2
LVS, Inc. 2555 Nicholson Street, San Leandro, CA 94577-4216 Phone: 510-352-9600 1-800-982-4587 Fax: 510-352-6707 www.lvscontrols.com Project: Model No.: Comments: APPLICATION FEATURES MOUNTING LED COMPATIBLE U L ® UL924 LISTED C US YEAR WARRANTY In the past, emergency lights were kept on 24 hours a day to meet life safety codes. Now, you can use a UL 924 listed Emergency Power Control, Model EPC-2-D-FM, to convert normal light fixtures into approved emergency lights. The EPC-2-D-FM saves energy and money while ensuring compli- ance with both life safety and energy codes. During normal operation, the same dimmer, occu- pancy sensor, dimming panel, or lighting control can switch and dim normal and emergency fixtures on and off simultaneously. During a utility power interruption, the EPC-2-D-FM automatically bypasses the normal lighting controls, turning the emergency lights ON at full brightness, regardless of dimmer position. The EPC-2-D-FM is fixture mounted. Unique, Patented Automatic Diagnostic Fire Alarm, Remote Test & 0-10V Dimming Option When the room switch is turned off, the EPC-2-D-FM will run a 2.5 self-test routine, veri- fying that the emergency power source was available and that the EPC-2-D-FM, ballast, and lamp(s) are all functioning correctly. This feature eliminates the need for time-consuming and costly manual monthly testing and is approved for this purpose. This also allows the unit to be installed in remote or inaccessible locations, because the unit does not rely on access to its manual test switch. Utility & Emergency Power Indicator LED’s Slim, profile allows mounting in most ballast channels. Isolated 0-10V relay contact ensures full bright- ness during utility power interruption, regardless of dimmer model. EPC-2-D-FM Emergency Power Control For 0-10V & DALI Dimmable Loads 0-10 V Dimmer Compatible
Transcript
Page 1: 20180312 EPC2DFM Spec - LVS Inc. · EPC-2-D-FM, to convert normal light fixtures into approved emergency lights. The EPC-2-D-FM saves energy and money while ensuring compli-ance

LVS, Inc. 2555 Nicholson Street, San Leandro, CA 94577-4216 Phone: 510-352-9600 1-800-982-4587 Fax: 510-352-6707

www.lvscontrols.com

Project:

Model No.:

Comments:

APPLICATION

FEATURESMOUNTING

LED COMPATIBLE

UL®UL924 LISTEDC US YEAR

WARRANTY

In the past, emergency lights were kept on 24 hours a day to meet life safety codes. Now, you can use a UL 924 listed Emergency Power Control, Model EPC-2-D-FM, to convert normal light fixtures into approved emergency lights. The EPC-2-D-FM saves energy and money while ensuring compli-ance with both life safety and energy codes.

During normal operation, the same dimmer, occu-pancy sensor, dimming panel, or lighting control can switch and dim normal and emergency fixtures on and off simultaneously.

During a utility power interruption, the EPC-2-D-FM automatically bypasses the normal lighting controls, turning the emergency lights ON at full brightness, regardless of dimmer position.

The EPC-2-D-FM is fixture mounted.

Unique, Patented Automatic Diagnostic

Fire Alarm, Remote Test & 0-10V Dimming Option

When the room switch is turned off, the EPC-2-D-FM will run a 2.5 self-test routine, veri-fying that the emergency power source was available and that the EPC-2-D-FM, ballast, and lamp(s) are all functioning correctly. This feature eliminates the need for time-consuming and costly manual monthly testing and is approved for this purpose. This also allows the unit to be installed in remote or inaccessible locations, because the unit does not rely on access to its manual test switch.

Utility & Emergency Power Indicator LED’sSlim, profile allows mounting in most ballast channels.

Isolated 0-10V relay contact ensures full bright-ness during utility power interruption, regardless of dimmer model.

EPC-2-D-FMEmergency Power ControlFor 0-10V & DALI Dimmable Loads

0-10 V Dimmer Compatible

Page 2: 20180312 EPC2DFM Spec - LVS Inc. · EPC-2-D-FM, to convert normal light fixtures into approved emergency lights. The EPC-2-D-FM saves energy and money while ensuring compli-ance

Fire Alarm Tie-In/Overridewww.lvscontrols.com/assets/UL924FAI.pdf

Red Fire Alarm Jumper (see

additional resources)

SPECIFICATIONS

SINGLE LINE DRAWING

WIRING DIAGRAM

ORDERING INFORMATION ADDITIONAL RESOURCES

EPC-2-D-FM Installation SheetFAQ SheetAlternative Wiring SheetTerms & Conditions/Warranty Information

20181215_LVUNV2

LVS, Inc. 2555 Nicholson Street, San Leandro, CA 94577-4216 Phone: 510-352-9600 1-800-982-4587 Fax: 510-352-6707

www.lvscontrols.com

DESIGNATEDEMERGENCY

LIGHT

REGULAR ROOM LIGHTS

EPC-2-DCONTROL

UL 1008Transfer SwitchOr Equivalent

NormalUtility Power

Emergency Power Source

Neutral Not Shown

EPC-2-DCONTROL

NORMALPANEL

Normal Utility Power

EMERGENCYPANEL

$

EPC-2-D

ZONECONTROLLER

Photo-cell D

EMERGENCY HOT

#3 WHITE

NORMAL PANEL

20A

#2 RED

#1 BLACK

*

Relay Panel, Power Pack, Sensor, or other (optional)*

Normal Light (optional)

EMERGENCY PANEL OR INVERTER

20ANORMAL HOT

NORMAL NEUTRALEMERGENCY NEUTRAL#4 WHITE/BLUE

#5 YELLOW

#6 BLUE

Emergency Light

Note: Emergency Light is also called N/E Light or Normal/Emergency

Light by many specifiers

VioletOrange

EMPOWER

TEST

UTILITYPOWER

Note: N/C low voltage yellow wire not shown, cap for 0-10V applications, see installation instructions for details

MODEL NO.SENSING INPUTLED LOAD RATINGBALLAST LOAD RATINGINCANDESCENT LOADWARRANTY

EPC-2-D-FM120V - 277V3A (120-277V)5A (120-277V)360W (120V) / 600W (277V)5 Year Replacement Warranty

ELECTRICAL

MOUNTINGRATINGSHIPPING WEIGHT / COLORTEMPERATURE

BODY SIZE

Fixture Mount, Panel MountUL94-5VA, Damp Location Rated

-40ºF - 140ºF (-40ºC - 60ºC)

MECHANICAL

8 oz. / Black

125mmx25.4mmx30mm (L x H x W)


Recommended