CLEAR VISION SOUND STRATEGIES SOLID PERFORMANCE 2nd Annual Middle East Sulphur Plant Operations Network Forum Abu Dhabi Practical Information from SRU-TGTU On-Line Analyzers Stephane CAPPE / Randy HAUER 1
Transcript
  • CLEAR VISION SOUND STRATEGIES SOLID PERFORMANCE

    2nd Annual Middle East Sulphur Plant

    Operations Network Forum

    Abu Dhabi

    Practical Information from

    SRU-TGTU On-Line Analyzers

    Stephane CAPPE / Randy HAUER

    1

  • CLEAR VISION SOUND STRATEGIES SOLID PERFORMANCE

    Agenda

    Summary…Eight SRU-TGTU analyzer tags with detailed discussion of:

    Acid Gas Feed Forward (Total HC, BTEX, H2S, NH3,CO2, H2O)

    Tail gas (H2S, SO2)

    After acid gas is introduced when can the analyzer be put in control ?

    Control signal, over range, best practices

    TGTU (H2, H2S, COS, CS2)

    Quench or Absorber where to place the H2

    Absorber outlet; H2S/COS/CS2 ranges

    Sulfur Pit Gas Analyzer (H2S, SO2)

    What constitutes abnormal operation conditions

    O2 (start up) Analyzer (O2, CO)

    2

  • CLEAR VISION SOUND STRATEGIES SOLID PERFORMANCE

    3

    SRU-TGTU Analyzer Tags

  • CLEAR VISION SOUND STRATEGIES SOLID PERFORMANCE

    Acid Gas Analyzer

    Feed Forward Control

    New Analysis & Control Schemes

    possibilities

  • CLEAR VISION SOUND STRATEGIES SOLID PERFORMANCE

    Field Data / HC Process Upset

    H2S swings from 83 to 87%

    THC =0.2%

    THC = 2.5%

    12 fold > in THC

    from 0.2 to 2.5%

    lasting ~3 minutes

  • CLEAR VISION SOUND STRATEGIES SOLID PERFORMANCE

    Acid Gas Analyzer

    Real time analysis of acid gas using a UV-IR Analyzer

    IR is to quantify the Total HC (as methane equivalent)

    UV to quantify the H2S

    CO2, H2O as required (ABC+)

    BTEX to know when to co-fire for higher reaction furnace temperatures

  • CLEAR VISION SOUND STRATEGIES SOLID PERFORMANCE

    Feed Forward Analysis

    Actual Control Response to Hydro-Carbons (Courtesy of Jacobs Comprimo)

    7

  • CLEAR VISION SOUND STRATEGIES SOLID PERFORMANCE

    Acid Gas Analysis - Benefits

    Improved control, fewer upsets, mitigation of upsets

    Demonstrated improvement of ~0.5% recovery efficiency (ER)but…

    More to the point it is the loss of 5% ER for 1 hour that is the benefit

    Prevention of SO2 breakthrough to the TGTU

    Can (should) be used for mass balance recovery efficiency calculation

    The objective is to place the analyzer in cascade control

    THC/BTEX Speciation is the new focus especially in ME

    8

  • CLEAR VISION SOUND STRATEGIES SOLID PERFORMANCE

    The Heated Acid Gas (HAG) Probe

    Membrane for liquid ingress, no water removal, no pump

    Maintained at process temp, spent sample returned back to process,

    Integral process isolation valves, safety is the paramount feature

    To be “ready”…Install the HAG at

    Turnaround

  • CLEAR VISION SOUND STRATEGIES SOLID PERFORMANCE

    Tail Gas Analyzer

    Feed Back Control

    Air Demand vs Ratio

    Start Up and Shutdowns

    When to put the analyzer on line

  • Tail Gas Analyzer

    Top of the Pipe Analyzer

    880 NSL

    Sample Line Analyzer

    900 ADA

    Insulated steam

    jacketed nozzle

    Weather cover

    for ASR

    probe and jacket

  • CLEAR VISION SOUND STRATEGIES SOLID PERFORMANCE

    Ratio vs Excess H2S vs Air Demand

    Ratio is the non linear expression of 2 H2S / SO2

    Excess H2S is the linear expression of

    [H2S] - 2[SO2] = -1%…0…+1% H2S

    Air Demand uses a scaling factor

    AD{[H2S] - 2[SO2]} = -5%...0...+5% AIR

    REMINDER

  • CLEAR VISION SOUND STRATEGIES SOLID PERFORMANCE

    Controlling “Off Ratio”

    To favor the TGTU with H2S

    The tail gas analyzer simply measures [H2S] and [SO2]

    And calculates a control algorithm….

    A dumb analyzer we ask to do a smart thing

    Running “Off ratio”

    Typically 4:1 or 5:1 but this is just a notional value…

    Perhaps better to express it as -1% air demand (~+0.2% xs H2S)

    Let’s not be slave to 2:1

    13

  • CLEAR VISION SOUND STRATEGIES SOLID PERFORMANCE

    Tail Gas: Process Upset & Over-Range Event

  • CLEAR VISION SOUND STRATEGIES SOLID PERFORMANCE

    “After start up when is the

    analyser put into control

    mode ?” Catalyst preference for H2S over

    SO2 can skew true air control.

    Sulphur Experts recommends

    control mode after 8 hours.

    15

    Putting the Analyzer in Control After Start-up

    “Do you consider tail gas

    analysers to be reliable ?” Thankfully yes was common

    response

    Responses capture the evolution

    of the tail gas products.

    Time for a 3rd generation.

  • CLEAR VISION SOUND STRATEGIES SOLID PERFORMANCE

    SRU Start-up O2 /CO Measurement

    • For start-ups and shut-downs

    Requires excess O2 to near

    stochiometric conditions of 0.1% xs air

    Tunable Diode Laser (TDL) process O2

    analyzer

    Can monitor CO also

    • A fixed (permanent) system or portable

    16

  • CLEAR VISION SOUND STRATEGIES SOLID PERFORMANCE

    TGTU Analyzer

    Where to install ?

    COS/CS2 analysis on top of Absorber

    SO2 breakthrough analysis

  • CLEAR VISION SOUND STRATEGIES SOLID PERFORMANCE

    Analytical Measurements on a TGTU

    H2 is the critical parameter ( so please no GC - ESD analyzer)

    H2S can be measured at the Quench outlet or Absorber outlet

    [H2S] at Quench outlet is a measure of SRU recovery efficiency

    [H2S] at Absorber outlet is a measure of absorber efficiency

    COS & CS2 are secondary measurements

    [COS] is indication of CoMo catalyst activity (first to breakthrough)

    [CS2] is also indication of catalyst activity and contribution to emissions

    SO2 can be measured at the quench inlet or outlet (not common)

    pH is measured in the quench water (not addressed here)

  • CLEAR VISION SOUND STRATEGIES SOLID PERFORMANCE

    Where to install TGTU analyzer

    Installed Base of ~175 Analyzers

    ~140 have sample point at top of Absorber (H2/H2S)

    25 of these also measure COS

    8 of these also measure COS + CS2

    ~30 have sample point at Quench outlet (H2/H2S only)

    ~5 have sample point at Quench inlet (SO2 breakthrough)

    Finding right balance between Analyzer complexity

    and Benefit of measurement for Operations

    19

  • CLEAR VISION SOUND STRATEGIES SOLID PERFORMANCE

    SO2 0 – 100

    ppm

  • CLEAR VISION SOUND STRATEGIES SOLID PERFORMANCE

    TGTU (COS & H2S) Steady State & Upset

    21

    COS

    H2S

    H2S

    COS

  • CLEAR VISION SOUND STRATEGIES SOLID PERFORMANCE

    Sulfur at Absorber Outlet After SO2 Upset

  • CLEAR VISION SOUND STRATEGIES SOLID PERFORMANCE

    Sulphur Pit Analyzer

    The neglected one…

  • CLEAR VISION SOUND STRATEGIES SOLID PERFORMANCE

    Sulfur Pit: Solubility of H2S in Sulfur

    • Produced sulfur has 200-350 ppm

    of dissolved H2S

    • Spontaneous degassing and

    concentration in the gas phase can

    increase to explosive levels (3.5%)

    • Pit gas analyzer requires same

    sample integrity as tail gas

    analyzer ( Sulphur Vapor )

    • H2S is measured to warn of LEL,

    SO2 is measured to warn sulfur fire

  • CLEAR VISION SOUND STRATEGIES SOLID PERFORMANCE

    H2S / SO2 values

    S-Tank sweep gas

  • CLEAR VISION SOUND STRATEGIES SOLID PERFORMANCE

    Sulphur Pit High H2S & SO2 Values

    (Just prior to an incident)

    26

    H2S

    SO2 CFD modeling confirms

    H2S can exist ~16x

    The mean value

  • CLEAR VISION SOUND STRATEGIES SOLID PERFORMANCE

    SRU Emission Analyzer

    Mass Emission

    TGTU bypass situation

  • CLEAR VISION SOUND STRATEGIES SOLID PERFORMANCE

    Emission Analyzers

    “The Color of Plumes” (courtesy of S-Experts)

    White: Steam plume caused by water condensation (cold, Canada)

    Bluish white: SO3 plume usually caused by high SO2 emissions

    Ask analyzer techs to watch for “green slime” (chromium from 316SS + S-acid)

    Orange: NOx plume

    Brown: Unburned hydrocarbon / soot plume

    Green: Burning H2S plume

    Dual Range of SO2 if TGTU can be bypassed (Habshan 5)

    Mass Emission if straight Claus SRU (no TGTU)

    28

  • CLEAR VISION SOUND STRATEGIES SOLID PERFORMANCE

    Major Problems Faced

    &

    Solutions

  • CLEAR VISION SOUND STRATEGIES SOLID PERFORMANCE

    What are the common problems that Operations

    have with Analyzers ? • Frequent choking problems !!!

    • Sampling system failure

    • Temperature Impacts??

    – Is it controlled at each locations with respect to sulfur dewpoint?

    30

    No heating/

    Jacketing

  • CLEAR VISION SOUND STRATEGIES SOLID PERFORMANCE

    Common problems …

    • Frequent downtime due to maintenance issues

    – Lack of SRU Analyzer trainings

    – Not much experience on SRU process

    – Frequent shifting/changing of site engineers

    • High H2S exposure…. SAFETY : People and Environment

    • Unpredicted behavior of Analyzer & readings

    ex. Unit 52 at Gasco Habshan

    31

  • CLEAR VISION SOUND STRATEGIES SOLID PERFORMANCE

    GASCO Habshan DCS

    Tail Gas Trends

  • CLEAR VISION SOUND STRATEGIES SOLID PERFORMANCE

    Remedies…

    • Regular control visits on SRU analyzers by expert

    ->if problem persist more than 2 times call Manufacturer

    • Sites have “generalist” analyzer tech not SRU experts (Do you have?)

    • Need SRU Process Trained Analyzer Service Engineers

    • Need experienced hands on CBA & other SRU process

    • Your Service Staff requires periodically training and evaluation by OEM…

    33

  • CLEAR VISION SOUND STRATEGIES SOLID PERFORMANCE

    Solutions for Ametek SRU analyzers in Middle East

    • AIMS is our local partner having Focussed SRU experience …

    • Big service team with extensive knowledge on all SRU process

    analyzers

    • First in kind analyzer successfully commissioned for

    H2S in Lean Amine & BTEX Analyzer at GASCO Habshan

    • AIMS involved with all EPC and System Integrators for

    Commissioning and Start Up on AMETEK for Middle East

    • Target is 100% uptime of our Analyzers at all sites in GCC

    AIMS is our Sulphur Police squad, call them if problems !