Energydistributioncatalogue
1011
Dear Friends and Partners,
As you have certainly noticed, this catalogue has a new,changed appearance. Just as our new representation,the Hager brand has developed considerably.
Since years, Hager has been successfully present at themarket of worldwide. Highest quality, reliability, goodcustomer relations and a high degree of innovation arekey features of the Hager brand.
Our range of products has been vastly enlarged:With us you can obtain everything from one source, fromenergy distribution, cable management and buildingautomation, to wiring accessories and safety andsecurity systems.
As a specialist, we provide you with a full-range supplyof solutions for residential and commercial buildings.
The brands of Hager and Tehalit were combined to formthe new Hager brand. A complete range of productsand services to guarantee electrical installations, easyto install while providing a high degree of safety.
Hager also stands for sustainability. We accept ourresponsibility and contribute actively in the protectionof resources. These aspects are key features for all ourinnovations. This line of energy saving is applied in allproduction processes and applies to all our products ingeneral, which contribute to save energy during theirentire product life.
Responsibility, openness and a focus on the future,these features are reflected in our new brand repre-sentation. Clarity, simplicity, a close customer relationand innovation are the old and new values of theHager brand.
In this spirit, we have created this catalogue as apractical tool for your own individual use. Please lookand see for yourself.
Yours sincerely
Daniel Hager
The partner for smartsolutions you can trust
Hager is a full-range supplier of electrical installation systemsfor building, residential and commercial properties. Fordecades, Hager has been syn-onymous with an extensive andcomplete offering. Highest quality, cutting-edge products,modularity, ease of installation, ease of use, excellent serviceand sophisticated design are the features that distinguishHager.
As a specialist in power distribution, cable management and room connection systems switch programmes and smart building automation as wellas safety technology such as alarm systems, smoke detectorsand motion detectors
Hager the supplier for professionals is a synonym for top-quality and innovative technology, as well as good customerrelations and reliability. All of which make Hager the partner forsmart solutions, you can trust.
Hager: a brand meeting
your expectationsInnovations and the systematic enhancement of the productsand systems are key features of the Hager brand. It has alwaysbeen our goal to use new designs and improvements to stayahead of developments.
The use of innovations and new technologies at Hager is al-ways customer-driven. Every year, Hager evaluates thousandsof customer contacts, result-ing in detailed knowledge of itscustomers needs in order to work efficiently and successfully.Based on this knowledge, Hager develops the innovative so-lutions that are so characteristic for the Hager brand. Ease ofinstallation, ease of use, intuitive user interfaces, modularityand durability are brand val-Use that guarantee highest qual-ity throughout in Hager systems.
80 per cent of Hager products and systems are younger thanfive years. This high degree of innovation enables the users tomeet various new challenges effectively. The strong demandfor innovations and enhancements is a good indicator for thecustomer-oriented policy of the Hager brand also resulting ina high turnover at wholesalers.
New ideas for the
customers benefit
The Hager Group is a leading supplier of solutions and servicesof electrical installation systems for residential and commercialproperties as well as industrial applications.
Across the world, the Hager Group has 30 productions sitesin 12 countries. The marketing presence in 55 countries issupported by more than 20,000 selling points of our wholesalepartners. As a global player, the company has about 10,000employees, and a turnover exceeding 1.37 billion Euro in 2008.Today, the Hager Group offers more than 74,000 references.
Shared strong values such as professionalism, team spirit,customer orientation, innovation, loyalty and entrepreneurialactivity unite the employee s throughout the Hager Group.
The business is owned and run by members of the Hager family.Since 2007, the Hager Group has been a European society(SE Societas European, emphasizing on the one hand itscultural diversity and on the other hand its Europeangrounding.
A flourishing group
New MCB board
4
The whole nature of electrical sub and final distribution for commercial installations has changed in thelast few years. Typically there are more outgoing ways, more RCBOs and/ or RCD protection, more metering and more control devices.
Hager decide that it was time to design a board that meets the needs of current installations, not those ofthe past. Our new range of Type B boards makes it easier for you to design and install electrical distributionsystems that meet the needs of today and the future.
Hager has developed the new Invicta Type B boardsas a solution for modern residential, commercial andIndustial installations.
5In addition, DIN rail mounted control devices such as time swit-ches, lighting dimmers and tgwilight switches are becomingincreasinglhy popular. On a more complex level many buildingautomation systems also operate by controlling the final circuits.
Factory suiteAsia
6
As a global player, the Hager Group has 30 productionsites in 12 countries, worldwide. Numerous sites producethe components for the respective markets. This provesto be sensible in order to provide for a better supply ofindividual installation fitting according to the respectivecustomer habits.
12
6
5
3
4
1. Huizhou factory, China2. Assembly line3. Warehouse4. Production line5. Meeting room6. Restaurant
7. Dongguan facotry, China8. Coating line9. Warehouse10. CNC stamping11. Bending machine
77
8
9
10 11
Project listsHong Kong
8
Goals often can be expressed by very simple words.But for our part, objective means for providing thesafe, comfortable and reliable electricity life to millionsof Chinese people.
4
1
2
1. International Commerical Center2. Wong Tai Sin - phase 13. Capitol4. One Silver Sea5. Manhattan Hill6. Nina Tower7. Celestial Heights8. Cullinan
3
98
5
6
7
Invicta
Protection devices
H3
Technical information
Technical information
Technical information
Consumer unit | MCB board | MCCB board | Encloased fuse combination switches and switchdisconnectors
Miniature circuit breakes MT, MU, NB, NC, ND, HLF | 2 & 4 pole RCCBs | RCCB single pole | RCBO singlepole & switched neutral | Switch disconnectors
MCCB x250 | MCCB h250 | MCCB h400-630 |MCCB h800-h1200 | MCCB h1250-1600 |
Consumer unit | MCB board | MCCB board | Encloased fuse combination switches and switchdisconnectors
Miniature circuit breakes MT, MU, NB, NC, ND, HLF | 2 & 4 pole RCCBs | RCCB single pole | RCBO singlepole & switched neutral | Switch disconnectors
MCCB x250 | MCCB h250 | MCCB h400-630 |MCCB h800-h1200 | MCCB h1250-1600 |
1.0
2.0
3.0
4.0
5.0
6.0
Energy
distribution
Energy
distribution
Energy
distribution
Technical
information
Technical
information
Technical
information
univers
Feldverteiler
univers
Verteilerschrnke
univers N
Innenausbau
Anhang
New MCCB boardConsumer units, TPN, New MCBboard, New MCCB board, LBS, FCSNice, Aesthestic design complied with modern decoration area
Consumer unit 14-16Consumer unit split load
Enclosures 17
Invicta TPN 125A type B distribution boards 18-20125A incoming, 63A outgoing
Invicta TPN 125 type B distribution boards 21extensions and accessories for TPN 125A
Invicta TPN 250A type B distribution boards 22-24200A incoming, 63A outgoing
Invicta TPN 125 type B distribution boards 25extensions and accessories for TPN 250A
Invicta 250A panel board system 26-28250A incoming, 125A outgoing
Invicta 250A panel boards system 29extensions and accessories
Invicta 400A panel board system 30-32400A incoming, 125A/ 250A outgoing
Invicta 400A panel board system 33extensions and accessories
Invicta 800A panel board system 34-36630A/ 800A incoming, 125A/ 250A/ 400A outgoing
Invicta 63A/ 800A panel boards system 37extensions and accessories
Enclosed fuse combination switches 38-41and switch disconnectors
Technical information 42-51
Consumer unit
1
3
4
The metal clad range of consumer units are available with a fixed and split load 100A fully tinned busbar. The units feature either metal cover, protecting the devices, and can be supplied as either a surface or flush mounted option.The 2 pole incomer options can be either a switch disconnector, a RCCB or a MCB. The outgoing devices are either MCBs or single / double modules RCBOs. Blank inserts are available to cover unused ways. All consumer units have standard size knockouts and are delivered with earth bar, neutral bar, busbar shroud and label kitThe units have been fully ASTA tested and comply with BS EN60439-3 (annex ZA).
The advantages for you : Compact
Fitting with enclosures tinned copper busbar
Ease of installation
Technical data : Standard BS EN60439-3
1.2mm thickness sheet steel with Epoxy powder coating in RAL 9002
IP4X
26
5
7
Experttips
Knock out For standard size condults1Neutral terminal Fully tinned Fully offer for incoming and
outgoing devices2Domed holes For ease of installation3Fixed busbar Fully tinned Ease of installation4
Earth terminal Fully tinned Fully offer for incoming and
outgoing devices5Outgoing devices Single pole MCBs 2 module RCCB (split load) Single pole RCBO6Cover Metal7
Consumer units
16
Technical characteristics
The metal range of consumerunits with fixed tinned busbaroffer up to a maximum 24 waysin a fixed load configuration, and 8 + 4 ways in a split load con-figuration.
The incoming and outgoing de-vices have to be separately se-lected and fitted by the installer. A neutral & earth terminal is sup-plied for each outgoing way and
extra earthing terminals for bond-ing purposes. All options must beinternally wired by the contractor.
Electrical specification:Rated Voltage (Ue) = 240V~Rated Current (In) = 100A Insula-tion Voltage(Ui ) = 690VConditional Short Circuit current = 25kA
Mechanical specification:Protection Category: IP 4X Material 1.2mm CR4: Steel Powder Coated: RAL 9002
Devices incoming:MCB 2P - 35mm
2
100A 2P SwitchDisconnector - 35mm
2
Terminal capacities16-63A rigid 25mm2
flexible 16mm2
80&100A rigid 50mm2
flexible 35mm2
Outgoing:SP MCBSP RCBO (with flying lead)
Switch disconnetor No. of Pack Cat.(isolator ) rating outgoing ways Qty. Ref.
63 / 100A incoming 4 1 HE04SN
6 1 HE06SN
8 1 HE08SN
10 1 HE10SN
12 1 HE12SN
14 1 HE14SN
16 1 HE16SN
18 1 HE18SN
24 1 HE24SN
Other models available on request
Consumer unit split load
Switch disconnetor No. of Pack Cat.(isolator ) rating outgoing ways Qty. Ref.
63/ 100A incoming 4 + 2 ways 1 HE42SN& 40/ 63/ 100A incomingdouble pole RCCB 5 + 2 ways 1 HE52SN
6 + 2 ways 1 HE62SN
5 + 3 ways 1 HE53SN
6 + 4 ways 1 HE64SN
7 + 3 ways 1 HE73SN
8 + 4 ways 1 HE84SN
Other models available on request
HE10SN
HE42SN
Enclosures
17
Technical characteristics
Surface mountingComplete with din rail1 row 1-16 ways
Enclosure manufactured from1.2mm steel.
Designation No. of Pack Cat Outgoing ways Qty. Ref.
Enclosure 1 row / 1 way 1 VT01E
1 row / 2 ways 1 VT02E
1 row / 4 ways 1 VT04E
1 row / 6 ways 1 VT06E
1 row / 8 ways 1 VT08E
1 row /10 ways 1 VT10E
1 row /12 ways 1 VT12E
2 row /14 ways 1 VT14E
2 row /16 ways 1 VT16E
Other models available on request
VT01E
TPN125 type B distribution boards
The advantages for you : Easy to install
Reversable door
Removable pre-punched top and bottom gland plates
More wiring space
Technical data : Standard BS EN60439-3 / IEC 60439-3
1.2mm thickness sheet steel with Epoxy powder coating in RAL 9002
IP41
4 way to 24 way
20kA at 415V for 0.2 sec.
9 modules cut out for fixed load
13 modules cut out for split load
5
1
3
2
- 125A incoming, 63A outgoing
4
6
Experttips
Earth terminal bars are mountedoffset to neutral terminal barsand angled towards the installerfor easy cable installation. Thescrews are fully turned down forsimple and fast cabling,
1
Transparent IP2X neutral coverallows for ease of cable instal-lation. Screw fully turned downfor easy and fast cabling.
2
Removable door and reversedfor ease of fitting
3Whole set of busbar separatedinto circuit A & circuit B insplit load board.
4
Top tap off for simple board ex-tensions or split load in 125A oran additional MCB up to 125A5
Ease of phase identification L1, L2, L3 mouldings showthrough when the front cover isfitted. Textured surface on bus-bar assembly allows contractorto write circuit identification.
6
20
Technical characteristics
Standards:
BS EN 60439-3IEC60439-3
Suitable for modular incomersas well as non modular incomers
Busbar current rating:
125A
ASTA certified insulated tinned
copper busbar assembly:
- Rated short circuit withstand for busbars: 20 kA at 415V for 0.2 sec.
Removable pre punched topand bottom gland plates.
Incomoer cutout width:
9 modules for fixed load 13 modules for split load.
Reversible door.
1.2 mm thickness sheet steelwith epoxy powder coating inRAL 9002
IP41
Accessories like key lock, DINrail extension boxes etc...
Fixed load board Cat. No. of ways Ref.
(Surface)
4 way JK1B04S1
6 way JK1B06S1
8 way JK1B08S1
10 way JK1B10S1
12 way JK1B12S1
16 way JK1B16S1
18 way JK1B18S1
24 way JK1B24S1
Notes:1. Come with JK1L1003SM link kit2. For MCB 80-125A as incomer, use JK1L1253SK/ JK1L1253MM incoming link kit3. For Direct incomer, use incoming link kit JK2L2504D
Invicta-TPN125typeBdistributionboards125Aincoming,63Aoutgoing
Split load board Cat. No. of ways Ref.Section 1 Section 2 (Surface)
2 2 JK1B022S1
4 2 JK1B042S1
4 4 JK1B044S1
6 2 JK1B062S1
6 4 JK1B064S1
6 6 JK1B066S1
8 4 JK1B084S1
8 6 JK1B086S1
8 8 JK1B088S1
10 4 JK1B104S1
Notes:1. Come with JK1L1003SMSL link kit
JK1B08S1
JK1B042S1
21
Invicta-TPN125typeBdistributionboardsextensionsandaccessoriesforTPN125A
Designation Cat. Ref.
Incoming link kits3P 63A/ 100A switch disc/ RCCB or 63A MCB incomer kit for 125A fixed load JK1L1003SM
3P 63A/ 100A switch disc/ RCCB or 63A MCB incomer kit for 125A split load JK1L1003SMSL
3P 80A - 125A MCB incomer kit for 125A JK JK1L1253MM
3P 125A switch disc incomer kit for 125A JK JK1L1253SK
4P 63A/ 100A switch disc/ RCCB or 63A MCB incomer kit for 125A fixed load JK1L1004SM
4P 63A/ 100A switch disc/ RCCB or 63A MCB incomer kit for 125A split load JK1L1004SMSL
4P 80A - 125A MCB incomer kit for 125A JK JK1L1254MM
125A direct connection kit JK2L2504D
Cable spreader box (Surface)
JK1 Cable spreader box JK1E01S
JK2 Cable spreader box JK2E01S
JK1 - 16 module din extension box (15M available) JK1E16S
JK1 - 32 module din extension box JK1E32S
JK1 - 48 module din extension box JK1E48S
Joint kit for spreader and extension box (Surface)
JK1 - Joint kit for spreader box JK1XJKES
AccessoriesJoint kit for spreader sand extension box for 125A JK1XJKES
Two pieces of gland plate with screws for 125A boards JK1XGPS
1 module blank P032H
Busbar protective boot P100H
Single phase blank for TPN boards JK1XBSP
Key lock for distribution boards JK1XKLS
Incomer shroud in 125A fixed load board in 9M with 3M cutout JK1XISF3
Incomer shroud in 125A fixed load board in 9M without cutout JK1XISF0
Incomer shroud in 125A split load board in 13M with 7M cutout JK1XISS7
Incomer shroud in 125A split load board in 13M with 11M cutout JK1XISS11
Incomer shroud in 125A split load board in 13M with 13M cutout JK1XISS13
Netural terminal cover IP2X JK1XNC
Spare neutral terminal (4 way) JK1XSNT
Spare neutral terminal extra (10 way) JK1XSNTE
Invicta TPN type B distributionboards can be extended verti-cally by combining them withDIN rail boards, for installationof modular devices like timeswitches, contactors etc...
Joining kits are used to com-bine TPN type B boards andDIN rail boards
JK1XBS
JK1XNC
P032H
JK1XSNT
JK1L1004SM
Invicta TPN 250 type B distribution boards
The advantages for you : Easy to install
Removable door
More wiring space
Technical data : Standard BS EN60439-3 / IEC 60439-3
1.2mm thickness sheet steel RAL 9002 Epoxy powder coated
IP41
13 modules cut out
20 kA for 0.2 sec.
4 way to 24 way
3
1
2
5
4
6
Experttips
1
2
3
4
5
6
Earth terminal bars are mountedoffset to neutral terminal barsand angled towards the installerfor easy cable installation. Thescrews are fully turned down forsimple and fast cabling,
Transparent IP2X neutral coverallows for ease of cable instal-lation. Screw fully turned downfor easy and fast cabling.
Removable door and reversedfor ease of fitting
Multiple incomer choices forswitch or MCCB
Top tap off for simple board ex-tensions or split load in 125A oran additional MCB up to 125A
Ease of phase identification L1, L2, L3 mouldings showthrough when the front cover isfitted. Textured surface on bus-bar assembly allows contractorto write circuit identification.
24
Technical characteristics
Standards: BS EN 60439-3IEC 60439-3
Suitable non modular incomers
Busbar current rating:250A
ASTA certified insulated tinnedcopper busbar assembly:- Rated short circuit withstand for busbars: 20 kA at 415V for 0.2 sec.
Removable pre punched topand bottom gland plates.
Reversible door.
1.2 mm thickness with sheetsteel epoxy powder coating inRAL 9002
IP41
Accessories like key lock, DINrail extension boxes etc...
Designation Cat. Ref.No. of ways (Surface)
4 way JK2B04S1
6 way JK2B06S1
8 way JK2B08S1
10 way JK2B10S1
12 way JK2B12S1
16 way JK2B16S1
18 way JK2B18S1
24 way JK2B24S1
Note: Link kits are not supplied with standard, please order I/e link kits separately
Invicta 63 TPN distribution boards200A incoming, 63A outgoing
Designation Number of Cat.TP ways Ref.
TP & N for DPIncoming 200A direct terminal 6 JD06P
12 JD12P
18 JD18P
24 JD24P
Invicta - TPN 250 type B distribution boards
JD06P
JK2B08S1
25
Invicta - type B distribution board extensions and accessories for TPN 250A
Designation Pole Cat. Ref.
Incoming link kits160A switch disc incomer kit for 250A JK 3 JK2L1603SK
200/ 250A switch disc incomer kit for 250A JK 3 JK2L2503SK
125/ 160A MCCB/ MCS incomer kit for 250A JK 3 JK2L1603MH
200/ 250A MCCB/ MCS incomer kit for 250A JK 3 JK2L2503MH
125/ 160A MCCB incomer kit for 200/ 250A JK 4 JK2L1604MH
250A MCCB incomer kit for 250A JK 4 JK2L2504MH
200/ 250A direct connection kit 4 JK2L2504D
Cable spreader box (Surface)JK2 Cable spreader box JK2E01S
DIN rail extension box (Surface)JK2 - 16 module (15M available) JK2E16S
JK2 - 32 module JK2E32S
JK2 - 48 module JK2E48S
Joint kit for spreader box (Surface)JK2 - Joint kit for spreader box JK2XJKES
AccessoriesJoint kit for spreader and extension box for 250A JK2XJKES
Two pieces of gland plate with screws for 250A boards JK2XGPS
1 module blank P032H
Busbar protective boot P100H
Single phase blank for TPN boards JK1XBSP
Key lock for distribution boards JK1XKLS
13M blank for 125/ 160A switch on cover in 250A boards JK2XBSK1
13M blank for 200/ 250A switch on cover in 250A boards JK2XBSK2
13M blank for 125/ 160A MCCB/ MCS on cover in 250A boards JK2XBMH1
13M blank for 125/ 160A MCCB/ MCS on cover in 250A boards JK2XBMH2
Neutral terminal cover IP2X JK1XNC
Spare neutral terminal (4 way) JK1XSNT
Spare neutral terminal extra (10 way) JK1XSNTE
Invicta TPN type B distributionboards can be extended verti-cally by combining them withDIN rail boards, for installationof modular devices like timeswitches, contactors etc...
Joint kits are used to combineTPN type B boards and DIN railboards
JK2XIS
JK1XBS P032H
P100H JK1XSNT
Invicta 250A panel board system250A incoming, 125A outgoing
The advantages for you : Easy to install
More wiring space
Technical data : Standard BS EN60439-1 / IEC 60439-1
1.5 mm thickness sheet steel with Epoxy powder coatingin RAL 9002
IP41
25 kA for 0.3 sec.
1
2
3
4
Experttips
1
2
3
4
Optimal cabling space.
Earth and neutral bars positioned for easier cabling
Multiple incomer choices forswitch or MCCB
Ease of phase identification L1, L2, L3 mouldings showthrough when the front cover isfitted. Textured surface on bus-bar assembly allows contractorto write circuit identification.
Invicta - 250A panel board system 250A incoming, 125A outgoing
28
Technical characteristics
Standards:
BS EN 60439 -1IEC 60439-1
Suitable for MCCBs & isolatingswitches incomers.
ASTA certified insulated tinned
copper busbar assembly:
- Rated short circuit withstand capacity for 250A busbar 25kA at 415V for 0.3 sec.
Removable pre punched topand bottom gland plates.
1.5 mm thickness sheet steelwith epoxy powder coating RAL9002
IP41
Accessories like key lock, DINrail extension boxes etc...
Designation No. of ways Cat.Ref.
Invicta - 2 way JN2B00002S1250 panel board system
250A incoming and 4 way JN2B00004S1125A (x 160) MCCB outgoings
6 way JN2B00006S1
8 way JN2B00008S1
10 way JN2B00010S1
12 way JN2B00012S1
16 way JN2B00016S1
Note: Link kits are not supplied with standard, please order I/e link kits separatelyJN2B0008S1
Invicta - 250A panel board system extensions and accessories
29
Description Cat. Ref.
Incomer kits
250A 3P MCCB incomer kit JN2L2503MH
250A 3P isolator incomer kit JN2L2503SK
250A direct incomer JN2L2503D
Extention box
250A spreader box JN2E01S
250A din rail box JN2E20S
Accessories/ spares
Single pole blanking plate 125A frame JN2XBSP
Key lock for distribution boards JK1XKLS
Invicta 400A panel board system400A incoming, 125A/ 250A outgoing
The advantages for you : Easy to install
More wiring space
Technical data : Standard BS EN60439-1 / IEC 60439-1
1.5 mm thickness sheet steel with Epoxy powder coating in RAL 9002
IP41
35 kA at 415V for 1 sec.
1
2
3
4
Experttips
1
2
3
4
Optimal cabling space.
Earth and neutral bars positioned for easier cabling
Multiple incomer choices forswitch or MCCB
Ease of phase identification L1, L2, L3 mouldings showthrough when the front cover isfitted. Textured surface on bus-bar assembly allows contractorto write circuit identification.
Technical characteristics
Standards:
BS EN 60439-1IEC 60439-1
Suitable for (MCCBs) incomersand outgoings.
ASTA certified insulated
tinned copper busbar assembly:
- Rated short circuit withstand capacity for busbar 35kA at 415V for 1 sec.
Removable pre punched top andbottom gland plates.
1.5 mm thickness with sheetsteel epoxy powder coating inRAL 9002
IP41
Accessories like key lock, DINrail extension boxes etc...
Designation No. of ways Cat.Ref.
Invicta -
400 panel board system 4 way JN4B00004S1up to 400A incoming
up to 125A (x160) outgoings 6 way JN4B00006S1
8 way JN4B00008S1
10 way JN4B00010S1
12 way JN4B00012S1
16 way JN4B00016S1
Designation No. of ways No. of ways Cat.250A 125A Outgoers Ref.
Invicta -
400 panel board system 2 way 2 way JN4B00202S1up to 400A incoming
up to 250A (x250) outgoings 2 way 4 way JN4B00204S1up to 125A (x160) outgoings
2 way 6 way JN4B00206S1
2 way 8 way JN4B00208S1
2 way 10 way JN4B00210S1
2 way 14 way JN4B00214S1
Invicta - 400A panel board system 400A incoming, 125A, 250A outgoing
32
JN4B00008S1
JN4B00208S1
Invicta - 400 panel board system extensions & accessories
33
Description Cat. Ref.
Incomer kits400A 3P MCCB incomer kit JN4L4003MH
400A direct incomer JN4L4003D
400A 3P MCCB extension bar JN4L4003EB
Extention box400A spreader box JN4E01S
400A small din rail box JN4E24S
400A large din rail box JN8E32S
Accessories/ sparesSingle pole blanking plate 125A frame JN2XBSP
Three pole blanking plate 250A frame JN4XBTP Key lock for distribution boards JK1XKLS
Invicta 800A panel board system630A / 800A incoming, 125A / 250Aoutgoing
The advantages for you : Easy to install
More wiring space
Technical data : Standard BS EN60439-1 / IEC 60439-1
1.5 mm thickness sheet steel with Epoxy powder coating inRAL 9002
IP41
40 kA at 415V for 1 sec.
43 kA at 415V for 0.2 sec.
1
2
3
4
Experttips
1
2
3
4
Ease of phase identification L1, L2, L3 mouldings showthrough when the front cover isfitted. Textured surface on bus-bar assembly allows contractorto write circuit identification.
Optimal cabling space.
Earth and neutral bars positioned for easier cabling
Multiple incomer choices forswitch or MCCB
Invicta - panel board 630/ 800A incoming 125A, 250A, 250+125Aoutgoing
36
Technical characteristics
Standards:
BS EN 60439-1IEC 60439-1
Suitable for MCCBs incomersand outgoings.
ASTA certified insulated tinned
copper busbar assembly:
- Rated short circuit withstand capacity for 630/ 800A busbar 40kA for 1 sec. or43kA for 0.2 sec
Removable pre punched topand bottom gland plates.
1.5 mm thickness sheet steelwith epoxy powder coating inRAL 9002
IP41
Accessories like key lock, DINrail extension boxes etc...
Description No. of ways No. of ways Cat.250A 125A Ref.
Invicta -630A/ 800A panel board system / 4 JN8B00004S1up to 630A/ 800A incomingup to 125A (x160) MCCB outgoings / 6 JN8B00006S1
/ 8 JN8B00008S1
/ 10 JN8B00010S1
/ 12 JN8B00012S1
/ 16 JN8B00016S1
Invicta -630A/ 800A panel board system 4 / JN8B00400S1up to 630A/ 800A incomingup to 250A (x250) MCCB outgoings 6 / JN8B00600S1
8 / JN8B00800S1
10 / JN8B01000S1
12 / JN8B01200S1
16 / JN8B01600S1
Invicta -630A/ 800A panel board system 2 2 JN8B00202S1up to 630A/ 800A incomingup to 250A (x250) outgoings and 2 4 JN8B00204S1up to 125A (x160) outgoings
2 6 JN8B00206S1
2 8 JN8B00208S1
2 10 JN8B00210S1
2 14 JN8B00214S1
Invicta -630A/ 800A panel board system 4 2 JN8B00402S1up to 630A/ 800A incomingup to 250A (x250) outgoings and 4 4 JN8B00404S1up to 125A (x160) outgoings
4 6 JN8B00406S1
4 8 JN8B00408S1
4 10 JN8B00410S1
Invicta -630A/ 800A panel board system 6 6 JN8B00606S1up to 630A/ 800A incomingup to 250A (x250) outgoings and 6 8 JN8B00608S1up to 125A (x160) outgoings
JN8B00008S1
Invicta - 630A/ 800A panel board system extensions & accessories
37
Description Cat. Ref.
Incomer kits630A 3P MCCB incomer kit JN8L6303MH
630A direct incomer JN8L6303D
800A 3P MCCB incomer kit JN8L8003MH
800A direct incomer JN8L8003D
630A 3P MCCB extension bar JN8L6303EB
800A 3P MCCB extension bar JN8L8003EB
Extention box800A spreader box JN8E01S
800A din rail box JN8E32S
Accessories/ sparesKey lock for distribution boards JN1XKLS
Single pole blanking plate 125A frame JN2XBSP
Three pole blanking plate 250A frame JN4XBTP
Enclosed fuse combination
switches and switch disconnectors
The advantages for you : Easy to install
Positives action door handle
Lockable off
Technical data : IEC 60947-3
Robust 1.2 mm steel enclosure
1
3
2
4
5
6
7
8
Experttips
2.0 mm (up to 400A)2.5 mm (up to 630A - 800A)
Knock outs and removable gland plate1
Robust 1.2 mm steel enclosure2
Terminal cover
3
Lockable off
4
Neutral bar
5
Can be top or bottom fed
6
Accepts BS88 fuses
7
Key hole mounting slots
8
Technical characteristics
DescriptionThe range of enclosed FCShave been designed to matchthe TP & N range of distributionboards. The number of enclo-sure sizes have been optimized,to ensure that the installation iseasy and uniform. The FCSproducts are designed to protect
& isolate individual circuits. Allhandles can be padlocked inthe off position. Extension boxesare available for extra cablingspace. Operation is through adoor operated rotary handle.
Electrical specification: Tested and complies to IEC 60497-3LBS Sequence 1 & 3FCS Sequence 1 & 4
Electrical Supply: 415V~AC Rating AC23(100A~AC22A)
Mechanical specification:Material 1.2mm CR4 SteelPowder Coated RAL 9002
Devices & accessoriesSPSN 20 - 100A ( 4 ratings) TP & N 20 - 800A (12 ratings) TPSN 20 - 800A (12 ratings)
Enclosed fuse combination switches 32-800A
40
Designation In Utilisation Fuse type Cat.Enclosed FCS A Category Ref.
Single pole switched neutral 20A AC23A A1 JFB20232A AC23A A1 JFB20363A AC23A A2-A3 JFD206100A AC22A A4 JFE210
Triple pole & neutral 20A AC23A A1 JFB30232A AC23A A1 JFB30363A AC23A A2-A3 JFD306100A AC22A A4 JFE310125A AC23A B1-B2 JFG312160A AC23A B1-B2 JFG316200A AC23A B1-B2 JFG320250A AC23A B1-B3 JFG325315A AC23B B1-B3 JFH331400A AC23B B1-B4 JFH340630A AC23B C1-C2 JFI363800A AC23B C1-C3 JFI380
Triple pole switched neutral 20A AC23A A1 JFB40232A AC23A A1 JFB40363A AC23A A2-A3 JFD406100A AC22A A4 JFE410125A AC23A B1-B2 JFG412160A AC23A B1-B2 JFG416200A AC23A B1-B2 JFG420250A AC23A B1-B3 JFG425315A AC23B B1-B3 JFH431400A AC23B B1-B4 JFH440630A AC23B C1-C2 JFI463800A AC23B C1-C3 JFI480
Cable extension boxes 125A, 160A, 200A B1-B2 JZA701triple pole & triple pole + 250A B1-B3 JZA701switched neutral 315A B1-B3 JZA702
400A B1-B4 JZA702630A C1-C2 JZA703800A C1-C3 JZA703
Auxiliary contact1AC type NO HZF3011AC type NC HZF302
Designation 2P 3P 4P
Terminal cover100A HZF201 HZF202 HZF203125A, 160A - HZF202 HZF203200A to 400A - HZF204 HZF205630A to 800A - HZF206 HZF207
JFD306
Enclosed load break switches 20-1600A
41
Technical characteristics
DescriptionThe range of enclosed LBS havebeen designed to match the TP& N range of distribution boards.The number of enclosure sizeshave been optimized, to ensurethat the installation is easy anduniform. Products are designedto isolate individual circuits. All
handles can be padlocked in theoff position. Extension boxes areavailable for extra cabling space.Operation is through a door op-erated rotary handle.
Electrical specification: Tested and complies to BS EN 60439-1 (enclosure)BS EN 60947-3 (device)LBS Sequence 1 & 3FCS Sequence 1 & 4
Electrical Supply: 415V ~ ACRating AC23A (100, 315, 400 &630A AC22A)
Mechanical specification:Material 1.2 mm CR4 SteelPowder Coated RAL 9002
Devices & accessoriesTPN 20-1600A (14 ratings)TPSN 20-1600A (14 ratings)
Designation In Utilisation CatEnclosed LBS A Category Ref.
Triple pole & neutral20A AC23A JAB30232A AC23A JAB30363A AC23A JAB306100A AC22A JAB310125A AC23A JAC312160A AC23A JAC316200A AC23A JAE320250A AC23A JAE325315A AC22A JAG331400A AC22A JAG340630A AC22B JAH363800A AC23B JAH3801250A AC23A JAH390*1600A AC23A JAH392*
Triple pole switched neutral20A AC23A JAB40232A AC23A JAB40363A AC23A JAB406100A AC22A JAB410125A AC23A JAC412160A AC23A JAC416200A AC23A JAE420250A AC23A JAE425315A AC22A JAG431400A AC22A JAG440630A AC22B JAH463800A AC23B JAH4801250A AC23A JAH490*1600A AC23A JAH492*
Cable extension boxes 125A , 160A JZA700triple pole & triple pole 200A , 250A , 315A , 400A JZA701switched neutral 630A , 800A JZA702
Auxiliary contact20A to 100A HZ021125A to 1600A HZ023
Terminal cover 3P 4P125A to 200A HZC201 HZC202250A to 400A HZC203 HZC204630A HZC205 HZC206800A HZ036 HZ0461250A~1600A HZ037 HZ047*
* For overseas only
JAB306
Technical informationTechnical information
Consumer units44
Din rail enclosure44
TPN 125A type B distribution boards125A incoming, 63A outgoing 45
TPN type B distribution boards- split busbar 45
TPN distribution boards200A incoming, 63A outgoing 46
Invicta -TPN 250 type B distribution boards46
Invicta 250A panel board system 250A incoming, 125A outgoing 47
Invicta 400A panel boards system 125A/ 250A outgoing 47
Invicta 800A panel board system125A/ 250A/ 400A outgoing 48
FCS49
LBS50
IP rating51
Consumer units with 100A SP busbar
44 Technical information
W
W1
H H1
D
D1
W
H
D
Din rail enclosure
Reference
Fixed load H W H1 W1 D1
HE04SN 231 214 266 208 71
HE06SN 231 250 266 244 71
HE08SN 231 286 266 280 71
HE10SN 231 322 266 316 71
HE12SN 231 358 266 352 71
HE14SN 231 394 266 388 71
HE16SN 231 430 266 424 71
HE18SN 231 466 266 460 71
HE24SN 231 574 266 568 71
Split load H W H1 W1 D1
HE42SN 231 304 266 298 71
HE52SN 231 322 266 316 71
HE62SN 231 340 266 334 71
HE53SN 231 340 266 334 71
HE63SN 231 358 266 352 71
HE73SN 231 476 266 370 71
HE84SN 231 512 266 406 71
Reference
Surface mounted H W D
VT01E 205 142 61
VT02E 205 178 61
VT04E 205 250 61
VT06E 205 322 61
VT08E 205 394 61
VT10E 205 466 61
VT12E 205 538 61
VT14E 205 361 80
VT16E 205 397 80
TPN 125 type B distribution boards
45Technical information
W
W1 D1
H
D
H1
TPN 125 type B distribution boards- split busbar
W
W1 D1
H
D
H1
Reference
Surface H W D H1 W1 D1
JK1B04S1 495 405 115 490 400 110
JK1B06S1 555 405 115 550 400 110
JK1B08S1 605 405 115 600 400 110
JK1B10S1 660 405 115 655 400 110
JK1B12S1 715 405 115 710 400 110
JK1B14S1 770 405 115 765 400 110
JK1B16S1 820 405 115 815 400 110
JK1B18S1 940 405 115 935 400 110
JK1B24S1 1105 405 115 1100 400 110
Reference
Surface H W D H1 W1 D1
JK1B022S1 555 445 115 550 440 110
JK1B042S1 610 445 115 605 440 110
JK1B044S1 665 445 115 660 440 110
JK1B062S1 665 445 115 660 440 110
JK1B064S1 720 445 115 715 440 110
JK1B066S1 775 445 115 770 440 110
JK1B082S1 720 445 115 715 440 110
JK1B084S1 775 445 115 770 440 110
JK1B086S1 830 445 115l 825 440 110
JK1B088S1 885 445 115 880 440 110
JK1B104S1 935 445 115 930 440 110
Invicta 63 - TP & N distribution boards200A incoming, 63A outgoing
46 Technical information
TPN 250 type B distribution boards
W
W1 D1
H
D
H1
W
W1
H
D
Reference
H W D W1
JD06P 485 385 105 265
JD12P 585 385 105 265
JD18P 705 385 105 265
JD24P 805 385 105 265
Reference
Surface H W D H1 W1 D1
JK2B04S1 655 445 115 650 440 110
JK2B06S1 705 445 115 700 440 110
JK2B08S1 760 445 115 755 440 110
JK2B10S1 815 445 115 810 440 110
JK2B12S1 865 445 115 860 440 110
JK2B14S1 920 445 115 915 440 110
JK2B16S1 975 445 115 970 440 110
JK2B18S1 1030 445 115 1025 440 110
JK2B24S1 1195 445 115 1190 440 110
Invicta - 250A panel boards system 250A incoming, 125A outgoing
47Technical information
W
H
D
Invicta 400A panel board system 125A/ 250A incoming
W
H
D
Reference
Surface mounted H W D
JN2B00002S1 700 615 160
JN2B00004S1 775 615 160
JN2B00006S1 855 615 160
JN2B00008S1 925 615 160
JN2B00010S1 1000 615 160
JN2B00022S1 1115 615 160
JN2B00016S1 1375 615 160
Reference
Surface mounted H W D
JN4B00004S1 930 690 200
JN4B00006S1 1005 690 200
JN4B00008S1 1080 690 200
JN4B00010S1 1155 690 200
JN4B00012S1 1230 690 200
JN4B00016S1 1380 690 200
JN4B00202S1 960 846 200
JN4B00204S1 1035 846 200
JN4B00206S1 1110 846 200
JN4B00208S1 1185 846 200
JN4B00210S1 1260 846 200
JN4B00214S1 1410 846 200
Invicta - 800A panel board system 125A/ 250A / 400A outgoing
48 Technical information
W
H
DJN8B00400S1 1095 846 200
JN8B00600S1 1200 846 200
JN8B00800S1 1305 846 200
JN8B01000S1 1410 846 200
JN8B01200S1 1515 846 200
JN8B01600S1 1725 846 200
Reference
Surface H W D
JN8B00004S1 1035 846 200
JN8B00006S1 1110 846 200
JN8B00008S1 1215 846 200
JN8B00010S1 1320 846 200
JN8B00012S1 1410 846 200
JN8B00016S1 1620 846 200
JN8B00202S1 1065 846 200
JN8B00204S1 1140 846 200
JN8B00206S1 1215 846 200
JN8B00208S1 1320 846 200
JN8B00210S1 1410 846 200
JN8B00214S1 1560 846 200
JN8B00402S1 1170 846 200
JN8B00404S1 1245 846 200
JN8B00406S1 1350 846 200
JN8B00408S1 1440 846 200
JN8B00410S1 1650 846 200
JN8B00606S1 1485 846 200
JN8B00608S1 1620 846 200
Reference Product type Rating
H W D W1 A B
JFB202 SPSN 20A/ A1 250 200 150 182 120 172
JFB302 TPN 20A/ A1 250 200 150 182 120 172
JFB402 TPSN 20A/ A1 250 200 150 182 120 172
JFB203 TPSN 32A/ A1 250 200 150 182 120 172
JFB303 TPN 32A/ A1 250 200 150 182 120 172
JFB403 TPSN 32A/ A1 250 200 150 182 120 172
FCS
49Technical information
D W1
W
H
A
B
3
JFD206 SPSN 63A/ A2-A3 325 300 150 282 190 217
JFD306 TPN 63A/ A2-A3 325 300 150 282 190 217
JFD406 TPSN 63A/ A2-A3 325 300 150 282 190 217
4
JFE210 SPSN 100A/ A4 400 375 200 357 265 292
JFE310 TPN 100A/ A4 400 375 200 357 265 292
JFE410 TPSN 100A/ A4 400 375 200 357 265 292
6
JFG312 TPN 125A/ B1-B2 500 375 200 357 265 380
JFG412 TPSN 125A/ B1-B2 500 375 200 357 265 380
JFG316 TPN 125A/ B1-B2 500 375 200 357 265 380
JFG416 TPSN 125A/ B1-B2 500 375 200 357 265 380
JFG320 TPN 125A/ B1-B2 500 375 200 357 265 380
JFG420 TPSN 125A/ B1-B2 500 375 200 357 265 380
JFG325 TPN 125A/ B1-B2 500 375 200 357 265 380
JFG425 TPSN 125A/ B1-B2 500 375 200 357 265 380
7
JFH331 TPN 315A/ B1-B3 650 500 300 481.5 390 529
JFH431 TPSN 315A/ B1-B3 650 500 300 481.5 390 529
JFH340 TPN 400A/ B1-B4 650 500 300 481.5 390 529
JFH440 TPSN 400A/ B1-B4 650 500 300 481.5 390 529
8
JFI363 TPN 630A/ C1-C2 800 600 350 581.5 490 679
JFI463 TPSN 630A/ C1-C2 800 600 350 581.5 490 679
JFI380 TPN 800A/ C1-C2 800 600 350 581.5 490 679
JFI480 TPSN 800A 800 600 350 581.5 490 679
LBS
50 Technical information
D W1W
H
A
B
Reference
H W D H1 W1 D1
JAB302 250 180 105 177 110 172
JAB402 250 180 105 177 110 172
JAB303 250 180 105 177 110 172
JAB403 250 180 105 177 110 172
JAB306 250 180 105 177 110 172
JAB406 250 180 105 177 110 172
JAB310 250 200 105 182 130 172
JAB410 250 200 105 182 130 172
JAB312 250 200 105 182 130 172
JAB412 250 200 105 182 130 172
JAB316 250 200 105 182 130 172
JAB416 250 200 105 182 130 172
JAB320 400 375 200 357 265 292
JAB420 400 375 200 357 265 292
JAB325 400 375 200 357 265 292
JAB425 400 375 200 357 265 292
JAG331 500 200 375 357 265 380
JAG431 500 200 375 357 265 380
JAG340 500 200 375 357 265 380
JAG440 500 200 375 357 265 380
JAH363 650 500 300 481.5 390 529
JAH463 650 500 300 481.5 390 529
JAH380 650 500 300 481.5 390 529
JAH480 650 500 300 481.5 390 529
JAH390 1058 750 300 732 390 937
JAH392 1058 750 300 732 130 937
IP rating
51Technical information
The International Protection (IP)code for all low voltage enclo-sures up to 1000 V a.c. and 1500V d.c. is defined in identical fash-ion by the standards BS EN60529 - IEC 529 it comprises theletters IP followed by two charac-ter numerals:
The first character numeral
indicates the degree of protectionprovided by the enclosure with re-spect to persons, also to theequipment inside the enclosure
The second character numeral
indicates the degree of protectionprovided by the enclosure with re-spect to harmful ingress of water;a third character may be used toindicate mechanical strength.
An x signifies that no test hasbeen carried out
IP Test Short DefinitionDescription
0 Non-protected No special protection
1 Protected against A large surface of thesolid objects body, such as a handgreater than (but no protection
50 mm 50 mm against deliberateaccess) solidobjects exceeding 50 mm in diameter
2 Protected against Fingers or similar solid objects objects not exceeding greater than 80 mm in length; solid
12,5 mm 12.5 mm objects exceeding 12.5mm in diameter
3 Protected against Tools, wires, etc...., ofsolid objects diameter or thicknessgreater than greater than 2.5 mm;
2,5 mm 2.5 mm solid objects exceeding2.5 mm in diameter
4 Protected against Wires or strips ofsolid objects thickness greater thangreater than 1.0 mm; solid objects
1 mm 1.0 mm exceeding 1.0 mm indiameter
5 Dust-protected Ingress of dust is nottotally prevented but dust does not enter in sufficient quantity tointerfere with satisfactory operation of the equipment
6 Dust-tight No ingress of dust
IP Test Short DefinitionDescription
0 Non-protected No special protection
1 Protected against Dripping water dripping water (vertically falling drops)
shall have no harmful effect
2 Protected against Vertically dripping waterdripping water shall have no harmful when tilted up effect when the to 15 enclosure is tilted at
any angle up to 15 from its normal position
3 Protected against Water falling as a sprayspraying water at an angle up to 60
from the vertical shallhave no harmful effect
4 Protected against Water splashed against splashing water the enclosure from any
direction shall have noharmful effect
5 Protected against Water projected by a water jets nozzle against the
enclosure from anydirection shall have noharmful effect
6 Protected against Water from heavy seasheavy seas or water projected in
powerful jets shall notenter the enclosure inharmful quantities
7 Protected against Ingress of water in athe effect of harmful quantity shallimmersion not be possible when
the enclosure is immersed in waterunder definedconditions of pressureand time
8 Protected against The equipment is submersion suitable for continuous
submersion in waterunder conditions which shall be specified by the manufacturer
The first character numeral
protection against solid substances
The second character numeral
protection against liquid substances
15 cm
m
Protection devices
The advantages for you : By a simple click the clip can be closed and the devices are fixed
Fitting with enclosures tinned copper busbar
Pull-up terminals against erroneous sticking
Quick and safe cabling of the modular devices
Ease of installation
Technical data : Standard IEC 61008, IEC 61009, IEC 60898-1, IEC 60947-3
Grey colour toggle
IP2X
31
2
4
5
Experttips
Grey colour toggle
1
Metal Din clipSafe mechanical fixing of thedevices on the bus bar DIN clipwith parking position: The devices are fixed on the dinrail, but are sliceable.
By a simple click the clip can beclosed and the devices are fixed.
2
The bus bar clicks on mechani-cally into the housing of themodular protective devices (MCBs, RCCBs, RCBOs).3
Terminal featureProtection against erroneoussticking - safe introduction of wires
Stable and safe connecting- noheating of the connectionHigh safety dur ing the wiringthanks to the insulated terminal
4
This indicator allows to clearly toshow whether the contacts arereally mechanically opened.
This functionality is really im-portant to personnel may carryout work on the isolated part inperfect safety.
5
Protection devicesMCB, RCCB, RCBO, HRC, Motor starters,
earth fault relays, earth fault torroids,
surge protection devices
Miniature circuit breakers MT, MU 56
Miniature circuit breakers NB, NC, ND 57
Auxiliaries and accessories for NB/ NC/ ND 58
Miniature circuit breakers HLF 59
2 and 4 pole RCCBs 60
RCCB single pole 61
RCBO single pole & switched neutral 62
Switch disconnectors 63
Miniature circuit breakers 6kA type B -MT, 6kA type C -MU
56
Technical characteristics
DescriptionProtection and control of circuitsagainst overloads and short circuits.
StandardIEC 60898-1
Technical dataType B and C tripping characteristics Tropicalisation T2
Breaking capacity:6000A10000A
Voltage rating: 230-400 VCurrent rating: 6-63A
Connection capacity25mm2 rigid cable16mm2 flexible cable
MT106A
MT232A
MT363A
MU463A
Designation In/A Width in I Pack B curve C curve17.5mm qty. Cat. Ref. Cat. Ref.
Single pole MCB 6 1 12 MT106A MU106A
10 1 12 MT110A MU110A
16 1 12 MT116A MU116A
20 1 12 MT120A MU120A
25 1 12 MT125A MU125A
32 1 12 MT132A MU132A
40 1 12 MT140A MU140A
50 1 12 MT150A MU150A
63 1 12 MT163A MU163A
Double pole MCB 6 2 6 MT206A MU206A
10 2 6 MT210A MU210A
16 2 6 MT216A MU216A
20 2 6 MT220A MU220A
25 2 6 MT225A MU225A
32 2 6 MT232A MU232A
40 2 6 MT240A MU240A
50 2 6 MT250A MU250A
63 2 6 MT263A MU263A
Triple pole MCB 6 3 4 MT306A MU306A
10 3 4 MT310A MU310A
16 3 4 MT316A MU316A
20 3 4 MT320A MU320A
25 3 4 MT325A MU325A
32 3 4 MT332A MU332A
40 3 4 MT340A MU340A
50 3 4 MT350A MU350A
63 3 4 MT363A MU363A
Four pole MCB 6 4 3 - MU406A
10 4 3 - MU410A
16 4 3 - MU416A
20 4 3 - MU420A
25 4 3 - MU425A
32 4 3 - MU432A
40 4 3 - MU440A
50 4 3 - MU450A
63 4 3 - MU463A
Miniature circuit breakers type B 10kA-NB, type C 10kA-NC, type D 10kA-ND
57
Technical characteristics
Descriptionprotection and control of circuitsagainst overloads and short circuits. In commercial and industrial
electrical distribution systems.
StandardIEC 60898-1
Technical datatype B, C & D tripping characteris-tics complies with IEC 60898 -1calibration temperature 30C.
Breaking capacity 10,000A 15,000A
Voltage rating: 230-400V.current rating: 0.5-63A.electrical endurance: 20,000 operations
Positive contact indicationRed contacts closedGreen contacts open will
accept accessories
Connection capacityRigid conductor 25mm2Flexible conductor 16mm2
NB116A NC116A
ND220A
ND320A
NC220A
NB432A
Designation In/A Width in I Pack Cat. Ref Cat. Ref Cat. Ref17.5mm Qty. B curve C curve D curve
.
Single pole MCB 0.5 1 12 - NC100A -1 1 12 - NC101A -2 1 12 - NC102A -3 1 12 - NC103A -4 1 12 - NC104A -6 1 12 NB106A NC106A ND106A10 1 12 NB110A NC110A ND110A16 1 12 NB116A NC116A ND116A20 1 12 NB120A NC120A ND120A25 1 12 NB125A NC125A ND125A32 1 12 NB132A NC132A ND132A40 1 12 NB140A NC140A ND140A50 1 12 NB150A NC150A ND150A63 1 12 NB163A NC163A ND163A
Double pole MCB 0.5 2 6 - NC200A -1 2 6 - NC201A -2 2 6 - NC202A -3 2 6 - NC203A -4 2 6 - NC204A -6 2 6 NB206A NC206A ND206A10 2 6 NB210A NC210A ND210A16 2 6 NB216A NC216A ND216A20 2 6 NB220A NC220A ND220A25 2 6 NB225A NC225A ND225A32 2 6 NB232A NC232A ND232A40 2 6 NB240A NC240A ND240A50 2 6 NB250A NC250A ND250A63 2 6 NB263A NC263A ND263A
Triple pole MCB 0.5 3 4 - NC300A -1 3 4 - NC301A -2 3 4 - NC302A -3 3 4 - NC303A -4 3 4 - NC304A -6 3 4 NB306A NC306A ND306A10 3 4 NB310A NC310A ND310A16 3 4 NB316A NC316A ND316A20 3 4 NB320A NC320A ND320A25 3 4 NB325A NC325A ND325A32 3 4 NB332A NC332A ND332A40 3 4 NB340A NC340A ND340A50 3 4 NB350A NC350A ND350A63 3 4 NB363A NC363A ND363A
Four pole MCB 0.5 4 3 - NC400A -1 4 3 - NC401A -2 4 3 - NC402A -3 4 3 - NC403A -4 4 3 - NC404A -6 4 3 NB406A NC406A ND406A10 4 3 NB410A NC410A ND410A16 4 3 NB416A NC416A ND416A20 4 3 NB420A NC420A ND420A25 4 3 NB425A NC425A ND425A32 4 3 NB432A NC432A ND432A40 4 3 NB440A NC440A ND440A50 4 3 NB450A NC450A ND450A63 4 3 NB463A NC463A ND463A
Auxiliaries and accessories for devices -NB, NC, ND, 10kA MCBs and RCCBs
58
Technical characteristics
All auxiliaries are common toboth single and multi-pole 10kAcircuit breakers and RCCBs
Use of MZ203 - MZ206 onRCCBs requires the use of interface auxiliary CZ001
connection capacity:4mm2 flexible6mm2 solid
MZ175
MZ205
MZ204
MZ201 MZ202
Designation Width in I Pack Cat.17.5mm Qty. Ref.
Auxiliary contacts 1NO +1NC allows remote 1/2 1 MZ2015A - 230V~. indication of main contact status.
Auxiliary contacts CA allows remote indication 1/2 1 MZ202and alarm indication of main contact status.
SD contact indicates a overcurrent(e.g. MCB tripped on overloador short circuit).
Shunt trip Allows remote tripping of the associated device.Operation of the coil is indicated by a flag on the product facia24Vac - 415Vac 1 1 MZ20312V - 130Vdc24 - 48Vac 1 1 MZ20412 - 48Vdc
Under voltage release Allows MCB to be closed onlywhen voltage is above 85% of Un. MCB will automatically trip whenvoltage falls to between 70-35% of Un. Operation of the coil is indicatedbya flag on the product facia
230Vac 1 1 MZ206
48Vdc 1 1 MZ205
Locking kit This allows locking of the device 2 MZN175for the toggle of the device. toggle in the on/off position. supplied without padlock. will accept two padlocks with
hasps of 4.75mm diameter max.
MZ 203 to + MZ 201+ MZ 201 + MZ 202 MCBMZ 206 MZ 201 MZ 201 MZ 201
91
92
93
94
C 1
C 2
D 1
D 2
U <
13
14
21
22
MCB - HLFtype C - 80, 100A and 125A
59
Technical characteristics
DescriptionProtection and control of circuitsagainst overloads and short circuits.- in commercial and industrial
electrical distribution systems
StandardIEC 60898-1
Technical dataType C tripping characteristicscomplies with IEC 60898-1reference calibration temperature30oC
Breaking capacity- 10,000A
Voltage rating - 230V-400VCurrent rating - 80 & 100Aelectrical endurance - 20,000
Connection capacityRigid conductor 50mm2
Flexible 35mm2
Note: not suitable for use in consumer units and distributionboards.
Designation In/A Width in I Pack Cat.17.5mm Qty. Ref.
Single pole MCB 80 1.5 12/ 144 HLF180S
100 1.5 12/ 144 HLF190S
125 1.5 12/ 144 HLF199S
Double pole MCB 80 3 6/ 72 HLF280S
100 3 6/ 72 HLF290S
125 3 6/ 72 HLF299S
Triple pole MCB 80 4.5 4/ 48 HLF380S
100 4.5 4/ 48 HLF390S
125 4.5 4/ 48 HLF399S
Four pole MCB 80 6 3/ 36 HLF480S
100 6 3/ 36 HLF490S
125 6 3/ 36 HLF499S
HLF299S
HLF399S
HLF499S
HLF199S
2 and 4 pole RCCBs
60
Technical characteristics
DescriptionTo open a circuit automatically inthe event an earth fault betweenphase and earth, and/or neutraland earth. A wide range of current ratings and sensitivitiesare available. Suitable for do-mestic, commercial, industrialapplications.
StandardIEC 61008
Technical dataSensitivities (fixed) -10, 30, 100, 300mA & 100 and300mA time delayed.
Terminal capacities16-63A rigid 25mm2
flexible 16mm2
80&100A rigid 50mm2
flexible 35mm2
FeaturesPositive contact indication isprovided by the rectangular flagindicatorred = closedgreen = open.
Indication of trip is provided bythe oval flag indicatoryellow = tripped.All RCCBs have trip free mechanisms and can be padlocked either on or off.
Operating temperature range- 5 to 40oC
Operating voltage2P: 110-230Vac4P: 230 - 400Vac
Width in 17.5mm modules I2P - 2 I4P - 4 I
Designation Current Pack Cat Ref. Cat Ref.rating Qty 2 pole 4 pole
Sensitivity10mA 16A 1 CC216B -- 25A 1 CC225B -
30mA 25A 1 CD225B CD425B30mA 40A 1 CD240B CD440B30mA 63A 1 CD263B CD463B30mA 80A 1 CD280B CD480U30mA 100A 1 CD284B CD484U
100mA 25A 1 CE225B CE425B100mA 40A 1 CE240B CE440B100mA 63A 1 CE263B CE463B100mA 80A 1 CE280B CE480B100mA 100A 1 CE284B CE484B
300mA 25A 1 CF225B CF425B300mA 40A 1 CF240B CF440B300mA 63A 1 CF263B CF463B300mA 80A 1 CF280B CF480B300mA 100A 1 CF284B CF484B
Time delayed
100mA 100A 1 CN284U CN484U300mA 100A 1 CP284U CP484U
Accessoriesterminal covers 16A-63A CZ005 CZ006
80A-100A CZ007 CZ008
CD425B
CD263B
RCBO - single pole
61
Technical characteristics
Descriptioncompact protection deviceswhich combine the overcurrentfunctions of an MCB with theearth fault functions of an RCCBin a single unit. A range of sensitivity and current ratings areavailable for use in domesticcommercial and industrial applications
StandardIEC 61009
Technical dataSensitivities (fixed) 10mA and 30mAbreaking capacity: 6kA, 10kA
Terminal capacities16mm2 rigid, 10mm2 flexible
Application1 module devices provide acompact solution for installationin Vision consumer units, Invicta63 distribution boards. These devices are 1 pole & solid neutral.
Operating voltage230V AC
Flying neutral lead length:700mm
Designation In/A Width in I Pack Cat 17.5mm Qty. Ref.
6kA 6A 1 1 AD104type B
10A 1 1 AD105
16A 1 1 AD107
20A 1 1 AD108
25A 1 1 AD109
32A 1 1 AD110
40A 1 1 AD111
6kA 6A 1 1 AD119type C
10A 1 1 AD120
16A 1 1 AD122
20A 1 1 AD123
25A 1 1 AD124
32A 1 1 AD125
40A 1 1 AD126
10kA 6A 1 1 AD184type C
10A 1 1 AD185
16A 1 1 AD187
20A 1 1 AD188
25A 1 1 AD189
32A 1 1 AD190
40A 1 1 AD191
6844
115
45
AD125
RCBO single pole and switched neutral
62
Technical characteristics
DescriptionCompact protection deviceswhich provide MCB overcurrent protection and RCCB earth fault protection in a single unit. complies with BSEN 61 009
StandardIEC 61009
Technical dataThe units are available with current ratings of 6A, 10A, 16A,20A, 25A and 32A. The device switches both the phase andneutral conductors. All ratingshave 30mA earth fault protection. The units feature indi-cators which show whether trip-ping is due to an overcurrent orearth fault.
voltage rating: 110-230V.current rating: 6-32A.
Operations.Bechanical life: 20,000
connection capacityrigid conductor 25mm2
flexible conductor 16mm2
Designation In/A Width in I Pack Cat. Ref. Cat. Ref.17.5mm Qty. Type B Type C
RCBO tripping current 30mA 6A 2 1 AD906U AD956U
with flying 500mm lead for 10A 2 1 AD910U AD960U
neutral connection. 16A 2 1 AD916U AD966U
For use with consumer units 20A 2 1 AD920U AD970U
and distribution boards 25A 2 1 AD925U AD975U
32A 2 1 AD932U AD982U*
* Note: product may aesthetically differ slightly from that shown
AD932U
Designation Characteristics Width in I Pack Cat.17.5mm Qty. Ref.
Single pole 1 x 25A 250V~ 1 12 SB116S
1 x 32A 250V~ 1 12 SB132S
1 x 63A 250V~ 1 12 SB163S
1 x 80A 250V~ 1 12 SB177S
1 x 100A 250V~ 1 12 SB197S
Double pole 2 x 32A 400V~ 1 12 SB232S
2 x 40A 400V~ 2 6 SB240S
2 x 63A 400V~ 2 6 SB263S
2 x 80A 400V~ 2 1 SB280S
2 x 100A 400V~ 2 1 SB299S
Triple pole 3 x 25A 400V~ 2 6 SB316S
3 x 32A 400V~ 2 6 SB332S
3 x 40A 400V~ 3 4 SB340S
3 x 63A 400V~ 3 4 SB363S
3 x 80A 400V~ 3 1 SB380S
3 x 100A 400V~ 3 1 SB399S
3 x 125A 400V~ * 1 JK125S
3 x 160A 400V~ * 1 JK160S
3 x 200A 400V~ * 1 JK200S
3 x 250A 400V~ * 1 JK250S
Four pole 4 x 25A 400V~ 2 6 SB416Swith indicator
4 x 32A 400V~ 2 6 SB432S
4 x 40A 400V~ 4 3 SB440S
4 x 63A 400V~ 4 3 SB463S
4 x 80A 400V~ 4 1 SB480S
4 x 100A 400V~ 4 1 SB499S
Switch disconnectors
63
SB499S
Technical characteristics
Descriptionfor use as a switch disconnectorin all types of circuit. Complieswith: IEC 60947-3
Technical dataAC 22
In : 25, 32Ashrouded cable clamps, connection capacity:10 mm2 rigid conductor.6 mm2 flexible conductor.
In : 40, 63, 80Acable clamps, connection capacity:25mm2 rigid conductor.16mm2 flexible conductor.
In : 100Acable clamps, connection capacity:50 mm2 rigid conductor.35 mm2 flexible conductor.All switches have a green / redmechanical indication giving a positive contact indication:
- version with pilot light for 25-32A SP/DP switches.
Optionhandle link pin
SB116S
SB240S
SB399S
JK200S
N
Technical informationTechnical information
Circuit protectiion principle66-67
Technical information circuit breakers68-71
Circuit breakers, and RCCB auxiliaries72
Transformer protection and lighting circuits73
Device selecion for motor applications74
Prospective fault current75-77
Technical information RCBO and fuse carriers78
Technical information RCCBs79-81
Circuit protection principle
66 Technical information
Basic PrinciplesThe proper selection of the correct circuit protective device requiresan understanding of the potential hazards against which protectionfor safety is required. The Wiring Regulations identify several hazards: electric shock thermal effects overcurrent undervoltage isolation
Electric shock - is divided into two parts: direct contact: contact with parts which result in an electric shock
in normal service indirect contact: contact with exposed conductive parts which re-
sult in an electric shock in case of a fault.
To protect against direct contact the Wiring Regulations suggest the following basic measures should be taken:(1) by insulation of live parts(2) by enclosures or barriers(3) by obstacles (4) by placing out of reach
To protect against indirect contact the Wiring Regulations suggest thefollowing basic measures should be taken:(1) earthed equipotential bonding and automatic disconnection of
supply(2) use of class II equipment or equivalent insulation(3) non-conducting location(4) earth-free local equipotential bonding(5) electrical separation
Of these five measures, the first is by far the most commonly used -(1) earthed equipotential bonding and automatic disconnection of
supply:
In each installation circuit protective conductors connect all exposedconductive parts of the installation to the main earthing terminal. Mainequipotential bonding conductors are used to connect extraneous conductive parts of other incoming services and structural metalwork to the main earthing terminal. These extraneousconductive parts include the following: main water pipes gas installation pipes other service pipes and ducting risers of central heating and air conditioning systems exposed metal parts of the building structure
This bonding creates a zone within which any voltages appearing be-tween exposed conductive parts and extraneous conductive parts,are minimized; the earth fault loop impedance must have a value lowenough to allow sufficient current to flow for the circuit protective de-vice to operate rapidly to disconnect the supply; disconnection mustbe sufficiently fast so that voltages appearing on the bonded metal-work cannot persist long enough to cause danger; depending on theoperating characteristics of the protective device and the earth im-pedance, such disconnection may be achieved either by overcurrent devices, Fuses, Miniature Circuit Breakers, (i.e. MCBs) orby Residual Current Devices, (i.e. RCCBs).
Thermal Effect - refers to heat generated by the electrical equipment in normal use and under fault conditions. The proper se-lection of equipment complying with the latest product standards isessential in providing protection against thermal effects.
Overcurrent - is defined as a current exceeding the rated value of thecircuit components. It may be caused by the overloading of a healthycircuit or it may take the form of a short-circuit current, defined as an"overcurrent resulting from a fault of negligible impedance between live conductors having a difference in potentialunder normal operating conditions". Overcurrent protection may beprovided by using fuses or circuit breakers singly or in combination.
Undervoltage - refers to the dangers that could be caused by the re-duction or loss in voltage and the subsequent restoration, such as theunexpected re-starting of motors or the automatic closing of protective devices. The proper selection of control and protective de-vices must take the protection against undervoltage into consideration.
Isolation - every circuit shall be provided with means of isolation (ex-cept in certain cases) to prevent or remove hazards associated withthe installation, equipment and machines. The new standards for cir-cuit breakers and switch-fuses now take this into account.
Protection against shock by indirect contactIndirect contact - is the contact of persons or livestock with exposedconductive parts made live by a fault and which may result in electricshock. An example would be where the insulation of an electricheater has broken down resulting in a live conductor internally touching the casing. This could result in the heater casing beingraised to a hazardous voltage level, causing electric shock to a person touching it.
Two important measures must be taken to prevent this hazard: the impedance of circuit conductors is kept to a minimum. The
earth fault loop impedance (Zs) is used as a measure of the circuit impedance under fault conditions.
the overcurrent device protecting the circuit is selected to rapidlydisconnect an earth fault.
The effect of these two measures is inter-related.1. By ensuring that the circuit protective conductor is of a low im-
pedance, the voltage to which the live casing is raised, underfault conditions, is kept to a minimum.
2. The low impedance path provided by the circuit conductors andthe circuit protective conductor will result in a high level of current in the event of an earth fault. This high fault current en-sures that the overcurrent protective device will disconnect thefault in a short time, reducing the interval during which the casingof the faulty equipment is live.
Components of earth fault loop impedance (Zs) in a system.(Earth fault at load between conductor and casing).Zs = Ze + (R1 +R2)
Fig 1
Earth fault loop impedance (Zs)To ensure the impedance of conductors in a circuit is sufficiently lowthe system designer has to establish the value of the earth fault loopimpedance.
Zs - is a measure of the earth fault current loop, comprising the phase conductor and the protective conductor. It comprises the complete loop including the winding of the transformer from which the circuit is supplied as defined by the following:
Ze - is the part of the earth fault loop impedance external to the installation, its value can be measured or a nominal value can be obtained from the supply authority.
R1
Ze
R2
E
L1
N
load
loadterminals
consumer'sterminals
transformerwinding
Circuit protection principle
67Technical information
(R1 +R2) - where R1 is the resistance of the phase conductor within the installation and R2 is the resistance of the circuit protective conductor. These two components constitute theloop impedance within the installation.
Therefore: Zs = Ze + (R1 + R2)
Once the value of Zs has been established a suitable overcurrent pro-tective device has to be selected to ensure disconnection of an earthfault within the specified time.The times are: 5 seconds for fixed equipment. For portable equipment and for fixed equipment installed outside
the equipotential bonding zone, the disconnection times are dependent on the nominal voltage to earth, i.e. 220 to 277 volts = 0.4 seconds.
Zs by calculationTo establish whether the relevant disconnection time can be achieveda simple calculation must be made, based on Ohm's law:
Uoc (open circuit voltage)*If (fault current) = Zs (earth fault loop)
* voltage between phase and earth (240V)
The fault current (If) must be high enough to cause the circuit protective device to trip in the specified time. This can be es-tablished by consulting the time/current characteristic for the protective device. If the maximum trip time for the fault current calculated is less than or equal to the relevant value (5s for fixedequipment; 0.4s for portable equipment) then compliance isachieved. It is important that when consulting the characteristic curvethe worst case is used, i.e. the maximum tripping time including any tolerance. An example is shown in Figs 1 and 2.
Zs by tablesThe above procedure can be used for any type of protective deviceproviding a time/current characteristic curve is available. Frequently,however, a much simpler method is available using tables listing max-imum Zs values which have been interpreted from the characteristic curves for the relevant devices. Providing the systemZs is equal to or less than the value given in the table, compliance isachieved. Tables for a number of 'standard' devices (certain fusesand MCBs) are given in the Wiring Regulations.
Zs too highIf the system Zs value is too high to achieve rapid enough disconnection with the overcurrent protective devices available then itis necessary to use one of the two following methods: fit a cable with a larger cross-section and consequently a lower
impedance. This may be a very expensive solution especiallywhen the installation is complete before the problem is discovered.
use a Hager residual current device (RCCB). Subject to certainconditions being met this provides a simple and economical solu-tion.
Example
Fig 2
Fig 2 shows a fixed circuit with an earth loop impedance Zs of 0.7 ohms protected with an MT132. The fault current (If) willtherefore be Uo/Zs = 240/0.7 = 343A
By referring to the characteristic for MT132 (see Fig 3) it can be seenthat the breaker will disconnect in 0.02 seconds for this current. Thebreaker therefore easily satisfies the requirement for disconnection in5 seconds.If the circuit Zs was 2.0 ohms then the fault current would be:
240/2 = 120Aand the disconnection time would be 10 seconds, in which casecompliance would not be achieved.
Fig 3
Protection against overcurrentOvercurrent - "A current exceeding the rated value. For conductorsthe rated value is the current-carrying capacity"
Overload Current - "An overcurrent occurring in a circuit which iselectrically sound"
Short-Circuit Current - "An overcurrent resulting from a fault ofnegligible impedance between live conductors having a difference inpotential under normal operating conditions."
Protection against Overload CurrentFor the protection against overload current, protective devices mustbe provided in the circuit to break any overload current flowing in thecircuit conductors before it can cause a temperature rise which wouldbe detrimental to insulation, joints, terminations or the surroundings of the conductors.
In order to achieve this protection the nominal current of the protective device In should be not less than the design current of thecircuit Ib and that In should not exceed the current-carrying capacityof the conductors Iz, and that the current causing effective operationof the protective device I2 does not exceed 1.45 times the current-carrying capacity of the conductor Iz, expressed asIb < In < IzI2 < 1.45Iz
Protection against Short-Circuit CurrentProtective devices must be provided to break any short-circuit current before it can cause danger due to thermal and mechanical(electro-dynamic) effects produced in the conductors and connections. The breaking capacity of the protective device shall notbe less than the prospective short-circuit current at the point at whichthe device is installed. However a lower breaking capacity is permit-ted provided that a properly co-ordinated back-up device having the necessary breaking capacity is installed on the supply side(see page 153).
Positioning of Overcurrent DevicesDevices for the protection against overload and short-circuit must beplaced at the point where a reduction occurs in the current-carryingcapacity of the conductors. This reduction could be caused by achange in the environmental conditions as well as the more obviouschange in the cross-sectional area of the cable.
There are of course exceptions to this general rule which relate to avery few special applications. These are set out in detail in the WiringRegulations.
load
MT132L1
N
E
Zs = 0.7 ohms
If = 343A
Time / currentcharacteristic
MT132
328115
0.02
10
I (amperes)
t(secs.)
An earth fault current of 343A causes a trip of the mag-netic protection in 20mS.
An earth fault current of 120A causes a trip of the ther-mal protection in 10 seconds.
Technical information circuit breakers
68 Technical information
Both of the new British Standards covering Low Voltage CircuitBreakers provide the user with a better assurance of quality and performance by taking into account the actual operating conditions ofthe breaker. New definitions and symbols have been introducedwhich should be committed to memory. Some of those most frequently used are:
Ue : rated service voltage
Ui : rated insulation voltage (> Uemax)
Uimp : rated impulse withstand
Icm : rated short circuit making capacity
Icn : rated short circuit capacity
Ics : rated service short circuit breaking capacity
Icu : rated ultimate short circuit breaking capacity
I n : rated residual operating current (often calledresidual sensitivity)
In: rated current = maximum value of current used for the temperature rise test
t: trip delay of residual current devices
In addition BS EN 60898 sets out to provide a greater degree ofsafety to the uninstructed users of circuit breakers. It is interesting tonote that the description "miniature circuit breaker" or MCB is notused at all in this standard, but no doubt both manufacturers andusers will continue to call circuit breakers complying with BS EN60898 miniature circuit breakers or MCBs for some time to come.
The scope of this standard is limited to ac air break circuit breakersfor operation at 50Hz or 60Hz, having a rated current not exceeding125A and a rated short-circuit capacity not exceeding 25kA.
A rated service short-circuit breaking capacity Ics is also includedwhich is equal to the rated short-circuit capacity Icn for short-circuitcapacity values up to and including 6kA, and 50% of Icn above 6kAwith a minimum value of 7.5kA. As the circuit- breakers covered bythis standard are intended for household and similar uses, Ics is ofacademic interest only. The rated short-circuit capacity of a MCB (Icn)is the alternating component of the prospective current expressed byits r.m.s. value, which the MCB is designed to make, carry for itsopening time and to break under specified conditions. Icn is shownon the MCB label in a rectangular box without the suffix A and is thevalue which is used for application purposes. Icn (of the MCB) shouldbe equal to or greater than the prospective short-circuit current at the point of application.
You will see from the curves that the inverse time / current characteristic which provides overload protection is the same on allthree. This is because the British Standard requires the breaker tocarry 1.13 times the rated current without tripping for at least onehour and when the test current is increased to 1.45 times the ratedcurrent, it must trip within one hour, and again from cold if the current is increased to 2.55 times the rated current the breaker musttrip between 1 and 120 seconds. The inverse time delay characteristic of all MCBs claiming compliance with BSEN 60898must operate within these limits.
The difference between the three types of characteristic curves designated 'B', 'C' and 'D' concerns only the magnetic instantaneous trip which provides short-circuit protection.
For type 'B' the breaker must trip between the limits of 3 to 5times rated current
For type 'C" the breaker must trip between the limits of 5 to 10times rated current, and
For type 'D' the breaker must trip between the limits of 10 to 20times rated current.
Often manufacturers publish their MCB tripping characteristics show-ing the limits set by the standard and guarantee that any breaker that you purchase will operate within these limits. So greatcare should be taken when working with characteristic curves showing lower and higher limits - on no account should you take amean point for application design purposes.
For cable protection applications you should take the maximum tripping time and some manufacturers publish single line characteristic curves which show the maximum tripping time. If thedesign problem is nuisance tripping then the minimum tripping timeshould be used and for desk top co-ordination studies, both lowerand upper limits have to be taken into account.
Energy limitingEnergy is measured in Joules. *James Prescott Joule proved thatthermal energy was produced when an electric current flowedthrough a resistance for a certain time, giving us the formula :-
Joules = I2 x R x t or because we know that watts = I2R
Joules = watts x seconds
Therefore we can say that :-
One Joule = one watt second
or energy = watts x seconds = I2 R t
If the resistance (R) remains constant or is very small compared withthe current (I) as in the case of short-circuit current, then energy be-comes proportional to I2t. Which is why the energy let-through of aprotective device is expressed in ampere squared seconds and re-ferred to as I2t
I2t (Joule Integral) is the integral of the square of the current over agiven time interval (t0, t1)
The I2t characteristic of a circuit breaker is shown as a curve givingthe maximum values of I2t as a function of the prospective current.
Manufacturers are required by the British Standard to produce the I2tcharacteristic of their circuit breakers.See Fig 8 on page 141.
The energy limiting characteristics of modern MCBs greatly reducethe damage that might otherwise be caused by short-circuits. Theyprotect the cable insulation and reduce the risk of fire and other dam-age. Knowledge of the energy limiting characteristic of a circuitbreaker also helps the circuit designer calculate discrimination withother protective devices in the same circuit.
Because of the importance of the energy limiting characteristic theBritish Standard for circuit breakers for household and similar installations suggests three energy limiting classes based on the permissible I2t (let-through) values for circuit breakers up to 32A;class 3 having the best energy limiting performance.
All Hager MCBs exceed the requirements for energy let-through setby the British Standard for energy limiting class 3.
Technical information circuit breakers
69Technical information
For use with DCBecause of their quick make and break design and excellent arcquenching capabilities Hager circuit breakers are suitable for DC ap-plications.
The following parameters must be considered.1 system voltage:
Determined by the number of poles connected in series (see table 13)
2 short circuit current:(see table 14)
3 tripping characteristics:- the thermal trip remains unchanged- the magnetic trip will become less sensitive requiring deratingby 2 the ac value. (see table 14)
Power lossThe power loss of MCBs is closely controlled by the standards and iscalculated on the basis of the voltage drop across the main terminals measured at rated current. The power loss of Hager circuitbreakers is very much lower than that required by the British Stan-dard, so in consequences run cooler and are less affected whenmounted together.
The table below gives the watts loss per pole at rated current.
Table 12
Table 13
Table 11
* din rail mount only, not for use in fixed busbar distribution boards.
Reference ML MM MT NB NC ND NM*
Poles SP+N SP DP TP 4P SP SP DP TP 4P SP DP TP 4P SP DP TP 4P 3P 4P
Rated operational volt-age Ue (V)
230 230/ 400 230 230/ 400 230/ 400 230/ 400 400
Nominal current 6-40A 6-63A 6-63A 6-63A 0.5-63A 6-63A 80-100A
Breaking capacity to IEC 60898
6kA 6kA 6kA 6kA 6kA 6kA
Breaking capacity to IEC 60947-2
N/A N/A N/A 15kA 15kA 15kA 10kA
Rated insulation voltage Ui (V)
500V 500V 500V 500V 500V 500V 500V
Rated insulation voltage Uimp (kV)
2500V 2500V 2500V 2500V 2500V 2500V 2500V
Electrical endurance 0.5 to 32A40 to 63A
10,000 cycles 20,000 cycles10,000 cycles
20,000 cycles10,000 cycles
20,000 cycles10,000 cycles
20,000 cycles10,000 cycles
20,000 cycles10,000 cycles
10,000 cycles
MCB ratedcurrent (A)
0.5 1 2 3 4 6 10 16 20 25 32 40 50 63 80 100
Watts lossper pole (W)
1.3 1.5 1.7 2.1 2.4 2.7 1.8 2.6 2.8 3.3 3.9 4.3 4.8 5.2 8 10
No. of poles 1 pole 2 poles inseries
Watts loss perpole (W)
max voltage
breaking ca-pacityL/R=15ms
max voltage
breaking ca-pacityL/R=15ms
MT 60V 6kA 125V 6kA
NB NC ND 60V 10kA 125V 10kA
Characteristiccurve
B C D
Magnetic trip 50Hz dc 50Hz dc 50Hz dc
Im1 3In 4.5In 5In 7.5In 10In 15In
Im2 5In 17.5In 10In 15In 20In 30In
Table 14
Technical information ciruit breakers
70 Technical information
correction factorThe breaker is calibrated at a temperature of 300C.
Temperature correction
No. of units n K
n = 1 1.0
2 < n < 4 0.95
4 < n < 6 0.9
6 < n 0.85
Table 16
frequencythermal unchangedmagnetic value multiplied by coefficient K
F (Hz) 17Hz 60Hz 100Hz 200Hz 400Hz
K 1 1.1 1.2 1.5
Table 17
Note: the circuit breaker can have the line\load connected to either the top or bottom terminals
Table 15
Temperature DeratingMCBs are designed and calibrated to carry their rated currentand to operate within their designated thermal time/current zoneat 30oC. Testing is carried out with the breaker mounted singly ina vertical plane in a controlled environment. Therefore if the circuit breaker is required to operate in conditions which differfrom the reference conditions, certain factors have to be appliedto the standard data. For instance if the circuit breaker is requiredto operate in a higher ambient temperature than 30oC it will re-quire progressively less current to trip within the designated time/current zone.
Grouping factorsConsideration should also be given to the proximity heating ef-fect of the breakers themselves when fully loaded and qmounted together in groups. There is a certain amount of wattsloss from each breaker depending on the trip rating which maywell elevate the ambient air temperature of the breaker above theambient air temperature of the enclosure.
grouping factor (rated current reduce by factor K)
ExampleFive circuit breakers are to be installed inside an enclosure in a switchroom which has an average ambient air temperature of35oC. Each circuit breaker will be required to supply a continuous current of 20A.
From Table 15 we would select a circuit breaker which has arated current of 25A at 30oC and 23.5A at 35oC. This takes care ofthe switchroom ambient air temperature of 35oC, but we alsohave to take into account the grouping factor of five continu-ously loaded breakers mounted together in one enclosure. Table 16 gives us a grouping factor K of 0.9. We thenapply this grouping factor to the rated current at 35oCwhich gives us a circuit breaker rated current of 23.5 x 0.9 = 21.15A in the specified conditions.
note: if the design current of a circuit (Ib) isless than 0.85 times the nominal setting of the circuit breaker (In)grouping factor can be ignored
In (A) 30C 35C 40C 45C 50C 55C 60C
0.5 0.5 0.47 0.45 0.4 0.38 - -
1 1 0.95 0.9 0.8 0.7 0.6 0.5
2 2 1.9 1.7 1.6 1.5 1.4 1.3
3 3 2.8 2.5 2.4 2.3 2.1 1.9
4 4 3.7 3.5 3.3 3 2.8 2.5
6 6 5.6 5.3 5 4.6 4.2 3.8
10 10 9.4 8.8 8 7.5 7 6.4
16 16 15 14 13 12 11 10
20 20 18.5 17.5 16.5 15 14 13
25 25 23.5 22 20.5 19 17.5 16
32 32 30 28 26 24 22 20
40 40 37.5 35 33 30 28 25
50 50 47 44 41 38 35 32
63 63 59 55 51 48 44 40
80 80 76 72 68 64 60 56
100 100 95 90 85 80 75 70
Technical information ciruit breakers
71Technical information
B curve (BSEN 60 898)MCBs: MT rated 6 63A
NB rated 6 63A
C curve (BSEN 60 898)MCBs: NC rated 0.5 63A
NM rated 80 - 100ANU rated 6 - 63A
D curve (BSEN 60 898) MCBs: ND rated 6 63A
100006000400036002000
1000600400
200
10060
40
20
1064
2
10,60,4
0,2
0,1
0,04
0,02
0,01
0,004
1 1,5 2 3 4 6 8 10 15 20 30 401,13
1,45
BC
100006000400036002000
1000600400
200
10060
40
20
1064
2
10,60,4
0,2
0,1
0,04
0,02
0,01
0,004
1 1,5 2 3 4 6 8 10 15 20 30 401,13
1,45
D
100006000400036002000
1000600400
200
10060
40
20
1064
2
10,60,4
0,2
0,1
0,04
0,02
0,01
0,004
1 1,5 2 3 4 6 8 10 15 20 30 401,13
1,45
multiples of In multiples of Inmultiples of In
time
in s
econ
ds
time
in s
econ
ds
time
in s
econ
ds
MT NB NC ND NM 80 - 100A
0,5 0,6 0,8 1
8
7
6
5
4
3
2
1
0,8
0,9
0,7
0,6
0,5
0,4
0,3
2 3 4 6 8 10 20 30
910
40 A
32 A
25 A20 A16 A10 A, 13 A
6 A
2 A
0,5 0,6 0,8 1
10
8
9
7
6
5
4
3
2
1
0,8
0,9
0,7
0,6
0,5
0,4
0,3
2 3 4 6 8 10 20 30
100 A80 A
short circuit current short circuit current
pea
k cu
rren
t in
kA
pea
k cu
rren
t in
kA
current limiting at 400V
MT NB NC ND NM 80 - 100A
0,5 0,6 0,8 1
1
0,8
0,6
0,5
0,4
2 3 4 6 8 10
10
8
6
5
4
3
2
100
80
60
50
40
30
20
20 30
50, 63 A 32, 40 A20 A,25 A13 A,16 A10 A
6 A
4 A,3 A
2 A,1 A
0,5 A
1
23
0,5 0,6 0,8 1
1
0,8
0,6
0,5
0,4
2 3 4 6 8 10
10
8
6
5
4
3
2
100
80
60
50
40
30
20
20 30
100 A80 A
short circuit current short circuit current
ener
gy le
t th
roug
h in
kA
2 s
ener
gy le
t th
roug
h in
kA
2 s
I2t characteristics
Fig 6
Fig 7
Fig 8
Circuit breakers, and RCCB auxiliaries
72 Technical information
FunctionsTripping and indication auxiliary contacts are common to therange of multi-pole 10kA MCBs, and RCCBs.They should be mounted on the left hand side of the device.
Auxiliary contact MZ201 (fig 9)Allows remote indication of the status of the device contacts towhich it is associated.
Auxiliary contact and alarm contact MZ202 This accessory has two separate functions.Like the MZ201 auxiliary contact, however the alarm contact will provide indication if the breaker trips under fault conditions.
MZ203 shunt trip*Allows tripping of the device by feeding the coil. The contactsalso allow for remote indication of operation.
MZ206 under voltage release* (fig 10)Allows the MCB to trip when the voltage drops or by pressing aremote off switch (ie emergency stop).
* Indication that the product has tripped due to the voltage release is provided by a flag on the product.
Wiring diagramMZ201 auxiliary contact and alarm contact
MZ206 under voltage release
Electrical characteristics Electrical connection
By terminal fitted with fixed clamp screws wiring capacity.flexible : 2 x 1.5mm2
rigid : 2 x 1.5mm2
MZ203Power - 8VA tolerance : -15% of Un
MZ206Latching voltage is between 35 and 70% of Un 230V~.Coil consumption 3VA
Grouping/combination of several auxiliariesOn 2, 3 and 4 pole MCBs it is possible to associate 3 auxiliaries 2 indication auxiliaries and 1 release auxiliary. In this case, it is important to first fix the indication auxiliary (MZ201 and