SAMSUNG ELECTRONICS Co. LTD.
HQ SE
INSTALLERERVVER. 01- Jan. 2011
ENERGY RECOVERY VENTILATION[ERV Plus]
2
Trainer Profile
• Name :• E-mail :
SAMSUNG ELECTRONICS CO.LTD
3
Contents
SAMSUNG ELECTRONICS CO.LTD
■ ERV + Basics
■ Key Technology
■ Controls & Solution
■ Case Study
■ ERV Line-up
■ Duct design
SAMSUNGERV
SAMSUNGERV
ERV Plus Introduction
5
ERV +
ERV Plus introduction
ERV Plus = ERV(Ventilator) + DX Coil + Humidifier(Option)
6
ERV+ USP
High efficiency of motor
100%100%
1000 CMH
500 CMH
Company D
131%
255%
Samsung
■ Power consumption comparison by models
Capacity Samsung Company D
500 CMH 220W 560W
1000 CMH 510W 670W
7
ERV+ USP
The Slimmest Height & Light Weight
- The slim height makes installation, maintenance
and repair very easy
Div D Company M Company X Company Samsung
Product
Image
Height387mm 317mm 365mm 270mm
100% 82% 97% 71%
Weight96kg 57kg 98kg 62kg
100% 59% 102% 64%
270mm270mm
8
ERV + USP
Simple line up
- ERV PLUS = ERV (Ventilator) + Dx-Coil (Air conditioner) + Humidifier(Optional)
=> Install humidifier to ERV Plus at any time.
D Company M Company X Company Samsung
Line Up
Humidifier ModelNon-Humidifier
Model(Separated Model)
Humidifier ModelNon-Humidifier
Model(Separated Model)
Humidifier ModelNon-Humidifier
Model(Separated Model)
Non-Humidifier Model +
Optional Humidifier Kit
ERV Plus
+
Humidifier Kit
9
ERV+ USP
Composition Spec.
Filter media
Media PP + PET Spun bond
Composition PP + PET Nonwoven
Weight 120g/ ㎡ ± 10%
FrameMaterial PET
Weight 260g/ ㎡ ± 20%
Hot meltMaterial Nylon
Softening point 139 ~ 149 ℃
D companyPre-filter
SamsungHigh Efficiency Medium-filter
■ Classified as high efficiency Medium-filter, while the other is defined as pre-filter
■ Dust spot efficiency is over 70% (based on ASHRAE Std 52.1)
■ Fractional efficiency is over 60% (based on MIL,STD-282)
9
Filter high efficiency
10
ERV+ USP
Class
Standard 52.2Min. Efficiency
Reporting Value
(MERV)
Pre/Medium(EN 779)
HEPA/ULPA(EN1822)
Pre filter
1G 1
2
3G 2
4
5G 3
6
7G 4
8
MediumFilter
9F 5
10
11 F 6
12 F 7
13 F 8
14 F 9
HEPA
15 H 10
16 H 11
17 H 12
18 H 13
19 H 14
ULPA
20 U 15
U 16
U 17
D companyD company
SamsungSamsung Compact Pocket TypeCompact Pocket Type Compact ECO Pocket TypeCompact ECO Pocket Type
HEPAHEPA ULPAULPA
G 35
F 40 / F 45
Compact Pocket TypeCompact Pocket Type
F 50
MF Series
Panel TypePanel Type
MP 35
EP Series
SF Series
10
11
ERV + Basic
Structure of ERV Plus
Damper
Total heat exchanger element
Humidifier (Option)
PCB DX CoilFilter
Return Air
Supply Air
Exhaust Air
Outdoor Air
Access panel
12
ERV + Basic
Schematic diagram of ERV Plus
OA temp. sensor
Return air temp. sensor
Total heat exchanger
EEV
DX coil
Humidifier
Water feed pipe
Gas pipe
ERV Plus
Liquid pipe
Suction air temp. sensor
RHF050KHEA RHF100KHEA
EEV DPF(Q) 1.3 DPF(Q) 2.0
< DX Coil specification>
< EDM type EEV>
RHF050KHEA RHF100KHEA
DX CoilL : 340 mm
2Row x 12 stepL : 644 mm3Row x 14
step
Fin 1.5 FP, Slit
- Max. 1400 step
Eva in temp.sensor
Eva out temp.sensor
13
ERV + Basic
The specification of RHF050KHEA
Classification UnitSamsung
(RHF050KHEA)D (VKM500GAMV1)
Ventilationperformanc
e
Air flow rate
Air flow rate ( ㎥ /h) 500 500
Static pressure
(Pa) 160 180/*160
Power input (W) 220 560
Temp. exchangeefficiency
cooling (%) 70 76
heating (%) 75 76
Enthalpyexchangeefficiency
cooling (%) 60 64
heating (%) 73 67
Outdoor air processing capacity
cooling (KW)5.1
(ERV:1.5)4.71
(ERV:1.91)
heating (KW)6.5
(ERV:2.5)5.58
(ERV:2.38)
Humidifying capacity (kg/h) 2.7 2.7
Sound level extra high (dB) 38.5/* 37.5 38.5/* 37.5
Set size(kg) 61 / * 63 96 /* 102
(mm) 1553*270*1000 1764*387*1214
13
* Including humidifier
14
ERV + Basic
The specification of RHF100KHEA
Classification Unit Samsung (RHF100KHEA) D (VKM100GAMV1)
Ventilationperformance
Air flow rateAir flow rate ( ㎥ /h) 1000 950
Static pressure (Pa) 150 150 / *110
Power input (W) 510 670
Temp. exchangeefficiency
cooling (%) 70 74
heating (%) 75 74
Enthalpyexchangeefficiency
cooling (%) 62 62
heating (%) 75 65
Outdoor air processing capacitycooling (KW)
10.5(ERV:3.4)
9.12(ERV:3.52)
heating (KW)13.2
(ERV:5.2)10.69
(ERV:4.39)
Humidifying capacity (kg/h) 5.4 5.4
Sound level extra high (dB) 40.5/* 39.5 40.5/* 39.5
Set size(kg) 90 / * 93 114 / * 125
(mm) 1763*340*1135 1764*387*1214
14
* Including humidifier
15
ERV + Basic
Psychrometric chart plotting with cooling operation
Total heat exchanger
Heat recovery Cooling
DXCoil
35℃RH 40% 27℃
RH 47%
32.4℃RH 38%
29.5℃RH 50.2%
13.3℃RH 80%
< Example>
Temperature Efficiency Enthalpy Efficiency
100
)()(
)()(
RAtOAt
SAtOAt
10077.537.71
82.627.71
ERV Pluscooling
performance
-5-5 00 55 1010 1515 2020 2525 3030 3535 4040
RARA
SASA
OAOA
Dry bulb (℃)Dry bulb (℃)
2020
4040
6060
8080100100
Ab
solu
te H
um
idit
y (
kg/k
g’)
Ab
solu
te H
um
idit
y (
kg/k
g’)
Enthalpy (
kcal/k
g)
Enthalpy (
kcal/k
g) CoolingCooling
71.7 kJ/Kg
53.77 kJ/Kg
62.82 kJ/Kg
Enthalpy efficiency ratio = 49.5 %
100
)()(
)()(
RAhOAh
SAhOAh
Cooling
16
ERV + Basic
Psychrometric chart plotting with heating operation
Total heat exchanger
Heat recovery heating
DXCoil
10.6℃RH 79%
20℃RH 59%
7℃RH 87%
16.4℃RH 67%
40 ℃RH 12.2 %
< Example>
10061.2091.41
61.206.36
-5-5 00 55 1010 1515 2020 2525 3030 3535 4040
RARA
SASAOAOA
Dry bulb (℃)Dry bulb (℃)
2020
4040
6060
8080100100
Ab
solu
te H
um
idit
y (
kg/k
g’)
Ab
solu
te H
um
idit
y (
kg/k
g’)
Enth
alpy
(kca
l/kg)
Enth
alpy
(kca
l/kg)
36.6 kJ/Kg
41.91 kJ/Kg
Enthalpy efficiency
= 75 %
100)()(
)()(
OAhRAh
OAhSAh
Humidifier
2/1℃
20/15 ℃
29.5℃RH 40%
Humidifying 20.61 kJ/Kg
HeatingHeating
HumidifyingHumidifying
Operation mode
Air flow Damper
Energy recovery(Heat exchange)
By-pass
18
Operation mode
Energy recovery(Heat-Ex) and By-pass ventilation
<Energy recovery mode display> <By-pass mode display>
<Wired remote controller>
Condition
Energy recovery(Heat exchange) |OA temp. –RA temp| >= 5℃
By-pass |OA temp. –RA temp| < 5℃
19
Operation mode
Auto ventilation
-According to OA and Return air temperature, the mode is determined.- The operation mode will be operating during 30 min.
Outdoor air temp. sensor
Return air temp. sensor
20
Operation mode
Clean up operation
Living Room
Toilet
Positive pressure
Switch 17 state Supply air volume Exhaust air volume Air volume difference
On Selected fan mode Silent fan mode Max. 35 %(Turbo and high fan
mode)Off Silent fan mode Selected fan mode
-To make positive or negative pressure of room, supply and exhaust air volume can be different by Clean up operation .
-To avoid toilet odor, more air volume 10 ~ 15% have to supply to make positive pressure of living
21
Operation mode
Outing operation
Operation mode Fan
Energy recovery ventilationOn : 10 min, Off : 50 min
Low
Quite operation
-The fan mode is fixed to the quite mode.
Fan mode RHF050KHEA RHF100KHEA
Turbo 38.5 40.5
High 36 38
Low 32 35
Quite 30 33
22
Operation mode
Energy saving operation
: Energy saving operation is run when all the following conditions are met. 1) One or more ERV units must be connected to MWR-WE10 (without or with indoor unit(s) ) 2) Either the indoor unit or ERV must be ON (if the indoor unit is ON, it must not be FAN mode). 3) ERV must not be in Outing mode 4) ERV external control must not be enabled. 5) ERV must not be in “Centralized” control mode. 6) ERV must not be in “Kitchen Hood” control mode.
NOTE : The sub wired remote controller does not support energy saving mode
23
Operation mode
Set temp >= Out temp : Heat exchange ↑
Heating
22°C
Room temp >= Out temp : Heat exchange ↑
R
S
Cooling
Out temp >= Set temp : Heat exchange ↑
26°C
R
S
Out temp < Set temp : Cool air intake ↑
Default setting temperature : 26°C.User can change it
Default setting temperature : 22°C.User can change it
Out temp < Room temp : Cool air intake ↑
Set temp < Out temp : Warm air intake ↑
Room temp < Out temp : Warm air intake ↑
EnergySaving
R : Room temperature / S : Setting temperature
Out temp >= Room temp : Heat exchange ↑
Energy saving operation
24
Operation mode
Auto operation (DX coil)
Outdoor air temp. sensor
Suction air temp. sensor
Outdoor air temp. sensor
A area
Cooling operation
B area Thermo off (Ventilation operation)
C area
Heating operation
Suction air temp >= auto cooling setting temp.(*25 ℃)
Suction air temp < auto cooling setting temp – Thermo off gap temp.(*25℃ – 10℃*)
* Default value can be changed by wired remote controller (SVC mode)
Set temp. range : Auto cooling set temp. : 15℃ ~ 30℃Thermo off gap temp. : 5℃ ~ 15℃
25
Operation mode
Heating operation (DX coil)
-After working of ventilation mode, cooling and heating mode of DX coli is possible.
Thermo on Thermo off Remark
Cooling Suction air temp >= *Default set temp. Suction air temp <= *Default set temp. –
4℃
*Default cooling set temp. : 25℃
(Set temp range : 15 ~ 30℃)
Heating
Suction air temp <= *Default set temp. + **Compensation
temp. - 6
Suction air temp >= *Default set temp. + **Compensation
temp. - 2
*Default cooling set temp. 22℃
**Compensation temp. : 2, 5 ℃
26
Safety operation
Outdoor Temp Operation Type Intake Discharge Remarks
Above 0℃ Normal Operation On On
0 ℃ > TOA >-5 ℃“A” Type Cyclic Operation Refer to below operation
pattern
Repeated on a regular time basis-5 ℃ > TOA >-10 ℃
“B” Type Cyclic Operation
-10 ℃ > TOA >-15 ℃ Off On
Below -15 ℃ Off Off
‘A’ Type 80min 10min
Both Intake and Discharge On Only Discharge On
80min
Both Intake and Discharge On
10min
Only Discharge On
‘B’ Type 50min 10min
Both Intake and Discharge On Only Discharge On
50min
Both Intake and Discharge On
10min
Only Discharge On
System is capable of self adjustment depending on outdoor temperature to prevent it from condensate on element
Prevention of condensate
27
Fan operation with CO2 sensor
☞ ERV is automatically operated to give fresh air into room by sensing CO2 Level
CO2
Fresh AirCO2
CO2
Fan Speed depending on Co2
density
□ CO2 1200ppm ↑ : Turbo RPM
□ CO2 Density 800ppm ↑ : High
RPM
□ CO2 Density 800ppm ↓ : Low
RPM
Note1. K9 dip switch should be off
position2. In general, above 1000ppm is
regarded as pollution
Refresh system - CO2 Sensor( option)
Humidification
29
Humidification
Comparison of Humidifier kit
D Company Samsung
Image
MethodVaporizing(Evaporating)(Indirect water supply)
Vaporizing(Evaporating)(Direct water supply)
MaterialPET
(Poly Ethylene Terephthalate)Ceramic
Cleanliness
Need to cleanIt is possible that dust can stick the
material during airflow and bacteria can breed in drain pan
Don’t need to clean
because Self-Cleaning
Life
Relatively ShortPossibility of corrosion and contamination
is higher than Inorganic materialas compared with mineral material
Relatively LongBecause ceramic itself is inorganic
material, possibility of corrosionand contamination is relatively low
30
Humidification
Components of Humidifier kit (Option )
Humidifier kit RHF050KHEA RHF100KHEA
Model MVO-VA050100 MVO-VA100100
Connecting hose
Humidifier element
Water feed pipe
Solenoid valvePressure regulation valve
Strainer (1/2 Inch)
Bracket
Connecting hoseRHF050KHEA RHF100KHEA
Regular flow rate
0.2 L/min 0.4 L/min
31
Humidification
Humidifier kit assembling
K4 switch in PCB : Off position
<Floating switch installation>
Water spray hose
<Connection of hose> <Installation of water feed pipe>
<Connection wiring of float switch and solenoid valve> <Insulation>
32
Humidification
Maintenance of humidifier kit
Intake air temperature : 0 ~ 40 ℃
Supply water temperature : 2 ~ 40 ℃
Supply water pressure : 0.08 ~ 0.7 Mpa
Use soft water
Use neutral detergent for cleaning
PCB
34
ERV Plus
• PCB
Main power input
External damper(250VAC, 0.5A)
Main address RMC address
Option switch
Internal damper Humidity controlHood contactComm. with outdoor unit (F1-F2)External controlPower supply to wired R/C (V1-V2)
EA motor
SA motor
Humidifier
Comm. with wired R/C (F3-F4)
Software upgrade
SW debugging
Damper feedback
MPI
Float switch
CO2 sensor
Room temp.EVA in/out temp.
EA temp.OA temp.
EEV
Operation/Erroroutput
IR sensor
Test run button
Inductor
35
ERV Plus
• Power/Communication wiring
L
N
F1
F2
ERV
ERV
ERV
Plus
ERV
Plus
ERV ERV
EHP ERV Plus
L
N
F1
F2
Wro
ng w
iring
Wro
ng w
iring
36
ERV Plus
• Push button
PUSH
Operation
Power LEDWhen humidifier is used(K4=ON)
When humidifier is not used(K4=OFF)
1st No operation 230VAC output to open the humidifier valve.
The LED lamp blinks one time
2ndDamper operation * Opens and closes one time
Damper operation * Opens and closes one time. * Keep the humidifier valve opened
The LED lamp blinks two times.
3rd Supply / Exhaust FAN operation * Turbo breeze is generated
Supply / Exhaust Fan operation * Turbo breeze is generated * Keep the humidifier valve opened
The LED lamp blinks three times.
4th Exit test runCancel the trial operation No 230VAC output to closethe humidifier valve.
Return to the normal state.
37
ERV Plus
• Option switch
SW No. Function ON OFF
K1 Remote sensor No use Use
K2 Central control No use Use
K3 - - -
K4 Humidifier No use Use
K5 Heating temperature compensation 2 ℃ 5 ℃
K6 Filter time 1000 hours 2000 hours
K7, K8 - - -
K9 EEV stop step in heating 160 35/160
K10 Priority of display on wired R/C Low High
K11 External control No use Use
K12 State output Output during operation Output during thermo-on
K13, K14 - - -
K15 External damper No use Use
K16 MPI No use Use
K17 CO2 sensor No use Use
K18 Special EEV control skip in heating No use Use
K19 Clean-up Exhaustion air RPM fixed to RPM in Quiet mode
Supply air RPM fixed to RPM in Quiet mode
K20 - - -
38
ERV Plus
Error code Detail
E101 No communication between indoor unit and outdoor unit(The indoor unit itself does not receive any communication signal from the outdoor unit)
E102 Communication error(s) occurred in other indoor unit(s).(The indoor unit itself succeeded communicating with the outdoor unit)
E122 EVA-IN sensor error (open/short)
E123 EVA-OUT sensor error (open/short)
E128 EVA-IN sensor separated from the pipe
E129 EVA-OUT sensor separated from the pipe
E151 EEV opened
E152 EEV closed
E161 Mixed mode operation
E174 Heat exchanger suction air sensor(open/short)
E201 Communication error between outdoor unit and indoor unit(s) due to the mismatching of the set number and installed number during tracking
E121 Indoor temperature sensor error (open/short)
E221 Outdoor temperature sensor error (open/short)
• Error code
39
ERV Plus
Error code Detail
E139 CO2 sensor error (detached or no feedback)
E162 EEPROM error (read/write failure)
E163 EEPROM option setting error (wrong option code setting)
E186 MPI Error (detached or no feedback)
E561 Supply Air fan motor error (RPM less than 120 for 40 seconds)
E562 Exhaust Air fan motor error
E654 Damper error (When there is no feedback for 100 seconds after damper drive output)
E490 No operation due to low outdoor temperature (Outdoor temp. < 0 ℃ and heat-EX suction air temp. < 0 ℃)
• Error code
• Connection with wired remote controller
F4 F3 V2 V1
F4
F3
V2
V1 F4 F3 V2 V1
MWTR-WE10
Wire specifications : 4-wire 0.75 ~ 1.5mm2 VCTF or equivalentWiring length : max. 100m
40
ERV Plus
41
ERV Plus
• Energy saving operation – EHP-ERV combined
EHP ERV Plus When the E.Saver button is pressed
ON(no Fan mode)
ON
- ERV : current operation mode Energy saving operation- EHP : No change in operation- ERV controlled by room temperature (sensed by EHP or wired R/C), set temperature and indoor temperature (sensed by ERV)
ON(no Fan mode)
OFF
- ERV : OFF energy saving operation- EHP : No change in operation- ERV controlled by room temperature (sensed by EHP or wired R/C), set temperature and indoor temperature (sensed by ERV)
OFF ON - ERV : current operation mode Energy saving operation- EHP : No change in operation
OFF OFF - No energy saving operation
: The operation of an ERV-combined indoor unit is not interfered by energy saving operation, but performs temperature control as it usually does.
F3-F4
EHP
ERV Plus MWR-WE10
Heat ExchangeLOW fan speed
42
ERV Plus
• Energy saving operation – ERV only
ERV Plus When the E.Saver button is pressed
ON - Operated in Heat Exchange, LOW fan speed with repeating sequence of 30-minute operation and 30-minute stop
OFF - No Energy Saving operation- “Restricted” displayed on wired R/C
ERV Plus MWR-WE10
F3-F4
Usercommand
Energy Saving modeBy-Pass mode by MWR-WE10 HIGH fan speed
Heat ExchangeLOW fan speed
By-PassHIGH fan speed
ERVoperation
Energy saving mode By-Pass mode
30 minutes 30 minutes
OFF
LOW
MEDIUM
HIGH
TURBO
4343
ERV Plus
- Operation/Error state output: ERV operation/error state output enabled by option setting (K12=OFF)
ERV Plus error12VDC, 500mA
Comp. operation12VDC, 500mA
ERV Plus error voltage-free contact openRating : 250ADC, 3A
ERV Plus ON voltage-free contact closedRating : 250VAC, 3A
MIM-B14 환기 ON or DX-coil ON ???
4-wire cable of MIM-B14
4444
ERV Plus
- External control
Type : Voltage-free switchTating : 5VDC, 5mA
Switch state = ON Switch state = OFF
ON/OFFcontrol
ERV operation ON OFF
Wired R/C Able to use Able to use
OFF-onlycontrol
ERV operation Unchanged OFF
Wired R/C Able to use Unable to use
- ERV ON/OFF control by external contact switch (enabled by option setting K11=OFF)
- Add the 6th digit of the option code by 8 to switch to OFF-only control mode
External control system
Cable : Unshielded TP 2-wire of 0.75mm2 or greater, VCTF or equivalentLength : Max. 100 meters
Option code
Model ON/OFF control OFF-only control
RHF050KHEA 015617-152380-200000-300000 01561F-152380-200000-300000
RHF100KHEA 015617-1C2373-200000-300000 01561F-1C2373-200000-300000Externalcontrol
Externalcontrol
Kitchen hoodcontrol
Kitchen hoodcontrol
Humidifiercontrol
Humidifiercontrol
4545
ERV Plus
- Kitchen hood control
Type : Voltage-free switchRating : 5VDC, 5mA
Cable : Unshielded TP 2-wire, 0.75mm2 or greater, VCTF or equivalentLength : Max. 100 meters
Externalcontrol
Externalcontrol
Kitchen hoodcontrol
Kitchen hoodcontrol
Humidifiercontrol
Humidifiercontrol
Kitchen hoodKitchen hood
- Kitchen hood mode - SA RPM : Turbo, EA RPM : Mid
Kitchen hood switch ERV operation Wired R/C
ON (closed)Normal Kitchen hood mode “Hood” displayed in normal display
OFF Kitchen hood mode “Hood” displayed in OFF
OFF (open)Kitchen hood mode Normal “Hood” disappeared
Kitchen hood mode OFF “Hood” disappeared
NOTE : The fan speed can be changed by the wired remote controller in kitchen hood mode.
: No need to set the option switch to enable kitchen hood control
4646
ERV Plus
- Humidify control
Externalcontrol
Externalcontrol
Kitchen hoodcontrol
Kitchen hoodcontrol
Humidifiercontrol
Humidifiercontrol
SamsungHumidifier
Humidity sensor(locally locally purchasedpurchased)
1. Basic operation
a. Humidity control enabled by option setting b. Humidity control input closed : Humidifier stop c. Humidity control input open : No change2. Humidity sensor switch specifications
a. Type : Voltage-free switch b. Rating : 5VDC, 5mA3. Operation sequence
a. Humidifier operation by wired remote controller b. Humidity level increase c. Humidity sensor switch closed at the set level d. Humidifier stop
Cable : Unshielded TP 2-wire, 0.75mm2 or greater, VCTF or equivalentLength : Max. 100 meters
: Humidity control by humidifier and locally purchased humidity sensor enabled by option setting (K4=OFF)
474747
ERV Plus
- External damper control: External damper control or interlocking signal enabled by option setting (K13=OFF)
ERV operation DAMPER output
ON 230VAC (max. 0.5A)
OFF No voltage
Direct connection to external load(load current : below 0.5A)
Connection to external load via relay/magnet(load current : over 0.5A)
Relay/Magnetswitch
484848
ERV Plus
- Internal damper control: The internal damper is controller by pulse detection sensed by the micro switch and interval between pulses.
Four pulses one rotation1
2
3
3 2 1 3
T1 T2 T3T1, T2 : short interval, T3 : Long interval
By-Pass mode Heat Exchange mode1. Internal damper operation start2. Pulse from switch detected by controller.3. Damper stop in detection of two short interval pulses
1. Internal damper operation start2. Pulse from switch detected by controller.3. Damper stop in detection of one long interval pulse
• Damper error - After the damper starts operating, E654 is displayed when the pulse from the switch is not detected for 100 seconds.
49
ERV Plus
• CO2 sensor (MOS-C1)
- Two minutes after power-on, the CO2 sensor is maintained at 500RPM as preheating standby- An error is detected when the pulse from the CO2 sensor is not generated for 2 minutes.
HL
HL
HL
OK
NG
NGCO2
sensor
- Pulse width variation depending on CO2 level (pulse period = 1004ms)
Pulsewidth
ppm
10022
2000
0ppm
2ms
4ms
4ppm
2000ppm
1002ms2ms