1 Carbon Reduction Strategies at the University of East Anglia CRed Carbon Reduction Rotary District 9700 Group Study Exchange 9 th May 2008 Energy and Climate Change Tour N.K. Tovey ( 杜杜杜 ) M.A, PhD, CEng, MICE, CEnv Н.К.Тови М.А., д-р технических наук Energy Science Director CRed Project Recipient of James Watt Gold Medal 2007
Transcript
Page 1: 1 Carbon Reduction Strategies at the University of East Anglia CRed Carbon Reduction Rotary District 9700 Group Study Exchange 9 th May 2008 Energy and.

1

Carbon Reduction Strategies at the University of East Anglia

CRedCarbon Reduction

Rotary District 9700Group Study Exchange

9th May 2008Energy and Climate Change Tour

N.K. Tovey (杜伟贤 ) M.A, PhD, CEng, MICE, CEnv

Н.К.Тови М.А., д-р технических наук

Energy Science Director CRed Project

HSBC Director of Low Carbon Innovation

Recipient of James Watt Gold Medal2007

Page 2: 1 Carbon Reduction Strategies at the University of East Anglia CRed Carbon Reduction Rotary District 9700 Group Study Exchange 9 th May 2008 Energy and.

2

Welcome to the University of East Anglia

• School of Environmental Sciences• A 5** Research department• Rated in top 5 Environmental Sciences

Department in world• Rated Excellent in Teaching• Many World Renowned Centres

– Tyndall Centre, Climate Research Unit– CRed – Carbon Reduction Project– etc.– Zuckerman Institute for Connective

Environmental Research (ZICER)

Page 3: 1 Carbon Reduction Strategies at the University of East Anglia CRed Carbon Reduction Rotary District 9700 Group Study Exchange 9 th May 2008 Energy and.

3

Original buildings

Teaching wall

Library

Student residences

Page 4: 1 Carbon Reduction Strategies at the University of East Anglia CRed Carbon Reduction Rotary District 9700 Group Study Exchange 9 th May 2008 Energy and.

4

Nelson Court

Constable Terrace

Page 5: 1 Carbon Reduction Strategies at the University of East Anglia CRed Carbon Reduction Rotary District 9700 Group Study Exchange 9 th May 2008 Energy and.

5

Low Energy Educational BuildingsDüşük Enerjili Eğitim Binaları

Elizabeth Fry Building

Elizabeth Fry Binası

ZICER

Nursing and Midwifery

Hemşirelik ve Ebelik Okulu

Medical SchoolTıp Fakültesi Binası

Medical School Phase 2 Tıp Fakültesi Binası 2. Evre

Page 6: 1 Carbon Reduction Strategies at the University of East Anglia CRed Carbon Reduction Rotary District 9700 Group Study Exchange 9 th May 2008 Energy and.

6

The Elizabeth Fry Building 1994Elizabeth Fry Binası - 1994

Cost ~6% more but has heating requirement ~20% of average building at time.Significantly outperforms even latest Building Regulations.Runs on a single domestic sized central heating boiler.

Maliyeti ~%6 daha fazla olsada, ısınma ihtiyacı zamanın ortalama binalarının ~%20’si.En son Bina Yönetmeliklerini bile büyük ölçüde aşmaktadır.

Tek bir ev tipi merkezi ısıtma kazanı ile çalışmaktadır.

Page 7: 1 Carbon Reduction Strategies at the University of East Anglia CRed Carbon Reduction Rotary District 9700 Group Study Exchange 9 th May 2008 Energy and.

7

Conservation: management improvements –

Careful Monitoring and Analysis can reduce energy consumption.

0

50

100

150

200

250

Elizabeth Fry Low Average

kWh/

m2/

yr

gas

electricity

thermal comfort +28%User Satisfaction

noise +26%

lighting +25%

air quality +36%

A Low Energy Building is also a better place to work in

Page 8: 1 Carbon Reduction Strategies at the University of East Anglia CRed Carbon Reduction Rotary District 9700 Group Study Exchange 9 th May 2008 Energy and.

8

ZICER Building

Heating Energy consumption as new in 2003 was reduced by further 50% by careful record keeping, management techniques and an adaptive approach to control.

Incorporates 34 kW of Solar Panels on top floor

Low Energy Building of the Year Award 2005 awarded by the Carbon Trust.

Page 9: 1 Carbon Reduction Strategies at the University of East Anglia CRed Carbon Reduction Rotary District 9700 Group Study Exchange 9 th May 2008 Energy and.

9

The ZICER Building - Description

• Four storeys high and a basement• Total floor area of 2860 sq.m• Two construction types

Main part of the building

• High in thermal mass • Air tight• High insulation standards • Triple glazing with low emissivity

Structural Engineers: Whitby Bird

Page 10: 1 Carbon Reduction Strategies at the University of East Anglia CRed Carbon Reduction Rotary District 9700 Group Study Exchange 9 th May 2008 Energy and.

10

The ground floor open plan office

The first floor open plan office

The first floor cellular offices

Page 11: 1 Carbon Reduction Strategies at the University of East Anglia CRed Carbon Reduction Rotary District 9700 Group Study Exchange 9 th May 2008 Energy and.

11Air enters the internal

occupied space

Return stale air is extracted from each floor

Incoming air into

the AHU

Regenerative heat exchanger

Filter Heater

The air passes through hollow

cores in the ceiling slabs

The return air passes through the heat

exchanger

Out of the building

Operation of the Main Building• Mechanically ventilated that utilizes hollow core ceiling slabs as supply air ducts to the space

Space for future chilling

Recovers 87% of Ventilation Heat Requirement.

Page 12: 1 Carbon Reduction Strategies at the University of East Anglia CRed Carbon Reduction Rotary District 9700 Group Study Exchange 9 th May 2008 Energy and.

12

Importance of the Hollow Core Ceiling Slabs

The concrete hollow core ceiling slabs are used to store heat and coolness at different times of the year to provide comfortable and stable temperatures

Cold air

Cold air

Draws out the heat accumulated during

the dayCools the slabs to act as a cool store the following day

Summer night

night ventilation/ free cooling

Page 13: 1 Carbon Reduction Strategies at the University of East Anglia CRed Carbon Reduction Rotary District 9700 Group Study Exchange 9 th May 2008 Energy and.

13

Importance of the Hollow Core Ceiling Slabs

The concrete hollow core ceiling slabs are used to store heat and coolness at different times of the year to provide comfortable and stable temperatures

Warm air

Warm air

Pre-cools the air before entering the

occupied space

The concrete absorbs and stores

the heat – like a radiator in reverse

Summer day

Page 14: 1 Carbon Reduction Strategies at the University of East Anglia CRed Carbon Reduction Rotary District 9700 Group Study Exchange 9 th May 2008 Energy and.

14

Importance of the Hollow Core Ceiling Slabs

The concrete hollow core ceiling slabs are used to store heat and coolness at different times of the year to provide comfortable and stable temperatures

Winter Day

The concrete slabs absorbs and

store heat

Heat is transferred to the air before entering

the room

Winter day

Page 15: 1 Carbon Reduction Strategies at the University of East Anglia CRed Carbon Reduction Rotary District 9700 Group Study Exchange 9 th May 2008 Energy and.

15

Importance of the Hollow Core Ceiling Slabs

The concrete hollow core ceiling slabs are used to store heat and coolness at different times of the year to provide comfortable and stable temperatures

Winter NightWhen the internal air temperature drops, heat stored in the

concrete is emitted back into the room

Winter night

Page 16: 1 Carbon Reduction Strategies at the University of East Anglia CRed Carbon Reduction Rotary District 9700 Group Study Exchange 9 th May 2008 Energy and.

16

The Energy Signature from the Old and the New Heating Strategies

0

200

400

600

800

1000

-4 -2 0 2 4 6 8 10 12 14 16 18

Mean external temperature over a 24 hour period (degrees C)

Hea

tin

g a

nd

ho

t-w

ate

r

con

sum

pti

on

(k

Wh

/24

ho

ur

per

iod

)

New Heating Strategy Original Heating Strategy

350

The space heating consumption has reduced by 57%

Good Management has reduced Energy Requirements

Page 17: 1 Carbon Reduction Strategies at the University of East Anglia CRed Carbon Reduction Rotary District 9700 Group Study Exchange 9 th May 2008 Energy and.

17

• Top floor is an exhibition area – also to promote PV

• Windows are semi transparent

• Mono-crystalline PV on roof ~ 27 kW in 10 arrays

• Poly- crystalline on façade ~ 6/7 kW in 3 arrays

ZICER Building

Photo shows only part of top

Floor

Page 18: 1 Carbon Reduction Strategies at the University of East Anglia CRed Carbon Reduction Rotary District 9700 Group Study Exchange 9 th May 2008 Energy and.

18

Arrangement of Cells on Facade

Individual cells are connected horizontally

As shadow covers one column all cells are inactive

If individual cells are connected vertically, only those cells actually in shadow are affected.

Page 19: 1 Carbon Reduction Strategies at the University of East Anglia CRed Carbon Reduction Rotary District 9700 Group Study Exchange 9 th May 2008 Energy and.

19

Use of PV generated energy

Sometimes electricity is exportedInverters are only 91% efficient

Most use is for computers

DC power packs are inefficient typically less than 60% efficientNeed an integrated approach

Peak output is 34 kW

Page 20: 1 Carbon Reduction Strategies at the University of East Anglia CRed Carbon Reduction Rotary District 9700 Group Study Exchange 9 th May 2008 Energy and.

20

Actual Situation excluding Grant

Actual Situation with Grant

Discount rate 3% 5% 7% 3% 5% 7%

Unit energy cost per kWh (£) 1.29 1.58 1.88 0.84 1.02 1.22

Avoided cost exc. the Grant

Avoided Costs with Grant

Discount rate 3% 5% 7% 3% 5% 7%

Unit energy cost per kWh (£) 0.57 0.70 0.83 0.12 0.14 0.16

Grant was ~ £172 000 out of a total of ~ £480 000

Performance of PV cells on ZICER

Cost of Generated Electricity

Page 21: 1 Carbon Reduction Strategies at the University of East Anglia CRed Carbon Reduction Rotary District 9700 Group Study Exchange 9 th May 2008 Energy and.

21

EngineGenerator

36% Electricity

50% Heat

GAS

Engine heat Exchanger

Exhaust Heat

Exchanger

11% Flue Losses3% Radiation Losses

86%

efficient

Localised generation makes use of waste heat.

Reduces conversion losses significantly

Conversion efficiency improvements – Building Scale CHP

61% Flue Losses

36%

efficient

Page 22: 1 Carbon Reduction Strategies at the University of East Anglia CRed Carbon Reduction Rotary District 9700 Group Study Exchange 9 th May 2008 Energy and.

22

Conversion efficiency improvements

1997/98 electricity gas oil Total

MWh 19895 35148 33

Emission factor kg/kWh 0.46 0.186 0.277

Carbon dioxide Tonnes 9152 6538 9 15699

Electricity Heat

1999/2000

Total site

CHP generation

export import boilers CHP oil total

MWh 20437 15630 977 5783 14510 28263 923Emission

factorkg/kWh -0.46 0.46 0.186 0.186 0.277

CO2 Tonnes -449 2660 2699 5257 256 10422

Before installation

After installation

This represents a 33% saving in carbon dioxide

Page 23: 1 Carbon Reduction Strategies at the University of East Anglia CRed Carbon Reduction Rotary District 9700 Group Study Exchange 9 th May 2008 Energy and.

23

Conversion efficiency improvements

Load Factor of CHP Plant at UEA

Demand for Heat is low in summer: plant cannot be used effectivelyMore electricity could be generated in summer

Page 24: 1 Carbon Reduction Strategies at the University of East Anglia CRed Carbon Reduction Rotary District 9700 Group Study Exchange 9 th May 2008 Energy and.

24

Conversion efficiency improvements

Condenser

Evaporator

Throttle Valve

Heat rejected

Heat extracted for cooling

High TemperatureHigh Pressure

Low TemperatureLow Pressure

Heat from external source

Absorber

Desorber

Heat Exchanger

W ~ 0

Normal Chilling

Compressor

Adsorption Chilling

19

Page 25: 1 Carbon Reduction Strategies at the University of East Anglia CRed Carbon Reduction Rotary District 9700 Group Study Exchange 9 th May 2008 Energy and.

25

A 1 MW Adsorption chiller

1 MW 吸附冷却器

• Reduces electricity demand in summer

• Increases electricity generated locally

• Saves ~500 tonnes Carbon Dioxide annually

• Uses Waste Heat from CHP

• provides most of chilling requirements in summer

•从 CHP 中使用废热•在夏天提供绝大部分供冷需要

•减少夏天电耗•增加本地发电量•每年节约 ~500 吨二氧化碳

Page 26: 1 Carbon Reduction Strategies at the University of East Anglia CRed Carbon Reduction Rotary District 9700 Group Study Exchange 9 th May 2008 Energy and.

26

Target Day

Results of the “Big Switch-Off”

With a concerted effort savings of 25% or more are possibleHow can these be translated into long term savings?

Page 27: 1 Carbon Reduction Strategies at the University of East Anglia CRed Carbon Reduction Rotary District 9700 Group Study Exchange 9 th May 2008 Energy and.

27

Conclusions• Buildings built to low energy standards have cost ~ 5% more,

but savings have recouped extra costs in around 5 years.

• Ventilation heat requirements can be large and efficient heat recovery is important.

• Effective adaptive energy management can reduce heating energy requirements in a low energy building by 50% or more.

• Photovoltaic cells need to take account of intended use of electricity use in building to get the optimum value.

• Building scale CHP can reduce carbon emissions significantly

• Adsorption chilling should be included to ensure optimum utilisation of CHP plant, to reduce electricity demand, and allow increased generation of electricity locally.

• Promoting Awareness can result in up to 25% savings

• The Future for UEA: Biomass CHP? Wind Turbines?

Lao Tzu (604-531 BC) Chinese Artist and Taoist philosopher

"If you do not change direction, you may end up where you are heading."

Page 28: 1 Carbon Reduction Strategies at the University of East Anglia CRed Carbon Reduction Rotary District 9700 Group Study Exchange 9 th May 2008 Energy and.

28

WEBSITE cred-uk.org/

This presentation is available from tomorrow at above WEB Site: follow Academic Links

Keith Tovey (杜伟贤 ) Energy Science Director

HSBC Director of Low Carbon Innovation

Carbon Reduction Strategies at the University of East Anglia