    10 (Max)No breakdownNo breakdown

    0.5No breakdownNo breakdown

    Special tests1. Conductor examination & check of dimensions

    - Material- Design type- Number of wires- Diameter of conductor

    2. Separator tape

    - Material

    3. Conductor screen

    - Material- Average thickness- Minimum thickness

    4. Insulation

    - Material- Average thickness- Minimum thickness- Diameter over insulation

    5. Hot set test

    - Elongation under load- Elongation after cooling

    6. Insulation screen

    - Material- Average thickness- Minimum thickness

    7. Synthetic water blocking tape

    - Material- Thickness- Width

    -

    --mm

    -

    -mmmm

    -mmmmmm

    %%

    mmmm

    -mm

    Plain annealed copper

    Compact circular strand53 (Min)34.0 1%

    Semi-conductive tape

    Semi-conductive XLPE1.51.2

    XLPE16

    14.469-72

    175 (Max)15 (Max)

    Semi-conductive XLPE1.51.2

    Semi-conductive0.4540

    Plain annealed copper

    Compact circular strand6133.9

    Semi-conductive tape

    Semi-conductive XLPE1.91.7

    XLPE16.916.270

    750.8

    Semi-conductive XLPE1.81.7

    Semi-conductive0.4540

    4.4.3 Acceptance Tests

    It is recommended that even though the supplier performs the entire routine and special

    tests on the cables, the utility should also perform sample tests for its own v


Recommended